GCS_City_Hall_Generator_Replacement_-_Electrical_Drawings_240826.pdf
PDF 1 MB Posted
- Attached to
- City Hall Generator Upgrade State and local contract opportunity
- Solicitation number
- 2024-08
- Issued by
- Clay County, Harold CDP, Florida
About this file
The document is a set of electrical drawings for the City of Green Cove Springs City Hall Backup Generator Replacement Project, located at 321 Walnut Street in Green Cove Springs, Florida. The project involves replacing the existing 125 KW generator with a new 250 KW generator and upgrading the building's electrical infrastructure to enable the entire city hall to operate on auxiliary power. The drawings, prepared by Evanlily Engineering and dated August 2024, include detailed electrical site plans, one-line diagrams, electrical legends, and installation details for the generator replacement and electrical system modifications.
The project scope includes removing the existing generator and transfer switch, installing a new diesel generator set, upgrading electrical panels and distribution systems, and ensuring comprehensive power coverage for the city hall facility. The electrical drawings specify technical requirements for conduit installations, grounding systems, and electrical equipment configurations. The one-line diagrams indicate the proposed electrical layout, showing how the new generator will interface with the existing electrical infrastructure, including main distribution panels, transfer switches, and various electrical loads throughout the building.
View the file
Other files for this state and local contract opportunity
| File | Type | Posted |
|---|---|---|
| green_cove_mec250_quote_11-21-2024_Estimate10556032.pdf | ||
| Form_W-9_(PDF).pdf | ||
| 4486-101-R-Executed_Contract_8-17-2023.pdf | ||
| GCS_City_Hall_Generator_Replacement_-_Electrical_Specifications_240826.pdf | ||
| RFP_2024-8,_City_Hall_Generator_Upgrade.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESCRIPTION OF WORK:
INDEX OF DRAWINGS
SHEET TITLE
CITY OF GREEN COVE SPRINGS
CITY HALL BACKUP
N
SCALE: NTS
PROJECT LOCATION MAP
ISSUED FOR CONSTRUCTION
AUGUST 2024
ISSUED FOR CONSTRUCTION
SHEET
321 WALNUT STREET, GREEN COVE SPRINGS, FL 32043
GENERATOR PROJECT
CO
VE
R S
HE
ET
E
-1
A S
S H
O W
N D
R A
W
IN
G N
O
S H
E E
T N
O
N O
. S H
E E
T S
S C
A
LE
D A
T E
P R
O J.
N O
F
LO
R
ID
A R
E G
IS
T
R A
T
IO
N N
O
D E
S
IG
N E
N G
IN
E
E R
C H
E C
K E
D B
Y
D A
T E
D R
A W
N B
Y
D E
S
IG
N E
R
0.
R E
V
IS
IO
N
S D
A T
E B
Y N
O
D A
T E
A U
G U
S T
CIT
Y O
F G
RE
EN
CO
VE
SP
RIN
GS
CIT
Y H
AL
L
BA
CK
UP
GE
NE
RA
TO
R R
EP
LA
CE
ME
NT
PR
OJ
EC
T
W
AL
NU
T S
TR
EE
T, G
RE
EN
CO
VE
SP
RIN
GS
, FL
F E
W A
U G
IS
S U
E D
F O
R C
O N
S T
R U
C T
IO
N
EV
AN
LI
LY
E
NG
IN
EE
RI
NG
M c La ur in
R d
E Ja ck so nv ill e, F
L
Ph
4)
-7
FL
C er tif ic at e of A ut ho riz at io n
F E
W
A U
G U
S T
F E
W
F E
W
A U
G U
S T
F R
A N
K E
. W E
LL
S
, P E
These drawings and associated engineering work are the property of Evanlily Engineering and shall not be reproduced without written consent. Drawings should not be used or repurposed in any manner other than as originally developed and by which Evanlily Engineering was commissioned. Evanlily Engineering takes no responsibility by any party except as originally intended and commissioned by.
No 73859
STATE OF
ALNOISSEF
O
R P
ENGIN
E
E R
RO IL D
F A
CLI ENSE
WELLSFR
ANK E.
THIS DOCUMENT HAS BEEN DIGITALLY
SIGNED AND SEALED BY:
PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED.
THE SIGNATURE MUST BE VERIFIED ON
THE ELECTRONIC DOCUMENTS.
LOW VOLTAGE MOLDED CASE CIRCUIT BREAKER.
("LSIG" ELECTRONIC TRIP, "MCP" MOTOR CIRCUIT
PROTECTOR, "GFI" GROUND FAULT INTERUPTING,
"BLANK" THERMAL MAGNETIC)
(AMP RATING AND NUMBER OF POLES AS INDICATED)
FUSE
(FUSE RATING AND CLASSIFICATION AS INDICATED)
TWO WINDING TRANSFORMER
(VOLTAGE, RATING, IMPEDANCE, CONNECTION
CONFIGURATION AS INDICATED)
(ANSI STANDARD IMPEDANCE IF NOT SPECIFIED)
ELECTRICAL LEGEND
UTILITY METER
UTILITY CONNECTION
(VOLTAGE AND PHASES AS
INDICATED)
SWITCH
(AMP RATING AND NUMBER OF POLES AS
INDICATED)
GENERAL NOTES
ABBREVIATIONS
A OR AMP AMPERES
AF AMP FRAME
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AT AMP TRIP
ATC AUTOMATIC TRANSFER CONTROLLER
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
C CONDUIT
/C CONDUCTOR
CB CIRCUIT BREAKER
CT CURRENT TRANSFORMER
CBL CABLE
DS DISCONNECT SWITCH
ESTOP EMERGENCY STOP
EX EXISTING
EP EXPLOSION PROOF
EF EXHAUST FAN
EG EQUIPMENT GROUND
EGC EQUIPMENT GROUND CONDUCTOR
EWH ELECTRIC WATER HEATER
F FUSE
G OR GND GROUND
GEC GROUNDING ELECTRODE CONDUCTOR
GEN GENERATOR
GF GROUND FAULT
GFI GROUND FAULT INTERRUPT
M
ELECTRICAL LEGEND
ABOVE GRADE CONDUIT RUN
MINIMUM SIZE 3/4-INCH
BELOW GRADE CONDUIT RUN
MINIMUM SIZE 1-INCH
HOMERUN CIRCUIT WITH TERMINATION
LOCATION AS DESIGNATED
OVERHEAD ELECTRICAL
FLEXIBLE CONDUIT
MINIMUM SIZE 3/4-INCH
"HH" HAND HOLE, "MH" MANHOLE
"PB" PULL BOX, "JB" JUNCTION BOX
HH
CABLE/CONDUIT TAG
("P" POWER, "C" CONTROL, "I"
INSTRUMENTATION/COMMUNICATIONS)
("ATS" EQUIPMENT REFERENCE)
("1" SEQUENCE NUMBER)
1. THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRIC SAFETY CODE, NECA
STANDARD OF INSTALLATION (EDITIONS ADOPTED BY THE AHJ), AND ANSI/NEMA
STANDARDS SHALL ESTABLISH THE MINIMUM REQUIREMENTS FOR INSTALLATION,
BUT IN ADDITION, ALL WORK SHALL ALSO COMPLY WITH OSHA, STATE, COUNTY,
LOCAL OR MUNICIPAL CODE REQUIREMENTS AND THE RULES OF THE LOCAL
ELECTRIC UTILITY. IN CASE OF CONFLICTS, CONFORM TO THE MORE STRINGENT
REQUIREMENTS.
2. TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THESE PLANS AND
SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AS
DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTER 553 AND
633 OF THE FLORIDA STATUTES. IN CASES OF CONFLICTS BETWEEN THESE
DESIGN DOCUMENTS AND REQUIREMENTS OF ANY OF THE ABOVE CRITERIA,
CONTACT THE ENGINEER BEFORE PROCEEDING.
3. THE CONTRACT DRAWINGS ARE DIAGRAMMATIC IN NATURE AND INTEND TO
CONVEY ELECTRICAL SCOPE OF WORK ONLY. NOT EVERY ELECTRICAL DETAIL,
WIRE, OR CONDUIT IS SHOWN. CONTRACTOR SHALL VERIFY ALL EXISTING
CONDITIONS AND DIMENSIONS PRIOR TO PROCUREMENT AND CONSTRUCTION
ACTIVITIES.
4. DEVIATIONS FROM THE INTENT OF THE CONTRACT DRAWINGS AND
SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER
AND/OR OWNER PRIOR TO PROCEEDING WITH CONSTRUCTION.
5. TO "PROVIDE" MEANS TO PROVIDE ALL LABOR, MATERIALS, EQUIPMENT,
TRANSPORTATION, AND SUPERVISION REQUIRED TO FURNISH AND INSTALL A
COMPLETE AND OPERATIONAL ELECTRICAL SYSTEM.
6. CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL NECESSARY COMPONENTS,
EQUIPMENT, AND INCIDENTALS REQUIRED FOR A FULLY FUNCTIONAL AND
OPERATIONAL ELECTRICAL SYSTEM AS DESCRIBED BY THE INTENT OF THE
CONTRACT DRAWINGS AND SPECIFICATIONS. CONTRACTOR SHALL APPLY FOR,
OBTAIN, AND PAY FOR ALL REQUIRED PERMITS AND INSPECTION CERTIFICATES,
AND PAY FOR ALL FEES ASSOCIATED WITH THE PROJECT.
7. EQUIPMENT AND MATERIALS PROVIDED SHALL BEAR LISTING AND LABELING BY A
NATIONALLY RECOGNIZED TESTING AGENCY WHERE SUCH STANDARD HAD BEEN
ESTABLISHED FOR THAT TYPE OF EQUIPMENT/MATERIAL.
8. PROVIDE EQUIPMENT NAMEPLATES FOR ALL EQUIPMENT. NAMEPLATES SHALL BE
ENGRAVED THREE-LAYER LAMINATED PLASTIC, BLACK LETTERS ON WHITE
BACKGROUND. USE 1/8 INCH LETTERS FOR IDENTIFYING INDIVIDUAL EQUIPMENT
AND LOADS AND 1/4 INCH LETTERS FOR GROUPED EQUIPMENT AND LOADS.
PROVIDE ARC FLASH AND SHOCK HAZARD WARNING LABELS FOR ELECTRICAL
EQUIPMENT PER NEC 110.16 AND OTHER ELECTRICAL LABELS AS REQUIRED BY
OSHA AND NEC.
9. CONTRACTOR SHALL PROVIDE A GUARANTEE OF ALL LABOR AND MATERIALS FOR
A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE FROM OWNER. ALL
WORK FOUND TO BE DEFECTIVE WITHIN THIS PERIOD SHALL BE REPAIRED OR
REPLACED AT NO COST TO THE OWNER.
10. CONTRACTOR SHALL PROVIDE AN AS-BUILT RECORD SET OF DRAWINGS TO THE
OWNER UPON PROJECT COMPLETION SHOWING ALL DEVIATIONS FROM ORIGINAL
DESIGN.
11. SIZE OF DISCONNECTS, FUSES, CIRCUIT BREAKERS, WIRING AND CONDUIT FOR
HVAC AND OTHER MECHANICAL EQUIPMENT IS BASED ON THE MECHANICAL BASIS
OF DESIGN. IF THE ELECTRICAL DATA VARIES FROM MECHANICAL SCHEDULES,
RESIZE THE RELATED ELECTRICAL COMPONENTS PER THE NEC AND
MANUFACTURER'S RECOMMENDATIONS AND SUBMIT FOR APPROVAL.
12. CONTRACTOR SHALL INSPECT, TEST, AND DOCUMENT RESULTS FOR ALL
EXISTING ELECTRICAL EQUIPMENT SUCH AS SWITCHBOARDS, PANELBOARDS,
BREAKERS, FUSES, DISCONNECT SWITCHES, CIRCUIT CONDUCTORS, CURRENT
TRANSFORMERS, BUS BARS, CONNECTIONS, AND TERMINATIONS TO ENSURE
EQUIPMENT IS OPERATING WITHIN ORIGINAL MANUFACTURER'S ACCEPTED
TOLERANCES AND DOES NOT POSE A HAZARD FOR CONTINUED OPERATION.
EQUIPMENT AND MATERIALS FAILING TO MEET MANUFACTURERS ACCEPTED
TOLERANCES SHALL BE REPAIRED OR REPLACED. TESTING SHALL BE
COMPLETED IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS,
NETA MTS, AND NFPA 70E CURRENT EDITIONS. ENGINEER TAKES NO
RESPONSIBILITY FOR FUTURE OPERATION OF EQUIPMENT NOR ANY
SUBSEQUENT DAMAGE OR HARM TO PERSONS OR PROPERTY AS A RESULT OF
CONTINUED OPERATION OF EXISTING ELECTRICAL EQUIPMENT WHICH DOES NOT
MEET ORIGINAL MANUFACTURERS SPECIFICATIONS.
H-O-A HAND-OFF-AUTO
HP HORSEPOWER
JB JUNCTION BOX
kVA KILOVOLT - AMPS kW KILOWATTS kWH KILOWATT-HOUR
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MLO MAIN LUGS ONLY
N NEUTRAL
NC NORMALLY CLOSED
NO NORMALLY OPEN
NTS NOT TO SCALE
OHE OVERHEAD ELECTRICAL
PH, Ø PHASE
PLC PROGRAMMABLE LOGIC CONTROLLER
PM POWER MONITOR
REC RECEPTACLE
SS STAINLESS STEEL
SPD SURGE PROTECTION DEVICE
SWBD SWITCHBOARD
TYP TYPICAL
UG UNDERGROUND
UL UNDERWRITER'S LABORATORIES
V VOLTS
VA VOLT AMPS
VAC VOLTS ALTERNATING CURRENT
VDC VOLTS DIRECT CURRENT
VFD VARIABLE FREQUENCY DRIVE
W WATT
WH WEATHERHEAD
WP WEATHER PROOF
XFMR TRANSFORMER
M
PADMOUNT TRANSFORMER
(ADDRESS AND SIZE AS SHOWN)
METER CENTER LOCATION
(ADDRESS AND SIZE AS SHOWN)
MANUAL PULL STATION WALL
MOUNTED AT 46 INCHES
FIRE DETECTION DEVICE CEILING MOUNTED
(TYPE AS INDICATED ON PLANS)
SPEAKER / HORN / STROBE LIGHT COMBINATION
WALL MOUNTED AT 80 INCHES
FIRE ALARM CONTROL PANEL
SPEAKER / HORN UNIT WALL MOUNTED AT 80 INCHES
FACP
S
CEILING MOUNTED DOWN-LIGHT FIXTURE
(FIXTURE TYPE AND CIRCUIT AS INDICATED)
INTERIOR / EXTERIOR WALL MOUNTED FIXTURE
(FIXTURE TYPE AND CIRCUIT AS INDICATED)
TWIN HEAD FLOOD FIXTURE WITH BATTERY BACKUP
(FIXTURE TYPE AND CIRCUIT AS INDICATED)
EXIT SIGN FIXTURE, DO NOT SWITCH, PROVIDE ARROWS
AS INDICATED, SHADING DENOTES FACE OPERATION
(FIXTURE TYPE AND CIRCUIT AS INDICATED)
POLE MOUNTED LIGHT FIXTURE
(FIXTURE TYPE AND CIRCUIT AS INDICATED)
WALL SWITCH 1 WAY WALL MOUNTED AT 44 INCHES U.N.O.
LUTRON DECORA, 20A, 120V, THERMOPLASTIC COVER
("3" THREE WAY, "4" FOUR WAY, "D" DIMMER, "OS"
OCCUPANCY SENSOR, "T" TIME SWITCH)
LIGHTING CONTROL SENSOR MOUNTED AT 44 INCHES U.N.O.
OR CEILING MOUNTED (TYPE AS INDICATED)
ALL DEVICE/PLATE COLORS TO BE OWNERS CHOICE
TRACK LIGHTING FIXTURE
(FIXTURE TYPE AND CIRCUIT AS INDICATED)
A,9
A,9
A,9
A,9
S
DUPLEX RECEPTACLE, 20A, 120V, MOUNTED AT 18 INCHES
U.N.O. BOX INDICATES FLOOR MOUNT (CIRCUIT AS INDICATED)
JUNCTION BOX
QUADPLEX RECEPTACLE, 20A, 120V, MOUNTED AT
18 INCHES U.N.O. (CIRCUIT AS INDICATED)
DATA OUTLET MOUNTED AT 18 INCHES U.N.O.
BOX INDICATES FLOOR MOUNT (SEE PLANS FOR DETAILS)
DUPLEX RECEPTACLE, GFI, 20A, 120V, MOUNTED
AT 18 INCHES U.N.O. (CIRCUIT AS INDICATED)
SPECIAL PURPOSE RECEPTACLE MOUNTED AT
18 INCHES U.N.O. (SEE PLANS FOR DETAILS)
TELEPHONE OUTLET MOUNTED AT 18 INCHES U.N.O.
(SEE PLANS FOR DETAILS)
TELEPHONE / DATA COMBINATION OUTLET MOUNTED AT
18 INCHES U.N.O. (SEE PLANS FOR DETAILS)
LP1-12
LP1-12
LP1-12
J
LP1-12
GFI
CEILING MOUNTED DOWN-LIGHT FIXTURE W/ BATTERY BACKUP
(FIXTURE TYPE AND CIRCUIT AS INDICATED)
DS DISCONNECT SWITCH
(FUSED/NON-FUSED AND RATING AS INDICATED)
F
F
H
CEILING MOUNTED PENDANT FIXTURE
(FIXTURE TYPE AND CIRCUIT AS INDICATED)
A,9
SUPPLEMENTAL SPECIFICATIONS
WIRING DEVICES
1. LIGHT SWITCHES SHALL BE LUTRON DECORA SERIES, 120V, 20A WITH THERMOPLASTIC COVERS. MOUNT SWITCHES AT
44-INCHES ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE.
2. RECEPTACLES SHALL BE LEVITON TDR20 SERIES, 120V, 20A WITH THERMOPLASTIC COVERS. MOUNT RECEPTACLES FLUSH AT 18-INCHES ABOVE FINISHED FLOOR WITH GROUNDING POLE AT THE TOP UNLESS NOTED OTHERWISE. NEW RECEPTACLES
SHALL BE OF THE TAMPER PROOF DESIGN PER NFPA 70, 406.12.
3. GROUND FAULT RECEPTACLES SHALL BE LEVITON G5362, 120V, 20A, TAMPER RESISTANT WITH THERMOPLASTIC COVERS.
MOUNT RECEPTACLES FLUSH AT 18-INCHES ABOVE FINISHED FLOOR WITH GROUNDING POLE ON TOP UNLESS NOTED
OTHERWISE.
4. RECEPTACLES ABOVE COUNTERS SHALL BE MOUNTED AT 44-INCHES VERTICALLY OR HORIZONTALLY IN THE BACKSPLASH
DEPENDING ON THE LOCATION UNLESS NOTED OTHERWISE.
5. THERMOPLASTIC LEXAN DEVICE COVER PLATES SHALL BE WHITE UNLESS NOTED OTHERWISE OR COLOR AS SPECIFIED BY THE
OWNER.
6. RECEPTACLES WHICH ARE BACK-TO-BACK ON A COMMON WALL SHALL BE OFFSET 6" MINIMUM TO AVOID SOUND
TRANSMISSION.
7. CONFIRM LOCATION, MOUNTING HEIGHT, AND ELECTRICAL REQUIREMENTS FOR ALL SPECIAL PURPOSE AND DEDICATED OUTLETS, OUTLETS NEAR CABINETS, AND PHONE / DATA OUTLETS WITH ARCHITECTURAL PLANS AND OWNER
REPRESENTATIVES.
JUNCTION BOXES
1. JUNCTION AND PULL BOXES SHALL ONLY BE USED WHERE CONDUIT IS REQUIRED FOR INSTALLATION AND SHALL BE MADE OF GALVANIZED STEEL UNLESS EXPOSED TO CORROSIVE ATMOSPHERES WHERE STAINLESS STEEL SHALL BE USED.
2. DEVICE BOXES SHALL BE PLASTIC ONE PIECE NOT LESS THAN 4-INCHES SQUARE UNLESS EXPOSED TO CONCRETE WHERE
GALVANIZED SHALL BE UTILIZED WITH SIMILAR COVERS.
CONDUCTORS
1. CONCEALED CONDUCTORS LOCATED INDOORS SHALL BE TYPE NMC, NONMETALLIC SHEATHED CABLE WITH INTEGRAL
EQUIPMENT GROUNDING CONDUCTOR.
2. EXPOSED CONDUCTORS LOCATED INDOORS SHALL BE COPPER TYPE MC CABLE OR THHN/THWN IN CONDUIT. NUMBER 10 AND
BELOW SHALL BE SOLID. NUMBER 8 AND ABOVE SHALL BE STRANDED.
3. CONDUCTORS LOCATED OUTDOORS SHALL BE COPPER TYPE XHHW-2, UNLESS NOTED OTHERWISE.
4. MINIMUM SIZE FOR LIGHTING CONDUCTORS SHALL BE #12AWG, UNLESS NOTED OTHERWISE. MINIMUM SIZE FOR CONTROL AND
SIGNAL CIRCUITS SHALL BE #14AWG UNLESS NOTED OTHERWISE.
5. CONDUCTORS FOR 480Y/277V, 3 PHASE SYSTEMS SHALL BE BROWN, ORANGE, YELLOW. CONDUCTORS FOR 208Y/120V, 3 PHASE SYSTEMS SHALL BE BLACK, RED, BLUE. 120/208V SYSTEMS SHALL BE COLOR CODED RED, BLACK, WHITE FOR LINE, LINE, NEUTRAL RESPECTIVELY.
6. ALL RACEWAYS SHALL CONTAIN A GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR SIZED PER THE NEC 250.122.
7. ALL PANEL FEEDERS SHALL BE 3 OR 4-WIRE WITH GROUND AS REQUIRED BY LOAD COPPER SER CABLE WITH CONDUCTORS SIZED BASED ON MAIN BREAKER RATING, CIRCUIT LENGTH, AND MAXIMUM VOLTAGE DROP OF 3%. CONTRACTOR SHALL ROUTE CIRCUITS WITH THE SHORTEST RUN LENGTH POSSIBLE TO REDUCE UNNECESSARILY LARGE CIRCUIT CONDUCTORS.VOLTAGE
CONFIGURATION.
8. CONTRACTOR SHALL VISUALLY INSPECT AND INTEGRITY TEST ALL EXISTING BUILDING WIRING TO BE REUSED AND CONFIRM SUITABILITY FOR CONTINUED OPERATION. DEFECTIVE WIRING SHALL BE REPAIRED OR REPLACED.
DISCONNECT SWITCHES
1. SAFETY SWITCHES SHALL BE HEAVY DUTY, FUSED OR NON-FUSED AS INDICATED, QUICK-MAKE AND QUICK-BREAK, HORSEPOWER RATED, MINIMUM RATING 250 0R 600 VOLTS A.C., AS APPROPRIATE. EXTERIOR DISCONNECTS SHALL BE NEMA 3R
RATED FOR OUTDOOR ENVIRONMENTS.
2. FUSIBLE DISCONNECT SWITCHES SHALL HAVE PROVISIONS FOR CLASS R FUSES.
3. DISCONNECT SWITCHES SHALL BE SERVICE ENTRANCE RATED WHERE REQUIRED BY CODE.
LOAD CENTERS
1. LOAD CENTERS SHALL BE RATED AND CONFIGURED AS INDICATED ON THE DRAWINGS. INSTALLATION SHALL BE IN
ACCORDANCE WITH THE MANUFACTURERS REQUIREMENTS.
2. CIRCUIT BREAKERS INSTALLED IN EXISTING LOAD CENTERS SHALL BE ACCEPTABLE FOR THEIR INTENDED INSTALLATION WITH SHORT CIRCUIT RATINGS EQUAL TO OR GREATER THAN EXISTING BREAKERS. BREAKERS FOR HEATING AND AIR CONDITIONING EQUIPMENT SHALL BE 'HACR' RATED. BREAKERS FOR LIGHTING CIRCUITS SHALL 'SWD' RATED.
3. BUS BARS SHALL BE COPPER WITH FULL SIZE NEUTRALS.
4. PROVIDE A PRINTED PANEL SCHEDULE WITHIN A CLEAR PLASTIC SLEEVE IN ALL LOAD CENTERS.
5. PANELBOARDS SHALL BE NEMA PB1, WITH COPPER BUSSES WITH AIC RATING AS INDICATED. PROVIDE TYPED PANEL
SCHEDULE WITH LOCATIONS OF LOADS.
6. EXISTING LOAD CENTERS CIRCUIT DESIGNATIONS AND LOAD RATINGS SHALL BE CONFIRMED IN THE FIELD BY THE CONTRACTOR. DEVIATIONS FROM DESIGN INTENTIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER WHERE
POSSIBLE MALFUNCTIONS MAY BE EXPERIENCED.
7. ALL NEW BREAKERS SHALL BE GFCI, AFCI, OR COMBINATION GFCI/AFCI TYPE WHERE REQUIRED BY NFPA 70, 2017. WHERE EXISTING PANELS ARE NOT CAPABLE OF BEING RETROFITTED WITH THE APPROPRIATE BREAKERS, THE CONTRACTOR SHALL
REPLACE THE PANELS AS REQUIRED.
8. MAIN AND BRANCH CIRCUIT BREAKERS SHALL HAVE MINIMUM SHORT CIRCUIT RATINGS AS IDENTIFIED IN THE PANEL
SCHEDULES.
CONDUIT
1. CONDUITS LOCATED IN DOORS IN NON CORROSIVE OR HAZARDOUS ENVIRONMENTS SHALL BE EMT, ELECTRICAL METALLIC
TUBING WITH COMPRESSION COUPLINGS AND FITTINGS.
2. CONDUITS LOCATED OUTDOORS OR EXPOSED TO PHYSICAL DAMAGE SHALL BE RGS, RIGID GALVANIZED STEEL WITH
THREADED COUPLINGS AND FITTINGS.
3. CONDUITS FOR CONNECTION TO VIBRATING EQUIPMENT, MOTORS, OR WHERE MAINTENANCE REQUIRES SHALL BE FMC, FLEXIBLE METALLIC CONDUIT. WET LOCATIONS SHALL BE LIQUID TIGHT. NO FLEXIBLE CONDUIT SHALL EXCEED 36-INCHES.
4. CONDUITS BELOW GRADE SHALL BE SCHEDULE 40 PVC WITH A MINIMUM DEPTH OF 24-INCHES. PROVIDE 2-INCH SEPERATION FOR ALL POWER SYSTEM CONDUITS AND ELECTRICAL MARKING TAPE SHALL BE INSTALLED 12-INCHES ABOVE THE CONDUIT
RUNNING LONGITUDINALLY WITH THE CONDUIT SYSTEM.
5. CONDUIT ELBOWS OR RISERS SHALL BE RGS AND WHERE EXPOSED TO SOIL OR CONCRETE SHALL BE WRAPPED WITH SCOTCH
WRAP OR VINYL TAPE.
THERMOSTATT
SURFACE MOUNTED OR SUSPENDED INDUSTRIAL STRIP
FIXTURE (FIXTURE TYPE AND CIRCUIT AS INDICATED)A
CEILING MOUNTED FIXTURE
(FIXTURE TYPE AND CIRCUIT AS INDICATED)
CEILING MOUNTED FIXTURE WITH BATTERY BACKUP
(FIXTURE TYPE AND CIRCUIT AS INDICATED)
A
A
SURFACE MOUNTED OR SUSPENDED INDUSTRIAL STRIP
FIXTURE (FIXTURE TYPE AND CIRCUIT AS INDICATED)A
SURFACE MOUNTED OR RECESSED ELECTRICAL
PANELBOARD. SEE POWER ONELINE/RISER DIAGRAM
AND PANEL SCHEDULES FOR MORE INFORMATION.
EL
EC
TR
ICA
L L
EG
EN
D A
ND
NO
TE
S
E -2
N O
S C
A
LE
D R
A W
IN
G
N O
S H
E E
T N
O
N O
. S H
E E
T S
S C
A
LE
D A
T E
P R
O J.
N O
F
LO
R
ID
A R
E G
IS
T
R A
T
IO
N N
O
D E
S
IG
N E
N G
IN
E
E R
C H
E C
K E
D B
Y
D A
T E
D R
A W
N B
Y
D E
S
IG
N E
R
0.
R E
V
IS
IO
N
S D
A T
E B
Y N
O
D A
T E
A U
G U
S T
CIT
Y O
F G
RE
EN
CO
VE
SP
RIN
GS
CIT
Y H
AL
L
BA
CK
UP
GE
NE
RA
TO
R R
EP
LA
CE
ME
NT
PR
OJ
EC
T
W
AL
NU
T S
TR
EE
T, G
RE
EN
CO
VE
SP
RIN
GS
, FL
F E
W A
U G
IS
S U
E D
F O
R C
O N
S T
R U
C T
IO
N
EV
AN
LI
LY
E
NG
IN
EE
RI
NG
M c La ur in
R d
E Ja ck so nv ill e, F
L
Ph
4)
-7
FL
C er tif ic at e of A ut ho riz at io n
F E
W
A U
G U
S T
F E
W
F E
W
A U
G U
S T
F R
A N
K E
. W E
LL
S
, P E
These drawings and associated engineering work are the property of Evanlily Engineering and shall not be reproduced without written consent. Drawings should not be used or repurposed in any manner other than as originally developed and by which Evanlily Engineering was commissioned. Evanlily Engineering takes no responsibility by any party except as originally intended and commissioned by.
M
SERVICE XFMR
23kV-208Y/120V
500KVA
3Φ, 4W
G
125KW
208Y/120V 3Φ, 4W
DIESEL
GENERATOR
GREEN COVE
SPRINGS ELECTRIC
#2 BC
EXISTING
EXISTING
400A 400A/3P70A/3P 400A/3P
1200A/3P
LSI
MDP 1200A, 208Y/120V, 35KAIC, 3PH, 4W
PANEL 1M1
400A MLO
208Y/120V
3Φ, 4W
PANEL 2M1
400A MLO
208Y/120V
3Φ, 4W
400A/3P 90A/3P
ELEVATOR
100A/3P
SPARE
100A/3P
PANEL 1L1
125A MLO
208Y/120V
3Φ, 4W
150A/3P
PANEL 1P1
225A MLO
208Y/120V
3Φ, 4W
175A/3P 225A/3P
PANEL 2P1
225A MLO
208Y/120V
3Φ, 4W
GND
#4/0 BC
PANEL 1M2
225A MLO
208Y/120V
3Φ, 4W
PANEL 1PE
500A MCB
208Y/120V
3Φ, 4W
PANEL 1PE1
225A MLO
208Y/120V
3Φ, 4W
PANEL 2PE
125A MLO
208Y/120V
3Φ, 4W
PANEL 2P2
125A MLO
208Y/120V
3Φ, 4W
100A
PANEL 1P2
225A MLO
208Y/120V
3Φ, 4W
PANEL 1P3
125A MLO
208Y/120V
3Φ, 4W
100A
200A
200A
100A
SPD
ATS
400A
208Y/120V 3Φ, 4W
E N
L
EXISTING
EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING
EXISTING EXISTING EXISTING
EXISTING
EXISTING
EXISTING
M
SERVICE XFMR
23kV-208Y/120V
500KVA
3Φ, 4W
250KW
208Y/120V 3Φ, 4W
DIESEL
GENSET
GREEN COVE
SPRINGS ELECTRIC
3 SETS:
4#600, 1#1/0 IN 4" C.
2 SETS:
4#600, 1#1/0G IN 4" C.
400A/3P70A/3P 400A/3P
1200A/3P
LSI
MDP 1200A, 208Y/120V, 35KAIC, 3PH, 4W
PANEL 1M1
400A MLO
208Y/120V
3Φ, 4W
PANEL 2M1
400A MLO
208Y/120V
3Φ, 4W
400A/3P 90A/3P
ELEVATOR
100A/3P
SPARE
100A/3P
PANEL 1L1
125A MLO
208Y/120V
3Φ, 4W
150A/3P
PANEL 1P1
225A MLO
208Y/120V
3Φ, 4W
175A/3P 225A/3P
PANEL 2P1
225A MLO
208Y/120V
3Φ, 4W
GND
#4/0 BC
PANEL 1M2
225A MLO
208Y/120V
3Φ, 4W
PANEL 1PE
500A MCB
208Y/120V
3Φ, 4W
PANEL 1PE1
225A MLO
208Y/120V
3Φ, 4W
PANEL 2PE
125A MLO
208Y/120V
3Φ, 4W
PANEL 2P2
125A MLO
208Y/120V
3Φ, 4W
100A
PANEL 1P2
225A MLO
208Y/120V
3Φ, 4W
PANEL 1P3
125A MLO
208Y/120V
3Φ, 4W
100A200A 200A
100A
SPD
ATS
1200A 208Y/120V 3Φ, 4W
EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING
EXISTING EXISTING EXISTINGEXISTING
EXISTING
2 SETS:
4#3/0N, 1#3G IN 2" C.
G
800A
LSI
#2/0 BC
3 SETS:
4#600, 1#1/0 IN 4" C.
EN
L
1200A
LSIG
NEW J-BOX IN PLACE OF
EXISTING AUTOMATIC
TRANSFER SWITCH
2 SETS:
4#600, 1#1/0G IN 4" C.3 SETS:
4#600, 1#1/0 IN 4" C.
UTILIZE BASE OF EXISTING
MDP PANEL FOR ROUTING
NEW SERVICE ENTRANCE
CONDUCTORS TO NEW
TRANSFER SWITCH
SHUNT
TRIP
SPD
SCALE: NTS
ONELINE DIAGRAM - DEMOLITION
SCALE: NTS
ONELINE DIAGRAM - PROPOSEDSCALE: NTS
CITY HALL LOAD CALCULATION
GREEN COVE SPRINGS CITY HALL LOAD CALCULATION w/o HEAT STRIPS
OFFICE
LOAD TYPE SQUARE FOOT - OFFICE 25494
LIGHTING @ 1.6 VA/SF (OFFICE PER NEC 220.42) 40790
SUBTOTAL A (VA) 40790
REFRIGERATOR 2400
MICROWAVE 3600
TELECOMMUNICATIONS 1200
WATER HEATER 4500
VENDING MACHINE 900
ICE MAKER 900
DISHWASHER 900
FIRST 10KW @ 100% 10000
REMAINDER @ 50% 4400
HEAT PUMP LOAD (KVA) 96044
AIR HANDLER UNITS (KVA) 36124
SUBTOTAL B (VA) 146568
TOTAL A + B (VA) 187358
TOTAL ESTIMATED LOAD @ 208VAC, 3 PHASE 520
MINIMUM FEEDER CIRCUIT AMPACITY 650
FEEDER CONDUCTOR SIZE
2 SETS:
3#600, 1#600N, 1#1/0G
FEEDER CONDUCTOR RATING (A) 840
GROUNDING ELECTRODE CONDUCTOR COPPER #4/0 CU
EMERGENCY AUXILIARY HEAT STRIPS HAVE NOT BEEN INCLUDED IN THIS
CALCULATION. DURING ABNORMAL COLD EVENTS WITH AUXILIARY HEAT STRIP
OPERATION THE SYSTEM MAY NOT FUNCTION SATSIFACTORILY AND MAY
EXPERIENCE INADVERTANT GENERATOR TRIPPING OR LOAD SHEDDING.
EL
EC
TR
ICA
L O
NE
-LIN
ES
AN
D C
AL
CU
LA
TIO
NS
E
-3
N O
S C
A
LE
D R
A W
IN
G
N O
S H
E E
T N
O
N O
. S H
E E
T S
S C
A
LE
D A
T E
P R
O J.
N O
F
LO
R
ID
A R
E G
IS
T
R A
T
IO
N N
O
D E
S
IG
N E
N G
IN
E
E R
C H
E C
K E
D B
Y
D A
T E
D R
A W
N B
Y
D E
S
IG
N E
R
0.
R E
V
IS
IO
N
S D
A T
E B
Y N
O
D A
T E
A U
G U
S T
CIT
Y O
F G
RE
EN
CO
VE
SP
RIN
GS
CIT
Y H
AL
L
BA
CK
UP
GE
NE
RA
TO
R R
EP
LA
CE
ME
NT
PR
OJ
EC
T
W
AL
NU
T S
TR
EE
T, G
RE
EN
CO
VE
SP
RIN
GS
, FL
F E
W A
U G
IS
S U
E D
F O
R C
O N
S T
R U
C T
IO
N
EV
AN
LI
LY
E
NG
IN
EE
RI
NG
M c La ur in
R d
E Ja ck so nv ill e, F
L
Ph
4)
-7
FL
C er tif ic at e of A ut ho riz at io n
F E
W
A U
G U
S T
F E
W
F E
W
A U
G U
S T
F R
A N
K E
. W E
LL
S
, P
These drawings and associated engineering work are the property of Evanlily Engineering and shall not be reproduced without written consent. Drawings should not be used or repurposed in any manner other than as originally developed and by which Evanlily Engineering was commissioned. Evanlily Engineering takes no responsibility by any party except as originally intended and commissioned by.
SCALE: 1/8" = 1'-0"
CITY HALL ELECTRICAL SITE PLAN
GENERAL NOTES:
KEYNOTES:
N
3" 3"3" 3"
24"
6"
24" MINIMUM
12"
18" MIN.
UNDERGROUND DIRECT BURIED CONDUIT DETAILU/G PVC CONDUIT INSTALLATION DETAIL GROUND ROD ASSEMBLY
SCALE: 1/8" = 1'-0"
0 8' 16'
PANEL MDP
EXISTING 500KVA,
208Y/120V SERVICE
TRANSFORMER
PANEL 1L1
TRANSFER SWITCH
TO BE DEMOLISHED
PANEL 1PE
PANEL 1P1
PANEL 1M1
PROPOSED
TRANSFER SWITCH
EXISTING 3-4" C.
EXISTING
2-4" C.
1-1.5" C.
PARKING LOT
PARKING LOT
STAIRWELL
ELECTRICAL ROOM
HVAC ENCLOSURE
GENERATOR
ENCLOSURE
PROPOSED DIESEL
GENERATOR AND
FUEL TANK
COVERED WALKWAY
COVERED WALKWAY
EL
EC
TR
ICA
L S
ITE
AN
D B
UIL
DIN
G P
LA
NS
E
-4
A S
S H
O W
N D
R A
W
IN
G N
O
S H
E E
T N
O
N O
. S H
E E
T S
S C
A
LE
D A
T E
P R
O J.
N O
F
LO
R
ID
A R
E G
IS
T
R A
T
IO
N N
O
D E
S
IG
N E
N G
IN
E
E R
C H
E C
K E
D B
Y
D A
T E
D R
A W
N B
Y
D E
S
IG
N E
R
0.
R E
V
IS
IO
N
S D
A T
E B
Y N
O
D A
T E
A U
G U
S T
CIT
Y O
F G
RE
EN
CO
VE
SP
RIN
GS
CIT
Y H
AL
L
BA
CK
UP
GE
NE
RA
TO
R R
EP
LA
CE
ME
NT
PR
OJ
EC
T
W
AL
NU
T S
TR
EE
T, G
RE
EN
CO
VE
SP
RIN
GS
, FL
F E
W A
U G
IS
S U
E D
F O
R C
O N
S T
R U
C T
IO
N
EV
AN
LI
LY
E
NG
IN
EE
RI
NG
M c La ur in
R d
E Ja ck so nv ill e, F
L
Ph
4)
-7
FL
C er tif ic at e of A ut ho riz at io n
F E
W
A U
G U
S T
F E
W
F E
W
A U
G U
S T
F R
A N
K E
. W E
LL
S
, P
These drawings and associated engineering work are the property of Evanlily Engineering and shall not be reproduced without written consent. Drawings should not be used or repurposed in any manner other than as originally developed and by which Evanlily Engineering was commissioned. Evanlily Engineering takes no responsibility by any party except as originally intended and commissioned by.
| Sheets and Views |
| E-1 Cover Sheet-E-1 |
| E-2 Electrical Legend and Notes-E-2 |
| E-3 Electrical One-Lines and Calculations-E-3 |
| E-4 Electrical Site and Bldg Power Plans-E-4 |
| 2024-08-26T13:45:52-0400 | |
| Franklin E Wells |