Appendix_A-Title_22_Water_Quality_Schedule.xls
XLS spreadsheet 59 KB Posted
- Attached to
- Water Testing
- Solicitation number
- FA9301-16-R-0027
About this file
Appendix A
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Q A_part_3_water_testing.docx | DOCX document | |
| Q A_part_2.docx | DOCX document | |
| Q A_Water_Testing.docx | DOCX document | |
| 252.209-7991.docx | DOCX document | |
| FY16_PWS__Water_sampling.docx | DOCX document | |
| Water_testing_solicitiation_FA9301-16-R-0027.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NewWell CLGD
| This schedule supersedes all previous monitoring schedules. | |||
| Chemical - Title 22 | MCL (mg/L) | EPA Method | Frequency |
| Primary Inorganics - Section 64432 | |||
| Aluminum | 1 | Every 3 years | |
| Antimony | 0.006 | Every 3 years | |
| Arsenic | 0.010 | Every 3 years* | |
| Barium | 1 | Every 3 years | |
| Beryllium | 0.004 | Every 3 years | |
| Cadmium | 0.005 | Every 3 years | |
| Chromium | 0.05 | Every 3 years | |
| Cyanide | 0.15 | Waived | |
| Fluoride | 2.0 | Every 3 years | |
| Mercury | 0.002 | Every 3 years | |
| Nickel | 0.1 | Every 3 years | |
| Perchlorate | 0.006 | 2 samples, 5 to 7 months apart** | |
| Selenium | 0.05 | Every 3 years | |
| Thallium | 0.002 | Every 3 years | |
| Asbestos - Section 64432.2 | |||
| Asbestos - Source Water | 7 MFL | Every 9 years | |
| Asbestos - Distribution System sampling | 7 MFL | Every 9 years | |
| if Asbestos-Cement pipe used | if Aggressive Index < 11.5 | ||
| Nitrate/Nitrite - Section 64432.1 | |||
| Nitrate (as NO3)*** | 45 | Annually if < 23 mg/L*** | |
| Nitrite (as nitrogen)**** | 1 | Every 3 years if <0.5 mg/L**** | |
| Nitrate + Nitrite (sum as nitrogen) | 10 | N/A | |
| Secondary Standards - Table 64449-A | |||
| Aluminum | 0.2 | Every 3 years | |
| Color | 15 | Every 3 years | |
| Copper | 1.0 | Every 3 years | |
| Foaming Agents | 0.5 | Every 3 years | |
| Iron | 0.3 | Every 3 years | |
| Manganese | 0.05 | Every 3 years | |
| Methyl-tert-butyl ether (MTBE) | 0.005 | 502.2, 524.2 | See MTBE frequency on page 2 |
| Odor | 3 | Every 3 years | |
| Silver | 0.1 | Every 3 years | |
| Thiobencarb | 0.001 | Waived | |
| Turbidity | 5 | Every 3 years | |
| Zinc | 5 | Every 3 years | |
| General Minerals - Section 64449 | |||
| Bicarbonate | N/A | Every 3 years | |
| Carbonate | N/A | Every 3 years | |
| Hydroxide Alkalinity | N/A | Every 3 years | |
| Calcium | N/A | Every 3 years | |
| Magnesium | N/A | Every 3 years | |
| Sodium | N/A | Every 3 years | |
| Hardness | N/A | Every 3 years | |
| pH | N/A | Every 3 years | |
| Secondary Standards - Table 64449-B | |||
| TDS | 500-1000;1500 | Every 3 years | |
| Specific Conductance | 900-1600; 2200 | Every 3 years | |
| Chloride | 250-500;600 | Every 3 years | |
| Sulfate | 250-500;600 | Every 3 years | |
| MCL = Maximum Contaminant Level | |||
| * Arsenic sampling shall be increased to quarterly following any result > 0.010 mg/L. | |||
| ** At least 1 sample must be collected during the period from May 1 through Sept. 30. | |||
| If no perchlorate is detected, the monitoring frequency will be every 3 years thereafter. | |||
| *** Nitrate sampling shall be increased to quarterly following any result > 23 mg/L. | |||
| This may be reduced to annual, upon request, if all 4 quarterly results are < 45 mg/L. | |||
| **** Nitrite sampling shall be increased to quarterly following any result > 0.5 mg/L. | |||
| This may be reduced to annual, upon request, if all 4 quarterly results are < 1.0 mg/L. | |||
| Chemical - Title 22 | MCL (mg/L) | EPA Method | Frequency* |
| VOCs - Table 64444-A (a) | |||
| Benzene | 0.001 | 502.2, 524.2 | 2 consec quarters, then every 3 years |
| Carbon Tetrachloride | 0.0005 | 502.2, 524.2 | 2 consec quarters, then every 3 years |
| 1,2-Dichlorobenzene | 0.6 | 502.2, 524.2 | 2 consec quarters, then every 3 years |
| 1,4-Dichlorobenzene | 0.005 | 502.2, 524.2 | 2 consec quarters, then every 3 years |
| 1,1-Dichloroethane | 0.005 | 502.2, 524.2 | 2 consec quarters, then every 3 years |
| 1,2-Dichloroethane | 0.0005 | 502.2, 524.2 | 2 consec quarters, then every 3 years |
| 1,1-Dichloroethylene | 0.006 | 502.2, 524.2 | 2 consec quarters, then every 3 years |
| cis-1,2-Dichloroethylene | 0.006 | 502.2, 524.2 | 2 consec quarters, then every 3 years |
| trans-1,2-Dichloroethylene | 0.01 | 502.2, 524.2 | 2 consec quarters, then every 3 years |
| Dichloromethane | 0.005 | 502.2, 524.2 | 2 consec quarters, then every 3 years |
| 1,2-Dichloropropane | 0.005 | 502.2, 524.2 | 2 consec quarters, then every 3 years |
| 1,3-Dichloropropene | 0.0005 | 502.2, 524.2 | 2 consec quarters, then every 3 years |
| Ethylbenzene | 0.3 | 502.2, 524.2 | 2 consec quarters, then every 3 years |
| Methyl-tert-butyl ether (MTBE) | 0.013 | 502.2, 524.2 | 4 consec quarters, then every 3 years** |
| Monochlorobenzene | 0.07 | 502.2, 524.2 | 2 consec quarters, then every 3 years |
| Styrene | 0.1 | 502.2, 524.2 | 2 consec quarters, then every 3 years |
| 1,1,2,2-Tetrachloroethane | 0.001 | 502.2, 524.2 | 2 consec quarters, then every 3 years |
| Tetrachloroethylene (PCE) | 0.005 | 502.2, 524.2 | 2 consec quarters, then every 3 years |
| Toluene | 0.15 | 502.2, 524.2 | 2 consec quarters, then every 3 years |
| 1,2,4-Trichlorobenzene | 0.005 | 502.2, 524.2 | 2 consec quarters, then every 3 years |
| 1,1,1-Trichloroethane | 0.200 | 502.2, 524.2 | 2 consec quarters, then every 3 years |
| 1,1,2-Trichloroethane | 0.005 | 502.2, 524.2 | 2 consec quarters, then every 3 years |
| Trichloroethylene (TCE) | 0.005 | 502.2, 524.2 | 2 consec quarters, then every 3 years |
| Trichlorofluoromethane | 0.15 | 502.2, 524.2 | 2 consec quarters, then every 3 years |
| 1,1,2-Trichloro-1,2,2-Trifluoroethane | 1.2 | 502.2, 524.2 | 2 consec quarters, then every 3 years |
| Vinyl Chloride | 0.0005 | 502.2, 524.2 | 2 consec quarters, then every 3 years |
| Xylenes (total) | 1.750 | 502.2, 524.2 | 2 consec quarters, then every 3 years |
| SOCs - Table 64444-A (b) | |||
| Alachlor | 0.002 | Waived | |
| Atrazine | 0.001 | 505, 507, 508.1, 525.2 | 2 consec quarters, then every 9 years |
| Bentazon | 0.018 | Waived | |
| Benzo(a)pyrene | 0.0002 | Waived | |
| Carbofuran | 0.018 | Waived | |
| Chlordane | 0.0001 | Waived | |
| 2,4-D | 0.07 | Waived | |
| Dalapon | 0.2 | Waived | |
| Dibromochloropropane (DBCP) | 0.0002 | Waived | |
| Di(2-ethylhexyl)adipate | 0.4 | Waived | |
| Di(2-ethylhexyl)phthalate | 0.004 | Waived | |
| Dinoseb | 0.007 | Waived | |
| Diquat | 0.02 | Waived | |
| Endothall | 0.1 | Waived | |
| Endrin | 0.002 | Waived | |
| Ethylene Dibromide (EDB) | 0.00005 | Waived | |
| Glyphosate | 0.7 | Waived | |
| Heptachlor | 0.00001 | Waived | |
| Heptachlor Epoxide | 0.00001 | Waived | |
| Hexachlorobenzene | 0.001 | Waived | |
| Hexachlorocyclopentadiene | 0.05 | Waived | |
| Lindane | 0.0002 | Waived | |
| Methoxychlor | 0.03 | Waived | |
| Molinate | 0.02 | Waived | |
| Oxamyl | 0.05 | Waived | |
| Pentachlorophenol | 0.001 | Waived | |
| Picloram | 0.5 | Waived | |
| Polychlorinated Biphenyls | 0.0005 | Waived | |
| Simazine | 0.004 | 505, 507, 508.1, 525.2 | 2 consec quarters, then every 9 years |
| Thiobencarb | 0.07 | Waived | |
| Toxaphene | 0.003 | Waived | |
| 2,3,7,8-TCDD (Dioxin) | 0.00000003 | Waived | |
| 2,4,5-TP (Silvex) | 0.05 | Waived | |
| * This frequency applies only to chemicals for which previous results have shown no detectable results (ND). | |||
| ** This frequency applies only after initial monitoring has been completed and no MTBE has been detected (ND). | |||
| Contact DWP for a special monitoring schedule when positive results are found. | |||
| Radiological Monitoring - Revised | |||
| 1. Initial Monitoring Requirements | |||
| Radioactivity - Section 64442 | MCL*** | EPA Method | Frequency |
| Gross Alpha * | 15 pCi/L | 4 quarters initial monitoring | |
| Radium-226 * | 5 pCi/L | When GA > 5 pCi/L** | |
| Radium-228 * | Radium-226 & -228 | 4 quarters initial monitoring | |
| Uranium * | 20 pCi/L | When GA > 5 pCi/L** | |
| Man Made Radioactivity - Section 64443 | |||
| Tritium | 20000 pCi/L | Not Required | |
| Strontium | 8 pCi/L | Not Required | |
| Gross Beta | 50 pCi/L | Not Required | |
| * If the results from the first two quarters of initial monitoring are below the detection limit for purposes of reporting | |||
| (DLR), the final two quarters of initial monitoring may be waived. | |||
| ** If the gross alpha (GA) activity is more than 5 pCi/L, analysis for uranium may be used to obtain the radium-226 activity | |||
| (Gross alpha - Uranium = Radium-226). If Gross alpha - Uranium > 0, call the DWP for further instructions. | |||
| If Gross alpha - Uranium < 0, report only the Gross alpha and Uranium results. If the GA activity is more than 15 pCi/L, | |||
| analysis for uranium must be performed. | |||
| *** Contact the Tehachapi District Office if the MCL is exceeded. | |||
| 2. After initial monitoring outlined above has been completed, the subsequent monitoring frequency will be | |||
| based on the initial monitoring results as follows: | |||
| If Gross Alpha is | Less than 3 pCi/L | Then | Monitoring Frequency is One Sample Every Nine Years |
| * If the gross alpha activity is below 3 pCi/L, and the sample was not analyzed for radium-226 and uranium, the monitoring | |||
| frequencies for Ra-226 and U would be 1 sample every 9 years because at this level gross alpha particle activity can | |||
| be substituted for Ra-226 and U. In this case, a sample collected once every nine years and analyzed for gross alpha | |||
| activity would satisfy the radiological monitoring requirements for gross alpha, Ra-226, and U. | |||
| If Gross Alpha is | > 3 and < 7.5 pCi/L | Then | Monitoring Frequency |
| If Radium-226* is | > 1 and < 2.5 pCi/L | Then | is |
| If Radium-228 is | > 1 and < 2.5 pCi/L | Then | One Sample |
| If Uranium* is | > 1 and < 10 pCi/L | Then | Every Six Years |
| * If the gross alpha activity is between 3 and 5 pCi/L, and the sample was not analyzed for radium-226 and uranium, the | |||
| monitoring frequencies for Ra-226 and U would be 1 sample every 6 years because at this level gross alpha particle | |||
| activity can be substituted for Ra-226 and U. In this case (GA between 3 and 5 pCi/L), a sample collected once | |||
| every six years and analyzed for gross alpha activity would satisfy the radiological monitoring requirements for gross | |||
| alpha, Ra-226, and U. | |||
| If the gross alpha activity is more than 5 pCi/L, the sample must be analyzed for Ra-226 or U. | |||
| If Gross Alpha is | > 7.5 and < 15 pCi/L | Then | Monitoring Frequency |
| If Radium-226* is | > 2.5 and < 5 pCi/L | Then | is |
| If Radium-228 is | > 2.5 and < 5 pCi/L | Then | One Sample |
| If Uranium* is | > 10 and < 20 pCi/L | Then | Every Three Years |
| * Because the gross alpha activity is more than 5 pCi/L, the sample must be analyzed for radium-226 or uranium. | |||
| If the gross alpha activity is more than 15 pCi/L, the sample must be analyzed for U. | |||
| The monitoring frequencies for gross alpha, radium -226, radium-228, and uranium may be different. |