Illick Enabling Walters Hall Lab Relocations Drawings.pdf
PDF 5 MB Posted
- Solicitation number
- 2138452
- Issued by
- Onondaga County, New York
About this file
Summary of Illick Enabling Projects, Walters Hall Lab Relocations (Lab 202 and 322)
This document set contains contract construction drawings for the renovation of two laboratory spaces (Rooms 202 and 322) in Walters Hall at SUNY ESF, located at 1 Forestry Drive, Syracuse, New York 13210. The project involves comprehensive renovation work including partial demolition, removal and reinstallation of acoustical drop ceilings, new wall partitions, relocation of base cabinets from Baker Hall, installation of new countertops, sinks, and fume hoods, center lab counters and reagent shelving, new HVAC split systems with ductwork and controls, plumbing installations including piping in ceilings and lab spaces, electrical work involving new receptacles, ceiling-mounted electrical reels, relocated lighting, panels and circuiting, and associated related work. The construction classification is Type II-B for both laboratory spaces, with sprinkler coverage per NFPA 13. All work must comply with the 2025 Energy Conservation Construction Code of New York State and the Building Code of New York State. The drawings are dated January 27, 2026, with revisions dated May 2026, and were prepared by C&S Architects, Engineers & Landscape Architects, LLC and C&S Engineers, Inc., with project number 555.064.006.
The project includes specific contracting goals for minority and women business enterprises, with a 15 percent Minority Business Enterprise (MBE) goal, 15 percent Women Business Enterprise (WBE) goal, and a 6 percent Service-Disabled Veteran-Owned Business (SDVOB) goal. No Disadvantaged Business Enterprise (DBE) goal is specified. The contract documents indicate this is an alteration-level project (Level 2) at an existing educational facility and represent a comprehensive technical specification set including architectural, mechanical, plumbing, and electrical systems. The scope encompasses detailed drawings for life safety compliance, code conformance plans, demolition plans, floor plans with reflected ceiling plans, and comprehensive specifications for materials, equipment, and installation methods across all trades.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Project Manual Illick Enabling Walters Hall Lab Relocations.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PLAN
NORTH
Copyright ©
CONTRACT DRAWINGS
FOR THE CONSTRUCTION OF
NO ALTERATION PERMITTED HEREON EXCEPT AS PROVIDED UNDER
SECTION 7209 SUBDIVISION 2 OF THE NEW YORK EDUCATION LAW
LOCATION MAP
TO THE BEST OF OUR KNOWLEDGE, INFORMATION AND BELIEF, THE
PLANS AND SPECIFICATIONS FOR THIS PROJECT ARE IN COMPLIANCE
WITH THE ENERGY CONSERVATION CONSTRUCTION CODE OF NEW
YORK STATE AND THE BUILDING CODE OF NEW YORK STATE
ILLICK ENABLING PROJECTS, WALTERS
HALL LAB RELOCATIONS (LAB 322)
SUNY ESF
1 FORESTRY DRIVE
SYRACUSE, NY 13210
JANUARY 27, 2026
G−001−322
C&S PROJECT NUMBER: 555.064.006
DRAWING LIST 322
G-001-322 COVER SHEET
G-101-322 THIRD FLOOR CODE COMPLIANCE PLAN
AD-103-322 DEMOLITION PLAN - LAB 322
A-001-322 GENERAL NOTES
A-103-322 FLOOR PLAN & REFLECTED CEILING PLAN - LAB 322
PD-101-322 PARTIAL SECOND AND THIRD FLOOR DEMOLITION PLANS - LAB 322
P-101-322 PARTIAL SECOND AND THIRD FLOOR PLANS - LAB 322
M-001-322. GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS
M-002-322 SPECIFICATIONS AND DETAILS
M-101-322 PARTIAL FLOOR PLANS LAB 322
E-001-322 GENERAL NOTES, SYMBOLS, ABBREVIATIONS, AND SCHEDULES
E-002-322 SPECIFICATIONS
E-101-322 LAB 322 POWER PLAN
E-501-322 DETAILS
MAY 2026
FLAMMABLE
CABINET
LARGE
STORAGE
CABINET
92'-9"
52'-2"
183'-0"
DIAGONAL: 54'-10"
COMMON PATH OF EGRESS TRAVEL (CPET) = 52'-2"
2025 NYSBC TABLE 410.5.3.3: 100 FEET MAX
EXIT ACCESS TRAVEL DISTANCE (EATD) = 183'-0"
2025 NYSBC TABLE 1017.2 SPRINKLERED 250 FEET MAX
LIFE SAFETY LEGEND
SYMBOL DESCRIPTION
EXIT ACCESS TRAVEL DISTANCE (EATD): DISTANCE TO EXITS FROM THE MOST REMOTE
POINT IN THE MOST REMOTE ROOM ON THE FLOOR
DARK GREY REPRESENTS 36" CLEAR ALONG PATH
LIGHT GREY PLUS DARK GREY REPRESENTS 44" CLEAR ALONG PATH
COMMON PATH OF EGRESS TRAVEL (CPET)
1 HOUR RATED ASSEMBLY (UL #U419)
EGRESS START POINT
E EA
E = ENCLOSED EXIT / EXIT TO EXTERIOR
EA = EXIT ACCESS
ED = EXIT DISCHARGE
HE = HORIZONTAL EXITED HE
FIRE EXTINGUISHER CABINET
AREA OF WORK
FEC
FX
REMOTENESS OF EXITS:
EXIT TO EXIT (D1)
BUILDING DIAGONAL (D2)
FIRE EXTINGUISHER (BRACKET)
FX
ACCESSIBLE ITEM:
ACCESSIBLE SEATING (WHEN LOCATED AT CHAIR)
ACCESSIBLE ENTRY (WHEN LOCATED AT DOOR)
FX
1.
2.
3.
FIRE EXTINGUISHER (UNDERCOUNTER):
FIRE EXTINGUISHER 1: (UNDERCOUNTER) - "COSMIC 5E" UL RATING 3A-40BC AS
MANUFACTURED BY JL INDUSTRIES - MOUNTING HEIGHT 12" TO BOTTOM OF FIRE
EXTINGUISHER
FIRE EXTINGUISHER 2: (UNDERCOUNTER) - "SATURN 1-A:K" UL RATING AS
MANUFACTURED BY JL INDUSTRIES MOUNTING HEIGHT 12" TO BOTTOM OF FIRE
EXTINGUISHER
NOTES: FX1 - UL RATING 2A-10BC
PROVIDE AND INSTALL FIRE EXTINGUISHER WHERE LOCATED ON PLAN.
EXTINGUISHER HEIGHTS PER LEGEND OR UNLESS NOTED OTHERWISE.
PROVIDE SHOP DRAWINGS FOR APPROVAL.
F FIRE ALARM
EXIT SIGNAGE (REFER TO ELECTRICAL DRAWINGS FOR SPECIFIED FIXTURE)
XXX'-X"
XXX'-X"
BASIC PROJECT INFORMATION (BUILDING DATA):
CONSTRUCTION CLASSIFICATION TYPE II-B
TABLE 601
OCCUPANCY BUSINESS - B
CHAPTER 3
SPRINKLER COVERAGE: NFPA13
FLOOR AREA (SECOND FLOOR): 9,985 SF [B-OCC, TYPE IIB CONSTRUCTION]
PROJECT AREA (SECOND FLOOR): 1,135 SF
EXITING REQUIREMENTS:
MINIMUM NUMBER OF EXITS:
PATH OF COMPLIANCE: NON-SEPARATED, MIXED
OCCUPANCY BUILDING
REFERENCED BUILDING CODES: 2025 EXISTING BUILDING CODE OF NYS
2025 FIRE CODE OF NYS
2025 PLUMBING CODE OF NYS
2025 MECHANICAL CODE OF NYS
2025 FUEL GAS CODE OF NYS
20205ENERGY CONSERVATION CONSTRUCTION CODE OF NYS
2017 ICC A117.1 ACCESSIBLE AND USABLE BUILDINGS
2010 ADA STANDARDS FOR ACCESSIBLE DESIGN
ALTERATION LEVEL: LEVEL 2
OCCUPANT LOAD LAB 202A: BUSINESS (B-OCC): 1,135sf / 150sf PER PERSON = 8 OCC
(1) PER LAB
BUSINESS (B-OCC) WITH OCCUPANT LOAD LESS THAN 50 REQUIRE
(1) EXIT.
805.4.1.1
PLAN
NORTH
NO ALTERATION PERMITTED HEREON
EXCEPT AS PROVIDED UNDER SECTION
7209 SUBDIVISION 2 OF THE NEW YORK
EDUCATION LAW
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJECT NO:
DATE
DATE:
MARK
REVISIONS
DESCRIPTION
A
1 2 3
1 2 3
C
A
D
B
C
D
B
499 Col. Eileen Collins Blvd.
Syracuse, New York 13212
Phone: 315-455-2000 Fax: 315-455-9667 www.cscos.com
C&S Architects, Engineers & Landscape Architect, LLC
Copyright ©
LAB 322
JANUARY 27, 2026
A. TOWLES
A. TOWLES
M. LAMONTAGNE
555.064.006
THIRD FLOOR CODE
COMPLIANCE PLAN
G-101-322
ILL
IC
K
EN
AB
LIN
G
PR
OJ
EC
TS
, W
AL
TE
RS
HA
LL
LA
B
RE
LO
CA
TIO
NS
(L
AB
2)
SU
NY
E
SF
1 F
OR
ES
TR
Y
DR
IV
E
SY
RA
CU
SE
, N Y
SCALE: 1/8" = 1'-0"B1 THIRD FLOOR CODE COMPLIANCE PLAN
SCALE: NOT TO SCALEA4 KEY PLAN - THIRD FLOOR
SCALE: 1/4" = 1'-0"C4 LIFE SAFETY LEGEND
CC
DD
D3
D3
D12
D13
D13
D12
D8
D7
D8
D8
D8
SCALE: NOT TO SCALEB4 KEYED AND GENERAL DEMOLITION NOTES
GENERAL DEMOLITION NOTES
1 PROTECT/ MAINTAIN ALL EXISTING FIRE PROTECTION AND FIRE RESISTANCE RATED CONSTRUCTION 2 PROTECT ALL EXISTING FINISH SURFACES TO REMAIN. PATCH EXISTING CONSTRUCTION TO MATCH ADJACENT FINISHES IN THE CASE
OF REMOVALS AS REQUIRED BY THE WORK. ALL DAMAGE CAUSED BY THE CONTRACTOR, WHETHER INSIDE OR OUTSIDE THE CONTRACT LIMIT, SHALL BE REPLACED OR REPAIRED TO A LIKE NEW CONDITION AT NO ADDITIONAL COST TO THE OWNER
3 REMOVE EXISTING FLOORING AT AREAS DESIGNATED TO RECEIVE FLOORING. PROVIDE SMOOTH, FLUSH AND LEVEL FLOOR TO
EXTENT REQUIRED TO RECEIVE FINISHES. PATCH AND LEVEL FLOOR THROUGHOUT
4 REFER TO PLUMBING, MECHANICAL, AND ELECTRICAL, DRAWINGS FOR ELEMENTS TO BE DEMOLISHED WITHIN THE SCOPE OF THOSE
DISCIPLINES. COORDINATE DEMOLITION WITH THIS RELATED WORK
5 RECYCLE ALL METAL TO BE REMOVED INCLUDING, BUT NOT LIMITED TO; FRAMING, PIPE AND CEILING GRID
6 RECYCLE ALL ACOUSTIC CEILING PANELS TO BE REMOVED
7 RECYCLE ALL GYPSUM BOARD TO BE REMOVED
8 IT IS THE INTENT OF THE DEMOLITION PLAN TO SHOW THE GENERAL NATURE OF THE DEMOLITION SCOPE OF WORK. THE GENERAL
CONTRACTOR IS RESPONSIBLE FOR VISITING THE JOB SITE AND VERIFYING THE EXISTING CONDITIONS. THE GENERAL CONTRACTOR
SHALL NOTIFY THE ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES
9 COORDINATE AND VERIFY WITH THE OWNER ALL ITEMS TO BE SALVAGED PRIOR TO REMOVAL. THESE ITEMS MAY INCLUDE, BUT ARE NOT LIMITED TO, THE FOLLOWING: LIGHT FIXTURES, DOORS/FRAMES AND HARDWARE, CASEWORK, PLUMBING FIXTURES
10 MAINTAIN SEPARATION BETWEEN AREAS OUTSIDE THE SCOPE OF WORK BY PROVIDING PLASTIC SHEATHING BETWEEN SPACES
AND/OR TEMPORARILY TAPING OF JOINTS AND CAPS TO
PREVENT DUST MIGRATION
11 DISPOSE OF ALL DEMOLISHED OR REMOVED MATERIALS LEGALLY OFF THE SITE. COMPLY WITH ALL LOCAL HAULING AND DISPOSAL
REQUIREMENTS
12 UTILITIES TO REMAIN IN SERVICE DURING DEMOLITION SHALL BE MAINTAINED AND PROTECTED AGAINST DAMAGE 13 SCHEDULE ALL SERVICE SHUT-DOWNS WITH THE OWNER. NOTIFY THE OWNER A MINIMUM TIME OF ONE (1) WEEK AND ADDITIONALLY
ONE (1) HOUR PRIOR TO SHUT DOWNS
14 UPON COMPLETION, CLEAN THE ENTIRE WORK AREA TO A TIDY, UNIFORM CONDITION; REMOVING ALL DEBRIS, DUST PARTITIONS AND
ASSOCIATED MATERIALS USED DURING DEMOLITION. CLEAN ALL AREAS IMPACTED BY DEMOLITION, INCLUDING BUT NOT LIMITED TO, ADJACENT OCCUPIED AREAS AND AREAS NOT WITHIN THE SCOPE OF WORK
15 ABANDONMENT OF ITEMS OR UNUSED UTILITIES IN PLACE IS STRICTLY PROHIBITED, UNLESS SPECIFICALLY PERMITTED BY OWNER 16 DISPOSAL OF ALL DEBRIS AND DEMOLISHED MATERIALS SHALL BE CONTRACTORS RESPONSIBILITY. DEBRIS REMOVAL SHALL BE
PROMPT AND GENERAL CLEAN-UP SHALL OCCUR DAILY
17 FIRE AND SMOKE DETECTION DEVICES SHALL REMAIN OPERATIONAL DURING DEMOLITION AND CONSTRUCTION. PROTECT FIRE AND
SMOKE DETECTION DEVICES FROM DUST, DAMAGE AND DEBRIS
18 IT IS THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE SELECTIVE DEMOLITION WORK AND ALL NEW WORK TO ASSURE THAT THE
BUILDING REMAINS WEATHERTIGHT. PROVIDE TEMPORARY PROTECTION AS NEEDED
19 CLEAN AND PREPARE ALL EXISTING SURFACES TO REMAIN AS REQUIRED TO PREAPRE FOR PROPOSED FINISHES 20 IT IS NOT EXPECTED THAT HAZARDOUS MATERIALS WILL BE ENCOUNTERED IN THE WORK. IF SUSPECTED HAZARDOUS MATERIALS
ARE ENCOUNTERED, DO NOT DISTURB; IMMEDIATELY NOTIFY ARCHITECT AND OWNER
NO ALTERATION PERMITTED HEREON
EXCEPT AS PROVIDED UNDER SECTION
7209 SUBDIVISION 2 OF THE NEW YORK
EDUCATION LAW
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJECT NO:
DATE
DATE:
MARK
REVISIONS
DESCRIPTION
A
1 2 3
1 2 3
C
A
D
B
C
D
B
499 Col. Eileen Collins Blvd.
Syracuse, New York 13212
Phone: 315-455-2000 Fax: 315-455-9667 www.cscos.com
C&S Architects, Engineers & Landscape Architect, LLC
Copyright ©
LAB 322
JANUARY 27, 2026
A. TOWLES
A. TOWLES
M. LAMONTAGNE
555.064.006
DEMOLITION PLAN -
LAB 322
AD-103-322
ILL
IC
K
EN
AB
LIN
G
PR
OJ
EC
TS
, W
AL
TE
RS
HA
LL
LA
B
RE
LO
CA
TIO
NS
(L
AB
2)
SU
NY
E
SF
1 F
OR
ES
TR
Y
DR
IV
E
SY
RA
CU
SE
, N Y
SCALE: 1/4" = 1'-0"C1 DEMOLITION PLAN - LAB 322 0 16'8'4'
PLAN
NORTH
KEYED DEMOLITION NOTES 322
D3 REMOVE CASEWORK
D7 PROTECT EXISTING CEILING DURING DEMOLITION
D8 EXISTING TRENCH DRAIN TO BE CLEANED. COORD. WITH PLMG. DWG.
D12 REMOVE WALL CABINET
D13 REMOVE STEEL STRUCTURE DOWN TO CONCRETE SLAB
SCALE: NOT TO SCALEA4 KEY PLAN - THIRD FLOOR
A
AFF ABOVE FINISHED FLOOR
ACT ACOUSTICAL CEILING TILE
AMP ACOUSTICAL METAL PANEL
ALUM ALUMINUM
L ANGLE
B
BLK BLOCK
BD BOARD
BOT BOTTOM
BLDG BUILDING
BL BUILDING LINE
C
CPT CARPET
CLKG CAULK(ING)
CLG CEILING
CBB CEMENTITIOUS BACKER BOARD
CTR CENTER
CL CENTER LINE
CT CERAMIC TILE
CB CHALKBOARD
CLR CLEAR / CLEARANCE
CLOS CLOSET
COL COLUMN
CONC CONCRETE
CMU CONCRETE MASONRY UNIT
CONT CONTINUOUS
CJ CONTROL JOINT
CG CORNER GUARD
CORR CORRIDOR
CTR COUNTER
CRS COURSE(S)
CW CURTAINWALL
D
DEMO DEMOLISH / DEMOLITION
DET DETAIL
DIA DIAMETER
DIM DIMENSION
DIS DISPENSER
DN DOWN
DWG DRAWING
DF DRINKING FOUNTAIN
E
EA EACH
ELEC ELECTRIC
EWC ELECTRIC WATER COOLER
EL ELEVATION
ELEV ELEVATOR
ENCL ENCLOSURE
ENTR ENTRANCE
ENTR GRL ENTRANCE GRILLE
EQ EQUAL
EQUIP EQUIPMENT
EXH EXHAUST
EXIST EXISTING
ETR EXISTING TO REMAIN
EXP EXPANSION
EJ EXPANSION JOINT
EXP EXPOSED
EXT EXTERIOR
F
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF STUDS
FOW FACE OF WALL
F/F FACE TO FACE
FT FEET/FOOT
FRP FIBER REINFORCED
POLYESTER / PLASTIC
FGL FIBERGLASS
FIN FINISH(ED)
FF FINISH FLOOR
FIN GR FINISH GRADE
FA FIRE ALARM
FEC FIRE EXTINGUISHER CABINET
FHC FIRE HOSE CABINET
FP FIRE PROTECTION
FRT FIRE RETARDANT
FP FIREPROOF
FIXT FIXTURE
FLASH FLASHING
FLR FLOOR
FD FLOOR DRAIN
FTG FOOTING
FDTN FOUNDATION
FURN FURNITURE
FBO FURNISHED BY OTHERS
FURG FURRED(ING)
G
GA GAGE / GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GL GLASS
GL BLK GLASS BLOCK
GL TL GLASS TILE
GB GRAB BAR
GR GRADE
GRL GRILLE
GYP BD GYPSUM BOARD
H
HCP HANDICAPPED
HNDRL HANDRAIL
HDWD HARDWOOD
HT HEIGHT
HP HIGH POINT
HM HOLLOW METAL
I
IRWC IMPACT RESISTANT WALL
COVERING
ID INSIDE DIAMETER
IMWP INSULATED METAL WALL PANEL
INSUL INSULATION / INSULATED
IG INSULATING GLASS
ISG INSULATING SPANDREL
GLAZING
ITG INSULATING TEMPERED GLASS
INT INTERIOR
J
JC JANITOR'S CLOSET
K
KD KNOCKDOWN
L
LAM LAMINATE
LAV LAVATORY
L LENGTH / LONG
LF LINEAL FEET
LG LAMINATED GLASS
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LPT LOW POINT
M
MFR MANUFACTURER
MO MASONRY OPENING
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MTL METAL
MEZZ MEZZANINE
MIN MINIMUM
N
NOM NOMINAL
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NO NUMBER
NTS NOT TO SCALE
O
OC ON CENTER
OPNG OPENING
OPP OPPOSITE
OD OUTSIDE DIAMETER
OH OVERHEAD
OSB ORIENTED STRAND BOARD
P
P PAINT
PR PAIR
PTD PAPER TOWEL DISPENSER
PBD PARTICLE BOARD
PTN PARTITION
PLAS PLASTIC
PLAM PLASTIC LAMINATE
PLBG PLUMBING
PLYWD PLYWOOD
POL POLISHED
POL CONC POLISHED CONCRETE
PVC POLYVINYL CHLORIDE
PEMB PRE-ENGINEERED METAL
BUILDING
PT PRESSURE TREATED
Q
QT QUARRY TILE
QTZ QUARTZ
R
R RADIUS (DIM)
RCP REFLECTED CEILING PLAN
REINF REINFORCE
REQD REQUIRED
RB RESILIENT BASE
RF RESILIENT FLOORING
REV REVISION / REVISED
R RISER(S)
RD ROOF DRAIN
RL ROOF LEADER
RTU ROOF TOP UNIT
RM ROOM
RO ROUGH OPENING
RBR RUBBER
S
SCH SCHEDULE(D)
SLNT SEALANT
SLR SEALER
SECT SECTION
SHTHG SHEATHING
SIM SIMILAR
SD SOAP DISPENSER
SAFB SOUND ATTENUATION
FIBERGLASS BATT
SPEC SPECIFICATION
SF SQUARE FEET OR
STOREFRONT
STN STAIN
SS SOLID SURFACE
SST STAINLESS STEEL
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL
SUSP SUSPENDED
SYS SYSTEM
T
TB TACK BOARD
TG TEMPERED GLASS
TERR TERRAZZO
TFL THERMALLY FUSED LAMINATE
THK THICKNESS
THRES THRESHOLD
TL TILE
TPTN TOILET PARTITION
T&B TOP AND BOTTOM
T/O TOP OF
TOS TOP OF STEEL/SLAB
TOW TOP OF WALL
T&G TONGUE AND GROOVE
T TREAD(S)
TYP TYPICAL
U
UC UNDER CUT
UNFIN UNFINISHED
UON UNLESS OTHERWISE NOTED
V
VB VAPOR BARRIER
VR VAPOR RETARDER
VTR VENT THROUGH ROOF
VIF VERIFY IN FIELD
VERT VERTICAL
VEST VESTIBULE
VCT VINYL COMPOSITION TILE
VWB VINYL WALL BASE
VWC VINYL WALL COVERING
VP VISION PANEL
W
WSCT WAINSCOT
W CAB WALL CABINET
W (CON'T)
WC WATER CLOSET
W WIDE
WG WIRE GLASS
W/ WITH
WM WIRE MESH
WD WOOD
WBL WOOD BLOCKING
A-101 A1
SIM
A
ROOM NAME
150 SF
A1 / A-101 VIEW REFERENCE
LEVEL REFERENCE
DETAIL CALLOUT
WALL SECTION
BUILDING SECTION
INTERIOR ELEVATION
EXTERIOR ELEVATION
STRUCTURAL GRID
DESCRIPTIONSYMBOL
ROOM TAG
DOOR TAG
WINDOW TAG
REVISION TAG
STRUCTURAL GRID LINE
FINISHED SURFACE LINE
DEMOLITION LINE
OVERHEAD/HIDDEN LINE
DESCRIPTIONSYMBOL
A1 A-101
SIM
A1 A-101
SIM
A1 A-101
SIM
A1 A-101
SIM
WALL TAG
(SHOWING DIM WHEN NOT TO DECK)
MA3
15'-10" MA3
CONSTRUCTION TO
BE DEMOLISHED
EXISTING CONSTRUCTION
TO REMAIN NEW CONSTRUCTION
FIXTURES & ACCESSORIES LEGEND
FIRE EXTINGUISHER
FIRE EXTINGUISHER CABINET
A52
A53
CLOCKA57
A58
A59
WALL MOUNTED EXIT SIGN
LIGHTING CONTROL SWITCH
A60
A61
OUTLET ABOVE COUNTER
A62
OUTLET AT FLOOR
A63 SPEAKER
TELEPHONE / INTERCOM
NOTE: REFER TO MATERIALS & ACCESSORIES
LEGEND FOR PRODUCT INFORMATION
1'
- 6
"VA
RI
ES
8"
COUNTERTOP
A60
A61
EQ
EQ
6" MAX
7'
- 0
4" M
IN
1'- 0"
M
AX
6'- 8"
8'-
0"
7'
- 6
OP
ER
AB
LE
P
AR
T 4'
- 0
A59 A62 A66
A63 A64A65 A67
A58 A57
NOMINAL 8'
CEILING HEIGHT
4'
- 6
" M
AX
4'
- 8
" M
AX
A52 A53
A64 FA SYSTEM A/V DEVICE
A65 SMOKE / HEAT DETECTOR
A66 MANUAL PULL STATION
A67 EMERGENCY LIGHT
SCALE: NOT TO SCALEC3 GENERAL NOTES
SCALE: NOT TO SCALEA3 SYMBOLS LEGEND SCALE: NOT TO SCALEA4 ABBREVIATIONS LIST
GENERAL NOTES
1 DIMENSIONS NOTED "EQ" ARE EQUAL TO EACH OTHER ONLY IF THEY ARE ON THE SAME DIMENSION STRING AND IN THE SAME ROW 2 DO NOT SCALE DRAWINGS TO OBTAIN DIMENSIONS. REFER TO DRAWINGS FOR DIMENSIONS. REQUIRED CRITICAL DIMENSIONS NOT
FOUND SHOULD BE FIELD VERIFIED OR OBTAINED FROM ARCHITECT. VERIFY ALL DIMENSIONS AND CONDITIONS IN FIELD (EXISTING AND PROPOSED CONSTRUCTION) AND BRING ANY DISCREPANCIES TO THE IMMEDIATE ATTENTION OF THE ARCHITECT
3 ROOM NUMBERING IS FOR CONSTRUCTION PURPOSES ONLY. ACTUAL ROOM NUMBERING TO BE COORDINATED WITH OWNER
PRIOR TO ANY SCHEDULING OR LABELING
4 PROVIDE BLOCKING OR PROVISIONS FOR SOLID ANCHORAGE AT WALL AND CEILING MOUNTED EQUIPMENT AND ACCESSORIES
PROVIDED UNDER THIS CONTRACT AND EQUIPMENT TO BE PROVIDED BY THE OWNER
5 MAINTAIN EXISTING FIRE PROOFING AND FIRE RATED CONSTRUCTION. PATCH AS NEEDED TO MEET REQUIREMENTS AS PER CODE
CONFORMANCE DRAWINGS
6 REFER TO CODE CONFORMANCE DRAWINGS FOR REQUIRED FIRE RATED CONSTRUCTION
7 ALL DIMENSIONS ARE TO FACE OF FRAMING, FACE OF MASONRY UNIT, OR FINISHED FACE OF EXISTING CONSTRUCTION 8 VERIFY ALL DIMENSIONS IN THE FIELD. NOTIFY THE ARCHITECT OF ANY DISCREPANCIES BETWEEN CONTRACT DOCUMENTS AND
FIELD CONDITIONS
9 EXTEND ALL PARTITIONS FROM FLOOR TO UNDERSIDE OF DECK ABOVE UNLESS OTHERWISE INDICATED. MAKE THIS JOINT SMOKE
TIGHT AND FIRESTOP AT RATED PARTITIONS
10 DOCUMENTS ARE BASED UPON ORIGINAL CONSTRUCTION DRAWINGS, EXISTING CONDITIONS MAY VARY. CONTACT ARCHITECT IF
DISCREPANCIES ARISE
11 PROTECT ALL EXISTING FINISH SURFACES TO REMAIN. PATCH EXISTING CONSTRUCTION TO MATCH ADJACENT FINISHES TO
REMAIN AT ALL REMOVALS AND AS REQUIRED BY NEW WORK. ALL DAMAGE CAUSED BY THE CONTRACTOR, WHETHER INSIDE OR OUTSIDE THE CONTRACT LIMIT, SHALL BE REPLACED OR REPAIRED TO A LIKE NEW CONDITION AT NO ADDITIONAL COST TO THE
OWNER
12 PROVIDE ACCESS PANELS AS REQUIRED AT ALL WALLS AND CEILINGS AT ALL VALVES, DAMPERS, CONCEALED JUNCTION BOXES, AND OTHER EQUIPMENT REQUIRING MAINTENANCE, ADJUSTMENTS OR SERVICING
13 THE TERM "WALL" AND "PARTITION" ARE USED INTERCHANGEABLY
14 PROVIDE METAL STUD INSERT BLOCKING AT ALL WALLS RECEIVING WALL MOUNTED EQUIPMENT AND/OR ACCESSORIES.
COORDINATE WITH ALL TRADES AND OWNER EQUIPMENT LAYOUTS
15 SEE PARTITION TYPES FOR LOCATIONS OF ACOUSTIC AND THERMAL INSULATION
16 ALL GYPSUM WALL BOARD SHALL BE INSTALLED VERTICALLY WITH JOINTS STAGGERED WHERE THERE ARE TWO LAYERS. ALL
GYPSUM BOARD IN FIRE RATED PARTITIONS TO COMPLY WITH LISTED UL ASSEMBLY
17 FIRE TAPE, SMOKE TIGHT, ALL GYPSUM WALL BOARD VENEER ABOVE CEILING OR OTHERWISE CONCEALED 18 INTERIOR WALL TYPES ARE SHOWN ON THE FLOOR PLANS AND/OR DETAILS USING WALL TYPE SYMBOL (REFER TO SYMBOLS
LEGEND)
19 PROVIDE ACOUSTICAL SEALANT AT ALL PARTITION PERIMETERS, RUNNERS, ELECTRICAL OUTLETS, PENETRATIONS AND OPENINGS.
TO MINIMIZE SOUND TRANSMISSION, ELECTRICAL OUTLETS SHALL BE SEPARATED BY A MINIMUM OF ONE STUD, BACK TO BACK 20 PROVIDE GYPSUM WALL BOARD CONTROL JOINTS WHERE ANY OF THE FOLLOWING CONDITIONS EXIST: (A) PARTITIONS OR
CEILINGS OF DISSIMILAR CONSTRUCTION MEET AND REMAIN IN THE SAME PLANE AND/OR (B) EXPANSION OR CONTROL JOINTS OCCUR IN THE BUILDING STRUCTURE OR WALL CONSTRUCTION AND/OR (C) GYPSUM BOARD PARTITIONS WHERE THE SURFACE EXCEEDS A LENGTH OF 30' MAXIMUM IN ANY DIRECTION AND/OR (D) GYPSUM BOARD CEILINGS WHERE THE SURFACE EXCEEDS A LENGTH OF 50' MAXIMUM IN ANY DIRECTION (WITH PERIMETER RELIEF) OR 30' MAXIMUM IN ANY DIRECTION (WITHOUT PERIMETER
RELIEF)
NO ALTERATION PERMITTED HEREON
EXCEPT AS PROVIDED UNDER SECTION
7209 SUBDIVISION 2 OF THE NEW YORK
EDUCATION LAW
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJECT NO:
DATE
DATE:
MARK
REVISIONS
DESCRIPTION
A
1 2 3
1 2 3
C
A
D
B
C
D
B
499 Col. Eileen Collins Blvd.
Syracuse, New York 13212
Phone: 315-455-2000 Fax: 315-455-9667 www.cscos.com
C&S Architects, Engineers & Landscape Architect, LLC
Copyright ©
JANUARY 27, 2026
A. TOWLES
A. TOWLES
M. LAMONTAGNE
555.064.006
GENERAL NOTES
A-001-322
ILL
IC
K
EN
AB
LIN
G
PR
OJ
EC
TS
, W
AL
TE
RS
HA
LL
LA
B
RE
LO
CA
TIO
NS
(L
AB
2)
SU
NY
E
SF
1 F
OR
ES
TR
Y
DR
IV
E
SY
RA
CU
SE
, N Y
SCALE: 3/8" = 1'-0"D1 TYPICAL ACCESSORIES AND DEVICES MOUNTING HEIGHTS LAB 322
REF.REF. REF.
LARGE
STORAGE
CABINET
FLAMMABLE
CABINET
CC
DD
N1
N1
N1
N1N3
N3
N43' - 3" 4' - 3"
5' - 2" 4' - 8" 5' - 2" 5' - 0" 5' - 2 3/4"
A
B
A
M
C
D
E
F F
E
D
C G
L
JJ
K
G
G
A
B
AN2
N6
N7 N7
N7N7
N8
N5 N5 N5 N5 N5
ALIGN
N5
N9
N10
0 16'8'4'
PLAN
NORTH
SCALE: NOT TO SCALEA4 KEY PLAN - THIRD FLOOR
SCALE: NOT TO SCALEC4 KEYED NOTES
NO ALTERATION PERMITTED HEREON
EXCEPT AS PROVIDED UNDER SECTION
7209 SUBDIVISION 2 OF THE NEW YORK
EDUCATION LAW
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJECT NO:
DATE
DATE:
MARK
REVISIONS
DESCRIPTION
A
1 2 3
1 2 3
C
A
D
B
C
D
B
499 Col. Eileen Collins Blvd.
Syracuse, New York 13212
Phone: 315-455-2000 Fax: 315-455-9667 www.cscos.com
C&S Architects, Engineers & Landscape Architect, LLC
Copyright ©
LAB 322
MAY 1, 2026
A. TOWLES
A. TOWLES
M. LAMONTAGNE
555.064.006
FLOOR PLAN &
REFLECTED CEILING
PLAN - LAB 322
A-103-322
ILL
IC
K
EN
AB
LIN
G
PR
OJ
EC
TS
, W
AL
TE
RS
HA
LL
LA
B
RE
LO
CA
TIO
NS
(L
AB
2)
SU
NY
E
SF
1 F
OR
ES
TR
Y
DR
IV
E
SY
RA
CU
SE
, N Y
0 16'8'4'
PLAN
NORTH
SCALE: 1/4" = 1'-0"C1 FLOOR PLAN - LAB 322
KEYED NOTES 322
N1 FURNISH AND INSTALL COUNTERTOP. EPOXY COUNTERTOP BASIS OF DESIGN: DURCON, SOLID EPOXY RESIN, BLACK W/ INTEGRATED
6" BACKSPLASH
N2 CLEAN AND SEAL CONCRETE SLAB
N3 FURNISH AND INSTALL FUME HOOD, COORD. COORD. W/ MECH., ELEC., & PLMG.
N4 INSTALL LAB SINK AND FAUCET PROVIDED BY CAMPUS, COORD. W/ PLMG. DWG.
N5 EQUIPMENT PROVIDED AND INSTALLED BY OWNER.
N6 INSTALL NEW REAGENT SHELVING, COORD. W/ MECH., ELEC., & PLBG. BASIS OF DESIGN: MOTT MANUFACTURING, SIGMA FLEX
SYSTEM. W/ INSERT PANELS, 12"D OPEN SHELVING
N7 EXISTING TRENCH DRAIN, COORD. W/ PLMG.
N8 COORDINATE LIGHT FIXTURES WITH REAGENT SHELVING
N9 PATCH AND REPAIR WALL, PAINT
N10 PROVIDE (2) DECK MOUTNED NEEDLE VALVES. COORD. LOCATION WITH PLMG. BASIS OF DESIGN: WATERSAVER, LABORATORY BALL
VALVE, DECK MOUNTED
SCALE: NOT TO SCALEC4 GENERAL FINISH NOTES
GENERAL FINISH NOTES 322
1 ALL WALLS TO BE PAINTED TO MATCH ADJACENT EXISTING
2 PAINT ALL PREVIOUSLY PAINTED SURFACES WITHIN LAB 322
3 ALL WALL BASE TO MATCH ADJACENT EXISTING
4 ALL FLOORING MATERIAL AND TRANSITIONS SHALL BE CENTERED UNDER THE DOOR IN THE CLOSED POSITION UNLESS
OTHERWISE NOTED
5 EXTEND ALL FINISHES UNDER CABINETS, BENCHES, SHELVING, COUNTERTOPS AND LAVATORIES 6 MISCELLANEOUS ELECTRICAL PANEL COVERS, GRILLES, ETC. TO BE PAINTED TO MATCH ADJACENT WALL SURFACES, UNLESS
OTHERWISE NOTED
7 ALL METAL UNDER-COUNTER SUPPORT BRACKETS TO BE PAINTED TO MATCH ADJACENT WALL FINISH 8 COORDINATE REMOVAL AND RELOCATION OF ALL EXISTING MOVEABLE EQUIPMENT WITH OWNER
CASEWORK SCHEDULE 322
MARK WIDTH DEPTH HEIGHT FURNISHED BY: INSTALLED BY
A 4' - 0" <varies> 2' - 10" OWNER CONTRACTOR B 4' - 0" <varies> 2' - 10" OWNER CONTRACTOR
C 3' - 0" 1' - 11" 2' - 10" OWNER CONTRACTOR
D 3' - 0" 1' - 11" 2' - 10" OWNER CONTRACTOR
E 3' - 0" 1' - 11" 2' - 10" OWNER CONTRACTOR
F 3' - 0" 1' - 11" 2' - 10" OWNER CONTRACTOR
G 4' - 0" 1' - 11" 2' - 10" OWNER CONTRACTOR
J 4' - 0" 2' - 5" 2' - 10" OWNER CONTRACTOR
K 3' - 0" 1' - 11" 2' - 10" OWNER CONTRACTOR
L 3' - 0" 1' - 11" 2' - 10" OWNER CONTRACTOR
M 4' - 0" 1' - 11" 2' - 10" OWNER CONTRACTOR
CAP
1/2" A
6" FROM TRENCH DRAIN
(TYP 5)
1/2" HW UP
1/2" CW UP
3/4" CW UP
3/4" HW UP
1/2" A UP
B
C
D
16 17 18 19 20 22
AW
A W
G A
V
CW
CAP
CAP
1/2" CW UP
G A
V
CW
DW DW
AW
B
C
D
16 17 18 19 20 22
CONNECT TO EXISTING
DISCONNECT FROM EXISTING
PIPE BREAK/CONTINUATION
ISOLATION VALVE
PIPE DOWN
PIPE UP
DEMOLITION WORK
EXISTING WORK
NEW WORK
COMPRESSED AIRA
COLD WATERCW
HOT WATERHW
DISTILLED WATERDW
WASTEW
EXISTING(E)
ACID WASTEAW
HOT WATER RE-CIRCHWRC
GASG
VACUUMV
CONTRACTOR SHALL VERIFY ALL CONDITIONS
ON JOB SITE & NOTIFY THE OWNER OF ANY
VARIATIONS FROM DIMENSIONS SHOWN ON
THESE DRAWINGS BEFORE PROCEEDING WITH
ANY CONSTRUCTION.
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJECT NO:
DATE
DATE:
MARK
REVISIONS
DESCRIPTION
A
1 2 3
1 2 3
C
A
D
B
C
D
B
Copyright ©
2940 Hebron Park Drive, Suite 216 Hebron, Kentucky 41048
Phone: 859-283-4450 www.cscos.com
C&S Engineers, Inc.
IL
LI
C K
E N
A B
LI
N
G P
R O
JE
C
T S
, W A
LT
E
R S
H
LL
L A
B R
E
LO
C A
T
IO
N S
LA
B
F
O R
E S
T R
Y D
R
IV
E
S Y
R A
C U
S E
N
Y
LAB 322
MAY 2026
E. COHEN
L. J. MERRY
K. L. PIERCE, PE
555.064.006
PARTIAL SECOND AND
THIRD FLOOR
DEMOLITION PLANS -
LAB 322
PD-101-322
0 16'8'4'
0 16'8'4'
SCALE: NOT TO SCALE
B4 KEYED NOTES
SCALE: NOT TO SCALE
A4 KEY PLAN
SCALE: 3/16" = 1'-0"
A1 PARTIAL SECOND FLOOR DEMOLITION PLAN
SCALE: 3/16" = 1'-0"
C1 PARTIAL THIRD FLOOR DEMOLITION PLAN - LAB 322
REMOVE CW PIPE, CAP AT POINT SHOWN IN SECOND FLOOR CEILING.
REMOVE 3/4" CW, 3/4" HW AND 1/2" A PIPES. CAP AT POINTS SHOWN IN
SECOND FLOOR CEILING.
1/2" CW AND 1/2" HW TO REMAIN.
EXISTING TRENCH FLOOR DRAIN TO REMAIN.
REMOVE HW AND CW UP TO WALL FAUCET. CAP AT MAINS.
REMOVE WALL FAUCET.
SCALE: NOT TO SCALE
C4 SYMBOLS AND ABBREVIATIONS
B
C
D
16 17 18 19 20 22
1/2" V & 1/2" A DN
B
C
D
16 17 18 19 20 22
6" FROM TRENCH DRAIN
(TYP 5)
1/2" HW UP (E)
1/2" CW UP (E)
AW
A W
G A
V
CW
G A
V
CW
DW DW
AW
CO
1/2" A 1/2" V
1/2" CW
1-1/4"AW
1/2" V & 1/2" A UP
1/2" DW UP
TO SINK
1/2" A UP
1/2" A
1/2" V
1/2" A UP
1/2" V UP
1/2" A
PIPING
• CW, VAC. & AIR: TYPE L COPPER TUBING, WROUGHT COPPER FITTINGS.
• DISTILLED WATER (DW): PIPE MATERIAL TO MATCH EXISTING.
SHUT-OFF VALVES
• VAC. & AIR: COPPER-ALLOY BALL VALVES, 3 PIECE BODY, STANDARD MSS SP-110.
• DW: BALL VALVES, STANDARD MSS SP-122 VALVES TO BE THE SAME MATERIAL AS PIPING
TO WHICH THEY ARE CONNECTED.
LAB FIXTURES
• VACUUM / AIR: DECK MOUNTED SINGLE OUTLET EQUAL TO WATERSAVER MODEL L2800-131WSA.
PIPING LEAK TESTS
• VAC. & AIR: TEST NEW AND MODIFIED PARTS OF EXISTING PIPING, CAP AND FILL PIPING WITH
OIL-FREE DRY NITROGEN TO PRESSURE OF 150 PSIG. ISOLATE TEST SOURCE AND LET STAND
FOR FOUR HOURS TO EQUALIZE TEMP. REFILL SYSTEM IF REQUIRED, HOLD FOR TWO HOURS WITH
NO PRESSURE DROP.
• CW & DW PIPING: HYDROSTATIC TEST; TEST PIPING AT 50 PSIG. HOLD TEST FOR TWO HOURS. PRESSURE SHALL
REMAIN CONSTANT WITHOUT PUMPING.
PIPE HANGERS
• HORIZONTAL PIPING HANGERS; ADJUSTABLE STEEL CLEVIS HANGERS AT MAXIMUM 6 FEET SPACING.
NO ALTERATION PERMITTED HEREON
EXCEPT AS PROVIDED UNDER SECTION
7209 SUBDIVISION 2 OF THE NEW YORK
EDUCATION LAW
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJECT NO:
DATE
DATE:
MARK
REVISIONS
DESCRIPTION
A
1 2 3
1 2 3
C
A
D
B
C
D
B
499 Col. Eileen Collins Blvd.
Syracuse, New York 13212
Phone: 315-455-2000 Fax: 315-455-9667 www.cscos.com
C&S Engineers, Inc.
Copyright ©
IL
LI
C K
E N
A B
LI
N
G P
R O
JE
C
T S
, W A
LT
E
LL
L A
B R
E
LO
C A
T
IO
N S
LA
B
F
O R
E S
T R
Y D
R
IV
E
S Y
R A
C U
S E
N
Y
LAB 322
MAY 2026
E. COHEN
L. J. MERRY
K. L. PIERCE, PE
555.064.006
PARTIAL SECOND AND
FLOOR PLANS - LAB 322
P-101-322 0 16'8'4'
0 16'8'4'
SCALE: 3/16" = 1'-0"
C1 PARTIAL THIRD FLOOR PLAN - LAB 322
SCALE: NOT TO SCALE
C4 SPECIFICATIONS
SCALE: NOT TO SCALE
A4 KEY PLAN
PROVIDE 1/2" CW, 1/2"A, 1/2"V AND 1-1/4"AW UP TO FUME HOODS.
EXTEND 1/2" CW AND 1/2" HW TO NEW SINK.
EXISTING TRENCH DRAIN.
SINK PROVIDED BY CAMPUS.
PROVIDE 1/2" V & 1/2" A UP TO REAGENT CABINETRY FAUCET SETS.
ONE VAC. & ONE AIR OUTLET MOUNT ON COUNTERTOP. LOCATE PIPING
IN CHASEWAY BEHIND CABINETRY.
PROVIDE 1/2"-A ON WALL ABOVE COUNTERTOP. CONNECT TO EXISTING
EQUIPMENT.
SCALE: 3/16" = 1'-0"
A1 PARTIAL SECOND FLOOR PLAN - LAB 322
SCALE: NOT TO SCALE
B4 KEYED NOTES
AAD AUTOMATIC AIR DAMPER
AHU AIR HANDLING UNIT
APD AIR PRESSURE DROP
BHP BRAKE HORSE POWER
BTU BRITISH THERMAL UNIT
CWS CHILLED WATER SUPPLY
CWR CHILLED WATER RETURN
CH CHILLER
CO CLEANOUT
C COMMON
CDWS CONDENSER WATER SUPPLY
CDWR CONDENSER WATER RETURN
CONV CONVECTOR
CFM CUBIC FEET PER MINUTE
DIA DIAMETER
DN DOWN
EAT ENTERING AIR TEMPERATURE
EDB ENTERING DRY BULB TEMPERATURE
EWT ENTERING WATER TEMPERATURE
EXIST EXISTING
HWS HOT WATER SUPPLY
HWR HOT WATER RETURN
HPS HIGH PRESSURE STEAM
IN INCH
KW KILOWATT
LAT LEAVING AIR TEMPERATURE
LWB LEAVING WET BULB
LPS LOW PRESSURE STEAM
LPC LOW PRESSURE CONDENSATE
LWT LEAVING WATER TEMPERATURE
LV LOUVER
MBH 1000 BTUH
MAX MAXIMUM
MIN MINIMUM
MV MANUAL VENT
NC NORMALLY CLOSED
NO NORMALLY OPEN, NUMBER
OA OUTSIDE AIR
RA RETURN AIR
RPM REVOLUTION PER MINUTE
SA SUPPLY AIR
SP STATIC PRESSURE
TD TRIPLE DUTY VALVE
TYP TYPICAL
V VOLT
VD VOLUME DAMPER
VSD VARIABLE SPEED DRIVE
FC FLEXIBLE CONNECTION
°F FAHRENHEIT
FCU FAN COIL UNIT
FD FIRE DAMPER
FSD COMBINATION FIRE/SMOKE DAMPER
FPM FEET PER MINUTE
FT FEET
AMP AMPERES
ACCU AIR COOLED CONDENSING UNIT
CT COOLING TOWER
CUH CABINET UNIT HEATER
ET EXPANSION TANK
FR FURNACE
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
P PUMP
PH PHASE
PTAC PACKAGED TERMINAL AIR CONDITIONER
RTH RADIANT TUBE HEATER
RTU ROOF TOP UNIT
SRV STATIONARY ROOF VENT
WH UNIT HEATER
UV UNIT VENTILATOR
VAV VARIABLE AIR VOLUME
WH WALL HEATER
WPD WATER PRESSURE DROP
ACV AIR CONTROL VALVE
B BOILER
BDD BACK DRAFT DAMPER
BTUH BRITISH THERMAL UNIT PER HOUR
BOD BOTTOM OF DUCT
CGR CHILLED GLYCOL RETURN
CGS CHILLED GLYCOL SUPPLY
DB DRY BULB TEMPERATURE
EFF EFFICIENCY
EWB ENTERING WET BULB TEMPERATURE
F FAN
F&T FLOAT AND THERMOSTATIC TRAP
FMS FLOW MEASURING STATION
FTR FIN TUBE RADIATION
DSD DUCT SMOKE DETECTOR
DP DEWPOINT TEMPERATURE
DTS DUAL TEMPERATURE WATER SUPPLY
DX DIRECT EXPANSION
DTR DUAL TEMPERATURE WATER RETURN
EC EXPANSION COMPENSATOR
ENC ENCLOSURE
ESP EXTERNAL STATIC PRESSURE
CD COLD CONDENSATE DRAIN
CCU CEILING CASSETTE UNIT
HD HEAD
HGR HOT GLYCOL RETURN
HGS HOT GLYCOL SUPPLY
HPC HIGH PRESSURE CONDENSATE
HP HORSEPOWER
HRU HEAT RECOVERY UNIT
HUM HUMIDIFIER
DWH DOMESTIC WATER HEATER
HX HEAT EXCHANGER
HR HUMIDITY RATIO, HOUR
HWC HOT WATER COIL
LDB LEAVING DRY BULB TEMPERATURE
MAU MAKEUP AIR UNIT
MOP MAXIMUM OVERCURRENT PROTECTION
MCA MINIMUM CIRCUIT AMPACITY
PD PRESSURE DROP
PG PROPYLENE GLYCOL
RCP RADIANT CEILING PANEL
RH RELATIVE HUMIDITY
RHC REHEAT COIL
SD SMOKE DAMPER
SQ SQUARE
TDH TOTAL DYNAMIC HEAD
PSI POUNDS PER SQUARE INCH
SHC SENSIBLE HEAT CAPACITY
TG TRANSFER GRILLE
THC TOTAL HEAT CAPACITY
WB WET BULB TEMPERATURE
WFS WATER FLOW SWITCH
WG WATER GAUGE
ZD ZONE DAMPER
BD BYPASS DAMPER
EBB ELECTRIC BASE BOARD
AS AIR SEPARATOR
FIL FILTER
EXH EXHAUST AIR
dB DECIBELS
GAL GALLONS
GR GRAINS
TSP TOTAL STATIC PRESSURE
NIC NOT IN CONTRACT
LB POUND
HZ HERTZ
VIF VERIFY IN FIELD
WWM WELDED WIRE MESH
WCU WALL CASSETTE UNIT
VUV VERTICAL UNIT VENTILATOR
KH KILN HOOD
ERU ENERGY RECOVERY UNIT
DC DUST COLLECTOR
CP CONDENSATE PUMP
ACU AIR CONDITIONING UNIT
IND INDUCTION UNIT
ABBREVIATIONS
VAL VALANCE UNIT
VP VACUUM PUMP
SS SOLIDS SEPARATOR
RAD RADIATOR, RADIANT PANEL
1. COORDINATE DEMOLITION WITH OTHER CONTRACTORS.
2. CONDUCT DEMOLITION TO MINIMIZE INTERFERENCE WITH OCCUPIED BUILDING AREAS. SERVICE TO OTHER PARTS OF
BUILDING SHALL REMAIN ACTIVE.
3. DISCONNECT, CAP, AND IDENTIFY DESIGNATED UTILITIES WITHIN DEMOLITION AREAS.
4. DEMOLISH IN AN ORDERLY AND CAREFUL MANNER, PROTECT EXISTING SUPPORTING STRUCTURAL MEMBERS AND
PARTITIONS TO REMAIN.
5. EXCEPT WHERE NOTED OTHERWISE, REMOVE DEMOLISHED MATERIALS FROM SITE. DO NOT DISPOSE OF ANY
MATERIAL ON SITE.
6. REMOVE DEMOLISHED MATERIAL FROM SITE AS WORK PROGRESSES. UPON COMPLETION OF WORK LEAVE AREAS IN
CLEAN CONDITION.
7. COMPLETELY REMOVE ALL PIPING, DUCTWORK, HANGERS, ETC..
8. PROVIDE REINSULATION TO EXISTING DISTRIBUTION AND SERVICES SCHEDULED TO REMAIN IN USE.
9. DEMOLITION SHALL INCLUDE REMOVAL OF ALL STRAPS, HANGERS, CLAMPS,CHANNEL, AND OTHER DEVICES USED
FOR SUPPORTING EQUIPMENT.
10. DRAIN, VENT, OR DISCHARGE MECHANICAL SYSTEMS PRIOR TO DISASSEMBLY.
11. IN MECHANICAL SYSTEMS BEING REMOVED, BLANK OFF, PLUG, OR CAP ALL BRANCH LINES (DUCTWORK OR PIPING)
SCHEDULED FOR DEMOLITION WHERE THEY TIE INTO MAIN LINES TO REMAIN.
12. DEMOLITION INCLUDES REMOVAL OF EQUIPMENT, SELECTED DUCTWORK, PIPING, ECT... THE DEMOLITION DRAWINGS SHOW THE GENERAL SCOPE OF ITEMS TO BE REMOVED. IT IS THE MECHANICAL CONTRACTORS RESPONSIBILITY TO REMOVE ALL ASSOCIATED EQUIPMENT AND MATERIALS THAT ARE NOT SPECIFICALLY IDENTIFIED TO BE REUSED, TO
PRODUCE A CLEAN AND WORKABLE SYSTEM.
13. REMOVE ALL OBSOLETE, FREE HANGING AND OPEN OR DEAD ENDED AIR, GLYCOL PIPING OR DUCT.
14. THE MECHANICAL DRAWINGS ARE DIAGRAMMATICAL. IT IS NOT POSSIBLE OR THE INTENT TO SHOW ALL PIECES OF THE SYSTEMS BEING REMOVED AND/OR INSTALLED UNDER THE CONTRACT. IT IS THE CONTRACTORS RESPONSIBILITY TO PROVIDE A COMPLETE, RELIABLE AND WORKING SYSTEM. IT IS ALSO THE CONTRACTORS RESPONSIBILITY TO DEMOLISH ALL MATERIALS ASSOCIATED TO REMOVALS TO PROVIDE A "LIKE NEW" APPEARANCE WITHIN THE SPACES (IE NO HANGARS, TUBING ETC ABANDONED IN PLACE UNLESS DIRECTED TO DO SO).
1. ALL WORK SHALL CONFORM TO ALL APPLICABLE RULES, REGULATIONS AND CODES, INCLUDING, BUT NOT LIMITED TO THE APPLICABLE ENERGY CONSERVATION CODE OF NEW YORK
STATE, AND BUILDING CODES OF NEW YORK STATE.
2. ALL EQUIPMENT SHALL COMPLY WITH THE PROVISIONS OF THE APPLICABLE ENERGY CONSERVATION CODE OF NEW YORK STATE. ALL SUBMITTALS FOR EQUIPMENT COVERED BY THE
CODE SHALL INCLUDE THE MANUFACTURER'S STATEMENT OF CONFORMANCE TO THE CODE.
3. FIELD VERIFY ALL DIMENSIONS PRIOR TO DUCTWORK FABRICATION OR ANY OTHER MECHANICAL WORK. MECHANICAL CONTRACTOR SHALL COORDINATE INSTALLATION OF EQUIPMENT, PIPING, DUCTWORK, AND PADS WITH OTHER CONTRACTORS. PROVIDE FITTINGS, ELEVATION CHANGES, TRANSITIONS, AND OFFSETS REQUIRED, WHETHER SHOWN OR NOT, TO AVOID
CONFLICTS WITH WORK OF OTHER CONTRACTS.
4. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR SEALING ALL HVAC PENETRATIONS (PIPING, DUCTWORK, ETC) IN ACCORDANCE WITH THE BUILDING CODE OF NEW YORK
STATE, AND WHERE SHOWN OR SPECIFIED.
5. ITEMS OF SPECIFIC MANUFACTURER'S SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE PRINTED INSTRUCTIONS AND/OR MANUFACTURER'S REPRESENTATIVES DIRECTIONS.
6. MECHANICAL CONTRACTOR TO INSTALL ALL NECESSARY STIFFENERS, BRACES, STRUTS, ETC, WHETHER SHOWN OR NOT, TO PROVIDE A COMPLETE, SAFE, AND DURABLE SYSTEM.
7. DIMENSIONS SHOWN "AFF" INDICATE THE ACTUAL CLEAR DIMENSIONS FROM THE BOTTOM OF THE ITEM TO THE FINISHED FLOOR ELEVATION; UNLESS INDICATED OTHERWISE.
8. SUPPORT AND EQUIPMENT DETAILS MAY VARY TO SUIT EQUIPMENT AND PARTS SUPPLIED.
9. WELD ALL STEEL ANGLE JOINTS UNLESS OTHERWISE SHOWN.
10. PROVIDE NECESSARY BY-PASSES AND BALANCING MEANS AS REQUIRED TO ASSURE PROPER SYSTEM OPERATION.
11. ALL DUCT DIMENSIONS SHOWN ARE "SIDE SEEN" BY "SIDE NOT SEEN" AND ARE THE CLEAR INSIDE DIMENSIONS UNLESS OTHERWISE NOTED.
12. PROVIDE ACCESS DOORS AND CLEARANCES FOR EASY ACCESS TO ALL FIRE DAMPERS, CONTROL DAMPERS, LOUVERS, FILTERS, COILS, AND FANS.
13. BRANCH DUCTS TO GRILLES, DIFFUSERS OR REGISTERS SHALL BE THE SAME SIZE AS GRILLE, DIFFUSER OR REGISTER NECK SIZE UNLESS INDICATED OTHERWISE.
14. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR PRECISE LOCATION OF DIFFUSERS AND REGISTERS.
15. PROVIDE MANUAL VOLUME DAMPERS IN ALL BRANCH TAKE-OFFS AND WHERE SHOWN.
16. PROVIDE ALL CONTROL AND INTERLOCK WIRING REQUIRED OR SPECIFIED THAT IS NOT PROVIDED BY THE ELECTRICAL CONTRACTOR.
17. COORDINATE WITH ELECTRICAL CONTRACTOR AND FIRE PROTECTION CONTRACTOR REGARDING THE RESPONSIBILITIES FOR SUPPLYING, INSTALLING AND WIRING OF HVAC-RELATED
DISCONNECT SWITCHES, STARTERS, SAFETY INTERLOCKS, EMERGENCY SHUTDOWN AND WIRING.
18. WORK ON M-SERIES DRAWINGS IS BY THE MECHANICAL CONTRACTOR UNLESS OTHERWISE NOTED.
19. VERIFY ALL LOCATIONS, DIMENSIONS, EQUIPMENT ARRANGEMENTS, CLEARANCES AND ELECTRICAL CHARACTERISTICS IN THE FIELD PRIOR TO BID. PROMPTLY NOTIFY THE
ARCHITECT/ENGINEER OF ANY DISCREPANCIES.
20. PRIOR TO CUTTING THROUGH FLOORS AND WALLS, THE CONTRACTOR SHALL VERIFY THE LOCATIONS OF ALL STRUCTURAL MEMBERS, JOISTS, AND OR COLUMNS. PROMPTLY NOTIFY THE ARCHITECT/ENGINEER OF ANY DISCREPANCIES. DO NOT CUT ANY STRUCTURAL MEMBERS UNLESS SPECIFICALLY DIRECTED TO DO SO.
21. THE MECHANICAL CONTRACTOR SHALL REMOVE DUCTWORK BACK TO A POINT WHICH WILL ALLOW THE INSTALLATION OF SUPPORT STEEL THAT IS REQUIRED / RELATED TO THE HVAC EQUIPMENT. THE MECHANICAL CONTRACTOR SHALL COORDINATE WITH THE GENERAL CONTRACTOR IN THE LOCATIONS WHICH WILL REQUIRE MECHANICAL SUPPORT STEEL.
22. INSTALL ALL NEW DUCT AND PIPE WITHIN EXISTING OPENINGS SUCH THAT IT ALLOWS AS MUCH SPACE AS POSSIBLE TO ONE SIDE WHICH MAY ALLOW PASSAGE.
23. ALL EXISTING-TO-REMAIN DIFFUSERS AND DUCT SYSTEMS TO BE REBALANCED TO CFM INDICATED.
24. PATCH AND SEAL DUCT WHERE BRANCHES / TAKEOFFS HAVE BEEN REMOVED AND NO NEW CONNECTION IS NEEDED.
25. CAP AND SEAL PIPING WHERE BRANCHES / TAKEOFFS HAVE BEEN REMOVED AND NO NEW CONNECTION IS NEEDED.
DUCTWORK
GENERAL
PIPING
MANUAL VOLUME DAMPER
AUTOMATIC AIR DAMPER
SQUARE ELBOW WITH TURNING VANES
LINEAR DIFFUSER
NEGATIVELY PRESSURIZED DUCT INTO THE PLANE
NEGATIVELY PRESSURIZED DUCT OUT OF THE PLANE
POSITIVELY PRESSURIZED DUCT INTO THE PLANE
POSITIVELY PRESSURIZED DUCT OUT OF THE PLANE
FLEXIBLE DUCT CONNECTOR
SQUARE TO ROUND DUCT TRANSITION
DAMPER MOTOR
DIRECTION OF AIRFLOW
TEMPERATURE SENSOR WITH LOCKING GUARD
PIPE GUIDE
PIPE ANCHOR
PIPE RISER
PIPE DROP
X
THREE-WAY CONTROL VALVE
TWO-WAY CONTROL VALVE
AUTOMATIC AIR VENT
MANUAL AIR VENT
PRESSURE RELIEF VALVE
NEEDLE VALVE
CHECK VALVE
CALIBRATED FLOW BALANCING VALVE
FLEXIBLE PIPE CONNECTOR
PIPE CAP
TRIPLE DUTY VALVE
STRAINER
REDUCER
UNION
THERMOMETER
PRESSURE GAUGE
FC
AAD
T
SQUARE MAIN TO ROUND BRANCH TAKE-OFF
INLINE PUMP
AIR SEPARATOR
TYPE
CFM
NECK SIZE
(TYPICAL OF) DIFFUSER DESIGNATION
PRESSURE SENSORP
M
BUTTERFLY VALVE
UNIT
GPMGPM
COOLING HEATING
UNIT WITH HEATING AND COOLING
UNIT
MAX. CFM
UNIT WITH AIR FLOW
UNIT
GPM
UNIT WITH HEATING OR COOLING
GENERAL EQUIPMENT DESIGNATIONUNIT
BASE MOUNTED PUMP
CONNECT TO EXISTING
DISCONNECT FROM EXISTING
DEMOLITION ITEMS
NEW WORK ITEMS
BALL VALVE
EXISTING ITEMS
SUPPLY DIFFUSER
RETURN DIFFUSER
KEYNOTE
FD FIRE DAMPER
VIEW
SHEET
ENLARGED PLAN & DETAIL CALL OUT
VOLUME DAMPER
NO ALTERATION PERMITTED HEREON
EXCEPT AS PROVIDED UNDER SECTION
7209 SUBDIVISION 2 OF THE NEW YORK
EDUCATION LAW
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJECT NO:
DATE
DATE:
MARK
REVISIONS
DESCRIPTION
A
1 2 3
1 2 3
C
A
D
B
C
D
B
499 Col. Eileen Collins Blvd.
Syracuse, New York 13212
Phone: 315-455-2000 Fax: 315-455-9667 www.cscos.com
C&S Engineers, Inc.
Copyright ©
IL
LI
C K
E N
A B
LI
N
G P
R O
JE
C
T S
, W A
LT
E
LL
L A
B R
E
LO
C A
T
IO
N S
LA
B
F
O R
E S
T R
Y D
R
IV
E
S Y
R A
C U
S E
N
Y
MAY 2026
E. COHEN
L. MERRY
K. PIERCE, PE
555.064.006
GENERAL NOTES,
SYMBOLS, &
ABBREVIATIONS
M-001-322
SCALE: NOT TO SCALEA1 ABBREVIATIONS
SCALE: NOT TO SCALEC2 GENERAL DEMOLITION NOTES
SCALE: NOT TO SCALEC1 GENERAL NOTES
SCALE: NOT TO SCALEA4 SYMBOLS
SHEET METAL DUCTWORK:
• ALL DUCTWORK TO BE RIGID SHEET METAL CONSTRUCTED FROM GALVANIZED SHEET STEEL IN ACCORDANCE WITH SMACNA LOW VELOCITY DUCT CONSTRUCTION STANDARDS. ASSEMBLE
AND INSTALL DUCTWORK IN ACCORDANCE WITH RECOGNIZED INDUSTRY PRACTICE FOR ACHIEVING AIR TIGHT (5% LEAKAGE) AND NOISELESS (NO OBJECTIONABLE NOISE) SYSTEMS, CAPABLE OF PERFORMING EACH INDICATED SERVICE. FURNISH ALL REQUIRED DAMPERS, TRANSITIONS, CONNECTIONS TO AIR TERMINALS, AND OTHER ACCESSORIES NECESSARY FOR A COMPLETE OPERATING SYSTEM. NO VARIATION OF DUCT CONFIGURATION OR SIZES WILL BE PERMITTED EXCEPT BY PERMISSION FROM THE ENGINEER.
FLEXIBLE AIR DUCT:
• FLEXIBLE DUCT FOR CONNECTIONS SHALL BE FACTORY FABRICATED ASSEMBLY CONSISTING OF AN INNER SLEEVE, INSULATION AND OUTER MOISTURE BARRIER. THE INNER SLEEVE SHALL
BE CONSTRUCTED OF A CONTINUOUS VINYL COATED SPRING STEEL WIRE HELIX FUSED TO CONTINUOUS LAYER OF FIBERGLASS IMPREGNATED AND COATED VINYL. A 1-1/4" THICK LAYER OF INSULATING BLANKET OF FIBERGLASS WOOL SHALL ENCASE THE INNER SLEEVE AND BE SHEATHED WITH AN OUTER MOISTURE BARRIER OF A BIDIRECTIONAL REINFORCED METALIZED VAPOR BARRIER. THE FLEXIBLE DUCT SHALL BE RATED FOR A MAXIMUM WORKING VELOCITY OF 6000FPM AND SHALL BE UL LISTED UNDER THEIR UL-181 STANDARDS AS A CLASS 1 DUCT AND SHALL COMPLY WITH NFPA 90A. THE FLEXIBLE DUCT SHALL BE THERMAFLEX M-KC OR APPROVED EQUIVALENT. FLEXIBLE DUCT SHALL ROUTE FROM SHEET METAL DUCTWORK TO
CEILING DIFFUSERS ONLY. THERE SHALL BE NO EXPOSED FLEXIBLE DUCT.
HANGERS & SUPPORTS:
• HANGER RODS FOR NONCORROSIVE ENVIRONMENTS: CADMIUM-PLATED STEEL RODS AND NUTS.
• STRAP AND ROD SIZES: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," TABLE 5-1, "RECTANGULAR DUCT HANGERS MINIMUM SIZE," AND TABLE
5-2, "MINIMUM HANGER SIZES FOR ROUND DUCT."
• DUCT ATTACHMENTS: SHEET METAL SCREWS, BLIND RIVETS, OR SELF-TAPPING METAL SCREWS; COMPATIBLE WITH DUCT MATERIALS.
• HORIZONTAL PIPING HANGERS: ADJUSTABLE, STEEL CLEVIS HANGERS AT MAXIMUM 6 FEET SPACING.
DAMPERS:
• STANDARD LEAKAGE RATING, SUITABLE FOR HORIZONTAL OR VERTICAL APPLICATIONS.
• FRAMES: HAT-SHAPED, GALVANIZED-STEEL CHANNELS, 0.064-INCH MINIMUM THICKNESS. MITERED AND WELDED CORNERS. FLANGES FOR ATTACHING TO WALLS AND FLANGELESS FRAMES
FOR INSTALLING IN DUCTS.
• BLADES: MULTIPLE OR SINGLE BLADE. PARALLEL- OR OPPOSED-BLADE DESIGN. STIFFEN DAMPER BLADES FOR STABILITY. GALVANIZED-STEEL, 0.064 INCH THICK.
• BLADE AXLES: GALVANIZED STEEL.
TESTING, ADJUSTING AND BALANCING:
• TESTING, ADJUSTING AND BALANCING OF ALL WORK SHALL BE COMPLETED BY AN INDEPENDENT CONTRACTOR WHO IS CURRENTLY LICENSED BY THE ASSOCIATED AIR BALANCING
COUNCIL (ABBC) OR NATIONAL ENVIRONMENTAL BALANCING BUREAU (NEBB).
• BALANCE AIR QUANTITIES TO WITHIN PLUS OR MINUS 10% OF THAT INDICATED ON THE DRAWINGS.
• ADJUST AIR INLETS AND OUTLETS FOR EACH SPACE TO INDICATE AIRFLOWS.
1. SET AIRFLOW PATTERNS OF ADJUSTABLE OUTLETS FOR PROPER DISTRIBUTION WITHOUT DRAFTS.
2. MEASURE INLETS AND OUTLETS AIRFLOW.
3. ADJUST EACH INLET AND OUTLET FOR SPECIFIED AIRFLOW.
4. RE-MEASURE EACH INLET AND OUTLET AFTER THEY HAVE BEEN ADJUSTED.
• FINAL BALANCING REPORT SHALL BE INCLUDED IN THE OPERATION AND MAINTENANCE MANUAL.
SUBMITTALS:
• SUBMIT THE FOLLOWING INFORMATION AS APPLICABLE AND AS REQUIRED FOR ALL WORK SCHEDULED AND SPECIFIED:
1. MANUFACTURER'S PRODUCT DATA SHEETS.
2. SHOP DRAWINGS INCLUDING DIMENSIONED EQUIPMENT LAYOUTS, POINT-TO-POINT WIRING DIAGRAMS AND SEQUENCES OF OPERATION.
3. OPERATION AND MAINTENANCE MANUALS.
HANGERS:
• HANGERS SHALL INCLUDE ALL MISCELLANEOUS STEEL SUCH AS ANGLE IRON, BANDS, C-CLAMPS WITH RETAINING CLIPS, CHANNELS, HANGER RODS, ETC. NECESSARY FOR THE
INSTALLATION OF WORK.
• HANGERS SHALL BE FASTENED TO BUILDING STEEL, CONCRETE, OR MASONRY, BUT NOT TO PIPING OR DUCTWORK. DUCTWORK SHALL NOT BE SUPPORTED FROM ROOF DECKING AND/OR
BRIDGING, BUT SHALL BE SUSPENDED FROM THE TOP CHORD OF BAR JOISTS, STEEL OR OTHER STRUCTURE. DUCTWORK SHALL CLEAR ALL SPRINKLERS AND OTHER OBSTACLES AND SHALL BE HUNG AS HIGH AS POSSIBLE IN WORK AND STORAGE AREAS. WHERE INTERFERENCES OCCUR, IN ORDER TO SUPPORT DUCTWORK OR PIPING, THE CONTRACTOR MUST INSTALL TRAPEZE TYPE HANGERS OR SUPPORTS WHICH SHALL BE LOCATED WHERE THEY DO NOT INTERFERE WITH ACCESS TO FIRE DAMPERS, VALVES, ACCESS DOORS AND OTHER EQUIPMENT SERVICE REQUIREMENTS AND/OR OTHER TRADES. HANGER TYPES AND INSTALLATION METHODS ARE SUBJECT TO OWNER CRITERIA.
• HANGERS AND PIPING OF DISSIMILAR METALS SHALL BE DI-ELECTRICALLY SEPARATED FROM ONE ANOTHER.
• ADJUSTABLE, STEEL CLEVIS HANGERS (MSS TYPE 1): FOR SUSPENSION OF NONINSULATED OR INSULATED STATIONARY PIPES, INSTALL HANGERS AND SUPPORTS COMPLETE WITH
NECESSARY INSERTS, BOLTS, RODS, NUTS, WASHERS, AND OTHER ACCESSORIES.
INSTRUMENTATION AND CONTROLS:
• GENERAL: CONTACT OWNER'S CONTROLS PROVIDER FOR CONTROLS WORK. CONTROLS CONTRACTOR SHALL PROVIDE ALL CONTROL COMPONENTS, WIRING, ETC. FOR A COMPLETE AND
OPERABLE SYSTEM.
GRILLES, REGISTERS & DIFFUSERS:
• TYPE S-1 - SUPPLY DIFFUSER - PRICE MODEL PDF OR EQUAL.
a. DESCRIPTION: PERFORATED DIFFUSER.
b. FABRICATION: STEEL.
c. BORDER: PROVIDE APPROPRIATE BORDER TO ACCOMMODATE MOUNTING PER CEILING TYPE.
CONDENSATE PIPING:
• PVC PLASTIC PIPE: ASTM D1785
• PVC SOCKET FITTINGS:ASTM D2466 FOR SCHEDULE 40
• SOLVENT CEMENTS FOR PVC PIPING: ASTM D2564
• SCHEDULE 40, PVC PLASTIC PIPE AND FITTINGS AND SOLVENT-WELDED JOINTS
HOSE EXTRACTION ARM:
• TELESCOPIC FLEXIBLE HOSE EXTRACTION ARM EQUAL TO IAP PRODUCTS MODEL FA-044872-T.
REFRIGERANT PIPING:
• LINE TEST PRESSURE: 535 PSIG.
• COPPER TUBE: ASTM B 280, TYPE ACR.
• WROUGHT-COPPER FITTINGS, BRAZED-JOINT: ASME B16.50.
• WROUGHT-COPPER UNIONS: ASME B16.22.
• SOLDER FILLER METALS: ASTM B 32. USE 95-5 TIN ANTIMONY OR ALLOY HB SOLDER TO JOIN COPPER SOCKET FITTINGS ON COPPER PIPE
THERMAL INSULATION:
• REFRIGERANT PIPING: FLAME - SPREAD INDEX OF 25 OR LESS, AND SMOKE-DEVELOPED INDEX OF 50 OR LESS. FLEXIBLE ELASTOMERIC: CLOSED-CELL, OR EXPANDED-RUBBER MATERIALS.
COMPLY WITH ASTM C534/C534M, TYPE I. THICKNESS: 1/2 IN.
• SUPPLY DUCTWORK: 1.5 INCH FIBERGLASS WRAP INSULATION WITH ALL PURPOSE ALUMINUM JACKET.
INDOOR UNIT (AC-1):
• MITSUBISHI ELECTRIC DUCTED INDOOR UNIT: MODEL PEAD-AA-36NL OR EQUAL. NOMINAL COOLING CAPACITY: 33,000 BTUH; HEATING CAPACITY: 33,500 BTUH; 208V / 1 PHASE; 1,100 CFM.
• PROVIDE WITH BUILT-IN CONDENSATE PUMP
• PROVIDE WITH WIRED CONTROLS WITH WALL MOUNTED THERMOSTAT.
THERMOSTAT:
• LCD BACKLIT SCREEN WITH BUTTONS TO SWITCH BETWEEN MODES AND ADJUST TEMPERATURE.
AIR-COOLED CONDENSING UNIT (ACCU-1):
• ACCU-1: MITSUBISHI ELECTRIC OUTDOOR UNIT: MODEL SUZ-AK36NLHZ OR EQUAL. 208 V / 1 PHASE. THE OUTDOOR UNIT POWERS THE INDOOR UNIT, AND SHOULD A POWER OUTAGE OCCUR, THE SYSTEM IS AUTOMATICALLY RESTARTED WHEN POWER RETURNS.
• INVERTER-DRIVEN COMPRESSOR
• BUILT-IN BASE PAN HEATER.
• PROVIDE WITH 18" H SNOW STAND.
FUME HOOD - MOTT MANUFACTURING:
• PRO BENCH - VERTICAL SASH MODEL #7221040 (FRP)
• HOOD SIZE: 48"; 10"Ø DUCT CONNECTION
• CAV SETUP (18" MAX SASH OPENING - 80 FPM/407 CFM)
• CHAIN AND SPROCKET SASH SYSTEM
• LED LIGHT
• AFA1000 FACE VELOCITY ALARM (CAV SETUP)
• ONE OF EACH LAB SERVICE FIXTURES
a. COLD WATER
b. VACUUM
c. AIR
d. GAS
• PLUMBING PRE-PIPED DOWN TO BOTTOM, ROUTED TO THE REAR OF THE FUME HOOD.
W
W
6" M
IN
NOTES:
1. CONTRACTOR HAS OPTION OF PROVIDING EITHER SQUARE
ELBOW WITH TURNING VANES OR LONG RADIUS ELBOW.
SQUARE ELBOW
RADIAL ELBOW
SUPPLY AIR FLOW
BRANCH DUCT
90 DEGREE ELBOW
WITH TURNING VANES
45 DEGREE BOOT
VOLUME DAMPER
RETURN/EXHAUST AIRFLOW
1.
5W
NO ALTERATION PERMITTED HEREON
EXCEPT AS PROVIDED UNDER SECTION
7209 SUBDIVISION 2 OF THE NEW YORK
EDUCATION LAW
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJECT NO:
DATE
DATE:
MARK
REVISIONS
DESCRIPTION
A
1 2 3
1 2 3
C
A
D
B
C
D
B
499 Col. Eileen Collins Blvd.
Syracuse, New York 13212
Phone: 315-455-2000 Fax: 315-455-9667 www.cscos.com
C&S Engineers, Inc.
Copyright ©
IL
LI
C K
E N
A B
LI
N
G P
R O
JE
C
T S
, W A
LT
E
LL
L A
B R
E
LO
C A
T
IO
N S
LA
B
F
O R
E S
T R
Y D
R
IV
E
S Y
R A
C U
S E
N
Y
MAY 2026
E. COHEN
L. MERRY
K. PIERCE, PE
555.064.006
SPECIFICATIONS &
DETAILS
M-002-322
SCALE: NOT TO SCALEA3 HVAC SPECIFICATIONS - LAB 322
SCALE: NOT TO SCALEA1 DUCT DETAIL
RHC (E)
VD
D
C
B
10 12 14
10ø(E)
10ø(E) ø
(E x1
2( E
18x12(E)19x10(E)
19x14(E) x1
6( E x6
(E
15x6(E)15x6(E)
20x16(E)
17x10(E)
10x4 SERVING 4TH
FLOOR ABOVE (TYP)
20x6 20x8
A
15 16 17 18 19 20 22
T
AC-1
ACCU-1
S1
12x12
12ø
14x12(E) x1
6( E
12x10(E)12x8(E)8x6(E)
26x16(E)
D
C
B
12 14
A
15 16 17 18 19 20 22
20x16(E)
14x12(E) 20x14(E)
WA-HC-21 (E)
WA-HC-22 (E)
CAP
B
10 12 14
10x16(E)
A
EX-14 (E)
EX-6 (E)
EX-7 (E)
EX-8 (E)
EX-9 (E)
EX-10 (E)
ALT 1 WORK
EX-12 (E)
REPLACE FAN MOTOR WITH
2HP/208V/3PH MOTOR. BALANCE
FAN TO 4,660 CFM @ 1.5 T.S.P.
EX-13 (E)
16X20 (E) TOP
14X14 (E) BOTTOM
22x20(E)
20x16(E)
EX-12 (E)
MEASURE FAN PERFORMANCE AT
EXISTING CONDITIONS. SUBMIT
RESULTS FOR REVIEW. NO ADDITIONAL
WORK TO BE PERFORMED UNTIL
REVIEW IS COMPLETED.
NO ALTERATION PERMITTED HEREON
EXCEPT AS PROVIDED UNDER SECTION
7209 SUBDIVISION 2 OF THE NEW YORK
EDUCATION LAW
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJECT NO:
DATE
DATE:
MARK
REVISIONS
DESCRIPTION
A
1 2 3
1 2 3
C
A
D
B
C
D
B
499 Col. Eileen Collins Blvd.
Syracuse, New York 13212
Phone: 315-455-2000 Fax: 315-455-9667 www.cscos.com
C&S Engineers, Inc.
Copyright ©
IL
LI
C K
E N
A B
LI
N
G P
R O
JE
C
T S
, W A
LT
E
LL
L A
B R
E
LO
C A
T
IO
N S
LA
B
F
O R
E S
T R
Y D
R
IV
E
S Y
R A
C U
S E
N
Y
LAB 322
MAY 2026
E. COHEN
L. MERRY
K. PIERCE, PE
555.064.006
PARTIAL FLOOR PLANS
LAB 322
M-101-322 0 16'8'4'
0 16'8'4' 0 16'8'4'
SCALE: NOT TO SCALE
A4 KEYPLAN
SUPPORT AC-1 FROM STRUCTURE ABOVE WITH THREADED RODS AND VIBRATION ISOLATORS.
SIZE REFRIGERANT PIPING PER MANUFACTURER'S RECOMMENDATIONS.
10" Ø FUME HOOD EXHAUST DOWN TO FUME HOOD.
4" Ø HOSE EXTRACTION ARM.
BALANCE TO 150 CFM EACH.
CLOSE REHEAT COIL CONTROL VALVE.
BALANCE OPEN END S.A. DUCT ABOVE CEILING TO 1,100 CFM.
BALANCE TO 250 CFM EACH.
WINDOW AC UNIT TO REMAIN.
SCALE: NOT TO SCALE
A3 KEYED NOTES
SCALE: 1/8" = 1'-0"C3 PARTIAL THIRD FLOOR PLAN - LAB 322
SCALE: 1/8" = 1'-0"A1 PARTIAL SECOND FLOOR PLAN
SCALE: 1/4" = 1'-0"C1 PARTIAL PENTHOUSE PLAN
PENTHOUSE
1. COORDINATE REMOVAL WORK WITH OTHER CONTRACTORS.
2. CONDUCT REMOVAL WORK TO MINIMIZE INTERFERENCE WITH OCCUPIED BUILDING AREAS. SERVICE TO
OTHER PARTS OF BUILDING SHALL REMAIN ACTIVE.
3. REMOVE IN AN ORDERLY AND CAREFUL MANNER, PROTECT EXISTING SUPPORTING STRUCTURAL
MEMBERS AND PARTITIONS TO REMAIN.
4. EXCEPT WHERE NOTED OTHERWISE, REMOVE MATERIALS FROM SITE. DO NOT DISPOSE OF ANY
MATERIAL ON SITE.
5. REMOVE MATERIAL FROM SITE AS WORK PROGRESSES. UPON COMPLETION OF WORK LEAVE AREAS IN
CLEAN CONDITION.
6. REMOVAL SHALL INCLUDE REMOVAL OF ALL STRAPS, HANGERS, CLAMPS, CHANNEL, AND OTHER DEVICES
USED FOR SUPPORTING EQUIPMENT.
7. PRIOR TO ENGAGING IN REMOVAL WORK, CONTRACTOR SHALL NOTIFY ENGINEER OF ANY
DISCREPANCIES BETWEEEN EXISTING FIELD CONDITIONS AND PROJECT DRAWINGS.
1. ELECTRICAL WORK SHALL CONFORM TO ALL STATE, LOCAL, AND NATIONAL ELECTRICAL CODES.
2. ELECTRICAL CHARACTERISTICS SHALL BE VERIFIED WITH EQUIPMENT MANUFACTURER.
3. ITEMS OF SPECIFIC MANUFACTURERS SHALL BE INSTALLED IN STRICT ACCORDANCE WITH
MANUFACTURER'S PRINTED INSTRUCTIONS AND/OR MANUFACTURER'S REPRESENTATIVE'S DIRECTIONS.
4. THE CONTRACTOR SHALL FIELD VERIFY ALL LOCATIONS AND DIMENSIONS SHOWN ON DRAWINGS.
5. ALL CONDUIT AND WIRING SCHEDULES SHALL BE VERIFIED BEFORE INSTALLATION.
6. THE ELECTRICAL CONTRACTOR SHALL COORDINATE THE INSTALLATION OF ALL EQUIPMENT WITH OTHER
CONTRACTORS.
7. ALL AREAS DISTURBED BY WORK SHALL BE RESTORED TO A CONDITION EQUAL TO OR BETTER THAN
ORIGINAL AS DETERMINED BY THE ARCHITECT.
8. ALL ELECTRICAL CONDUIT AND CONDUCTORS DISCONNECTED AND NOT TO BE REUSED SHALL BE
REMOVED.
9. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS BEFORE STARTING WORK. IF ONLY A PORTION OF AN EXISTING CIRCUIT IS BEING REMOVED FOR DEMOLITION, CONTINUITY SHALL BE
MAINTAINED TO THE REST OF THE REMAINING CIRCUIT.
10. ALL BRANCH CIRCUIT CONDUCTORS SHALL BE #12AWG UNLESS OTHERWISE SHOWN.
11. ALL BRANCH CIRCUITS SHALL CONSIST OF 2 CONDUCTORS PLUS GROUND, UNLESS OTHERWISE SHOWN.
J
XXX
S
QUAD RECEPTACLE, MOUNT 18" AFF UNLESS OTHERWISE NOTED
JUNCTION BOX
FUSED DISCONNECT SWITCH
NON FUSED DISCONNECT SWITCH
BRANCH CIRCUIT HOME RUN WITH CIRCUIT NUMBER
SEE PANEL SCHEDULES FOR DETAILS
SPECIAL RECEPTACLE
DATA OUTLET, EXISTING
PANEL BOARD, REFER TO PANEL BOARD SCHEDULE
EXISTING WORK LINETYPE
DEMOLITION WORK LINETYPES
NEW WORK LINETYPE
XX
DUPLEX RECEPTACLE, MOUNT AT 18" AFF UNLESS NOTATION INDICATES OTHERWISE.
CTR = ABOVE COUNTER
IG = ISOLATED GROUND
GFI = GROUND FAULT CIRCUIT INTERRUPTER, MOUNT AT 48" AFF UNLESS OTHERWISE NOTED
WP = GFI WITH IN-USE WEATHERPROOF COVER, MOUNT AT 42" AFF UNLESS OTHERWISE NOTED
XP = EXPLOSION PROOF
SP = SURGE PROTECTED
SINGLE POLE SWITCH, UNLESS NOTATION INDICATES OTHERWISE.
OS = OCCUPANCY SENSOR
OSD = OCCUPANCY SENSOR WITH DIMMER
2 = DOUBLE POLE SWITCH
3 = THREE-WAY SWITCH
4 = FOUR-WAY SWITCH
D = DIMMER SWITCH
K = KEYED SWITCH
M = MANUAL MOTOR STARTER
T = TIMER SWITCH
LV = LOW VOLTAGE SWITCH
XX
PLAN SYMBOLS
or
DATA OUTLET, NEW
CR CORD REEL
A AMPERE
A/C AIR CONDITIONING
AC ALTERNATE CURRENT
ACCU AIR COOLED CONDENSING UNIT
AF AMPERE FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
A/H AIR HANDLER
AIC AMPERE INTERRUPTING CAPACITY
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AU AT UNIT
AUX AUXILIARY
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BFG BELOW FINISHED GRADE
BRK BREAKER
BOH BACK OF HOUSE
C CONDUIT
CA CABLE
CAB CABINET
CAT5E CATEGORY-5E
CC CABLED CONDUCTORS
CH CHILLER
CKT CIRCUIT
CLL CONTRACT LIMIT LINE
CMH COMMUNICATION MANHOLE
CO CONDUIT ONLY
COMM COMMUNICATION
CPB COMMUNICATION PULLBOX
CT CURRENT TRANSFORMER
CTR ABOVE COUNTER
CUC COMMON USER CABLE
CUTC COMMON USER TERMINAL CABINET
D DEEP
DC DIRECT CURRENT
DISC DISCONNECT
DN DOWN
DP DISTRIBUTION PANEL
DPST DOUBLE POLE SINGLE THROW
DPDT DOUBLE POLE DOUBLE THROW
EER ELECTRICAL EQUIPMENT ROOM
ELECT ELECTRICAL
ELEV ELEVATION
EMT ELECTRICAL METALLIC TUBING
EQUIP EQUIPMENT
EXIST EXISTING
(E) EXISTING TO REMAIN
F FUSE
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FAT FIRE ALARM TERMINATION
FBO FURNISHED BY OWNER
FD/SD FIRE DAMPER / SMOKE DETECTOR
FDR FEEDER
FLA FULL LOAD AMPERES
GFI GROUND FAULT INTERRUPT
GND GROUND
H HIGH
HP HORSEPOWER
HZ HERTZ
I/C INTERCOM
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
JB JUNCTION BOX
KA KILOAMP
KV KILOVOLT
KVA KILOVOLT AMPERES
KW KILOWATT
KWH KILOWATT HOUR
KWHD KILOWATT HOUR DEMAND METER
L LENGTH, LONG
LGT LIGHTING
MA MILLIAMPERES
MBB MONITOR BREAKOUT BOX
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCM 1000 CIRCULAR MILLS
MECH MECHANICAL
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MM MULTI MODE
MTD MOUNTED
N/A NOT APPLICABLE
NC NORMALLY CLOSED
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASS.
NF NON-FUSED
NFPA NATIONAL FIRE PROTECTION ASS.
NO NORMALLY OPEN
NTS NOT TO SCALE
OLS OVERLOADS
OC ON CENTER
P POLE
PB PULLBOX
PNL PANEL
PR PAIR
PVC POLYVINYL CHLORIDE
PWR POWER
POC POINT OF CONNECTION
POS POINT OF SALES
PT POTENTIAL TRANSFORMER
REF REFERENCE
REM REMARKS
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT-MEAN-SQUARE
RCPT RECEPTACLE
SBB SOUND BREAKOUT BOX
SDB SOUND DISTRIBUTION BOX
SLC SIGNALING LINE CIRCUIT
SM SINGLE MODE
SPECS SPECIFICATIONS
SPKR SPEAKER
SPST SINGLE POLE SINGLE THROW
SPDT SINGLE POLE DOUBLE THROW
SR SOUND RACK
SST STAINLESS STEEL
ST SHUNT TRIP
SW SWITCH
SWBD SWITCHBOARD
TEL TELEPHONE
TP TWISTED PAIR CABLE
TTB TELEPHONE TERMINAL BOARD
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
V VOLT
VFD VARIABLE FREQUENCY DRIVE
W WATT, WIRE, WIDE
WP WEATHERPROOF
XFMR TRANSFORMER
XP EXPLOSION PROOF
INDICATOR LIGHT LETTER INDICANTS COLOR. R=RED, G=GREEN, Y=YELLOW,
B=BLUE, NO LETTER=CLEAR
CONNECTION POINT OR CABLE SPLICE
TRANSFORMER
CIRCUIT BREAKER
FUSE
GROUND
ONE-LINE SYMBOLS
GENERATOR
TRANSFER SWITCH
UTILITY POLE
PANELBOARD
NO ALTERATION PERMITTED HEREON
EXCEPT AS PROVIDED UNDER SECTION
7209 SUBDIVISION 2 OF THE NEW…