This Statement of Work (SOW) outlines the requirements for an indoor walk-in cooler for the Federal Brucellosis Laboratory (FBL) at the USDA's Animal and Plant Health Inspection Service (APHIS) in Frankfort, KY. The cooler must be 111" W x 94" L, with a maximum height of 80-98" depending on sprinkler placement, and maintain a temperature range of 2-10°C. Key specifications include a single door without a window, compatibility with a tile floor, electrical flexibility (20-amp 120V, 30-amp 220V, or wired connections), and various condensing unit placement options.

The pre-solicitation is set aside for small businesses with an estimated value under $25,000, using NAICS code 333415. The solicitation will be available on SAM around June 4, 2025, with delivery required by September 1, 2025. The vendor must verify cooler specifications with the Contracting Officer's Representative, provide all necessary installation parts, and potentially offer assembly and installation services. The cooler must be shipped unassembled through a 79"H x 47 3/4"W door opening and delivered to 105 Corporate Dr, Suite H, Frankfort, KY. Questions can be directed to Jim Roloff at james.g.roloff@usda.gov.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Statement of Work (SOW) for Indoor Walk-In Cooler Background

The Federal Brucellosis Laboratory (FBL), which is part of the United States Department of Agriculture (USDA), provides important surveillance of a variety of diseases that may infect cattle, swine, and sheep. The results of these tests help support the mission statements of the Animal Plant Health Inspection Services (APHIS) and USDA. Proper storage conditions for samples and testing reagents directly relate to the accuracy of test results.

Scope

The scope of this effort includes providing and installing an indoor walk-in cooler that fits inside a designated room within the FBL and maintains the required temperatures for storage of samples and testing reagents. For the FBL to provide accurate surveillance testing of its targeted diseases, samples and testing reagents must be stored at specific temperatures to maintain quality. The vendor should be able to provide an indoor walk-in cooler that meets all requirements of the FBL described in this SOW.

Tasks

1. The vendor must provide an indoor walk-in cooler that meets the following requirements:

· Maximum cooler dimensions of 111” W x 94” L

· Maximum cooler height of 80” (including top-mounted compressing unit if applicable) if placed directly under existing ceiling sprinklers.

· Maximum cooler height of 98” (including top-mounted compressing unit if applicable) if not placed directly under existing ceiling sprinklers.

· Must maintain a temperature range of 2-10(C considering room ambient temperature of 65-75(C.

· Must be capable of installation on tile floor.

· Must include one door with no window.

· Door must be oriented so that it is not obstructed by room walls.

· Must include a floor or include screed for floorless unit.

· Must either be able to (1) plug into an existing 20-amp 120-volt single phase outlet (2) plug into an existing 30-amp 220-volt single phase outlet or (3) have capability of wired connections installed by a licensed electrician, considering budget limitations.

· Must either (1) have a top-mounted condensing unit (self-contained or remote) that is suitable for the designated laboratory room considering a room ceiling height of 100” and clearance for existing sprinklers, (2) have a remote condensing unit suitable for roof installation considering the Place of Performance is two-stories, has no designated roof access, and considering the budget limitations regarding installation, or (3) have a side-mounted condensing unit that would not be inhibited by height restrictions or HVAC installation costs.

· Warranty must be included on panels and refrigeration system.

· Price of shipping must be included in the purchase.

· Must be shipped unassembled in parts that will be transportable through a 79"H x 47 3'4"W door opening.

· Must be able to be shipped to the Place of Performance considering that it has a ground-level garage door available but no ramp, loading dock, or pallet jack.

· Must be delivered no later than 9/1/2025.

2. The vendor must verify that all dimensions and specifications of indoor coolers quoted are truly suitable for the designated FBL laboratory room by communicating with the Contracting Officer’s Representative and FBL supervisory staff prior to contract finalization. Suitability will vary depending on the dimensions, orientation, placement of each specific indoor cooler unit quoted.

3. The vendor must (1) include all parts required for installation and/or (2) provide a complete list of all parts and tools needed for installation.

4. If able, the vendor shall provide assembly and installation services for the walk-in cooler.

· If the vendor is unable to provide assembly and installation services, contracted services must be acquired separately from the contract for purchasing the cooler.

· Assembly and installation services needed (such as a handyman, HVAC technician, or electrician) will vary depending on the specific cooler model contracted and the recommendations and requirements by the manufacturer of that specific model.

Delivery

The work will be performed at 105 Corporate Dr, Suite H, Frankfort, KY, 40601.