Little Goose Bascule Bridge Motor Control Center LGABBMCC
PROJECT TABLE OF CONTENTS
DI VI SI ON 26 - ELECTRI CAL
26 05 26.00 40 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
26 05 48.00 10 SEISMIC PROTECTION FOR ELECTRICAL EQUIPMENT
26 05 71.00 40 LOW VOLTAGE OVERCURRENT PROTECTIVE DEVICES
26 28 00.00 10 MOTOR CONTROL CENTERS, SWITCHBOARDS AND PANELBOARDS
-- End of Project Table of Contents --
PROJECT TABLE OF CONTENTS Page 1 31 Jan 23
THIS PAGE INTENTIONALLY LEFT BLANK
PROJECT TABLE OF CONTENTS Page 2
SECTION TABLE OF CONTENTS
DIVISION 26 - ELECTRICAL
SECTION 26 05 26.00 40
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
08/19
PART 1 GENERAL
1.1 REFERENCES
1.2 SUBMITTALS
1.3 QUALITY CONTROL
1.3.1 Regulatory Requirements
1.3.2 Standard Products
1.3.3 Ground Resistance Test Equipment
1.3.4 Micro-Ohmmeter Test Equipment
PART 2 PRODUCTS
2.1 MATERIALS
2.1.1 Ground Rods
2.1.2 Ground Wires
2.1.2.1 Bare
2.1.2.2 Insulated
2.1.2.3 Straps/Jumpers
2.1.3 Connectors and Fasteners
2.1.3.1 Exothermic Welds
2.1.3.2 Irreversible Compression Lugs
2.1.3.3 Mechanical
2.1.3.4 Fasteners
2.1.4 Conductive Corrosion Inhibiting Compounds
2.1.5 Ground Buses
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Ground Rods
3.1.2 Conductors
3.1.3 Ground Buses
3.1.4 Building Grounds
3.1.5 Equipment Grounding
3.1.5.1 Equipment and Enclosure Bonding
3.1.5.2 Bonding of Conduit and Raceway Systems
3.1.5.3 Cable Tray Bonding
3.1.6 Bonding Materials And Methods
3.1.6.1 Welding
3.1.6.2 Cleaning of Bonding Surfaces
3.1.6.3 Protection of Finished Bonds
3.2 FIELD QUALITY CONTROL
3.2.1 Bond Resistance Test
3.2.2 Ground Resistance Tests
3.2.3 Ground Isolation Test
3.2.4 Equipment Continuity Test
SECTION 26 05 26.00 40 Page 1
3.3 CLOSEOUT ACTIVITIES
-- End of Section Table of Contents --
SECTION 26 05 26.00 40 Page 2
SECTION 26 05 26.00 40
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
08/19
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN WELDING SOCIETY (AWS)
AWS A3.0M/A3.0 (2020) Standard Welding Terms and Definitions
AWS B2.1/B2.1M (2014; Errata 2015) Specification for Welding Procedure and Performance Qualification
ASTM INTERNATIONAL (ASTM)
ASTM B3 (2013) Standard Specification for Soft or Annealed Copper Wire
ASTM B8 (2011; R 2017) Standard Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft
ASTM B187/B187M (2020) Standard Specification for Copper, Bus Bar, Rod and Shapes and General Purpose Rod, Bar and Shapes
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 81 (2012) Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System
IEEE C2 (2017; Errata 1-2 2017; INT 1 2017) National Electrical Safety Code
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
ANSI/NEMA GR 1 (2007) Grounding Rod Electrodes and Grounding Rod Electorode Couplings
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2020; ERTA 20-1 2020; ERTA 20-2 2020; TIA
20-1; TIA 20-2; TIA 20-3; TIA 20-4)
National Electrical Code
NFPA 780 (2020) Standard for the Installation of Lightning Protection Systems
SECTION 26 05 26.00 40 Page 3
TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)
TIA-607 (2019d) Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises
U.S. DEPARTMENT OF DEFENSE (DOD)
MIL-STD-889 (2021; Rev D) Galvanic Compatibility of Electrically Conductive Materials
UNDERWRITERS LABORATORIES (UL)
UL 467 (2013; Reprint Jun 2017) UL Standard for Safety Grounding and Bonding Equipment
UL 546 (2008) UL Outline of Investigation for Conductor Termination Compounds
1.2 SUBMITTALS
Government approval is required for submittals. Submit the following to the Contract Performance Specialist:
Product Data
Ground Rods
Ground Wires
Connectors and Fasteners
Test Wells
Conductive Corrosion Inhibiting Compounds
Ground Buses
Test Reports
Bond Resistance Test
Ground Resistance Tests
Ground Isolation Test
Equipment Continuity Test
Certificates
Ground Resistance Test Equipment
Micro-Ohmmeter Test Equipment
Closeout Submittals
Record Drawings
SECTION 26 05 26.00 40 Page 4
Certificates
Ground Resistance Test Equipment
1.3 QUALITY CONTROL
1.3.1 Regulatory Requirements
In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the word, "shall" had been substituted for "should" wherever it appears. Interpret references in these publications to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer. Ensure equipment, materials, installation, and workmanship are in accordance with the mandatory and advisory provisions of NFPA 70 , IEEE C2 unless more stringent requirements are specified or indicated.
1.3.2 Standard Products
Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship. Provide products which have been in satisfactory commercial or industrial use for 2 years prior to bid opening. Ensure the 2-year period includes applications of equipment and materials under similar circumstances and of similar size. Ensure the product has been on sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2-year period. Where two or more items of the same class of equipment are required, these items must be products of a single manufacturer.
1.3.3 Ground Resistance Test Equipment
Provide combination 3-point and 4-point type ground resistance test equipment specifically designed for grounding electrode resistance and soil resistivity tests. Submit proof of current equipment calibration with test equipment product data.
1.3.4 Micro-Ohmmeter Test Equipment
Perform circuit and bond resistance tests using a micro-ohmmeter with the following characteristics:
a. Resistance range selectable and capable of measuring to 10 micro-Ohms using a minimum of 1 ampere of test current.
b. Positive and negative test leads of the 2-wire balanced type.
Provide both clamp and probe type connections to allow measurements across all bonded surfaces. Provide long length balanced test lead to allow measurements from a bonding location to the nearest test well.
Submit proof of current equipment calibration with test equipment product data.
PART 2 PRODUCTS
Submit material, equipment, and fixture lists for grounding systems, including manufacturer's style or catalog numbers, specification and drawing reference numbers, warranty information, and fabrication site information.
SECTION 26 05 26.00 40 Page 5
2.1 MATERIALS
2.1.1 Ground Rods
Provide ground rods of copper-clad steel conforming to UL 467 and ANSI/NEMA GR 1 . Ensure ground rods are not less than 3/4 inch in diameter and 10 feet in length.
Where ground rod length is greater than 10 feet, provide sectional type ground rods with each section 10 feet in length. Join sectional type ground rods using threaded brass couplings. Ensure ground rods have cone-shaped point on the end of the first section driven into the ground.
Provide ground rods and ground rod sections die-stamped near the top with the name or trademark of the manufacturer and the length of the segment in feet.
2.1.2 Ground Wires
2.1.2.1 Bare
Provide annealed bare copper, Class "B" stranded ground and bond wires in accordance with ASTM B8 for wires #4 AWG and larger and solid in accordance with ASTM B3 for wires #6 AWG and smaller. Provide conductors with 98 percent conductivity and sized wires in accordance with the requirements of NFPA 70 and NFPA 780 .
2.1.2.2 Insulated
Unless specified or indicated otherwise or required by NFPA 70, provide power and lighting wires rated for 600-volts, Type XHHW, except that grounding wire may be type TW conforming to UL 83. Provide conductors with a minimum of 90-degree C insulation, or better.
Where installed in conduit as part of a complete circuit provide conductors with green insulation for sizes #8 AWG and smaller and with green phase tape at each end and in each junction box for sizes #6 AWG and larger.
2.1.2.3 Straps/Jumpers
Provide copper bonding straps and jumpers with a cross-sectional area of not less than No. 6 AWG. Ensure bonding straps and jumpers for shock-mounted devices with hinged joints are made of flexible stranded wire.
2.1.3 Connectors and Fasteners
2.1.3.1 Exothermic Welds
Ensure the molds, materials and powder charges used to make exothermic welds are the standard product of a single manufacturer and listed by the manufacturer for use on the specific type, size, quantity and configuration of conductors to which the weld is applied.
2.1.3.2 Irreversible Compression Lugs
Provide irreversible compression lug type connectors manufactured from
SECTION 26 05 26.00 40 Page 6 tin-plated copper and installed using a hydraulic compression tool and die to apply correct, uniformly distributed, circumferential pressure. Ensure tools and dies are as recommended by the irreversible compression lug type connector manufacturer. Use an embossing die code or other standard method to provide visible indication that a connector has been adequately compressed onto the conductor. Apply irreversible compression lug type connectors in strict accordance with the manufacturer's written instructions and published installation instructions. Use 2-hole lug type connectors for connections to NEMA cable pads and bus bars, and single-hole connectors otherwise.
2.1.3.3 Mechanical
Provide split bolt and clamp style mechanical type connectors manufactured from copper listed by the manufacturer as suitable for direct burial use.
Ensure mechanical type connectors are applied in strict accordance with the manufacturer's published installation instructions.
2.1.3.4 Fasteners
Provide bolts, nuts, washers, lock washers, and associated fasteners used for grounding and bonding connections manufactured of copper. Where fasteners contact dissimilar metals, apply conductive oxide-inhibiting compound.
2.1.4 Conductive Corrosion Inhibiting Compounds
Provide conductive corrosion inhibiting compounds UL Listed in accordance with UL 546 , listed by the manufacturer as suitable for the application, and suitable for all aluminum and copper conductor/connector applications. Ensure conductive corrosion inhibiting compounds inhibit oxidation at the conductor/connector interface and have no deleterious effect on the conductor/connector metal or EPDM, natural rubber, or polyethylene insulating materials.
2.1.5 Ground Buses
Provide solid copper ground buses conforming to ASTM B187/B187M with minimum dimensions of 0.25 inches thick, 4 inches wide, and 12 inches in length or as indicated. Ensure ground buses are equipped with two UL Recognized red 1000V rated insulated standoffs and stainless steel mounting brackets.
Provide Telecommunications Main Ground Buses and Telecommunications Ground Buses in meeting the standards of TIA-607 .
Provide grounding buses with predrilled NEMA hole configuration as indicated.
PART 3 EXECUTION
3.1 INSTALLATION
Install grounding systems in accordance with NFPA 70 , NFPA 780 and IEEE C2 , and as indicated.
Bond exposed non-current-carrying metallic parts of electrical equipment and metallic raceway systems to ground.
SECTION 26 05 26.00 40 Page 7
Bond grounding conductors in metallic and non-metallic raceways to ground. Make ground connections at equipment and to ground rods as indicated. Interconnect all grounding media in or on the structure to provide a common ground potential. This includes lightning protection, electrical service, telecommunications system grounds, as well as underground metallic piping systems.
Bond wiring system neutrals to ground in accordance with the requirements of NFPA 70 . Where ground fault protection is employed, ensure that connection of ground and neutral does not interfere with correct operation of fault protection.
3.1.1 Ground Rods
Install ground rods using a water jetting procedure.
3.1.2 Conductors
Install bare or insulated conductors as indicated. Install bare conductors where not specifically identified as bare or insulated except where installed in conduit with associated phase conductors. Install insulated conductors in conduit with insulation of the same material as the associated phase conductors with which it is installed.
Provide straps/jumpers across joints subject to vibration. Install strap/jumper such that vibration will not change its electrical characteristics. Apply strap/jumper to the metallic structure on each side of the joint; do not penetrate any adjacent parts. Install straps/jumpers in areas that are accessible for maintenance. Install strap/jumper such that it does not restrict the movement of the metallic structures to which it is connected. Install strap/jumper such that it does not weaken the metallic structures to which it is attached. Do not connect two or more straps/jumpers in series.
3.1.3 Ground Buses
Install ground busses in accordance with manufacturer's instructions.
3.1.4 Building Grounds
Install No. 4/0 AWG bare copper ground conductor from concrete encased foundation rebar to counterpoise. Connect conductors to rebar using exothermic welds. Install one conductor a minimum of every 60 feet of concrete foundation perimeter. Connect ground conductors to counterpoise using exothermic welds.
3.1.5 Equipment Grounding
Install ground systems for power, telecommunications, and instrumentation. Independently connect each system to the building counterpoise.
3.1.5.1 Equipment and Enclosure Bonding
Bond each metallic enclosure and all electrical equipment to ground. Make at least one copper connection from the system ground point to one or more enclosures in the area such that all enclosures and equipment provide a low-impedance path to ground when properly bonded together.
SECTION 26 05 26.00 40 Page 8
Individually and directly connect indoor substations, transformers, switchboard frames, switchgear assemblies, motors, motor control centers, air compressors, air handlers, refrigerated air dryers, generators, frames and tracks of cranes, and to the building ground. Ensure the current-carrying capacity of the grounding conductor is the same as the current-carrying capacity of the power conductors for circuits utilizing power lines size No. 2 AWG and smaller. For circuits with power wiring larger than No. 2 AWG, ensure the grounding conductor is in accordance with NFPA 70 .
3.1.5.2 Bonding of Conduit and Raceway Systems
Bond all metal conduit, fittings, junction boxes, outlet boxes, armored and metal sheathed cable, and other raceways. Ensure adequate electrical contact at the joints and terminations. Ensure metallic raceway systems have electrical continuity with equipment. Individually and directly connect equipment to the building ground, independent of the raceway system.
For rigid metal conduit and terminations, ensure threaded connections are wrench-tight with no exposed threads. Ream all ends of the conduit to remove burrs and rough edges. Bond conduits entering boxes and enclosures to the box with bonding-type locknuts, one outside and one inside.
Locknuts that gouge into the metal box when tightened are not acceptable.
Conduit systems that are interrupted by PVC dielectric links are bonded separately on either side of the link. Do not jumper the dielectric link.
Install flexible metal conduit with an integral grounding conductor.
3.1.5.3 Cable Tray Bonding
Bond cable tray sections together. Cable tray sections in tandem assembly are considered as having electrical continuity when these sections are bonded with the appropriate bolts. Install bond straps across expansion joints. Bond cable trays to the building ground system.
3.1.6 Bonding Materials And Methods
Accomplish bonding of metal surfaces by welding.
3.1.6.1 Welding
Weld using the exothermic process with procedures conforming to AWS A3.0M/A3.0 , AWS B2.1/B2.1M , and manufacturer's recommendation. Where dissimilar metals are to be joined via exothermic weld, follow the weld kit manufacturer's recommendations and published instructions. Ensure connections between dissimilar metals do not produce galvanic action in accordance with MIL-STD-889 .
Use welding processes of the exothermic fusion type that makes a connection without corroding or loosening. Ensure process joins all strands and does not cause the parts to be damaged or weakened. Completed connection or joint is equal or larger in size than the conductors joined and has the same current-carrying capacity as the largest conductor.
Paint the buried ground connections with a bitumastic paint.
SECTION 26 05 26.00 40 Page 9
3.1.6.2 Cleaning of Bonding Surfaces
Thoroughly clean surfaces that comprise the bond before joining. Apply an appropriate abrasive with gentle and uniform pressure to ensure a smooth and uniform surface. Do not remove excessive metal from the surface.
Clean clad metals in such a manner that the cladding material is not penetrated by the cleaning process. Then clean bare metal with an appropriate solvent to remove any grease, oil, dirt, corrosion preventives, and other contaminants. Bond to the cleaned area within one hour after cleaning. Seal joint and refinish the exposed surfaces within two hours of exposure to prevent oxidation. When additional time is required, apply a corrosion preventive compound until the area can be refinished.
3.1.6.3 Protection of Finished Bonds
Protect finished bonds by painting to match the original finish after the bond is made.
3.2 FIELD QUALITY CONTROL
Perform the following tests in the presence of the Contracting Officer.
Furnish test equipment and personnel and submit written results of each test. Notify the Contracting Officer at least 14 calendar working days prior to each test.
Submit written results of each test to Contracting Officer for review and approval. Document each location where test is performed, the field conditions at the time of the test, the measured results of the test, and whether the measured results "PASSED" or "FAILED" relative to specified pass/fail performance criteria.
Perform rework to correct FAILED conditions at no additional cost to the Government.
3.2.1 Bond Resistance Test
Resistance of any bond connection cannot exceed 0.5 milliohm. Rework bonds that exceed this resistance at no additional cost to the Government.
3.2.2 Ground Resistance Tests
Test grounding systems for ground resistance. Total resistance from any point on the ground network to the building counterpoise cannot exceed 50 milliohms.
Make ground resistance and counterpoise tests during dry weather, and no sooner than 48 hours after rainfall. Conduct tests using the ratio method that measures the ratio of the resistance to earth of an auxiliary test electrode to the series resistance of the electrode under test and a second auxiliary electrode. Perform measurements in accordance with
IEEE 81 .
3.2.3 Ground Isolation Test
Test ground systems for isolation from other ground systems.
SECTION 26 05 26.00 40 Page 10
3.2.4 Equipment Continuity Test
Test connection from electrical distribution equipment including panelboards, switchboards, transformers, substations, and motor control centers to counterpoise. Measure and record the circuit resistance between electrical equipment ground connections and the counterpoise. The circuit resistance shall not exceed 5 Ohms.
3.3 CLOSEOUT ACTIVITIES
Submit record drawings indicating the location of ground rods, mats, grids, building ground bus, supplementary grounding electrodes, steel building columns, and other metal structures connected to the grounding system.
-- End of Section --
SECTION 26 05 26.00 40 Page 11
SECTION 26 05 26.00 40 Page 12
DIVISION 26 - ELECTRICAL
SECTION 26 05 48.00 10
SEISMIC PROTECTION FOR ELECTRICAL EQUIPMENT
10/07
PART 1 GENERAL
1.1 REFERENCES
1.2 SYSTEM DESCRIPTION
1.2.1 General Requirements
1.2.2 Electrical Equipment
1.2.3 Electrical Systems
1.2.4 Contractor Designed Bracing
1.2.5 Conduits Requiring No Special Seismic Restraints
1.3 EQUIPMENT REQUIREMENTS
1.3.1 Rigidly Mounted Equipment
1.4 SUBMITTALS
PART 2 PRODUCTS - NOT USED
PART 3 EXECUTION - NOT USED
-- End of Section Table of Contents --
SECTION 26 05 48.00 10 Page 1
SECTION 26 05 48.00 10 Page 2
SECTION 26 05 48.00 10
SEISMIC PROTECTION FOR ELECTRICAL EQUIPMENT
10/07
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
AISC 325 (2017) Steel Construction Manual
U.S. DEPARTMENT OF DEFENSE (DOD)
UFC 3-301-01 (2019) Structural Engineering
1.2 SYSTEM DESCRIPTION
1.2.1 General Requirements
The requirements for seismic protection measures described in this section shall be applied to the electrical equipment and systems listed below.
1.2.2 Electrical Equipment
Electrical equipment shall include the following items to the extent required on the drawings or in other sections of these specifications:
Control Panels Air Handling Units
Pumps with Motors Switchgear
Light Fixtures Unit Substations
Motor Control Centers Transformers
Switchboards (Floor Mounted) Storage Racks
Solar Heating Units
1.2.3 Electrical Systems
The following electrical systems shall be installed as required on the drawings and other sections of these specifications and shall be seismically protected in accordance with this specification: Motor Control Center
SECTION 26 05 48.00 10 Page 3
1.2.4 Contractor Designed Bracing
Submit copies of the Design Calculations with the Drawings. Calculations shall be approved, certified, stamped and signed by a Registered Professional Engineer. Calculations shall verify the capability of structural members to which bracing is attached for carrying the load from the brace. Design the bracing in accordance with UFC 3-301-01 and additional data furnished by the Contracting Officer. Resistance to lateral forces induced by earthquakes shall be accomplished without consideration of friction resulting from gravity loads. UFC 3-301-01 uses parameters for the building, not for the equipment in the building;
therefore, corresponding adjustments to the formulas shall be required.
Loadings determined using UFC 3-301-01 are based on strength design;
therefore, AISC 325 shall be used for the design. Develop the bracing for the following electrical equipment and systems: Motor Control Center.
1.2.5 Conduits Requiring No Special Seismic Restraints
Seismic restraints may be omitted from electrical conduit less than 2-1/2 inches trade size. All other interior conduit, shall be seismically protected as specified.
1.3 EQUIPMENT REQUIREMENTS
Submit detail drawings along with catalog cuts, templates, and erection and installation details, as appropriate, for the items listed.
Submittals shall be complete in detail, indicating thickness, type, grade, class of metal, and dimensions; and shall show construction details, reinforcement, anchorage, and installation with relation to the building construction. Submit copies of the design calculations with the detail drawings. Calculations shall be stamped by a registered engineer and shall verify the capability of structural members to which bracing is attached for carrying the load from the brace.
1.3.1 Rigidly Mounted Equipment
The following specific items of equipment: Motor Control Center to be furnished under this contract shall be constructed and assembled to withstand the seismic forces specified in UFC 3-301-01 . Each item of rigid electrical equipment shall be entirely located and rigidly attached on one side only of a building expansion joint. Piping, electrical conduit, etc., which cross the expansion joint shall be provided with flexible joints that are capable of accommodating displacements equal to the full width of the joint in both orthogonal directions.
Engine-Generators Substations Transformers Switch Boards and Switch Gears Motor Control Centers Free Standing Electric Motors
1.4 SUBMITTALS
Government approval is required for submittals. Submit the following to the Contract Performance Specialist:
Shop Drawings
SECTION 26 05 48.00 10 Page 4
Lighting Fixtures in Buildings
Equipment Requirements
Product Data
Lighting Fixtures in Buildings
Equipment Requirements
Contractor Designed Bracing
PART 2 PRODUCTS - NOT USED
PART 3 EXECUTION - NOT USED
-- End of Section --
SECTION 26 05 48.00 10 Page 5
SECTION 26 05 48.00 10 Page 6
DIVISION 26 - ELECTRICAL
SECTION 26 05 71.00 40
LOW VOLTAGE OVERCURRENT PROTECTIVE DEVICES
02/17
PART 1 GENERAL
1.1 REFERENCES
1.2 SUBMITTALS
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
2.2 EQUIPMENT
2.2.1 Motor Controllers
2.2.1.1 Manual Motor Controllers
2.2.1.2 Magnetic Motor Controllers
2.2.1.3 Combination Motor Controllers
2.2.2 Circuit Breakers
2.2.2.1 Molded-Case Circuit Breakers
2.2.2.2 Enclosed Molded-Case Circuit Breakers
2.2.3 Fuses
2.2.4 Control Devices
2.2.4.1 Magnetic Contactors
2.2.4.2 Control-Circuit Transformers
2.2.4.3 Magnetic Control Relays
2.2.4.4 Pushbuttons and Switches
2.2.5 Finish
2.3 COMPONENTS
2.3.1 Instrument Transformers
2.3.1.1 Current Transformers
2.3.1.2 Potential Transformers
2.3.2 Enclosures
2.3.2.1 Equipment Enclosures
2.3.2.2 Remote-Control Station Enclosures
2.3.3 Protective Relays
2.3.3.1 Overcurrent Relays
2.3.3.2 Directional Overcurrent Relays
2.3.3.3 Reclosing Relays
2.3.3.4 Undervoltage Relays
2.3.4 Indicating Instruments
2.3.4.1 Ammeters
2.3.4.2 Voltmeters
2.3.4.3 Watt-Hour Meters/Wattmeters
2.3.4.4 Graphic Demand Meters
2.3.4.5 Specialty-Type Meters
2.3.5 Indicating Lights
2.3.5.1 General-Purpose Type
2.3.5.2 Switchboard Indicating Lights
PART 3 EXECUTION
SECTION 26 05 71.00 40 Page 1
3.1 INSTALLATION
3.2 FIELD QUALITY CONTROL
3.2.1 Tests
-- End of Section Table of Contents --
SECTION 26 05 71.00 40 Page 2
SECTION 26 05 71.00 40
LOW VOLTAGE OVERCURRENT PROTECTIVE DEVICES
02/17
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI C12.1 (2014; Errata 2016) Electric Meters - Code for Electricity Metering
ASTM INTERNATIONAL (ASTM)
ASTM D877/D877M (2019) Standard Test Method for Dielectric Breakdown Voltage of Insulating Liquids Using Disk Electrodes
ELECTRONIC INDUSTRIES ALLIANCE (EIA)
EIA 443 (1979) NARM Standard for Solid State Relays Service
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE C37.17 (2012) Standard for Trip Devices for AC and General-Purpose DC Low-Voltage Power Circuit Breakers
IEEE C37.90 (2005; R 2011) Standard for Relays and Relay Systems Associated With Electric Power Apparatus
IEEE C57.13 (2016) Standard Requirements for Instrument Transformers
IEEE C63.2 (2009) Standard for Electromagnetic Noise and Field Strength Instrumentation, 10 Hz to 40 GHz - Specifications
IEEE C63.4 (2014) American National Standard for Methods of Measurement of Radio-Noise Emissions from Low-Voltage Electrical and Electronic Equipment in the Range of 9 kHz to 40 GHz
IPC - ASSOCIATION CONNECTING ELECTRONICS INDUSTRIES (IPC)
IPC D330 (1992) Design Guide Manual
SECTION 26 05 71.00 40 Page 3
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
ANSI C78.23 (1995; R 2003) American National Standard for Incandescent Lamps - Miscellaneous Types
NEMA 250 (2020) Enclosures for Electrical Equipment (1000 Volts Maximum)
NEMA AB 3 (2013) Molded Case Circuit Breakers and Their Application
NEMA FU 1 (2012) Low Voltage Cartridge Fuses
NEMA ICS 1 (2000; R 2015) Standard for Industrial Control and Systems: General Requirements
NEMA ICS 2 (2000; R 2020) Industrial Control and Systems Controllers, Contactors, and Overload Relays Rated 600 V
NEMA ICS 6 (1993; R 2016) Industrial Control and Systems: Enclosures
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2020; ERTA 20-1 2020; ERTA 20-2 2020; TIA
20-1; TIA 20-2; TIA 20-3; TIA 20-4)
National Electrical Code
UNDERWRITERS LABORATORIES (UL)
UL 20 (2018; Reprint Jan 2021) UL Standard for Safety General-Use Snap Switches
UL 489 (2016; Rev 2019) UL Standard for Safety Molded-Case Circuit Breakers, Molded-Case Switches and Circuit-Breaker Enclosures
UL 508 (2018; Reprint Jul 2021) UL Standard for Safety Industrial Control Equipment
1.2 SUBMITTALS
Government approval is required for submittals. Submit the following to the Contract Performance Specialist:
Shop Drawings
Connection Diagrams
Fabrication Drawings
Control Devices
Protective Devices
Product Data
SECTION 26 05 71.00 40 Page 4
Fuses
Motor Controllers
Instrument Transformers
Enclosures
Circuit Breakers
Control Devices
Time Switches
Protective Relays
Indicating Instruments
Indicating Lights
Test Reports
Dielectric Tests
Final Test Reports
Certificates
Insulating Oil
Manufacturer's Instructions
Control Devices
Protective Devices
Operation and Maintenance Data
Manual Motor Controllers
Magnetic Motor Controllers
Combination Motor Controllers
Circuit Breakers
Time Switches
Protective Relays
Indicating Instruments
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
Submit connection diagrams showing the relations and connections of control devices and protective devices by showing the general physical layout of all controls, the interconnection of one system (or portion of
SECTION 26 05 71.00 40 Page 5 system) with another, and internal tubing, wiring, and other devices.
Submit fabrication drawings for control devices and protective devices consisting of fabrication and assembly details performed in the factory.
2.2 EQUIPMENT
2.2.1 Motor Controllers
Conform to NEMA ICS 1 , NEMA ICS 2 , and UL 508 for motor controllers.
Ensure controllers have thermal overload protection in each phase.
2.2.1.1 Manual Motor Controllers
Provide full-voltage, manually operated manual motor controllers for the control and protection of single-phase 60-Hz AC fractional-horsepower squirrel-cage induction motors.
Provide single-throw, single- or double-pole, three-position controllers rated at not more than 1 horsepower at 115 V and 230 V single-phase.
Include a supporting base or body of electrical insulating material with enclosed switching mechanism, yoke, thermal-overload relay, and terminal connectors. Provide controllers that clearly indicate operating condition: on, off, or tripped.
Provide toggle- or key-operated-type manual motor controllers as indicated and arrange them so that they are lockable with a padlock in the "OFF" position.
Provide recessed manual motor controllers for single-speed, fractional-horsepower, squirrel-cage induction motors. Include a single controller and indicating light in a 4-inch-square wall outlet box; for flush-wiring devices, include matching corrosion-resistant steel flush cover plates. Provide surface-mounted manual motor controllers for single-speed, fractional-horsepower squirrel-cage induction motors that include a single controller and indicating light in a NEMA 250, Type 1, general-purpose enclosure.
Provide recessed and surface-mounted manual motor controllers for two-speed, fractional-horsepower, squirrel-cage induction motors; include two controllers, two indicating lights, and a selector switch in a multiple-gang wall outlet box for flush-wiring devices, with matching corrosion-resistant steel flush cover plates. Provide surface-mounted manual motor controllers for two-speed, fractional-horsepower, squirrel-cage induction motors; include two controllers, two indicating lights, and a selector switch in a NEMA 250, Type 1, general-purpose enclosure.
2.2.1.2 Magnetic Motor Controllers
a. Full-Voltage Controllers
Provide full-voltage, full-magnetic devices for the control and protection of single- and three-phase, 60 Hz, squirrel-cage induction motors in accordance with NEMA ICS 1 , NEMA ICS 2 , and UL 508 for magnetic motor controllers.
Ensure that the operating coil assembly operates satisfactorily between 85 percent and 110 percent of rated coil voltage. Provide 120 V, 60 Hz motor
SECTION 26 05 71.00 40 Page 6 control circuits.
Provide the controllers with two normally open and two normally closed auxiliary contacts rated according to NEMA ICS 1 and NEMA ICS 2 , in addition to the sealing-in contact for the control circuits.
Provide solderless pressure wire terminal connectors for line and load connections to the controllers.
Include three manual-reset thermal-overload devices for overcurrent protection, one in each pole of the controller. Provide thermal-overload relays of the bimetallic nonadjustable type with continuous-current ratings and service-limit current ratings. Ensure that ratings have a plus or minus 15 percent adjustment to compensate for ambient operating conditions.
Provide an externally operable manual-reset button to reestablish control power to the holding coil of the electromagnet. After the controller has tripped from overload, ensure that resetting the motor-overload device does not restart the motor.
Provide an enclosure in accordance with NEMA 250, Type 3R.
b. Reduced-Voltage Starters
Conform to the requirements for full-voltage controllers for reduced-voltage starters, except for voltage, and to the following additional requirements:
(1) Fully protect the motor during all phases of motor starting with an overload device in each motor leg. Rate the starter contacts to withstand the switching surges during selector to full voltage. Provide a starter that contains the sensing and timing devices necessary to monitor motor operation and select the correct time for selector to full voltage.
(2) Ensure adequate ventilation of resistors and autotransformers used for starting. Ventilate solid-state starters for starting cycles as well as any follow-on restart-run cycles. Operate external control circuits or solid-state starters at a maximum of 120 VAC..
(3) For solid-state starters, provide adjustable starting torque from 0 percent to 50 percent of applied voltage, minimum. Provide autotransformer starters with a minimum of three taps above 50 percent reduced voltage.
2.2.1.3 Combination Motor Controllers
The following requirements are in addition to the requirements specified for magnetic motor controller:
a. Provide combination motor controllers for the control and protection of single- and three-phase, 60 Hz AC squirrel-cage induction motors with branch-circuit disconnecting and protective devices in accordance with NEMA ICS 1 , NEMA ICS 2 , and NEMA ICS 6 .
b. For combination motor controllers, include magnetic motor controllers and molded-case circuit breakers or motor circuit protectors (MCPs) in metal enclosures in accordance with NEMA 250 or motor control center
SECTION 26 05 71.00 40 Page 7 draw-out assemblies with control-power transformers, selector switches, pushbuttons, and indicating lights as follows:
(1) Provide full-voltage, full-magnetic devices as specified in this section under paragraph REMOTE-CONTROL STATION ENCLOSURES for magnetic motor controllers and enclosures.
(2) Provide thermal-magnetic breakers as specified in paragraph MANUAL MOTOR CONTROLLERS for molded-case circuit breakers.
Manufacturer's standard MCPs may be used in lieu of molded-case circuit breakers.
(3) Provide control-power transformers 120 VAC maximum, selector switches, pushbuttons, and pilot lights as required.
(4) Identify combination motor controllers with identification plates affixed to the front cover of the controller.
a. Nonreversing Combination Motor Controllers
The following requirements are in addition to the requirements for magnetic motor controllers:
(1) For the control and protection of single-speed squirrel-cage induction motors, include a magnetic controller with molded-case circuit breaker or MCPs with selector switch or start/stop pushbutton and indicating light in the cover of the enclosure.
(2) Provide rating of single and three-phase, single-speed, full-voltage magnetic controllers for nonplugging and nonjogging duty in accordance with NEMA ICS 1 and NEMA ICS 2 .
(3) Provide wiring and connections for full-voltage, single-speed magnetic controllers in accordance with NEMA ICS 1 and NEMA ICS 2 .
b. Reversing Combination Motor Controllers
The following requirements are in addition to the requirements for magnetic motor controllers:
(1) For the control and protection of single-speed squirrel-cage induction motors, include two interlocked magnetic controllers with molded-case circuit breaker or MCPs, with selector switch or forward/reverse/stop pushbutton and two indicating lights in the cover of the enclosure. Provide indicating lights to identify the forward and reverse running connection of the motor controller.
(2) Provide rating of single and three-phase, single-speed, full-voltage magnetic controllers for plug-stop, plug-reverse, or jogging duty in accordance with NEMA ICS 1 and NEMA ICS 2 .
(3) Provide wiring and connections for full-voltage, single-speed magnetic controllers in accordance with NEMA ICS 1 and NEMA ICS 2 .
c. Two-Speed Combination Motor Controllers
The following requirements are in addition to the requirements for magnetic motor controllers:
SECTION 26 05 71.00 40 Page 8
(1) For the control and protection of single- and two-winding, two-speed, three-phase, squirrel-cage induction motors, include two magnetic controllers with molded-case circuit breaker or MCPs, with selector switch or fast/slow/stop pushbutton and two indicating lights in the cover of the enclosure. Provide indicating lights to identify the high- and low-speed running connection of the motor controller.
(2) Provide rating of three-phase, two-speed, full-voltage magnetic controllers for nonplugging and nonjogging duty for constant- and variable-torque motors in accordance with NEMA ICS 1 and NEMA ICS 2 .
(3) Provide rating of three-phase, two-speed, full-voltage magnetic controllers for nonplugging and nonjogging duty for constant-horsepower motors in accordance with NEMA ICS 1 and NEMA ICS 2 .
(4) Provide rating of three-phase, two-speed, full-voltage magnetic controllers for plug-stop, plug-reverse, or jogging duty for constant-torque, variable-torque, and constant-horsepower motors in accordance with NEMA ICS 1 and NEMA ICS 2 .
2.2.2 Circuit Breakers
Provide circuit breakers that conform to UL 489 and NEMA AB 3.
2.2.2.1 Molded-Case Circuit Breakers
Provide molded-case, manually operated, trip-free circuit breakers, with inverse-time thermal-overload protection and instantaneous magnetic short-circuit protection as required. Completely enclose circuit breakers in a molded case, with a factory-sealed, calibrated sensing element to prevent tampering.
Locate thermal-magnetic tripping elements in each pole of the circuit breaker, and provide inverse-time-delay thermal-overload protection and instantaneous magnetic short-circuit protection. Provide an instantaneous magnetic tripping element that is adjustable and accessible from the front of the breaker on frame sizes larger than 100 A.
Size the breaker as required for the continuous-current rating of the circuit. Provide the breaker class as required.
Provide sufficient interrupting capacity of the panel and lighting branch circuit breakers to successfully interrupt the maximum short-circuit current imposed on the circuit at the breaker terminals. Provide circuit breaker interrupting capacities with a minimum of 10,000 A and that conform to NEMA AB 3.
Provide the common-trip-type multipole circuit breakers having a single operating handle and a two-position on/off indication. Provide circuit breakers with temperature compensation for operation in an ambient temperature of 104 degrees F. Provide circuit breakers that have root mean square (rms) symmetrical interrupting ratings sufficient to protect the circuit being supplied. Interrupting ratings may have selective-type tripping (time delay, magnetic, thermal, or ground fault).
Provide a phenolic-composition breaker body capable of having such accessories as handle-extension, handle-locking, and padlocking devices attached where required.
SECTION 26 05 71.00 40 Page 9
For meter circuit disconnects, provide circuit breakers of the motor-circuit-protector type that meet the applicable requirements of
NFPA 70 .
For service disconnection, provide enclosed circuit-breakers with external handles for manual operation. Provide sheet-metal enclosures with hinged covers suitable for surface mounting.
2.2.2.2 Enclosed Molded-Case Circuit Breakers
For enclosed circuit breakers, provide thermal-magnetic, molded-case circuit breakers in surface-mounted, nonventilated enclosures conforming to NEMA 250 and UL 489 .
Provide enclosed circuit breakers in nonhazardous locations as follows:
c. Contain circuit breakers installed in wet locations, in NEMA Type 4, watertight corrosion-resistant, sheet-steel enclosures constructed to prevent entrance of water.
2.2.3 Fuses
Provide a complete set of fuses for all switches and switchgear. Ensure that fuses have a voltage rating of not less than the circuit voltage.
Make no change in continuous-current rating, interrupting rating, or clearing or melting time of fuses unless written permission is first obtained from the Contracting Officer.
Provide nonrenewable-cartridge-type fuses for ratings 30 A, 125 V or less. Provide renewable-cartridge-type fuses for ratings above 30 A 600 V or less with time-delay dual elements, except where otherwise indicated.
Ensure fuses conform to NEMA FU 1.
Install special fuses such as extra-high interrupting-capacity fuses, fuses for welding machines, and capacitor fuses where required. Do not use plug fuses.
Label fuses showing UL class, interrupting rating, and time-delay characteristics, when applicable.
Provide porcelain fuse holders when field-mounted in a cabinet or box. Do not use fuse holders made of such materials as ebony asbestos, Bakelite, or pressed fiber for field installation.
2.2.4 Control Devices
2.2.4.1 Magnetic Contactors
Provide magnetic contactors in accordance with NEMA ICS 1 and NEMA ICS 2 as required for the control of low-voltage, 60-Hz, tungsten-lamp loads, fluorescent-lamp loads, resistance-heating loads, and the primary windings of low-voltage transformers.
Provide core-and-coil assembly that operates satisfactorily with coil voltage between 85 percent and 110 percent of its voltage rating.
Provide contactors that are designed with a normally open holding-circuit
SECTION 26 05 71.00 40 Page 10 auxiliary contact for control circuits, with a rating in accordance with NEMA ICS 1 and NEMA ICS 2 .
Furnish solderless pressure wire terminal connectors, or make available for line and load connections to contactors in accordance with NEMA ICS 1 and NEMA ICS 2 .
Provide magnetic contactors with a rating in accordance with NEMA ICS 1 and NEMA ICS 2 .
2.2.4.2 Control-Circuit Transformers
Provide control-circuit transformers within the enclosure of magnetic contactors and motor controllers when the line voltage exceeds 120 V.
Provide an encapsulated dry-type, single-phase, 60-Hz transformer, with a 120 V (or 24 V) isolated secondary winding.
Do not provide a transformer with a rated primary voltage less than the rated voltage of the controller, or a rated secondary current less than the continuous-duty current of the control circuit.
Provide voltage regulation of the transformer such that, with rated primary voltage and frequency, the secondary voltage is not less than 95 percent nor more than 105 percent of rated secondary voltage.
Provide a source of supply for control-circuit transformers at the load side of the main disconnecting device. Protect the secondary winding of the transformer and control-circuit wiring against overloads and short circuits, with fuses selected in accordance with NEMA ICS 6 . Ground the secondary winding of the control-circuit transformer in accordance with
NEMA ICS 6 .
2.2.4.3 Magnetic Control Relays
Provide magnetic control relays for energizing and de-energizing the coils of magnetic contactors or other magnetically operated devices, in response to variations in the conditions of electric control devices in accordance with NEMA ICS 1 , and NEMA ICS 2 .
Ensure that the core-and-coil assembly operates satisfactorily with coil voltages between 85 percent and 110 percent of their voltage rating.
Provide relays that are designed to accommodate normally open and normally closed contacts.
Provide 120 V, 60-Hz, Class AIB magnetic control relays with a continuous--contact rating of 10 A, and with current-making and -breaking ability in accordance with NEMA ICS 1 and NEMA ICS 2 , two normally open and two normally closed.
2.2.4.4 Pushbuttons and Switches
a. Pushbuttons
For low-voltage AC full-voltage magnetic pushbutton controllers, provide heavy-duty, oiltight NEMA 250, Type 12 , momentary-contact devices rated 600 V, with pilot light, and with the number of buttons and the marking of identification plates as shown. Furnish pushbutton color code in accordance with NEMA ICS 6 .
SECTION 26 05 71.00 40 Page 11
Provide pushbuttons that are designed with normally open, circuit-closing contacts; normally closed circuit-opening contacts; and two-circuit normally open and normally closed circuit-closing and -opening contacts.
Ensure that pushbutton-contact ratings are in accordance with NEMA ICS 1 and NEMA ICS 2 , with contact designation A600.
Identify pushbuttons in remote-control stations with identification plates affixed to the front cover in a prominent location. Identify the system being controlled on the identification plate.
b. Selector Switches
Provide heavy-duty, oiltight, maintained-contact selector switches for low-voltage control circuits, with the number of positions and the marking of identification plates in accordance with NEMA ICS 1 and NEMA ICS 2 .
Identify selector switches in remote-control stations with engraved identification plates affixed to the front cover in a prominent location.
Identify the system being controlled on the identification plate.
c. Ammeter Selector Switches
Provide rotary, multistage, snap-action-type ammeter selector switches for switchgear in accordance with UL 20 . Use silver-plated contacts rated for 600 V, AC or DC. Provide a manually operated, four-position selector switch rated for 600 V, 20 A, minimum. Ensure that the switch is designed to select the display of current readings on each bus of the main bus from a single indicating instrument. Mount the ammeter switch on the hinged front panel of the switchgear compartment, with engraved escutcheon plate. Completely isolate the switch from high-voltage circuits.
Provide a pistol-grip -type selector switch handle.
d. Voltmeter Selector Switches
Provide rotary, snap-action-type voltmeter selector switches for switchgear in accordance with UL 20 . Use silver-plated contacts rated for 600 V AC or DC. Provide manually operated, four-position switches designed to select the display of voltage readings on each phase of the main bus from a single indicating instrument. Mount the voltmeter switch on the hinged front panel of the switchgear compartment, with engraved escutcheon plate. Completely isolate the switch from high-voltage circuits.
Provide a pistol-grip -type selector switch handle.
e. Miscellaneous Switches
Provide float, limit, door, pressure, proximity, and other types of switches in accordance with IPC D330 and of the types and classes indicated.
2.2.5 Finish
Protect metallic materials against corrosion. Provide equipment with the standard finish by the manufacturer when used for most indoor installations. For harsh indoor environments (any area subjected to chemical or abrasive action) and all outdoor installations.
SECTION 26 05 71.00 40 Page 12
2.3 COMPONENTS
2.3.1 Instrument Transformers
Comply with the interference requirements listed below, measured in accordance with IEEE C63.2 , and IEEE C63.4 for Instrument transformers.
Insulation Class kV
Basic Insulation
Level kV
Nominal System Voltage kV
Preferred Test
Voltage for
Potential Transformers kV
Test Voltage for Current Transformers kV
Radio Influence Voltage Level, Microvolts
Dry Oil Type Filled
0.6 10 ---- ---- 0.76 250 250
1.2 30 0.208
0.416 0.832 1.04
0.132 0.264 0.528 0.66
0.76 250 250
2.5 45 2.40 1.52 1.6
250 250
5.0 60 4.16 4.80
2.64 3.04
3.34 250 250
8.7 75 7.20 8.32
4.57 5.28
5.77 250 250
15L or 15H
95 - 110 12.00 12.47 14.40
7.62 7.92 9.14
9.41 1000 250
25 150 23.00 14.60 15.70 2500 650
34.5 200 34.50 21.90 23.0 ---- 650
46 250 46.00 29.20 29.30 ---- 1250
69 350 69.00 43.80 44.00 ---- 1250
92 450 92.00 58.40 58.40 ---- 2500
115 550 115.00 73.40 73.40 ---- 2500
138 650 138.00 88.00 88.00 ---- 2500
2.3.1.1 Current Transformers
Ensure that current transformers conform to IEEE C57.13 for installation in metal-clad switchgear. Use a standard 3-A secondary transformer.
Provide wound -type transformers.
SECTION 26 05 71.00 40 Page 13
Provide transformers that have single secondary winding.
Provide transformers that are complete with a secondary short-circuiting device.
For window-type current transformers, provide indoor, dry-type construction, with secondary current ratings as indicated with the specified burden, frequency, and accuracy.
2.3.1.2 Potential Transformers
For potential transformers, conform to IEEE C57.13 for installation in metal-clad switchgear. Use standard 120-volt secondary transformers.
Provide transformers that have single secondary winding.
Provide burden, frequency, and accuracy as required.
For disconnecting potential transformers with integral fuse mountings and current-limiting fuses, provide indoor, dry-type two-winding construction with primary and secondary voltage ratings as required.
2.3.2 Enclosures
2.3.2.1 Equipment Enclosures
Provide enclosures for equipment in accordance with NEMA 250.
Contain equipment that is installed in wet locations in a NEMA Type 4, watertight, corrosion-resistant, sheet-steel enclosure. Construct the enclosure to prevent entrance of water when tested in accordance with NEMA ICS 6 for Type 4 enclosures.
2.3.2.2 Remote-Control Station Enclosures
Provide remote-control station enclosures for pushbuttons, selector switches, and indicating lights in accordance with NEMA ICS 6 and NEMA 250.
Contain remote-control stations installed in wet locations in NEMA Type 4, watertight, corrosion-resistant, sheet-steel enclosures. Construct enclosures to prevent entrance of water when tested in accordance with NEMA ICS 6 and NEMA 250 for Type 4 enclosures.
Install remote-control stations with…