This posting provides references for a sole source requirement for dynamic positioning services on the NOAA ship Reuben Lasker. The references indicate that the incumbent contractor, Marine Systems, Inc., has successfully provided dynamic positioning services on the Reuben Lasker since 2015. The references describe Marine Systems' experienced crew, their familiarity with the vessel through previous contracts, and their satisfactory performance in maintaining the dynamic positioning system.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES
A
B
C
D
A
B
C
DRAWING NO. SH REV
D
A
D
REVDRAWING NO.SIZE
USCG APVD: DATE:
SCALE
ABS APVD: DATE:
FSCM CAGE NO.
98042
OF
FSV6-320-01
FSV6-320-01 G
H
1 39N.T.S.
12345678
1345678
REVISIONS
SHT REV DESCRIPTION DATE APPROVED
C REV C 12/02/1 T.T.
D REV D 3/13/13 T.T.
E REV E 8/16/13 D.K.
CONTRACT NO: AB133M-10-CN-0091
DWN:
MARINETTE WISCONSIN 54143
CHKD:
APRV:
APRV:
PE STAMP:
DATE:
Consulting Engineers Serving the Marine Community
1201 Western Avenue, Suite 200 Seattle, Washington 98101-2921
TEL
FAX
WEB
206.624.7850 206.682.9117 www.glosten.com
NATIONAL OCEANIC &
ATMOSPHERIC ADMINISTRATION
(NOAA)
FISHERIES SURVEY VESSEL 6
(FSV6)
10/01/10
10/01/10
10/01/10
10/01/10
C.J.
B.J.
B.J.
A.R. DIAGRAM
ONE-LINE
POWER
1. THIS DRAWING WAS DEVELOPED IN ACCORDANCE WITH ABS, USCG AND
IEEE STANDARD 45 REQUIREMENTS.
2. STEERING PUMP CIRCUIT BREAKERS SHALL HAVE AN "INSTANTANEOUS
MAGNETIC TRIP ONLY" SET AT 175-200% OF THE LOCKED ROTOR CURRENT
VALUE IN ACCORDANCE WITH USCG 46 CFR 58.25-55(a)(2).
3. THE STEERING CIRCUITS SHALL MEET ALL OF THE REQUIREMENTS OF
ABS "RULES FOR BUILDING AND CLASSING STEEL VESSELS UNDER 90
METERS (295 FEET) IN LENGTH" SECTION 4-6-2/11, USCG
46CFR58.25-55, AND 46CFR113.43.
4. ALL ABBREVIATIONS ARE IN ACCORDANCE WITH MIL-STD-12D UNLESS
OTHERWISE NOTED.
5. ALL CABLE IS LOW SMOKE HALOGEN TYPE IN ACCORDANCE WITH
MIL-C-24643 OR COMMERCIAL MARINE TYPE "XIU" UNLESS OTHERWISE
NOTED.
6. THE FOLLOWING 600V OPERATIONAL BUS TIE CONFIGURATIONS SHALL BE
PROVIDED:
• OPERATION OF ANY COMBINATION OF GENERATORS CONNECTED IN PARALLEL
TO THE INTEGRATED PROPULSION AND SHIP SERVICE BUS.
• SEPARATE GENERATOR(S) DEDICATED TO SHIP SERVICE ELECTRIC LOADS
AND TO PROPULSION PLANT LOADS. PROPULSION PLANT LOADS IN THIS
CASE INCLUDE BOW THRUSTER.
• SEGREGATION OF THE BOW THRUSTER AND GENERATOR FROM ALL OTHER
LOADS.
7. PROPULSION CABLE MUST BE CERTIFIED IN ACCORDANCE WITH ABS
4-1-1/3.3 PRIOR TO SHIPMENT OF CABLE TO YARD.
8. WHEN THE SHIP IS ON SHORE POWER, MEANS ARE PROVIDED TO
PREVENT INADVERTENT PARALLELING OF SHIP'S GENERATORS WITH SHORE
POWER UPON LOSS OF SHORE POWER. SCIENTIFIC POWER SYSTEMS ARE
NOT INTERRUPTED DURING TRANSFER TO AND FROM SHORE POWER.
9. BREAKERS FOR MOTOR CIRCUITS IN MOTOR CONTROL CENTERS WILL BE
MOTOR CIRCUIT PROTECTION BREAKERS ONLY INSTANTANEOUS ADJUSTABLE
MAGNETIC TRIP UNITS SHALL BE USED, IN CONFORMANCE WITH N.E.C. PART
430D. EACH MCP SHALL BE SIZED AND ADJUSTED TO CARRY THE STARTING
CURRENT OF THE MOTOR. ALL OTHER BREAKERS NOT NOTED MCP WILL BE
THERMAL MAGNETIC BREAKERS.
10. ALL CIRCUIT BREAKERS ARE 3 POLE UNLESS LABELED 2P FOR
TWO-POLE OR 1P FOR SINGLE POLE.
11. BONDING AND GROUNDING SHALL BE IN ACCORDANCE WITH REFERENCE
9. CABLES EXITING THE HULL OF THE SHIP SHALL BE SHIELDED OR RUN IN
EMI CONDUIT OR PIPE IN ACCORDANCE WITH REFERENCE 11. FOR SHIELDED
CABLE INSERT GROUND ADAPTERS IN SWAGE TUBE.
12. CONTROLLERS SHALL BE FULL VOLTAGE NON REVERSING, 600/480VAC
AS REQUIRED, 60 HZ, 3 PHASE IN NEMA 12 DRIPPROOF ENCLOSURE AND
SHALL INCLUDE A CONTROL POWER TRANSFORMER (600/480-120VAC) WITH
FUSES FOR BOTH PRIMARY AND SECONDARY LEGS AND A TERMINAL STRIP
FOR WIRING EXTERNAL DEVICES. CONTROLLERS SHALL MEET THE
REQUIREMENTS OF ABS, USCG, IEEE-45 AND UL 508 INCLUDING MARINE
SUPPLEMENT.
13. SOLID STATE PASSIVE INSULATION RESISTANCE MONITORS, IN
ACCORDANCE WITH ASTM F1134, SHALL BE PROVIDED FOR GENERATORS AND
MOTORS FOR PROPULSION, STEERING, HYDRAULIC POWER, SEAWATER AND
FRESH WATER SERVICES, AND THOSE MOTORS IN THE WEATHER SUBJECT TO
MOISTURE CONDENSATION. THE INSULATION RESISTANCE MONITOR SHALL
ACTIVATE A LOCAL RED "IRM ALARM" PILOT LIGHT IN THE FACE OF THE
CONTROLLER, AND AT THE EOS FOR A LOW INSULATION CONDITION.
14. MOTOR CONTROL CENTERS SHALL BE NEMA TYPE 1 DRIPPROOF
ENCLOSURES WITH COPPER HORIZONTAL AND VERTICAL BUSES. WIRING SHALL
BE NEMA CLASS 1, TYPE B AND CONNECTION INPUT TERMINALS SHALL BE
MOUNTED AS REQUIRED FOR CABLE ENTRY. ALL STARTERS ARE
COMBINATION TYPE. MOTOR CONTROL CENTERS SHALL MEET THE
REQUIREMENTS OF ABS, USCG, IEEE-45 AND UL 845.
15. FOR CIRCUIT BREAKER SETTINGS ON 600 VOLT, 480 VOLT AND
EMERGENCY SWITCHBOARD, SEE COORDINATION STUDY (REF 3).
16. CIRCUIT BREAKERS REFERENCING THIS NOTE SHALL BE CAPABLE OF
BEING 'LOCKED-OUT' IN THE OFF POSITION.
17. ALL PROPULSION CABLES SHALL BE TESTED IN ACCORDANCE WITH ABS
4-6-5/3.17.12(e) BY THE SUPPLIER PRIOR TO SHIPMENT.
18. NON-STANDARD ABBREVIATIONS:
• A/C - AIR CONDITIONING
• GCC - GROUP CONTROL CENTER
•MSD - MARINE SANITATION DEVICE
• ECC - ENGINEER'S CONTROL CONSOLE
•MCC - MAIN CONTROL CONSOLE
19. THE MOTOR HEATERS FOR THE VENT FANS SHALL BE SUPPLIED FROM
THE MOTOR CONTROLLER FOR THE FAN AND THE CONTROL POWER
TRANSFORMER SHALL BE SIZED TO CARRY THE LOAD OF THE HEATER.
HEATERS SHALL BE INTERLOCKED TO COME ON WHEN MOTOR IS SECURED.
20. ALL POWER PANELS AND LOAD CENTERS ARE TO BE NEMA 1,
DRIPPROOF.
21. CONTROLLER SHALL BE TWO SPEED REVERSING, SINGLE WINDING,
CONSTANT HORSEPOWER FOR REMOTE CONTROL ONLY. SHALL ALSO HAVE
NON-FUSED DISCONNECT AND CPT FOR CONTROL POWER. CPT SHALL BE
SIZED AND WIRED TO POWER SPACE HEATER FOR MOTOR.
22. AUTO TRANSFER SHALL SWITCH TO THE OTHER BUS IF THERE IS A
FAILURE ON THE BUS FOR ANY REASON.
23. ALL CIRCUIT BREAKERS LOCATED IN THE ENGINE ROOM/MACHINERY
SPACE WILL BE RATED FOR 50C AMBIENT TEMPERATURE IAW 116 CFR
111.54-16e.
24. GROUND GRID - PROPULSION MOTORS PROPULSION DRIVES AND
PROPULSION TRANSFORMERS SHALL BE GROUNDED AT THE MAIN
SWITCHBOARD. NO OTHER GROUNDS SHALL BE INSTALLED ON THIS
EQUIPMENT.
25. ALL CABLES BETWEEN VARIABLE FREQUENCY DRIVES (VFD) AND ITS
MOTOR(S) SHALL BE VFD-RATED. ALL MOTORS CONNECTED TO VFDs SHALL
BE INVERTER DUTY-RATED.
26. ALL 208V & 120V DISTRIBUTION PANELS HAVE AN ISOLATED NEUTRAL
BUS.
27. REFER TO ELECTRIC PLAN LOAD ANALYSIS, FSV6-300-01, FOR POWER
RATINGS NOT DESIGNATED ON THIS DRAWING.
MISSION SCIENTIFIC BLOCK WIRING DIAGRAM
EXTERIOR COMMUNICATIONS BD
NAV, SIG, & SEARCHLTS ARR & WD
CATHODIC PROT SYS ARR & DET
W.T. DOOR SYSTEM WD
I.C. SYSTEMS BD
LCTN. OF PRPLN. CONT & AUTOMATION EQPT
CABLEWAY KEY PLAN
ELEC STANDARDS WRG PRACTICES & INSTALL DETAILS
STEERING CONTROL SYSTEM BD
FIRE ALARM SYSTEM WD
LIGHTING SYSTEM ONE LINE DIAGRAM
PHASE BALANCE STUDY
VOLTAGE DROP CALCULATIONS
BREAKER COORDINATION STUDY
FAULT CURRENT ANALYSIS
DRAWING TITLE
REFERENCE DRAWINGS
POWER LOAD ANALYSIS
NO.
FSV6-300-01
DE-ICING SYSTEM ARR & DET18
MACHR'Y CTL & ALARM SYS BD19
ARRANGEMENT OF ELECTRICAL PWR EQUIPMENT
BOW THRUSTER SYSTEM BLOCK DIAGRAM
22 WINCH & TRAWL CTL SYS BD
SHIPS INTERIOR COMMUNICATION SYS BD
DYNAMIC POSITIONING SYS BD23
25 MAIN MACHINERY ROOM ARRANGEMENT
26 CCTV/CATV/CLOCK/H2SO4 BWD
27 SHIP'S METEOROLOGICAL EQUIPMENT BD
SHIP'S SERVICE COMPRESSED AIR SYS DIA
PROPULSION CONTROL SYSTEM BD
PROPULSION SYSTEM TERMINATION LIST
PIPING SYSTEM DIAG - FRESH & POT WTR
MISCELLANEOUS HOOKUP
MMC DWG NO.
P603 & P604
SCIENCE POWER SWITCHBOARD
EMERGENCY GEN, SWITCHBOARD & 24VDC SYS
600V & 480V DISTRIBUTION SWITCHBOARDS
PROPULSION MOTORS & BT MOTORS/DRIVES
PARTS LIST
DESCRIPTION
PARTS LIST3
SYMBOL LIST
SHEET
INDEX
P610 & P616 P614, P415A & P415B
P607 & P608
25 P420, P222 & P120-1
P416, P419 & P103 P405, P406, P415
P111-3 & P111-4 P111-1 & P111-2
P609, P609-1 & P609-2
SCP107A & SCP107B
SCP104A & SCP104B
EP404, EP122-A & EP128
SHEET DESCRIPTION
P619 & P620
P411 & P412
29 SCP103A, SCP105A, SCP106A & SCP110A
SCP110A-331
32 SCP110A-4 & SCP110A-5
SCP110A-6 & SCP110A-733
SCP110A-1 & SCP111A
P112-119
600V SWITCHBOARD & GENERATORS5
PROPULSION TRANSFORMERS AND DRIVES6
35 BLANK
EMER LOUVERS WD36
1 GENERAL MOTES, REFERENCES, SHEET INDEX
PRPLN SYS GND GRID INSTALL & CABLE DIAG
DETAIL 298-B, WASTE OIL HEATER INTERLOCK38
FSV6-300-02
FSV6-300-03
FSV6-300-04
FSV6-300-05
FSV6-330-01
FSV6-610-01
FSV6-426-01
FSV6-321-01
FSV6-304-01
FSV6-201-01
FSV6-432-01
FSV6-437-01
FSV6-633-01
FSV6-422-01
FSV6-441-01
FSV6-461-01
FSV6-333-02
FSV6-202-01
FSV6-437-02
FSV6-301-01
FSV6-437-06
FSV6-438-03
FSV6-432-01
FSV6-200-01
FSV6-439-01
FSV6-493-01
FSV6-202-05
FSV6-551-01
FSV6-202-04
FSV6-533-01
FSV6-430-01
P605 & P606
34 SCP110A-8
RES. NO.
RESERVATIONS
R001
DESCRIPTION DATE APPROVED
PENDING VENDER INFORMATION 10/01/10 B.J.
- 10/01/10
1A REVISIONS
33 MISCELLANEOUS HOOKUP FSV6-437-08
1-38 B.J.INITIAL ISSUE
1-38 A REV A BJ2/16/11
34 INTEGRATED BRIDGE SYSTEM BD FSV6-438-01
1-38 B REV B 8/04/11 T.T.
35 HVAC DIAGRAM SUPPLY AND EXHAUST FSV6-512-01
36 HVAC CONTROL SYSTEMS FSV6-437-09
SCP110A-2 & SCP110A-939
20 P112-2
1B REVISIONS
37 MISCELLANEOUS ALARM SYSTEMS FSV6-436-02
1-39
1C REVISIONS
1D REVISIONS
1-39 1-39
1E REVISIONSF
1 - 39 H REV H 6/ 28/ 22
B
C
D
A
B
C
DRAWING NO. SH REV
D
A
D
REVDRAWING NO.SIZE
USCG APVD: DATE:
SCALE
ABS APVD: DATE:
FSCM CAGE NO.
98042
OF
FSV6-320-01
FSV6-320-01 G
H
1A
1A 39N.T.S.
9A10A11A12A13A14A15A16A
9A11A12A13A14A15A16A
DATEDESCRIPTIONZONE REV
REVISIONS
APPROVED
1. GENERAL NOTE 6 WORDING WAS "OPERATION OF ANY NUMBER OF GENERATORS."
A
7D
2. REVISED GENERAL NOTE 8, WAS "SHIP SERVICE GENERATORS SHALL BE
INTERLOCKED WITH SHORE POWER TO PREVENT PARALLELING THE TWO."
3. GENERAL NOTE 11 BONDING & GROUNDING WAS CALLED OUT AS REFERENCE 11.
7C
7C
5. REVISED RESERVATION R001 FROM PENDING HVAC SOLICITATION.5A
5A 3D
4. COMPLETELY REPLACED GENERAL NOTE 23.
SH 1A 9. ADDED SHEET 1A.
10. REVISED DESCRIPTION OF THRUSTER TRANSFORMERS.
6. REVISED REV - ISSUE DESCRIPTION & DATE. ADDED REV A ISSUE INFORMATION.
7. ADDED REFERENCE DWG # 33.
8. ADDED SHEET 1A TO SHEET INDEX.
22C 11. ADDED PART NO'S FOR ITEMS 30 & 31.
13. BUS A & D WERE CON'T ON SH 5.
19C
39C
14. ADDED 6GP-1B & CABLE SIZE37C
12. ADDED MANUFACTURER AND PART NO. FOR ITEM 100 & DELETED REMARKS.
15. P081 & P091 WERE (4) LSDSGU-400.42B
46B 51C
17. RELEASED RESERVATION R001.
52C 59A-
18. REVISED SHORE POWER FROM REF 25 TO REF 21.
63C 60C
68A
19. REVISED PHASE SHIFTING XFMR FROM
20. REVISED WATERTIGHT DOOR REFERENCE FROM 16 TO 13.
59C
7A
5B
15C
34C,
16. P081 & P091 WERE (4) LSDSGU-400.
VV
67C 67C
21. ADDED CABLE TYPE TO EP415.
22. CIRCUIT EP407 WAS SPARE. ADDED WATER MIST SYS. (SOLAS REQ.)
69C 23. CIRCUIT EP404 WAS LSTSGU-200.
74C 24. ADDED AMP METER TO GROUND DETECTION CIRCUIT.
84B 25. REVISED IRM FROM REF 23 TO REF 19.
92C 26. DELETED REF ON P107-3(C) & P107-4(C).
94C 27. REVISED C-AM-500-19 & C-AM-500-6 FROM REF 23 TO REF 19.
102A 28. REVISED POTABLE WATER SKID TO FWD STBD BULKHEAD.
108C 29. REVISED STBD BRIDGE CONSOLE FROM REF 26 TO REF 22.
110B 30. REVISED IP415-A & B FROM SEE SHEET 23 TO SEE SHEET 8.
110C
31. RELEASED RESERVATION R001.118D
32. P610-1 WAS LSTSGU-41.118D
33. RELEASED RESERVATION R001.123D
125D
34. RELEASED RESERVATION R001.131D
133D 135D
35. IRM WAS REF 23 NOW REF 19.130B
36. P609-5 WAS LSTSGU-41.133D
37. RELEASED RESERVATION R001.139D
141B 142D
38. RELEASED RESERVATION R001.149D
39. RELEASED RESERVATION R001.157D
40. RELEASED RESERVATION R001.163D
166D
41. RELEASED RESERVATION R001.173D
42. P111-4A WAS LSDSGU-9.171C
43. P416-8 & P416-8(M) WERE LSTSGU-9.178C
179C
44. ADDED REF 14 TO CATHODIC PROTECTION.181D
45. P419-3 WAS 2P.182D
46. P103-14 & P103-15 WERE SPARE.181A
47. P103-13 WAS 2P.182A
48. REFERENCE DRAWING WAS REF 22.189A
49. ADDED REF 14 TO P222-14.194B
50. P120-1B WAS 2P.199B
51. EP128-14 WAS 3P.202B
191B
52. EP128-20 WAS SPARE.202B
53. EP404 WAS LSTSGU-200.206D
54. EP122-A19 WAS SPARE.207A
55. SCCP104A & B WERE NEMA-4 W/DRIPSHIELD, SURFACE MTD(LOCATED: WET LAB).211B
56. SCP104A-10 WAS 2P.214C
57. SCP104B WAS, SURFACE MTD.119B
58. SCP107B-15 WAS LSTSGU-9, UNTERNET PWR SW (IPS-400).219C
221C 59. SCP107A-14 WAS LSTSGU-4, PRESERVATION ALCOVE RECEPTACLE STRIP.
223C 60. SCP107A-11 WAS LSTSGU-4, PRESERVATION ALCOVE RECEPTACLE STRIP.
SCP107A-13 WAS LSTSGU-4, PRESERVATION ALCOVE RECEPTACLE STRIP.
226B 61. SCP110A WAS LSFSGU-75.
235D 62. SCP110A-1B WAS 35AT, LSDSGU-9, VSAT CABINET.
235C 63. SCP110A-1D(102), WAS 15AT, LSDSGU-4, REF 26.
233C 64. SCP110A-1M(202), WAS REF 26.
235D 65. SCP110A-1A, WAS REF 35.
236C 66. SCP110A-1J WAS REF 21.
235C 67. SCP110A-1L WAS REF 26.
235C 68. SCP110A-1T WAS REF 26.
235C 69. SCP110A-1W(4) WAS REF 26.
DESCRIPTIONZONE REV APPROVED
70. SCP111A-1 WAS REF 35.239D
244C
244B
76. SCP110A-5 WAS NEMA-4 & IN FISH LAB.251B
252B 254B
75. SCP110A-3 WAS SURFACE MTD..
260B 80. SCP110A-7R WAS REF 21.
81. SCP110A-7J WAS SPARE.
77. SCP110A-5T(99) WAS REF 26.
79. SCP110A-7T WAS BONGO NET PROFLIER, LSDSGU-4.
263C 82. SCP110A-6R WAS 30AT.
84. ADDED LSTSGU-23 TO SCP110A-8.
267B
277A 85. ADDED RESERVATION R001 CALL-OUT.
277A
83. RE-DREW DETAIL 267-B SHOWING DASHED LINES PROPERLY.
REV A AUTHORIZATION.
42B 46B
244B
260B
260C
270C
71. SCP110A-3M WAS REF 21.244C
72. SCP110A-3P WAS REF 21.
73. SCP110A-3S WAS REF 21.244B
74. SCP110A-3U WAS REF 21.
78. SCP110A-4 WAS NEMA-4 & IN WET LAB.
CONTINUED ZONE 14A-D THIS SHEET.
6D 86. ADDED GENERAL NOTE 26.
92C 87. C-AM-500-142 WAS RES 23, NOW RES 19.
135A
CONTINUED FROM ZONE 11A-A THIS SHEET.
REVISIONS
NOAA- REF. COMMENT TRANSMITTAL INFORMATION LETTER: DATE DEC 27, 2010,
TRANSMITTAL SERIAL NO. 0120-0133.
ABS- REF. ABS REQ. TRANSMITTAL LETTER.
TRANSMITTAL SERIAL NO. 0120-0133.
OPN: 2416603
TASK NO:642098
SOLAS-REF. SOLAS REQ., EDITION (2009) CHAPTER -2,
PART C, REQ. 10, SECT 5.6.
MMC- REF. DESIGN DEVELOPMENT & IMPROVEMENT.
59C 88. CIRCUIT P613 WAS WINCH PWR PNL NO. 2. NOW SPARE.
214B
89. EP404-6, 10, 11 & 12 WERE SPARES. ADDED XMFR'S & GA/PA NODES.
207C 205C
258B 90. SCP110A-7S & SCP110-7U WERE SPARES.
258C
221C 91. SCP107A-8 WAS SPARE IS SCIENTIFIC SEAWATER.
204C 92. EP128-5 WAS PA PANEL, LSDSGU-9, IS SPARE.
229C 93. SCP103A WAS SHIP'S INTERCOM SYS, LSTSGU-4, IS SPARE.
29B 94. ADDED ITEM 221 TO PARTS LIST.
APPROVEDDATE
APPROVEDDATEDESCRIPTIONREV
CONTINUED ZONE 16A-D THIS SHEET.CONTINUED ZONE 11B-D SHEET 1B.
B
8/04/11 TT1. ADDED REFERENCE 34, 35, AND 36.
2. ADDED SHEETS 1B AND 39 TO INDEX.
3. REVISED REFERENCE 16 (WAS INTEGRATED BRIDGE
(FSV6-438-01).
4. RELEASED RESERVATION R001.
5. ADDED SHEET 1B.
6. ADDED SYMBOL FDC.
7. REVISED ITEMS 1-4 (ADDED WEIGHTS), ITEMS 92-95
(CORRECTED MMC PART NUMBER), AND ITEM 94 (ADDED PNL
SERVICE TO DESCRIPTION).
8. REVISED ITEMS 168 (WAS QTY 8) ,169 (WAS SOLENOID VALVE)
AND 222 (WAS ITEM NO. 221.
9. DELETED ITEMS 187, 212, 215.
10. ADDED ITEMS 221 & 223-226.
11. ADDED MMC PART NUMBER FOR ITEM 189 AND 190.
12. DELETED CIRCUITS P410-1 AND P415-1.
13. ADDED TRAWL SYS XFMR ITEM 226.
14. DELETED IRM CIRCUITS FROM ITEM 91 & 92.
15. REVISED DESCRIPTION (WAS STEERING CTRL PNL).
16. REVISED DESCRIPTION (WAS STEERING CTRL PNL).
17. REVISED NOMENCLATURE FOR CIRCUITS CP24-13 (WAS
STEERING CTRL PANEL), CP24-15 (WAS STEERING ALARM
UNIT), AND CP24-16 (WAS SPARE).
18. REVISED DESCRIPTION (WAS ENVIRONMENT UNIT)
19. DELETED CIRCUITS P604-13, P604-14, AND P103-1B.
20. DELETED JUNCTION BOX, (ITEM 187) AND CIRCUIT P603-6A.
21. DELETED CIRCUIT P608-10 P103-1A, AND ONE BLANK
CIRCUIT FROM P608.
22. REVISED BREAKER RATING AND NOMENCLATURE OF CIRCUIT
P607-2 (WAS 20AT/SCR DRIVE #2).
23. REVISED REFERENCE SHEET NUMBER FOR CIRCUIT
P105-6(C3).
24. DELETED CIRCUITS P103-4A, P607-12, P607-13, P607-14,
AND P607-15.
25. DELETED THREE BLANK CIRCUITS FROM PANEL P607.
26. REVISED BREAKER TYPE/RATING FOR CKT P606-6 (WAS 15A).
27. REVISED SPELLING OF INCINERATOR AND REFERENCE SHEET
NUMBER FOR CIRCUIT P105-6(C3).
B
SHEET
SHEET
REVISIONS
28. DELETED CIRCUIT P103-8(A) AND IRM CIRCUIT.
29. REVISED CABLE SIZE OF CKT P614-7 (WAS LSTSGU-23).
30. ADDED CIRCUIT BREAKER TO CIRCUIT P614-2.
31. REVISED CONFIGURATION OF GCC P610 AND P616 TO
LATEST HVAC DATA.
32. RELEASED RESERVATION R001.
33. DELETED GAYLORD HOOD SYSTEM DIAGRAM.
34. DELETED GALLEY/SCULLERY DUCT HEATER WIRING
DIAGRAM.
35. REVISED CONFIGURATION OF GCC P620 TO LATEST HVAC
DATA.
36. REVISED CONFIGURATION OF GCC P619 TO LATEST HVAC
DATA.
37. REVISED CONFIGURATION OF GCC P609-1, P609, AND
P609-2 TO LATEST HVAC DATA.
38. REVISED CONFIGURATION OF P411, P412, AND P412-3
TO LATEST HVAC DATA.
39. REVISED NOMENCLATURE OF CIRCUITS P112-1C AND
P112-1E TO AGREE WITH LATEST HVAC DATA.
40. REVISED CONFIGURATION OF P112-2 TO LATEST HVAC
DATA.
41. REVISED CONFIGURATION OF P111-1 AND P111-2 TO
LATEST HVAC DATA.
42. REVISED CONFIGURATION OF P111-3 AND P111-4 TO
LATEST HVAC DATA.
43. DELETED FN 212 213, 214, AND 215 FROM CIRCUIT
P419-1.
44. REVISED NOMENCLATURE OF CIRCUIT P103-14A.
45. DELETED CIRCUITS P419-9 (WAS BT UNIT HEATER) AND
P103-1 (WAS IRM TO GCC P608 AND P604).
46. ADDED CIRCUITS P419-11 AND P103-16.
47. ADDED CALLOUT (FN 223) TO CIRCUIT P416-10.
48. DELETED CIRCUITS P415-1 AND P410-1.
49. REVISED NOMENCLATURE OF CIRCUITS, WAS P410-1C
AND P410-1B.
50. REVISED LOCATION OF TRANSFORMER P420-1 (WAS MMR
2ND DECK PORT).
51. REVISED LOCATION OF POWER PANEL P120-1 (WAS
GALLEY).
52. ADDED STEAMER CIRCUIT P420-3.
53. REVISED NOMENCLATURE OF CIRCUIT P420-9.
54. REVISED CABLE TYPE OF CIRCUIT P420-4 WAS
LSTSGU-4.
55. DELETED CIRCUITS P222-7, P222-8, P222-9, P222-10,
AND P222-16.
56. REVISED CKT NOMENCLATURE (WAS MCC UPS NO.1).
57. REVISED CKT NOMENCLATURE (WAS MCC UPS NO. 2).
58. REVISED CKT NOMENCLATURE (WAS SCC PWR SUPPLY
NO.2).
59. REVISED CKT NOMENCLATURE (WAS SCC PWR SUPPLY
NO.1).
60. REVISED CKT NOMENCLATURE (WAS HF#2).
61. REVISED CKT NOMENCLATURE (WAS HF#1 INMARSAT B#1).
62. REVISED NOMENCLATURE OF CIRCUITS EP404-1,
EP404-2, EP404-3, EP404-4, EP404-11, EP404-12A,
EP122-A19A, EP128-4, EP128-6, EP128-14,
EP128-16, AND EP128-18.
63. ADDED CIRCUITS EP128-5, AND EP128-13.
64. DELETED CIRCUIT EP122-A6 (WAS SCC UPS).
65. ADDED CIRCUITS SCP104A-11 AND SCP104A-12.
66. DELETED CIRCUITS SCP107A-9 AND SCP107A-12 FOR
PRESERVATION ALCOVE.
67. ADDED CIRCUITS SCP105A-23, SCP103A-11, SCP110A-2,
AND SCP110A-9.
68. REVISED NOMENCLATURE OF CIRCUITS SCP105A-24 AND
SCP103A-14.
69. ADDED CIRCUITS SCP111A-7, SCP111A-14, SCP111A-15,
SCP111A-16, SCP111A-17, AND SCP110A-1Z.
70. REVISED CABLE TYPE OF CIRCUIT SCP111A-6.
71. REVISED NOMENCLATURE OF CIRCUITS SCP111A-13 AND
SCP110A-1P.
72. DELETED CIRCUITS SCP110A-1D, SCP110A-1M,
SCP110A-1T SCP110A-1V, AND SCP110A-1W(4). (TRAWL
WINCH CKTS).
73. ADDED CIRCUIT SCP110A-3E.
1B
C
D
A
B
C
DRAWING NO. SH REV
D
A
D
REVDRAWING NO.SIZE
USCG APVD: DATE:
SCALE
ABS APVD: DATE:
FSCM CAGE NO.
98042
OF
FSV6-320-01
FSV6-320-01 G
H
1B
1B 39N.T.S.
9B10B11B12B13CB14B15B16B
9B11B12B13B14B15B16B
DESCRIPTIONSHEETREV
REVISIONS
DESCRIPTIONSHEETREV
REVISIONS
DESCRIPTIONREVSHEET
REVISIONS
B 74. REVISED DESTINATION OF S SCP110A-3P AND
SCP110-3S.
75. REVISED DESTINATION (WAS PRESERVATION ALCOVE).
76. ADDED CABLE TYPE TO CKT SCP110A-75 AND
SCP110A-76.
77. DELETED DAMPER ACTUATOR DETAIL 267-B.
78. DELETED AFT DECK CRANE DETAIL.
79. DELETED DETAIL 283-A, 286-A, AND 286-C.
80. DELETED STOREROOM, SCIENTIFIC, AND CONTROLLED
ENVIRONMENT CONDENSING SYSTEM CONTROLLER WIRING
DIAGRAMS.
81. ADDED SHEET 39 PANELS SCP110A-2 & SCP110A-9.
REV B AUTHORIZATION.
ITEM 1-30, 32-75, AND 77-79 & 81 PER DESIGN DEVELOPMENT.
ITEM 31, 76, AND 80 PER ABS TASK 675573 DATED 11-MAR-2011.
C 1. REVISED INDEX SHEET 38 DESCRIPTION.
2. ADDED LASER OPTICAL PLANKTON COUNTER TO CIRCUIT SCP107A-9
3. ADDED CHEM LAB RECEPTACLE STRIP TO CIRCUIT SCP107A-11
4. REVISED DESCRIPTION OF CIRCUITS SCP107B-2, SCP107B-4, SCP107B-5,
SCP107B-8, SCP107B-8, SCP107B-9
5. DELETED CIRCUITS SCP107B-10, SCP107B-11, SCP107B-12, SCP107B-13,
SCP107B-14.
6. REVISED CIRCUIT BREAKER RATING AND DELETED CIRCUIT FROM SCP107B-24
7. DELETED CIRCUIT SCP105A-3
8. REVISED DESTINATION OF CIRCUITS SCP105A-16, SCP105A-17, SCP105A-18,
SCP105A-19, SCP105A-20, SCP105A-21 AND SCP105A-22.
9. REVISED DESTINATION OF CIRCUITS SCP110A-3A, SCP110A-3B, SCP110A-3C,
SCP110A-3D, SCP110A-3G AND SCP110A-3W.
10. DELETED CIRCUIT SCP110A-3M.
11. REVISED DESTINATION OF CIRCUIT SCP110A-4K FROM SPARE, TO WET LAB
RECEPTACLE -DUPLEX WT.
12. REVISED CIRCUITS SCP110A-7L, SCP110A-7N, FROM SPARE TO DRY LAB
RECEPTACLE STRIP.
13. REVISED CIRCUITS SCP110A-7M, SCP110A-7P FROM SPARE TO HYDROGRAPHIC
LAB RECEPTACLE STRIP.
14. REVISED CIRCUITS SCP110A-8A, SCP110A-8B, SCP110A-8C, SCP110A-8E,
SCP110A-8J FROM CHEM LAB RECEPTACLE STRIP TO SPARE.
15. REVISED CIRCUITS SCP110A-8D, SCP110A-8F, SCP110A-8G, SCP110A-8H,
FROM CHEM LAB RECEPTACLE STRIP TO ET SHOP RECEPTACLE STRIP.
16. REVISED CIRCUITS SCP110A-8K, SCP110A-8L, SCP110A-8N, FROM ET SHOP
RECEPTACLE STRIP TO SPARE.
17. REVISED CABLE TYPE OF CIRCUITS 1GP-1A(CONT3), 1GP-1B(CONT3),
1GP-1C(CONT3) AND 1GP-1D(CONT3) FROM LS2SWU-3, TO LS2SWU-7.
18. DELETED CIRCUITS P103-9.
19. ADDED CIRCUITS K-BTMNSB, AND K-MNSB-4SBUV.
20. REVISED CIRCUIT PMCB-1 AND PMCB-1 CABLE TYPE FROM LSMSCS-19 TO
(6)LSFSGU-4.
21. DELETED CIRCUITS P085 AND P095.
22. REVISED CABLE TYPE OF CIRCUITS P055A AND P065A FROM LSTSGU-14 TO
LSTSGU-23.
23. ADDED CIRCUITS P607-2 AND P608-2.
24. REVISED CABLE TYPE OF CIRCUITS P083(HS) AND P093(HS) FROM LSTSGU-9
TO LSFSGU-9.
25. ADDED CIRCUIT K-BTMNSB
26. ADDED CIRCUIT K-MNSB-4SBUV TO 480V SWITCHBOARD.
27. ADDED CIRCUITS K-PC2-35 AND K-PC1-35.
28. DELETED HEATER CIRCUITS P110-2(HTR), P110-3(HTR), P110-4(HTR),
P110-5(HTR), P110-6(HTR), P110-7(HTR), P110-8(HTR), P110-9(HTR),
P110-10(HTR), AND P110-11(HTR).
29. REVISED CONTROLLER TYPE OF CIRCUITS P610-3 AND P610-8 FROM FSS TO
SS.
30. ADDED FIRE DAMPER CIRCUITS P110-2(C1), P110-4(C1), P110-7(C1), AND
P110-8(C1).
31. ADDED FIRE DAMPER CONTROLLERS TO CIRCUITS P120-1(C1), AND
P119-1(C1)
32. DELETED HEATER CIRCUITS P120-1(HTR_, P120-2(HTR), P120-9(HTR),
P119-1(HTR), P119-2(HTR), P119-8(HTR), P119-9(HTR), AND P119-10(HTR),
33. ADDED FIRE DAMPER CONTROL CIRCUIT P119-9(C1).
CONTINUED ZONE 13C-D THIS SHEET.
34. DELETED HEATER CIRCUITS P109-1A(HTR), P109-1D(HTR), P109-1E(HTR),
P109-1F(HTR), P109-1G(HTR), AND P109-1H(HTR).
35. REVISED FIRE DAMPER CIRCUITS P109-1D(C1), P109-1E(C1), P109-1F(C1),
AND P109-1G(C1).
36. ADDED FIRE DAMPER CIRCUITS P109-1B(C), P109-1F(C), AND P109-1H(C).
37. DELETED CIRCUITS P120-4(C2), P620-4(L), AND P619-12.
38. REVISED CIRCUIT P619-13 CIRCUIT BREAKER SIZE FROM 35AT TO 50AT AND
CABLE SIZE FROM LSTSGU-14 TO LSTSGU-50.
39. DELETED CIRCUIT P609-4, TRASH ROOM S09 DUCT HEATER.
40. ADDED CIRCUITS P412-3M AC05 DUCT PREHEATER EOS, AND P412-3N EOS
DUCT HEATER.
41. REVISED CIRCUIT P412-3D FROM UNIT HEATER LOWER LEVEL, TO AC02 EOS
AHU
42. REVISED CIRCUIT P412-3H FROM PAINT LOCKER CONVECTOR TO AC03 DUCT
PREHEATER.
43. DELETED CIRCUIT P111-2E, WAS PRESERVATION ALCOVE FCU 38.
44. ADDED CIRCUIT P111-2N C02 ROOM EXHAUST FAN E17.
45. ADDED CIRCUIIT P111-2P HAZMAT LKR EXH FAN E09
46. ADDED CIRCUIT P111-2M(C2) FOR C02 PRESSURE SWITCH.
47. ADDED CIRCUIT P111-4S MESSROOM FR 30-35P FCU 29
48. ADDED ITEM NUMBER 228, ALLEN BRADLEY CONTACTOR.
49. REVISED CIRCUIT NAME FROM P405-6(HTR) TO P105-6(C4).
50. REVISED CIRCUIT P415-2 FROM SPARE TO WASTE OIL HTR.
51. ADDED DETAIL 298-B, WASTE OIL HEATER.
52. REVISED CIRCUIT P112-1A FROM HEAT LAMPS TO OCEANOGRAPHIC WINCH ROOM
FAN (S15)
53. REVISED CIRCUIT P112-1B FROM HEAT LAMPS TO OCEANOGRAPHIC WINCH ROOM
FAN (S16)
54. REVISED CIRCUIT P111-4T FROM SPARE TO FORWARD MAST WINCH RECEPTACLE.
55. ADDED ITEMS 229 AUTOMATIC POWER SELECT SWITCH, 230 JUNCTION BOX, AND
231 POWER DISTRIBUTION BLOCK.
56. DELETED RECEPTACLE FROM CIRCUIT P414
57. ADDED CIRCUIT C-AM-1003
58. DELETED CIRCUITS P600/EMERCONTROL, EG(CONT 1), EG(CONT 2).
59. REVISED CIRCUIT NAME FROM EP125 TO EP127
60. REVISED CIRCUIT NAME FROM EP127 TO EP129
61. REVESED NAME OF POWER PANEL EP100.
62. REVISED NAME OF POWER PANEL EP24.
63. ADDED CIRCUIT C-AM-4021
64. ADDED CIRCUIT C-AM-3019
65. REVISED CABLE TYPE OF CIRCUIT EP410(C2) FROM LSMSCU-7 TO LSMSCU-10.
66. REVISED CABLE TYPE OF CIRCUIT EP100-3 FROM LSTSGU-50 TO LSTSGU-400.
67. REVISED CIRCUIT EP405 DESIGNATION FROM ELECTRIC WHISTLE TO SPARE.
68. REVISED CIRCUIT EP413 DESTINATION FROM SUBMERSIBLE PUMP TO SPARE.
69. ADDED CIRCUITS EP129-4, EP129-5, EP129-6, EP129-7, (2) 12VDC
BATTERY'S, AND BATTERY SELECT SWITCH.
70. REVISED CIRCUIT NAME FROM CAM-500-109 TO C-AM-7011.
71. REVISED CIRCUIT NAME FROM CAM 500-18 TOC-AM-2014
72. ADDED CIRCUIT C-AM-2003
73. REVISED CIRCUIT NAME FROM C-AM-500-31 TO C-AM-3014
74. REVISED CIRCUIT NAME FROM C-AM-500-6 TO C-AM-1004
75. DELETED CIRCUIT C-AM-19
76. REVISED CIRCUIT NAME FROM CAM 500-31 TO C-AM-7021
77. REVISED CIRCUIT NAME FROM C-AM-500-142 TO C-AM-2004
78. ADDED CIRCUIT C-AM-3015, C-AM-3012, C-AM-3016, C-AM-3013.
79. DELETE NOTE
80. ADDED CIRCUIT C-AM-8004
81. ADDED CIRCUIT C-AM-3020
82. DELETED CIRCUIT P614-8(B), ANCHORWINDLASS BRAKE
83. REVISED DUCT HEATER FROM 8KW TO 26KW, REVISED CABLE TYPE FROM
LSTSGU-4 TO LSTSGU-9
84. ADDED CIRCUIT P120-1(C2) FOR C02 PRESSURE SWITCH
85. ADDED CIRCUIT P119-1(C2) FOR C02 PRESSURE SWITCH
86. ADDED CIRCUIT DESIGNATION C-AM-4016
87. REVISED CIRCUIT DESTINATION FROM SPARE TO SX93 HULLUNIT
88. ADDED CIRCUIT DESIGNATION C-AM-4017
89. REVISED CIRCUIT P415-7 DESTINATION FROM WET LAB MONORAIL HOIST TO
SPARE
90. REVISED CIRCUIT P415-9 DESTINATION FROM CONTROLLED ENVIRONMENT
CONDENSING SYSTEM CONTROLLER TO SPARE
91. REVISED CIRCUIT P420-5 DESTINATION FROM ELECTRIC GRIDDLE TO
DISHWASHER.
C17
CONTINUED ZONE 16C-D THIS SHEET.
92. REVISED CIRCUIT P420-2 DESTINATION FROM SPARE TO SANITIZING SINK
HEATER
93. REVISED CIRCUIT P222-7 DESTINATION FROM SPARE TO FREQ CONVERTER
#1
94. REVISED CIRCUIT P222-9 DESTINATION FROM SPARE TO PENTAGON MASTER
CONTROL CABINET HEATER
95. REVISED CIRCUIT P222-8 DESTINATION FROM SPARE TO FREQ CONVERTER
#2
96. REVISED CIRCUIT P222-10 DESTINATION FROM SPARE TO FREQ CONVERTER
#2
97. REVISED CIRCUIT P222-16 DESTINATION FROM SPARE TO ANTI FOULING BT
UNIT CTRL PNL
98. ADDED SYMBLE AND ITEM NUMBER CALLOUT TO CIRCUIT EP404-9 AND
EP404-8
99. DELETED ABT FROM CIRCUIT EP128-2
100. DELETED JUNCTION BOX FROM CIRCUIT EP128-8
101. DELETED JUNCTION BOX AND BRANCH CIRCUITS FROM CIRCUIT EP128-12
102. REVISED CIRCUIT EP128-19 DESTINATION FROM SPARE TO SHIPS WHISTLE
103. REVISED CIRCUIT SCP104A DESTINATION FROM SPARE TO ITI BATTERY
CHARGER
104. REVISED DESTINATION OF CIRCUIT SCP107A-15 FROM SPARE TO PILOT
HOUSE RECEPTACLES
105. REVISED DESTINATION OF CIRCUIT SCP107A-16 FROM SPARE TO 04 LEVEL
WEATHER RECEPTACLES
106. REVISED DESTINATION OF CIRCUIT SCP111A-9 FROM FISH FINDING SYSTEM
TO SPARE
107. REVISED DESTINATION OF CIRCUIT SCP111A-10 FROM SCIENTIFIC
COMPUTER SYTEM #1 TO SPARE
108. REVISED DESTINATION OF CIRCUIT SCP111A-12 FROM SCIENTIFIC
COMPUTER SYSTEM #2 TO SPARE
109. REVISED DESTINATION OF CIRCUIT SCP110A-1F FROM DP WIND SENSOR
BATT CHG TO SPARE
110. REVISED DESTINATION OF CIRCUIT SCP110A-12 FROM GPS PWR SUPPLY
TO SPARE
111. REVISED DESTINATION OF CIRCUIT SCP110A-3N FROM 18 KHZ GPT TO
SPARE
112. REVISED DESTINATION OF CIRCUIT SCP110A-3P FROM 38 KHZ GPT TO
SPARE
113. REVISED DESTINATION OF CIRCUIT SCP110A-3R FROM 120 KHZ GPT TO
SPARE
114. REVISED DESTINATION OF CIRCUIT SCP110A-3S FROM 200 KHZ GPT TO
SPARE
115. REVISED DESTINATION OF CIRCUIT SCP110A-7S FROM WATER COLUMN
PROFILER TO CTD DECK UNIT.
116. REVISED DESTINATION OF CIRCUIT SCP110A-2H FROM SPARE TO SX90
TRANSCEIVER
117. REVISED DESTINATION OF CIRCUIT P610-1 FROM AC04 DUCT HEATER TO
SPARE.
118. REVISED DESTINATION OF CIRCUIT P619-16 FROM AC01 AC AHU TO SPARE
119. ADDED CIRCUIT P119-10(C1) CO2 PRESSURE SWITCH
120. REVISED DESTINATION OF CIRCUIT P609-1B FROM AC04 LAB AREA AC AHU
TO SPARE
121. REVISED DESTINATION OF CIRCUIT P609-7 FROM AC04 PREHEATER TO AIR
HANDLING UNIT AC04
122. REVISED DESTINATION OF CIRCUIT P609-8 FROM AC01 DUCT PREHEATER
01 LEVEL FAN ROOM TO AIR HANDLING UNIT AC01
123. ADDED MMC PART NUMBER TO ITEM NUMBER 88
124. DELETED ITEM NUMBERS 111 AND 113
125. REVISED QTY OF ITEM 108 FROM 24 TO 28
126. REVISED QTY OF ITEM 102 FROM 6 TO 8
127. ADDED ITEM NUMBER 232 (PUSHBUTTON), 233 "START NAMEPLATE", 234
"STOP NAME PLATE", 235 "LIGHT", AND 236 "30A DUAL BATTERY
CHARGER"
128. REVISE QTY OF ITEM 118 FROM 3 TO 5
129. ADDED SHEET 4A AND ITEM NUMBERS 237 AND 238.
130. DELETED CIRCUITS P089 AND P099
131. REVISED DESTINATION OF CKT P625 FROM SPARE TO TRAWL HPU
132. ADDED START STOP PUSH BUTTONS TO AND CIRCUITS EP412(C1) AND
EP412(C2).
133. REVISED FIND NUMBER OF BATTER CHARGER FROM 165 TO 236.
C25
4A
CONTINUED ZONE 9D-D SHEET 1D.
C
D
A
B
C
DRAWING NO. SH REV
D
A
D
REVDRAWING NO.SIZE
USCG APVD: DATE:
SCALE
ABS APVD: DATE:
FSCM CAGE NO.
98042
OF
FSV6-320-01
FSV6-320-01 G
H
1C
1C 39N.T.S.
9C10C11C12C13C14C15C16C
9C11C12C13C14C15C16C
DESCRIPTIONSHEETREV
REVISIONS
DESCRIPTIONSHEETREV
REVISIONS
DESCRIPTIONREV
REVISIONS
C134. REVISED DESTINATION OF CKT CP24-5 FROM 600VAC SWBD BUS A&B CONTROL
POWER TO WATERTIGHT DOORS CTRL CABINET (1)
135. REVISED DESTINATION OF CKT CP24-6 FROM TACHTROL 30 SHAFT RPM TO
EMERGENCY GENERATOR
136. REVISED DESTINATION OF CKT CP24-8 FROM WATERTIGHT DOORS TO WATERTIGHT
DOORS CTRL CABINET (2)
137. REVISED DESTINATION OF CKT CP24-10 FROM 600VAC WBD BUS C&D CONTROL
POWER TO SPARE
138. REVISED DESTINATION OF CKT P604-7 FROM FISH MACERATOR TO SPARE
139. DELETED CIRCUITS CAM 500-109 AND CAM 500-18
140. DELETED CIRCUIT P2407-11H
141. REVISED DESTINATINO OF CKT P614-4 FROM AFT DECK CRANE SKID TO SPARE
142. REVISED DESTINATION OF CKT P614-7 FROM AFT A FRAME HPU TO SPARE
143. REVISED CONTROLER TYPE OF CIRCUITS P610-2 AND P610-4 FROM HOA TO
FSS
144. REVISED DESTINATION OF CIRCUITS P112-1F AND P112-1G FROM SPARE TO
SH&T HEAT LAMPS
145. REVISED DESTINATION OF CKT P419-1 FROM RESCUE BOAT BATTERY CHARGER
TO SPARE
146. REVISED DESTINATION OF CKT P419-3 FROM 910KW GEN NO 3 JACKET WATER
HTRS TO SPARE
147. REVISED DESTINATION OF CKT P419-5 FROM GEN NO 2 JACKET WATER HTRS TO
SPARE
148. REVISED DESTINATION OF CKT P419-6 FROM GEN NO 4 JACKET WATER HTRS TO
SPARE
149. REVISED DESTINATION OF CKT P419-8 FROM GEN NO 1 JACKET WATER HTRS TO
SPARE
150. REVISED DESTINATION OF CKT P419-12 FROM SPARE TO WORK BOAT DAVIT HPU
151. REVISED DESTINATION OF CKT P103-9 FROM A/C UNIT #2 TO SPARE
152. REVISED DESTINATION OF CKT P103-12 FROM A/C UNIT #1 TO SPARE
153. ADDED CIRCUITS K-PC2-35 (STBD PRPLN MOTOR #2) AND K-PC1-35 (STBD
PRPLN MOTOR #1)
154. REVISED DESTINATINO OF CKTS P415-4, P415-5, P415-11, AND P415-12
FROM SPARE TO JACKET WATER HEATERS.
155. REVISED DESTINATION OF CKT P415-5 FROM SPARE TO OILY WATER SEPERATOR.
156. REVISED DESTINATION OF CKT P420-11 FROM GARBAGE GRINDER TO SPARE.
157. ADDED TRANSFORMER FIND NUMBER 238 TO CKT P120-1A
158. ADDED TRANSFORMER, FIND NUMBER 237, TO CKTS P120-1E AND P120-1F
159. REVISED DESTINATION OF CIRCUIT EP122-A1 FROM DAU#2 TO SPARE
160. REVISED DESTINATION OF CIRCUIT EP122-A7 FROM DAU#1 TO SPARE
161. REVISED DESTINATION OF CIRCUIT EP122-A9 FROM DAU#3 TO SPARE
162. REVISED DESTINATION OF CIRCUIT EP122-A11 FROM DAU#5 TO SPARE
163. REVISED DESTINATION OF CIRCUIT EP122-A13 FROM DAU#7 TO SPARE
164. REVISED DESTINATION OF CIRCUIT EP122-A8 FROM DAU#4 TO SPARE
165. REVISED DESTINATION OF CIRCUIT EP122-A10 FROM DAU#6 TO SPARE
166. REVISED DESTINATION OF CIRCUIT EP122-A12 FROMDAU#8 TO SPARE
167. DELETED CKT CAM 500-176
168. DELETED JUNCTION BOX AND BRANCH CIRCUITS FROM CKT EP128-3
169. REVISED CKT EP128-3 CABLE TYPE FROM LSDSGU-4 TO LSDSGU-9 AND
CIRCUIT BREAKER RATING FROM 15AT TO 30AT
170. REVISED DESTINATION OF CKT SCP107A-8 FROM SCIENTIFIC SEAWATER TO
SCIENTIFIC SEAWATER THERMOSALINOGRAPH.
171. REVISED CKTS SCP110A-2 AND SCP110A-9 CIRCUIT BREAKER RATING FROM
50AT TO 100AT, AND REVISED CABLE SIZE FROM LSTSGU-23 TO LSTSGU-75.
172. REVISED CABLE TYPE FROM LSTSGU-23 TO LSTSGU-75 OF CKTS SCP110A-2
AND SCP110A-9
173. ADDED SHEET 1C
174. ADDED CABLE TYPE LSDSGU-4 TO CKT P103-16
175. ADDED SHAFT BRAKE INTERLOCK CIRCUIT K-PC(1-2)-35.
176. ADDED GENERAL NOTE 27.
1C
SHEET
REV C AUTHORIZATION.
ITEM 1-174 PER DESIGN DEVELOPMENT.
APVDDATE
12/03/12 TT
C
D 1. ADDED ITEM #239, 5KVA TRANSFORMER
2. ADDED LATHE TRANSFORMER, ITEM #239.
3. ADDED SIDE SAMPLING STATION RECEPTACLE AND CKT EP404-7
4. REVISED QTY OF FIND# 195 FROM 2 TO 3
5. REVISED CKTS SCP110A-1E FROM SM2000 MULTIBEAM ECHO SOUNDER
TO SPARE
6. REVISED CKTS SCP110A-1L FROM WINCH REMOTE CONTROLS 24VDC
POWER SUPPLY TO SPARE
7. REVISED CKT SCP110A-1H FROM SCIENTIFIC DGPS TO SPARE.
8. REVISED CKT SCP110A-1K FROM NETWORK SWITCH TO SPARE
9. REVISED CKT SCP110A-1S FROM NETWORK SWITCH TO SPARE
10. REVISED CKT SCP110A-3U FROM ETHERNET SWITCH TO SPARE
11. REVISED CKT SCP110A-4L FROM SPARE TO FUME HOOD WET LAB
12. REVISED CKT SCP110A-4L FROM SPARE TO FUME HOOD CHEM LAB
4A
REV D AUTHORIZATION.
ITEM 1-12 PER DESIGN DEVELOPMENT.
E 1. REVISED CKT SCP111A-18 FROM SPARE TO CCT POWER SUPPLY
2. REVISED CKT SCP107A-11 FROM CHEM LAB RECEPTACLE STRIP TO
SPARE.
3. ADDED CKT BATT-4.3UPS, AND UPS DC BATTERY CABINET
4. ADDED FIND NUMBER 241 TO 18KVA UPS DC BATTERY CABINET
5. ADDED ITEM NUMBERS 240 THRU 242 TO EQUIPMENT LIST.
6. REVISED DESCRIPTION OF TRANSFORMER AND TRANSFORMER IRON CORE
WITH ELECTROSTATIC SHIELD
7. DELETED CKT CP24-10
8. DELETED CKT CP24-5
9. REVISED CKTS WAS P419-3 AND P419-3A, IS P415-11 AND P41511A.
10. REVISED CKTS WAS P419-8 AND P419-8A, IS P415-4 AND P415-4A.
11. REVISED CKTS WAS P419-5 AND P419-5A, IS P415-5 AND P415-5A.
12. REVISED CKTS WAS P419-6 AND P419-6A, IS P415-12 AND
P415-12A.
13. REVISED XFMR P602, P601, P422, AND P403 DESCRIPTION FROM XFMR
TO ISLN XFMR AND REVISED SYMBOL
14. ADDED ITEM NUMBERS 244 AND 245.
15. REVISED CKT SCP108A MOVED CKT DESTINATION TO SHEET 39
16. ADDED DISTRIBUTION PANEL SCP108A
17. REVISED XFMR EP400-2 AND EP400-1 DESCRIPTION FROM XFMR TO
ISLN XFMR AND REVISED XFMR SYMBOL
18. REVISED DESCRIPTION OF PHASE SHIFTING XFMR
19. REVISED SYMBOL OF XFMR P617, SCP111-1, AND SCP110-1.
20. REVISED DESCRIPTION OF WINCH POWER PANELS P415-A AND P415-B
21. REVISED MOTOR HP RATING OF GALLEY FAN E04, DIVER LOCKER FAN
S10, GALLEY FAN S12, TRANSDUCER RM SUPPLY FAN S08, 2ND/MAIN
DK FWD FAN S11.
22. REVISED LOAD RATING OF DUCT HEATERS DH-15, DH-10, DH-01,
DH-11, DH14, AND DH-04.
23. REVISED MOTOR HP RATING OF WET LAB SCI READY ROOM FAN E08,
TRASH RM EXH FAN E15, EMER. GEN RM/DECK LKR FAN E03,
SCIENTIFIC STORES SUPPLY FAN S01.
24. REVISED LOAD RATING OF DUCT HEATERS DH-5, DH-6, AND DH-12.
25. REVISED LOAD RATING OF AIR HANDLING UNIT AC01.
26. REVISED CIRCUIT BREAKER RATING FOR CIRCUITS P609-2G, P609-3,
AND P609-5.
27. REVISED SUPPLY FAN S14 MOTOR FROM SINGLE SPEED TO 2 SPEED.
28. REVISED CABLE SIZE OF CKT P609-5 FROM LSTSGU-9 TO LSTSGU-23.
29. REVISED CIRCUIT BREAKER RATING FOR CIRCUITS P610-14, P616-1,
P616-3, P616-6.
30. REVISED SYMBOL OF HVAC XFMR P412-1, P412-2, P411-1, P411-2,
P411-3, AND P411-4.
31. REVISED LOAD RATING OF CKTS P412-4, P412-8, P412-10, P412-3J,
P412-3D, P412-3H, P412-3K, P412-3M, P411-5, P411-6, P411-8, P411-10.
32. REVISED LOAD RATING OF CKTS P112-1C, AND P112-1E.
33. REVISED CKT BREAKER RATING OF CKTS P112-1E
4A
E 34. REVISED LOAD RATING OF CKTS P111-1E, P111-1G, P111-1D,
P111-2L, P111-2N, AND P111-2P.
35. REVISED DESCRIPTION OF CIRCUITS P111-3G, AND P111-3D.
36. REVISED MOTOR LOAD RADING OF CKTS P111-4R AND P111-4N
37. REVISED SYMBOL OF XFMR P120-1E, P120-1A, P120-1F, AND
P420-1.
38. REVISED DESCRIPTION OF XFMR P120-1A, P120-1E, AND P120-1F.
39. REVISED DESTINATION OF CKT EP122
40. REVISED DESTINATION OF CKT SCP104A-12
41. REVISED REF OF CKT SCP103A-16
42. REVISED VOLTAGE RATING OF PANEL SCP110A
43. REVISED SHEET DESCRIPTION
44. REVISED VOLTAGE RATING OF POWER PANELS SCP111A AND
SCP110A-1
45. REVISED SHEET DESCRIPTION
46. REVISED VOLTAGE RATING OF POWER PANEL SCP110A-3
47. REVISED SHEET DESCRIPTION
48. REVISED VOLTAGE RATING OF POWER PANELS SCP110A-4 AND
SCP110A-5
49. REVISED VOLTAGE RATING OF POWER PANELS SCP110A-6, AND
SCP110A-7
50. REVISED VOLTAGE RATING OF POWER PANEL SCP110A-8.
51. REVISED SHEET DESCRIPTION
52. REVISED VOLTAGE RATING OF POWER PANELS SCP110A-2, AND
SCP110A-9
53. REVISED DESCRIPTION OF ITEM NO. 118
54. ADDED ITEM NO. 246
55. REVISED DESCRIPTION OF CKT P604-5
56. REVISED BREAKER RATING OF CKTS P608-7, P608-8, P608-9,
P607-7 P607-8, P607-9.
57. REVISED CTRL TYPE OF CKT P608-9 FROM SS TO HOA
58. ADDED CKTS P108-3(C1), P108-4(C1), P107-3(C2) P107-4(C1)
59. ADDED UV SYMBOL TO CKT P614-8.
60. DELETED "REF 19" CKT FROM ATS.
61. REVISED CKT EP404-7 CABLE TYPE FROM LSTSGU-4 TO LSTSGU-9.
62. REVISED CKT EP122-A3 FROM CHIEF ENG'R NO.1 UPS TO SPARE
63. REVISED CKT EP122-A5 FRM CHIEF ENG'R NO 2 UPS TO SPARE.
64. REVISED CKT EP122-A15 FROM MCC AMS/PWR SUPPLY TO SPARE
65. REVISED CKT EP122-A18 FROM DEPTH SOUNDER DISPLAY TO SPARE
66. REVISED CKT EP122-A20 FROM BILGE VLV CONT (MCC) TO SPARE
67. REVISED LOCATION OF DUCT HEATER DH-04.
68. REVISED CKT P420-3 FROM STEAMER TO SPARE
69. REVISED CKT P420-9 FROM STEAM KETTLE TO SPARE
70. REVISED CKT P222-18 FROM SPARE TO STEAM KETTLE
71. REVISED CKT P222-22 FROM BLANK TO STEAMER.
72. REVISED CABLE TYPE OF CKT K-MNSB-4SBUV
73. REVISED CKT P418 MOTOR LOAD RATING
74. REVISED CKT P414 LOCATION
75. ADDED CKT P413(C1)
76. REVISED CKT P413 MOTOR LOAD RATING
77. REVISED KW RATING OF CKT P417
78. REVISED KW RATING OF CKTS EP410, EP408, EP407, EP415.,
EP121, EP129
79. REVISED CKT EP411 FROM DIVERS AIR COMPRESSOR TO SPARE.
80. DELETED CKT EP24-4
81. REVISED XFMR SCP110-1 LOCATION
82. REVISED KW RATING FOR CKTS P604-1, P604-2, P604-5, P604-2,
P604-4, P604-6, P604-10, P603-4, P603-5, P603-6.
83. REVISED KW RATING FOR CKTS P608-2, P608-4, P607-2, P607-3,
P607-4, P607-11.
84. DELETED CKTS P108-3(C), P108-4(C), P107-3(C), P107-4(C).
P108-4(C), P107-3(C1), P107-3(C1)
85. REVISED LOAD RATING FOR VARIOUS CKTS
86. REVISED NOMENCLATURE OF PANELS P415-A AND P415-B
87. REVISED LOAD RATING OF P614-5.
88. REVISED LOAD RATING OF P616-5 AND P616-4
89. REVISED CKT BREAKER RATING OF P609-3
90. ADDED KW RATING TO P412-7
91. REVISED LOAD RATING OF VARIOUS CKTS ON PNL P103
92. REVISED CKT P103-3, AND P103-7 BREAKER RATING.
93. REVISED NOMENCLATURE OF CKT P103-17, P103-4, P103-8.
94. REVISED VARIOUS LOAD RATINGS ON PNL P415 AND P415-1
95. REVISED BREAKER SIZE OF CKTS P415-3, P415-4, P415-8,
P415-10, P415-11, AND P415-12.
4A
CONTINUED ZN 16C-D, THIS SHEET
CONTINUED ZN 11D-D, SHEET 1D
C
D
A
B
C
DRAWING NO. SH REV
D
A
D
REVDRAWING NO.SIZE
USCG APVD: DATE:
SCALE
ABS APVD: DATE:
FSCM CAGE NO.
98042
OF
FSV6-320-01
FSV6-320-01 G
H
1D
1D 39N.T.S.
9D10D11D12D13D14D15D16D
9D11D12D13D14D15D16D
DESCRIPTIONSHEETREV
REVISIONS
DESCRIPTIONSHEETREV
REVISIONS
DESCRIPTIONREV
REVISIONS
96. ADDED SHEET 1D
97. REVISED CABLE TYPE OF CKTS P415-8 AND P415-10
98. REVISED CKT BREAKER SIZE AND NEMENCLATURE OF CKTS P222-7, P222-8,
P222-10
99. ADDED LOAD KW RATING TO VARIOUS CKTS
100. REVISED CKT EP404-7 FROM SIDE SAMPLIN STATION RECEPTACLE TO SPARE
101. REVISED CKT EP404-9 FROM SUMP PUMP RCPT TO SPARE
102. REVISED CKT EP404-8 FROM ISO VAN SITE RCPT TO SPARE
103. REVISED CKT EP122-A16 FROM MCC PWR SUPPLY TO MCC ETHERNET PWR
SUPPLY
104. REVISED CKT SCP111A-7 FROM MOBILE EARTH STATION TO INMARSAT C FURUNO
FALCOM 15
105. REVISED CKT SCP110A-1A FROM SCIENTIFIC METEOROLOGICAL SYSTEM TO WIND
TRACKER SYSTEM
106. ADDED 4 BLANKS TO PANEL EP100
107. REVISED CABLE TYPE OF CKT CP24-5
108. ADDED CKT P614-15 AND BLANK SPACE TO PANEL P614
109. REVISED CKT P614-2 FROM SPARE TO BLANK
110. REVISED CTRL TYPE OF CKTS P610-2, P610-6, P610-8.
111. REVISED CKT OF EOS DUCT HEATER (DH-03) FROM P412-3N TO P412-3L
112. REVISED CKTS P112-1F AND P112-1G FROM SH&t HEAT LAMPS TO SPARE.
113. REVISED CKT P112-2D FROM SH&T HEAT LAMPS TO SPARE
114. REVISED CKT BREAK RATING OF CKT P112-2S FROM 20AT TO 15AT.
115. ADDED 2 BLANK PANEL LOCATIONS TO PANEL P111-2
116. REMOVED 2 BLANK PANEL LOCATIONS FROM PANEL P412
117. REVISED DESCRIPTION OF CKT P111-4T.
118. REVISED CABLE TYPE AND CKT BREAKER RATING OF CKTS P111-3N, P111-3M,
P111-3P, P111-3S, P111-3A
119. REVISED BREAKER RATING OF CKT P416-9 FROM 10AT TO 15AT.
120. REVISED CKT P416-3 FROM SCIENTIFIC VACUUM PMP TO SPARE
121. ADDED CKTS P419-15, AND P419-16.
122. REMOVED 5 BLANKS FROM PANEL P406
123. REMOVED 1 BLANK FROM PANEL P405
124. REVISED CABLE TYPE OF CKTS P415-4, P415-5, P415-11, AND P415-12
FROM LSDSGU-9 TO LSTSGU-4
125. REVISED CKT P120-1V BREAKER SIZE FROM 15AT TO 20AT
126. REVISED BREAKER SIZE OF CKT P222-13 FROM 15AT 2P TO 20AT 1P.
127. REVISED BREAKER SIZE OF CKT P222-14 FROM 1P TO 2P
128. REVISED CKT P222-16 FROM ANTI FOULING BT UNIT CTRL PNL TO SPARE
129. REVISED CKT P222-20 FROM SPARE TO ANTI FOULING BT UNIT CTRL PNL PORT.
130. REVISED DESCRIPTION OF CKT P222-14
131. DELETED 3 BLANKS FROM PNL SCP104A.
132. REVISED CKT SCP104A-28 BREAKER SIZE FROM 1P TO 2P
133. ADDED BLANK TO PANEL SCP107B
134. DELETED 12 BLANK LOCATIONS FROM PANEL SCP103A
135. DELETED 2 BLANK LOCATIONS FROM PANEL SCP106A
136. ADDED 6 BLANK LOCATIONS TO PANEL SCP111A
137. ADDED 2 BLANK LOCATIONS TO PANEL SCP110A-1
138. ADDED 2 BLANK LOCATIONS TO PANEL SCP110A-3
139. ADDED 6 BLANK LOCATIONS TO PANEL SCP110A-4
140. ADDED 4 BLANK LOCATIONS TO PANEL SCP110A-5
141. ADDED 6 BLANK LOCATIONS TO PANEL SCP110A-6
142. ADDED 4 BLANK LOCATIONS TO PANEL SCP110A-7
143. ADDED 2 BLANK LOCATIONS TO PANEL SCP110A-2
144. ADDED 2 BLANK LOCATIONS TO PANEL SCP110A-9
145. REVISED LOCATION OF XFMR SCP110-1
146. ADDED KW RATING TO CKT P103-2 AND P103-5.
147. ADDED KW RATING TO CKT P103-6, P123F-13, AND P123F-15.
148. ADDED KW RATING TO CKT EP416, EP123, EP417, EG(HTR).
149. REVISED CKT P608-4(L), AND P607-4(L), BREAKER RATING FROM 15AT TO
50AT, AND CABLE TYPE FROM LSTSGU-4 TO LSTSGU-14.
150. ADDED KW RATINGS TO PANEL P415-A, AND P415-B.
151. REVISED MOTOR RATING OF CKTS P614-9, AND P614-10.
152. ADDED KW RATINGS TO CKTS P112-1H AND P112-1J.
153. ADDED KW RATING TO CKT P111-2G
154. ADDED KW RATING TO CKTS P111-3F, AND P111-3J.
155. REVISED CKT P111-4T CIRCUIT BREAKER RATING
156. ADDED KW RATING TO CKTS P419-4, P103-15, P103-14, P416-4, P416-7,
P416-8, P416-9, AND P416-10.
157. REVISED CKT P103-9 FROM SPARE TO GEN S.W. CUTOUT VALVES CONTROL.
158. ADDED KW RATING TO PANELS P406, P405, AND P415.
159. REVISED KW RATING OF CKT P415-3.
160. ADDED KW RATINGS TO CKTS P420-5, P420-2, P420-6, P120-1A, P120-1C,
P120-1L, P120-1T, P222-1, P222-3, P222-5, P222-9, P222-11, P222-2, P222-6, P222-12, P222-14, P222-18, P222-20, AND P222-22.
161. REVISED KW RATING OF CKT P420-6, AND P222-12.
SHEET APVDDATE
E162. ADDED KW RATING TO CKTS EP122-A2, EP122-A4, EP128-1,
EP128-3, EP128-5, EP128-13, EP128-15, EP128-17, EP128-19,
EP128-20, EP128-18, EP128-14, AND EP128-2.
163. ADDED KW RATING TO CKTS SCP104A-11, SCP104A-13, AND
SCP104A-15.
164. ADDED KW RATINGS TO CKTS SCP107A-9, AND SCP107A-8.
165. ADDED KW RATINGS TO CKTS SCP105A-23, SCP105A-24, SCP103A-11,
SCP103A-13.
166. REVISED CKTS ON PANEL SCP106A FROM STATEROOMS TO STATEROOM
RCPT'S.
167. REVISED CKT CP24-15 FROM ALARM PANEL TO STEERING ALARM PANEL
168. REVISED LOCATION OF XFMR P623 FROM ENG STOREROOM TO AMR
169. REVISED CKT SCP104A-11 FROM NET SOUNDER BATTERY CHARGER TO
SPARE
170. REVISED LOCATION OF XFMR P623 FROM ENG STORE TO AMR
171. REVISED SYMBOL OF NODE XFMR P411-6, P411-10, P411-11,
P411-12 FROM ISOLATION TO IRON CORE WITH ELECTROSTATIC SHIELD,
ISOLATION.
172. REVISED WORDING OF GENERAL NOTE 24.
173. ADDED REMARKS TO ITEM NUMBERS
5,6,10,11,14,15,16,17,18,19,20,21,AND 22
174. REVISED MMC PART NUMBER OF ITEM NUMBERS 10 AND 11.
175. REVISED QTY OF ITEM NUMBERS 89,91.
176. REVISED DESCRIPTION OF ITEM NO. 102.
177. DELETED REMARK FROM ITEM NO. 112
178. REVISED AMP RATING, AND ADDED REMARK TO ITEM NO. 163.
179. REVISED ITEM NO. 180 AND 183 REMARKS
180. REVISED PART NO. AND ADDED REMARKS TO ITEM NO. 211 AND 222.
181. ADDED REMARKS AND SYMBOL TO ITEM NO. 229.
182. REVISED DESCRIPTION AND MANUFACTURER OF ITEM NO. 226.
183. REVISED DESCRIPTION OF ITEM NO. 184.
184. REVISED DESCRIPTION, SPEC NO., MANUFACTURER, AND PART NO., OF
ITEM NO. 244 AND 245
185. ADDED ITEM NO 247.
186. DELETED CKTS P415-11A, P415-4A, P415-5A, P415-12A.
187. REVISED CABLE TYPE OF CKTS P415-11 P415-4, P415-5, P415-12
FROM LSDSGU-9 TO LSTSGU-4.
188. REVISED ITEM NO. OF CKT EP416-1 BATTERY CABINET, EP24-2
BATTERY SELECTOR SWITCH, EP417-1 BATTERY CABINET, EP129-4
BATTERY SELECT SWITCH.
189. ADDED AMP RATINGS TO PANEL EP24
190. REVISED DESCRIPTION OF ITEM NO 229.
191. REVISED DETAIL CALLOUT OF CKT EG(C02PS) FROM 283-A TO 283-B.
192. REVISED QTY OF PART NO. 232 FROM 4 TO 2.
193. REVISED CKT BREAKER RATING OF SCP108.
194. REVISED CABLE TYPE AND DESCRIPTION OF CKT SCP108A.
195. REVISED DESCRIPTION OF CKTS SCP110A AND SCP111A.
196. REVISED CKT BREAKER POLE RATING OF SCP111-1
197. REVISED KW RATING OF CKT P608-3(L)
198. REVISED CKT BREAKER SIZE OF CKT P610-14 FROM 15AT TO 35AT
199. REVISED CKT BREAKER SIZE OF CKT P609-5 FROM 30AT TO 50AT
200. REVISED CKT BREAKER SIZE FO CKT P609-8 FROM 60AT TO 20AT
201. REVISED CKT BREAKER RATING OF CKTS P412-9, P412-3A, P412-3E,
P411-7, AND P411-10.
202. REVISED CKT BREAKER RATING OF CKTS P112-2A, P112-2B,
P112-2C, P112-2H, AND P112-2L.
203. REVISED CKT BREAKER RATING OF CKTS P111-1F, AND P111-2C.
204. REVISED CKT BREAKER RATING OF CKTS P111-3A, P111-3M,
P111-3N, P111-3P P111-3S, P111-4A, P111-4F, P111-4N, P111-4R.
205. REVISED CKT BREAKER RATING OF CKTS P419-4, P103-6, AND
P416-10.
206. REVISED CKT BREAKER RATING OF CKTS P415-3, P415-4, P415-8,
P415-10, P415-11, AND P415-12.
207. DELETED CKTS P415-4(A), P415-5(A), P415-11(A), AND P415-12(A).
208. REVISED CABLE TYPE OF CKTS P415-4, P415-5, P415-11, AND
P415-12.
209. REVISED DESCRIPTION OF ITEM NO. 239, LATHE XFMR.
210. ADDED KW RATING TO CKT P415-10.
211. REVISED C.B. RATING OF CKTS P420-8, P120-1U, P222-12.
212. REVISED KW RATING OF CKTS P222-18, P222-17.
213. REVISED DESCRIPTION OF CKT P222-5.
214. REVISED SYMBOL OF CKTS EP404-1, EP404-2, EP404-3, EP404-4,
AND EP404-5.
215. REVISED C.B. RATING OF CKTS EP122-A2, EP122-A4, EP128-2,
EP128-8, EP128-15, EP128-17, EP128-19.
4A
CONTINUED ZN 14D-D, THIS SHEET
8/13/13 CE
SHEETREV
E
CONTINUED ZN 14D-D, THIS SHEET
216. REVISED CABLE TYPE AND KW RATING OF CKT
EP128-8.
217. REVISED DESCRIPTION OF CKT EP128-3, EP128-6,
EP128-4, EP128-7, EP122-A19, AND EP128-9.
218. REVISED DESCRIPTION OF CKT SCP104A-15
219. REVISED GENERAL NOTE
220. REVISED NOTE
221. REVISED CKT SCP111A-13 DESCRIPTION
222. REVISED NOTE
223. REVISED DESCRIPTION OF CKT SCP110A-3J
224. REVISED GENERAL NOTE
E
REV E AUTHORIZATION.
ITEM 1-224 PER DESIGN DEVELOPMENT.
APVDDATE
8/13/13 DK
1. REVISED CKT NAME FROM EP416-1 TO EP24-5
2. REVISED CKT NAME FROM EP417-1 TO EP24-4
3. REVISED PANEL NAME FROM EP24 TO CP24
4. DELETED CKT P120-1(C2), P119-1(C3),
P119-2(C2), P119-2(C2), p119-10(C1).
5. DELETED DETAIL 283-B
6. REVISED CKT CP24-6 FROM SPARE TO EMER SWBD
7. REVISED CKT CP24-9 FROM SPARE TO AUTOPILOT
8. REVISED CKT CP24-5 FROM SATERTIGHT DOORS
CTRL CABINET TO SPARE
9. ADDED CKTS P125-HPU-E-STOP, AND
P125-HPU-E-STOP(1)
10. REVISED CKT EG(C02PS) FROM C02 PRESSURE
SWITCH OR C02 CONT PANEL.
11. ADDED 4 BLANK LOCATIONS TO PNL CP24
12. ADDED CKT P604-5, AND FIND NUMBER 210 TO
CKT P604-5
13. REVISED CKT P415-A3 AND P415-B3 CABLE TYPE
FROM LSTSGU-100 TO LSTSGU-150
14. REVISED CKT P614-3 FROM SPARE TO
OCEANOGRAPHIC PMP#1
15. REVISED CKT P614-4 FROM SPARE TO
OCEANOGRAPHIC PMP#2
16. REVISED CKT P616-10 FROM PASSAGE 1-7-1 TO
DRY STORES 1-7-3 DUCT HEATER.
17. REVISED CKT P111-1M BREAKER RATING FROM
15AT TO 20AT
18. REVISED CKT P111-3J AND P111-3F FROM HEAT
LAMPS TO SPARE
19. REVISED CKT P111-4T FROM FORWARD MAST
RECEPTACLE TO SPARE
20. REVISED VARIOUS CABLE TYPES OF CKT
P103-18(C1-3), C2-3, C3-3, AND C4-3.
21. DELETED CKTS P420-13 AND P420-14
22. REVISED CKT SCP104A-13 FROM ITI BATTERY
CHARGER TO SPARE
23. REVISED CKT SCP104A-15 FROM DIGITAL SCALE TO
SPARE
24. REVISED CKT SCP107A-9 FROM LASTER OPTICAL
PLANKTON COUNTER TO SPARE
25. REVISED CKT SCP107A-15 FROM PILOT HOUSE
RECEPTACLES TO SPARE
26. REVISED CKT SCP107A-16 FROM 04 LEVEL
WEATHER RECEPTACLES TO SPARE
27. REVISED CKT SCP103A-3 FROM SPARE TO
FWD/STBD SCC RCPT
28. REVISED CKT SCP103A-2 FROM SPARE TO PH
RCPTS
29. REVISED CKT SCP103A-4 FROM SPARE TO
CONSOLE FWD/STBD CONT
30. REVISED CKT SCP103A-8 FROM BRIDGE RCPT TO
SPARE
31. REVISED CKT SCP103A-14, SCP103A-18,
SCP103A-20, FROM BRIDGE EQUIPMENT RACK RCPT
TO SPARE
F
C
D
A
B
C
DRAWING NO. SH REV
D
A
D
REVDRAWING NO.SIZE
USCG APVD: DATE:
SCALE
ABS APVD: DATE:
FSCM CAGE NO.
98042
OF
FSV6-320-01
FSV6-320-01 G
H
1E
1E 39N.T.S.
9D10D11D12D13D14D15D16D
9D11D12D13D14D15D16D
DESCRIPTIONSHEETREV
REVISIONS
DESCRIPTIONSHEETREV
REVISIONS
32. ADDED SHEET 1E TO INDEX
33. REVISED CKT SCP111A-1 FROM VAISALA BAROMETER TO BLANK
34. REVISED CKT SCP111A-18 FROM CCTV POWER SUPPLY TO SPARE
35. REVISED CKT SCP110A-1J FROM SCC TO SPARE
36. REVISED CKT SCP110A-1R, SCP110A-1X FROM EQUIPMENT RACK TO SPARE
37. ADDED 2 BLANK LOCATIONS TO SCP110A-1
38. REVISED SCP110A-4M FROM WET LAB FUME HOOD TO SPARE
39. REVISED SCP110A-5T FROM HEATING AFT WORK DECK CONTROL STATION TO
SPARE
40. REVISED SCP110A-5V FROM SPARE TO ICE MACHINE
41. REVISED SCP110A-6Z FROM NETWORK SWITCH IMU ROOM TO SPARE
42. REVISED SCP110A-7L RECEPTACLE STRIP FROM DRY LAB TO SCI EQUIPMENT RM
43. REVISED SCP110A-7D FROM CHEM LAB RECEPTACLE STRIP TO SCI SEAWATER
THERMO SALINOGRAPH
44. REVISED SCP110A-7M AND SCP110A-7P HYDROGRAPHIC LAB RECEPTACLE FROM
RECEPTACLE STRIP TO DUPLEX W.T.
45. REVISED SCP110A-7W FROM SPARE TO CCTV RCPTS CHEM LAB, FISH LAB, WET
LAB.
46. REVISED SCP110A-2A FROM CB0 TO SPARE
47. REVISED SCP110A-9G FROM CB3 TO SPARE
48. REVISED SCP110A-9J FROM SPARE TO RAPID FREEZER.
49. ADDED ITEM NO. 248 THRU 253
50. REVISED DESCRIPTION OF PANELS EP100 AND EP24
51. REVISED MOTOR SYMBOL FOR CKTS P610-2, AND P610-4.
52. REVISED DESCRIPTION OF CKTS P616-5, P616-4, AND P616-10..
53. REVISED CKT P609-10 FROM SPARE TO J. BOX FOR FUTURE DIVERS AIR
SYSTEM.
54. REVISED P412-4 CKT BREAKER FROM 15AT TO 100AT.
55. REVISED P412-4 FROM UNIT HEATER (UH-1) TO POWER PANEL P412-4
56. ADDED UNIT HEATER (UH-1) TO CKT P412-8A.
57. ADDED POWER PANEL P412-4
58. REVISED DESCRIPTION OF CKTS P112-1H AND P112-1J
59. REVISED DESCRIPTION OF CKTS P112-2N AND P112-2M
60. REVISED DESCRIPTION OF CKT P111-2D
61. REVISED CABLE TYPE OF CKT P419-15, P419-16, P103-9, P103-15,
P103-14, P103-16.
62. REVISED BREAKER RATING OF CKTS P120-1D, P222-18, AND P222-19.
63. REVISED CABLE TYPE OF CKTS P120-1D, P222-19, P222-20, AND P222-18.
64. REVISED DESCRIPTION OF CKT P420-4.
65. REVISED CKT EP404-7 FROM SPARE TO S-BAND RADAR.
66. ADDED PANEL EP128A
67. REVISED CKT SCP107A-8 FROM THERMOSALINOGRAPH TO CHEM LAB RCPT
68. REVISED CKT SCP105A-24 FROM INERTIAL REF SYS PWR SUPPLY TO SPARE.
69. REVISED CKT SCP110A-3M FROM SPARE TO SIMRAD CABINET
70. ADDED CKT P109-7(C1), FIRE DAMPER FD1
71. ADDED BLANK LOCATION TO PANEL P103
72. REVISED DESCRIPTION OF CKT EP128-10
73. REVISED CKT FROM PMCB-1 TO PMCB1-1, PMCB1-2, PMCB1-3, AND PMCB1-4.
74. REVISED CKT FROM PMCB-2 TO PMCB2-1, PMCB2-2, PMCB2-3, AND PMCB2-4.
75. ADDED DISCONNECT SWITCH (2 EA) ITEM 251 & 252, CKT EP24-2A AND
EP24-1A.
76. DELETED 2 EA BLANK LOCATIONS FROM POWER PANEL EP100
77. REVISED LABELING OF CKTS OFF OF PANEL EP100. EX FROM EP121 TO
EP100-121.
78. ADDED CKT P108-3(C2), P108-4(C2), P107-3(C2), P107-3(C3), P107-4(C2),
P107-4(C3),
79. REVISED CONTROLLER TYPE OF P610-2, AND P610-4 FROM HOA TO FSS
80. REVISED BREAKER SIZE OF P610-14 FROM 35AT TO 40AT
81. REVISED BRAEKER SIZE OF P616-11 FROM 15AT TO 125AT
82. REVISED BREAKER SIZE OF P616-12 FROM 15AT TO 35AT.
83. ADDED CKT'S P120-6(T), P120-7(T), AND P119-13(T)
84. ADDED CKT P109-2G(T)
85. ADDED CKT P112-3L(T)
86. REVISED CKT BREAKER SIZE OF P112-2R FROM 20AT TO 25AT
87. REVISED CKT BREAKER SIZE OF P416-11, P416-12, AND P416-13 FROM 15AT
TO 20AT
88. REVISED CKT P406-5 FROM 02 LVL DK TO 01 LVL DK
89. REVISED ITEM 239 FROM 5KVA 1 PHASE TO 6 KVA 3 PHASE.
90. ADDED ITEM 253 TO CKT P222-19.
91. REVISED P222-9 BREAKER FROM 3P TO 2P
92. REVISED P222-14 FROM 1P TO 2P
93. REVISED P222-21 FROM BLANK TO SPARE
94. REVISED P120-1V FROM SPARE TO GARBAGE DISPOSAL
95. REVISED P120-1K AND P120-1M CKT BREAKER FROM…