Responses to Questions Set 2 dated 19 June 2019
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FA8604-19-R-8106-0004.pdf | ||
| FA8604-19-R-8106-0003.pdf | ||
| Questions_and_Answers_Set_No._1_revA.pdf | ||
| FA8604-19-R-8106-0002.pdf | ||
| FA8604-19-R-8106_0001.pdf | ||
| BMC802-02_-_3101_C_Bay_TC.dwg | DWG drawing | |
| BMC802-04_-_1757_Tire_Carousel_TC.dwg | DWG drawing | |
| BMC802-01_-_3101_A_Bay_TC.dwg | DWG drawing | |
| BMC802-03_-_1757_Mezzanine_Modification_TC.dwg | DWG drawing | |
| Final_RFP_FA8604-19-R-8106.pdf | ||
| Summary_Pricing_Sheet.docx | DOCX document |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FA8604-19-R-8106
Questions and Answers Set #2 19 June 2019
1. The inward rotating pallet gates for the mezzanine modification are requested to be 126”. This style of pallet gate is generally limited to 96” without significant increases in cost for a custom design. Would another style of pallet gate be acceptable?
Each opening does not consist of just one long gate that swings inward, but two gates that are roughly 62” - 63” long each (126” total opening). This type of gate has been specified and required.
FA8604-19-R-8106
Questions and Answers Set #1 18 June 2019
1. Appendix A – Mezzanine
a. Can you provide additional specs and as-Built drawings for the existing mezzanine?
*Yes. See attachment, “B1757 Mezzanine Shop Drawings”, for images of the shop drawings. If variances are noted upon visual inspection, the contractor shall submit these discrepancies to the CO.
b. Is 150 psf enough to support 463L on the mezzanine to be modified? Mezzanines designed to hold 463L are generally a minimum 175 psf.
*Yes & Changed. See Appendix A: Section 3.2.3.1 & TPQ.
c. Will engineer stamped drawings be required for the modifications to the existing mezzanine?
*Yes & Changed. See Appendix A: Section 3.2.1.5, Certifications, and TPQ.
d. What depth is requested for the pivoting safety gate? The 6 foot width is listed, but not the depth.
*Changed. See Appendix A: Section 3.2.1.11 & TPQ. Providing the dimensions of items passing through the gate will set the necessary requirements for width, height, and depth of the gate system.
2. Appendix D – Pallet Rack
a. TPQ question from section 3.2.7.1 asks if solid wood decking will be provided and installed as specified. There is no 3.2.7.1 in the appendix or mention of wood decking. Please advise.
*Changed. See Appendix D: TPQ.
3. Appendix E – Widespan
a. TPQ Question from section 3.1. asks for a number of 2 and 4 foot uprights. Should this be 6 and 14 foot uprights? Please advise.
*Changed. See Appendix E: TPQ.
4. Appendix H – Modular Office
a. 3.2.7 panel width is not included. “The panels shall be a width of feet.” Please advise.
*Changed. See Appendix H: Section 3.2.7.
b. 3.2.10 states that there shall be 2 personnel doorways while the drawing only shows 1.
Please advise.
*Changed. See Appendix H: Section 3.2.10.
c. 3.2.17 tpq questions asks “Are exit signs provided as required?”. There is no section 3.2.17.
or other section about exit signs. Please advise.
*Changed. See Appendix H: Section 3.2.16. & TPQ.