Hutcheson Hall Roof Bid Drawings Feb 2025.pdf

PDF 2 MB Posted

Attached to
Hutcheson Hall Roof Replacement
Solicitation number
87615
Issued by
Middlesex County, Virginia

About this file

This is a set of architectural and engineering drawings for a roof replacement project at Hutchenson Hall at Virginia Polytechnic Institute and State University (Virginia Tech) in Blacksburg, Virginia, issued under IFB #306852505. The project involves replacing the low-slope roofs at Hutchenson Hall, including installation of new EPDM membrane roofing, insulation, cover board, and lightning protection systems. The drawings include detailed construction plans, demolition notes, material specifications, and installation requirements. The work must comply with the 2021 Virginia Uniform Statewide Building Code and Virginia Tech's 2023 Design and Construction Standards. According to asbestos and lead inspections performed in April 2024, no asbestos-containing materials or lead-based paint were detected in the existing roof system.

The building is classified as Type 2B construction with a Business (B) occupancy classification and is equipped with a fire alarm system but not an automatic sprinkler system. The drawings provide comprehensive details for the roof replacement including fastening schedules, material specifications, and detailed installation requirements for the new roofing system and lightning protection components. The lightning protection system must be installed by an experienced contractor and meet UL96A & NFPA-780 standards, with materials based on Heary Bros. Lightning Protection Co. specifications or approved equivalents.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BLACKSBURG, VIRGINIA

2021 EDITION

VIRGINIA UNIFORM STATEWIDE BUILDING CODE,

HUTCHENSON HALL

AND STATE UNIVERSITY

VIRGINIA POLYTECHNIC INSTITUTE

COMMONWEALTH OF VIRGINIA

FEBRUARY 2025

SITE LOCATION MAP

SHEET NO.

INDEX OF DRAWINGS

DRAWING TITLE

CONSTRUCTION DETAILS AND NOTES

ROOF REPLACEMENT

A2

AN ASBESTOS INSPECTION WAS PERFORMED ON THE LOW-SLOPE ROOFS AT HUTCHENSON

HALL AT THE VIRGINIA TECH MAIN CAMPUS WITH REPORT ISSUED ON APRIL 23, 2024 BY HDH

TECHNICAL, INC. ASBESTOS-CONTAINING MATERIALS WERE NOT IDENTIFIED. THE

CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH ALL FEDERAL, STATE, AND

UNIVERSITY REQUIREMENTS FOR REMOVAL AND DISPOSAL OF ASBESTOS-CONTAINING

MATERIALS (ACM). IF A SUSPECT ASBESTOS MATERIAL IS ENCOUNTERED IN THE COURSE OF

THE WORK THAT IS NOT DISCUSSED AS PART OF THE REPORT, THE WORK MUST BE STOPPED

IMMEDIATELY AND VIRGINIA TECH SHOULD BE CONTACTED IMMEDIATELY AT (540) 231-0708.

A LEAD PAINT SCREENING WAS PERFORMED AND REPORT ISSUED BY HDH TECHNICAL INC. ON

APRIL 23, 2024. LEAD-BASED PAINT WAS NOT DETECTED. THE CONTRACTOR SHALL BE

RESPONSIBLE FOR COMPLYING WITH THE REQUIREMENTS OF THE OSHA LEAD STANDARD, 29

CFR 1926,.62 AND SHALL EXERCISE DUE DILIGENCE TO AVOID THE CREATION OF LEAD DUST. IF

SUSPECT LEAD MATERIALS ARE ENCOUNTERED IN THE COURSE OF THE WORK THAT ARE NOT

DISCUSSED AS PART OF THE REPORT, THE WORK MUST BE STOPPED AND VIRGINIA TECH

SHOULD BE CONTACTED AT (540) 231-0708.

ASBESTOS AND LEAD NOTE:

BUILDING CODE DATA

APPLICABLE CODES:

APPLICABLE CODE GOVERNING RENOVATION WORK: 2021 VIRGINIA EXISTING BUILDING CODE

PRESCRIPTIVE COMPLIANCE METHOD:

· GENERAL: EXISTING MATERIALS WILL REMAIN IN USE AND NEW AND REPLACEMENT

MATERIALS PERMITTED BY THE APPLICABLE CODE WILL BE USED.

· REPAIRS: BUILDING AND STRUCTURES, AND PARTS THEREOF, SHALL BE REPAIRED IN

COMPLIANCE WITH SECTION 501.2 OF THE VEBC. WORK ON NON DAMAGED COMPONENTS

THAT IS NECESSARY FOR THE REQUIRED REPAIR OF DAMAGED COMPONENTS SHALL BE

CONSIDERED PART OF THE REPAIR AND SHALL NOT BE SUBJECT TO THE REQUIREMENTS

OF ALTERATIONS.

GOVERNING BUILDING CODE:

ORIGINAL CONSTRUCTION - UNKNOWN.

USE GROUP CLASSIFICATION B (BUSINESS), THE USE GROUP CLASSIFICATION DOES NOT

CHANGE FROM EXISTING CONDITIONS.

ALLOWABLE HEIGHT AND AREAS: NO INCREASE IN EXISTING FOOTPRINT.

FIRE RESISTANCE RATING FOR BUILDING ELEMENTS: NOT CHANGED

TYPE OF CONSTRUCTION : TYPE 2B

AUTOMATIC SPRINKLER SYSTEM: BUILDING IS NOT EQUIPPED THROUGHOUT WITH AN

AUTOMATIC SPRINKLER SYSTEM

FIRE ALARM AND DETECTION SYSTEMS: BUILDING IS EQUIPPED WITH A FIRE ALARM SYSTEM.

CONSTRUCTION DETAILSA3

DESIGN CRITERIA

VIRGINIA TECH 2023 DESIGN AND CONSTRUCTION STANDARDS

CONSTRUCTION PLAN AND NOTESA1

SITE

250 DRILLFIELD DR., BLACKSBURG, VA 24061

LIGHTNING PROTECTION PLANE201

DETAILSE301

ABBREVIATIONS, SPECIFICATIONS & SYMBOLSE001

DETAILSE303

DETAILSE304

DETAILSE302

IFB #306852505

F

AC

AC

CC

AC

FV

C

C

AC

AC

F

F

AC

C

C

C

AC

OF

OF

OF

C

HVAC

AC

F

OFOF

VP

VP

VP

VP

VP

VP

OF

VP

VP

C

F

OF

C

VP

C

SYMBOL

LEGEND

DEFINITION

ROOF TOP HVAC UNIT

ROOF SECTION

THROUGH-WALL SCUPPER

ROOF DRAIN

RIDGE LINE

VALLEY LINE

INSULATION SLOPE

OF

FALL RESTRAINT

TIE- BACK

VP

VENT PIPE

V VENT

C CAPPED CURB

HVAC

HS HOT STACK

HS

DUCT THROUGH ROOF

AC AIR CONDITIONING

UNIT

F CURB MOUNTED FAN

ROOF HATCH

A3

A2

A2

A2

A2

A2

A2

A3

SIM.

A P P R O V E D

D E S I G N E D

C H E C K E D

D R A W N

P R O J E C T N O.D A T E

C L

I E

N T

C A D D F I L E

PROFESSIONAL SEAL

A1

SHEET

FEBRUARY 2025

HUTCHENSONHALLROOF.DWG

BTI

DLW

R01.2018.009410

DLW

MF

VI

R

G

IN

IA

P

O

LY

TE

C

H N

IC

IN

ST

IT

U

TE

S

TA

TE

U N

IV

ER

SI

TY

BL

AC

KS

BU

R G

, V A

CO

NS

TR

UC

TI

ON

P

LA

N

AN

D

NO

TE

S

HU

TC

HE

NS

ON

H

AL

L R

OO

F R

EP

LA

CE

ME

NT

VI

R

G

IN

IA

P

O

LY

TE

C

H N

IC

IN

ST

IT

U

TE

A N

D S

TA

TE

U N

IV

ER

SI

TY

H U

TC

H

EN

SO

N H

AL

L

R O

O F

R

EP

LA

C

EM

EN

T H

U

TC

H

EN

SO

N

H

AL

L

DEMOLITION NOTES

1. THE EXISTING ROOF CONSTRUCTION INFORMATION PROVIDED IS BASED ON A 2024 STUDY

PERFORMED BY FEA. THE ACTUAL MATERIAL TYPE AND THICKNESS MAY VARY

THROUGHOUT THE ROOF SECTIONS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR

VERIFYING FIELD CONDITIONS PRIOR TO SUBMISSION OF BID.

2. EXISTING ROOF CONSTRUCTION IS SHOWN IN THE SCHEDULE ON THIS SHEET

3. REMOVE ALL EXISTING ROOF MEMBRANE AND INSULATION MATERIALS DOWN TO THE

SURFACE OF THE ROOF DECK. EXAMINE ROOF DECK SURFACE AND DETERMINE IF IT IS IN

SUITABLE CONDITION FOR ROOF INSULATION AND MEMBRANE WORK. REPAIR ROOF DECK

WHERE DETERIORATED OR DAMAGED.

4. PROTECT EXISTING EQUIPMENT SUCH AS: VENTS, MECHANICAL UNITS, AND OTHER

ROOFTOP EQUIPMENT DURING RE-ROOFING OPERATION

5. VERIFY ROOF-MOUNTED EQUIPMENT, CURBS, AND ACCESSORIES ARE PROPERLY INSTALLED

AND SECURED.

6. SEAL CONSTRUCTION JOINTS AND COLD JOINTS IN ROOF DECK WITH MATERIAL COMPATIBLE

TO ROOF MEMBRANE AND INSULATION WHERE JOINTS ARE OPEN.

7. ASBESTOS SURVEY WAS PERFORMED AT THE LOW-SLOPED ROOFS AND

ASBESTOS-CONTAINING MATERIALS WERE NOT IDENTIFIED.

CONSTRUCTION NOTES

1. PREPARE DECK SURFACE IN ACCORDANCE WITH PROJECT SPECIFICATIONS AND ROOF SYSTEM MANUFACTURER'S REQUIREMENTS PRIOR TO INSTALLATION OF NEW ROOFING MATERIALS. ALL NEW ROOFING MATERIALS SHALL BE FREE OF

ASBESTIFORM MINERALS.

2. INSTALL A FILLY-ADHERED, SINGLE-PLAY 90-MIL EPDM MEMBRANE OVER BASE INSULATION LAYER AND TAPERED INSULATION.

BASE INSULATION LAYER SHALL BE POLYISOCYANURATE. POLISOCYANURATE INSULATION SHALL BE TAPERED AS SHOWN ON DRAWINGS. BEGIN INSTALLATION OF TAPERED INSULATION AT DRAIN LINES. CRICKETS AND SADDLES SHALL BE CONSTRUCTED

WITH POLYISOCYANURATE INSULATION TAPERED AT 1/2- INCH PER FOOT.

3. PROHIBIT TRAFFIC OVER COMPLETED ROOF SECTIONS. PROHIBIT STORAGE OF EQUIPMENT AND MATERIALS ON AND MINIMIZE TRAFFIC OVER COMPLETED ROOF SECTIONS. PROTECTION OF EXISTING AND NEW ROOF SURFACES THROUGHOUT THE

CONTRACT SHALL BE THE CONTRACTOR'S RESPONSIBILITY.

4. PROVIDE WALKWAY PADS AT HATCHES, AROUND SERVICEABLE ROOFTOP UNITS, AND BETWEEN HATCHES AND SERVICEABLE

UNITS.

5. CREATE SUMPS IN INSULATION AT ALL DRAIN LOCATIONS.

6. AFTER THE INSTALLATION OF THE EPDM MEMBRANE, THE ENGINEER, OWNER, MANUFACTURER REPRESENTATIVE AND CONTRACTOR SHALL OBSERVE THE ROOF SURFACE AND PERFORM A WATER TEST IN AN ATTEMPT TO IDENTIFY ANY AREAS THAT POND WATER. ANY AREAS THAT POND WATER SHALL BE ADDRESSED BY THE INSTALLATION OF ADDITIONAL INSULATION, OR OTHER METHODS RECOMMENDED BY THE ENGINEER. THE FINISHED ROOF SURFACE SHALL PROVIDE POSITIVE SLOPE AND NOT

POND WATER.

7. PROVIDE ALL REQUIRED MECHANICAL, ELECTRICAL, AND PLUMBING MODIFICATIONS FOR EXISTING FANS, VENTS, AND ALL REMAINING ROOFTOP EQUIPMENT TO PROVIDE CURB HEIGHT TO ACCOMMODATE REQUIRED FLASHING HEIGHT (MINIMUM 8 INCHES ABOVE TOP OF FINISHED MEMBRANE). DISCONNECT, EXTEND, AND RECONNECT IN-KIND, ALL DUCTWORK, WIRING, CONTROLS, PLUMBING, OR OTHER RELATED ACCESSORIES PRIOR TO THE INSTALLATION OF NEW CURBS. PROVIDE TEMPORARY

TRAFFIC PROTECTION AND WATERPROOFING OVER ANY OPENINGS DURING THE WORK.

8. INSTALL THROUGH-WALL FLASHING TO RAISE BASE WALL FLASHING HEIGHTS.

9. INSTALL ONE PORTABLE FALL RESTRAINT TIE-BACK AT SECTION B.

10. INSTALL THE SPECIFIED COATING ON EXPOSED PARAPET ROOFSIDE VERTICAL AND TOP SURFACES NOT VISIBLE FROM THE GROUND.

11. RAISE THE WALL BETWEEN SECTIONS A AND B BY 6 INCHES TO PROVIDE ADDITIONAL FLASHING HEIGHT.

EXISTING ROOF CONSTRUCTION SCHEDULE

ROOF SECTION AREA PLAN (SF) INSULATION TYPE COVER BOARD MEMBRANE DECK TYPE

A 7,222 ISO GLASS-FACED

GYPSUM EPDM CONCRETE

B 2,040 ISO GLASS-FACED

GYPSUM EPDM STEEL

C 1,256 ISO GLASS-FACED

GYPSUM EPDM CONCRETE

D 1,160 ISO GLASS-FACED

GYPSUM EPDM CONCRETE

E 14 ISO GLASS-FACED

GYPSUM EPDM CONCRETE

1/128"=1'-0"

ROOF PLAN

A1

LAP SEALANT

CURB FLASHING

(TYPICAL)

PIPE PENETRATION

(TYPICAL)

A2

PIPE FIELD WRAP

(TYPICAL)

MEMBRANE SPLICE7

A2

6" MINIMUM SPLICE

WIDTH

A2

A2

BASE WALL FLASHING

(TYPICAL)

A2

NOTE: REPLACE FLEXIBLE SEALANTS AT ALL COPING JOINTS

THROUGH-WALL FLASHING REPLACEMENT 6

A2

FASTENER SCHEDULE

NOTE:

1. METAL SECTIONS SHALL BE SECURED AT EACH END ON THE INSIDE EDGE UNDER THE JOINT COVER WITH TWO LARGE STAINLESS STEEL

NAILS THROUGH SLOTTED HOLES. 6-INCH WIDE JOINT COVERS SHOULD BE HOOKED OVER THE METAL AT THE UPPER AND LOWER ENDS. A BEAD OF SEALANT SHALL BE APPLIED UNDER THE JOINT COVER 1-INCH FORM THE END OF EACH METAL ROOF EDGE SECTION. ADD ONE #10 STAINLESS STEEL SHEET METAL SCREW WITH NEOPRENE WASHER AT THE CENTER OF EACH SECTION ON THE INSIDE EDGE, AND AT THE CENTER OF EACH JOINT COVER. THE SECTIONS OF METAL ROOF EDGE SHALL BE SEPARATED BY 3/4-INCH SO THAT THE SCREW

THROUGH THE JOINT COVER CLEARS THE METAL FASCIA.

2. FASTENER FREQUENCY SHALL BE DOUBLED WITHIN 8-FEET OF CORNERS.

ELEMENT SUBSTRATE FASTENER CONNECTION TYPE NUMBER AND SPACING

HORIZONTAL WOOD NAILER CONCRETE BLOCK OR

MASONRY WALL

1/4 INCH COATED STEEL

SCREW MIN. 1-3/4 INCH

EMBEDMENT

DIRECT 4" O.C. STAGGERED (NOTE 2)

HORIZONTAL WOOD NAILER HORIZONTAL WOOD NAILER 16 D GALV. NAILS DIRECT

2 ROWS / 24" O.C. EACH ROW MIN. 1 1/4"

PENETRATION MIN. PULLOUT

RESISTANCE OF 100LB (NOTE 2)

VERTICAL WOOD NAILER HORIZONTAL WOOD NAILER 16 D GALV. NAILS TOE NAIL 24" O.C. EACH SIDE (NOTE 2)

VERTICAL WOOD NAILER VERTICAL WOOD NAILER 16 D GALV. NAILS ANGLE 24" O.C. EACH SIDE (NOTE 2)

WOOD BLOCKING CONCRETE

1/4 INCH COATED STEEL

SCREW MIN. 1-3/4 INCH

EMBEDMENT

DIRECT 2' O.C. STAGGERED (NOTE 2)

HOOK STRIP WOOD #8 WOOD SCREWS DIRECT 16" O.C. (NOTE 2)

HOOK STRIP CONCRETE

1/4 INCH COATED STEEL

SCREW MIN. 1-3/4 INCH

EMBEDMENT

DIRECT 16" O.C. (NOTE 2)

METAL EDGE / CAP PIECE

(PAINTED GALVANIZED) WOOD

OUTSIDE - CONT. HOOK STRIP

INSIDE - #10 (PAINTED)

GALVANIZED SCREWS

W/NEOPRENE WASHERS

DIRECT SEE HOOK STRIP 12" O.C. (NOTE 2)

METAL FLASHING /

EQUIPMENT SUPPORT WOOD

#10 (PAINTED) GALVANIZED

SCREWS W/NEOPRENE

WASHERS

DIRECT

12" O.C. AT EQUIP. SUPPORT FLASHING

(NOTE 2)

METAL COUNTERFLASHING

(GALVANIZED) CONCRETE 3/16 INCH STAINLESS STEEL

NAIL-IN EXPANSION FASTENER DIRECT 18" O.C. (NOTE 2)

SCUPPER INSERT CONCRETE

3/16 INCH COATED STEEL

FASTERNER WITH NEOPRENE

WASHER

DIRECT 12" O.C.

1. ALL FASTENERS REQUIRED SHALL BE PROVIDED AND PLACED IN ACCORDANCE

WITH THESE DETAILS, THE FASTENER SCHEDULE, MANUFACTURER'S

REQUIREMENTS, THE PROJECT SPECIFICATIONS, AND FACTORY MUTUAL

SYSTEMS BULLETIN 1-49.

2. ALL NAILERS, BLOCKING AND CANTS SHALL BE NEW PRESSURE TREATED WOOD.

PROVIDE PROPER SIZE AND QUANTITY OF WOOD NAILERS TO INCREASE EDGE

HEIGHTS AS REQUIRED.

3. EXISTING DRAIN ASSEMBLIES SHALL BE CLEANED, RE-WELDED AS REQUIRED,

AND RE-INSTALLED.

4. ALL EDGE METAL IS TO BE FABRICATED IN SECTIONS NOT TO EXCEED 10-FEET IN

LENGTH.

THE FOLLOWING IS A SUMMARY OF THE METAL FLASHING REQUIREMENT.

5. THE TOP EDGE OF ALL BASE FLASHING SHALL BE POSITIVELY FASTENED WITH

3/16-INCH STAINLESS STEEL NAIL-IN EXPANSION FASTENER IN PREDRILLED

HOLES (MASONRY AND CONCRERE SUBSTRATE), #10 STAINLESS STEEL METAL

SCREWS WITH 1-INCH DIAMATER STAINLESS STEEL WASHERS, (METAL

SUBSTRATE), OR ROOFING NAILS WITH MINIMUM 1-INCH DIAMETER HEADS, 8

INCHES ON CENTERS (WOOD SUBSTRATE).

6. SCHEDULE SELECTIVE SHUTDOWN OF ROOFTOP EQUIPMENT WITH THE OWNER,

DISCONNECT AND LIFT EXISTING MECHANICAL EQUIPMENT TO INSTALL NEW

FLASHING AS SHOWN. EXTEND EXISTING UTILITY LINES AND DUCTS AS

REQUIRED. RECONNECT EQUIPMENT AND REPAIR ALL DAMAGES CAUSED BY

ROOF AND FLASHING INSTALLATION.

7. ALL MATERIAL SHALL BE NEW, UNLESS DESIGNATED AS "EXISTING".

8. ALL SEAMS SHALL BE OVERLAPPED A MINIMUM OF 6 INCHES.

9. ATTACH SKIRT METAL TO EXISTING STRIP CURBS WITH GASKETED SHEET METAL

SCREWS.

10. TERMINATION BARS SHALL HAVE RECEIVER AND FLEXIBLE SEALANT AT TOP

EDGE.

11. THE INSULATION IS SHOWN AS SINGLE AND MULTIPLE LAYERS IN THE DETAILS.

INSTALL INSULATION AS REQUIRED PER THE SPECIFICATIONS AND TO PROVIDE

TAPER TO DRAIN.

12. ALL EXPOSED EDGES OF SHEET METAL SHALL HAVE A HEMMED EDGE

13. AT SECTION B, ADD MECHANICALLY-ATTACHED ROOF BOARD AND VAPOR

RETARDER PRIOR TO INSTALLING BASE INSULATION LAYER.

14. ALL DETAILS SHALL BE MODIFIED AND SUPPLEMENTED AS APPROPRIATE TO

PROVIDE MANUFACTURER 30-YEAR WARRANTY

DETAIL NOTES

CONDITION METAL TYPE

METAL EDGE / CAP FASHING 24 GAUGE PAINTED GALVANIZED

STEEL

PITCH POCKETS, BONNETS,

ACCESSORIES 24 GAUGE STAINLESS STEEL

TERMINATION BARS

3/16" THICK STAINLESS STEEL

W/PREDRILLED HOLES, MINIMUM 1.5

INCH WIDE

SCUPPER INSERT 16 OZ. COPPER

SKIRT METAL 24 GAUGE STAINLESS STEEL

BE

LO

W B

LO

C

KI

N

G 1"

IN

C

H M

IN

(TYPICAL)

A2

WALL WITH METAL CAP FLASHING

NOTE: RAISE THE WALL BETWEEN SECTIONS A AND B BY 6 INCHES TO PROVIDE

ADDITIONAL FLASHING HEIGHT.

EXTEND MEMBRANE TO FULL WALL HEIGHT

AND SECURE WITH FASTENER AS SHOWN

EXISTING WALL

SHEET METAL PARAPET CAP. REFER TO DETAIL NOTE 4

FASTENERS APPROX. 12" ON CENTER

CONTINUOUS TAPERED WOOD SHIM

HIGH-DOMED, CAPPED, GASKETED FASTENERS

PRESSURE TREATED WOOD NAILER

FLASHING MEMBRANE (ADHERED TO WALL WITH

ADHESIVE)

FULLY ADHERED EPDM

MEMBRANE

COVER BOARD

POLYISOCYANURATE

INSULATION

VAPOR RETARDER

EXISTING STEEL DECK

BLOCKING

PROVIDE SUFFICIENT

BLOCKING FOR MINIMUM

8" FLASHING HEIGHT

(IF REQUIRED)

GASKETED FASTENERS

ANCHOR STRIP

FULLY ADHERED EPDM FLASHING

COVER BOARD

POLYISOCYANURATE

INSULATION

EXISTING ROOF DECK

CURB BLOCKING

FULLY ADHERED EPDM MEMBRANE

EXISTING SHEET METAL FLASHING

EXISTING COPING

REMOVE AND REPLACE ALL COPING

FLEXIBLE SEALANTS (ADDITIVE BID #1)

NAIL IN EXPANSION FASTENER

TERMINATION BAR WITH SEALANT

SURFACE MOUNTED COUNTERFLASHING FASTEN

IN ACCORDANCE WITH FASTENER SCHEDULE

FLASHING MEMBRANE

FASTENERS, SEAM PLATES, AND

PERIMETER SECUREMENT STRIP

COVER BOARD

POLYISOCYANURATE

INSULATION

EXISTING ROOF DECK

FULLY ADHERED EPDM

MEMBRANE

EXISTING VENT STACK

SEALANT

DRAWBAND

INSTALL SEALANT BETWEEN

PIPE AND PREFABRICATED

MEMBRANE FLASHING

MANUFACTURER'S PREFABRICATED

MEMBRANE FLASHING

SEALANT

FULLY ADHERED EPDM MEMBRANE

POLYISOCYANURATE INSULATION

COVER BOARD

EXISTING ROOF DECK

FULLY ADHERED EPDM

MEMBRANE

COVER BOARD

POLYISOCYANURATE

INSULATION

EXISTING ROOF DECK

EXISTING PIPE

PENETRATION

SEALANT

DRAWBAND

FLASHING MEMBRANE

SEALANT

HOKIE STONE

ATTACH THROUGH-WALL FLASHING TO WALL IN ACCORDANCE

WITH MANUFACTURER'S INSTRUCTIONS

THROUGH-WALL FLASHING WITH DRIP EDGE

TERMINATION BAR WITH FLEXIBLE SEALANT

FULLY ADHERED EPDM FLASHING

ANCHOR STRIP

LAP SEALANT

COVER BOARD INSULATION

POLYISOCYANURATE

INSULATION

EXISTING ROOF DECK

FULLY ADHERED EPDM MEMBRANE

REINFORCING STEEL ATTACHED

TO DECK WITH EPOXY ADHESIVE

COVER BOARD

POLYISOCYANURATE INSULATION

FULLY ADHERED EPDM MEMBRANE

PRIMER AND

ADHESIVE TAPE

EXISTING ROOF DECK A P P R O V E D

D E S I G N E D

C H E C K E D

D R A W N

P R O J E C T N O.D A T E

C L

I E

N T

C A D D F I L E

PROFESSIONAL SEAL

A2

SHEET

FEBRUARY 2025

HUTCHENSONHALLROOF.DWG

BIT

DLW

R01.2018.009410

DLW

MF

VI

R

G

IN

IA

P

O

LY

TE

C

H N

IC

IN

ST

IT

U

TE

S

TA

TE

U N

IV

ER

SI

TY

BL

AC

KS

BU

R G

, V A

CO

NS

TR

UC

TI

ON

D

ET

AI

LS

A

ND

N

OT

ES

HU

TC

HE

NS

ON

H

AL

L R

OO

F R

EP

LA

CE

ME

NT

VI

R

G

IN

IA

P

O

LY

TE

C

H N

IC

IN

ST

IT

U

TE

A N

D S

TA

TE

U N

IV

ER

SI

TY

H U

TC

H

EN

SO

N H

AL

L

R O

O F

R

EP

LA

C

EM

EN

T H

U

TC

H

EN

SO

N

H

AL

L

HOT STACK FLASHING DETAIL

(TYPICAL)

A3

STAINLESS STEEL

CLAMP

MEMBRANE TARGET

POLYISOCYANURATE INSULATION

COVER BOARD

FULLY ADHERED EPDM MEMBRANE

ANCHOR STRIP, FASTEN IN

ACCORDANCE WITH

MANUFACTURER REQUIREMENTS

WALL PANEL

SYSTEM

EXISTING WALL

GASKETED SELF-TAPPING

SHEET METAL SCREWS

WALL / PANEL DETAIL

HAT CHANNELS AT 2-FEET ON-CENTER

MAXIMUM ENSURE FASTENERS DO NOT

PENETRATE EPDM

STAINLESS STEEL

A3

NOTE:

1. INSTALL SPECIFIED SILICONE COATING TO EXISTING WALL SURFACE PRIOR TO

INSTALLING METAL WALL PANELS.

2. REMOVE AND RE-INSTALL COPING TO INSTALL SHEET METAL FLASHING AT HEAD

OF METAL WALL PANELS

3. THIS DETAIL APPLIES TO ALL RISING WALLS AT SECTION D.

4. HAT CHANNEL FASTENERS SHALL NOT PENETRATE THE WALL COATING OR

EPDM FLASHING.

REMOVE AND RESET

COPING

ROOF HATCH FLASHING

(TYPICAL)

A3

HIGH TEMPERATURE

INSULATION

PLATES & FASTENER 12" O.C.

- 4 PER LOCATION

EXISTING ROOF DECK

TERMINATION BAR WITH SEALANT

HIGH TEMPERATURE

PIPE STACK

RAIN HOOD

HIGH TEMPERATURE SEALANT

22 GA. GALVANIZED PAN

WOOD NAILERS SECURED TO DECK

POLYISOCYANURATE INSULATION

COVER BOARD

FULLY ADHERED EPDM MEMBRANE

EXISTING ROOF DECK

EXISTING ROOF HATCH

BACKER ROD

EPDM FLASHING ADHERED TO HATCH

PERIMETER TERMINATION FASTEN IN ACCORDANCE

WITH MANUFACTURER REQUIREMENTS

EXISTING ROOF DECK

POLYISOCYANURATE INSULATION

COVER BOARD

EPDM MEMBRANE

A P P R O V E D

D E S I G N E D

C H E C K E D

D R A W N

P R O J E C T N O.D A T E

C L

I E

N T

C A D D F I L E

PROFESSIONAL SEAL

A3

SHEET

FEBRUARY 2025

HUTCHENSONHALLROOF.DWG

BIT

DLW

R01.2018.009410

DLW

MF

VI

R

G

IN

IA

P

O

LY

TE

C

H N

IC

IN

ST

IT

U

TE

S

TA

TE

U N

IV

ER

SI

TY

BL

AC

KS

BU

R G

, V A

CO

NS

TR

UC

TI

ON

D

ET

AI

LS

HU

TC

HE

NS

ON

H

AL

L R

OO

F R

EP

LA

CE

ME

NT

VI

R

G

IN

IA

P

O

LY

TE

C

H N

IC

IN

ST

IT

U

TE

A N

D S

TA

TE

U N

IV

ER

SI

TY

H U

TC

H

EN

SO

N H

AL

L

R O

O F

R

EP

LA

C

EM

EN

T H

U

TC

H

EN

SO

N

H

AL

L

PART 1 GENERAL

1.1 SUMMARY

A. FURNISH ALL LABOR, COMPONENTS AND ITEMS OF SERVICE REQUIRED FOR THE COMPLETION OF A FUNCTIONAL AND UNOBTRUSIVE LIGHTNING

PROTECTION SYSTEM.

B. IF ANY DEPARTURES FROM THE CONTRACT DRAWINGS ARE DEEMED NECESSARY BY THE CONTRACTOR, SUBMIT DETAILS OF SUCH DEPARTURES AND REASONS AS SOON AS POSSIBLE TO THE ENGINEER FOR APPROVAL. NO SUCH DEPARTURES SHALL BE MADE WITHOUT THE PRIOR WRITTEN APPROVAL

OF THE ENGINEER .

1.2 QUALITY ASSURANCE

A. A NATIONAL TESTING LABORATORY (UNDERWRITERS LABORATORIES) SHALL LIST THE COMPONENTS AND PROVIDE CERTIFICATION OF THE LIGHTNING PROTECTION SYSTEM INSTALLATION (INSPECT AND CERTIFY) FOR COMPLIANCE WITH APPLICABLE STANDARDS.

B. THE SYSTEM SHALL BE THE STANDARD PRODUCT OF A MANUFACTURER REGULARLY ENGAGED IN THE PRODUCTION OF LIGHTNING PROTECTION SYSTEMS

AND SHALL BE THE MANUFACTURER'S LATEST APPROVED DESIGN.

1.3 SUBMITTALS

A. SUBMIT COMPLETE SHOP DRAWINGS, SHOWING THE TYPE, SIZE, CABLE ROUTINGS, GROUND RODS AND LOCATIONS OF ALL EQUIPMENT, TO THE

ENGINEER FOR APPROVAL, PRIOR TO START OF WORK.

B. SUBMIT SAMPLES AND PERTINENT CATALOG DATA TO THE ENGINEER FOR APPROVAL UPON REQUEST.

PART 2 PRODUCTS

2.1 STANDARD

A. ALL EQUIPMENT SHALL BE NEW, THE PRODUCT OF A SINGLE MANUFACTURER AS OUTLINED ABOVE, AND OF A DESIGN AND CONSTRUCTION TO SUIT THE

APPLICATION WHERE IT IS USED IN ACCORDANCE WITH ACCEPTED INDUSTRY STANDARDS.

a. UL96

b. UL96A

c. NFPA-780

2.2 EQUIPMENT

A. ALL COMPONENTS SHALL BE ALUMINUM AND OF THE SIZE, WEIGHT AND CONSTRUCTION TO SUIT THE APPLICATION WHERE USED IN ACCORDANCE WITH

REQUIREMENTS FOR CLASS I STRUCTURES.

B. ROOF CONDUCTORS SHALL BE ALUMINUM, 24 STRANDS 14-GAUGE, 98,600 CIRCULAR MILS, NET WEIGHT 110 LBS. / 1000 FT.

C. DOWN CONDUCTORS SHALL BE COPPER, 17 STRANDS 14-GAUGE, 62,000 CIRCULAR MILS, NET WEIGHT 200 LBS./1000FT.

D. AIR TERMINALS SHALL BE SOLID ROUND ALUMINUM BAR 1/2” X 12” MINIMUM, AND SHALL PROJECT 10" MINIMUM ABOVE THE OBJECT TO BE PROTECTED.

E. AIR TERMINALS AT MID-ROOF LOCATIONS SHALL BE SOLID ROUND ALUMINUM BAR ½” X 48” MINIMUM AND SHALL BE PROPERLY SUPPORTED WITH A TRIPOD

BRACE.

F. AIR TERMINAL BASES SHALL BE ALUMINUM WITH BOLT PRESSURE CABLE CONNECTORS AND SHALL BE SECURELY MOUNTED WITH STAINLESS STEEL

SCREWS OR BOLTS.

1. ADHESIVE TYPE BASES SHALL BE SECURED WITH AN ADHESIVE COMPOUND WHICH IS COMPATIBLE WITH THE ROOFING SYSTEM. THE

ROOFING MANUFACTURER SHALL APPROVE THE ADHESIVE COMPOUND.

2. OFFSET TYPE BASES SHALL BE USED AT PARAPET AND SECURED WITH STAINLESS STEEL SCREWS OR ANCHORS.

G. DOWN CONDUCTORS SHALL BE RUN EXPOSED ON THE BUILDING EXTERIOR IN INCONSPICUOUS LOCATIONS.

H. PROTECT EXPOSED DOWN CONDUCTORS FROM MECHANICAL INJURY BY USE OF PVC GROUND GUARDS.

I. GROUND RODS SHALL BE 5/8" X 10'-0" MINIMUM. THEY SHALL BE CONNECTED TO THE SYSTEM WITH A TWO-BOLT COPPER CLAMP HAVING A MINIMUM

LENGTH OF 1-1/2" AND EMPLOYING STAINLESS STEEL CAP SCREWS.

J. CABLE FASTENERS SHALL BE SUBSTANTIAL IN CONSTRUCTION, GALVANICALLY COMPATIBLE WITH THE CONDUCTOR AND MOUNTING SURFACE.

K. BONDING DEVICES, CABLE SPLICERS AND CONNECTORS SHALL BE OF ALUMINUM WITH BOLT PRESSURE CABLE CONNECTORS.

L. EQUIPMENT ON STACKS SHALL BE PROTECTED FROM CORROSION AND SIZED IN ACCORDANCE WITH REQUIREMENTS.

M. BOLTS, NUTS AND SCREWS SHALL BE STAINLESS STEEL.

PART 3 EXECUTION

3.1 INSTALLATION

A. THE INSTALLATION SHALL BE ACCOMPLISHED BY AN EXPERIENCED INSTALLER. THE INSTALLER SHALL WORK UNDER THE DIRECT SUPERVISION OF A MANUFACTURER AS LISTED ABOVE OR A QUALIFIED DISTRIBUTOR OF SUCH MANUFACTURER'S PRODUCTS.

B. ALL EQUIPMENT SHALL BE INSTALLED IN A NEAT WORKMANLIKE MANNER IN THE MOST INCONSPICUOUS MANNER POSSIBLE.

C. PROVIDE COMPLETE CABLE NETWORK ON THE ROOF INCLUDING; AIR TERMINALS, SPLICES, BONDING ONNECTORS AND CABLE DOWNLEADS TO GROUND

RODS.

D. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL NECESSARY PVC CONDUIT.

E. A BIMETAL TRANSITION FITTING SHALL BE USED WHERE ALUMINUM CONDUCTOR AND COPPER CONDUCTOR ARE SPLICED TOGETHER.

F. IDENTIFY ALL UNDERGROUND UTILITIES BEFORE INSTALLING GROUND RODS TO AVOID DISRUPTIONS.

3.2 COORDINATION

A. WORK WITH OTHER TRADES TO ENSURE A CORRECT, NEAT AND UNOBTRUSIVE INSTALLATION.

B. ASSURE A SOUND BOND TO THE MAIN WATER SERVICE AND TO ASSURE INTERCONNECTION WITH OTHER BUILDING GROUND SYSTEMS, INCLUDING BOTH

TELEPHONE AND ELECTRICAL.

C. INSTALL PROPER ARRESTERS ON THE POWER AND TELEPHONE SERVICE BY EITHER THE UTILITY OR THE ELECTRICAL CONTRACTOR AS APPLICABLE.

3.3 COMPLETION

A. PROVIDE AN AS-BUILT DRAWING, UPON COMPLETION OF THE INSTALLATION.

B. PROVIDE UL MASTER LABEL CERTIFICATION.

PART 4 ACCEPTABLE MANUFACTURERS AND SUPPLIERS

A. AVAILABLE MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, MANUFACTURERS OFFERING PRODUCTS THAT MAY BE INCORPORATED

INTO THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE FOLLOWING:

A. HEARY BROS. LIGHTNING PROTECTION CO., INC.

B. AUTOMATIC LIGHTNING PROTECTION.

C. ERICO INTERNATIONAL CORPORATION.

D. THOMPSON LIGHTNING PROTECTION, INC.

SYMBOL

LEGEND

DEFINITION

ROOF TOP HVAC UNIT

ROOF SECTIONA

ROOF DRAIN

FALL RESTRAINT TIE

BACK

VP

VENT PIPE

V VENT

C CAPPED CURB

HVAC

HS HOT STACK

DUCT THROUGH ROOF

AC AIR CONDITIONING

UNIT

F CURB MOUNTED FAN

ROOF HATCH

A

12" AIR TERMINAL ADHERED

TO TOP OF CONCRETE CAP

V

24" AIR TERMINAL AT VENT

PIPE

F

12" AIR TERMINAL AT ROOF

TOP EQUIPMENT

GROUNDING ROD AB

BR

EV

IA

TI

O

N S, S

PE

C

IF

IC

AT

IO

N

S

SY

M

BO

LS

AS NOTED

E001

MOHAMED F ABDELMEGUID

Lic. No. 0402 037500

C O

M M

O

N

AEW

LTH OF

VIRG

NI

IA

R E

E

NIGNELAOISSEF

OR

N

P

02/03/2025

A

A

D

B

C C

V

C

C

F

F

C

C

C

C

C

F VP

VP

VP

VP

VP

VP

VP

VP

C

C

VP

C

HS

E

A A

A

A

A

A

A A

A

A

A A

F

DN

LIGHTNING PROTECTION CABLE

FASTENED TO ROOF (TYP.)

EXPOSED DOWN CONDUCTOR TUCKED IN CORNER (TYP. OF 2)

LIGHTNING PROTECTION GROUND ROD (TYP.)

(ACTUAL LOCATIONS MAY VARY DUE TO SITE CONDITIONS)

V

V

A

A

AA

A

A

A

AA

A A A

A

A

A

A

A

A

A

A A

A A

A

AIR TERMINALS SHALL BE LOCATED

WITHIN 24" OF OUTSIDE CORNERS (TYP.)

A

A A

AAAA

AAAA

A

DN DN

DNDN

DN

DN

F

3:12 MAX. RISE 3:12 MAX. RISE

3:12 MAX. RISE

3:12 MAX. RISE

3:12 MAX. RISE

3:12 MAX. RISE

3:12 MAX. RISE

3:12 MAX. RISE

3:12 MAX. RISE

3:12 MAX. RISE

BOND TO HATCH

(ACTUAL LOCATIONS MAY VARY DUE TO SITE CONDITIONS)

F

V

BOND TO VENT PIPE (TYP.)

12" AIR TERMINAL AT MECHANICAL EQUIPMENT (TYP.)

12" AIR TERMINAL ADHERED TO TOP OF CAP (TYP.)

24" AIR TERMINAL AT VENT PIPE (TYP.)

A

A

A

12" AIR TERMINAL AT ROOF TOP EQUIPMENT (TYP.)

A

A

A

A

A

A

A

24" AIR TERMINAL AT STACK (TYP.)

LIGHTNING PROTECTION CABLE ADHERED TO TOP OF CAP

EVERY 36" MAX. (TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

GENERAL DRAWING NOTES:

1. THE DESIGN IS BASED ON HEARY BROS. LIGHTNING PROTECTION CO.,

INC. ANY APPROVED EQUIVALENT THAT MEETS THE SAME STANDARDS

WILL ALSO BE ACCEPTED.

2. THE LIGHTNING PROTECTION SYSTEM AS SHOWN ON DRAWING HAS

BEEN DESIGNED IN ACCORDANCE WITH UL96A & NFPA-780 LIGHTNING

PROTECTION SYSTEM STANDARDS.

3. CONDUCTORS SHALL MAINTAIN A HORIZONTAL OR DOWNWARD COURSE,

FREE FROM "U" OR "V" (DOWN AND UP) POCKETS.

4. NO BEND OF CONDUCTOR SHALL FORM AN ANGLE OF LESS THAN 90°

NOR SHALL HAVE A RADIUS OF BEND LESS THAN 8".

5. AIR TERMINALS SHALL BE SPACED EVERY 20'-0" MAXIMUM AROUND THE

ROOF PERIMETER AND/OR ALONG ROOF RIDGES. AIR TERMINALS SHALL

BE LOCATED WITHIN 2'-0" OF OUTSIDE CORNERS.

6. AIR TERMINALS SHALL BE SPACED EVERY 50'-0" MAXIMUM IN CENTER

ROOF AREAS.

7. ACTUAL JOBSITE CONDITIONS MAY REQUIRE SLIGHT ALTERATIONS IN

AIR TERMINAL, DOWN CONDUCTOR AND GROUND ROD LOCATIONS.

8. BARE COPPER MATERIALS SHALL NOT BE INSTALLED ON ALUMINUM OR

GALVALUM SURFACES, AND ALUMINUM MATERIALS SHALL NOT BE

INSTALLED ON COPPER SURFACES.

9. ALL LIGHTNING PROTECTION CONDUCTORS SHALL BE FASTENED EVERY

3'-0" MAX.

10. ALL BOLTS ON BOLT-PRESSURE CONNECTORS SHALL BE TORQUED AT

150 IN-LB.

11. ALL CONNECTIONS MUST BE USED WITH UL LISTED CABLE OF SAME

METAL TYPE.

12. SMALL METALLIC BODIES OF INDUCTANCE SITUATED WITHIN 6'-0" OF A

LIGHTNING CONDUCTOR OR ANOTHER BONDED METAL BODY SHALL BE

INTERCONNECTED TO THE LIGHTNING CONDUCTOR SYSTEM, UNLESS

INHERENTLY GROUNDED. (ROOF DRAINS, SMALL PLUMBING VENTS,

FLASHINGS, COUNTERFLASHINGS, ETC).

13. BOND ALL LARGE METAL BODIES TO THE MAIN LIGHTNING PROTECTION

CONDUCTOR. (I.E.; EXHAUST FANS, ROOF VENTS/FLUES, METAL

COOLING TOWERS, HVAC UNITS, LADDERS, RAILINGS, ANTENNAS,

SKYLIGHTS, METAL STACKS AND ANY OTHER LARGE METAL BODY

WHOSE HEIGHT EXCEEDS THAT OF THE AIR TERMINAL IN USE, UNLESS

PROTECTED BY HIGHER ROOF ELEVATIONS).

14. IDENTIFY ALL UNDERGROUND UTILITIES BEFORE INSTALLING GROUND

RODS TO AVOID DISRUPTIONS. CONNECTIONS TO GROUND RODS SHALL

BE MADE AT A POINT NOT LESS THAN 1'-0" BELOW FINISHED GRADE AND

2'-0" AWAY FROM FOUNDATION WALL.

15. BOND TO WATERLINES (DOMESTIC & FIRE).

16. A LIGHTNING ARRESTOR, PROTECTOR OR ANTENNA DISCHARGE UNIT

SHALL BE INSTALLED ON EACH ELECTRIC AND TELEPHONE SERVICE

AND RADIO AND TELEVISION ANTENNA LEAD-IN BY THE ELECTRICAL

CONTRACTOR, IN ACCORDANCE WITH NFPA-70.

17. TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) OF SERVICES SHALL

BE PROVIDED BY THE ELECTRICAL CONTRACTOR. (I.E. COMPUTERS,

COPIERS, TELEPHONE, ETC.).

18. PROVIDE UL MASTER LABEL CERTIFICATION UPON COMPLETION OF

INSTALLATION.

19. SEE DETAILS ON SHEETS E301 - E304 FOR TYPICAL CONNECTION

DETAILS.

KEYED DRAWING NOTES:

DOWN CONDUCTOR TO GROUND ROD. DOWN CONDUCTORS SHALL NOT

EXCEED 100' (TYP.). CONFIRM DOWN CONDUCTOR LOCATIONS WITH THE

UNIVERSITY PROJECT MANAGER BEFORE INSTALLATION.

LIGHTNING PROTECTION GROUND ROD (TYP.).

12" AIR TERMINAL AND ADHESIVE BASE (TYP.).

LIGHTNING PROTECTION CABLE FASTENED TO ROOF EVERY 36" MAX

(TYP.).

LI

G

H

TN

IN

G

P R

O

TE

C

TI

O N

P

LA

N

AS NOTED

E201

LIGHTNING PROTECTION PLAN1

E201 1/8"=1'-0"

MOHAMED F ABDELMEGUID

Lic. No. 0402 037500

C O

M M

O

N

AEW

LTH OF

VIRG

NI

IA

R E

E

NIGNELAOISSEF

OR

N

MECHANICAL UNIT

SYMBOL

1/2" x 12" ALUMINUM AIR TERMINAL

#AAHB-302 (LOCATED WITHIN 24"

OF OUTSIDE CORNERS)

FASTEN CABLE EVERY 3'-0" MAX.

WITH ADHESIVE CABLE FASTENERS

#AFHB-72

ALUMINUM CONDUCTOR

#ACHB-24-14

ALUMINUM ADHESIVE BASE

#ABHB-23D ADHERED TO

TOP OF UNIT

BOND PLATE #APHB-54D

NOTE: SEAL ALL PENETRATIONS

WITH SILICONE SEALANT.

CONNECT TO NEAREST

LIGHTNING CONDUCTOR

WITH CABLE CONNECTOR

#ANHB-44D

ALUMINUM CONDUCTOR

#ACHB-24-14

#ABHB-23D

ALUMINUM BASE

ALUMINUM CONDUCTOR

#ACHB-24-14

SYMBOL

ADHESIVE TYPE AIR TERMINAL

#AFHB-72

ALUMINUM ADHESIVE

CABLE FASTENER

EVERY 3'-0" MAX.

20FT. MAX. (TYP.)

ADHESIVE CABLE FASTENER

THE ADHESIVE COMPOUND SHALL BE

COMPATIBLE WITH THE MOUNTING

SURFACE.

NOTE:

AIR TERMINAL #AAHB-304

ALUMINUM BASE

1/2" x 24" ALUMINUM

ALUMINUM

ALUMINUM CLIP / FASTENER (TYP.)

BONDING PLATE #APHB-54D

#AFHB-64/BOLT

SYMBOL

ALUMINUM CONDUCTOR

#ACHB-24-14

#ABHB-22

ALUMINUM CONDUCTOR #ACHB-24-14

CONNECT TO NEAREST LIGHTNING

PROTECTION ROOF CONDUCTOR

EXTEND 10" MIN. ABOVE TOP OF FLUE

TIP OF AIR TERMINAL SHALL

FASTENED EVERY 36" MAX.

ALUMINUM CONDUCTOR

#ACHB-24-14

NOTE: BARE COPPER MATERIALS SHALL NOT BE INSTALLED ON ALUMINUM OR GALVALUM

SURFACES, AND ALUMINUM MATERIALS SHALL NOT BE INSTALLED ON COPPER SURFACES.

OPTIONAL:

STAINLESS STEEL BANDING.

TO BE DETERMINED IN FIELD

D

ET

AI

LS

AS NOTED

E301

ADHESIVE TYPE AIR TERMINAL1

E301 NOT TO SCALE

AIR TERMINAL AT STACKS/FLUES2

E301 NOT TO SCALE

LIGHTNING PROTECTION AT ROOF TOP UNIT3

E301 NOT TO SCALE

MOHAMED F ABDELMEGUID

Lic. No. 0402 037500

C O

M M

O

N

AEW

LTH OF

VIRG

NI

IA

R E

E

NIGNELAOISSEF

OR

N

#AAHB-302

AIR TERMINAL

(ADHERED TO TOP

AIR TERMINAL BASE

1/2" x 12" ALUMINUM

OF FAN) #ABHB-23D

ALUMINUM BONDING

BIMETAL CONNECTION

ALUMINUM CONDUCTOR

PLATE #APHB-54D

#MNHB-93

#ACHB-24-14

ALUMINUM CONDUCTOR

#ACHB-24-14

CONNECT TO NEAREST

LIGHTNING PROTECTION

CABLE

NOTE: AIR TERMINALS ARE REQUIRED ON ROOF VENTILATORS/EXH. FANS

THAT ARE NOT WITHIN A ZONE OF PROTECTION OR WHEN HIGHER

THAN ADJACENT AIR TERMINALS.

SYMBOL

#CGHB-57D

CONNECTOR

ALUMINUMBOND

GROUND ROD

5/8"x10'-0"

COPPER LIGHTNING PROTECTION

TO NEAREST DOWN CONDUCTOR

8'-0" PVC GROUND GUARD #CGHB-108PVC

CONDUCTOR #CCHB-17-14

24"MIN.

SYMBOL

GROUND ROD

#CGHB-106GR

STRUCTURE EXTERIOR

COPPER CONDUCTOR #CCHB-17-14

FASTENED EVERY 3'-0" MAX.

TO EXTERIOR WALL

BOND TO WATERLINE (FIRE & DOMESTIC)

12" (MIN.) BELOW FINISHED GRADE

DN

IDENTIFY ALL UNDERGROUND UTILITIES

BEFORE INSTALLING GROUND RODS TO

AVOID DISRUPTIONS

D

ET

AI

LS

AS NOTED

E302

AIR TERMINAL AT EXHAUST FAN1

E302 NOT TO SCALE

EXPOSED LIGHTNING PROTECTION DOWN CONDUCTOR AND GROUNDING2

E302 NOT TO SCALE

MOHAMED F ABDELMEGUID

Lic. No. 0402 037500

C O

M M

O

N

AEW

LTH OF

VIRG

NI

IA

R E

E

NIGNELAOISSEF

OR

N

SECONDARY BONDING

CONDUCTOR #ACHB-#4

BONDING STRAP AND

STAINLESS

STEEL SCREW

CABLE CONNECTOR #ANHB-160D

BOND TO ROOF DRAINS AND SMALL VENTS WHEN LOCATED WITHIN 6'-0"

OF LIGHTNING CONDUCTOR OR OTHER GROUNDED METAL BODIES.

TO BE DETERMINED AT JOB SITE.

BONDING STRAP AT (METAL VENT PIPES)

1" BONDING STRAP

AND CABLE CONNECTOR

#ANHB-42XD

SECONDARY BONDING

CONDUCTOR #ACHB-#4

ROOF FLASHING

FLASHING CONNECTOR

FLASHING CONNECTOR

#ANHB-44D

SECONDARY BONDING CONDUCTOR

#ACHB-#4 (CONNECT TO NEAREST

DOWN CONDUCTOR)

NOTE:

PROVIDE BONDING

CONNECTION TO

METAL FLASHING

AT EACH DOWNLEAD

LOCATION.

#PPHB-54D

COPPER BONDING PLATE

CONDUCTOR #ACHB-24-14 OR #CCHB-17-14

CORROSION RESISTANT

EXCEPT ALUMINUM

#APHB-54D SIMILAR

ALUMINUM CONDUCTOR

CROSSOVER CABLE

#ACHB-24-14

CONNECTOR

#AMHB-57XXX

1" WIDE

#PMHB-103D

COPPER BONDING STRAP

CORROSION RESISTANT

ALUMINUM CONDUCTOR

#ACHB-24-14

2" WIDE ALUMINUM STRAP

COPPER CONDUCTOR

(CONNECT TO NEAREST

DOWN CONDUCTOR)

#CCHB-17-14

#CMHB-97D

NTS

STRAIGHT SPLICER

#ARHB-26

STRAIGHT SPLICER

CABLE CONNECTOR

ALUMINUM LIGHTNING

ALUMINUM CABLE CONNECTOR

ALUMINUM LIGHTNING

PROTECTION CONDUCTOR

#ANHB-44D

PROTECTION CONDUCTOR

EXCEPT COPPER

#CNHB-44D SIMILAR

D

ET

AI

LS

AS NOTED

E303

BONDING LUG (METAL ROOF DRAINS)1

E303 NOT TO SCALE

BONDING STRAP AT (METAL VENT PIPES)2

E303 NOT TO SCALE

FLASHING CONNECTOR3

E303 NOT TO SCALE

BONDING PLATE4

E303 NOT TO SCALE

PIPE CLAMP (RAILINGS, ANTENNAS, ETC.)5

E303 NOT TO SCALE

CROSSOVER CABLE CONNECTOR6

E303 NOT TO SCALE

CABLE CONNECTOR7

E303 NOT TO SCALE

WATERLINE BONDING STRAP8

E303 NOT TO SCALE

STRAIGHT SPLICER9

E303 NOT TO SCALE MOHAMED F ABDELMEGUID

Lic. No. 0402 037500

C O

M M

O

N

AEW

LTH OF

VIRG

NI

IA

R E

E

NIGNELAOISSEF

OR

N

LOCATE AIR TERMINAL WITHIN

24" OF OUTSIDE CORNERS

ROOF

24" MAX.

TIP OF AIR TERMINALS

SHALL EXTEND 10" MIN.

ABOVE TOP OF PARAPET

MID-ROOF CABLE

3:12 MAX.

SLOPE

8" MIN. RADIUS BEND

AAHB-302, ABHB-23D1/2" x 12" ALUMINUM AIR TERMINAL AND ADHESIVE BASE

ACHB-#4

#CCHB-17-14

#ACHB-24-14

AFHB-72, 66, 64

CFHB-64

ANHB-44D

PPHB-54D

APHB-54D

ANHB-42XD

PMHB-103D

MNHB-93

ANHB-44D, CNHB-44

ARHB-26

AMHB-57XXX

CMHB-97D

BONDING PLATE (TO BASE OF STEEL AT EACH DOWNLEAD)

CROSSOVER CABLE CONNECTOR

PIPE CLAMP (ANTENNAS, RAILINGS, ETC.)

BONDING PLATE (AT ALUM. RTU & FANS)

*METAL VENT PIPE CONNECTOR

CABLE CONNECTOR

STRAIGHT SPLICER

*SECONDARY BONDING (USE SECONDARY BONDING CABLE #ACHB-#4):

*FLASHING CONNECTOR

LIGHTNING PROTECTION MATERIALS LIST

ALUMINUM LIGHTNING PROTECTION MAIN CONDUCTOR

ALUMINUM LIGHTNING PROTECTION SECONDARY CABLE*

COPPER LIGHTNING PROTECTION DOWN CONDUCTOR

ALUMINUM CABLE FASTENERS (TO FASTEN ALUMINUM CABLE)

BIMETAL CONNECTOR

WATERLINE CONNECTOR (FIRE WATER & DOMESTIC WATER)

CGHB-106GR, 57D5/8" x 10'-0" MIN. ALUMINUMBOND GROUND RODS AND CONNECTOR

AAHB-302, ABHB-23D1/2" x 12" ALUMINUM AIR TERMINAL AND ADHESIVE BASE

ADHERED TO EQUIPMENT (AT ROOF TOP EQUIPMENT/FANS)

COPPER CABLE FASTENERS (TO FASTEN COPPER CABLE)

ANHB-160D*METAL ROOF DRAIN / GUTTER CONNECTOR

AAHB-304, ABHB-221/2" x 24" ALUMINUM AIR TERMINAL AND VERTICAL BASE (AT FLUES)

CGHB-108PVCPVC GROUND GUARDDN

NOTE :

THE DESIGN AND THE PART NUMBER LISTED ABOVE ARE BASED ON HEARY BROS. LIGHTNING PROTECTION CO., INC. ANY APPROVED

EQUIVALENT MEETING THE SAME STANDARDS WILL ALSO BE ACCEPTED.

OF BEND LESS THAN 8".

ANGLE OF LESS THAN 90° OR HAVE A RADIUS

-NO BEND OF A CONDUCTOR SHALL FORM AN INCLUDED

WARD PATH AVOIDING "U" & "V" POCKETS (DOWN & UP).

-LP CONDUCTOR SHALL REMAIN IN A HORIZONTAL OR DOWN-

R=RADIUS OF BEND, 8" (203mm) MINIMUM

R

NOTE:

90 MINIMUM

8" MIN. RADIUS BEND IN CABLE

D

ET

AI

LS

AS NOTED

E304

8" MIN. RADIUS BEND IN CABLE1

E304 NOT TO SCALE

AIR TERMINALS SHALL BE LOCATED WITHIN 24" OF OUTSIDE CORNERS2

E304 NOT TO SCALE

MOHAMED F ABDELMEGUID

Lic. No. 0402 037500

C O

M M

O

N

AEW

LTH OF

VIRG

NI

IA

R E

E

NIGNELAOISSEF

OR

N

Hutcheson Hall Design Feb 2025.pdf
Sheets and Views
Hutcheson Hall Design Feb 2025-COVER
Hutcheson Hall Design Feb 2025-A1 - CONSTRUCTION PLAN AND NOTES
Hutcheson Hall Design Feb 2025-A2 - CONSTRUCTION DETAILS AND NOTES
Hutcheson Hall Design Feb 2025-A3 - CONSTRUCTION DETAILS
HUTCHESON HALL LIGHTNING PROTECTION.pdf
Sheets and Views
ELEC PLAN - HUTCHESON - 2024119-E001
ELEC PLAN - HUTCHESON - 2024119-E201
ELEC PLAN - HUTCHESON - 2024119-E301
ELEC PLAN - HUTCHESON - 2024119-E302
ELEC PLAN - HUTCHESON - 2024119-E303
ELEC PLAN - HUTCHESON - 2024119-E304

File details come from the government source that posted it. Updated .