REQUEST FOR INFORMATION (RFI) #2

FCI MORGANTOWN REPAIR WATER TOWER

IFBP01131300002

1. Was the lead paint test done by a testing lab? If yes, are the results available? In parts per million or mg/kg?

RESPONSE: No, Only a swab test was conducted at the institution.

2. Are there any existing Ground Rods for the tank?

RESPONSE: There are no existing ground rods.

3. What size drain valve is desired?

RESPONSE: It should at least meet minimum AWWA ground storage tank code requirements.

4. How thick is the sediment on bottom of tank? Is it spotty or fully covering floor?

RESPONSE: Information not available.

5. Is there a rinse and disinfectant specification for tank interior?

RESPONSE: No, It is the contractor’s choice.