Illick Enabling Walters Hall Lab Relocations Drawings.pdf

PDF 5 MB Posted

Attached to
Illick Enabling Projects, Walters Hall Lab Relocations (Lab 202 and 322)
Solicitation number
2138452
Issued by
Onondaga County, New York

About this file

Summary of Illick Enabling Projects, Walters Hall Lab Relocations (Lab 202 and 322)

This document set contains contract construction drawings for the renovation of two laboratory spaces (Rooms 202 and 322) in Walters Hall at SUNY ESF, located at 1 Forestry Drive, Syracuse, New York 13210. The project involves comprehensive renovation work including partial demolition, removal and reinstallation of acoustical drop ceilings, new wall partitions, relocation of base cabinets from Baker Hall, installation of new countertops, sinks, and fume hoods, center lab counters and reagent shelving, new HVAC split systems with ductwork and controls, plumbing installations including piping in ceilings and lab spaces, electrical work involving new receptacles, ceiling-mounted electrical reels, relocated lighting, panels and circuiting, and associated related work. The construction classification is Type II-B for both laboratory spaces, with sprinkler coverage per NFPA 13. All work must comply with the 2025 Energy Conservation Construction Code of New York State and the Building Code of New York State. The drawings are dated January 27, 2026, with revisions dated May 2026, and were prepared by C&S Architects, Engineers & Landscape Architects, LLC and C&S Engineers, Inc., with project number 555.064.006.

The project includes specific contracting goals for minority and women business enterprises, with a 15 percent Minority Business Enterprise (MBE) goal, 15 percent Women Business Enterprise (WBE) goal, and a 6 percent Service-Disabled Veteran-Owned Business (SDVOB) goal. No Disadvantaged Business Enterprise (DBE) goal is specified. The contract documents indicate this is an alteration-level project (Level 2) at an existing educational facility and represent a comprehensive technical specification set including architectural, mechanical, plumbing, and electrical systems. The scope encompasses detailed drawings for life safety compliance, code conformance plans, demolition plans, floor plans with reflected ceiling plans, and comprehensive specifications for materials, equipment, and installation methods across all trades.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PLAN

NORTH

Copyright ©

CONTRACT DRAWINGS

FOR THE CONSTRUCTION OF

NO ALTERATION PERMITTED HEREON EXCEPT AS PROVIDED UNDER

SECTION 7209 SUBDIVISION 2 OF THE NEW YORK EDUCATION LAW

LOCATION MAP

TO THE BEST OF OUR KNOWLEDGE, INFORMATION AND BELIEF, THE

PLANS AND SPECIFICATIONS FOR THIS PROJECT ARE IN COMPLIANCE

WITH THE ENERGY CONSERVATION CONSTRUCTION CODE OF NEW

YORK STATE AND THE BUILDING CODE OF NEW YORK STATE

ILLICK ENABLING PROJECTS, WALTERS

HALL LAB RELOCATIONS (LAB 322)

SUNY ESF

1 FORESTRY DRIVE

SYRACUSE, NY 13210

JANUARY 27, 2026

G−001−322

C&S PROJECT NUMBER: 555.064.006

DRAWING LIST 322

G-001-322 COVER SHEET

G-101-322 THIRD FLOOR CODE COMPLIANCE PLAN

AD-103-322 DEMOLITION PLAN - LAB 322

A-001-322 GENERAL NOTES

A-103-322 FLOOR PLAN & REFLECTED CEILING PLAN - LAB 322

PD-101-322 PARTIAL SECOND AND THIRD FLOOR DEMOLITION PLANS - LAB 322

P-101-322 PARTIAL SECOND AND THIRD FLOOR PLANS - LAB 322

M-001-322. GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS

M-002-322 SPECIFICATIONS AND DETAILS

M-101-322 PARTIAL FLOOR PLANS LAB 322

E-001-322 GENERAL NOTES, SYMBOLS, ABBREVIATIONS, AND SCHEDULES

E-002-322 SPECIFICATIONS

E-101-322 LAB 322 POWER PLAN

E-501-322 DETAILS

MAY 2026

FLAMMABLE

CABINET

LARGE

STORAGE

CABINET

92'-9"

52'-2"

183'-0"

DIAGONAL: 54'-10"

COMMON PATH OF EGRESS TRAVEL (CPET) = 52'-2"

2025 NYSBC TABLE 410.5.3.3: 100 FEET MAX

EXIT ACCESS TRAVEL DISTANCE (EATD) = 183'-0"

2025 NYSBC TABLE 1017.2 SPRINKLERED 250 FEET MAX

LIFE SAFETY LEGEND

SYMBOL DESCRIPTION

EXIT ACCESS TRAVEL DISTANCE (EATD): DISTANCE TO EXITS FROM THE MOST REMOTE

POINT IN THE MOST REMOTE ROOM ON THE FLOOR

DARK GREY REPRESENTS 36" CLEAR ALONG PATH

LIGHT GREY PLUS DARK GREY REPRESENTS 44" CLEAR ALONG PATH

COMMON PATH OF EGRESS TRAVEL (CPET)

1 HOUR RATED ASSEMBLY (UL #U419)

EGRESS START POINT

E EA

E = ENCLOSED EXIT / EXIT TO EXTERIOR

EA = EXIT ACCESS

ED = EXIT DISCHARGE

HE = HORIZONTAL EXITED HE

FIRE EXTINGUISHER CABINET

AREA OF WORK

FEC

FX

REMOTENESS OF EXITS:

EXIT TO EXIT (D1)

BUILDING DIAGONAL (D2)

FIRE EXTINGUISHER (BRACKET)

FX

ACCESSIBLE ITEM:

ACCESSIBLE SEATING (WHEN LOCATED AT CHAIR)

ACCESSIBLE ENTRY (WHEN LOCATED AT DOOR)

FX

1.

2.

3.

FIRE EXTINGUISHER (UNDERCOUNTER):

FIRE EXTINGUISHER 1: (UNDERCOUNTER) - "COSMIC 5E" UL RATING 3A-40BC AS

MANUFACTURED BY JL INDUSTRIES - MOUNTING HEIGHT 12" TO BOTTOM OF FIRE

EXTINGUISHER

FIRE EXTINGUISHER 2: (UNDERCOUNTER) - "SATURN 1-A:K" UL RATING AS

MANUFACTURED BY JL INDUSTRIES MOUNTING HEIGHT 12" TO BOTTOM OF FIRE

EXTINGUISHER

NOTES: FX1 - UL RATING 2A-10BC

PROVIDE AND INSTALL FIRE EXTINGUISHER WHERE LOCATED ON PLAN.

EXTINGUISHER HEIGHTS PER LEGEND OR UNLESS NOTED OTHERWISE.

PROVIDE SHOP DRAWINGS FOR APPROVAL.

F FIRE ALARM

EXIT SIGNAGE (REFER TO ELECTRICAL DRAWINGS FOR SPECIFIED FIXTURE)

XXX'-X"

XXX'-X"

BASIC PROJECT INFORMATION (BUILDING DATA):

CONSTRUCTION CLASSIFICATION TYPE II-B

TABLE 601

OCCUPANCY BUSINESS - B

CHAPTER 3

SPRINKLER COVERAGE: NFPA13

FLOOR AREA (SECOND FLOOR): 9,985 SF [B-OCC, TYPE IIB CONSTRUCTION]

PROJECT AREA (SECOND FLOOR): 1,135 SF

EXITING REQUIREMENTS:

MINIMUM NUMBER OF EXITS:

PATH OF COMPLIANCE: NON-SEPARATED, MIXED

OCCUPANCY BUILDING

REFERENCED BUILDING CODES: 2025 EXISTING BUILDING CODE OF NYS

2025 FIRE CODE OF NYS

2025 PLUMBING CODE OF NYS

2025 MECHANICAL CODE OF NYS

2025 FUEL GAS CODE OF NYS

20205ENERGY CONSERVATION CONSTRUCTION CODE OF NYS

2017 ICC A117.1 ACCESSIBLE AND USABLE BUILDINGS

2010 ADA STANDARDS FOR ACCESSIBLE DESIGN

ALTERATION LEVEL: LEVEL 2

OCCUPANT LOAD LAB 202A: BUSINESS (B-OCC): 1,135sf / 150sf PER PERSON = 8 OCC

(1) PER LAB

BUSINESS (B-OCC) WITH OCCUPANT LOAD LESS THAN 50 REQUIRE

(1) EXIT.

805.4.1.1

PLAN

NORTH

NO ALTERATION PERMITTED HEREON

EXCEPT AS PROVIDED UNDER SECTION

7209 SUBDIVISION 2 OF THE NEW YORK

EDUCATION LAW

DESIGNED BY:

DRAWN BY:

CHECKED BY:

PROJECT NO:

DATE

DATE:

MARK

REVISIONS

DESCRIPTION

A

1 2 3

1 2 3

C

A

D

B

C

D

B

499 Col. Eileen Collins Blvd.

Syracuse, New York 13212

Phone: 315-455-2000 Fax: 315-455-9667 www.cscos.com

C&S Architects, Engineers & Landscape Architect, LLC

Copyright ©

LAB 322

JANUARY 27, 2026

A. TOWLES

A. TOWLES

M. LAMONTAGNE

555.064.006

THIRD FLOOR CODE

COMPLIANCE PLAN

G-101-322

ILL

IC

K

EN

AB

LIN

G

PR

OJ

EC

TS

, W

AL

TE

RS

HA

LL

LA

B

RE

LO

CA

TIO

NS

(L

AB

2)

SU

NY

E

SF

1 F

OR

ES

TR

Y

DR

IV

E

SY

RA

CU

SE

, N Y

SCALE: 1/8" = 1'-0"B1 THIRD FLOOR CODE COMPLIANCE PLAN

SCALE: NOT TO SCALEA4 KEY PLAN - THIRD FLOOR

SCALE: 1/4" = 1'-0"C4 LIFE SAFETY LEGEND

CC

DD

D3

D3

D12

D13

D13

D12

D8

D7

D8

D8

D8

SCALE: NOT TO SCALEB4 KEYED AND GENERAL DEMOLITION NOTES

GENERAL DEMOLITION NOTES

1 PROTECT/ MAINTAIN ALL EXISTING FIRE PROTECTION AND FIRE RESISTANCE RATED CONSTRUCTION 2 PROTECT ALL EXISTING FINISH SURFACES TO REMAIN. PATCH EXISTING CONSTRUCTION TO MATCH ADJACENT FINISHES IN THE CASE

OF REMOVALS AS REQUIRED BY THE WORK. ALL DAMAGE CAUSED BY THE CONTRACTOR, WHETHER INSIDE OR OUTSIDE THE CONTRACT LIMIT, SHALL BE REPLACED OR REPAIRED TO A LIKE NEW CONDITION AT NO ADDITIONAL COST TO THE OWNER

3 REMOVE EXISTING FLOORING AT AREAS DESIGNATED TO RECEIVE FLOORING. PROVIDE SMOOTH, FLUSH AND LEVEL FLOOR TO

EXTENT REQUIRED TO RECEIVE FINISHES. PATCH AND LEVEL FLOOR THROUGHOUT

4 REFER TO PLUMBING, MECHANICAL, AND ELECTRICAL, DRAWINGS FOR ELEMENTS TO BE DEMOLISHED WITHIN THE SCOPE OF THOSE

DISCIPLINES. COORDINATE DEMOLITION WITH THIS RELATED WORK

5 RECYCLE ALL METAL TO BE REMOVED INCLUDING, BUT NOT LIMITED TO; FRAMING, PIPE AND CEILING GRID

6 RECYCLE ALL ACOUSTIC CEILING PANELS TO BE REMOVED

7 RECYCLE ALL GYPSUM BOARD TO BE REMOVED

8 IT IS THE INTENT OF THE DEMOLITION PLAN TO SHOW THE GENERAL NATURE OF THE DEMOLITION SCOPE OF WORK. THE GENERAL

CONTRACTOR IS RESPONSIBLE FOR VISITING THE JOB SITE AND VERIFYING THE EXISTING CONDITIONS. THE GENERAL CONTRACTOR

SHALL NOTIFY THE ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES

9 COORDINATE AND VERIFY WITH THE OWNER ALL ITEMS TO BE SALVAGED PRIOR TO REMOVAL. THESE ITEMS MAY INCLUDE, BUT ARE NOT LIMITED TO, THE FOLLOWING: LIGHT FIXTURES, DOORS/FRAMES AND HARDWARE, CASEWORK, PLUMBING FIXTURES

10 MAINTAIN SEPARATION BETWEEN AREAS OUTSIDE THE SCOPE OF WORK BY PROVIDING PLASTIC SHEATHING BETWEEN SPACES

AND/OR TEMPORARILY TAPING OF JOINTS AND CAPS TO

PREVENT DUST MIGRATION

11 DISPOSE OF ALL DEMOLISHED OR REMOVED MATERIALS LEGALLY OFF THE SITE. COMPLY WITH ALL LOCAL HAULING AND DISPOSAL

REQUIREMENTS

12 UTILITIES TO REMAIN IN SERVICE DURING DEMOLITION SHALL BE MAINTAINED AND PROTECTED AGAINST DAMAGE 13 SCHEDULE ALL SERVICE SHUT-DOWNS WITH THE OWNER. NOTIFY THE OWNER A MINIMUM TIME OF ONE (1) WEEK AND ADDITIONALLY

ONE (1) HOUR PRIOR TO SHUT DOWNS

14 UPON COMPLETION, CLEAN THE ENTIRE WORK AREA TO A TIDY, UNIFORM CONDITION; REMOVING ALL DEBRIS, DUST PARTITIONS AND

ASSOCIATED MATERIALS USED DURING DEMOLITION. CLEAN ALL AREAS IMPACTED BY DEMOLITION, INCLUDING BUT NOT LIMITED TO, ADJACENT OCCUPIED AREAS AND AREAS NOT WITHIN THE SCOPE OF WORK

15 ABANDONMENT OF ITEMS OR UNUSED UTILITIES IN PLACE IS STRICTLY PROHIBITED, UNLESS SPECIFICALLY PERMITTED BY OWNER 16 DISPOSAL OF ALL DEBRIS AND DEMOLISHED MATERIALS SHALL BE CONTRACTORS RESPONSIBILITY. DEBRIS REMOVAL SHALL BE

PROMPT AND GENERAL CLEAN-UP SHALL OCCUR DAILY

17 FIRE AND SMOKE DETECTION DEVICES SHALL REMAIN OPERATIONAL DURING DEMOLITION AND CONSTRUCTION. PROTECT FIRE AND

SMOKE DETECTION DEVICES FROM DUST, DAMAGE AND DEBRIS

18 IT IS THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE SELECTIVE DEMOLITION WORK AND ALL NEW WORK TO ASSURE THAT THE

BUILDING REMAINS WEATHERTIGHT. PROVIDE TEMPORARY PROTECTION AS NEEDED

19 CLEAN AND PREPARE ALL EXISTING SURFACES TO REMAIN AS REQUIRED TO PREAPRE FOR PROPOSED FINISHES 20 IT IS NOT EXPECTED THAT HAZARDOUS MATERIALS WILL BE ENCOUNTERED IN THE WORK. IF SUSPECTED HAZARDOUS MATERIALS

ARE ENCOUNTERED, DO NOT DISTURB; IMMEDIATELY NOTIFY ARCHITECT AND OWNER

NO ALTERATION PERMITTED HEREON

EXCEPT AS PROVIDED UNDER SECTION

7209 SUBDIVISION 2 OF THE NEW YORK

EDUCATION LAW

DESIGNED BY:

DRAWN BY:

CHECKED BY:

PROJECT NO:

DATE

DATE:

MARK

REVISIONS

DESCRIPTION

A

1 2 3

1 2 3

C

A

D

B

C

D

B

499 Col. Eileen Collins Blvd.

Syracuse, New York 13212

Phone: 315-455-2000 Fax: 315-455-9667 www.cscos.com

C&S Architects, Engineers & Landscape Architect, LLC

Copyright ©

LAB 322

JANUARY 27, 2026

A. TOWLES

A. TOWLES

M. LAMONTAGNE

555.064.006

DEMOLITION PLAN -

LAB 322

AD-103-322

ILL

IC

K

EN

AB

LIN

G

PR

OJ

EC

TS

, W

AL

TE

RS

HA

LL

LA

B

RE

LO

CA

TIO

NS

(L

AB

2)

SU

NY

E

SF

1 F

OR

ES

TR

Y

DR

IV

E

SY

RA

CU

SE

, N Y

SCALE: 1/4" = 1'-0"C1 DEMOLITION PLAN - LAB 322 0 16'8'4'

PLAN

NORTH

KEYED DEMOLITION NOTES 322

D3 REMOVE CASEWORK

D7 PROTECT EXISTING CEILING DURING DEMOLITION

D8 EXISTING TRENCH DRAIN TO BE CLEANED. COORD. WITH PLMG. DWG.

D12 REMOVE WALL CABINET

D13 REMOVE STEEL STRUCTURE DOWN TO CONCRETE SLAB

SCALE: NOT TO SCALEA4 KEY PLAN - THIRD FLOOR

A

AFF ABOVE FINISHED FLOOR

ACT ACOUSTICAL CEILING TILE

AMP ACOUSTICAL METAL PANEL

ALUM ALUMINUM

L ANGLE

B

BLK BLOCK

BD BOARD

BOT BOTTOM

BLDG BUILDING

BL BUILDING LINE

C

CPT CARPET

CLKG CAULK(ING)

CLG CEILING

CBB CEMENTITIOUS BACKER BOARD

CTR CENTER

CL CENTER LINE

CT CERAMIC TILE

CB CHALKBOARD

CLR CLEAR / CLEARANCE

CLOS CLOSET

COL COLUMN

CONC CONCRETE

CMU CONCRETE MASONRY UNIT

CONT CONTINUOUS

CJ CONTROL JOINT

CG CORNER GUARD

CORR CORRIDOR

CTR COUNTER

CRS COURSE(S)

CW CURTAINWALL

D

DEMO DEMOLISH / DEMOLITION

DET DETAIL

DIA DIAMETER

DIM DIMENSION

DIS DISPENSER

DN DOWN

DWG DRAWING

DF DRINKING FOUNTAIN

E

EA EACH

ELEC ELECTRIC

EWC ELECTRIC WATER COOLER

EL ELEVATION

ELEV ELEVATOR

ENCL ENCLOSURE

ENTR ENTRANCE

ENTR GRL ENTRANCE GRILLE

EQ EQUAL

EQUIP EQUIPMENT

EXH EXHAUST

EXIST EXISTING

ETR EXISTING TO REMAIN

EXP EXPANSION

EJ EXPANSION JOINT

EXP EXPOSED

EXT EXTERIOR

F

FOF FACE OF FINISH

FOM FACE OF MASONRY

FOS FACE OF STUDS

FOW FACE OF WALL

F/F FACE TO FACE

FT FEET/FOOT

FRP FIBER REINFORCED

POLYESTER / PLASTIC

FGL FIBERGLASS

FIN FINISH(ED)

FF FINISH FLOOR

FIN GR FINISH GRADE

FA FIRE ALARM

FEC FIRE EXTINGUISHER CABINET

FHC FIRE HOSE CABINET

FP FIRE PROTECTION

FRT FIRE RETARDANT

FP FIREPROOF

FIXT FIXTURE

FLASH FLASHING

FLR FLOOR

FD FLOOR DRAIN

FTG FOOTING

FDTN FOUNDATION

FURN FURNITURE

FBO FURNISHED BY OTHERS

FURG FURRED(ING)

G

GA GAGE / GAUGE

GALV GALVANIZED

GC GENERAL CONTRACTOR

GL GLASS

GL BLK GLASS BLOCK

GL TL GLASS TILE

GB GRAB BAR

GR GRADE

GRL GRILLE

GYP BD GYPSUM BOARD

H

HCP HANDICAPPED

HNDRL HANDRAIL

HDWD HARDWOOD

HT HEIGHT

HP HIGH POINT

HM HOLLOW METAL

I

IRWC IMPACT RESISTANT WALL

COVERING

ID INSIDE DIAMETER

IMWP INSULATED METAL WALL PANEL

INSUL INSULATION / INSULATED

IG INSULATING GLASS

ISG INSULATING SPANDREL

GLAZING

ITG INSULATING TEMPERED GLASS

INT INTERIOR

J

JC JANITOR'S CLOSET

K

KD KNOCKDOWN

L

LAM LAMINATE

LAV LAVATORY

L LENGTH / LONG

LF LINEAL FEET

LG LAMINATED GLASS

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

LPT LOW POINT

M

MFR MANUFACTURER

MO MASONRY OPENING

MATL MATERIAL

MAX MAXIMUM

MECH MECHANICAL

MTL METAL

MEZZ MEZZANINE

MIN MINIMUM

N

NOM NOMINAL

NA NOT APPLICABLE

NIC NOT IN CONTRACT

NO NUMBER

NTS NOT TO SCALE

O

OC ON CENTER

OPNG OPENING

OPP OPPOSITE

OD OUTSIDE DIAMETER

OH OVERHEAD

OSB ORIENTED STRAND BOARD

P

P PAINT

PR PAIR

PTD PAPER TOWEL DISPENSER

PBD PARTICLE BOARD

PTN PARTITION

PLAS PLASTIC

PLAM PLASTIC LAMINATE

PLBG PLUMBING

PLYWD PLYWOOD

POL POLISHED

POL CONC POLISHED CONCRETE

PVC POLYVINYL CHLORIDE

PEMB PRE-ENGINEERED METAL

BUILDING

PT PRESSURE TREATED

Q

QT QUARRY TILE

QTZ QUARTZ

R

R RADIUS (DIM)

RCP REFLECTED CEILING PLAN

REINF REINFORCE

REQD REQUIRED

RB RESILIENT BASE

RF RESILIENT FLOORING

REV REVISION / REVISED

R RISER(S)

RD ROOF DRAIN

RL ROOF LEADER

RTU ROOF TOP UNIT

RM ROOM

RO ROUGH OPENING

RBR RUBBER

S

SCH SCHEDULE(D)

SLNT SEALANT

SLR SEALER

SECT SECTION

SHTHG SHEATHING

SIM SIMILAR

SD SOAP DISPENSER

SAFB SOUND ATTENUATION

FIBERGLASS BATT

SPEC SPECIFICATION

SF SQUARE FEET OR

STOREFRONT

STN STAIN

SS SOLID SURFACE

SST STAINLESS STEEL

STL STEEL

STOR STORAGE

STRUCT STRUCTURAL

SUSP SUSPENDED

SYS SYSTEM

T

TB TACK BOARD

TG TEMPERED GLASS

TERR TERRAZZO

TFL THERMALLY FUSED LAMINATE

THK THICKNESS

THRES THRESHOLD

TL TILE

TPTN TOILET PARTITION

T&B TOP AND BOTTOM

T/O TOP OF

TOS TOP OF STEEL/SLAB

TOW TOP OF WALL

T&G TONGUE AND GROOVE

T TREAD(S)

TYP TYPICAL

U

UC UNDER CUT

UNFIN UNFINISHED

UON UNLESS OTHERWISE NOTED

V

VB VAPOR BARRIER

VR VAPOR RETARDER

VTR VENT THROUGH ROOF

VIF VERIFY IN FIELD

VERT VERTICAL

VEST VESTIBULE

VCT VINYL COMPOSITION TILE

VWB VINYL WALL BASE

VWC VINYL WALL COVERING

VP VISION PANEL

W

WSCT WAINSCOT

W CAB WALL CABINET

W (CON'T)

WC WATER CLOSET

W WIDE

WG WIRE GLASS

W/ WITH

WM WIRE MESH

WD WOOD

WBL WOOD BLOCKING

A-101 A1

SIM

A

ROOM NAME

150 SF

A1 / A-101 VIEW REFERENCE

LEVEL REFERENCE

DETAIL CALLOUT

WALL SECTION

BUILDING SECTION

INTERIOR ELEVATION

EXTERIOR ELEVATION

STRUCTURAL GRID

DESCRIPTIONSYMBOL

ROOM TAG

DOOR TAG

WINDOW TAG

REVISION TAG

STRUCTURAL GRID LINE

FINISHED SURFACE LINE

DEMOLITION LINE

OVERHEAD/HIDDEN LINE

DESCRIPTIONSYMBOL

A1 A-101

SIM

A1 A-101

SIM

A1 A-101

SIM

A1 A-101

SIM

WALL TAG

(SHOWING DIM WHEN NOT TO DECK)

MA3

15'-10" MA3

CONSTRUCTION TO

BE DEMOLISHED

EXISTING CONSTRUCTION

TO REMAIN NEW CONSTRUCTION

FIXTURES & ACCESSORIES LEGEND

FIRE EXTINGUISHER

FIRE EXTINGUISHER CABINET

A52

A53

CLOCKA57

A58

A59

WALL MOUNTED EXIT SIGN

LIGHTING CONTROL SWITCH

A60

A61

OUTLET ABOVE COUNTER

A62

OUTLET AT FLOOR

A63 SPEAKER

TELEPHONE / INTERCOM

NOTE: REFER TO MATERIALS & ACCESSORIES

LEGEND FOR PRODUCT INFORMATION

1'

- 6

"VA

RI

ES

8"

COUNTERTOP

A60

A61

EQ

EQ

6" MAX

7'

- 0

4" M

IN

1'- 0"

M

AX

6'- 8"

8'-

0"

7'

- 6

OP

ER

AB

LE

P

AR

T 4'

- 0

A59 A62 A66

A63 A64A65 A67

A58 A57

NOMINAL 8'

CEILING HEIGHT

4'

- 6

" M

AX

4'

- 8

" M

AX

A52 A53

A64 FA SYSTEM A/V DEVICE

A65 SMOKE / HEAT DETECTOR

A66 MANUAL PULL STATION

A67 EMERGENCY LIGHT

SCALE: NOT TO SCALEC3 GENERAL NOTES

SCALE: NOT TO SCALEA3 SYMBOLS LEGEND SCALE: NOT TO SCALEA4 ABBREVIATIONS LIST

GENERAL NOTES

1 DIMENSIONS NOTED "EQ" ARE EQUAL TO EACH OTHER ONLY IF THEY ARE ON THE SAME DIMENSION STRING AND IN THE SAME ROW 2 DO NOT SCALE DRAWINGS TO OBTAIN DIMENSIONS. REFER TO DRAWINGS FOR DIMENSIONS. REQUIRED CRITICAL DIMENSIONS NOT

FOUND SHOULD BE FIELD VERIFIED OR OBTAINED FROM ARCHITECT. VERIFY ALL DIMENSIONS AND CONDITIONS IN FIELD (EXISTING AND PROPOSED CONSTRUCTION) AND BRING ANY DISCREPANCIES TO THE IMMEDIATE ATTENTION OF THE ARCHITECT

3 ROOM NUMBERING IS FOR CONSTRUCTION PURPOSES ONLY. ACTUAL ROOM NUMBERING TO BE COORDINATED WITH OWNER

PRIOR TO ANY SCHEDULING OR LABELING

4 PROVIDE BLOCKING OR PROVISIONS FOR SOLID ANCHORAGE AT WALL AND CEILING MOUNTED EQUIPMENT AND ACCESSORIES

PROVIDED UNDER THIS CONTRACT AND EQUIPMENT TO BE PROVIDED BY THE OWNER

5 MAINTAIN EXISTING FIRE PROOFING AND FIRE RATED CONSTRUCTION. PATCH AS NEEDED TO MEET REQUIREMENTS AS PER CODE

CONFORMANCE DRAWINGS

6 REFER TO CODE CONFORMANCE DRAWINGS FOR REQUIRED FIRE RATED CONSTRUCTION

7 ALL DIMENSIONS ARE TO FACE OF FRAMING, FACE OF MASONRY UNIT, OR FINISHED FACE OF EXISTING CONSTRUCTION 8 VERIFY ALL DIMENSIONS IN THE FIELD. NOTIFY THE ARCHITECT OF ANY DISCREPANCIES BETWEEN CONTRACT DOCUMENTS AND

FIELD CONDITIONS

9 EXTEND ALL PARTITIONS FROM FLOOR TO UNDERSIDE OF DECK ABOVE UNLESS OTHERWISE INDICATED. MAKE THIS JOINT SMOKE

TIGHT AND FIRESTOP AT RATED PARTITIONS

10 DOCUMENTS ARE BASED UPON ORIGINAL CONSTRUCTION DRAWINGS, EXISTING CONDITIONS MAY VARY. CONTACT ARCHITECT IF

DISCREPANCIES ARISE

11 PROTECT ALL EXISTING FINISH SURFACES TO REMAIN. PATCH EXISTING CONSTRUCTION TO MATCH ADJACENT FINISHES TO

REMAIN AT ALL REMOVALS AND AS REQUIRED BY NEW WORK. ALL DAMAGE CAUSED BY THE CONTRACTOR, WHETHER INSIDE OR OUTSIDE THE CONTRACT LIMIT, SHALL BE REPLACED OR REPAIRED TO A LIKE NEW CONDITION AT NO ADDITIONAL COST TO THE

OWNER

12 PROVIDE ACCESS PANELS AS REQUIRED AT ALL WALLS AND CEILINGS AT ALL VALVES, DAMPERS, CONCEALED JUNCTION BOXES, AND OTHER EQUIPMENT REQUIRING MAINTENANCE, ADJUSTMENTS OR SERVICING

13 THE TERM "WALL" AND "PARTITION" ARE USED INTERCHANGEABLY

14 PROVIDE METAL STUD INSERT BLOCKING AT ALL WALLS RECEIVING WALL MOUNTED EQUIPMENT AND/OR ACCESSORIES.

COORDINATE WITH ALL TRADES AND OWNER EQUIPMENT LAYOUTS

15 SEE PARTITION TYPES FOR LOCATIONS OF ACOUSTIC AND THERMAL INSULATION

16 ALL GYPSUM WALL BOARD SHALL BE INSTALLED VERTICALLY WITH JOINTS STAGGERED WHERE THERE ARE TWO LAYERS. ALL

GYPSUM BOARD IN FIRE RATED PARTITIONS TO COMPLY WITH LISTED UL ASSEMBLY

17 FIRE TAPE, SMOKE TIGHT, ALL GYPSUM WALL BOARD VENEER ABOVE CEILING OR OTHERWISE CONCEALED 18 INTERIOR WALL TYPES ARE SHOWN ON THE FLOOR PLANS AND/OR DETAILS USING WALL TYPE SYMBOL (REFER TO SYMBOLS

LEGEND)

19 PROVIDE ACOUSTICAL SEALANT AT ALL PARTITION PERIMETERS, RUNNERS, ELECTRICAL OUTLETS, PENETRATIONS AND OPENINGS.

TO MINIMIZE SOUND TRANSMISSION, ELECTRICAL OUTLETS SHALL BE SEPARATED BY A MINIMUM OF ONE STUD, BACK TO BACK 20 PROVIDE GYPSUM WALL BOARD CONTROL JOINTS WHERE ANY OF THE FOLLOWING CONDITIONS EXIST: (A) PARTITIONS OR

CEILINGS OF DISSIMILAR CONSTRUCTION MEET AND REMAIN IN THE SAME PLANE AND/OR (B) EXPANSION OR CONTROL JOINTS OCCUR IN THE BUILDING STRUCTURE OR WALL CONSTRUCTION AND/OR (C) GYPSUM BOARD PARTITIONS WHERE THE SURFACE EXCEEDS A LENGTH OF 30' MAXIMUM IN ANY DIRECTION AND/OR (D) GYPSUM BOARD CEILINGS WHERE THE SURFACE EXCEEDS A LENGTH OF 50' MAXIMUM IN ANY DIRECTION (WITH PERIMETER RELIEF) OR 30' MAXIMUM IN ANY DIRECTION (WITHOUT PERIMETER

RELIEF)

NO ALTERATION PERMITTED HEREON

EXCEPT AS PROVIDED UNDER SECTION

7209 SUBDIVISION 2 OF THE NEW YORK

EDUCATION LAW

DESIGNED BY:

DRAWN BY:

CHECKED BY:

PROJECT NO:

DATE

DATE:

MARK

REVISIONS

DESCRIPTION

A

1 2 3

1 2 3

C

A

D

B

C

D

B

499 Col. Eileen Collins Blvd.

Syracuse, New York 13212

Phone: 315-455-2000 Fax: 315-455-9667 www.cscos.com

C&S Architects, Engineers & Landscape Architect, LLC

Copyright ©

JANUARY 27, 2026

A. TOWLES

A. TOWLES

M. LAMONTAGNE

555.064.006

GENERAL NOTES

A-001-322

ILL

IC

K

EN

AB

LIN

G

PR

OJ

EC

TS

, W

AL

TE

RS

HA

LL

LA

B

RE

LO

CA

TIO

NS

(L

AB

2)

SU

NY

E

SF

1 F

OR

ES

TR

Y

DR

IV

E

SY

RA

CU

SE

, N Y

SCALE: 3/8" = 1'-0"D1 TYPICAL ACCESSORIES AND DEVICES MOUNTING HEIGHTS LAB 322

REF.REF. REF.

LARGE

STORAGE

CABINET

FLAMMABLE

CABINET

CC

DD

N1

N1

N1

N1N3

N3

N43' - 3" 4' - 3"

5' - 2" 4' - 8" 5' - 2" 5' - 0" 5' - 2 3/4"

A

B

A

M

C

D

E

F F

E

D

C G

L

JJ

K

G

G

A

B

AN2

N6

N7 N7

N7N7

N8

N5 N5 N5 N5 N5

ALIGN

N5

N9

N10

0 16'8'4'

PLAN

NORTH

SCALE: NOT TO SCALEA4 KEY PLAN - THIRD FLOOR

SCALE: NOT TO SCALEC4 KEYED NOTES

NO ALTERATION PERMITTED HEREON

EXCEPT AS PROVIDED UNDER SECTION

7209 SUBDIVISION 2 OF THE NEW YORK

EDUCATION LAW

DESIGNED BY:

DRAWN BY:

CHECKED BY:

PROJECT NO:

DATE

DATE:

MARK

REVISIONS

DESCRIPTION

A

1 2 3

1 2 3

C

A

D

B

C

D

B

499 Col. Eileen Collins Blvd.

Syracuse, New York 13212

Phone: 315-455-2000 Fax: 315-455-9667 www.cscos.com

C&S Architects, Engineers & Landscape Architect, LLC

Copyright ©

LAB 322

MAY 1, 2026

A. TOWLES

A. TOWLES

M. LAMONTAGNE

555.064.006

FLOOR PLAN &

REFLECTED CEILING

PLAN - LAB 322

A-103-322

ILL

IC

K

EN

AB

LIN

G

PR

OJ

EC

TS

, W

AL

TE

RS

HA

LL

LA

B

RE

LO

CA

TIO

NS

(L

AB

2)

SU

NY

E

SF

1 F

OR

ES

TR

Y

DR

IV

E

SY

RA

CU

SE

, N Y

0 16'8'4'

PLAN

NORTH

SCALE: 1/4" = 1'-0"C1 FLOOR PLAN - LAB 322

KEYED NOTES 322

N1 FURNISH AND INSTALL COUNTERTOP. EPOXY COUNTERTOP BASIS OF DESIGN: DURCON, SOLID EPOXY RESIN, BLACK W/ INTEGRATED

6" BACKSPLASH

N2 CLEAN AND SEAL CONCRETE SLAB

N3 FURNISH AND INSTALL FUME HOOD, COORD. COORD. W/ MECH., ELEC., & PLMG.

N4 INSTALL LAB SINK AND FAUCET PROVIDED BY CAMPUS, COORD. W/ PLMG. DWG.

N5 EQUIPMENT PROVIDED AND INSTALLED BY OWNER.

N6 INSTALL NEW REAGENT SHELVING, COORD. W/ MECH., ELEC., & PLBG. BASIS OF DESIGN: MOTT MANUFACTURING, SIGMA FLEX

SYSTEM. W/ INSERT PANELS, 12"D OPEN SHELVING

N7 EXISTING TRENCH DRAIN, COORD. W/ PLMG.

N8 COORDINATE LIGHT FIXTURES WITH REAGENT SHELVING

N9 PATCH AND REPAIR WALL, PAINT

N10 PROVIDE (2) DECK MOUTNED NEEDLE VALVES. COORD. LOCATION WITH PLMG. BASIS OF DESIGN: WATERSAVER, LABORATORY BALL

VALVE, DECK MOUNTED

SCALE: NOT TO SCALEC4 GENERAL FINISH NOTES

GENERAL FINISH NOTES 322

1 ALL WALLS TO BE PAINTED TO MATCH ADJACENT EXISTING

2 PAINT ALL PREVIOUSLY PAINTED SURFACES WITHIN LAB 322

3 ALL WALL BASE TO MATCH ADJACENT EXISTING

4 ALL FLOORING MATERIAL AND TRANSITIONS SHALL BE CENTERED UNDER THE DOOR IN THE CLOSED POSITION UNLESS

OTHERWISE NOTED

5 EXTEND ALL FINISHES UNDER CABINETS, BENCHES, SHELVING, COUNTERTOPS AND LAVATORIES 6 MISCELLANEOUS ELECTRICAL PANEL COVERS, GRILLES, ETC. TO BE PAINTED TO MATCH ADJACENT WALL SURFACES, UNLESS

OTHERWISE NOTED

7 ALL METAL UNDER-COUNTER SUPPORT BRACKETS TO BE PAINTED TO MATCH ADJACENT WALL FINISH 8 COORDINATE REMOVAL AND RELOCATION OF ALL EXISTING MOVEABLE EQUIPMENT WITH OWNER

CASEWORK SCHEDULE 322

MARK WIDTH DEPTH HEIGHT FURNISHED BY: INSTALLED BY

A 4' - 0" <varies> 2' - 10" OWNER CONTRACTOR B 4' - 0" <varies> 2' - 10" OWNER CONTRACTOR

C 3' - 0" 1' - 11" 2' - 10" OWNER CONTRACTOR

D 3' - 0" 1' - 11" 2' - 10" OWNER CONTRACTOR

E 3' - 0" 1' - 11" 2' - 10" OWNER CONTRACTOR

F 3' - 0" 1' - 11" 2' - 10" OWNER CONTRACTOR

G 4' - 0" 1' - 11" 2' - 10" OWNER CONTRACTOR

J 4' - 0" 2' - 5" 2' - 10" OWNER CONTRACTOR

K 3' - 0" 1' - 11" 2' - 10" OWNER CONTRACTOR

L 3' - 0" 1' - 11" 2' - 10" OWNER CONTRACTOR

M 4' - 0" 1' - 11" 2' - 10" OWNER CONTRACTOR

CAP

1/2" A

6" FROM TRENCH DRAIN

(TYP 5)

1/2" HW UP

1/2" CW UP

3/4" CW UP

3/4" HW UP

1/2" A UP

B

C

D

16 17 18 19 20 22

AW

A W

G A

V

CW

CAP

CAP

1/2" CW UP

G A

V

CW

DW DW

AW

B

C

D

16 17 18 19 20 22

CONNECT TO EXISTING

DISCONNECT FROM EXISTING

PIPE BREAK/CONTINUATION

ISOLATION VALVE

PIPE DOWN

PIPE UP

DEMOLITION WORK

EXISTING WORK

NEW WORK

COMPRESSED AIRA

COLD WATERCW

HOT WATERHW

DISTILLED WATERDW

WASTEW

EXISTING(E)

ACID WASTEAW

HOT WATER RE-CIRCHWRC

GASG

VACUUMV

CONTRACTOR SHALL VERIFY ALL CONDITIONS

ON JOB SITE & NOTIFY THE OWNER OF ANY

VARIATIONS FROM DIMENSIONS SHOWN ON

THESE DRAWINGS BEFORE PROCEEDING WITH

ANY CONSTRUCTION.

DESIGNED BY:

DRAWN BY:

CHECKED BY:

PROJECT NO:

DATE

DATE:

MARK

REVISIONS

DESCRIPTION

A

1 2 3

1 2 3

C

A

D

B

C

D

B

Copyright ©

2940 Hebron Park Drive, Suite 216 Hebron, Kentucky 41048

Phone: 859-283-4450 www.cscos.com

C&S Engineers, Inc.

IL

LI

C K

E N

A B

LI

N

G P

R O

JE

C

T S

, W A

LT

E

R S

H

LL

L A

B R

E

LO

C A

T

IO

N S

LA

B

F

O R

E S

T R

Y D

R

IV

E

S Y

R A

C U

S E

N

Y

LAB 322

MAY 2026

E. COHEN

L. J. MERRY

K. L. PIERCE, PE

555.064.006

PARTIAL SECOND AND

THIRD FLOOR

DEMOLITION PLANS -

LAB 322

PD-101-322

0 16'8'4'

0 16'8'4'

SCALE: NOT TO SCALE

B4 KEYED NOTES

SCALE: NOT TO SCALE

A4 KEY PLAN

SCALE: 3/16" = 1'-0"

A1 PARTIAL SECOND FLOOR DEMOLITION PLAN

SCALE: 3/16" = 1'-0"

C1 PARTIAL THIRD FLOOR DEMOLITION PLAN - LAB 322

REMOVE CW PIPE, CAP AT POINT SHOWN IN SECOND FLOOR CEILING.

REMOVE 3/4" CW, 3/4" HW AND 1/2" A PIPES. CAP AT POINTS SHOWN IN

SECOND FLOOR CEILING.

1/2" CW AND 1/2" HW TO REMAIN.

EXISTING TRENCH FLOOR DRAIN TO REMAIN.

REMOVE HW AND CW UP TO WALL FAUCET. CAP AT MAINS.

REMOVE WALL FAUCET.

SCALE: NOT TO SCALE

C4 SYMBOLS AND ABBREVIATIONS

B

C

D

16 17 18 19 20 22

1/2" V & 1/2" A DN

B

C

D

16 17 18 19 20 22

6" FROM TRENCH DRAIN

(TYP 5)

1/2" HW UP (E)

1/2" CW UP (E)

AW

A W

G A

V

CW

G A

V

CW

DW DW

AW

CO

1/2" A 1/2" V

1/2" CW

1-1/4"AW

1/2" V & 1/2" A UP

1/2" DW UP

TO SINK

1/2" A UP

1/2" A

1/2" V

1/2" A UP

1/2" V UP

1/2" A

PIPING

• CW, VAC. & AIR: TYPE L COPPER TUBING, WROUGHT COPPER FITTINGS.

• DISTILLED WATER (DW): PIPE MATERIAL TO MATCH EXISTING.

SHUT-OFF VALVES

• VAC. & AIR: COPPER-ALLOY BALL VALVES, 3 PIECE BODY, STANDARD MSS SP-110.

• DW: BALL VALVES, STANDARD MSS SP-122 VALVES TO BE THE SAME MATERIAL AS PIPING

TO WHICH THEY ARE CONNECTED.

LAB FIXTURES

• VACUUM / AIR: DECK MOUNTED SINGLE OUTLET EQUAL TO WATERSAVER MODEL L2800-131WSA.

PIPING LEAK TESTS

• VAC. & AIR: TEST NEW AND MODIFIED PARTS OF EXISTING PIPING, CAP AND FILL PIPING WITH

OIL-FREE DRY NITROGEN TO PRESSURE OF 150 PSIG. ISOLATE TEST SOURCE AND LET STAND

FOR FOUR HOURS TO EQUALIZE TEMP. REFILL SYSTEM IF REQUIRED, HOLD FOR TWO HOURS WITH

NO PRESSURE DROP.

• CW & DW PIPING: HYDROSTATIC TEST; TEST PIPING AT 50 PSIG. HOLD TEST FOR TWO HOURS. PRESSURE SHALL

REMAIN CONSTANT WITHOUT PUMPING.

PIPE HANGERS

• HORIZONTAL PIPING HANGERS; ADJUSTABLE STEEL CLEVIS HANGERS AT MAXIMUM 6 FEET SPACING.

NO ALTERATION PERMITTED HEREON

EXCEPT AS PROVIDED UNDER SECTION

7209 SUBDIVISION 2 OF THE NEW YORK

EDUCATION LAW

DESIGNED BY:

DRAWN BY:

CHECKED BY:

PROJECT NO:

DATE

DATE:

MARK

REVISIONS

DESCRIPTION

A

1 2 3

1 2 3

C

A

D

B

C

D

B

499 Col. Eileen Collins Blvd.

Syracuse, New York 13212

Phone: 315-455-2000 Fax: 315-455-9667 www.cscos.com

C&S Engineers, Inc.

Copyright ©

IL

LI

C K

E N

A B

LI

N

G P

R O

JE

C

T S

, W A

LT

E

LL

L A

B R

E

LO

C A

T

IO

N S

LA

B

F

O R

E S

T R

Y D

R

IV

E

S Y

R A

C U

S E

N

Y

LAB 322

MAY 2026

E. COHEN

L. J. MERRY

K. L. PIERCE, PE

555.064.006

PARTIAL SECOND AND

FLOOR PLANS - LAB 322

P-101-322 0 16'8'4'

0 16'8'4'

SCALE: 3/16" = 1'-0"

C1 PARTIAL THIRD FLOOR PLAN - LAB 322

SCALE: NOT TO SCALE

C4 SPECIFICATIONS

SCALE: NOT TO SCALE

A4 KEY PLAN

PROVIDE 1/2" CW, 1/2"A, 1/2"V AND 1-1/4"AW UP TO FUME HOODS.

EXTEND 1/2" CW AND 1/2" HW TO NEW SINK.

EXISTING TRENCH DRAIN.

SINK PROVIDED BY CAMPUS.

PROVIDE 1/2" V & 1/2" A UP TO REAGENT CABINETRY FAUCET SETS.

ONE VAC. & ONE AIR OUTLET MOUNT ON COUNTERTOP. LOCATE PIPING

IN CHASEWAY BEHIND CABINETRY.

PROVIDE 1/2"-A ON WALL ABOVE COUNTERTOP. CONNECT TO EXISTING

EQUIPMENT.

SCALE: 3/16" = 1'-0"

A1 PARTIAL SECOND FLOOR PLAN - LAB 322

SCALE: NOT TO SCALE

B4 KEYED NOTES

AAD AUTOMATIC AIR DAMPER

AHU AIR HANDLING UNIT

APD AIR PRESSURE DROP

BHP BRAKE HORSE POWER

BTU BRITISH THERMAL UNIT

CWS CHILLED WATER SUPPLY

CWR CHILLED WATER RETURN

CH CHILLER

CO CLEANOUT

C COMMON

CDWS CONDENSER WATER SUPPLY

CDWR CONDENSER WATER RETURN

CONV CONVECTOR

CFM CUBIC FEET PER MINUTE

DIA DIAMETER

DN DOWN

EAT ENTERING AIR TEMPERATURE

EDB ENTERING DRY BULB TEMPERATURE

EWT ENTERING WATER TEMPERATURE

EXIST EXISTING

HWS HOT WATER SUPPLY

HWR HOT WATER RETURN

HPS HIGH PRESSURE STEAM

IN INCH

KW KILOWATT

LAT LEAVING AIR TEMPERATURE

LWB LEAVING WET BULB

LPS LOW PRESSURE STEAM

LPC LOW PRESSURE CONDENSATE

LWT LEAVING WATER TEMPERATURE

LV LOUVER

MBH 1000 BTUH

MAX MAXIMUM

MIN MINIMUM

MV MANUAL VENT

NC NORMALLY CLOSED

NO NORMALLY OPEN, NUMBER

OA OUTSIDE AIR

RA RETURN AIR

RPM REVOLUTION PER MINUTE

SA SUPPLY AIR

SP STATIC PRESSURE

TD TRIPLE DUTY VALVE

TYP TYPICAL

V VOLT

VD VOLUME DAMPER

VSD VARIABLE SPEED DRIVE

FC FLEXIBLE CONNECTION

°F FAHRENHEIT

FCU FAN COIL UNIT

FD FIRE DAMPER

FSD COMBINATION FIRE/SMOKE DAMPER

FPM FEET PER MINUTE

FT FEET

AMP AMPERES

ACCU AIR COOLED CONDENSING UNIT

CT COOLING TOWER

CUH CABINET UNIT HEATER

ET EXPANSION TANK

FR FURNACE

GC GENERAL CONTRACTOR

GPM GALLONS PER MINUTE

P PUMP

PH PHASE

PTAC PACKAGED TERMINAL AIR CONDITIONER

RTH RADIANT TUBE HEATER

RTU ROOF TOP UNIT

SRV STATIONARY ROOF VENT

WH UNIT HEATER

UV UNIT VENTILATOR

VAV VARIABLE AIR VOLUME

WH WALL HEATER

WPD WATER PRESSURE DROP

ACV AIR CONTROL VALVE

B BOILER

BDD BACK DRAFT DAMPER

BTUH BRITISH THERMAL UNIT PER HOUR

BOD BOTTOM OF DUCT

CGR CHILLED GLYCOL RETURN

CGS CHILLED GLYCOL SUPPLY

DB DRY BULB TEMPERATURE

EFF EFFICIENCY

EWB ENTERING WET BULB TEMPERATURE

F FAN

F&T FLOAT AND THERMOSTATIC TRAP

FMS FLOW MEASURING STATION

FTR FIN TUBE RADIATION

DSD DUCT SMOKE DETECTOR

DP DEWPOINT TEMPERATURE

DTS DUAL TEMPERATURE WATER SUPPLY

DX DIRECT EXPANSION

DTR DUAL TEMPERATURE WATER RETURN

EC EXPANSION COMPENSATOR

ENC ENCLOSURE

ESP EXTERNAL STATIC PRESSURE

CD COLD CONDENSATE DRAIN

CCU CEILING CASSETTE UNIT

HD HEAD

HGR HOT GLYCOL RETURN

HGS HOT GLYCOL SUPPLY

HPC HIGH PRESSURE CONDENSATE

HP HORSEPOWER

HRU HEAT RECOVERY UNIT

HUM HUMIDIFIER

DWH DOMESTIC WATER HEATER

HX HEAT EXCHANGER

HR HUMIDITY RATIO, HOUR

HWC HOT WATER COIL

LDB LEAVING DRY BULB TEMPERATURE

MAU MAKEUP AIR UNIT

MOP MAXIMUM OVERCURRENT PROTECTION

MCA MINIMUM CIRCUIT AMPACITY

PD PRESSURE DROP

PG PROPYLENE GLYCOL

RCP RADIANT CEILING PANEL

RH RELATIVE HUMIDITY

RHC REHEAT COIL

SD SMOKE DAMPER

SQ SQUARE

TDH TOTAL DYNAMIC HEAD

PSI POUNDS PER SQUARE INCH

SHC SENSIBLE HEAT CAPACITY

TG TRANSFER GRILLE

THC TOTAL HEAT CAPACITY

WB WET BULB TEMPERATURE

WFS WATER FLOW SWITCH

WG WATER GAUGE

ZD ZONE DAMPER

BD BYPASS DAMPER

EBB ELECTRIC BASE BOARD

AS AIR SEPARATOR

FIL FILTER

EXH EXHAUST AIR

dB DECIBELS

GAL GALLONS

GR GRAINS

TSP TOTAL STATIC PRESSURE

NIC NOT IN CONTRACT

LB POUND

HZ HERTZ

VIF VERIFY IN FIELD

WWM WELDED WIRE MESH

WCU WALL CASSETTE UNIT

VUV VERTICAL UNIT VENTILATOR

KH KILN HOOD

ERU ENERGY RECOVERY UNIT

DC DUST COLLECTOR

CP CONDENSATE PUMP

ACU AIR CONDITIONING UNIT

IND INDUCTION UNIT

ABBREVIATIONS

VAL VALANCE UNIT

VP VACUUM PUMP

SS SOLIDS SEPARATOR

RAD RADIATOR, RADIANT PANEL

1. COORDINATE DEMOLITION WITH OTHER CONTRACTORS.

2. CONDUCT DEMOLITION TO MINIMIZE INTERFERENCE WITH OCCUPIED BUILDING AREAS. SERVICE TO OTHER PARTS OF

BUILDING SHALL REMAIN ACTIVE.

3. DISCONNECT, CAP, AND IDENTIFY DESIGNATED UTILITIES WITHIN DEMOLITION AREAS.

4. DEMOLISH IN AN ORDERLY AND CAREFUL MANNER, PROTECT EXISTING SUPPORTING STRUCTURAL MEMBERS AND

PARTITIONS TO REMAIN.

5. EXCEPT WHERE NOTED OTHERWISE, REMOVE DEMOLISHED MATERIALS FROM SITE. DO NOT DISPOSE OF ANY

MATERIAL ON SITE.

6. REMOVE DEMOLISHED MATERIAL FROM SITE AS WORK PROGRESSES. UPON COMPLETION OF WORK LEAVE AREAS IN

CLEAN CONDITION.

7. COMPLETELY REMOVE ALL PIPING, DUCTWORK, HANGERS, ETC..

8. PROVIDE REINSULATION TO EXISTING DISTRIBUTION AND SERVICES SCHEDULED TO REMAIN IN USE.

9. DEMOLITION SHALL INCLUDE REMOVAL OF ALL STRAPS, HANGERS, CLAMPS,CHANNEL, AND OTHER DEVICES USED

FOR SUPPORTING EQUIPMENT.

10. DRAIN, VENT, OR DISCHARGE MECHANICAL SYSTEMS PRIOR TO DISASSEMBLY.

11. IN MECHANICAL SYSTEMS BEING REMOVED, BLANK OFF, PLUG, OR CAP ALL BRANCH LINES (DUCTWORK OR PIPING)

SCHEDULED FOR DEMOLITION WHERE THEY TIE INTO MAIN LINES TO REMAIN.

12. DEMOLITION INCLUDES REMOVAL OF EQUIPMENT, SELECTED DUCTWORK, PIPING, ECT... THE DEMOLITION DRAWINGS SHOW THE GENERAL SCOPE OF ITEMS TO BE REMOVED. IT IS THE MECHANICAL CONTRACTORS RESPONSIBILITY TO REMOVE ALL ASSOCIATED EQUIPMENT AND MATERIALS THAT ARE NOT SPECIFICALLY IDENTIFIED TO BE REUSED, TO

PRODUCE A CLEAN AND WORKABLE SYSTEM.

13. REMOVE ALL OBSOLETE, FREE HANGING AND OPEN OR DEAD ENDED AIR, GLYCOL PIPING OR DUCT.

14. THE MECHANICAL DRAWINGS ARE DIAGRAMMATICAL. IT IS NOT POSSIBLE OR THE INTENT TO SHOW ALL PIECES OF THE SYSTEMS BEING REMOVED AND/OR INSTALLED UNDER THE CONTRACT. IT IS THE CONTRACTORS RESPONSIBILITY TO PROVIDE A COMPLETE, RELIABLE AND WORKING SYSTEM. IT IS ALSO THE CONTRACTORS RESPONSIBILITY TO DEMOLISH ALL MATERIALS ASSOCIATED TO REMOVALS TO PROVIDE A "LIKE NEW" APPEARANCE WITHIN THE SPACES (IE NO HANGARS, TUBING ETC ABANDONED IN PLACE UNLESS DIRECTED TO DO SO).

1. ALL WORK SHALL CONFORM TO ALL APPLICABLE RULES, REGULATIONS AND CODES, INCLUDING, BUT NOT LIMITED TO THE APPLICABLE ENERGY CONSERVATION CODE OF NEW YORK

STATE, AND BUILDING CODES OF NEW YORK STATE.

2. ALL EQUIPMENT SHALL COMPLY WITH THE PROVISIONS OF THE APPLICABLE ENERGY CONSERVATION CODE OF NEW YORK STATE. ALL SUBMITTALS FOR EQUIPMENT COVERED BY THE

CODE SHALL INCLUDE THE MANUFACTURER'S STATEMENT OF CONFORMANCE TO THE CODE.

3. FIELD VERIFY ALL DIMENSIONS PRIOR TO DUCTWORK FABRICATION OR ANY OTHER MECHANICAL WORK. MECHANICAL CONTRACTOR SHALL COORDINATE INSTALLATION OF EQUIPMENT, PIPING, DUCTWORK, AND PADS WITH OTHER CONTRACTORS. PROVIDE FITTINGS, ELEVATION CHANGES, TRANSITIONS, AND OFFSETS REQUIRED, WHETHER SHOWN OR NOT, TO AVOID

CONFLICTS WITH WORK OF OTHER CONTRACTS.

4. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR SEALING ALL HVAC PENETRATIONS (PIPING, DUCTWORK, ETC) IN ACCORDANCE WITH THE BUILDING CODE OF NEW YORK

STATE, AND WHERE SHOWN OR SPECIFIED.

5. ITEMS OF SPECIFIC MANUFACTURER'S SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE PRINTED INSTRUCTIONS AND/OR MANUFACTURER'S REPRESENTATIVES DIRECTIONS.

6. MECHANICAL CONTRACTOR TO INSTALL ALL NECESSARY STIFFENERS, BRACES, STRUTS, ETC, WHETHER SHOWN OR NOT, TO PROVIDE A COMPLETE, SAFE, AND DURABLE SYSTEM.

7. DIMENSIONS SHOWN "AFF" INDICATE THE ACTUAL CLEAR DIMENSIONS FROM THE BOTTOM OF THE ITEM TO THE FINISHED FLOOR ELEVATION; UNLESS INDICATED OTHERWISE.

8. SUPPORT AND EQUIPMENT DETAILS MAY VARY TO SUIT EQUIPMENT AND PARTS SUPPLIED.

9. WELD ALL STEEL ANGLE JOINTS UNLESS OTHERWISE SHOWN.

10. PROVIDE NECESSARY BY-PASSES AND BALANCING MEANS AS REQUIRED TO ASSURE PROPER SYSTEM OPERATION.

11. ALL DUCT DIMENSIONS SHOWN ARE "SIDE SEEN" BY "SIDE NOT SEEN" AND ARE THE CLEAR INSIDE DIMENSIONS UNLESS OTHERWISE NOTED.

12. PROVIDE ACCESS DOORS AND CLEARANCES FOR EASY ACCESS TO ALL FIRE DAMPERS, CONTROL DAMPERS, LOUVERS, FILTERS, COILS, AND FANS.

13. BRANCH DUCTS TO GRILLES, DIFFUSERS OR REGISTERS SHALL BE THE SAME SIZE AS GRILLE, DIFFUSER OR REGISTER NECK SIZE UNLESS INDICATED OTHERWISE.

14. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR PRECISE LOCATION OF DIFFUSERS AND REGISTERS.

15. PROVIDE MANUAL VOLUME DAMPERS IN ALL BRANCH TAKE-OFFS AND WHERE SHOWN.

16. PROVIDE ALL CONTROL AND INTERLOCK WIRING REQUIRED OR SPECIFIED THAT IS NOT PROVIDED BY THE ELECTRICAL CONTRACTOR.

17. COORDINATE WITH ELECTRICAL CONTRACTOR AND FIRE PROTECTION CONTRACTOR REGARDING THE RESPONSIBILITIES FOR SUPPLYING, INSTALLING AND WIRING OF HVAC-RELATED

DISCONNECT SWITCHES, STARTERS, SAFETY INTERLOCKS, EMERGENCY SHUTDOWN AND WIRING.

18. WORK ON M-SERIES DRAWINGS IS BY THE MECHANICAL CONTRACTOR UNLESS OTHERWISE NOTED.

19. VERIFY ALL LOCATIONS, DIMENSIONS, EQUIPMENT ARRANGEMENTS, CLEARANCES AND ELECTRICAL CHARACTERISTICS IN THE FIELD PRIOR TO BID. PROMPTLY NOTIFY THE

ARCHITECT/ENGINEER OF ANY DISCREPANCIES.

20. PRIOR TO CUTTING THROUGH FLOORS AND WALLS, THE CONTRACTOR SHALL VERIFY THE LOCATIONS OF ALL STRUCTURAL MEMBERS, JOISTS, AND OR COLUMNS. PROMPTLY NOTIFY THE ARCHITECT/ENGINEER OF ANY DISCREPANCIES. DO NOT CUT ANY STRUCTURAL MEMBERS UNLESS SPECIFICALLY DIRECTED TO DO SO.

21. THE MECHANICAL CONTRACTOR SHALL REMOVE DUCTWORK BACK TO A POINT WHICH WILL ALLOW THE INSTALLATION OF SUPPORT STEEL THAT IS REQUIRED / RELATED TO THE HVAC EQUIPMENT. THE MECHANICAL CONTRACTOR SHALL COORDINATE WITH THE GENERAL CONTRACTOR IN THE LOCATIONS WHICH WILL REQUIRE MECHANICAL SUPPORT STEEL.

22. INSTALL ALL NEW DUCT AND PIPE WITHIN EXISTING OPENINGS SUCH THAT IT ALLOWS AS MUCH SPACE AS POSSIBLE TO ONE SIDE WHICH MAY ALLOW PASSAGE.

23. ALL EXISTING-TO-REMAIN DIFFUSERS AND DUCT SYSTEMS TO BE REBALANCED TO CFM INDICATED.

24. PATCH AND SEAL DUCT WHERE BRANCHES / TAKEOFFS HAVE BEEN REMOVED AND NO NEW CONNECTION IS NEEDED.

25. CAP AND SEAL PIPING WHERE BRANCHES / TAKEOFFS HAVE BEEN REMOVED AND NO NEW CONNECTION IS NEEDED.

DUCTWORK

GENERAL

PIPING

MANUAL VOLUME DAMPER

AUTOMATIC AIR DAMPER

SQUARE ELBOW WITH TURNING VANES

LINEAR DIFFUSER

NEGATIVELY PRESSURIZED DUCT INTO THE PLANE

NEGATIVELY PRESSURIZED DUCT OUT OF THE PLANE

POSITIVELY PRESSURIZED DUCT INTO THE PLANE

POSITIVELY PRESSURIZED DUCT OUT OF THE PLANE

FLEXIBLE DUCT CONNECTOR

SQUARE TO ROUND DUCT TRANSITION

DAMPER MOTOR

DIRECTION OF AIRFLOW

TEMPERATURE SENSOR WITH LOCKING GUARD

PIPE GUIDE

PIPE ANCHOR

PIPE RISER

PIPE DROP

X

THREE-WAY CONTROL VALVE

TWO-WAY CONTROL VALVE

AUTOMATIC AIR VENT

MANUAL AIR VENT

PRESSURE RELIEF VALVE

NEEDLE VALVE

CHECK VALVE

CALIBRATED FLOW BALANCING VALVE

FLEXIBLE PIPE CONNECTOR

PIPE CAP

TRIPLE DUTY VALVE

STRAINER

REDUCER

UNION

THERMOMETER

PRESSURE GAUGE

FC

AAD

T

SQUARE MAIN TO ROUND BRANCH TAKE-OFF

INLINE PUMP

AIR SEPARATOR

TYPE

CFM

NECK SIZE

(TYPICAL OF) DIFFUSER DESIGNATION

PRESSURE SENSORP

M

BUTTERFLY VALVE

UNIT

GPMGPM

COOLING HEATING

UNIT WITH HEATING AND COOLING

UNIT

MAX. CFM

UNIT WITH AIR FLOW

UNIT

GPM

UNIT WITH HEATING OR COOLING

GENERAL EQUIPMENT DESIGNATIONUNIT

BASE MOUNTED PUMP

CONNECT TO EXISTING

DISCONNECT FROM EXISTING

DEMOLITION ITEMS

NEW WORK ITEMS

BALL VALVE

EXISTING ITEMS

SUPPLY DIFFUSER

RETURN DIFFUSER

KEYNOTE

FD FIRE DAMPER

VIEW

SHEET

ENLARGED PLAN & DETAIL CALL OUT

VOLUME DAMPER

NO ALTERATION PERMITTED HEREON

EXCEPT AS PROVIDED UNDER SECTION

7209 SUBDIVISION 2 OF THE NEW YORK

EDUCATION LAW

DESIGNED BY:

DRAWN BY:

CHECKED BY:

PROJECT NO:

DATE

DATE:

MARK

REVISIONS

DESCRIPTION

A

1 2 3

1 2 3

C

A

D

B

C

D

B

499 Col. Eileen Collins Blvd.

Syracuse, New York 13212

Phone: 315-455-2000 Fax: 315-455-9667 www.cscos.com

C&S Engineers, Inc.

Copyright ©

IL

LI

C K

E N

A B

LI

N

G P

R O

JE

C

T S

, W A

LT

E

LL

L A

B R

E

LO

C A

T

IO

N S

LA

B

F

O R

E S

T R

Y D

R

IV

E

S Y

R A

C U

S E

N

Y

MAY 2026

E. COHEN

L. MERRY

K. PIERCE, PE

555.064.006

GENERAL NOTES,

SYMBOLS, &

ABBREVIATIONS

M-001-322

SCALE: NOT TO SCALEA1 ABBREVIATIONS

SCALE: NOT TO SCALEC2 GENERAL DEMOLITION NOTES

SCALE: NOT TO SCALEC1 GENERAL NOTES

SCALE: NOT TO SCALEA4 SYMBOLS

SHEET METAL DUCTWORK:

• ALL DUCTWORK TO BE RIGID SHEET METAL CONSTRUCTED FROM GALVANIZED SHEET STEEL IN ACCORDANCE WITH SMACNA LOW VELOCITY DUCT CONSTRUCTION STANDARDS. ASSEMBLE

AND INSTALL DUCTWORK IN ACCORDANCE WITH RECOGNIZED INDUSTRY PRACTICE FOR ACHIEVING AIR TIGHT (5% LEAKAGE) AND NOISELESS (NO OBJECTIONABLE NOISE) SYSTEMS, CAPABLE OF PERFORMING EACH INDICATED SERVICE. FURNISH ALL REQUIRED DAMPERS, TRANSITIONS, CONNECTIONS TO AIR TERMINALS, AND OTHER ACCESSORIES NECESSARY FOR A COMPLETE OPERATING SYSTEM. NO VARIATION OF DUCT CONFIGURATION OR SIZES WILL BE PERMITTED EXCEPT BY PERMISSION FROM THE ENGINEER.

FLEXIBLE AIR DUCT:

• FLEXIBLE DUCT FOR CONNECTIONS SHALL BE FACTORY FABRICATED ASSEMBLY CONSISTING OF AN INNER SLEEVE, INSULATION AND OUTER MOISTURE BARRIER. THE INNER SLEEVE SHALL

BE CONSTRUCTED OF A CONTINUOUS VINYL COATED SPRING STEEL WIRE HELIX FUSED TO CONTINUOUS LAYER OF FIBERGLASS IMPREGNATED AND COATED VINYL. A 1-1/4" THICK LAYER OF INSULATING BLANKET OF FIBERGLASS WOOL SHALL ENCASE THE INNER SLEEVE AND BE SHEATHED WITH AN OUTER MOISTURE BARRIER OF A BIDIRECTIONAL REINFORCED METALIZED VAPOR BARRIER. THE FLEXIBLE DUCT SHALL BE RATED FOR A MAXIMUM WORKING VELOCITY OF 6000FPM AND SHALL BE UL LISTED UNDER THEIR UL-181 STANDARDS AS A CLASS 1 DUCT AND SHALL COMPLY WITH NFPA 90A. THE FLEXIBLE DUCT SHALL BE THERMAFLEX M-KC OR APPROVED EQUIVALENT. FLEXIBLE DUCT SHALL ROUTE FROM SHEET METAL DUCTWORK TO

CEILING DIFFUSERS ONLY. THERE SHALL BE NO EXPOSED FLEXIBLE DUCT.

HANGERS & SUPPORTS:

• HANGER RODS FOR NONCORROSIVE ENVIRONMENTS: CADMIUM-PLATED STEEL RODS AND NUTS.

• STRAP AND ROD SIZES: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," TABLE 5-1, "RECTANGULAR DUCT HANGERS MINIMUM SIZE," AND TABLE

5-2, "MINIMUM HANGER SIZES FOR ROUND DUCT."

• DUCT ATTACHMENTS: SHEET METAL SCREWS, BLIND RIVETS, OR SELF-TAPPING METAL SCREWS; COMPATIBLE WITH DUCT MATERIALS.

• HORIZONTAL PIPING HANGERS: ADJUSTABLE, STEEL CLEVIS HANGERS AT MAXIMUM 6 FEET SPACING.

DAMPERS:

• STANDARD LEAKAGE RATING, SUITABLE FOR HORIZONTAL OR VERTICAL APPLICATIONS.

• FRAMES: HAT-SHAPED, GALVANIZED-STEEL CHANNELS, 0.064-INCH MINIMUM THICKNESS. MITERED AND WELDED CORNERS. FLANGES FOR ATTACHING TO WALLS AND FLANGELESS FRAMES

FOR INSTALLING IN DUCTS.

• BLADES: MULTIPLE OR SINGLE BLADE. PARALLEL- OR OPPOSED-BLADE DESIGN. STIFFEN DAMPER BLADES FOR STABILITY. GALVANIZED-STEEL, 0.064 INCH THICK.

• BLADE AXLES: GALVANIZED STEEL.

TESTING, ADJUSTING AND BALANCING:

• TESTING, ADJUSTING AND BALANCING OF ALL WORK SHALL BE COMPLETED BY AN INDEPENDENT CONTRACTOR WHO IS CURRENTLY LICENSED BY THE ASSOCIATED AIR BALANCING

COUNCIL (ABBC) OR NATIONAL ENVIRONMENTAL BALANCING BUREAU (NEBB).

• BALANCE AIR QUANTITIES TO WITHIN PLUS OR MINUS 10% OF THAT INDICATED ON THE DRAWINGS.

• ADJUST AIR INLETS AND OUTLETS FOR EACH SPACE TO INDICATE AIRFLOWS.

1. SET AIRFLOW PATTERNS OF ADJUSTABLE OUTLETS FOR PROPER DISTRIBUTION WITHOUT DRAFTS.

2. MEASURE INLETS AND OUTLETS AIRFLOW.

3. ADJUST EACH INLET AND OUTLET FOR SPECIFIED AIRFLOW.

4. RE-MEASURE EACH INLET AND OUTLET AFTER THEY HAVE BEEN ADJUSTED.

• FINAL BALANCING REPORT SHALL BE INCLUDED IN THE OPERATION AND MAINTENANCE MANUAL.

SUBMITTALS:

• SUBMIT THE FOLLOWING INFORMATION AS APPLICABLE AND AS REQUIRED FOR ALL WORK SCHEDULED AND SPECIFIED:

1. MANUFACTURER'S PRODUCT DATA SHEETS.

2. SHOP DRAWINGS INCLUDING DIMENSIONED EQUIPMENT LAYOUTS, POINT-TO-POINT WIRING DIAGRAMS AND SEQUENCES OF OPERATION.

3. OPERATION AND MAINTENANCE MANUALS.

HANGERS:

• HANGERS SHALL INCLUDE ALL MISCELLANEOUS STEEL SUCH AS ANGLE IRON, BANDS, C-CLAMPS WITH RETAINING CLIPS, CHANNELS, HANGER RODS, ETC. NECESSARY FOR THE

INSTALLATION OF WORK.

• HANGERS SHALL BE FASTENED TO BUILDING STEEL, CONCRETE, OR MASONRY, BUT NOT TO PIPING OR DUCTWORK. DUCTWORK SHALL NOT BE SUPPORTED FROM ROOF DECKING AND/OR

BRIDGING, BUT SHALL BE SUSPENDED FROM THE TOP CHORD OF BAR JOISTS, STEEL OR OTHER STRUCTURE. DUCTWORK SHALL CLEAR ALL SPRINKLERS AND OTHER OBSTACLES AND SHALL BE HUNG AS HIGH AS POSSIBLE IN WORK AND STORAGE AREAS. WHERE INTERFERENCES OCCUR, IN ORDER TO SUPPORT DUCTWORK OR PIPING, THE CONTRACTOR MUST INSTALL TRAPEZE TYPE HANGERS OR SUPPORTS WHICH SHALL BE LOCATED WHERE THEY DO NOT INTERFERE WITH ACCESS TO FIRE DAMPERS, VALVES, ACCESS DOORS AND OTHER EQUIPMENT SERVICE REQUIREMENTS AND/OR OTHER TRADES. HANGER TYPES AND INSTALLATION METHODS ARE SUBJECT TO OWNER CRITERIA.

• HANGERS AND PIPING OF DISSIMILAR METALS SHALL BE DI-ELECTRICALLY SEPARATED FROM ONE ANOTHER.

• ADJUSTABLE, STEEL CLEVIS HANGERS (MSS TYPE 1): FOR SUSPENSION OF NONINSULATED OR INSULATED STATIONARY PIPES, INSTALL HANGERS AND SUPPORTS COMPLETE WITH

NECESSARY INSERTS, BOLTS, RODS, NUTS, WASHERS, AND OTHER ACCESSORIES.

INSTRUMENTATION AND CONTROLS:

• GENERAL: CONTACT OWNER'S CONTROLS PROVIDER FOR CONTROLS WORK. CONTROLS CONTRACTOR SHALL PROVIDE ALL CONTROL COMPONENTS, WIRING, ETC. FOR A COMPLETE AND

OPERABLE SYSTEM.

GRILLES, REGISTERS & DIFFUSERS:

• TYPE S-1 - SUPPLY DIFFUSER - PRICE MODEL PDF OR EQUAL.

a. DESCRIPTION: PERFORATED DIFFUSER.

b. FABRICATION: STEEL.

c. BORDER: PROVIDE APPROPRIATE BORDER TO ACCOMMODATE MOUNTING PER CEILING TYPE.

CONDENSATE PIPING:

• PVC PLASTIC PIPE: ASTM D1785

• PVC SOCKET FITTINGS:ASTM D2466 FOR SCHEDULE 40

• SOLVENT CEMENTS FOR PVC PIPING: ASTM D2564

• SCHEDULE 40, PVC PLASTIC PIPE AND FITTINGS AND SOLVENT-WELDED JOINTS

HOSE EXTRACTION ARM:

• TELESCOPIC FLEXIBLE HOSE EXTRACTION ARM EQUAL TO IAP PRODUCTS MODEL FA-044872-T.

REFRIGERANT PIPING:

• LINE TEST PRESSURE: 535 PSIG.

• COPPER TUBE: ASTM B 280, TYPE ACR.

• WROUGHT-COPPER FITTINGS, BRAZED-JOINT: ASME B16.50.

• WROUGHT-COPPER UNIONS: ASME B16.22.

• SOLDER FILLER METALS: ASTM B 32. USE 95-5 TIN ANTIMONY OR ALLOY HB SOLDER TO JOIN COPPER SOCKET FITTINGS ON COPPER PIPE

THERMAL INSULATION:

• REFRIGERANT PIPING: FLAME - SPREAD INDEX OF 25 OR LESS, AND SMOKE-DEVELOPED INDEX OF 50 OR LESS. FLEXIBLE ELASTOMERIC: CLOSED-CELL, OR EXPANDED-RUBBER MATERIALS.

COMPLY WITH ASTM C534/C534M, TYPE I. THICKNESS: 1/2 IN.

• SUPPLY DUCTWORK: 1.5 INCH FIBERGLASS WRAP INSULATION WITH ALL PURPOSE ALUMINUM JACKET.

INDOOR UNIT (AC-1):

• MITSUBISHI ELECTRIC DUCTED INDOOR UNIT: MODEL PEAD-AA-36NL OR EQUAL. NOMINAL COOLING CAPACITY: 33,000 BTUH; HEATING CAPACITY: 33,500 BTUH; 208V / 1 PHASE; 1,100 CFM.

• PROVIDE WITH BUILT-IN CONDENSATE PUMP

• PROVIDE WITH WIRED CONTROLS WITH WALL MOUNTED THERMOSTAT.

THERMOSTAT:

• LCD BACKLIT SCREEN WITH BUTTONS TO SWITCH BETWEEN MODES AND ADJUST TEMPERATURE.

AIR-COOLED CONDENSING UNIT (ACCU-1):

• ACCU-1: MITSUBISHI ELECTRIC OUTDOOR UNIT: MODEL SUZ-AK36NLHZ OR EQUAL. 208 V / 1 PHASE. THE OUTDOOR UNIT POWERS THE INDOOR UNIT, AND SHOULD A POWER OUTAGE OCCUR, THE SYSTEM IS AUTOMATICALLY RESTARTED WHEN POWER RETURNS.

• INVERTER-DRIVEN COMPRESSOR

• BUILT-IN BASE PAN HEATER.

• PROVIDE WITH 18" H SNOW STAND.

FUME HOOD - MOTT MANUFACTURING:

• PRO BENCH - VERTICAL SASH MODEL #7221040 (FRP)

• HOOD SIZE: 48"; 10"Ø DUCT CONNECTION

• CAV SETUP (18" MAX SASH OPENING - 80 FPM/407 CFM)

• CHAIN AND SPROCKET SASH SYSTEM

• LED LIGHT

• AFA1000 FACE VELOCITY ALARM (CAV SETUP)

• ONE OF EACH LAB SERVICE FIXTURES

a. COLD WATER

b. VACUUM

c. AIR

d. GAS

• PLUMBING PRE-PIPED DOWN TO BOTTOM, ROUTED TO THE REAR OF THE FUME HOOD.

W

W

6" M

IN

NOTES:

1. CONTRACTOR HAS OPTION OF PROVIDING EITHER SQUARE

ELBOW WITH TURNING VANES OR LONG RADIUS ELBOW.

SQUARE ELBOW

RADIAL ELBOW

SUPPLY AIR FLOW

BRANCH DUCT

90 DEGREE ELBOW

WITH TURNING VANES

45 DEGREE BOOT

VOLUME DAMPER

RETURN/EXHAUST AIRFLOW

1.

5W

NO ALTERATION PERMITTED HEREON

EXCEPT AS PROVIDED UNDER SECTION

7209 SUBDIVISION 2 OF THE NEW YORK

EDUCATION LAW

DESIGNED BY:

DRAWN BY:

CHECKED BY:

PROJECT NO:

DATE

DATE:

MARK

REVISIONS

DESCRIPTION

A

1 2 3

1 2 3

C

A

D

B

C

D

B

499 Col. Eileen Collins Blvd.

Syracuse, New York 13212

Phone: 315-455-2000 Fax: 315-455-9667 www.cscos.com

C&S Engineers, Inc.

Copyright ©

IL

LI

C K

E N

A B

LI

N

G P

R O

JE

C

T S

, W A

LT

E

LL

L A

B R

E

LO

C A

T

IO

N S

LA

B

F

O R

E S

T R

Y D

R

IV

E

S Y

R A

C U

S E

N

Y

MAY 2026

E. COHEN

L. MERRY

K. PIERCE, PE

555.064.006

SPECIFICATIONS &

DETAILS

M-002-322

SCALE: NOT TO SCALEA3 HVAC SPECIFICATIONS - LAB 322

SCALE: NOT TO SCALEA1 DUCT DETAIL

RHC (E)

VD

D

C

B

10 12 14

10ø(E)

10ø(E) ø

(E x1

2( E

18x12(E)19x10(E)

19x14(E) x1

6( E x6

(E

15x6(E)15x6(E)

20x16(E)

17x10(E)

10x4 SERVING 4TH

FLOOR ABOVE (TYP)

20x6 20x8

A

15 16 17 18 19 20 22

T

AC-1

ACCU-1

S1

12x12

12ø

14x12(E) x1

6( E

12x10(E)12x8(E)8x6(E)

26x16(E)

D

C

B

12 14

A

15 16 17 18 19 20 22

20x16(E)

14x12(E) 20x14(E)

WA-HC-21 (E)

WA-HC-22 (E)

CAP

B

10 12 14

10x16(E)

A

EX-14 (E)

EX-6 (E)

EX-7 (E)

EX-8 (E)

EX-9 (E)

EX-10 (E)

ALT 1 WORK

EX-12 (E)

REPLACE FAN MOTOR WITH

2HP/208V/3PH MOTOR. BALANCE

FAN TO 4,660 CFM @ 1.5 T.S.P.

EX-13 (E)

16X20 (E) TOP

14X14 (E) BOTTOM

22x20(E)

20x16(E)

EX-12 (E)

MEASURE FAN PERFORMANCE AT

EXISTING CONDITIONS. SUBMIT

RESULTS FOR REVIEW. NO ADDITIONAL

WORK TO BE PERFORMED UNTIL

REVIEW IS COMPLETED.

NO ALTERATION PERMITTED HEREON

EXCEPT AS PROVIDED UNDER SECTION

7209 SUBDIVISION 2 OF THE NEW YORK

EDUCATION LAW

DESIGNED BY:

DRAWN BY:

CHECKED BY:

PROJECT NO:

DATE

DATE:

MARK

REVISIONS

DESCRIPTION

A

1 2 3

1 2 3

C

A

D

B

C

D

B

499 Col. Eileen Collins Blvd.

Syracuse, New York 13212

Phone: 315-455-2000 Fax: 315-455-9667 www.cscos.com

C&S Engineers, Inc.

Copyright ©

IL

LI

C K

E N

A B

LI

N

G P

R O

JE

C

T S

, W A

LT

E

LL

L A

B R

E

LO

C A

T

IO

N S

LA

B

F

O R

E S

T R

Y D

R

IV

E

S Y

R A

C U

S E

N

Y

LAB 322

MAY 2026

E. COHEN

L. MERRY

K. PIERCE, PE

555.064.006

PARTIAL FLOOR PLANS

LAB 322

M-101-322 0 16'8'4'

0 16'8'4' 0 16'8'4'

SCALE: NOT TO SCALE

A4 KEYPLAN

SUPPORT AC-1 FROM STRUCTURE ABOVE WITH THREADED RODS AND VIBRATION ISOLATORS.

SIZE REFRIGERANT PIPING PER MANUFACTURER'S RECOMMENDATIONS.

10" Ø FUME HOOD EXHAUST DOWN TO FUME HOOD.

4" Ø HOSE EXTRACTION ARM.

BALANCE TO 150 CFM EACH.

CLOSE REHEAT COIL CONTROL VALVE.

BALANCE OPEN END S.A. DUCT ABOVE CEILING TO 1,100 CFM.

BALANCE TO 250 CFM EACH.

WINDOW AC UNIT TO REMAIN.

SCALE: NOT TO SCALE

A3 KEYED NOTES

SCALE: 1/8" = 1'-0"C3 PARTIAL THIRD FLOOR PLAN - LAB 322

SCALE: 1/8" = 1'-0"A1 PARTIAL SECOND FLOOR PLAN

SCALE: 1/4" = 1'-0"C1 PARTIAL PENTHOUSE PLAN

PENTHOUSE

1. COORDINATE REMOVAL WORK WITH OTHER CONTRACTORS.

2. CONDUCT REMOVAL WORK TO MINIMIZE INTERFERENCE WITH OCCUPIED BUILDING AREAS. SERVICE TO

OTHER PARTS OF BUILDING SHALL REMAIN ACTIVE.

3. REMOVE IN AN ORDERLY AND CAREFUL MANNER, PROTECT EXISTING SUPPORTING STRUCTURAL

MEMBERS AND PARTITIONS TO REMAIN.

4. EXCEPT WHERE NOTED OTHERWISE, REMOVE MATERIALS FROM SITE. DO NOT DISPOSE OF ANY

MATERIAL ON SITE.

5. REMOVE MATERIAL FROM SITE AS WORK PROGRESSES. UPON COMPLETION OF WORK LEAVE AREAS IN

CLEAN CONDITION.

6. REMOVAL SHALL INCLUDE REMOVAL OF ALL STRAPS, HANGERS, CLAMPS, CHANNEL, AND OTHER DEVICES

USED FOR SUPPORTING EQUIPMENT.

7. PRIOR TO ENGAGING IN REMOVAL WORK, CONTRACTOR SHALL NOTIFY ENGINEER OF ANY

DISCREPANCIES BETWEEEN EXISTING FIELD CONDITIONS AND PROJECT DRAWINGS.

1. ELECTRICAL WORK SHALL CONFORM TO ALL STATE, LOCAL, AND NATIONAL ELECTRICAL CODES.

2. ELECTRICAL CHARACTERISTICS SHALL BE VERIFIED WITH EQUIPMENT MANUFACTURER.

3. ITEMS OF SPECIFIC MANUFACTURERS SHALL BE INSTALLED IN STRICT ACCORDANCE WITH

MANUFACTURER'S PRINTED INSTRUCTIONS AND/OR MANUFACTURER'S REPRESENTATIVE'S DIRECTIONS.

4. THE CONTRACTOR SHALL FIELD VERIFY ALL LOCATIONS AND DIMENSIONS SHOWN ON DRAWINGS.

5. ALL CONDUIT AND WIRING SCHEDULES SHALL BE VERIFIED BEFORE INSTALLATION.

6. THE ELECTRICAL CONTRACTOR SHALL COORDINATE THE INSTALLATION OF ALL EQUIPMENT WITH OTHER

CONTRACTORS.

7. ALL AREAS DISTURBED BY WORK SHALL BE RESTORED TO A CONDITION EQUAL TO OR BETTER THAN

ORIGINAL AS DETERMINED BY THE ARCHITECT.

8. ALL ELECTRICAL CONDUIT AND CONDUCTORS DISCONNECTED AND NOT TO BE REUSED SHALL BE

REMOVED.

9. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS BEFORE STARTING WORK. IF ONLY A PORTION OF AN EXISTING CIRCUIT IS BEING REMOVED FOR DEMOLITION, CONTINUITY SHALL BE

MAINTAINED TO THE REST OF THE REMAINING CIRCUIT.

10. ALL BRANCH CIRCUIT CONDUCTORS SHALL BE #12AWG UNLESS OTHERWISE SHOWN.

11. ALL BRANCH CIRCUITS SHALL CONSIST OF 2 CONDUCTORS PLUS GROUND, UNLESS OTHERWISE SHOWN.

J

XXX

S

QUAD RECEPTACLE, MOUNT 18" AFF UNLESS OTHERWISE NOTED

JUNCTION BOX

FUSED DISCONNECT SWITCH

NON FUSED DISCONNECT SWITCH

BRANCH CIRCUIT HOME RUN WITH CIRCUIT NUMBER

SEE PANEL SCHEDULES FOR DETAILS

SPECIAL RECEPTACLE

DATA OUTLET, EXISTING

PANEL BOARD, REFER TO PANEL BOARD SCHEDULE

EXISTING WORK LINETYPE

DEMOLITION WORK LINETYPES

NEW WORK LINETYPE

XX

DUPLEX RECEPTACLE, MOUNT AT 18" AFF UNLESS NOTATION INDICATES OTHERWISE.

CTR = ABOVE COUNTER

IG = ISOLATED GROUND

GFI = GROUND FAULT CIRCUIT INTERRUPTER, MOUNT AT 48" AFF UNLESS OTHERWISE NOTED

WP = GFI WITH IN-USE WEATHERPROOF COVER, MOUNT AT 42" AFF UNLESS OTHERWISE NOTED

XP = EXPLOSION PROOF

SP = SURGE PROTECTED

SINGLE POLE SWITCH, UNLESS NOTATION INDICATES OTHERWISE.

OS = OCCUPANCY SENSOR

OSD = OCCUPANCY SENSOR WITH DIMMER

2 = DOUBLE POLE SWITCH

3 = THREE-WAY SWITCH

4 = FOUR-WAY SWITCH

D = DIMMER SWITCH

K = KEYED SWITCH

M = MANUAL MOTOR STARTER

T = TIMER SWITCH

LV = LOW VOLTAGE SWITCH

XX

PLAN SYMBOLS

or

DATA OUTLET, NEW

CR CORD REEL

A AMPERE

A/C AIR CONDITIONING

AC ALTERNATE CURRENT

ACCU AIR COOLED CONDENSING UNIT

AF AMPERE FRAME

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

A/H AIR HANDLER

AIC AMPERE INTERRUPTING CAPACITY

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AU AT UNIT

AUX AUXILIARY

AWG AMERICAN WIRE GAUGE

BC BARE COPPER

BFG BELOW FINISHED GRADE

BRK BREAKER

BOH BACK OF HOUSE

C CONDUIT

CA CABLE

CAB CABINET

CAT5E CATEGORY-5E

CC CABLED CONDUCTORS

CH CHILLER

CKT CIRCUIT

CLL CONTRACT LIMIT LINE

CMH COMMUNICATION MANHOLE

CO CONDUIT ONLY

COMM COMMUNICATION

CPB COMMUNICATION PULLBOX

CT CURRENT TRANSFORMER

CTR ABOVE COUNTER

CUC COMMON USER CABLE

CUTC COMMON USER TERMINAL CABINET

D DEEP

DC DIRECT CURRENT

DISC DISCONNECT

DN DOWN

DP DISTRIBUTION PANEL

DPST DOUBLE POLE SINGLE THROW

DPDT DOUBLE POLE DOUBLE THROW

EER ELECTRICAL EQUIPMENT ROOM

ELECT ELECTRICAL

ELEV ELEVATION

EMT ELECTRICAL METALLIC TUBING

EQUIP EQUIPMENT

EXIST EXISTING

(E) EXISTING TO REMAIN

F FUSE

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

FAT FIRE ALARM TERMINATION

FBO FURNISHED BY OWNER

FD/SD FIRE DAMPER / SMOKE DETECTOR

FDR FEEDER

FLA FULL LOAD AMPERES

GFI GROUND FAULT INTERRUPT

GND GROUND

H HIGH

HP HORSEPOWER

HZ HERTZ

I/C INTERCOM

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

JB JUNCTION BOX

KA KILOAMP

KV KILOVOLT

KVA KILOVOLT AMPERES

KW KILOWATT

KWH KILOWATT HOUR

KWHD KILOWATT HOUR DEMAND METER

L LENGTH, LONG

LGT LIGHTING

MA MILLIAMPERES

MBB MONITOR BREAKOUT BOX

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MCM 1000 CIRCULAR MILLS

MECH MECHANICAL

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MM MULTI MODE

MTD MOUNTED

N/A NOT APPLICABLE

NC NORMALLY CLOSED

NEMA NATIONAL ELECTRICAL MANUFACTURERS ASS.

NF NON-FUSED

NFPA NATIONAL FIRE PROTECTION ASS.

NO NORMALLY OPEN

NTS NOT TO SCALE

OLS OVERLOADS

OC ON CENTER

P POLE

PB PULLBOX

PNL PANEL

PR PAIR

PVC POLYVINYL CHLORIDE

PWR POWER

POC POINT OF CONNECTION

POS POINT OF SALES

PT POTENTIAL TRANSFORMER

REF REFERENCE

REM REMARKS

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT-MEAN-SQUARE

RCPT RECEPTACLE

SBB SOUND BREAKOUT BOX

SDB SOUND DISTRIBUTION BOX

SLC SIGNALING LINE CIRCUIT

SM SINGLE MODE

SPECS SPECIFICATIONS

SPKR SPEAKER

SPST SINGLE POLE SINGLE THROW

SPDT SINGLE POLE DOUBLE THROW

SR SOUND RACK

SST STAINLESS STEEL

ST SHUNT TRIP

SW SWITCH

SWBD SWITCHBOARD

TEL TELEPHONE

TP TWISTED PAIR CABLE

TTB TELEPHONE TERMINAL BOARD

TYP TYPICAL

UON UNLESS OTHERWISE NOTED

V VOLT

VFD VARIABLE FREQUENCY DRIVE

W WATT, WIRE, WIDE

WP WEATHERPROOF

XFMR TRANSFORMER

XP EXPLOSION PROOF

INDICATOR LIGHT LETTER INDICANTS COLOR. R=RED, G=GREEN, Y=YELLOW,

B=BLUE, NO LETTER=CLEAR

CONNECTION POINT OR CABLE SPLICE

TRANSFORMER

CIRCUIT BREAKER

FUSE

GROUND

ONE-LINE SYMBOLS

GENERATOR

TRANSFER SWITCH

UTILITY POLE

PANELBOARD

NO ALTERATION PERMITTED HEREON

EXCEPT AS PROVIDED UNDER SECTION

7209 SUBDIVISION 2 OF THE NEW…

This is the start of the file's text. The full file is on GovTribe.