10 x
DIAMETER
6 x
DIAMETER
IMPORTANT!
·DETAIL "A"
· FLOW SWITCH MUST BE FIELD INSTALLED
HORIZONTAL WITH NO LESS THAN 10 TIMES THE
DIAMETER OF STRAIGHT PIPE ON THE INLET SIDE
AND NO LESS THAN 6 TIMES THE DIAMETER ON
THE OUTLET SIDE.
111 1 2 "
22 11 16 "
66 9 16 "
74 9 16 "
93 5 16 "
122 5 16 "
57" - SHELL
REMOVAL CLEARANCE
FRONT
MAIN
POWER IN
DIGITAL
TEMPERATURE
CONTROLLER
REFRIGERANT
COMPONENT
SERVICE PANEL
ACCESS
FIELD INSTALL
FLOW SWITCH
4 3 16 "
56 1 2 "
AIR BLEED
3" NPS SLIP UNION
WATER OUTLET
TITANIUM
TUBE BUNDLE
INSULATED 8" SCH 40
PVC HEAT EXCHANGER
SHELL
3" NPS SLIP UNION
WATER INLET
304 STAINLESS
STEEL STAND
RIGHT
44" 47" 53"
45 1 2 "
110"
ELECTRICAL COMPONENT
SERVICE PANEL ACCESSPLAN VIEW
MULTI TEMP AIR COOLED WATER CHILLER MT-25
FOR INDOOR OR OUTDOOR FRESH AND SALT
WATER APPLICATIONS
MT-25 SPECIFICATIONS SHEET
*NOTES:
· AIR OUTLET DISCHARGE SHOULD BE UNRESTRICTED
AT LEAST 100 INCHES ABOVE THE UNIT.
· UNIT SHOULD BE PLACED SO ROOF RUN-OFF
WATER DOES NOT POUR DIRECTLY ON UNIT.
· MINIMUM CLEARANCE FOR PROPER OPERATION IS
36 INCHES FROM WALLS, SHRUBBERY, FENCES, ETC.
· MINIMUM CLEARANCE BETWEEN ADJACENT UNITS
IS 72 INCHES.
· RECOMMENDED SERVICE CLEARANCE 48".
· ALL DIMENSIONS ARE APPROXIMATE AND CAN
CHANGE AT ANY TIME.
OPTIONS:
· SCH 80 SHELL CONSTRUCTION.
· 316 STAINLESS STEEL STAND AND HARDWARE.
· LOW AMBIENT HEAD PRESSURE CONTROL
(USE IN 50 F WEATHER AND BELOW).
· HAIL GUARDS TO PROTECT CONDENSER FINS.
· COASTAL MARINE CONDENSER COATING.
PDF-0305
1:30 -(a) HACR TYPE CIRCUIT BREAKER PER NEC
AIR OUTLET KEEP CLEAR
* SEE NOTES
MULTI-TEMP WATER CHILLERS
MODEL NO.
NOMINAL
CAPACITY
TONS / BTUH / KW
VOLTS / PHASE
TOTAL
AMPS
RLA / LRA
UNIT
OPERATING
VOLTAGE
RANGE
MINIMUM
CIRCUIT
AMPACITY
MAXIMUM
FUSE SIZE OR
MAXIMUM
CIRCUIT
BREAKER (a)
WATER
FLOW RATE
(GPM)
AIR
OULET
EA. FAN
(CFM)
WEIGHT
(LBS.)
MT-25 25 / 300K / 87.2 208 - 240 / 3 82 / 267 187 - 253 103 125 120 / 180 15,500 2000 MT-25-460 25 / 300K / 87.2 460 / 3 40 / 142 414 - 506 49 60 120 / 180 15,500 2000
DATEDRAWN BY
* COPYRIGHT *
These drawings including design idea and construction techniques herin are the sole property of Aqua Logic Inc. They shall not be revised, copied, or reproduced in any manner without the written consent of Aqua Logic Inc..
12/13/2018 1 OF 1
SHEET #
SHEET TITLE
SCALE
DESCRIPTION
REVISION
DRAWING #