PROJECT SUMMARY

PROJECT NAME:

PROJECT ADDRESS:

PROJECT SUMMARY / SCOPE OF WORK:

INTERAGENCY NATURAL RESOURCE CENTER (INRC) - SITEWORK & WAREHOUSE - PHASE 1

3815 SCHREIBER WAY, COEUR D'ALENE, ID 83815 - CLIMATE ZONE B5

PROJECT INCLUDES A ENTIRELY NEW WAREHOUSE THAT WILL BE A PRE-ENGINEERED, METAL FRAMED BUILDING.

SPACES WILL INCLUDE: RADIO DISPATCH (OFFICE), HOTSHOTS (OFFICE + STORAGE), GENERAL STORAGE, AND VEHICLE STORAGE FOR THE INRC OFFICE BUILDING. A SECURE, FENCED WAREYARD WILL BE BETWEEN THE NURSERY

PROPERTY AND THE WAREHOUSE BUILDING.

IDAHO STATE MAP VICINITY MAP

Image Courtesy of Google Earth

PROJECT LOCATION

COEUR D'ALENE

IDAHO FALLSBOISE

TWIN FALLS

POCATELLO

SPOKANE

LEWISTON

MISSOULA

I90

N R

A M

S E

Y R

D

W. KATHLEEN AVE.

L

IN

C O

L N

W A

Y

MT

WA

DRAWING INDEXPROJECT TEAM

OWNER

US DEPARTMENT OF AGRICULTURE - USDA

IDAHO PANHANDLE NATIONAL FORESTS

3815 SCHREIBER WAY

COEUR D'ALENE, ID 83815

(208) 765-7204 office

MIKE SHOUP, CONTRACTING OFFICER REPRESENTATIVE

ARCHITECT

A&E ARCHITECTS

222 NORTH HIGGINS

MISSOULA, MT 59802

406.721.5643 office

CHRIS MARTISON, AIA, PRINCIPAL-IN-CHARGE

BRANDON PRINZING, PROJECT MANAGER

CIVIL ENGINEER

MORRISON-MAIERLE, INC.

3011 PALMER ST

MISSOULA, MT 59808

406.542.8880 office

TOBY MCCLUE, CIVIL ENGINEER

STRUCTURAL ENGINEER

BEAUDETTE CONSULTING ENGINEERS

131 W. MAIN ST

MISSOULA, MT 59802

406.721.7315 office

TOM BEAUDETTE, STRUCTURAL ENGINEER

M/P/E ENGINEER

MORRISON-MAIERLE, INC.

3011 PALMER ST

MISSOULA, MT 59808

406.542.8880 office

ARIAN BLOOMFIELD, BUILDINGS DIVISION TEAM LEAD, ELECTRICAL ENGINEER

JODY WAVEREK, MECHANICAL & PLUMBING ENGINEER

LANDSCAPE ARCHITECT

KENT WATSON AND ASSOCIATES

210 N. HIGGINS AVE., ST. 334

MISSOULA, MT 59802

406.721.3500 office

KENT WATSON, LANDSCAPE ARCHITECT

SYSTEMS FURNITURE DESIGNER

INSITE INC.

631 PARK LANE

BILLINGS, MT 59102

(406) 256-6232 office

MARY SUE GUNNIFSON, INTERIOR DESIGNER

1. EVERY ATTEMPT HAS BEEN MADE TO ASSURE THE ACCURACY OF THE DRAWINGS THROUGH FIELD VERIFICATION & EXISTING PLAN REVIEW. THE CONTRACTOR REMAINS RESPONSIBLE TO VERIFY EXISTING CONDITIONS, SIZES, QUANTITIES, & COORDINATE ALL ASPECTS OF THE PROJECT BEFORE CONSTRUCTION/ ORDERING/ OR INSTALLATION OF ANY COMPONENT. NOTIFY ARCHITECT IMMEDIATELY FOR WRITTEN CLARIFICATION IF ANY DISCREPANCY EXISTS.

2. DRAWINGS CONTAINED WITHIN THESE DOCUMENTS ARE ABBREVIATED IN NATURE. THE CONTRACTOR IS EXPECTED TO USE QUALITY, ACCEPTABLE, CONSTRUCTION PRACTICES & TECHNIQUES FOR THE EXTENT & TYPE OF WORK DESCRIBED HEREIN. SPECIAL CONSTRUCTION METHODS MAY BE REQUIRED DUE TO THE NATURE OF THE

WORK.

3. ALL CONSTRUCTION SHALL CONFORM TO ALL APPLICABLE STANDARDS & REGULATIONS AS PRESCRIBED BY THE 2012 INTERNATIONAL EXISTING BUILDING CODE, 2012 INTERNATIONAL ENERGY CONSERVATION CODE, IDAPA 07.03.01 - RULES OF BUILDING SAFETY AMENDING PREVIOUSLY MENTIONED CODES, IDAHO STATE PLUMBING CODE BASED ON THE 2009 UNIFORM PLUMBING CODE, IDAHO RULES GOVERNING PLUMBING SAFETY IDAPA 07.02.02-07.02.07, 2014 NATIONAL ELECTRICAL CODE, INCLUDING AMENDMENTS AS LISTED IN IDAPA 07.01.06, 2014 NATIONAL ELECTRICAL CODE INCLUDING AMENDMENTS AS LISTED IN IDAPA 07.01.06, 2012 INTERNATIONAL MECHANICAL CODE - IDAPA RULE 07.07.01.004, 2012 INTERNATIONAL FUEL GAS CODE - IDAPA RULE 07.07.01.005, 2012 IDAHO FIRE CODE, UNIFORM FIRE CODE, AMERICAN NATIONAL STANDARDS, NFPA, THE AMERICANS WITH DISABILITIES ACT, & ANY APPLICABLE LOCAL CODES & REGULATIONS AND ALL WORK SHALL BE PERFORMED IN ACCORDANCE

WITH ALL REQUIREMENTS OF THE LOCAL AUTHORITY OF JURISDICTION

4. THE CONTRACTOR IS RESPONSIBLE FOR DOCUMENTING ACCURATE AS-BUILT INFORMATION BEFORE DEMOLITIONS COMMENCES.

5. DO NOT SCALE DRAWINGS. VERIFY ALL EXISTING DIMENSIONS IN THE FIELD; IF A DIMENSION DOES NOT EXIST OR IS IN ERROR, CONTACT THE ARCHITECT IMMEDIATELY

FOR WRITTEN CLARIFICATION.

6. CONTRACTOR(S) SHALL GUARANTEE THEIR WORK FOR A PERIOD OF NO LESS THAN ONE YEAR FROM THE DATE OF SUBSTANTIAL COMPLETION. CONTRACTOR(S)

SHALL REPLACE ALL DEFECTIVE PARTS & SUPPLIES AT THEIR COST.

7. CONTRACTOR SHALL SUPPLY ALL PARTS, MATERIALS, & LABOR REQUIRED TO COMPLETE THE WORK INDICATED INCLUDING ALL ACCESSORIES, FINISHES, & SYSTEMS NECESSARY OR APPLICABLE TO ENSURE A COMPLETE & FUNCTIONAL PROJECT UPON COMPLETION.

8. ANY ITEM SHOWN OR REFERENCED IN ONE INSTANCE SHALL BE AS IF SHOWN IN ALL INSTANCES.

9. CONTRACTOR TO REFER TO ALL DRAWINGS INCLUDED IN THIS SET FOR DESCRIPTION OF WORK. CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF ALL REQUIREMENTS BETWEEN THE DRAWINGS & THE WORK OF ANY & ALL EMPLOYEES, SUB-CONTRACTORS, SUB-SUB-CONTRACTORS OR ANY PERSON OR TRADE

PARTICIPATING IN ANY ASPECT OF THE WORK OUTLINED.

10. PROVIDE & MAINTAIN ALL NECESSARY BARRICADES, FLAGMEN, SIGNAGE, & TEMPORARY STRUCTURES NECESSARY TO FACILITATE SAFE ACCESS & TRAVEL TO THE

GENERAL PUBLIC.

11. CONTRACTOR SHALL COORDINATE ALL SIZES OF EXISTING OPENINGS WITH THE REQUIREMENTS FOR ANY NEW WORK.

12. ALL NEW FINISHES SHALL ALIGN WITH ADJOINING SURFACES UNLESS NOTED OTHERWISE. CONTRACTOR SHALL PROVIDE SMOOTH, EVEN TRANSITIONS FROM ONE SURFACE TO ANOTHER. COORDINATE FINISHES TO MATCH HISTORIC CONDITIONS UNLESS SPECIFICALLY NOTED OTHERWISE.

13. ALL FINISHES SHALL BE SCRIBED TO ADJACENT SURFACES TO ENSURE COVERAGE OF ANY GAPS OR SPACES NOT INTENDED TO BE EXPOSED.

14.ALL DAMAGED OR DETERIORATED BUILDING ELEMENTS SHALL BE REPAIRED OR REPLACED WETHER INDICATED OR NOT BY IN-KIND MATERIALS AND METHODS TO

PROVIDE A SOUND & VISUALLY COMPLETE FINISHED STRUCTURE.

GENERAL NOTES

PHASING PLAN

PHASE 1

SITE WORK, UTILITIES AND WAREHOUSE (NORTH END)

(DESCRIBED IN THESE DOCUMENTS)

PHASE 2

WAREHOUSE (SOUTH END) BUILDING AND FINISHES ONLY

(NOT DESCRIBED IN THESE DOCUMENTS)

PHASE 3

OFFICE BUILDING & LANDSCAPING

(NOT DESCRIBED IN THESE DOCUMENTS)

PHASE 1

P H

A S

E

PHASE 3

WORK TO BE PERFORMED

WORK TO BE PERFORMED IN A FUTURE PHASE

NOTE: REFER TO CIVIL DRAWINGS FOR

SITEWORK PHASING

PHASE 1 - UNDERGROUND UTILITIES,

FOOTINGS, FOUNDATION, AND SLAB

ONLY

FOREST SUPERVISOR

DATETECHNICAL SERVICES OFFICER

DATE

REGIONAL ENGINEER DATE

SIGNATURES

REGIONAL FACILITIES PROGRAM MANAGER DATE

0 1 2 3 4 5 6 7 8 9 10 inches

DRAWING NO.

PKG

NO.

SHEET

OF

PROJECT NO.:

REVISIONS:

DESIGNED

TECH. REVIEW

CADD

DESIGNED SUB SHEET NO. TITLE OF SHEET

6/

/2

:3 0:

A

M

CV-1

03.01.17

COVERSHEET & GENERAL INFORMATION

13083.00

INRC WAREHOUSE - PHASE 1

USDA FOREST SERVICE

CM

BP/MEH

BP

INRC WAREHOUSE - PHASE 1

GENERAL INFORMATION - PHASE 1

CV-1 COVERSHEET & GENERAL INFORMATION

BUILDING AREAS (GROSS SF)

Name Area (GSF)

WAREHOUSE

(PHASE II)

17163 SF

HOTSHOTS

(PHASE I)

3651 SF

DISPATCH

(PHASE I)

6909 SF

27723 SF

ARCHITECTURAL DRAWINGS - PHASE 1

A0.1 GENERAL INFORMATION

A0.2 INTERIOR WALL TYPES

A0.3 LIFE SAFETY / CODE REVIEW

A1.0 ARCHITECTURAL SITE PLAN

A1.1 MONUMENT SIGN

A2.0 FIRST LEVEL PLAN - PHASE 1

A2.0F FIRST LEVEL FINISH PLAN - PHASE 1

A2.2 MEZZANINE PLAN - PHASE 1

A2.3 ROOF PLAN - PHASE 1

A3.0 ENLARGED PLANS - PHASE 1

A3.1 PLAN DETAILS - PHASE 1

A4.0 EXTERIOR ELEVATIONS - PHASE 1

A4.1 EXTERIOR ELEVATIONS - PHASE 1

A5.0 BUILDING SECTIONS - PHASE 1

A5.2 WALL SECTIONS - PHASE 1

A5.3 WALL SECTIONS - PHASE 1

A6.1 INTERIOR ELEVATIONS - PHASE 1

A6.2 INTERIOR ELEVATIONS - PHASE 1

A6.3 INTERIOR ELEVATIONS - PHASE 1

A6.4 INTERIOR ELEVATIONS - PHASE 1

A6.5 INTERIOR ELEVATIONS - PHASE 1

A6.6 INTERIOR ELEVATIONS - PHASE 1

A6.7 INTERIOR ELEVATIONS - PHASE 1

A6.8 INTERIOR ELEVATIONS - PHASE 1

A6.9 INTERIOR ELEVATIONS - PHASE 1

A7.0 RCP - FIRST/GROUND LEVEL - PHASE 1

A8.0 VERTICAL CIRCULATION - PHASE 1

A9.0 SCHEDULES - PHASE 1

FURNITURE DRAWINGS - PHASE 1

F2.1 FIRST LEVEL FURNITURE PLAN

F9.1 FURNITURE - DETAILS

MECHANICAL DRAWINGS - PHASE 1

M0.1 HVAC NOTES, SCHEDULES & LEGENDS

M0.3 HVAC SCHEDULES

M0.6 MEP COORDINATION

M2.1 1ST FLOOR HVAC PLAN

M2.3 ROOF HVAC PLAN

M2.5 MEZZANINE HVAC PLAN

M9.1 HVAC DETAILS

M9.2 HVAC DETAILS

FIRE PROTECTION DRAWINGS - PHASE 1

FP0.1 FIRE PROTECTION NOTES

FP2.1 FIRE PROTECTION PLANS

FP9.1 FIRE PROTECTION DETAILS

PLUMBING DRAWINGS - PHASE 1

P0.1 PLUMBING NOTES, SCHEDULES & LEGENDS

P2.1 FIRST LEVEL UNDERSLAB PLUMBING PLAN

P2.1A 1ST LEVEL UNDERSLAB PLUMBING - OPTION ITEM #1

P2.3 FIRST LEVEL PLUMBING PLAN

P2.5 MEZZANINE PLUMBING PLAN

P9.1 PLUMBING DETAILS

ELECTRICAL DRAWINGS - PHASE 1

E0.1 SYMBOLS AND ABBREVIATIONS

E1.1 ELECTRICAL SITE PLAN

E1.2 RADIO TOWER GROUNDING

E2.1 1ST LEVEL POWER PLAN

E2.1A 1st LEVEL POWER PLAN - OPTION ITEM #1

E2.3 SERVER MEZZANINE POWER PLAN

E2.4 1ST LEVEL SIGNAL PLAN

E2.6 SERVER MEZZANINE SIGNAL PLAN

E7.1 RCP 1ST LEVEL LIGHTING PLAN

E7.3 MEZZANINE LIGHTING PLAN

E9.1 DETAILS

E9.2 DETAILS

E9.3 DETAILS

E9.4 DETAILS

E9.5 DETAILS

E9.6 DETAILS

E9.7 DETAILS

E9.8 SCHEDULES

E9.9 SCHEDULES

E9.10 SCHEDULES

E9.11 SCHEDULES

E9.12 SCHEDULES

CIVIL DRAWINGS - PHASE 1

C1.1 2013 TOPOGRAPHIC SURVEY

CD1.1 DEMOLITION PLAN

C1.2 OVERALL PHASING PLAN

C1.3 PROPOSED SITE PLAN

C1.3A BUILDING SLAB OPTION

C1.4 GRADING & DRAINAGE PLAN

C1.5 GRADING & DRAINAGE PLAN

C1.6 PROPOSED UTILITY PLAN

C1.7 INTERSECTION IMPROVEMENTS

C1.8 WAREHOUSE SECURITY FENCING & GATE LAYOUT

C1.9 WATER & FIRE SERVICE PLAN & PROFILE

C1.10 SANITARY SEWER PLAN & PROFILE

C1.11 SIGNAGE PLAN

C1.12 COORDINATE LAYOUT PLAN

T1.1 TRAFFIC SIGNAL TABLE OF QUANTITIES (SHT. 1 OF 2)

T1.2 TRAFFIC SIGNAL TABLE OF QUANTITIES (SHT. 2 OF 2)

T1.3 TRAFFIC SIGNAL PLAN

T1.4 TRAFFIC SIGNAL CONDUIT & WIRING DIAGRAM

T1.5 TRAFFIC SIGNAL FIELD WIRING DIAGRAM

T1.6 TRAFFIC SIGNAL VIDEO DETECTION DIAGRAM

T1.7 TRAFFIC SIGNAL POLES & MAST ARM DETAILS

T1.8 TRAFFIC SIGNAL POLE AND MASTARM STANDARD

C9.1 CIVIL DETAILS

C9.2 CIVIL DETAILS

C9.3 CIVIL DETAILS

C9.4 CIVIL DETAILS

C9.5 CIVIL DETAILS

C9.6 CIVIL DETAILS

C9.7 CIVIL DETAILS

C9.8 CIVIL DETAILS

C9.9 TRAFFIC DETAILS

C9.10 TRAFFIC DETAILS

LANDSCAPING DRAWINGS

CP1.1 TREE PRESERVATION PLAN

STRUCTURAL DRAWINGS - PHASE 1

S0.1 GENERAL NOTES

S0.2 SITE PLAN

S1.0 FOUNDATION PLAN

S2.0 MEZZANINE FRAMING PLAN

S2.1 ROOF FRAMING PLAN

S9.1 DETAILS

1 1

No. Date

1 05.04.17

RFQ No.: 12034320Q0200 – INRC HVAC Preventive Maintenance - Idaho Panhandle N.F. / Attach 02: 191009 Warehouse Mechanical Drawings / Page 1 of 16

PROJECT SPECIFICATIONS

A. ALL WORK ON THE PROJECT SHALL CONFORM TO ALL LOCAL CITY, STATE AND

NATIONAL CODES AND REGULATIONS, INCLUDING BUT NOT LIMITED TO THE

N.F.P.A., N.E.C., U.B.C., I.E.C.C., I.M.C., U.P.C., THE LOCAL UTILITY SERVING

COMPANIES AND THE AUTHORITY HAVING JURISDICTION.

B. THE WORK ON THIS PROJECT SHALL CONSIST OF ALL ITEMS, ARTICLES,

MATERIALS, EQUIPMENT, AND LABOR FURNISHED TOGETHER ALONG WITH ALL

INCIDENTAL ITEMS REQUIRED BY GOOD PRACTICE AND WORKMANSHIP TO

PROVIDE A SATISFACTORY, COMPLETE AND FUNCTIONAL SYSTEM IN

ACCORDANCE WITH THE DRAWINGS AT NO ADDITIONAL COST TO THE

CONTRACTING OFFICER.

C. THE CONTRACTOR SHALL BE RESPONSIBLE FOR AND PAY FOR ALL FEES AND

PERMITS REQUIRED FOR WORK UNDER THEIR CONTRACT AND UNDER THEIR

SUPERVISION BY SUBCONTRACT.

D. MANUFACTURER'S TRADE NAMES AND CATALOG NUMBERS ARE LISTED TO

INDICATE SPECIAL CONDITIONS AND QUALITY OF MATERIALS OR EQUIPMENT

SUPPLIED. ALTERNATIVE EQUIPMENT OR MATERIALS MAY BE SUBMITTED FOR

REVIEW AFTER BIDS HAVE BEEN AWARDED.

E. ALL WORK BY THE CONTRACTOR IS SUBJECT TO REVIEW AT ANY TIME BY THE

CONTRACTING OFFICER.

F. ALL WORK TO BE PERFORMED SHALL FIRST BE SCHEDULED AND SUBMITTED TO

THE CONTRACTING OFFICER FOR ACCEPTANCE.

G. SMOKING SHALL NOT BE PERMITTED ANYWHERE IN THIS FACILITY.

H. THE CONTRACTOR SHALL BE CAREFUL NOT TO BLOCK ANY PATHS OF EGRESS

WHILE PERFORMING THE WORK SPECIFIED.

I. THE CONTRACTOR SHALL BE RESPONSIBLE FOR CLEANUP OF ALL MATERIALS

RESULTING FROM HIS/HER WORK. CLEANUP SHALL BE PERFORMED TO THE

LEVEL OF ACCEPTANCE OF THE CONTRACTING OFFICER.

J. THE CONTRACTOR SHALL AND HEREBY DOES WARRANT AND GUARANTEE THAT

ALL WORK EXECUTED UNDER HIS/HER CONTRACT SHALL BE FREE OF DEFECTS

OF MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE(1) YEAR FROM THE

DATE OF SUBSTANTIAL COMPLETION.

K. SUBMIT ALL SHOP DRAWINGS FOR ALL EQUIPMENT ASSOCIATED WITH THIS

PROJECT TO THE CONTRACTING OFFICER FOR REVIEW/APPROVAL PRIOR TO

ORDERING ANY EQUIPMENT. ALL MATERIALS AND OR EQUIPMENT SHALL BE NEW.

L. UPON SUBSTANTIAL COMPLETION THE CONTRACTOR SHALL SUBMIT AN

OPERATIONS AND MAINTENANCE (O&M) MANUAL/BROCHURE OF ALL EQUIPMENT

TO THE CONTRACTING OFFICER FOR REVIEW/APPROVAL. AFTER RECEIVING

APPROVAL FROM CONTRACTING OFFICER, PROVIDE (2 APPROVED COPIES) TO

CONTRACTING OFFICER AND PROVIDE THE NECESSARY TRAINING TO THE

FACILITIES PERSONNEL REGARDING ALL EQUIPMENT ASSOCIATED WITH THIS

PROJECT.

SEISMIC GENERAL NOTES

A. ALL MECHANICAL AND PLUMBING EQUIPMENT SHALL BE SEISMICALLY BRACED

PER THE 2012 INTERNATIONAL BUILDING CODE. SEISMIC DESIGN

REQUIREMENTS FOR THE PROJECT ARE AS FOLLOWS:

• SEISMIC DESIGN CATEGORY: D

• IMPORTANCE FACTOR (Ip): 1.0

• IMPORTANCE FACTOR FOR GAS PIPING: 1.5

B. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE TO INCLUDE BRACING

AND RESTRAINTS. BRACING & RESTRAINT DETAILS SHALL BE INCLUDED IN SHOP

DRAWING SUBMITTAL FOR REVIEW AND BY THE CONTRACTING OFFICER.

T

C

H

SP

D S

THERMOSTAT

CARBON DIOXIDE SENSOR

HUMIDISTAT

WALL SWITCH

STATIC PRESSURE SENSOR

DUCT SMOKE DETECTOR

HVAC CONTROLS LEGEND

REFRIGERANT

CONDENSATE

HVAC PIPING SYSTEMS LEGEND

AIR SEPARATOR

AUTOMATIC AIR VENT

MANUAL AIR VENT

AUTOFLOW VALVE

BACKFLOW PREVENTER

BALL VALVE

BUTTERFLY VALVE

CIRCUIT SETTER

CHECK VALVE

COMBINATION FLOW CONTROL

VALVE

COMBINATION STRAINER VALVE

TWO-WAY CONTROL VALVE

THREE-WAY CONTROL VALVE

HOSE END DRAIN

FLEXIBLE CONNECTOR

FLOW METERING STATION

FLOW SWITCH

GATE VALVE

MULTI-PURPOSE VALVE

PIPE WELL- EMPTY

PRESSURE GAUGE AND COCK

PRESSURE REDUCING VALVE

PRESSURE RELIEF VALVE

PRESSURE SENSOR

PRESSURE SWITCH

PRESSURE/TEMPERATURE PORT

SOLENOID VALVE

STRAINER

STRAINER W/ BLOWOUT

TEMPERATURE SENSOR

THERMOMETER

THREE-WAY VALVE

HVAC PIPING SPECIALTIES LEGEND

18x12

PROJECT INFORMATION

PIPE MATERIAL SCHEDULE

SYSTEM MATERIAL SIZES

INSULATION

THICKNESS** ADD'L DETAILS

COMBUSTION AIR & VENT PIPING SCHEDULE 40 PVC ALL NONE SEE BELOW

REFRIGERANT PIPING REFER TO SPECIFICATIONS.

CONDENSATE DRAIN PIPING SCHEDULE 40 PVC ALL NONE SEE BELOW

** BASED ON INSULATION HAVING A CONDUCTIVITY

(K) NOT EXCEEDING 0.27 BTU PER INCH/H*FT^2*DEG F

1. PROVIDE SEISMIC BRACING OF PIPING 2 1/2" AND LARGER OR AS REQUIRED BY LOCAL CODES.

2. INSULATION SHALL BE FIBERGLASS WITH ALL SERVICE JACKET

3. ALL SERVICE INSULATION JACKET IS TO BE SEALED AT ALL SEAMS, EDGES, ETC.

4. PROVIDE PVC COATED JACKET OVER INSULATION FOR MECHANICAL ROOM PIPING.

5. ANY CONNECTIONS THAT ARE DISSIMILAR METALS SHALL REQUIRE BRASS UNIONS OR FLANGE SEPARATION.

PIPE MATERIAL REMARKS:

TEMP. CONTROL GEN'L NOTES

A. THE MECHANICAL CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE

SUCCESSFUL OPERATION OF THE MECHANICAL INSTALLATION AND SYSTEMS

INCLUDING CONTROLS. THE M.C. SHALL HIRE A TEMPERATURE CONTROLS

CONTRACTOR AND ELECTRICAL CONTRACTOR AS NECESSARY TO ACHIEVE

THE SPECIFIED SEQUENCE OF OPERATIONS. CONTROL WIRING IS NOT SHOWN

ON THE ELECTRICAL DRAWINGS. ELECTRICAL WORK REQUIRED FOR SYSTEM

OPERATION BUT NOT SHOWN ON THE ELECTRICAL DRAWINGS SHALL BE THE

RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO HIRE AN ELECTRICIAN

INDEPENDENT FROM THIS PROJECTS CONTRACT DOCUMENTS.

B. IN GENERAL ALL TEMPERATURE CONTROLS ARE STAND ALONE FOR EACH

SPECIFIC PIECE OF MECHANICAL EQUIPMENT. THERE IS NOT A CENTRAL

BUILDING MANAGEMENT SYSTEM UNLESS OTHERWISE SHOWN ON THE

ELECTRICAL DRAWINGS. ROUGH-IN WIRING FOR THERMOSTATS AND OTHER

CONTROL COMPONENTS ARE THE RESPONSIBILITY OF THE MECHANICAL

CONTRACTOR.

DUCT MATERIAL SCHEDULE

DESCRIPTION SHAPE APPLICATION MATERIAL PRESSURE CLASS INSULATION JACKET R-VALUE ADDITIONAL DETAILS

SUPPLY RECTANGULAR INDOOR - CONDITIONED SHEET METAL 2" WRAP FACTORY APPLIED R-5 SEE BELOW

SUPPLY ROUND INDOOR - CONDITIONED SPIRAL SHEET METAL 2" WRAP FACTORY APPLIED R-5 SEE BELOW

RETURN AIR RECTANGULAR INDOOR - CONDITIONED SHEET METAL 2" NONE - - - - SEE BELOW

RETURN AIR ROUND INDOOR - CONDITIONED SPIRAL SHEET METAL 2" NONE - - - - SEE BELOW

EXHAUST AIR RECTANGULAR INDOOR - CONDITIONED SHEET METAL 2" NONE - - - - SEE BELOW

EXHAUST AIR ROUND INDOOR - CONDITIONED SPIRAL SHEET METAL 2" NONE - - - - SEE BELOW

5' LENGTH MAX - SUPPLY ROUND INDOOR - CONDITIONED FLEX 2" INTEGRAL FACTORY APPLIED R-5 SEE BELOW

OUTSIDE AIR RECTANGULAR INDOOR - CONDITIONED SHEET METAL 2" WRAP FACTORY APPLIED R-8 SEE BELOW

OUTSIDE AIR ROUND INDOOR - CONDITIONED

</=12" SNAPPY DUCT, >12"

SPIRAL SHEET METAL 2" WRAP FACTORY APPLIED R-8 SEE BELOW

ALL DUCTWORK IN UNCONDITIONED SPACE RECTANGULAR INDOOR - UNCONDITIONED SHEET METAL 2" WRAP FACTORY APPLIED R-8 SEE BELOW

ALL DUCTWORK IN UNCONDITIONED SPACE ROUND INDOOR - UNCONDITIONED SPIRAL SHEET METAL 2" WRAP FACTORY APPLIED R-8 SEE BELOW

GENERAL NOTES:

1. PROVIDE SEISMIC BRACING OF ALL DUCTWORK AS REQUIRED BY LOCAL CODES.

2. ALL SHEET METAL DUCTWORK SHALL BE A MINIMUM OF 24 GAGE SHEET METAL.

3. ALL DUCTWORK SHALL BE CONSTRUCTED AND INSTALLED PER SMACNA GUIDELINES.

4. SEAL AND INSULATED ALL DUCTWORK PER 2012 I.E.C.C.

5. INSULATE EXHAUST DUCTWORK WITHIN 10 FT OF PENETRATION THROUGH BUILDING ENVELOPE.

JACKET:

1. FACTORY APPLIED ALL SERVICE JACKETS (ASJ) SHALL BE FOIL SCRIM KRAFT

(FSK). SEAL AT ALL EXPOSED SEAMS/ EDGES/ CORNERS WITH FSK ADHESIVE TAPE,

REFER TO "DUCT INSULATION" SPECIFICATIONS FOR MORE INFORMATION

RECTANGULAR DUCTWORK

ROUND DUCTWORK

AIR DEVICE NUMBER AND CFM

CEILING SUPPLY DIFFUSER

CEILING RETURN GRILLE

CEILING EXHAUST GRILLE

CEILING SLOT DIFFUSER

FLOOR REGISTER

SIDEWALL DIFFUSER OR GRILLE

VERTICAL TRANSITION-

RECTANGULAR SUPPLY DUCT

VERTICAL TRANSITION-

ROUND SUPPLY DUCT

VERTICAL TRANSITION-

RECTANGULAR RETURN DUCT

VERTICAL TRANSITION-

ROUND RETURN DUCT

VERTICAL TRANSITION-

RECTANGULAR EXHAUST DUCT

VERTICAL TRANSITION-

ROUND EXHAUST DUCT

TURNING VANE

MANUAL VOLUME DAMPER

REMOTE VOLUME DAMPER

MOTORIZED DAMPER

ZONE DAMPER

FIRE DAMPER

SMOKE DAMPER

FIRE/SMOKE DAMPER

CFM

16 �

PROJECT LOCATION: COEUR D'ALENE, ID

PROJECT ALTITUDE: 2,188 FEET ABOVE SEA LEVEL

SUMMER DESIGN TEMP: 89°F DRY BULB, 62°F WET BUL B (ASHRAE 99% DESIGN)

WINTER DESIGN TEMP: -15°F DRY BULB

HVAC LEGEND

HVAC GENERAL NOTES

A. ALL NEW PIPING, DUCTWORK AND EQUIPMENT TO BE INSTALLED IN

ACCORDANCE WITH THE 2012 INTERNATIONAL MECHANICAL CODE AND THE 2012

INTERNATIONAL BUILDING CODE REQUIREMENTS.

B. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT NECESSARILY SHOW

EXACT LOCATIONS AND SIZES OF ALL EXISTING DUCTWORK, PIPING, SYSTEM

AND EQUIPMENT UNLESS SPECIFICALLY DIMENSIONED. IT IS NOT THE INTENT OF

THESE DRAWINGS TO GRAPHICALLY REPRESENT ALL OF THE WORK REQUIRED

FOR A COMPLETE INSTALLATION IN EVERY RESPECT. THE PURPOSE OF THESE

PLANS IS TO INDICATE THE INTENDED SIZES, APPROXIMATE LOCATION AND

ROUTING OF MAJOR COMPONENTS. ADJUST TO FIELD CONDITIONS. ACTUAL

CONDITIONS AND LOCATIONS SHALL BE FIELD VERIFIED.

C. EXAMINE AND REFER TO ALL ARCHITECTURAL, STRUCTURAL, ELECTRICAL,

MECHANICAL, FIRE PROTECTION AND SITE CIVIL DRAWINGS FOR

CONSTRUCTION CONDITIONS WHICH MAY AFFECT THE CONTRACTORS WORK.

INSPECT THE EXISTING CONDITIONS AND SYSTEMS WHICH MAY HAVE AN

EFFECT ON HIS/HER WORK PRIOR TO SUBMISSION OF BID.

D. IT IS NECESSARY FOR ALL TRADES INVOLVED TO COORDINATE WITH EACH

OTHER AND VERIFY THAT THERE ARE NO CONFLICTS IN LOCATION OF DUCTS,

CONDUITS, DIFFUSERS, BOXES AND OTHER ITEMS THROUGHOUT THIS PROJECT

BEFORE FINAL PLACEMENT OF MATERIALS. REFER TO ARCHITECTURAL,

STRUCTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS AND FIRE

PROTECTION SHOP DRAWINGS FOR ADDITIONAL DETAILS NECESSARY FOR

COORDINATION.

E. THE CONTRACTOR IS TO PROVIDE MATERIALS, LABOR, TRANSPORTATION,

TOOLS, PERMITS, FEES, INSPECTIONS, UTILITIES AND INCIDENTALS NECESSARY

FOR THE COMPLETE INSTALLATION OF THE WORK INDICATED AND DESCRIBED

IN THESE CONTRACT DOCUMENTS.

F. LOCATIONS AND DIMENSIONS ON THIS DRAWING ARE APPROXIMATE AND

REPRESENT THE BEST AVAILABLE INFORMATION BASED ON A COMBINATION OF

FIELD INVESTIGATIONS AND VARIOUS DESIGN AND RECORD DRAWINGS

AVAILABLE AT THE TIME OF DESIGN. FIELD VERIFY LOCATIONS AND DIMENSIONS

PRIOR TO ORDERING EQUIPMENT AND DURING PERFORMANCE OF THE WORK.

PROVIDE ALL DEMOLITION WORK, NECESSARY FITTINGS, TRANSITIONS, AND

OTHER COMPONENTS AS REQUIRED FOR A COMPLETE AND FUNCTIONAL

INSTALLATION OF NEW SYSTEMS AT NO ADDITIONAL COST TO THE

CONTRACTING OFFICER.

G. THE CONTRACTOR IS TO BE RESPONSIBLE FOR ANY ADDITIONAL DETAILS OR

SPECIAL CONSTRUCTION REQUIRED IN ORDER TO COMPLETE THE

INSTALLATION, WHETHER MENTIONED OR NOT. THE CONTRACTOR IS TO

PROVIDE ALL MATERIALS AND EQUIPMENT THAT ARE TO BE FURNISHED FOR

THE PROPER INSTALLATION OF THE TYPE OF EQUIPMENT AND SYSTEMS

INDICATED.

H. ALL EQUIPMENT SHALL BE INSTALLED LEVEL, PLUMB, AND FIRMLY ANCHORED IN

LOCATIONS INDICATED. OBSERVE MANUFACTURER'S INSTALLATION

INSTRUCTIONS AND RECOGNIZED INDUSTRY PRACTICES TO INSURE THAT

PRODUCTS SERVE THEIR INTENDED FUNCTION.

I. FOLLOW MANUFACTURES WRITTEN INSTALLATION INSTRUCTION FOR RUNNING

THE COMBUSTION AIR AND VENT PIPING AS WELL AS THE TERMINATION

THROUGH THE ROOF. FOLLOW ALL SAFETY INSTRUCTIONS.

J. PROVIDE SEISMIC BRACING OF ALL EQUIPMENT, PIPING, AND DUCTWORK AS

REQUIRED BY LOCAL CODES.

K. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL FIRE BARRIERS,

FIRE PARTITIONS, FIRE WALLS OR ANY OTHER FIRE AND/OR SMOKE SEPARATION

WITHIN THE BUILDING AS DEFINED BY THE ARCHITECTURAL CODE PLAN WITH A

UL LISTED FIRE AND/OR SMOKE STOP SYSTEM.

L. ALL MATERIAL IN A PLENUM RATED SPACE SHALL HAVE A SPREAD NOT

EXCEEDING 25 AND A SMOKE DEVELOPMENT RATING NOT EXCEEDING 50.

M. PROVIDE ACCESS DOORS TO ALLOW SERVICE AND INSPECTION OF EQUIPMENT,

VALVES, DAMPERS, DEVICES INSTALLED ABOVE NON-REMOVABLE CEILINGS.

N. ALL ELEMENTS PENETRATING BUILDING COMPONENTS (ROOF ASSEMBLIES,

WALL ASSEMBLIES, ETC.) SHALL BE SEALED WEATHER AND WATER TIGHT.

O. ALL NEW PIPING SHALL BE IDENTIFIED WITH SETON SETMARK PIPE MARKERS,

LETTERED TO MATCH EXISTING AND MARKED AT A MAXIMUM OF EVERY 25 FT.

ALSO, ALL NEW VALVES SHALL BE IDENTIFIED WITH BRASS OR ALUMINUM VALVE

TAGS.

P. PROVIDE PIPE GUIDES, EXPANSION JOINTS, AND HANGERS PER

MANUFACTURER'S RECOMMENDATIONS.

Q. ALL PIPING WALL PENETRATIONS SHALL HAVE A CHROME ESCUTCHEON PLATE.

ALL SOLDER TO BE LEAD-FREE TYPE. AT THE CONTRACTORS OPTION

MECHANICAL COMPRESSION TYPE FITTING (I.E. PRO-PRESS) MAY BE USED.

R. VERIFY THE LOCATION OF ALL THERMOSTATS AND SENSORS WITH THE

CONTRACTING OFFICER PRIOR TO INSTALLATION. INSTALL THERMOSTATS 48"

ABOVE FINISHED FLOOR PER ADA REQUIREMENTS.

S. ALL DUCT WORK SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE LATEST

REQUIREMENTS OF SMACNA DUCT WORK CONSTRUCTION MANUALS, MINIMUM

GAUGE OF 24, GALVANIZED STEEL. DUCTWORK SHALL BE AIRTIGHT (5%

LEAKAGE). ALL TRANSVERSE JOINTS AND LONGITUDINAL SEAMS SHALL BE

SEALED. FABRICATE ELBOWS WITH CENTERLINE RADIUS EQUAL TO 1.5 TIMES

THE DUCT WIDTH IN THE PLANE OF THE TURN; AND FABRICATE TO INCLUDE

FACTORY MANUFACTURED TURNING VANES IN ELBOWS WHERE SHORTER

RADIUS IS NECESSARY.

T. PROVIDE FLEX CONNECTIONS FROM ALL DUCT WORK TO EQUIPMENT

CONNECTIONS ON THIS PROJECT.

U. FLEXIBLE DUCT SHALL NOT BE USED IN PLACE OF ELBOWS.

V. A COMPLETE AIR AND WATER SYSTEM TEST AND BALANCE (T&B) SHALL BE

PERFORMED BY A NEBB OR AABC CERTIFIED T&B CONTRACTOR FOR ALL NEW

AND MODIFIED DEVICES. MECHANICAL CONTRACTOR SHALL MODIFY EQUIPMENT

AS DIRECTED BY BALANCING CONTRACTOR, IF REQUIRED, TO ACHIEVE DESIGN

PARAMETERS WITH NO EXTRA COST. T&B REPORT SHALL BE PREPARED AND

SUBMITTED TO CONTRACTING OFFICER. REPORT SHALL INCLUDE ALL AIR AND

WATER FLOW READINGS, ALL TEMPERATURE AND PRESSURE SETPOINTS AND

ALL ELECTRICAL CONDITIONS FOR ALL DEVICES. REPORT SHALL ALSO VERIFY

PROPER OPERATION OF ENTIRE CONTROL SYSTEM. WHERE REQUIRED FOR AIR

BALANCING, INSTALL ADDITIONAL MANUAL VOLUME DAMPERS.

W. THE MECHANICAL CONTRACTOR SHALL PROVIDE UP TO 4 HOURS OF TRAINING

TO ENSURE PROPER OPERATION AND MAINTENANCE OF THE SYSTEMS.

X. COORDINATE ALL CONCRETE PENETRATIONS WITH STRUCTURAL DRAWINGS TO

VERIFY HOW AND WHERE CONCRETE CAN BE CUT.

Y. ALL PIPING THAT IS EXPOSED MUST BE PAINTED TO MATCH SURROUNDINGS.

Z. MECHANICAL CONTRACTOR SHALL FIRE SEAL ALL PIPING AND DUCTWORK

PASSING THROUGH RATED CONSTRUCTION.

BILLINGS | BOZEMAN | MISSOULA

0 1 2 3 4 5 6 7 8 9 10 inches

DRAWING NO.

PKG

NO.

SHEET

OF

PROJECT NO.:

REVISIONS:

DESIGNED

TECH. REVIEW

CADD

DESIGNED SUB SHEET NO. TITLE OF SHEET

INRC WAREHOUSE (NORTH)

-PHASE 1

/2

/2

:2

:5

P

M

M0.1

03.01.17C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

HVAC NOTES, SCHEDULES, & LEGENDS

13083.00

USDA FOREST SERVICE

BJK/JTW

REB

DMP

Ø

P

R E E

NI

GN

ELANOISSEF

O R R

EG

ISTERE

D

S

T A

TE OF ID

AH

O

WAVERE

K

TYD

O J

11076

RFQ No.: 12034320Q0200 – INRC HVAC Preventive Maintenance - Idaho Panhandle N.F. / Attach 02: 191009 Warehouse Mechanical Drawings / Page 2 of 16

HVAC FAN SCHEDULE

MARK MANUFACTURER

MODEL

NUMBER TYPE SERVING CFM E.S.P. DRIVE H.P. MOTOR RPM

SOUND

(dBA)

WEIGHT

(LBS.) CONTROL ACCESSORIES REMARKS

EF-1 COOK 90C15DL DOWN BLAST

HOTSHOT TOOL

SHOP 300 0.5 DIRECT 1/8 1550 53 22 1 A,B,C,D,E SEE BELOW

EF-2 COOK 90C15DL DOWN BLAST HOTSHOT EQUIP. 300 0.5 DIRECT 1/8 1550 53 22 2 A,B,C,D,E SEE BELOW

EF-3 COOK 100C15DH DOWN BLAST HOTSHOT LOCKERS 400 0.5 DIRECT 1/8 1550 59 46 2 A,B,C,D,E SEE BELOW

EF-4 COOK 100 ACE-B DOWN BLAST RESTROOMS &

LOCKERS 700 0.5 BELT 1/6 1725 60 28 3 A,B,C,D,E SEE BELOW

ACCESSORIES

(A) -STANDARD DISCONNECT PREWIRED

(B) -LINE VOLTAGE MOTORIZED DAMPER.

(C) -14" ROOF CURB INSULATED.

(D) -FAN SPEED CONTROLLER FOR BALANCING.

(E) -BIRDSCREEN

ELECTRICAL DATA:

SEE MEP COORDINATION

SCHEDULE FOR

STARTER/DISCONNECT AND

ALL OTHER ELEC. DATA.

LOUVER SCHEDULE

MARK MANF. MODEL NUMBER SERVING SIZE TYPE FUNCTION MAX CFM

PRESSURE

DROP AIR VELOCITY MOUNTING NOTES

L-1 RUSKIN ELF6375DX

HOTSHOT TOOL

SHOP 36" x 12" STATIONARY INTAKE 300 0.01 285 WALL SEE BELOW

NOTES:

1. 6" DEPTH LOUVER

2. DRAINABLE LOUVER

3. PROVIDE PRIME COAT & FINISH PAINT COLOR AS SELECTED BY ARCHITECT.

4. PROVIDE MOTORIZED DAMPER WHERE SHOWN ON PLANS. SEE

CONTROL DAMPER SCHEDULE.

UNIT HEATER SCHEDULE

MARK AREA SERVED MANUF.

MODEL

NUMBER HEATING TYPE GAS CONN.

INPUT/OUTPUT

(MBH) COMB. AIR VENT CFM IGNITION H.P. WEIGHT ADDITIONAL DETAILS

UH-1 ROOM 125 - HOTSHOT TOOL SHOP REZNOR 30 UDAS NAT. GAS 1/2" 30 / 24.6 4" 4" 456 DIRECT SPARK 0.06 55 SEE BELOW

ACCESSORIES:

1. PROVIDE FACTORY MOUNTED DISCONNECT

2. HIGH ALTITUDE KIT AS REQIRED

3. WALL-MOUNTED TOTALLY ENCLOSED FAN MOTOR AS REQUIRED.

4. THERMOSTAT, RELAY KIT AND STEP DOWN TRANSFORMER

5. FOUR-POINT SUSPENSION/MOUNTING ISOLATION KIT FOR WALL OR CEILING MOUNTING AS REQUIRED.

6. MANUAL GAS SHUT-OFF AND UNION

7. SINGLE-STAGE NATURAL GAS VALVE & THERMOSTAT

8. PROVIDE FACTORY CONCENTRIC VENT KIT THROUGH ROOF

9. ALL STANDARD ACCESSORIES

CONTROLS:

1. WALL-MOUNTED THERMOSTAT,

LOW VOLTAGE SEE DETAIL 2/M9.2

COORDINATE WITH E.C.

CONDENSING UNIT SCHEDULE

MARK MANUFACTURER MODEL

NUMBER

CAPACITY

(NOMINAL TONS) SEER REFRIGERANT COMPRESSOR COOLING STAGES SOUND DATA

(dBA)

UNIT PHYSICAL DATA

ADDITIONAL DETAILS

LENGTH (IN) WIDTH (IN)

HEIGHT

(IN)

OPERATING

WEIGHT

(LBS)

CU-1 CARRIER 24ACC642A003 3.5 16 R-410A SCROLL 1 74 35 35 39 - 1/8 234 SEE BELOW

CU-2 CARRIER 24ACC630A003 2.5 16 R-410A SCROLL 1 74 31 - 3/16 31 - 3/16 32 - 5/16 167 SEE BELOW

CU-3 CARRIER 24ACC648A003 4 16 R-410A SCROLL 1 74 35 35 32 - 5/16 248 SEE BELOW

CU-4 CARRIER 24ACC660A003 5 16 R-410A SCROLL 1 74 35 35 45 - 15/16 337 SEE BELOW

CU-5 CARRIER 24ACC642A003 3.5 16 R-410A SCROLL 1 74 35 35 39 - 1/8 234 SEE BELOW

CU-6 CARRIER 24ACC660A003 5 16 R-410A SCROLL 1 74 35 35 45 - 15/16 337 SEE BELOW

CU-7 CARRIER 24ACC648A003 4 16 R-410A SCROLL 1 74 35 35 32 - 5/16 248 SEE BELOW

CONDENSING UNIT ACCESSORIES:

1. TIME DELAY RELAY

2. EVAP. FREEZE T-STAT

3. CYCLE PROTECTOR

4. FILTER / DRYER

5. PERMANENTLY LUBRICATED BALL BEARING FAN MOTOR

6. HIGH PRESSURE SWITCH

7. LOW PRESSURE SWITCH

ELECTRICAL DATA:

1. SEE MEP COORDINATION SCHEDULE FOR

STARTER/DISCONNECT AND ALL OTHER ELEC. DATA.

LOW AMBIENT ACCESSORIES:

1. WINTER START CONTROL

2. CRANKCASE HEATER

3. START ASSIST CAPACITOR

4. LOW AMBIENT PRESSURE SWITCH

5. LOW AMBIENT CONTROLLER

CONTROLS:

1. FACTORY CONTROLS

FURNACE SCHEDULE

MARK AREA SERVED MANUF. MODEL NUMBER CONFIGURATION

SUPPLY AIRFLOW DESIGN

VENTILATION

E.S.P

(IN. W.C.)

FAN

MOTOR FAN SPEED ZONES BYPASS

DAMPER

HEATING SECTION COOLING ADD'L

DETAILSCOOLING HEATING MBH IN TYPE AFUE

COMB.

AIR VENT INDOOR COIL

OUTDOOR

UNIT

FN-1 HOTSHOT AREA CARRIER 59TP6A080-16 DOWNFLOW 1610 CFM 1505 CFM 240 CFM 0.5 3/4 HP VARIABLE 1 NO 80 NAT. GAS 96.2% 3" 3" CNPVP4221ALA CU-1 SEE

BELOW

FN-2

CORRIDOR AND

SHOWERS CARRIER 59TP6A060-12 DOWNFLOW 1065 CFM 1120 CFM 130 CFM 0.5 1/2 HP VARIABLE 1 NO 60 NAT. GAS 95.0% 3" 3" CNPVP3014ALA CU-2

SEE

BELOW

FN-3

ENTRY &

CLASSROOM CARRIER 59TP6A080-20 DOWNFLOW 1610 CFM 1555 CFM 320 CFM 0.5 1 HP VARIABLE 1 NO 80 NAT. GAS 96.5% 3" 3" CNPVP4821ALA CU-3

SEE

BELOW

FN-4 DISPATCH AREA CARRIER 59TP6A120-22 DOWNFLOW 2005 CFM 2375 CFM 320 CFM 0.5 1 HP VARIABLE 1 NO 120 NAT. GAS 96.5% 3" 3" CNPVP6024ALA CU-4

SEE

BELOW

FN-5 DISPATCH

BRIEFING ROOM CARRIER 59TP6A060-14 DOWNFLOW 1475 CFM 1135 CFM 220 CFM 0.5 3/4 HP VARIABLE 1 NO 60 NAT. GAS 96.3% 3" 3" CNPVP4217ALA CU-5 SEE

BELOW

FN-6

PHASE 2 &

STORAGE CARRIER 59TP6A120-22 DOWNFLOW 2005 CFM 2375 CFM 335 CFM 0.5 1 HP VARIABLE 1 NO 120 NAT. GAS 96.5% 3" 3" CNPVP6024ALA CU-6

SEE

BELOW

FN-7 TELE/COM CARRIER 59TP6A080-20 UPFLOW 1610 CFM 1555 CFM 300 CFM 0.5 1 HP VARIABLE 1 NO 80 NAT. GAS 96.5% 3" 3" CNPVP4821ALA CU-7 SEE

BELOW

ACCESSORIES:

1. CONCENTRIC VENT TERMINATION KIT

2. 7-DAY PROGRAMMABLE THERMOSTAT (LOW VOLTAGE)

3. CUBE ECONOMIZER MIXING BOX WITH DRYBULB

CONTROLS & INTEGRAL OA & RA DAMPERS.

4. CASED INDOOR EVAPORATOR COIL.

5. PROVIDE DUCT-MOUNTED SMOKE DETECTOR IN

RETURN DUCT FOR ANY FURNACE SUPPLYING OVER

2000 CFM OF AIR.

REMARKS:

1. PROVIDE CONDENSATE NEUTRALIZATION KIT. ROUTE

PIPING TO NEAREST FLOOR DRAIN. SEE 11/M9.1

CONTROLS:

1. CARRIER INFINITY CONTROL SYSTEM

ELECTRICAL DATA:

SEE MEP COORDINATION SCHEDULE

FOR STARTER/DISCONNECT AND ALL

OTHER ELEC. DATA.

ELECTRICAL DATA:

SEE MEP COORDINATION SCHEDULE

FOR STARTER/DISCONNECT AND ALL

OTHER ELEC. DATA.

ELECTRICAL DATA:

SEE MEP COORDINATION SCHEDULE

FOR STARTER/DISCONNECT AND ALL

OTHER ELEC. DATA.

NOTES:

1. PROVIDE MULTIPLE SECTIONS, ACTUATORS, & LINKAGE AS REQUIRED TO ACHIEVE TOTAL SIZE.

2. PROVIDE MOUNTING SLEEVE AS REQUIRED FOR EACH INSTANCE.

3. PROVIDE ACTUATOR(S) FOR EACH DAMPER TO APPLY THE TORQUE NECESSARY FOR THE SPECIFIC INSTALLATION PER THE MANUFACTURER'S

RECOMMENDATIONS. U.N.O., SEE DETAIL 12/M9.1 & COORDINATE WITH E.C.

4. PROVIDE INTERLOCK TO OPEN WHEN ASSOCIATED FAN IS OPERATING.

CONTROL DAMPER SCHEDULE

MARK MANF. MODEL NUMBER SIZE TYPE FUNCTION MAX CFM MOUNTING CONTROL NOTES

CD-1 RUSKIN CD40x2 36" x 12"

TWO-ROW, OPPOSED BLADE,

LOW-LEAKAGE, INSULATED INTAKE FOR EF-1 300 WALL

TWO-POSITION,

FAIL-CLOSED SEE BELOW

ELECTRICAL DATA:

SEE MEP COORDINATION

SCHEDULE FOR

STARTER/DISCONNECT AND ALL

OTHER ELEC. DATA.

GRAVITY VENTILATOR SCHEDULE

MARK AREA SERVED FUNCTION MANUFACTURER MODEL NUMBER CFM SP (INWC)

FREE AREA

(SQ. FT.)

THROAT VEL.

(FPM) THROAT SIZE

THROAT AREA

(SQ. FT.)

WEIGHT

(LBS)

HOOD SIZE

(IN) NOTES

GRV-1 NORTHWEST RELIEF COOK 30X72GR 6000 0.02 14.75 400 30"x72" 15 246 51 X 87 X

19.9 SEE BELOW

GRV-2 NORTHEAST RELIEF COOK 30X48GR 4000 0.019 10 400 30"x48" 10 278 51 X 63 X

18.5 SEE BELOW

GIV-1 MECHANICAL ROOM INTAKE COOK 42X84GI 11,400 0.018 28 407 48x84" 28 801 95 X 135 X

32.2 SEE BELOW

CONTROL:

MOTORIZED DAMPER PROVIDED

INTEGRAL WITH ERV. MOTORIZED

DAMPER NOT REQUIRED WITH GRV.

ACCESSORIES (BY DIV. 23):

1. FOR RELIEF VENTILATORS PROVIDE GRAVITY DAMPER BALANCED TO OPEN COMPLETELY WHEN FURNACES ARE IN ECONOMIZER MODE.

2. PROVIDE SEISMICALLY COMPLIANT ROOF CURB MIN 14" TO MATCH ROOF SLOPE. COORDINATE FLASHING WITH G.C.

3. PROVIDE BIRD SCREEN.

CONTROL

1. PROVIDE THERMOSTAT & MANUAL OVERRIDE. SEE DETAIL 2/M9.2.

2. PROVIDE WALL-MOUNTED MANUAL ON/OFF & SPEED CONTROLLER.

3. COORDINATE WITH E.C. FOR CONTROL BY OCCUPANCY SENSOR/LIGHT

SWITCH.

ELECTRIC HEATER SCHEDULE

MARK AREA SERVED MANUF. CAPACITY MODEL

NUMBER

DIMENSIONS

FINISH MOUNTING ADDITIONAL DETAILS

WIDTH HEIGHT DEPTH

EWH-1 HOTSHOT CORRIDOR KING 1500 W LPWA1215 13 7/8" 23 1/4" 3 3/4" ALUM. WALL-RECESSED SEE BELOW

EWH-2 DISPATCH CORRIDOR KING 1500 W LPWA1215 13 7/8" 23 1/4" 3 3/4" ALUM. WALL-RECESSED SEE BELOW

EWH-3 ENTRY/WAITING KING 1500 W LPWA1215 13 7/8" 23 1/4" 3 3/4" ALUM. WALL-RECESSED SEE BELOW

EWH-4 MECH 201 KING 500 W PAW1215 12 1/2" 6" 4 1/2" WHITE WALL-SURFACE SEE BELOW

EWH-5 MECH 201 KING 500 W PAW1215 12 1/2" 6" 4 1/2" WHITE WALL-SURFACE SEE BELOW

ETH-1 RECEPTION QMARK 1125 W QTS1100 15" 3 1/2" 8 8/7" WHITE TOE SPACE SEE BELOW

ACCESSORIES:

1. WALL-MOUNTED, LINE VOLTAGE T-STAT

2. INTEGRAL DISCONNECTING MEANS AND OVERLOADS

3. INTEGRAL FAN

ELECTRICAL DATA:

1. SEE MEP COORDINATION SCHEDULE

FOR STARTER/DISCONNECT AND ALL

OTHER ELEC. DATA.

GRILLE, REGISTER AND DIFFUSER SCHEDULE

MARK MODULE SIZE FUNCTION TYPE MAX CFM

PERFORMANCE DATA AT MAX CFM

NECK SIZE AT

MAX CFM

SELECTION MOUNTING & FINISH

ADDITIONAL

DETAILSNC AT MAX PRESSURE DROP AT MAX

CFM (IN. W.C.)

MAX THROW

(FT) VELOCITY (FPM) MANF. MODEL NUMBER THROW PATTERN MOUNTING MATERIAL

S-1 24"x24" SUPPLY CEILING DIFFUSER 265 - 0.03 15' 382 10"x10" KRUEGER 1240 4-WAY LAY-IN STEEL SEE BELOW

S-2 NECK + 5" SUPPLY CEILING DIFFUSER 670 16 0.05 23' 377 16"x16" KRUEGER 1240 4-WAY SURFACE STEEL SEE BELOW

S-3 NECK + 1-3/4" SUPPLY

DUCT MOUNTED

DIFFUSER 405 16 0.03 37' 405 24"x8" KRUEGER DMGDR

DOUBLE

DEFLECTION DUCT MOUNTED ALUMINUM SEE BELOW

S-4 NECK + 7" SUPPLY CEILING DIFFUSER 400 17 0.05 27' 400 12"x12" KRUEGER 1240P 4-WAY CEILING

MOUNTED STEEL SEE BELOW

R-1 24"x24" RETURN EGG CRATE 540 - 0.00 - 174 16"x16" KRUEGER EGC5 - LAY-IN SEE BELOW

R-2 NECK + 1-3/4" RETURN EGG CRATE 1610 22 0.04 - 520 30"x16" KRUEGER EGC5 - SURFACE ALUMINUM SEE BELOW

E-1 NECK + 1-3/4" EXHAUST EGG CRATE 200 14 0.04 - 548 8"x8" KRUEGER EGC5 - SURFACE SEE BELOW

REMARKS:

1. PROVIDE INTEGRAL OPPOSED BLADE DAMPER FOR ALL SURFACE MOUNTED AIR TERMINALS FOR BALANCING AIRFLOW.

2. FOR ALL AIR TERMINALS WHICH ARE NOT SURFACE-MOUNTED, PROVIDE A MANUAL VOLUME DAMPER AT EACH BRANCH

TAKE-OFF WHERE A CFM IS NOTED ON THE PLANS.

REMARKS FOR ALL:

1. SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR CEILING TYPES.

2. SUBMITTAL DATA SHALL INCLUDE N.C., THROW, VELOCITY, PRESSURE DROP AS

WELL AS ALL PHYSICAL AND INSTALLATION DATA.

BILLINGS | BOZEMAN | MISSOULA

0 1 2 3 4 5 6 7 8 9 10 inches

DRAWING NO.

PKG

NO.

SHEET

OF

PROJECT NO.:

REVISIONS:

DESIGNED

TECH. REVIEW

CADD

DESIGNED SUB SHEET NO. TITLE OF SHEET

INRC WAREHOUSE (NORTH)

-PHASE 1

/2

/2

:2

:5

P

M

M0.3

03.01.17C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

HVAC SCHEDULES

13083.00

USDA FOREST SERVICE

BJK/JTW

REB

DMP

P

R E E

NI

GN

ELANOISSEF

O R R

EG

ISTERE

D

S

T A

TE OF ID

AH

O

WAVERE

K

TYD

O J

RFQ No.: 12034320Q0200 – INRC HVAC Preventive Maintenance - Idaho Panhandle N.F. / Attach 02: 191009 Warehouse Mechanical Drawings / Page 3 of 16

M.E.P. COORDINATION SCHEDULE

MARK DESCRIPTION

ELECTRICAL DATA CONTROL

NOTES

STARTER/DISCONNECT

LOAD VOLT-PH TYPE DIV TYPE DIV (NEMA)

CD-1 CONTROL DAMPER, INTAKE FOR EF-1

FRACTIONAL

HP 120 V - 1 PH SEE DETAIL 12/M9.1

CU-1 CONDENSING UNIT FOR FN-1 23.6 MCA 208 V - 1 PH T 23 / 23 2 FD 26 / 26

CU-2 CONDENSING UNIT FOR FN-2 16.7 MCA 208 V - 1 PH T 23 / 23 2 FD 26 / 26

CU-3 CONDENSING UNIT FOR FN-3 26.1 MCA 208 V - 1 PH T 23 / 23 2 FD 26 / 26

CU-4 CONDENSING UNIT FOR FN-4 28.0 MCA 208 V - 1 PH T 23 / 23 2 FD 26 / 26

CU-5 CONDENSING UNIT FOR FN-5 23.6 MCA 208 V - 1 PH T 23 / 23 2 FD 26 / 26

CU-6 CONDENSING UNIT FOR FN-6 28.0 MCA 208 V - 1 PH T 23 / 23 2 FD 26 / 26

CU-7 CONDENSING UNIT FOR FN-7 26.1 MCA 208 V - 1 PH T 23 / 23 2 FD 26 / 26

DWH1 DOMESTIC WATER HEATER 5.0 FLA 115 V - 1 PH UC 22 / 22 2 MSS 26 / 26

EF-1 HOTSHOT TOOL SHOP EXHAUST FAN 1/8 HP 115 V - 1 PH SEE DETAIL 13/M9.1

EF-2 HOTSHOT EQUIP. STORAGE EXHAUST FAN 1/8 HP 115 V - 1 PH MSS 23 / 23 9 FW 23 / 26

EF-3 HOTSHOT LOCKERS EXHAUST FAN 1/8 HP 115 V - 1 PH MSS 23 / 23 9 FW 23 / 26

EF-4 RESTROOM & LOCKER EXHAUST FAN 1/8 HP 115 V - 1 PH L / OCC 23 / 23 9 FW 23 / 26

ETH-1 RECEPTION TOE HEATER 4.7 MCA 120 V - 1 PH T 23 / 23 2 INT 23 / 26

EWH-1 HOTSHOT CORRIDOR WALL HEATER 1500 W 120 V - 1 PH T 23 / 23 2 INT 23 / 26

EWH-2 DISPATCH CORRIDOR WALL HEATER 1500 W 120 V - 1 PH T 23 / 23 2 INT 23 / 26

EWH-3 ENTRY/WAITING WALL HEATER 1500 W 120 V - 1 PH T 23 / 23 2 INT 23 / 26

EWH-4 MECHANICAL ROOM WALL HEATER 500 W 120 V - 1 PH T 23 / 23 2 INT 23 / 26

EWH-5 MECHANICAL ROOM WALL HEATER 500 W 120 V - 1 PH T 23 / 23 2 INT 23 / 26

FN-1 HOTSHOT AREA FURNACE 14.5 MCA 115 V - 1 PH T 23 / 23 12 MSS 26 / 26

FN-2 ENTRY & SHOWER AREA FURNACE 10.3 MCA 115 V - 1 PH T 23 / 23 12 MSS 26 / 26

FN-3 CLASSROOM FURNACE 19.3 MCA 115 V - 1 PH T 23 / 23 12 MSS 26 / 26

FN-4 DISPATCH AREA FURNACE 19.4 MCA 115 V - 1 PH T 23 / 23 12 MSS 26 / 26

FN-5 DISPATCH CONFERENCE ROOM FURNACE 14.5 MCA 115 V - 1 PH T 23 / 23 12 MSS 26 / 26

FN-6 LAB & STORAGE AREA FURNACE 19.4 MCA 115 V - 1 PH T 23 / 23 12 MSS 26 / 26

FN-7 TEL/COM FURNACE 19.3 MCA 115 V - 1 PH T 23 / 23 12 MSS 26 / 26

UH-1 HOTSHOT TOOL SHOP UNIT HEATER 1.9 FLA 115 V - 1 PH SEE DETAIL 12/M9.1

CONTROL TYPE DIVISION OF RESPONSIBILITIES:

DD

CO

CO2

L

MSS

T

UC

NA

DDC

H/O/A

PN

DUCT SMOKE DETECTOR

CARBON MONOXIDE DETECTORS

CARBON DIOXIDE DETECTORS

LIGHT SWITCH

MANUAL SPEED SWITCH

THERMOSTAT

UNIT CONTROLLER

NOT APPLICABLE

DIRECT DIGITAL CONTROLS

HAND / OFF / AUTO SWITCH

PNEUMATIC

22/22 22/26 23/23 23/26 26/26

FURNISHED AND INSTALLED BY DIV. 22, WIRED BY DIV. 22

FURNISHED AND INSTALLED BY DIV. 22, WIRED BY DIV. 26

FURNISHED AND INSTALLED BY DIV. 23, WIRED BY DIV. 23

FURNISHED AND INSTALLED BY DIV. 23, WIRED BY DIV. 26

FURNISHED AND INSTALLED BY DIV. 26, WIRED BY DIV. 26

STARTER/DISCONNECT TYPE NOTES:

FD

CSFD

RVSS

VFD

MSS

MOC

FW

NA

SC

INT

3PP

FUSED DISCONNECT PROVIDED BY MC

COMBINATION STARTER/DISCONNECT - HOA

REDUCED VOLTAGE SOLID-STATE

VARIABLE FREQUENCY DRIVE - HOA

MANUAL STARTER SWITCH PROVIDED BY EC

MOTOR OVER-CURRENT PROTECTION

FACTORY-WIRED SINGLE PT. CONNECTION

NOT APPLICABLE

SPEED CONTROL

INTEGRAL CONTROLS

THREE-PRONG PLUG

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

INTEGRAL DISCONNECTS AND OVERLOADS

INTEGRAL OVERLOADS

INTEGRAL OVERLOADS, RECEPTACLE

RECEPTACLE PROVIDED BY EC

SINGLE POINT CONNECTION. DISCONNECT PROVIDED BY MC

PROVIDE RECEPTACLE AND DATA CONNECTION FOR PANEL

MOUNT ON UNI-STRUT IN FRONT OF UNIT

PROVIDE EMERGENCY SHUNT TRIP AT EACH EXIT FROM THE SPACE

DISCONNECT SWITCH PROVIDED WITH EQUIPMENT BY MC

TOGGLE SWITCH DISCONNECT PROVIDED BY MC WITH EQPM.

DUCT SMOKE DECTOR PROVIDED BY EC

EC TO PROVIDE STARTER/DISCONNECT W/ IN SIGHT OF UNIT.

EC TO INSTALL SPEED CONTROL SWITCH FURNISHED BY MC.

CONTROL PANEL W/ INTEGRAL STARTERS PROVIDED BY MC WIRED

BY EC. INDOOR UNIT IS POWERED FROM OUTDOOR UNIT.

GENERAL NOTES:

1. ALL DUCT SMOKE DETECTORS FURNISHED BY DIV. 26, INSTALLED BY DIV. 23 AND WIRED BY DIV. 26. DIV 26 SHALL WIRE SMOKE DAMPER TO

SHUT WHEN ALARM IS INITIATED BY DUCT SMOKE DETECTOR.

BILLINGS | BOZEMAN | MISSOULA

0 1 2 3 4 5 6 7 8 9 10 inches

DRAWING NO.

PKG

NO.

SHEET

OF

PROJECT NO.:

REVISIONS:

DESIGNED

TECH. REVIEW

CADD

DESIGNED SUB SHEET NO. TITLE OF SHEET

INRC WAREHOUSE (NORTH)

-PHASE 1

/2

/2

:2

:5

P

M

M0.6

03.01.17C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

MEP COORDINATION

13083.00

USDA FOREST SERVICE

BJK/JTW

REB

DMP

P

R E E

NI

GN

ELANOISSEF

O R R

EG

ISTERE

D

S

T A

TE OF ID

AH

O

WAVERE

K

TYD

O J

RFQ No.: 12034320Q0200 – INRC HVAC Preventive Maintenance - Idaho Panhandle N.F. / Attach 02: 191009 Warehouse Mechanical Drawings / Page 4 of 16

R E

F

MAC

ROOM /

BRIEFING

ROOM

IA

FLOOR

CENTER

MNGR.

OFFICE

ASST.

CENTER

MNGR.

OFFICE

INTEL/DUTY

OFFICER

SHARED

TRAINING

ROOM/CLASSROOM

CORRIDOR

122A

ENTRY

WAITING

HOTSHOT

SQUAD

LEADER/SRFF

OFFICE

CORRIDOR

HOTSHOT

OFFICE

HOTSHOT

OFFICE

HOTSHOT

TOOL

SHOP/WORK

AREA

HOTSHOT

EQUIPMENT

STORAGE

HOTSHOT

READY

ROOM/PERSONAL

GEAR/LOCKERS

UNISEX

TOILET

PRINTER

AREA

MENS

LOCKERS/

SHOWERS

WOMENS

LOCKERS/

SHOWERS

WOMENS

RESTROOM

MENS

RESTROOM

ELEC.

RM.

STORAGE

RECEPTION

STG.

123A

STORAGE

103A

BREAKROOM

HISTORICAL

FILE

STORAGE

CORRIDOR

WATER

SERVICE

/ RISER

RM.

EWH-1

EWH-2

EWH-3

ETH-1

10 11 12 13

E

D

C

B

A

"ø

12"ø

8"ø 10"ø

8"x8" S-1

12"x12" R-1

12"x12" R-1

10"x10" S-1

16"x16" R-1

8"x8" S-1

6"x6" S-2

16"x16" S-2

TYP. 3

10"x10" S-1

TYP. 4

8"x8" S-2

12"x12" R-2

8"x8" S-2

TYP. 2

6"x6" S-2

6"ø

"ø

"ø

10"ø

"x

10"ø

6"ø

6"ø

6"ø

20"x20" R-1

"ø

16"ø16"x16"

"ø

"ø

"ø

UH-1

8"x8" S-1

TYP. 4

8"x8" S-2

8"x8" S-2

TYP. 2

TYP. 2

"ø

8" ø

10"ø

4 4

4 4

6"x6" S-3

"ø

"ø

8" ø

8"ø

10"ø

8" ø

8"ø

8"x8" E-1

TYP. 2

8"x8" E-2

TYP. 2

4 18"x18" 14"ø

"ø

"ø

"ø

12"ø

"x

"ø

"ø

8"ø

10"ø

6" ø

10"ø

10"ø

10"ø 10"ø

"ø

"ø

10"ø

8" ø

8" ø

10"x10" S-1

TYP. 3

12"x12" R-1

TYP. 3

10"x10" S-1

TYP. 4

20"x20" R-1

TYP. 2

10"x10"

S-1 21512"x12"

R-1

8"x8" S-1

TYP. 2

14"x14" R-1

6"x6" S-1

8"x8" S-2

6"x6" S-2

8"x8" S-2

18"x18" R-2

18"x18" R-2

10"x10" R-2

10"x10" E-1

8"x8" E-1

CU-3

CU-4

CU-7CU-2

CU-6

CU-5

CU-1

L-1

CD-1

6"ø

8"ø

8" ø

10"x10" S-1

TYP. 2

T

UH-1

EF-1

8" ø

8" ø

8"ø

10"ø 10"ø

8"ø

8" ø

6" ø

10"ø

T EWH-1

T FN-1

T

EWH-3

T

ETH-1

T EWH-2

T FN-5 T

FN-4

T FN-3

T FN-2

KEY NOTES:

BILLINGS | BOZEMAN | MISSOULA

0 1 2 3 4 5 6 7 8 9 10 inches

DRAWING NO.

PKG

NO.

SHEET

OF

PROJECT NO.:

REVISIONS:

DESIGNED

TECH. REVIEW

CADD

DESIGNED SUB SHEET NO. TITLE OF SHEET

INRC WAREHOUSE (NORTH)

-PHASE 1

/2

/2

:2

:0

P

M

M2.1

03.01.17C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

1ST FLOOR HVAC PLAN

13083.00

USDA FOREST SERVICE

BJK/JTW

REB

DMP

: 1/8" = 1'-0"M2.1

13 1ST LEVEL HVAC PLAN NORTH

P H

A S

E

9/ M

2.

P H

A S

E

/M

2.

M2.1

1. INTERLOCK CONTROL DAMPER TO OPEN WHEN ASSOCIATED EXHAUST FAN EF-1 OPERATES.

2. 12"Ø EXHAUST DUCT UP TO EXHAUST FAN EF-4 ON ROOF.

3. 10"Ø SA BRANCH DUCT DROPS FROM MAIN AT THIS LOCATION TO ENTER CEILING CAVITY BELOW MEZZANINE

FLOOR.

4. REMOTE BALANCING DAMPER, TYP. FOR ALL LOCATIONS ABOVE HARD LID. B.O.D.: GREENHECK RBDR-50. MOUNT

WALL PLATES WITH 9V CONTROL PORTS CLEARLY MARKED FOR ALL LOCATIONS IN MEZZANINE MECHANICAL

ROOM.

5. 10"Ø SA DROPS BELOW MEZZANINE LANDING AT THIS LOCATION.

6. AIR-COOLED CONDENSING UNIT ON CONCRETE PAD, TYP. 7. PROVIDE MANUFACTURER'S RECOMENDED

CLERARANCES IN ALL DIRECTIONS. PROVIDE LOCKING PORTS ON ALL REFRIGERATION LINES PER IMC

REQUIREMENTS.

7. 14"x14" EA UP TO EF-1 ON ROOF. PROVIDE LINE-VOLTAGE MOTORIZED DAMPER. TERMINATE EA DUCT OPEN-

ENDED IN SPACE.

8. 12"x12" SA & RA TO FURNACE FN-2 IN MEZZANINE MECHANICAL ROOM SEE 13/M2.5 FOR CONTINUATION.

9. 16"x16" SA & RA TO FURNACE FN-1 IN MEZZANINE MECHANICAL ROOM SEE 13/M2.5 FOR CONTINUATION.

10. 16"x16" SA & RA TO FURNACE FN-3 IN MEZZANINE MECHANICAL ROOM SEE 13/M2.5 FOR CONTINUATION.

11. 18"x18" SA & RA TO FURNACE FN-4 IN MEZZANINE MECHANICAL ROOM SEE 13/M2.5 FOR CONTINUATION.

12. 16"x16" SA & RA TO FURNACE FN-5 IN MEZZANINE MECHANICAL ROOM SEE 13/M2.5 FOR CONTINUATION.

13. 18"x18" SA & RA TO FURNACE FN-6 IN MEZZANINE MECHANICAL ROOM SEE 13/M2.5 FOR CONTINUATION.

14. TERMINATE 18"x18" SA & RA DUCT OPEN-ENDED IN MEZZANINE FOR FUTURE (PHASE 2) CONNECTION.

15. 4" FLUE AND VENT UP THROUGH ROOF IN CONCENTIC TERMINATION.

16. DASHED LINE REPRESENTS OUTLINE OF MEZZANINE ABOVE.

17. REFRIGERANT LINES FROM CONDENSING UNITS UP TO ATTIC AND THEN TO MEZZANINE ABOVE.

P

R E E

NI

GN

ELANOISSEF

O R R

EG

ISTERE

D

S

T A

TE OF ID

AH

O

WAVERE

K

TYD

O J

RFQ No.: 12034320Q0200 – INRC HVAC Preventive Maintenance - Idaho Panhandle N.F. / Attach 02: 191009 Warehouse Mechanical Drawings / Page 5 of 16

GRV-2

GRV-1

GIV-1

EF-4

11 12 13

E

D

C

B

A

EF-3

EF-2

EF-1

KEY NOTES:

BILLINGS | BOZEMAN | MISSOULA

0 1 2 3 4 5 6 7 8 9 10 inches

DRAWING NO.

PKG

NO.

SHEET

OF

PROJECT NO.:

REVISIONS:

DESIGNED

TECH. REVIEW

CADD

DESIGNED SUB SHEET NO. TITLE OF SHEET

INRC WAREHOUSE (NORTH)

-PHASE 1

/2

/2

:2

:0

P

M

M2.3

03.01.17C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

ROOF HVAC PLAN

13083.00

USDA FOREST SERVICE

BJK/JTW

REB

DMP

: 1/8" = 1'-0"M2.3E2.4

13 ROOF HVAC PLAN NORTH

P H

A S

E

9/ M

2.

P H

A S

E

/M

2.

M2.3

1. DOWNBLAST EXHAUST FAN ON 14" INSULATED ROOF CURB. SEE DETAIL 9/M9.1. COORDINATE FLASHING WITH G.C.

2. RELIEF VENTILATOR ON 14" INSULATED ROOF CURB WITH INTEGRAL GRAVITY DAMPER BALANCED TO 0.05 IN

W.G. (ADJ.). COORDINATE FLASHING WITH G.C.

3. INTAKE VENTILATOR ON 14" INSULATED ROOF CURB. COORDINATE FLASHING WITH G.C.

4. FURNACE FLUE AND VENT IN CONCENTRIC VENT KIT BY MANUFACTURER DOWN THROUGH ROOF. TYP. 7.

COORDINATE FLASHING WITH G.C. PROVIDE MIN. 10FT CLEARANCE FROM ALL AIR INTAKES.

5. FLUE & VENT DOWN THROUGH ROOF IN CONCENTRIC VENT KIT TO UH-1.

P

R E E

NI

GN

ELANOISSEF

O R R

EG

ISTERE

D

S

T A

TE OF ID

AH

O

WAVERE

K

TYD

O J

RFQ No.: 12034320Q0200 – INRC HVAC Preventive Maintenance - Idaho Panhandle N.F. / Attach 02: 191009 Warehouse Mechanical Drawings / Page 6 of 16

FN-2

FN-5 FN-4

FN-3

FN-1

FN-6

EWH-4

EWH-5

10 11

C

FN-7

12"ø 14"ø 12"ø 12"ø

"ø

12"ø

"ø

"x

10"ø

"ø

"x

16"x16" 16"x16"

16"x16"

16"x16"

16"x16"

16"x16"18"x18"

18"x18"

"x

"x

"x

"x

18"x18"

18"x18"

24"x8" S-3

30"x16" R-2

30"x16" R-2

30"x16"

"x

T

T

EWH-4

FN-7

24"x8" S-3 405 24"x8"

S-3 400 24"x8"

S-3

S D

S D

13 13

KEY NOTES:

BILLINGS | BOZEMAN | MISSOULA

0 1 2 3 4 5 6 7 8 9 10 inches

DRAWING NO.

PKG

NO.

SHEET

OF

PROJECT NO.:

REVISIONS:

DESIGNED

TECH. REVIEW

CADD

DESIGNED SUB SHEET NO. TITLE OF SHEET

INRC WAREHOUSE (NORTH)

-PHASE 1

/2

/2

:2

:0

P

M

M2.5

03.01.17C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

MEZZANINE HVAC PLAN

13083.00

USDA FOREST SERVICE

BJK/JTW

REB

DMP

: 1/4" = 1'-0"M2.5E2.4

13 2ND LEVEL MEZZANINE HVAC PLAN

M2.5

1. OA FROM INTAKE VENTILATOR TO ECONOMIZER MIXING BOX AT FURNACE INTAKE, TYP. ALL.

2. 42"x48" OA PLENUM UP TO INTAKE VENTILATOR GIV-1 ON ROOF.

3. U.N.O., RA DUCT STUB THROUGH MEZZANINE WALL TERMINATES IN PLENUM WITH 1/4" WIRE MESH SCREEN.

TYP. ALL. CONNECT RA TO ECONOMIZER MIXING BOX.

4. 30"x16" TRANSFER DUCT TERMINTATES IN PLENUM WITH 1/4" W.M .S.

5. DOWNFLOW FURNACE, TYP. 6. PROVIDE CONDENSATE NEUTALIZATION KIT & ROUTE TO FLOOR DRAIN. SEE

DETAIL 2/M9.2.

6. UPFLOW FURNACE. PROVIDE CONDENSATE NEUTALIZATION KIT & ROUTE TO FLOOR DRAIN. SEE DETAIL 2/M9.2.

7. FLUE & VENT UP THROUGH ROOF IN CONCENTRIC VENT KIT.

8. SA DUCT ROUTED IN PLENUM TO ZONE. SEE 13/M2.1.

9. 18"x18" SA MAIN DOWN THROUGH FLOOR.

10. TERMINATE 18"x18" SA & RA DUCTS OPEN-ENDED IN MEZZANINE FOR FUTURE (PHASE 2) CONNECTION.

11. SEE SHEET KEYNOTE 5 ON M2.1 FOR CONTINUATION.

12. REFER TO PLUMBING PLANS FOR GAS PIPING TO FURNACES.

13. REFRIGERANT LINES FROM ADJACENT ATTIC.

P

R E E

NI

GN

ELANOISSEF

O R R

EG

ISTERE

D

S

T A

TE OF ID

AH

O

WAVERE

K

TYD

O J

RFQ No.: 12034320Q0200 – INRC HVAC Preventive Maintenance - Idaho Panhandle N.F. / Attach 02: 191009 Warehouse Mechanical Drawings / Page 7 of 16

N.T.S. N.T.S. N.T.S. N.T.S.

N.T.S. N.T.S. N.T.S.

N.T.S.

N.T.S.

1"

EXTENDED BASE OR

MINIMUM 14" CURB

CURB FURNISHED AND

INSTALLED BY MECHANICAL

CONTRACTOR

EXHAUST DUCT W/

EXTERNAL

INSULATION

EXHAUST FAN

MOTORIZED BACKDRAFT

DAMPER PER SCHEDULE

ROOF

PROVIDE GALVANIZED

DRAIN PAN WITH MIN. 8" AIR

GAP.

BIRD SCREEN

COORDINATE FLASHING

WITH G.C.

SUPPORT WITH STEEL

ANGLE AS NEEDED

BIRD SCREEN

CAULK

MOTORIZED DAMPER

2-POSITION INTERLOCK

WITH EXHAUST FAN

SHEET METAL

SLEEVE

TILT DUCT AND MOTORIZED DAMPER

SLIGHTLY FOR DRAINAGE

SILL EXTENSION

EXTRUDED ALUM. OR

GALV. STEEL LOUVER

(SEE SPECIFICATIONS)

BUILDING WALL

HEAD SECTION (JAMB SIMILAR)

ANCHOR SECURELY TO WALL

CONSTRUCTION

CAULK ALL AROUND TO

MAKE WEATHER TIGHT

USE THIS WITH ROUND

DUCT TAKEOFF'S

SPIN-IN FITTING WITH

MANUAL VOLUME

DAMPER

USE THIS WITH

RECTANGULAR

DUCT TAKEOFF'S

MANUAL VOLUME DAMPER

REFER TO GRILLE-DIFFUSER

SCHEDULE

MAIN SUPPLY

RETURN OR

EXHAUST DUCT

INSULATION

12"X12" (300X300MM) MIN.

SIZE DUCT ACCESS

DOOR

24 GAGE METAL

INSULATION NOTE

EXHAUST

TUBE

INLET TUBE

HOLES FACE

UPSTREAM OF

AIR FLOW

AIR

DUCT

SMOKE DETECTOR

HOUSING MOUNTED TO

SIDE OF DUCT

NOTES

1. DETAIL SHOWS GENERAL INSTALLATION METHODS. REFER TO INDIVIDUAL

MFR. FOR THEIR SPECIFIC INSTALLATION & LOCATION INSTRUCTIONS.

2. STANDOFF BRACKET NOT REQUIRED ON NON-INSULATED DUCT.

NOTE:

CUT INLET AND

EXHAUST TUBES

TO LENGTH

SPECIFIED BY

MANUFACTURER

DIRECTION

RECTANGULAR

90 DEGREE DUCT

TURNING

VANE

NOTE:

REQUIRED IN ALL 90

DEGREE RECTANGULAR

ELBOWS IN BUILDING. AIR FLOW

L

L+2"

W+2"

45°

4" 12"

SUPPLY DUCTWORK

45 DEG. ENTRANCE TAP

DOUBLE DEFLECTION

SIDE WALL REGISTER

W

CL

LOCKING STRAPS PER

SPECIFICATIONS COLLAR WITH

TAPE AND POSITIVE SERCURE

FLEX DUCT TO SHEETMETAL

SUPPORT STRAP

INSULATED FLEX DUCT

(MAXIMUM 72") OR RIGID

DUCT AS INDICATED

ON PLANS

SHEETMETAL PLENUM WITH

1" LINER - INSIDE DIMENSIONS

SAME SIZE AS DIFFUSER NECK

OPPOSED BLADE DAMPER

AS SCHEDULED

GWB CEILING CEILING DIFFUSER LAY-IN SUSPENDED CEILING

COOLING COIL

CONDENSATE DRAIN PAN

OPEN VENT

DRAIN OUTLET

ALL PIPING SAME SIZE AS DRAIN PAN

CONNECTION (3/4" MINIMUM)

J"

H"

L"

H" = STATIC PRESSURE + 1"

J" = 1/2 x H"

L" = H" + J" + PIPE DIAMETER

1 DUCT BRANCH & SPIN-IN CONNECTION DETAIL

M2.1 : M9.1

2 RECTANGULAR DUCT TURNING VANE DETAIL

M2.1 : M9.1

3 DUCT-MOUNTED REGISTER DETAIL

M2.1 : M9.1

4 LOUVER DETAIL

M2.1 : M9.1

9 DUCT MOUNTED SMOKE DETECTOR DETAIL

M2.1 : M9.1

10 CEILING DIFFUSER/GRILLE DETAIL

M2.1 : M9.1

11 CONDENSATE TRAP DETAIL

M2.5 : M9.1

13 ROOF EXHAUST FAN DETAIL

M2.3 : M9.1

12 DOUBLE-ROW CONTROL DAMPER DETAIL

M2.1 : M9.1

OPPOSED DAMPER

BLADE W/ TPR BLADE

EDGE SEAL

BIRD SCREEN

LOUVER BLADE

DOUBLE-ROW

CONTROL DAMPERS

(AS SCHEDULED)

BILLINGS | BOZEMAN | MISSOULA

0 1 2 3 4 5 6 7 8 9 10 inches

DRAWING NO.

PKG

NO.

SHEET

OF

PROJECT NO.:

REVISIONS:

DESIGNED

TECH. REVIEW

CADD

DESIGNED SUB SHEET NO. TITLE OF SHEET

INRC WAREHOUSE (NORTH)

-PHASE 1

/2

/2

:2

:0

P

M

M9.1

03.01.17C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

HVAC DETAILS

13083.00

USDA FOREST SERVICE

BJK/JTW

REB

DMP

P

R E E

NI

GN

ELANOISSEF

O R R

EG

ISTERE

D

S

T A

TE OF ID

AH

O

WAVERE

K

TYD

O J

RFQ No.: 12034320Q0200 – INRC HVAC Preventive Maintenance - Idaho Panhandle N.F. / Attach 02: 191009 Warehouse Mechanical Drawings / Page 8 of 16

AIRFLOW

AIRFLOW

AIRFLOW

PIANO HINGE

1/4" OVERLAP

DOOR W/ (2)

SNAP LOCKS

MIXING BOX

RETURN AIR DUCT TO MIXING

BOX SEE SHEET M2.1 FOR DUCT

ROUTING

MERV-8, 30% EFFICIENT

PRE-FILTER

INSULATE ALL SUPPLY DUCTWORK PER

DUCTWORK MATERIAL SCHEDULE

FILTER

FRESH AIR INTAKE

SEE SHEET M2.1 FOR

DUCT ROUTING

MIXING BOX

MERV-13, 80% EFFICIENT FINAL-FILTER

FILTER HOUSING DETAIL

NOTE:

UPFLOW FURNACE SHOWN -

DOWNFLOW FURNACE SIMILAR

T

EXHAUST FAN

AND DISCONNECT

BY M.C.

HEAT

NOTE:

ALL 120 VOLT WIRING BY ELECTRICAL

CONTRACTOR. ALL LOW VOLTAGE WIRING,

THERMOSTATS AND DAMPER ACTUATORS BY

MECHANICAL CONTRACTOR/TEMPERATURE

CONTOLS CONTRACTOR.

THERMOSTAT

(1 OR 2 HEAT AS

SCHEULED / 1 COOL)

BY T.C.

120 VOLT WIRE IN

NEC APPROVED

CONDUIT (TYP OF ALL) BY T.C.

RELAY

BY T.C.

N

MANUAL OVERRIDE

SWITCH BY T.C.

DAMPER

ACTUATOR (TYP)

BY T.C.

CONTROL DAMPER

BY M.C.

HOT 24V

UNIT

HEATER

BY M.C.

N

TRANSFORMER

BY T.C.

H

N

120V

COOL

MOTORIZED

DAMPER INTEGRAL

TO EXHAUST FAN BY

M.C.

C

LINE

VOLTAGE

POWER BY

E.C.

24V

BY T.C.

BY T.C.

24V

BY T.C.

120V

BY E.C.

120V

BY E.C.

BILLINGS | BOZEMAN | MISSOULA

0 1 2 3 4 5 6 7 8 9 10 inches

DRAWING NO.

PKG

NO.

SHEET

OF

PROJECT NO.:

REVISIONS:

DESIGNED

TECH. REVIEW

CADD

DESIGNED SUB SHEET NO. TITLE OF SHEET

INRC WAREHOUSE (NORTH)

-PHASE 1

/2

/2

:2

:0

P

M

M9.2

03.01.17C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

HVAC DETAILS

13083.00

USDA FOREST SERVICE

BJK/JTW

REB

DMP

: N.T.S.M9.2

3 UNIT HEATER, EXHAUST FAN, & CONTROL DAMPER TEMPERATURE CONTROL SCHEMATIC

M2.5 : M2.1 :: 1/8" = 1'-0"M9.2

2 FURNACE DETAIL

P

R E E

NI

GN

ELANOISSEF

O R R

EG

ISTERE

D

S

T A

TE OF ID

AH

O

WAVERE

K

TYD

O J

RFQ No.: 12034320Q0200 – INRC HVAC Preventive Maintenance - Idaho Panhandle N.F. / Attach 02: 191009 Warehouse Mechanical Drawings / Page 9 of 16

PROJECT SPECIFICATIONS

A. ALL WORK ON THE PROJECT SHALL CONFORM TO ALL LOCAL CITY, STATE AND

NATIONAL CODES AND REGULATIONS, INCLUDING BUT NOT LIMITED TO THE

N.F.P.A., N.E.C., U.B.C., I.E.C.C., I.M.C., U.P.C., THE LOCAL UTILITY SERVING

COMPANIES AND THE AUTHORITY HAVING JURISDICTION.

B. THE WORK ON THIS PROJECT SHALL CONSIST OF ALL ITEMS, ARTICLES,

MATERIALS, EQUIPMENT, AND LABOR FURNISHED TOGETHER ALONG WITH ALL

INCIDENTAL ITEMS REQUIRED BY GOOD PRACTICE AND WORKMANSHIP TO

PROVIDE A SATISFACTORY, COMPLETE AND FUNCTIONAL SYSTEM IN

ACCORDANCE WITH THE DRAWINGS AT NO ADDITIONAL COST TO THE

CONTRACTING OFFICER.

C. THE CONTRACTOR SHALL BE RESPONSIBLE FOR AND PAY FOR ALL FEES AND

PERMITS REQUIRED FOR WORK UNDER THEIR CONTRACT AND UNDER THEIR

SUPERVISION BY SUBCONTRACT.

D. MANUFACTURER'S TRADE NAMES AND CATALOG NUMBERS ARE LISTED TO

IND…

This is the start of the file's text. The full file is on GovTribe.