LIMITED ASBESTOS AND LEAD-CONTAINING PAINT SURVEY REPORT
This is a diagnostic environmental survey report prepared by Geocon Consultants, Inc. for the California Department of General Services (DGS) regarding the Diagnostic Center of Central California located at 1818 West Ashlan Avenue in Fresno, California. The survey was conducted on March 29-30, 2023, to identify and quantify asbestos-containing materials (ACM) and lead-containing paint (LCP) in designated renovation areas prior to planned construction activities. The project encompassed five structures (Wings A, B, C, E, and G) with a combined square footage of approximately 25,700 square feet. The survey included exterior areas, restrooms in Wings B and C, the boiler room in Wing E, and interior painted door trim in Wing G. The consultant collected 59 bulk asbestos samples representing 22 material types and seven bulk samples of suspect lead-containing paint, with all samples submitted to accredited laboratories for analysis under chain-of-custody protocols. The survey was performed under Standard Agreement No. 18343-A, Task Order No. 26, dated March 14, 2023, with the report completed on June 27, 2023.
The survey results documented findings of asbestos-containing materials in various building components, with laboratory analysis conducted using EPA Test Method 600/R-93/116 (polarized light microscopy) performed by EMSL Analytical, Inc., an NIST-NVLAP accredited laboratory. Lead paint samples were analyzed by Asset Laboratories using EPA Test Method 6010B. The investigation identified regulatory considerations under 40 CFR 61 Subpart M (NESHAP), Title 8 California Code of Regulations Section 1529 (Cal/OSHA asbestos standard), and Title 8 CCR Section 1532.1 (Cal/OSHA lead standard). The report distinguished between friable and nonfriable ACM materials, evaluated paint deterioration conditions, and provided waste characterization guidance for hazardous material management. The scope excluded evaluation of lead-based paint hazards per HUD guidelines and architectural drawings were not available for consultant review.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Project_Manual_15364.pdf | ||
| Bid_Package_15364.pdf | ||
| Drawings_15364.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LIMITED ASBESTOS AND
LEAD-CONTAINING PAINT
SURVEY REPORT
Diagnostic Center Central California 1818 West Ashlan Avenue
Fresno, California
Project No. S2170-07-26 June 27, 2023
Edgar Reyes, Associate Architect Department of General Services Real Estate Services Division Project Management and Development Branch – Environmental Section 707 3rd Street, 4th Floor West Sacramento, California 95605
Subject: LIMITED ASBESTOS AND LEAD-CONTAINING PAINT SURVEY REPORT
DIAGNOSTIC CENTER CENTRAL CALIFORNIA
1818 WEST ASHLAN AVENUE, FRESNO, CALIFORNIA
PROJECT NO. 00000 00000 09003
STANDARD AGREEMENT NO. 18343-A, TASK ORDER NO. 26
Mr. Reyes:
In accordance with your request, Geocon Consultants, Inc. has conducted a limited asbestos and lead-containing paint (LCP) survey of designated renovation areas at the Diagnostic Center of Central California (the Site) at 1818 West Ashlan Avenue in Fresno, Fresno County, California. We performed our services to provide information regarding the potential for asbestos and lead at the Site prior to planned renovation activities.
Our scope of services included a limited survey of the Site for suspect asbestos-containing materials and potential LCP, collecting bulk samples, and submitting the samples to laboratories for analyses.
The limited survey included exterior areas (excluding the roofs), the restroom in Wing B, the restroom walls in the restroom in Wing C, the boiler room in Wing E, and interior painted door trim in Wing G.
The accompanying report summarizes the services performed and the results of laboratory analyses.
We appreciate the opportunity to provide our services to the Department of General Services on this project. Please contact us if you have any questions concerning this report, or if we may be of further service.
Respectfully Submitted, GEOCON CONSULTANTS, INC.
Matthew Alberti, CAC (No. 17-5996) Project Scientist
TABLE OF CONTENTS
ASBESTOS AND LEAD-CONTAINING PAINT SURVEY REPORT PAGE
1.0 INTRODUCTION
1.1 Site Description and Location
2.0 REGULATORY BACKGROUND
2.1 Asbestos
2.2 Lead
2.3 Architectural Drawings
3.0 SCOPE OF SERVICES
3.1 Asbestos
3.2 Lead
4.0 INVESTIGATIVE RESULTS
4.1 Asbestos
4.1.1 Exterior of Wings A, B, E and G
4.1.2 Wing B – Restroom (interior)
4.1.3 Wing C – IT Restroom (exterior walls and wall cavities)
4.1.4 Wing E – Boiler Room (interior)
4.2 Lead
4.2.1 Exterior of Wings A, B, C, E and G
4.2.2 Interior of Wings B, E and G
5.0 CONCLUSIONS AND RECOMMENDATIONS
5.1 Asbestos
5.2 Lead
6.0 REPORT LIMITATIONS
FIGURES
1. Vicinity Map
2. Site Plan – Exterior and Wings B and G
3. Site Plan – Boiler Room
SITE PHOTOGRAPHS (1 through 15)
TABLES
1. Summary of Analytical Laboratory Results – Asbestos
2. Summary of Analytical Laboratory Results – Paint
APPENDICES
A. Personnel Certifications B. Laboratory Reports and Chain-of-custody Documentation
Geocon Project No. S2170-07-26 - 1 - June 27, 2023
ABESTOS AND LEAD-CONTAINING PAINT SURVEY REPORT
1.0 INTRODUCTION
Geocon Consultants, Inc. (Geocon) has performed a limited asbestos and lead-containing paint (LCP) survey of designated renovation areas at the Diagnostic Center of Central California (the Site) at 1818 West Ashlan Avenue in Fresno, Fresno County, California, as described herein, for the Department of General Services (DGS) in accordance with Standard Agreement No. 18343-A, Task Order No. 26, dated March 14, 2023.
1.1 Site Description and Location
Designated renovation areas at the Site included in the limited asbestos and LCP survey consisted of the following:
• Wing A – an approximate 7,500-square-foot, single-story, wood-frame structure with asphalt roof (exterior walls, windows and doors);
• Wing B – an approximate 7,500-square-foot, single-story, wood-frame structure with asphalt roof (interior restroom and exterior walls, windows and doors);
• Wing C – an approximate 1,200-square-foot, single-story, wood-frame structure with built-up asphalt roof (Exterior walls and wall cavity);
• Wing E – an approximate 4,000-square-foot, single-story, wood-frame structure with asphalt roof (interior of boiler room and exterior walls); and
• Wing G – an approximate 5,500-square-foot, single-story, wood-frame structure with asphalt roof (interior brown painted wood door trim).
The approximate site location is depicted on the Vicinity Map, Figure 1. The site structures are depicted on the Site Plans (Figures 2 and 3) and shown in the attached photographs.
1.2 Purpose and Objectives
The purpose of our scope of services was to perform a limited survey for the potential presence and quantity of asbestos and LCP at the Site prior to planned renovation activities in designated areas.
The objectives of the limited asbestos and LCP survey were to collect representative samples of building materials at the Site to determine their asbestos and lead content so these materials may be managed and disposed of appropriately and to minimize impacts to the health of construction workers and the public during renovation activities.
The information obtained from this investigation will be used by the DGS for waste profiling, determining California Occupational Safety and Health Administration (Cal/OSHA) applicability, and coordinating hazard materials disturbance activities.
It was not Geocon’s intent during this inspection to conduct an evaluation of lead-based paint hazards in accordance with United States Department of Housing and Urban Development (HUD) guidelines.
Geocon Project No. S2170-07-26 - 2 - June 27, 2023
2.0 REGULATORY BACKGROUND
2.1 Asbestos
The Code of Federal Regulations (CFR), 40 CFR 61, Subpart M, National Emissions Standards for Hazardous Air Pollutants (NESHAP) and Federal Occupational Safety and Health Administration (FED OSHA) classify asbestos-containing material (ACM) as any material or product that contains more than 1% asbestos. Nonfriable ACM is classified by NESHAP as either Category I or Category II material defined as follows:
• Category I – asbestos-containing packings, gaskets, resilient floor coverings, and asphalt roofing products.
• Category II – all remaining types of nonfriable ACM not included in Category I that when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure.
Regulated asbestos-containing material (RACM), a California hazardous waste when friable, is classified as any manufactured material that contains greater than 1% asbestos by dry weight and is:
• Friable; or
• Category I material that has become friable; or
• Category I material that has been subjected to sanding, grinding, cutting or abrading; or
• Category II nonfriable material that has a high probability of becoming crumbled, pulverized, or reduced to a powder during demolition or renovation.
Activities that disturb materials containing any amount of asbestos are subject to certain requirements of the Cal/OSHA asbestos standard in Title 8, California Code of Regulations (CCR) §1529. Typically, removal or disturbance of more than 100 square feet of material containing more than 0.1% asbestos must be performed by a registered asbestos abatement contractor, but associated waste labeling is not required if the material contains 1% or less asbestos. When the asbestos content of a material exceeds 1%, virtually all requirements of the standard become effective.
Materials containing more than 1% asbestos are also subject to NESHAP regulations (40 CFR Part 61, Subpart M). RACM (friable ACM and nonfriable ACM that will become friable during demolition or renovation operations) must be removed from buildings prior to demolition or renovation. Contractors are responsible for segregating and characterizing waste streams prior to disposal.
With respect to potential worker exposure, notification, and registration requirements, Cal/OSHA defines asbestos-containing construction material (ACCM) as construction material that contains more than 0.1% asbestos (Title 8, CCR 341.6).
Geocon Project No. S2170-07-26 - 3 - June 27, 2023
2.2 Lead
Construction activities (including demolition) that disturb materials or paints containing any amount of lead are subject to certain requirements of the Cal/OSHA lead standard in Title 8, CCR, §1532.1. Deteriorated paint is defined by Title 17, CCR, Division 1, Chapter 8, §35022 as a surface coating that is cracking, chalking, flaking, chipping, peeling, non-intact, failed, or otherwise separating from a component.
Demolition of a deteriorated LCP component would require waste characterization and appropriate disposal.
Intact LCP on a component is currently accepted by most landfills and recycling facilities; however, contractors are responsible for segregating and characterizing waste streams prior to disposal.
For a solid waste containing lead, the waste is classified as California hazardous when: 1) the representative total lead content equals or exceeds the respective Total Threshold Limit Concentration (TTLC) of 1,000 milligrams per kilogram (mg/kg); or 2) the representative soluble lead content equals or exceeds the respective Soluble Threshold Limit Concentration (STLC) of 5 milligrams per liter (mg/l) based on the standard Waste Extraction Test (WET). The soluble lead concentration of a waste has the potential to exceed the lead STLC when the waste’s representative total lead concentration is greater than or equal to 10 times the respective STLC value since the WET uses a 1:10 dilution ratio. Hence, when total lead is detected at a concentration greater than or equal to 50 mg/kg, and assuming that 100 percent of the total lead is soluble, soluble lead analysis is warranted.
Lead-containing waste is classified as “Resource, Conservation, and Recovery Act” (RCRA) hazardous, or Federal hazardous, when its soluble lead concentration equals or exceeds the Federal regulatory level of 5 mg/l based on the Toxicity Characteristic Leaching Procedure (TCLP).
The above regulatory criteria are based on chemical concentrations. Wastes may also be classified as hazardous based on other criteria such as ignitability; however, for the purposes of this investigation, toxicity (i.e., lead concentrations) is the primary factor considered for waste classification since waste generated during the construction activities would not likely warrant testing for ignitability or other criteria. Waste that is classified as either California hazardous or RCRA hazardous requires management as a hazardous waste.
Potential hazards exist to workers who remove or cut through LCP coatings during demolition. Dust containing hazardous concentrations of lead may be generated during scraping or cutting materials coated with lead-containing paint. Torching of these materials may produce lead oxide fumes.
Therefore, air monitoring and/or respiratory protection may be required during the demolition of materials coated with LCP. Guidelines regarding regulatory provisions for construction work where workers may be exposed to lead are in the Title 8, CCR, §1532.1.
2.3 Architectural Drawings
Detailed structure architectural plans and copies of prior asbestos and LCP survey reports for the Site were not available for our review.
Geocon Project No. S2170-07-26 - 4 - June 27, 2023
3.0 SCOPE OF SERVICES
Matt Alberti performed the asbestos and LCP survey at the Site on March 29th and March 30th, 2023.
Mr. Alberti is a California-Certified Asbestos Consultant (CAC), Certification Number 17-5996 (expiration August 16, 2023), and California Department of Public Health (CDPH) Certified Lead Paint Inspector/Assessor, Certification Number LRC-6569 (expiration September 28, 2023). Copies of Mr. Alberti’s Cal/OSHA and CDPH certification cards are in Appendix A.
3.1 Asbestos
We grouped suspect ACM into homogeneous areas with representative samples randomly collected from each area. In addition, we evaluated each potential ACM for quantity and friability. We collected 59 bulk asbestos samples representing 22 material types at the Site.
Our procedures for inspection and sampling included:
• Collecting bulk asbestos samples after first wetting friable material with a mist of water. We then cut representative samples from the substrates and transferred them to labeled containers.
Note that when we collected multiple samples, we distributed the sampling locations throughout the homogeneous area (spaces where we observed the materials).
• Relinquishing bulk asbestos samples under chain-of-custody protocol to EMSL Analytical, Inc.
(EMSL), a California-licensed laboratory, for asbestos analysis in accordance with Environmental Protection Agency (EPA) Test Method 600/R-93/116 using polarized light microscopy (PLM) procedures. EMSL is accredited by the National Institute of Standards and Technology National Voluntary Laboratory Accreditation Program (NIST-NVLAP) (NVLAVP No. 101048-3) for bulk asbestos fiber analysis. We requested the laboratory analyses on a 5-day turnaround time.
Sample locations are depicted on Figures 2 and 3. Geocon sample group identification numbers, material descriptions, locations, approximate quantities, friability assessments, and photo references are summarized in Table 1. Materials represented by the samples collected are shown in the attached photographs.
3.2 Lead
We collected five discrete bulk samples of suspect LCP and two composite bulk samples of suspect LCP during our survey. We collected composite bulk samples of suspect LCP from teal paint on exterior wood window and door components. Our sampling procedures included:
• Collecting representative bulk samples of suspect LCP using techniques presented in HUD guidelines. In addition, we evaluated each painted area for evidence of deterioration such as flaking or cracking.
Geocon Project No. S2170-07-26 - 5 - June 27, 2023
• Relinquishing suspect LCP samples under chain-of-custody to Asset Laboratories. (Asset), a California and Nevada-licensed laboratory, for lead analyses in accordance with EPA Test Method 6010B. Asset is accredited by the California State Water Resources Control Board (SWRCB) under the Environmental Laboratory Accreditation Program (ELAP) for lead analysis. We requested the laboratory analyses on 5-day turnaround time.
Sample locations are depicted on Figures 2 and 3. Geocon paint sample identification numbers, descriptions, locations, and photo references are summarized in Table 2. Materials represented by the samples collected are shown in the attached photographs.
Geocon Project No. S2170-07-26 - 6 - June 27, 2023
4.0 INVESTIGATIVE RESULTS
This section presents the results of field observations and laboratory analysis of samples for asbestos and lead content.
4.1 Asbestos
4.1.1 Exterior of Wings A, B, E and G
Exterior of Wings A, B, E and G Fresno DCC
Summary of Positive Asbestos Analysis Results Polarized Light Microscopy (PLM) - USEPA Test Method 600/R-93/116
Sample Group
No.
Description of Material Approximate
Quantity 1 Friable Asbestos Content 2
USEPA
Category
1818-4 Tan stucco 2,500 square feet No <0.25 to 0.25%* NA
USEPA –United States Environmental Protection Agency 1 - Quantities of ACM listed are approximate. Contractors are responsible for field verifying field site conditions and actual
ACM quantities prior to abatement 2 - Identified asbestos is the chrysotile variety unless otherwise indicated < - Less than NA = Not applicable
* - The concentration of chrysotile asbestos was determined to be <0.25% by 400-point-count PLM analysis
With the exception of the sample analysis results listed above, asbestos was not detected in the remaining representative samples of suspect materials collected from the exterior of Wings A, B, E and G structures during the survey.
4.1.2 Wing B – Restroom (interior)
Wing B – Restroom (interior) Fresno DCC
Summary of Positive Asbestos Analysis Results Polarized Light Microscopy (PLM) - USEPA Test Method 600/R-93/116
Sample Group
No.
Description of Material Approximate
Quantity 1 Friable Asbestos Content 2
USEPA
Category
1818-17 Plaster 200 square feet Yes
<2to 4% Chrysotile (black wall mastic) 2% Amosite and 4% Chrysotile
(wall insulation) ND (plaster)
RACM
USEPA –United States Environmental Protection Agency 1 - Quantities of ACM listed are approximate. Contractors are responsible for field verifying field site conditions and actual
ACM quantities prior to abatement 2 - Identified asbestos is the chrysotile variety unless otherwise indicated RACM – Regulated Asbestos-Containing Material
Geocon Project No. S2170-07-26 - 7 - June 27, 2023
With the exception of the sample analysis results listed above, asbestos was not detected in the remaining representative samples of suspect materials collected from the interior of the restroom in Wing B during the survey.
4.1.3 Wing C – IT Restroom (exterior walls and wall cavities)
Asbestos was not detected in the representative samples of suspect materials collected from the IT Restroom (exterior walls and wall cavities) in Wing C during the survey.
4.1.4 Wing E – Boiler Room (interior)
Wing E – Boiler Room (interior) Fresno DCC
Summary of Positive Asbestos Analysis Results Polarized Light Microscopy (PLM) - USEPA Test Method 600/R-93/116
Sample Group
No.
Description of Material Approximate
Quantity 1 Friable Asbestos Content 2
USEPA
Category
1818-5 Silver cloth-like gasket 5 square feet No 65 to 75% Category I Nonfriable
1818-11 Multicolor debris (interior and at exhaust of boiler) 5 square feet Yes 8 to 12% RACM
1818-12 White boiler hatch mastic 1 square foot No *<1% Category I Nonfriable
1818-14 White TSI and brown cap at northwest corner floor 2 linear feet Yes
4 to 7% Amosite (white TSI)
7 to 8% (brown cap)
RACM
Not sampled
Asbestos labeled TSI elbows and fittings above boiler unit 5 linear feet Yes Assumed ACM RACM
Not sampled
Asphalt roof shingle system and roof mastics 800 square feet No Assumed ACM Category I
Nonfriable USEPA –United States Environmental Protection Agency 1 - Quantities of ACM listed are approximate. Contractors are responsible for field verifying field site conditions and actual
ACM quantities prior to abatement 2 - Identified asbestos is the chrysotile variety unless otherwise indicated < - Less than TSI – Thermal System Insulation
* - Insufficient sample volume for 400-point-count PLM analysis
With the exception of the sample analysis results listed above, asbestos was not detected in the remaining representative samples of suspect materials collected from the interior of the boiler room in Wing E during the survey.
A summary of the analytical laboratory test results for asbestos is in Table 1. Reproductions of the laboratory reports and chain-of-custody documentation are in Appendix B.
Geocon Project No. S2170-07-26 - 8 - June 27, 2023
4.2 Lead
4.2.1 Exterior of Wings A, B, C, E and G
The composite sample representing approximately 25 square feet of deteriorated teal exterior paint applied to wood door components exhibited a representative total lead concentration of 55 mg/kg and a representative WET soluble lead concentration of 3.1 mg/l.
The composite sample representing approximately 20 square feet of deteriorated teal exterior paint applied to wood window components exhibited a representative total lead concentration of 19 mg/kg.
The sample representing approximately 100 square feet of deteriorated tan exterior paint applied to stucco walls exhibited a representative total lead concentration of 14 mg/kg.
The sample representing approximately 100 square feet of deteriorated tan exterior paint applied to wood walls exhibited a representative total lead concentration of 12 mg/kg.
4.2.2 Interior of Wings B, E and G
The sample representing approximately 2 square feet of deteriorated brown interior paint applied to wood door components of Wing G exhibited a representative total lead concentration of 39 mg/kg.
The sample representing intact white interior paint applied to the interior walls of Wings B and E exhibited a representative total lead concentration of 3.0 mg/kg.
The sample representing intact silver interior paint applied to the boiler unit in Wing E exhibited a representative total lead concentration of 70 mg/kg and a representative WET soluble lead concentration of 0.63 mg/l.
A summary of the analytical laboratory test results for paint is presented in Table 2. Reproductions of the laboratory reports and chain-of-custody documentation are presented in Appendix B.
Geocon Project No. S2170-07-26 - 9 - June 27, 2023
5.0 CONCLUSIONS AND RECOMMENDATIONS
5.1 Asbestos
NESHAP and San Joaquin Valley Air Pollution Control District (SJVAPCD) regulations require that the friable asbestos-containing TSI (pipe elbows, fittings and capped pipe lagging at floor) and multicolored boiler debris (inside boiler unit in the Boiler Room of Wing E); and the plaster wall system (Restroom in Wing B) which represents RACM (California hazardous waste) identified during our asbestos survey be removed prior to renovation or demolition activities that would disturb these materials. The removal of these materials must be performed by a licensed asbestos abatement contractor registered with Cal/OSHA.
NESHAP and SJVAPCD regulations do not require that the gaskets, mastics and asphalt roof materials (Category I nonfriable/nonhazardous material) identified during our survey in the Boiler Room (Wing E) be removed prior to demolition/renovation or be treated as a hazardous waste. However, activities causing disturbance of the material (i.e., cutting, abrading, sanding, grinding, etc…) would require compliance with the Cal/OSHA asbestos standard (Title 8, CCR §1529).
NESHAP and SJVAPCD regulations do not require that materials containing 1% or less asbestos (i.e., exterior stucco) identified during our survey be removed prior to disturbance activities associated with renovation or demolition. However, the disturbance of these materials is still covered by the Cal/OSHA asbestos standard (Title 8, CCR §1529). We recommend that a licensed contractor who is registered with Cal/OSHA for asbestos-related work perform disturbance activities associated with renovation or demolition.
We also recommend the notification of contractors (that may be conducting renovation, demolition, or related activities) and building occupants of the presence of asbestos in their work areas (i.e., provide the contractor[s] and building occupants with a copy of this report and a list of asbestos removed by contractor[s] during subsequent activities). Personnel not trained for asbestos work should be instructed not to disturb asbestos.
In accordance with NESHAP, written notification to SJVAPCD is required ten working days prior to commencement of any demolition activity (whether asbestos is present or not). In accordance with Title 8, CCR 341.9, written notification to the nearest Cal/OSHA district office is required at least 24 hours prior to certain asbestos-related work.
5.2 Lead
The representative samples collected of intact and deteriorated paints identified during our survey would not be classified as California or Federal hazardous waste based on lead content.
Geocon Project No. S2170-07-26 - 10 - June 27, 2023
We recommend that all paints at the project site be treated as lead-containing for the purpose of determining the applicability of the Cal/OSHA lead standard during maintenance, renovation, and demolition activities. This recommendation is based on the paint sample results and the fact that lead was a common ingredient of paints manufactured before 1978 and is still an ingredient of some paints.
In accordance with Title 8, CCR, §1532.1(p), written notification to the nearest Cal/OSHA district office is required at least 24 hours prior to certain lead-related work. Compliance and training requirements regarding construction activities where workers may be exposed to lead are presented in Title 8, CCR, §1532.1, subsections (e) and (l), respectively. The removal, transportation, placement, handling, and disposal of LCP must result in no visible dust.
Geocon Project No. S2170-07-26 - 11 - June 27, 2023
6.0 REPORT LIMITATIONS
This report has been prepared exclusively for the DGS. The information contained herein is valid as of the date of the report and will require an update to reflect additional information obtained.
The limited asbestos and LCP survey was conducted in conformance with generally accepted standards of practice for identifying and evaluating asbestos and LCP in structures. The limited survey addressed only the site structures and features identified in Section 1.1. Due to the nature of structure surveys, asbestos and LCP use, and laboratory analytical limitations, some asbestos and deteriorated LCP at the Site may not have been identified. Spaces, such as cavities, crawlspaces, voids, and pipe chases, may have been concealed to our investigator. Previous retrofit/rehabilitation work may have concealed or covered spaces or materials, or may have partially demolished materials and left debris in inaccessible areas. Additionally, retrofit/rehabilitation activities may have partially replaced asbestos with indistinguishable non-asbestos. Asbestos and LCP may exist in areas not accessible or sampled in conjunction with our scope of services.
During demolition operations, suspect materials may be uncovered which are different from those accessible for sampling during this assessment. Personnel in charge of demolition should be alerted to note materials uncovered during such activities that differ substantially from those included in this or previous assessment reports. If additional suspect materials are found, they should be treated as asbestos and lead-containing materials until/unless sampling and analysis indicate otherwise.
This report is not a comprehensive site characterization and should not be construed as such. The findings as presented in this report are predicated on the results of the limited sampling and laboratory testing performed. In addition, the information obtained is not intended to address potential impacts related to sources other than those specified herein. Therefore, the report should be deemed conclusive with respect to only the information obtained. We make no warranty with respect to the content of this report or subsequent reports, correspondence, or consultation. Geocon strove to perform the services summarized herein in accordance with the local standard of care in the geographic region at the time the services were rendered.
The contents of this report reflect the views of the author who is responsible for the facts and accuracy of the data presented herein. This report does not constitute a standard, specification, or regulation.
PROJECT
LIMITS
ASHLAN AVENUE
DAKOTA AVENUE
SH IELDS AVENUE
CLINTON AVENUE
MCKINLEY AVENUE
SHAW AVENUE
BARSTOW AVENUE
OLIVE AVENUE
BULLARD AVENUE
SI ERRA AVENUE
HERNDON AVENUE
H U
G H
E S
A V
E N
U E
M A
R K
S A
V E
N U
E
B R
A W
L E
Y A
V E
N U
E
W E
S T
A V
E N
U E
F R
U
IT
A V
E N
U E
B L
A C
K S
T O
N E
A V
E N
U E
P A
L M
A V
E N
U E
M A
R O
A A
V E
N U
E
V A
L E
N T
IN
E
A V
E N
U E
B
LY
T H
E A
V E
N U
E
C O
R N
E L
IA
A
V E
N U
E
CONSULTANTS, INC.
3 1 6 0 G O LD VA LLE Y D R - SU IT E 8 0 0 - R A N C H O C O R D O VA , C A 9 5 7 4 2
PH O N E 9 1 6 . 8 5 2 . 9 1 1 8 - FA X 9 1 6 . 8 5 2 . 9 1 3 2
Figure 1June 2023S2170-07-26
VICINITY MAP
1818 West Ashlan Avenue Fresno, California
Diagnostic Center Central California
GE
OC
ON
6/
/2
3 U
SE
R B row n M
PA
TH
C:
\U se rs\
Br ow n M \O ne Dr ive
- G eo co n, Inc
\G
IS_
Gr ap hic s\
Pro jec ts\ S2
0-0
7-2 6_
Dia gn os tic
Ce nte r_F res no \0
1_ Re po rtM ap s\
Fig ure
_1 _V icin ity
_M ap
.m xd
0 1
Scale in Miles
N
SACRAMENTO
SAN FRANCISCO
LOS ANGELES
SAN DIEGO
PROJECT
LOCATION
PROJECT
SITE
N
Not to Scale
C :\U se rs
\B ro w n
M \O ne D riv e
- G eo co n, In c\
G
IS
_G ra ph ic s\ Pr oj ec ts \S
-0 7-
_D ia gn os tic
C en te r_
Fr es no \0
1_ R ep or tM ap s\ Fi gu re
_2 _S ite _P la n_
Ex te rio r.a i
SITE PLAN - EXTERIOR AND WINGS B AND G
June 2023 Figure 2S2170-07-26
P H O N E 9 1 6 . 8 5 2 . 9 11 8 – FA X 9 1 6 . 8 5 2 . 9 1 3 2
3 1 6 0 G O L D VA L L E Y D R – S U I T E 8 0 0 – R A N C H O C O R D O VA , C A 9 5 7 4 2
Basemap: CA Dept of General Services
Diagnostic Center Central California 1818 West Ashlan Avenue
Fresno, California
Approximate Bulk Sample Location (Asbestos Analysis)
Approximate Paint Sample Location (Lead Analysis)
LEGEND:
WING F
WING C
(IT RM)
WING A
WING GWING B
WING E
WING D
COURTYARD
BOILER
RM
RESTROOM
1818-4B
1818-P1B 1818-P2B 1818-P3B 1818-P4
1818-2A
1818-3A 1818-3B1818-1A 1818-2B
1818-2C 1818-4A 1818-2D 1818-1B
1818-19A 1818-19B 1818-20A 1818-20B 1818-21A 1818-21B 1818-21C 1818-22A 1818-22B 1818-22C
1818-4E
1818-2E 1818-1C
1818-4D1818-4C
1818-15A 1818-15B 1818-16A 1818-16B 1818-17A 1818-17B 1818-17C 1818-18A 1818-18B 1818-18C
1818-P2A 1818-P1A
1818-P7
1818-P3A
25’ - 6”
6’
0”
(E) DRINKING
FOUNTAIN
(E) ELECTRICAL
PANE
(E) FIXED EQUIP.
(E) FLOOR DRAIN
(E) FIXED EQUIP.
(E) PANLE
(E) COMM.
EQUIPMENT
(E) ELECTRICAL
PANE
N
Not to Scale
C :\U se rs
\B ro w n
M \O ne D riv e
- G eo co n, In c\
G
IS
_G ra ph ic s\ Pr oj ec ts \S
-0 7-
_D ia gn os tic
C en te r_
Fr es no \0
1_ R ep or tM ap s\ Fi gu re
_3 _S ite _P la n_
Bo ile r_ R oo m
.a i
SITE PLAN - BOILER ROOM
June 2023 Figure 3S2170-07-26
P H O N E 9 1 6 . 8 5 2 . 9 11 8 – FA X 9 1 6 . 8 5 2 . 9 1 3 2
3 1 6 0 G O L D VA L L E Y D R – S U I T E 8 0 0 – R A N C H O C O R D O VA , C A 9 5 7 4 2
Basemap: CA Dept of General Services
Diagnostic Center Central California 1818 West Ashlan Avenue
Fresno, California
Approximate Bulk Sample Location (Asbestos Analysis)
Approximate Paint Sample Location (Lead Analysis)
LEGEND:
BOILER
1818-14A 1818-14B
1818-P61818-7B
1818-11A 1818-11B 1818-11C
1818-10A 1818-10B
1818-12A 1818-12B
1818-7A
1818-13C
1818-8A
1818-8B
1818-6A
1818-9B
1818-13A 1818-13B
1818-6B
1818-9A
1818-7C 1818-8C
1818-P5
1818-5B
1818-5A
Photo 1 – Diagnostic Center Central California (DCC), 1818 West Ashlan Avenue, Fresno, San Joaquin County, California
Photo 2 – DCC “Wing B” exterior asbestos-containing stucco and lead-containing tan and teal paint
Photo 3 – DCC “Wing B” deteriorated tan lead-containing paint on wood and stucco
PHOTOGRAPHS 1, 2, & 3
Diagnostic Center Central California
1818 West Ashlan Avenue Fresno, San Joaquin County, California
S2170-07-26 June 2023
Photo 4 – DCC “Wing B” deteriorated lead-containing teal paint applied to window sill
Photo 5 – DCC “Wing E” non-asbestos-containing concrete and silver boiler paint in boiler room
Photo 6 – DCC “Wing E” asbestos-containing debris inside exhaust area of boiler
PHOTOGRAPHS 4, 5, & 6
Diagnostic Center Central California
1818 West Ashlan Avenue
Photo 7 –DCC “Wing E” asbestos-containing silver gasket on boiler
Photo 8 – DCC “Wing E” non-asbestos-containing tan 10” OD gasket on boiler
Photo 9 – DCC “Wing E” asbestos-containing white mastic on boiler hatch
PHOTOGRAPHS 7, 8, & 9
Diagnostic Center Central California
1818 West Ashlan Avenue
Photo 10 – DCC “Wing E” asbestos-containing pipe insulation with brown cap on floor in boiler room
Photo 11 – DCC “Wing E” labeled asbestos-containing TSI on elbows and fittings on boiler pipes
Photo 12 – DCC “Wing G” deteriorated lead-containing brown paint on wood door trim
PHOTOGRAPHS 10, 11, & 12
Diagnostic Center Central California
1818 West Ashlan Avenue
Photo 13 – DCC “Wing B” asbestos-containing plaster wall and ceiling system in restroom
Photo 14 – DCC “Wing C” non-asbestos-containing HVAC duct tape on exterior of the IT Room
Photo 15 – DCC “Wing C” deteriorated lead-containing white paint on wood siding and non-asbestos-containing vapor barrier, fiberglass insulation and wall plaster on exterior of the IT Room
PHOTOGRAPHS 13, 14, & 15
Diagnostic Center Central California 1818 West Ashlan Avenue
Geocon Project No. S2170-07-26
Sample Group Nos. Material Description Location Approximate Quantity 1 Friable Site Photos
Asbestos Content 2
USEPA
Category
Exterior - Wings A, B, E and G 1818-1A to 1C Teal paint Window sills and door trims 900 square feet NA 2 & 4 ND NA 1818-2A to 2E Tan paint Walls 150 square feet NA 1 to 4 ND NA 1818-3A/3B Concrete Slab 150 square feet NA 1 to 3 ND NA
1818-4A to 4E Stucco Walls 2,500 square feet No 1 to 4 *<0.25 to 0.25% NA Wing E - Boiler Room (Interior)
1818-5A/5B Silver/tan, cloth-like gasket Boiler end caps 5 square feet No 7 65 to 75% Category I Nonfriable
1818-6A/6B Concrete Slab 400 square feet NA 5 & 10 ND NA 1818-7A to 7C White textured paint Walls 400 square feet NA 5 & 10 ND NA 1818-8A to 8C Gypsum board system Walls 950 square feet NA 5 ND NA
1818-9A/9B Brown mastic associated with 4" baseboard Walls 25 square feet NA 10 ND NA
1818-10A/10B Black/tan 10" OD gasket Boiler pipes 5 square feet NA 8 ND NA
1818-11A to 11C Multicolored debris North side of boiler 5 square feet Yes 6 8 to 12%
(vapor barrier) ND (debris)
RACM
1818-12A/12B White mastic West side of boiler at hatch 1 square feet No 9 <1% Category I Nonfriable
1818-13A to 13C Silver paint Boiler 150 square feet NA 5, 7, 8 & 9 ND NA
1818-14A/14B White TSI and brown cap material
Northwest corner of room at floor pipes 2 linear feet Yes 10
4 to 7% Amosite (white
TSI)
7 to 8%
(brown cap)
RACM
No sample collected
TSI elbows and fittings (labeled asbestos-containing)
Above boiler at pipe elbows and fittings 5 linear feet Yes 11 Assumed ACM RACM
No sample collected ARS, tar and mastic Boiler room roof 400 square feet No NP Assumed ACM Category I
Nonfriable Wing B - Restroom (Interior)
1818-15A/15B Blue linoleum and tan mastic Floor 20 square feet NA 13 ND NA
1818-16A/16B Tan/brown mastic associated with 6" blue baseboard Walls 10 square feet NA 13 ND NA
Polarized Light Microscopy (PLM) - EPA Test Method 660/R-93/116
TABLE 1
SUMMARY OF ANALYTICAL LABORATORY RESULTS - ASBESTOS
1818 WEST ASHLAN AVENUE, FRESNO, CALIFORNIA
DIAGNOSTIC CENTER CENTRAL CALIFORNIA
Sample Group Nos. Material Description Location Approximate Quantity 1 Friable Site Photos
Asbestos Content 2
USEPA
Category
Polarized Light Microscopy (PLM) - EPA Test Method 660/R-93/116
TABLE 1
SUMMARY OF ANALYTICAL LABORATORY RESULTS - ASBESTOS
1818 WEST ASHLAN AVENUE, FRESNO, CALIFORNIA
DIAGNOSTIC CENTER CENTRAL CALIFORNIA
1818-17A to 17C Plaster Walls 200 square feet Yes 13
ND (plaster) 2 to 4% (black mastic) 2% Amosite and 4% Chrysotile
(white insulation)
RACM
1818-18A to 18C Texture Walls 200 square feet NA 13 ND NA Wing C - IT Room
1818-19A/19B Tan vapor barrier Exterior walls 200 square feet NA 15 ND NA 1818-20A/20B White HVAC tape Exterior HVAC ducting 50 square feet NA 14 ND NA
1818-21A to 21C White paint Exterior walls 200 square feet NA 14 & 15 ND NA 1818-22A to 22C Plaster Interior restroom walls 200 square feet NA 15 ND NA
Notes:
USEPA = United States Environmental Protection Agency
NA = Not applicable ND = Asbestos fibers not detected NP = No photograph TSI = Thermal system insulation
ARS = Asphalt roofing shingles HVAC = Heating,ventillation, and air conditioning ACM = Asbestos-Containing Material (>1%)
RACM = Regulated Asbestos-Containing Material < = Less than > = Greater than
* = Verified by 400-point count polarized light microscopy 1 = Quantities of ACM listed are approximate. Contractors are responsible for field verifying field site conditions and actual ACM quantities prior to abatement of ACMs.
2 = Identified asbestos is the chrysotile variety unless otherwise indicated
Sample No. Description Location Approximate Quantity
Peeling/Flaking Site Photos Total Lead
(mg/kg) WET Lead (mg/l)
Exterior - Wings A, B, C, E and G 1818-P1A/B Teal exterior paint Wood door casing/trims 25 square feet 2 55 3.1 1818-P2A/B Teal exterior paint Wood window sills 20 square feet 4 19 ---
1818-P3 Tan exterior paint Stucco walls 100 square feet 1 to 4 14 --- 1818-P7 White exterior paint Wood siding 100 square feet 14 & 15 12 ---
1818-P4 Brown interior paint Wood door casing/trims (Wing G) 2 square feet 12 39 ---
1818-P5 White interior paint Walls Intact 5, 10 & 13 3.0 --- 1818-P6 Silver interior paint Boiler steel housing Intact 5, 7, 8 & 9 70 0.63
Notes:
mg/kg = milligrams per kilogram (EPA Test Method 6010B) WET = Waste Extraction Test mg/l = milligrams per liter (EPA Test Method 6010B)
--- = not analyzed
Interior - Wings B, E and G
TABLE 2
SUMMARY OF ANALYTICAL LABORATORY RESULTS - PAINT
DIAGNOSTIC CENTER CENTRAL CALIFORNIA
1818 WEST ASHLAN AVENUE, FRESNO, CALIFORNIA
Total and Soluble Lead
APPENDIX A
STATE OF CALIFORNIA
DEPARTMENT OF PUBLIC HEALTH
LEAD-RELATED CONSTRUCTION CERTIFICATE
Disclaimer: This document alone should not be relied upon to confirm certification status. Compare the individual’s photo and name to another valid form of government issued photo identification. Verify the individual’s certification status by searching for Lead-Related Construction Professionals at www.cdph.ca.gov/programs/clppb or calling (800) 597-LEAD
INDIVIDUAL: CERTIFICATE TYPE: NUMBER: EXPIRATION DATE:
Lead Inspector/Assessor LRC-00006569 9/28/2023
Matthew Alberti
APPENDIX B
EMSL Analytical, Inc.
464 McCormick Street San Leandro, CA 94577
Tel/Fax: (510) 895-3675 / (510) 895-3680 http://www.EMSL.com / sanleandrolab@emsl.com
092307343EMSL Order:
Customer ID: GECN80
Customer PO: S2170-07-26
Project ID:
Attention: Phone:Chris Giuntoli (775) 685-6116
Fax:Geocon Consultants, Inc. (916) 852-9132
Received Date:3160 Gold Valley Drive 03/31/2023 9:00 AM
Analysis Date:Suite 800 04/07/2023
Collected Date:Rancho Cordova, CA 95742 03/29/2023 - 03/30/2023
Project: FRESNO DCC / S2170-07-26
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
1818-1A
092307343-0001
None DetectedMatrix
Non-fibrous (Other)
80%
10%
Cellulose10%Brown/Green
Fibrous
Heterogeneous
TEAL PAINT
Result includes a small amount of inseparable attached material
1818-1B
092307343-0002
None DetectedMatrix
Non-fibrous (Other)
80%
10%
Cellulose10%Brown/Green
Fibrous
Heterogeneous
TEAL PAINT
Result includes a small amount of inseparable attached material
1818-1C
092307343-0003
None DetectedMatrix
Non-fibrous (Other)
65%
35%
Tan/Green
Non-Fibrous
Homogeneous
TEAL PAINT
1818-2A
092307343-0004
None DetectedMatrix
Non-fibrous (Other)
80%
20%
Tan
Non-Fibrous
Homogeneous
TAN PAINT
1818-2B
092307343-0005
None DetectedMatrix
Non-fibrous (Other)
80%
20%
Tan
Non-Fibrous
Homogeneous
TAN PAINT
1818-2C
092307343-0006
None DetectedMatrix
Non-fibrous (Other)
80%
10%
Cellulose10%Tan
Fibrous
Heterogeneous
TAN PAINT
Result includes a small amount of inseparable attached material
1818-2D
092307343-0007
None DetectedMatrix
Non-fibrous (Other)
80%
20%
Tan
Non-Fibrous
Homogeneous
TAN PAINT
1818-2E
092307343-0008
None DetectedMatrix
Non-fibrous (Other)
85%
15%
Tan
Non-Fibrous
Homogeneous
TAN PAINT
1818-3A
092307343-0009
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
40%
30%
Gray
Non-Fibrous
Homogeneous
CONCRETE
FOUNDATION
1818-3B
092307343-0010
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
25%
50%
25%
Gray
Non-Fibrous
Homogeneous
CONCRETE
FOUNDATION
1818-4A
092307343-0011
<1% ChrysotileQuartz
Ca Carbonate
Non-fibrous (Other)
30%
40%
30%
Gray
Non-Fibrous
Homogeneous
EXT. TAN STUCCO
1818-4B
092307343-0012
<1% ChrysotileQuartz
Ca Carbonate
Non-fibrous (Other)
30%
40%
30%
Gray
Non-Fibrous
Homogeneous
EXT. TAN STUCCO
1818-4C
092307343-0013
<1% ChrysotileQuartz
Ca Carbonate
Non-fibrous (Other)
30%
40%
30%
Gray
Non-Fibrous
Homogeneous
EXT. TAN STUCCO
1818-4D
092307343-0014
<1% ChrysotileQuartz
Ca Carbonate
Non-fibrous (Other)
30%
50%
20%
Gray
Non-Fibrous
Homogeneous
EXT. TAN STUCCO
1818-4E
092307343-0015
<1% ChrysotileQuartz
Ca Carbonate
Non-fibrous (Other)
30%
60%
10%
Gray
Non-Fibrous
Homogeneous
EXT. TAN STUCCO
Initial report from: 04/07/2023 19:05:05
Page 1 of 6ASB_PLM_0008_0001 - 1.78 Printed: 4/7/2023 7:05 PM
Tel/Fax: (510) 895-3675 / (510) 895-3680 http://www.EMSL.com / sanleandrolab@emsl.com
092307343EMSL Order:
Customer ID: GECN80
Customer PO: S2170-07-26
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
1818-5A
092307343-0016
65% ChrysotileMatrix
Non-fibrous (Other)
10%
5%
Cellulose20%Tan/Silver
Fibrous
Homogeneous
SILVER / TAN
CLOTH - LIKE
GASKET
Inseparable silver paint included in analysis
1818-5B
092307343-0017
75% ChrysotileNon-fibrous (Other)25%Gray/White
Fibrous
Homogeneous
SILVER / TAN
CLOTH - LIKE
GASKET
1818-6A
092307343-0018
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
40%
30%
Gray
Non-Fibrous
Homogeneous
CONCRETE
FOUNDATION
1818-6B
092307343-0019
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
60%
10%
Gray
Non-Fibrous
Homogeneous
CONCRETE
FOUNDATION
1818-7A
092307343-0020
None DetectedCa Carbonate
Gypsum
Non-fibrous (Other)
20%
50%
30%
White
Non-Fibrous
Homogeneous
WHITE TEXTURE
1818-7B
092307343-0021
None DetectedCa Carbonate
Gypsum
Non-fibrous (Other)
20%
50%
30%
White
Non-Fibrous
Homogeneous
WHITE TEXTURE
1818-7C
092307343-0022
None DetectedCa Carbonate
Non-fibrous (Other)
80%
20%
White
Non-Fibrous
Homogeneous
WHITE TEXTURE
1818-8A-Drywall
092307343-0023
None DetectedGypsum
Non-fibrous (Other)
80%
20%
White
Non-Fibrous
Homogeneous
DW / JC
1818-8A-Joint
Compound
092307343-0023A
None DetectedCa Carbonate
Gypsum
Non-fibrous (Other)
20%
50%
30%
White
Non-Fibrous
Homogeneous
DW / JC
1818-8A-Mastic
092307343-0023B
None DetectedMatrix
Non-fibrous (Other)
90%
10%
Brown
Non-Fibrous
Homogeneous
DW / JC
1818-8B-Drywall
092307343-0024
None DetectedGypsum
Non-fibrous (Other)
80%
20%
White
Non-Fibrous
Homogeneous
DW / JC
1818-8B-Joint
Compound
092307343-0024A
None DetectedCa Carbonate
Gypsum
Non-fibrous (Other)
20%
50%
30%
White
Non-Fibrous
Homogeneous
DW / JC
1818-8C-Drywall
092307343-0025
None DetectedGypsum
Non-fibrous (Other)
80%
20%
White
Non-Fibrous
Homogeneous
DW / JC
1818-8C-Joint
Compound
092307343-0025A
None DetectedCa Carbonate
Non-fibrous (Other)
70%
15%
Cellulose15%White
Fibrous
Homogeneous
DW / JC
1818-9A-Mastic
092307343-0026
None DetectedMatrix
Non-fibrous (Other)
90%
10%
Brown
Non-Fibrous
Homogeneous
BROWN MASTIC
ASSOC. W / 4"
BROWN BB
1818-9A-Compound
092307343-0026A
None DetectedCa Carbonate
Gypsum
Non-fibrous (Other)
20%
50%
30%
White
Non-Fibrous
Homogeneous
BROWN MASTIC
ASSOC. W / 4"
BROWN BB
1818-9B-Mastic
092307343-0027
None DetectedMatrix
Non-fibrous (Other)
90%
10%
Brown
Non-Fibrous
Homogeneous
BROWN MASTIC
ASSOC. W / 4"
BROWN BB
1818-9B-Compound
092307343-0027A
None DetectedCa Carbonate
Gypsum
Non-fibrous (Other)
70%
10%
20%
White
Non-Fibrous
Homogeneous
BROWN MASTIC
ASSOC. W / 4"
BROWN BB
Page 2 of 6ASB_PLM_0008_0001 - 1.78 Printed: 4/7/2023 7:05 PM
Tel/Fax: (510) 895-3675 / (510) 895-3680 http://www.EMSL.com / sanleandrolab@emsl.com
092307343EMSL Order:
Customer ID: GECN80
Customer PO: S2170-07-26
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
1818-10A
092307343-0028
None DetectedMatrix
Non-fibrous (Other)
70%
18%
Synthetic12%Black
Fibrous
Homogeneous
10" OD BLACK / TAN
GASKET
1818-10B
092307343-0029
None DetectedMatrix
Non-fibrous (Other)
85%
10%
Glass5%Black
Non-Fibrous
Homogeneous
10" OD BLACK / TAN
GASKET
1818-11A-Debris
092307343-0030
None DetectedMatrix
Non-fibrous (Other)
30%
70%
Brown
Non-Fibrous
Heterogeneous
MULTICOLOR
BOILER DEBRIS /
INSULATION
Result includes a small amount of inseparable attached material
1818-11A-Vapor Barrier
092307343-0030A
10% ChrysotileNon-fibrous (Other)70%Fibrous (Other)20%Brown
Fibrous
Homogeneous
MULTICOLOR
BOILER DEBRIS /
INSULATION
Fibers were found with refractive indices outside of the acceptable range for regulated asbestos. These fibers are possibly altered asbestos fibers and were not included in the final asbestos concentration.
1818-11B-Debris
092307343-0031
None DetectedMatrix
Non-fibrous (Other)
30%
70%
Brown
Non-Fibrous
Heterogeneous
MULTICOLOR
BOILER DEBRIS /
INSULATION
Result includes a small amount of inseparable attached material
1818-11B-Vapor Barrier
092307343-0031A
12% ChrysotileNon-fibrous (Other)68%Fibrous (Other)20%Brown/Black
Fibrous
Homogeneous
MULTICOLOR
BOILER DEBRIS /
INSULATION
Fibers were found with refractive indices outside of the acceptable range for regulated asbestos. These fibers are possibly altered asbestos fibers and were not included in the final asbestos concentration.
1818-11C-Debris
092307343-0032
None DetectedCa Carbonate
Matrix
Non-fibrous (Other)
15%
40%
45%
Tan/Beige
Non-Fibrous
Homogeneous
MULTICOLOR
BOILER DEBRIS /
INSULATION
1818-11C-Vapor Barrier
092307343-0032A
8% ChrysotileNon-fibrous (Other)67%Fibrous (Other)25%Black/Rust
Fibrous
Homogeneous
MULTICOLOR
BOILER DEBRIS /
INSULATION
Fibers were found with refractive indices outside of the acceptable range for regulated asbestos. These fibers are possibly altered asbestos fibers and were not included in the final asbestos concentration.
1818-12A
092307343-0033
<1% ChrysotileCa Carbonate
Matrix
Non-fibrous (Other)
40%
30%
30%
Silver/Beige
Non-Fibrous
Homogeneous
WHITE BOILER
SEALANT
Inseparable silver paint included in analysis.
1818-12B
092307343-0034
None DetectedMatrix
Non-fibrous (Other)
80%
20%
Tan/White
Non-Fibrous
Homogeneous
WHITE BOILER
SEALANT
1818-13A
092307343-0035
None DetectedMatrix
Non-fibrous (Other)
80%
20%
Brown/Silver
Non-Fibrous
Heterogeneous
SILVER BOILER
PAINT
Result includes a small amount of inseparable attached material
1818-13B
092307343-0036
None DetectedMatrix
Non-fibrous (Other)
80%
20%
Brown/Silver
Non-Fibrous
Homogeneous
SILVER BOILER
PAINT
Result includes a small amount of inseparable attached material
1818-13C
092307343-0037
None DetectedMatrix
Non-fibrous (Other)
90%
10%
Silver
Non-Fibrous
Homogeneous
SILVER BOILER
PAINT
1818-14A-Insulation 1
092307343-0038
7% AmositeCa Carbonate
Non-fibrous (Other)
50%
28%
Cellulose15%White
Fibrous
Homogeneous
WHITE TSI W / TAN
CAP MATERIAL
1818-14A-Insulation 2
092307343-0038A
7% ChrysotileMatrix
Non-fibrous (Other)
70%
13%
Cellulose10%Black
Fibrous
Homogeneous
WHITE TSI W / TAN
CAP MATERIAL
1818-14B-Insulation 1
092307343-0039
4% AmositeCa Carbonate
Non-fibrous (Other)
40%
21%
Cellulose35%White
Fibrous
Homogeneous
WHITE TSI W / TAN
CAP MATERIAL
Page 3 of 6ASB_PLM_0008_0001 - 1.78 Printed: 4/7/2023 7:05 PM
Tel/Fax: (510) 895-3675 / (510) 895-3680 http://www.EMSL.com / sanleandrolab@emsl.com
092307343EMSL Order:
Customer ID: GECN80
Customer PO: S2170-07-26
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
1818-14B-Insulation 2
092307343-0039A
8% ChrysotileMatrix
Non-fibrous (Other)
40%
52%
Tan/Black
Non-Fibrous
Homogeneous
WHITE TSI W / TAN
CAP MATERIAL
1818-15A-Linoleum
092307343-0040
None DetectedMatrix
Non-fibrous (Other)
60%
40%
Blue
Non-Fibrous
Homogeneous
BLUE LINOLEUM +
TAN MASTIC
1818-15A-Mastic
092307343-0040A
None DetectedMatrix
Non-fibrous (Other)
80%
20%
Tan
Non-Fibrous
Homogeneous
BLUE LINOLEUM +
TAN MASTIC
1818-15B-Linoleum
092307343-0041
None DetectedCa Carbonate
Matrix
Non-fibrous (Other)
40%
30%
30%
Blue
Non-Fibrous
Homogeneous
BLUE LINOLEUM +
TAN MASTIC
1818-15B-Mastic
092307343-0041A
None DetectedMatrix
Non-fibrous (Other)
90%
10%
Tan/Yellow
Non-Fibrous
Homogeneous
BLUE LINOLEUM +
TAN MASTIC
1818-16A-Mastic 1
092307343-0042
None DetectedMatrix
Non-fibrous (Other)
80%
20%
Tan/White
Non-Fibrous
Homogeneous
TAN / BROWN BB
MASTIC
1818-16A-Baseboard
092307343-0042A
None DetectedMatrix
Non-fibrous (Other)
60%
40%
Blue
Non-Fibrous
Homogeneous
TAN / BROWN BB
MASTIC
1818-16A-Mastic 2
092307343-0042B
None DetectedMatrix
Non-fibrous (Other)
80%
20%
Brown
Non-Fibrous
Homogeneous
TAN / BROWN BB
MASTIC
1818-16A-Cementitious
Material
092307343-0042C
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
40%
30%
Gray
Non-Fibrous
Homogeneous
TAN / BROWN BB
MASTIC
1818-16B-Mastic 1
092307343-0043
None DetectedMatrix
Non-fibrous (Other)
90%
10%
Tan/Yellow
Non-Fibrous
Homogeneous
TAN / BROWN BB
MASTIC
1818-16B-Mastic 2
092307343-0043A
None DetectedMatrix
Non-fibrous (Other)
85%
15%
Brown
Non-Fibrous
Homogeneous
TAN / BROWN BB
MASTIC
1818-17A-Plaster
092307343-0044
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
40%
30%
Gray
Non-Fibrous
Heterogeneous
PLASTER
Composite analysis of dark gray and light gray plaster
1818-17A-Mastic 1
092307343-0044B
None DetectedMatrix
Non-fibrous (Other)
90%
10%
Brown
Non-Fibrous
Homogeneous
PLASTER
1818-17A-Mastic 2
092307343-0044C
4% ChrysotileMatrix
Non-fibrous (Other)
80%
16%
Black
Non-Fibrous
Homogeneous
PLASTER
1818-17A-Insulation
092307343-0044D
2%
4%
Amosite
Chrysotile
Ca Carbonate
Non-fibrous (Other)
50%
44%
White
Fibrous
Homogeneous
PLASTER
1818-17B-Plaster
092307343-0045
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
40%
50%
10%
Gray
Non-Fibrous
Heterogeneous
PLASTER
1818-17B-Mastic 1
092307343-0045A
None DetectedMatrix
Non-fibrous (Other)
85%
15%
White/Yellow
Non-Fibrous
Homogeneous
PLASTER
1818-17B-Mastic 2
092307343-0045B
4% ChrysotileMatrix
Non-fibrous (Other)
80%
16%
Black
Non-Fibrous
Homogeneous
PLASTER
Page 4 of 6ASB_PLM_0008_0001 - 1.78 Printed: 4/7/2023 7:05 PM
Tel/Fax: (510) 895-3675 / (510) 895-3680 http://www.EMSL.com / sanleandrolab@emsl.com
092307343EMSL Order:
Customer ID: GECN80
Customer PO: S2170-07-26
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
1818-17C-Plaster
092307343-0046
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
40%
50%
10%
Gray
Non-Fibrous
Homogeneous
PLASTER
1818-17C-Mastic 1
092307343-0046A
None DetectedMatrix
Non-fibrous (Other)
85%
15%
Brown
Non-Fibrous
Homogeneous
PLASTER
1818-17C-Mastic 2
092307343-0046B
2% ChrysotileMatrix
Non-fibrous (Other)
90%
8%
Black
Non-Fibrous
Homogeneous
PLASTER
1818-18A
092307343-0047
None DetectedMatrix
Non-fibrous (Other)
80%
20%
Tan/White
Non-Fibrous
Homogeneous
WALL TEXTURE
1818-18B
092307343-0048
None DetectedQuartz
Ca Carbonate
Matrix
Non-fibrous (Other)
30%
30%
30%
10%
Gray/Tan/White
Non-Fibrous
Heterogeneous
WALL TEXTURE
Inseparable paint / coating layer included in analysis
1818-18C
092307343-0049
None DetectedMatrix
Non-fibrous (Other)
75%
25%
Tan/White
Non-Fibrous
Homogeneous
WALL TEXTURE
1818-19A
092307343-0050
None DetectedMatrix
Non-fibrous (Other)
30%
30%
Cellulose40%Gray/Tan/Black
Fibrous
Homogeneous
TAN VAPOR
BARRIER
1818-19B
092307343-0051
None DetectedMatrix
Non-fibrous (Other)
5%
5%
Cellulose90%Brown/Black
Non-Fibrous
Homogeneous
TAN VAPOR
BARRIER
1818-20A
092307343-0052
None DetectedMatrix
Non-fibrous (Other)
50%
30%
Cellulose20%Gray
Fibrous
Homogeneous
WHITE HVAC TAPE
Result includes a small amount of inseparable attached material
1818-20B
092307343-0053
None DetectedMatrix
Non-fibrous (Other)
50%
30%
Cellulose20%White
Fibrous
Homogeneous
WHITE HVAC TAPE
Result includes a small amount of inseparable attached material
1818-21A
092307343-0054
None DetectedMatrix
Non-fibrous (Other)
80%
20%
White
Non-Fibr…