Amendment_02.pdf
PDF 824 KB Posted
- Attached to
- P Domenici Chiller Replacement
- Solicitation number
- GS-07-P-15-UF-C-7002
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amendment_01.pdf | ||
| PBS_Past_Performance_Questionnaire.docx | DOCX document | |
| Waste_Diversion_Form.docx | DOCX document | |
| GS-07-P-15-UF-C-7002_Solicitation_Package.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
E UUT ab \ d b c P R Z ] ^ f [T S V T aT R T X_ c ^ U cW Xb P \ T ] S \ T ] c _ aX̂ a c^ cW T W ^ d a P ] S S P cT b _ T R XUXT S X] cW T b ^ [XR XcP cX̂ ] ^ a P b P \ T ] S T S & Q h ^ ] T ^ U cW T U^ [[̂ f X] V \ T cW ^ S b 4
$P % 7 h R ^ \ _ [T cX] V XcT \ b 2 P ] S + / & P ] S aT cd a] X] V
^ a $R % 7 h b T _ P aP cT [T ccT a ^ a cT [T V aP \ f W XR W X] R [d S T b P aT UT aT ] R T c^ cW T b ^ [XR XcP cX̂ ] P ] S P \ T ] S \ T ] c ] d \ Q T ab ( < 6 ?B K H ; E < O E K H 6 8 A D E M B ; 9 = C ; D J J E 7 ; H ; 8 ; ?L ; 9 6 J J > ;
F B 6 8 ; 9 ; I ?= D 6 J ; 9 < E H J > ; H ; 8 ; ?F J E < E < < ; H I F H ?E H J E J > ; > E K H 6 D 9 9 6 J ; I F ; 8 ?< ?; 9 C 6 O H ; I K B J ?D H ; @ ; 8 J ?E D E < O E K H E < < ; H ( ?U Q h e Xacd T ^ U cW Xb
P \ T ] S \ T ] c h ^ d a S T b XaT c^ R W P ] V T P ] ^ UUT a P [aT P S h b d Q \ XccT S & b d R W R W P ] V T \ P h Q T \ P S T Q h cT [T V aP \ ^ a [T ccT a& _ a^ e XS T S T P R W cT [T V aP \ ^ a [T ccT a \ P Z T b aT UT aT ] R T c^ cW T b ^ [XR XcP cX̂ ]
P ] S cW Xb P \ T ] S \ T ] c& P ] S Xb aT R T Xe T S _ a X̂ a c^ cW T ^ _ T ] X] V W ^ d a P ] S S P cT b _ T R XUXT S (
,! /2 5468( 38' 8 ^ ] caP R c^ a Xb ] ^ c& Xb aT ` d XaT S c^ b XV ] cW Xb S ^ R d \ T ] c P ] S aT cd a] R ^ _ XT b c^ cW T Xb b d X] V ^ UUXR T (
( 2 ,3+ 2 ,38 4- 741/* /8( 8/43"2 4+ /-/* ( 8/43 4- * 4386( * 8 + ( 8 E D J H 6 8 J ?9 8 E 9 ;
, ( 6 C ; D 9 C ; D J )C E 9 ?< ?8 6 J ?E D D E ( - ( ; < < ; 8 J ?L ; 9 6 J ; . ( H ; G K ?I ?J ?E D )F K H 8 > 6 I ; H ; G ( D E ( / ( F H E @ ; 8 J D E ( !,; 5 DD@>7 5 6 @9 "
1 ( 6 9 C ?D ?I J ; H ; 9 7 O !,; CH= 9 FH= 5 B,H9 A ( " 8 E 9 ;
78( 3+ ( 6+ -462 %# $H ; L ( + * '2 - %
F aT b R aXQ T S Q h = I 6 < 6 H $. 2 8 < H % / - (, . -
< 6 8 ?B ?J O 8 E 9 ;
3 6 ( 6 C ; D 9 C ; D J E < I E B ?8 ?J 6 J ?E D D E (
3 7 ( 9 6 J ; 9 !1 * * ,2 * - & & "
+ * 6 ( C E 9 ?< ?8 6 J ?E D E < 8 E D J H 6 8 J )E H 9 ; H D E (
+ * 7 ( 9 6 J ; 9 !1 * * ,2 * - & ' "
$$! 8./7 /8,2 4319 ( 551/,7 84 ( 2 ,3+ 2 ,387 4- 741/* /8( 8/437
J W T P Q ^ e T ] d \ Q T aT S b ^ [XR XcP cX̂ ] Xb P \ T ] S T S P b b T c U^ acW X] ?cT \ + . ( J W T W ^ d a P ] S S P cT b _ T R XUXT S U^ a aT R T X_ c ^ U E UUT ab Xb T g cT ] S T S & Xb ] ^ c T g cT ] S T S (
+ , ( 6 8 8 E K D J ?D = 6 D 9 6 F F H E F H ?6 J ?E D 9 6 J 6 !,; F9 EI >F9 8 "
R ^ _ XT b ^ U cW T P \ T ] S \ T ] c5 $Q % 7 h P R Z ] ^ f [T S V X] V aT R T X_ c ^ U cW Xb P \ T ] S \ T ] c ^ ] T P R W R ^ _ h ^ U cW T ^ UUT a b d Q \ XccT S 5
$%! 8./7 /8,2 4319 ( 551/,7 84 2 4+ /-/* ( 8/43 4- * 4386( * 87"46+ ,67!
/8 2 4+ /-/,7 8., * 4386( * 8"46+ ,6 34! ( 7 + ,7* 6/),+ /3 /8,2 $& !
8 > ; 8 A E D ; 6 ( J > ?I 8 > 6 D = ; E H 9 ; H ?I ?I I K ; 9 F K H I K 6 D J J E 4 !1 D9 7 >;K 5 I H= CF>HK " J > ; 8 > 6 D = ; I I ; J < E H J > ?D ?J ; C + . 6 H ; C 6 9 ; ?D J > ; 8 E D J H 6 8 J E H 9 ; H D E ( ?D ?J ; C + * 6 (
7 ( J > ; 6 7 E L ; D K C 7 ; H ; 9 8 E D J H 6 8 J )E H 9 ; H ?I C E 9 ?< ?; 9 J E H ; < B ; 8 J J > ; 6 9 C ?D ?I J H 6 J ?L ; 8 > 6 D = ; I !G I 7 = 5 G 7 = 5 B< 9 G >BD5 K >B< C;;>7 9 # 5 DDFCDF>5 H>CB
8 5 H9 # 9 H7 $% I ; J < E H J > ?D ?J ; C + . & F K H I K 6 D J J E J > ; 6 K J > E H ?J O E < < 6 H . - (+ * - $Q %(
8 ( J > ?I I K F F B ; C ; D J 6 B 6 = H ; ; C ; D J ?I ; D J ; H ; 9 ?D J E F K H I K 6 D J J E 6 K J > E H ?J O E < 4
9 ( E J > ; H !1 D9 7 >;K HK D9 C; A C8 >;>7 5 H>CB5 B8 5 I H= CF>HK "
; g R T _ c P b _ a^ e XS T S W T aT X] & P [[ cT a\ b P ] S R ^ ] S XcX̂ ] b ^ U cW T S ^ R d \ T ] c aT UT aT ] R T S X] ?cT \ 3 6 ^ a + * 6 & P b W T aT c^ U^ aT R W P ] V T S & aT \ P X] b d ] R W P ] V T S P ] S X] Ud [[ U^ aR T P ] S T UUT R c(
+ / 8 ( 9 6 J ; I ?= D ; 9
+ / 6 ( D 6 C ; 6 D 9 J ?J B ; E < I ?= D ; H !2 K D9 CFDF>BH"
+ 0 8 ( 9 6 J ; I ?= D ; 9
+ 0 6 ( D 6 C ; 6 D 9 J ?J B ; E < 8 E D J H 6 8 J ?D = E < < ?8 ; H !2 K D9 CFDF>BH"
+ . ( 9 ; I 8 H ?F J ?E D E < 6 C ; D 9 C ; D J )C E 9 ?< ?8 6 J ?E D $/ F< 5 B>L9 8 6 K 3 ) + G 9 7 H>CB= 9 5 8 >B< G # >B7 @I 8 >B< G C@>7 >H5 H>CB%7 CBHF5 7 H G I 6 ?9 7 H A 5 HH9 FJ = 9 F9 ;9 5 G >6 @9 $"
F 6 = ; E < F 6 = ; I
0 ( ?I I K ; 9 7 O 8 E 9 ;
2 ( D 6 C ; 6 D 9 6 9 9 H ; I I E < 8 E D J H 6 8 J E H !. C$# G HF9 9 H# 7 CI BHK # 1 H5 H9 5 B8 4 ,0 ) C8 9 " $N %
8 E 9 ;
+ / 7 ( 8 E D J H 6 8 J E H )E < < ; H E H
!1 >< B5 HI F9 C; D9 FG CB5 I H= CF>L9 8 HC G >< B"
+ 0 7 ( K D ?J ; 9 I J 6 J ; I E < 6 C ; H ?8 6
!1 >< B5 HI F9 C; ) CBHF5 7 H>B< / ;;>7 9 F"
D I D 1 / . * '* + '+ / , '2 * 1 * F aT e X̂ d b T S XcX̂ ] d ] d b P Q [T
7PQ
See attached.
GSA PBS 7PQ
ACQUISITION MANAGEMENT DIVISION
819 TAYLOR ST RM 12B01
FORT WORTH, TX 76102
See Block 6
GS-07-P-15-UF-C-7002
08/25/2015
07/31/2015
8 8
1 9
Amendment No. 2– Solicitation No. GS-07-P-15-UF-C-7002 for Chiller Replacement at the Pete V. Domenici Courthouse in Albuquerque, NM
This amendment is issued to provide the Pre-Proposal Sign-in Sheet/Agenda, solicitation changes and to respond to questions.
1. Attached is the Pre-Proposal Sign-in Sheet/Agenda.
2. Notes from Site Visit:
a) Under Item 001 of the schedule "work shall be performed during normal working hours" please add "however, due to high traffic during normal hours and to avoid interfering with the courts or the USMS, removal of the existing chiller and placing the new mag/lev chiller on the chiller #4 housekeeping pad shall be done after hours during a weekend.
b) Under Sec B. Alteration paragraph xxiii -although the site visit confirmed an existing refrigerant monitor that may be capable of monitoring both R22 and R134A, this unit will be replaced as per the SOW.
c) Under Sec B. Alteration the incorrect reference to the "Lanham BAS" needs to be corrected to "Pete Domenici BAS."
d) Under Sec C. Specifications and Requirements, paragraph 2 "Automatic Isolation valves"; the site walk confirmed that these valves already exist. Replacing these valves is solely at the discretion of the contractor.
3. Will the contractor be responsible for re-painting the epoxy floors at project completion if the floor gets damaged (there is a high likelihood they will)?
A: Yes, floors to remain as they were before project start.
4. Can we obtain a copy of the current sequence of operations? If the plan is to run this chiller simultaneously with the screw chillers currently in place, the York screw chillers will lose efficiency based on the condenser water temperatures required for the Mag-Lev chiller.
A: See attached PDF for existing SOO. CHILLER STAGING The number of Chillers required is determined by looking at the chill water return temperature (CWRT). The lead chiller is always enabled if outside air temperature is greater than 50 Deg F. Each chiller will be enabled and disabled by the chart below if the lockout period has been met. When ever the mag lev chiller is in operation as the lead and or lag chiller and the load increases to 70% of its full load KW for 15 consecutive mins (field adjustable from the BAS chiller graphics page for KW & Mins) a lag chiller shall be started in addition to the mag lev chiller.
CONDENSING WATER TEMPATURE CONTROL If the chillers are enabled then the bypass valve will be used to control the supply temperature to the chillers to a set point of 73 Deg F, such that if the temperature is greater than 73 deg F then the bypass valve will be full open, and the cooling towers will maintain the supply to 77 Deg F. If the heat exchanger is in operation then the condensing water temperature will be controlled to reset so that at an outside air temperature of 30 Deg F the condensing water temperature set point will be 60 Deg F, and an outside air temperature of 60 Deg F the condensing water temperature set point will be 45 Deg F. The bypass valve will be fully opened.
5. The scope calls for repainting the curbs with epoxy paint, even though the curbs are not currently expoxied. Is this correct?
A: Correct.
Amendment No. 2– Solicitation No. GS-07-P-15-UF-C-7002 for Chiller Replacement at the Pete V. Domenici Courthouse in Albuquerque, NM
6. Do you have a contact for your current fire alarm service provider?
A: Intraworks is the EST Certified company the Operations and Maintenance contractor is currently using. Their phone is 505-884-1970, toll free 800-287-5641.
7. Can we get a copy of the required CSI Master Format 2010 Form (cost breakdown)?
A: There is not a form. You are to prepare your price proposal in accordance with the CSI Master Format 2010.
8. Can we get a copy of the existing Auto-Cad format drawings of the mechanical space?
A: GSA currently does not have CAD drawings for this space.
9. Is this project exclusive to GSA Contract Holders (GS-21F-0013V) operating as small businesses?
A: No. This solicitation was issued on fbo.gov and is available to all small businesses.
10. Will owner adjust chemical treatment in the chilled water and cooling tower water loops due to draining existing chiller and filling new chiller?
A: Yes, that is the plan.
11. Page 3 of 80- ‘The contractor shall be required to complete the entire work ready for use no later than 30 calendar days after Notice to Proceed is issued.
Period of Performance- Page 7 of 80 (bottom) and 8 of 80- ‘All work shall be completed within 30 calendar days after Chiller delivery.
Liquidated Damages- ‘If substantial completion is not achieved, ….
Can this be verified/defined? i.e. Substantial completion- Chiller is operational, capable of providing cooling, prior to the 30 days from delivery.
All other work to be complete 30 days from chiller delivery, excluding final customer walk through and sign off.?
A: Substantial completion shall be achieved when the chiller is running and operating under control of the building automation system as per the sequence of operations in the SOW. Only then can it be said that the new chiller is "fully" providing design intent and benefitting the government by operating in the most energy efficient manner.
12. Is a bid bond required?
A: Please see section 1.F of the solicitation (p. 60 of the solicitation package) that discusses bid guarantees.
Pre-Bid Walk for Pete Domenici Chiller #4 Replacement
Pre-Bid Agenda
8/18/2015 1:00 PM
1) Introductions-All GSA
2) Opening Remarks-Shawn Villarreal
3) RFP response on 8/31/2015_2:00 pm central time
4) Security Requirements-Badges and OPM NACI –Frank Campagna
5) Hours of Operation and Access-Stuart Blakley
6) End date for RFI 8/21/2015-Sent to shawn.villarreal@gsa.gov cc: frank.campagna@gsa.gov
7) Cooling System items of note-Dan Lewis and David Blea
8) Q&A
9) Site walk mailto:shawn.villarreal@gsa.gov mailto:frank.campagna@gsa.gov
PRE-PROPOSAL CONFERENCE AGENDA
SOLICITATION NUMBER: GS-07-P-15-UF-C-7002
Chiller Replacement at the Pete V. Domenici Courthouse
1:00 PM, MOUNTAIN STANDARD TIME - TUESDAY – AUGUST 18, 2015
1. GREETING AND INTRODUCTIONS
A. No oral statements made shall change the solicitation – any changes will be documented in a written amendment posted to FBO.gov.
B. Sign-in sheet: All attendees must sign in on the sign-in sheet.
C. Minutes will be issued in an amendment to the solicitation.
D. Submit all questions to the Contracting Officer, Shawna Villarreal, so that we may capture all questions accurately.
2. GSA CONTRACTING COMMENTS
A. Overview of Technical Evaluation Factors
1) Experience on similar projects
2) Past performance of offeror
B. Basis for Award - Award will be made on the basis of the lowest evaluated price of proposals meeting the acceptability standards for non-price factors
C. Questions/Request for Information must be sent to Shawna Villarreal, Contracting Officer, AT shawna.villarreal@gsa.gov. Submit no later than 10 days prior to the proposal due date (August 21, 2015).
D. Proposal due date: August 31, 2015 (Extensions are not currently anticipated) E. Proposal Submission Requirements
1) Volume 1 – Technical Proposal
2) Volume 2 – Price Proposal
3. TIPS FOR PREPARING A PROPOSAL
A. Read the solicitation and amendments.
B. Does your proposal contain all the items the solicitation is asking for? Make sure your proposal fully addresses the submittal requirements for each evaluation factor.
C. Never assume we know about your company and your performance. We can only evaluate what you provide.
mailto:shawna.villarreal@gsa.gov
Pete Domenici Chiller Replacement Pre-Bid Walk
August 18, 2015
Name Org Phone Email
3. DlCUVCL^-^-'^^ ^Y^v^-^\^VS> ^ S ^ ^ / t > ^ - 7 3 Ai^^rs^0>fm^{/^ddty^nm^^
-Com
7- Cho^iA
.A
10. ^ fh>Ver-^ 4 /\^
12. D n̂̂ Y Rv^l^ /̂ -̂S
15. ^o^en, ft^-^^z.
Via Telephone
^- '8-lf
SCHEDULE Continued
ITEM NO SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT
0001 The contractor shall provide all the necessary materials, supplies, labor, equipment and supervision necessary to complete the demolition and replacement of the 155 ton chiller #4 at the Pete Domenici Courthouse
Building in Albuquerque, New Mexico. All work shall be done in accordance with the Scope of Work dated 04/30/15.
The following item is hereby incorporated by reference:
Scope of Work, Dated 04/30/15
Exhibit A
Wage Determination NM150040, Dated 07/10/2015
The Agreement (C101-SB / APR 2015)
The Solicitation (C201-SB LPTA/ APR 2015)
Offerors Representations and Certifications (C301 /APR 2015)
Contractor shall provide payment bond, performance bond and insurance documents within 10 calendar days after contract award. Notice to Proceed will not be issued until all bonding and insurance are accepted.
The contractor shall be required to complete the entire work ready for use no later than 30 calendar days after Notice to Proceed is issued. Work shall be performed during normal working hours (7:00 am – 6:00 pm), Monday through Friday, excluding Federal holidays or as directed by GSA. However, due to high traffic during normal hours and to avoid interfering with the courts or the USMS, removal of the existing chiller and placing the new mag/lev chiller on the chiller #4 housekeeping pad shall be done after hours during a weekend. If the contractor fails to complete the work within the time specified in the contract, the contractor shall pay liquidated damages to the Government in the amount of $296.00 for each calendar day of delay until the work is completed or accepted.
All contract employees working on premises at GSA owned and operated buildings are required to pass a security background check conducted by the Office of Personnel Management (OPM). The contractor shall provide the Contractor Information Worksheet (CIW) for each employee to GSA
R7Suitability at r7suitability@gsa.gov within 15 calendar days after contract award. The employee will receive detail instructions and access to the online application from accesscard@gsa.gov within a couple of days after they submit the CIW.
A Pre Proposal Conference is scheduled for Tuesday, August 18, 2015 at
1:00 PM MST at the Pete Domenici Courthouse Building in Albuquerque, New
Mexico. Contractor needS to verify all existing conditions at the job site prior to bidding on project. Failure to do so will not relieve contractor of his/her responsibility to properly estimate the cost of this project. This is the only opportunity contractors will get to visit the site to conduct a walk-through and ask questions. GSA will not have anyone available to accompany contractor or their representative (sub-contractors) after the scheduled pre proposal conference.
Proposal is due by 2:00 pm CST on Monday, August 31, 2015. If you have any questions, please contact Shawna Villarreal, Contracting Officer at