Drawings_Rpl_Cooling_Tower_F10262.pdf
PDF 14 MB Posted
- Attached to
- Replace Cooling Tower Federal contract opportunity
- Solicitation number
- FA860115R0039
About this file
Drawings
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FA8601-15-R-0039-0003.pdf | ||
| FFP_Addendum_02_SOW.pdf | ||
| RFI_Responses_29_JUL_15.pdf | ||
| Addendum_01_M401.pdf | ||
| FA8601-15-R-0039-P0002_Addendum_1.pdf | ||
| FFP_Addendum_01_SOW.pdf | ||
| FA8601-15-R-0039-0001_Amendment_1.pdf | ||
| General_Decision_Number_OH150102_21_Jul_15.pdf | ||
| 16._Rules_of_Engagement.pdf | ||
| sign-in_sheet.pdf | ||
| FA8601-15-R-0039.pdf | ||
| General_Decision_Number_OH150102_5_Jun_15.pdf | ||
| Specifications_Rpl_Cooling_Tower_F10262_.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STM
Location
Soil Boring
Location
Soil Boring
CW
C W
C W
C W
C W
C W
CW
C W
S T
M
S T
M
STM
STM
STM STM STM STM
STM
STM STM
S T
M
S T
M
S T
M
STM
S T
M
STM
STM STM STM
STM
STM STM
S T
M
C W
C W
C W
C W
C W
C W
C W
COORDINATOR ENGINEERING CHIEF
DATE REVISION BYNO. DATE NO. REVISION BY
C I
V
IL
ENGIN
E E R
USAF
OF
DESIGN CHIEF
DATE
TEL 513 621 6211
W PAFB
WRIGHT-PATTERSON AIR FORCE BASE
88TH ABW
SEAL
* * * SUPPORT VALUE ENGINEERING - IT PAYS * * *
* * * SAFETY PAYS * * *
CHECKED P. BATTAGLIADRAWN K. ELLIOTTDESIGNED J. BENEDICT
S T
A T
E OF O
H
IO
P R
O F
E
S S
IONAL
E N
G I N
E E
R
R
E
GISTERE
D
E51255
BATTAGLIA
S.
PETER
CORRECTED FINAL
23 JUN 15
N
GRAPHIC SCALE
0 20 40
P
L
T
Steam Manhole
Water Service
Storm Inlet Sign Valve
Landscaping
Bollard
Tree
Light Pole
Power Pole
Electric Manhole
Electric Manhole
Telephone Manhole
Ex. Sanitary Sewer
Ex. Storm Sewer
Ex. Waterline
Ex. Waterline
Ex. Fence
Ex. Electric
Ex. Major Contour
Ex. Minor Contour
Ex. Gasline
Existing Site Legend
Sanitary Manhole
Ex. Chilled WaterCW
Exist Utility
Connect to
Inv LOCKED
Top=834.63
STMH
Inv FULL
Top=834.93
CI
Top=835.21
SSMH
Elect. MH
Inv 12" RCP(W)= 832.26
Top=834.73
Inv 15" CPP(W)= 830.21
Inv 12" CPP(S)= 830.21
Top=834.82
Inv 12" CPP(S)= 829.32
Inv 15" CPP(E)= 829.32
Inv 15" CPP(W)= 829.32
Top=834.41
Inv 12" CPP(N)= 829.52
Top=834.32
Inv 8" VCP(E)= 831.13
Inv 18" RCP(W)= 828.03
Inv 18" RCP(NE)= 827.98
Top=833.88
Top=834.76
Inv 8" PVC(S)= 832.29
Top=834.14
Inv 12" RCP(N)= 830.97
Inv 8" VCP(W)= 831.22
Inv 12" RCP(E)= 831.47
Top=834.72
CBS
12" Tree
12" Tree
12" Tree
12" Tree
2" Tree
12" Evergreen
14" Evergreen
10" Evergreen
10" Evergreen
10" Evergreen
12" Evergreen
12" Evergreen
12" Evergreen
8' Chain Link
Fence
Top=834.54 reserved park.
Sign Private reserved park.
Sign Private (4)
C P P
15" CPP15" CPP
15" CPP
C P
Inv 8" VCP(W)= 831.60
Inv 8" VCP(E)= 831.70
Top=836.00
CBS
STMH
F.F.=837.36
Building
CONC WALK
C O
N C
W A L K
C O
LK
CONC WALK
C O
L K
834834
F.F.=840.88
Building 262
Existing Cooling Tower
"T" Road
20" Return Piping
Piping
20" Supply
Conc. Walk
CONC WALK
Drive
Dock
Dock Drive Grass
Grass
S a c r a m e n t o
S
F.Hyd.
Tele.MH
20" Return Piping
822.85 PLAN
Inv LOCKED
Top=834.62
SSMH
Inv 821.50 PLAN
Top=835.28 PLAN
SSMH
CONTRACT: FA8601-12-D-0005
REPL COOLING TOWER F10262 F10266
PROJECT - ZHTV040019
K Z F
.0
F
U L L S
IZ
E P
R
IN
T
X
EXISTING SITE PLAN
C100
POSSIBLE 30" CASING Pipe
COORDINATOR ENGINEERING CHIEF
DATE REVISION BYNO. DATE NO. REVISION BY
C I
V
IL
ENGIN
E E R
USAF
OF
DESIGN CHIEF
DATE
TEL 513 621 6211
W PAFB
WRIGHT-PATTERSON AIR FORCE BASE
88TH ABW
SEAL
* * * SUPPORT VALUE ENGINEERING - IT PAYS * * *
* * * SAFETY PAYS * * *
CHECKED P. BATTAGLIADRAWN K. ELLIOTTDESIGNED J. BENEDICT
S T
A T
E OF O
H
IO
P R
O F
E
S S
IONAL
E N
G I N
E E
R
R
E
GISTERE
D
E51255
BATTAGLIA
23 JUN 15
CW
C W
C W
C W
C W
C W
CW
C W
S T
M
S T
M
STM
STM
STM STM STM STM
STM
S T
M
S T
M
STM
S T
M
STM
STM STM STM
STM
C W
C W
C W
C W
C W
C W
C W
N
GRAPHIC SCALE
0 20 40
C101
SITE PHASING PLAN
PHASE I
-REROUTE STORM SEWER
-CONSTRUCT ELECTRICAL CONDUIT TO BUILDING 262
-CONSTRUCT NEW WATER SERVICE
-CONSTRUCT NEW SANITARY LATERAL
-CONSTRUCT COOLING TOWER COMPLEX
COOLING COMPLEX
-DEMOLISH SITE ITEMS REQUIRED TO CONSTRUCT THE NEW
CONNECTION LOCATIONS
-VERIFY ELEVATION & LOCATION OF EXISTING UTILITIES AT
PHASE II
PHASE III
-DEMOLISH EXISTING COOLING TOWER COMPLEX
-RECONSTRUCT SIDEWALKS, REPAIR PAVING
-REMOVE STAGING AREA
-FINAL GRADE, SEED AND MULCH
PHASE I
PHASE III
PHASE I
-TEST OPERATION OF COOLING TOWER EQUIPMENT
30' OF BUILDING CONNECTION POINT
-CONSTRUCT NEW SUPPLY AND RETURN COOLING LINES TO WITHIN
-REMOVE EXISTING SUPPLY AND RETURN LINES AS REQUIRED.
-CONNECT NEW SUPPLY AND RETURN LINES TO BUILDING SYSTEM.
-DISCONNECT AND REMOVE TEMPORARY COOLING UNIT
-ABANDON IN PLACE EXISTING SUPPLY AND RETURN LINES BY FILLING WITH GROUT
PHASE II
PHASE III
SHEET M-401
RENTAL CHILLERS
TEMPORARY
-INSTALL TEMPORARY RENTAL CHILLER UNITS AND CONNECT TO BUILDING SYSTEM.
CONTRACT: FA8601-12-D-0005
REPL COOLING TOWER F10262 F10266
PROJECT - ZHTV040019
K Z F
.0
F
U L L S
IZ
E P
R
IN
T
X
Inv 18" RCP(NE)= 827.98
Inv 12" RCP(E)= 831.47
Top=834.72
CBS
reserved park.
Sign Private reserved park.
Sign Private (4)
15" CPP
STMH
F.F.=837.36
Building
CONC WALK
C O
L K
C O
LK
CONC WALK
F.F.=840.88
Building 262
20" Return Piping
Piping
20" Supply
Conc. Walk
Drive
Dock
Dock Drive Grass
Grass
S a c r a m e n
C I
V
IL
ENGIN
E E R
USAF
OF
DESIGN CHIEF
DATE
TEL 513 621 6211
W PAFB
WRIGHT-PATTERSON AIR FORCE BASE
88TH ABW
SEAL
* * * SUPPORT VALUE ENGINEERING - IT PAYS * * *
* * * SAFETY PAYS * * *
CHECKED P. BATTAGLIADRAWN K. ELLIOTTDESIGNED J. BENEDICT
S T
A T
E OF O
H
IO
P R
O F
E
S S
IONAL
E N
G I N
E E
R
R
E
GISTERE
D
E51255
BATTAGLIA
23 JUN 15
CW
C W
C W
C W
C W
C W
CW
C W
S T
M
S T
M
STM
STM
STM STM STM STM
STM
STM STM
S T
M
STM
S T
M
S T
M
STM
S T
M
STM
STM STM STM
STM
STM STM
S T
M
STM
C W
C W
C W
C W
C W
C W
C W
N
GRAPHIC SCALE
0 20 40
CONTRACT: FA8601-12-D-0005
REPL COOLING TOWER F10262 F10266
PROJECT - ZHTV040019
K Z F
.0
F
U L L S
IZ
E P
R
IN
T
X
Inv 12" CPP(S)= 829.32
Inv 15" CPP(E)= 829.32
Inv 15" CPP(W)= 829.32
Top=834.41
Inv 18" RCP(NE)= 827.98
Inv 12" RCP(E)= 831.47
Top=834.72
CBS
reserved park.
Sign Private reserved park.
Sign Private (4)
C P P
15" CPP15" CPP
15" CPP
C
STMH
F.F.=837.36
Building
CONC WALK
C O
L K
C O
LK
CONC WALK
C O
L K
F.F.=840.88
Building 262
"T" Road
20" Return Piping
Piping
20" Supply
Conc. Walk
CONC WALK
Drive
Dock
Dock Drive Grass
Grass
S a c r a m e n
C200
DEMOLITION PLAN
XXXXXXXXXXXXXXXXXXXXXXXX
X X
X X
X
X
X X
X X
X
X X X X X X X X X X X X X X X X X X X X X X X
REMOVE PAVEMENT
REMOVE CONCRETE WALK
WALK
REMOVE CONC.
PIPE
REMOVE STORM
REMOVE TREES TYP.
REMOVE C.B.
REMOVE STORM PIPE
REMOVE CURB
REMOVE STORM PIPE REMOVE PAVEMENTREMOVE CURB
WALK
REMOVE CONC.
TREES
EXISTING
PROTECT
PROVIDE NEW 5' WIDE CONCRETE WALK.2
4 REMOVE EXISTING TREES.
CORE NEW SOUTH OUTLET FOR NEW 12" STORM.
SEAL EXISTING STORM MANHOLE AT EAST OUTLET.
REMOVE EXISTING 12" DIA. STORM SEWER.
7 REMOVE EXISTING CONCRETE CURB.
8 REMOVE EXISTING CATCH BASIN.
9 REMOVE EXISTING CONCRETE WALK.
10 REMOVE EXISTING ASPHALT PAVEMENT.
5 5
FENCE
CONSTRUCTION
1A
6 8
(SEE PHASING PLAN FOR TIMING)
FILL SITE AS NEEDED, FINE GRADE, SEED AND MULCH.
TANK CONTAINMENT AREA.
PERIMETER FENCING, UTILITY CONNECTIONS, ACID
POST INDICATOR VALVES, CONC. FOUNDATIONS,
DEMOLISH EXISTING COOLING TOWER, 20" DIA. PIPING,
TO THE FOLLOWING NOTES
DEMOLITION INCLUDES, BUT IS NOT LIMITED
DEMOLITION NOTES:
11 CONTRACTOR LAY DOWN AREA 8" AGGREGATE BASE
AREA
LAY DOWN
WITH 4 SPACES (SEE C300)
REMOVE 12 EXISTING SPACES REPLACED
ASPHLAT PAVEMENT AS REQUIRED.
REMOVE EXISTING CONCRETE WALK, STAIRS AND
REQUIRD. IF TRANSIT PIPE REFER TO NOTES ON C500.
REMOVE EXISTING SUPPLY AND RETURN LINES AS
LINES BY FILLING WITH GROUT.
ABANDON IN PLACE EXISTING SUPPLY AND RETURN
OF LAY DOWN AREA.
AFTER COMPLETION OF PROJECT AND REMOVAL
REMOVE EXISTING CONCRETE SIDEWALK. REPLACE
1A REMOVE EXISTING CONCRETE SIDEWALK.
C I
V
IL
ENGIN
E E R
USAF
OF
DESIGN CHIEF
DATE
TEL 513 621 6211
W PAFB
WRIGHT-PATTERSON AIR FORCE BASE
88TH ABW
SEAL
* * * SUPPORT VALUE ENGINEERING - IT PAYS * * *
* * * SAFETY PAYS * * *
CHECKED P. BATTAGLIADRAWN K. ELLIOTTDESIGNED J. BENEDICT
S T
A T
E OF O
H
IO
P R
O F
E
S S
IONAL
E N
G I N
E E
R
R
E
GISTERE
D
E51255
BATTAGLIA
23 JUN 15
CW
C W
C W
C W
C W
C W
CW
C W
S T
M
S T
M
STM
STM
STM STM STM STM
STM
STM STM
S T
M
STM
S T
M
S T
M
STM
S T
M
STM
STM STM STM
STM
STM STM
S T
M
STM
C W
C W
C W
C W
C W
C W
C W
N
GRAPHIC SCALE
0 20 40
CONTRACT: FA8601-12-D-0005
REPL COOLING TOWER F10262 F10266
PROJECT - ZHTV040019
K Z F
.0
F
U L L S
IZ
E P
R
IN
T
X
Inv 18" RCP(NE)= 827.98
Inv 12" RCP(E)= 831.47
Top=834.72
CBS
reserved park.
Sign Private reserved park.
Sign Private (4)
C P
15" CPP15" CPP
STMH
F.F.=837.36
Building
CONC WALK
C O
L K
C O
LK
CONC WALK
C O
L K
F.F.=840.88
Building 262
"T" Road
20" Return Piping
Piping
20" Supply
Conc. Walk
CONC WALK
Drive
Dock
Dock Drive Grass
Grass
S a c r a m e n
C300
SITE PLAN
FENCE
CONSTRUCTION
LAY DOWN AREA
CONC WALK
MOW STRIP
MOW STRIP
CONSTRUCTION FENCE
NEW CURB & GUTTER
BE PROTECTED
EX. TREES TO
WALK
REPLACE CONC.
WALK
REPLACE CONC.
TO THE FOLLOWING NOTES
CONSTRUCTION INCLUDES, BUT IS NOT LIMITED
CONSTRUCTION NOTES:
REPLACE CONCRETE SIDEWALKS. MATCH EXISTING WIDTH.
CONNECTIONS ARE COMPLETE.
RESTORE ASPHALT PAVING AFTER COOLING LINE
AND GRADING WORK IS COMPLETE.
REPLACE CONCRETE PAD AFTER STORM SEWER
WALK
CONCRETE
GENERAL NOTES:
REQUIRED WITH BASE SECURITY FORCES.
REMOVAL & REPLACEMENT OF CONC. BARRIERS IF
CONTRACTOR SHALL COORDINATE THE TEMPORARY
MAINTAINED AT ALL TIMES.
ACCESS TO DOCK AT BUILDING 262 SHALL BE
PAVEMENT
RESTORE ASPHALT
.0
6.82'
OF CONSTRUCTION
RESTORE AREA TO LAWN CONDITION AT COMPLETION
5 4" WHITE PAINT STRIPE
9.00'1 .0
6 REPLACE CURB, MATCH EXISTING
7 REPLACE STAIARS MATCH EXISTING
C I
V
IL
ENGIN
E E R
USAF
OF
DESIGN CHIEF
DATE
TEL 513 621 6211
W PAFB
WRIGHT-PATTERSON AIR FORCE BASE
88TH ABW
SEAL
* * * SUPPORT VALUE ENGINEERING - IT PAYS * * *
* * * SAFETY PAYS * * *
CHECKED P. BATTAGLIADRAWN K. ELLIOTTDESIGNED J. BENEDICT
S T
A T
E OF O
H
IO
P R
O F
E
S S
IONAL
E N
G I N
E E
R
R
E
GISTERE
D
E51255
BATTAGLIA
23 JUN 15
S T
M
S T
M
STM
STM
STM STM STM STM
STM
STM STM
S T
M
STM
S T
M
S T
M
STM
S T
M
STM
STM STM STM
STM
STM STM
S T
M
STM
C W
C W
C W
C W
C W
C W
C W
N
GRAPHIC SCALE
0 20 40
INLET PROTECTION
CONSTRUCTION FENCE
PROPOSED GRADE
DRAINAGE FLOW PATTERN
SILT FENCE
CONTRACT: FA8601-12-D-0005
REPL COOLING TOWER F10262 F10266
PROJECT - ZHTV040019
K Z F
.0
F
U L L S
IZ
E P
R
IN
T
X
Inv 18" RCP(NE)= 827.98
Inv 12" RCP(E)= 831.47
Top=834.72
CBS
reserved park.
Sign Private reserved park.
Sign Private (4)
C P
STMH
F.F.=837.36
Building
CONC WALK
C O
L K
C O
LK
CONC WALK
C O
L K
835835
F.F.=840.88
Building 262
"T" Road
20" Return Piping
Piping
20" Supply
Conc. Walk
CONC WALK
Drive
Dock
Dock Drive Grass
Grass
S a c r a m e n
C400
GRADING PLAN
835.75
835.75
836.00 836.00 836.00
836.00
835.75 835.75
835.75 835.75
833.50
835.75
836.21 835.81 835.65 835.45 834.95
834.55
835.06
835.48835.36835.25
IP
CONSTRUCTION LEGEND
IP
IP
IP
IP
IP
IP
IP
IP
IP
IP
IP
836.00
SF
SF
SF834.86834.75 834.98
MATCH EX.
834.56
BLDG FIN FLR 836.33
C I
V
IL
ENGIN
E E R
USAF
OF
DESIGN CHIEF
DATE
TEL 513 621 6211
W PAFB
WRIGHT-PATTERSON AIR FORCE BASE
88TH ABW
SEAL
* * * SUPPORT VALUE ENGINEERING - IT PAYS * * *
* * * SAFETY PAYS * * *
CHECKED P. BATTAGLIADRAWN K. ELLIOTTDESIGNED J. BENEDICT
S T
A T
E OF O
H
IO
P R
O F
E
S S
IONAL
E N
G I N
E E
R
R
E
GISTERE
D
E51255
BATTAGLIA
23 JUN 15
CW
C W
C W
C W
C W
C W
CW
C W
S T
M
S T
M
STM
STM
STM STM STM STM
STM STM
S T
M
S T
M
STM
S T
M
STM
STM STM STM
STM
S T
M
STM
C W
C W
C W
C W
C W
C W
C W
N
GRAPHIC SCALE
0 20 40
CONTRACT: FA8601-12-D-0005
REPL COOLING TOWER F10262 F10266
PROJECT - ZHTV040019
K Z F
.0
F
U L L S
IZ
E P
R
IN
T
X
Inv 18" RCP(NE)= 827.98
Inv 12" RCP(E)= 831.47
Top=834.72
CBS
12" Tree
12" Tree
12" Tree
12" Tree
2" Tree
14" Evergreen
10" Evergreen
8' Chain Link
Fence
Top=834.54 reserved park.
Sign Private reserved park.
Sign Private (4)
C P
STMH
F.F.=837.36
Building
CONC WALK
C O
L K
C O
LK
CONC WALK
C O
L K
F.F.=840.88
Building 262
Existing Cooling Tower
"T" Road
20" Return Piping
Piping
20" Supply
Conc. Walk
CONC WALK
Drive
Dock
Dock Drive Grass
Grass
S a c r a m e n
822.85 PLAN
Inv LOCKED
Top=834.62
SSMH
Inv 821.50 PLAN
Top=835.28 PLAN
SSMH
C500
UTILITY PLAN
WATER RETURN(UG)
20" CONDENSER
WATER SUPPLY(UG)
20" CONDENSER
12" INV.=831.00'
TOP=833.50'
STM INLET
4" UNDER DRAIN
4" UNDER DRAIN
TO THE FOLLOWING NOTES
CONSTRUCTION INCLUDES, BUT IS NOT LIMITED
CONSTRUCTION NOTES:
GENERAL NOTES:
PROVIDE 6" SANITARY LATERAL MIN. SLOPE 0.80%
BUILDING.
PROVIDE 2" WATER SERVICE LATERAL TO NEW CHEMICAL
7 RESTORE UTILITY TRENCH AS PER DETAIL.
6" SAN. LATERAL
2" WATER SERVICE
@ 0.34%
56'~15" STM
INV. 12"= 829.33
INV. 15"= 829.33
TOP=835.50
STM MH-2
INV. 15"= 829.52
TOP=835.50
STM MH-3
@ 0.33%
36'~15" STM
@ 0.32%
25'~15" STM
INV. 15"= 829.21
TOP=835.50
STM MH-1
INV. 15"= 829.13
TOP=834.63
STM MH-EX.
ELECTRICAL CONDUITS ARE INSTALLED.
RESTORE ASPHALT PAVING PER DETAIL AFTER
ARE INSTALLED.
RESTORE LAWN AFTER ELECTRICAL CONDUITS
MAIN. INV 822.51 VERIFY
CONNECT 6" SANITARY LATERAL TO EXISTING SANITARY
INV 6" 826.00 VERIFY
18" CLEARANCE. ASSUMED STEAM BOTTOM 828.00
COORDINATE UTILITY ELEVATION AT STEAM LINES. PROVIDE
18" CLEARANCE. ASSUMED STEAM BOTTOM 828.00
COORDINATE UTILITY ELEVATION AT STEAM LINES. PROVIDE
PROVIDE CONSTANT SLOPE TO STEAM LINE CROSSING
6" CLEAN OUT INV 632.15
REFER TO M101 FOR EXACT LOCATION
4"DRAIN INV @ SLAB 632.15 MIN SLOPE 1.0%
@ 2.70%
37'~12" STM
INV. 12"= 830.00
INV. 15"= 829.60
OPEN GRATE=835.50
STM MH-4
@ 0.36%
22'~15" STM
1-1" WATER LEVEL PROBE CONDUIT (SEE SHEET ES01).
3-1" HVAC CONTROL CONDUITS &
2-3" ELECTRICAL CONDUITS CONCRETE ENCASED
PIPE AND UTILITY CROSSINGS ELEVATIONS.
WATER PIPING, VERIFY ELEVATIONS OF EXISTING CW
PRIOR TO START OF CONSTRUCTION OF CONDENSER
21 BUILDING FINISH FLOOR 836.33
22 30" CASING PIPE FROM ASBUILT DRAWINGS
CONDUITS AND COOLING LINES ARE INSTALLED.
RESTORE CONCRETE WALK AFTER ELECTRICAL
FOR DETAILS.
BY FILLING WITH GROUT. REFER TO SHEET C510
EXISTING 20" PIPE TO BE ABANDONED IN PLACE
FOR DETAILS.
BY FILLING WITH GROUT. REFER TO SHEET C510
EXISTING 20" PIPE TO BE ABANDONED IN PLACE
AND CONNECTING TO THE EXISTING SYSTEM.
CONSTRUCTION FOR THE REMOVAL OF THE EXISTING PIPETHE
ABATEMENT PROGRAM FOR APPROVAL PRIOR TO THE START OF
IF PIPE MATERIAL IS TRANSITE PIPE, CONTRACTOR TO SUBMIT AN
PIPE MATERIAL.
TRANSITE PIPE NEAR BUILDING 262 TO VERIFY SUPPLY AND RETURN
CONTRACTOR SHALL EXCAVATE TO THE TOP OF THE EXISTING POSSIBLE
A PORTION OF THE PIPE IS IN A 30" STEEL CASING PIPE.
CONSTRUCTION PLANS INDICATE A COVER DEPTH OF 7' AND
ALL EXISTING UTILITIES PRIOR TO START OF CONSTRUCTION.
CONTRACTOR SHALL EXCAVATE AND VERIFY ELEVATIONS OF
PROVIDE SLOPE TO BUILDING 262.
IS 828.80. (SEE M101 FOR CONNECTION TO TOWER)
AS PER MECHANICAL SPECIFICATIONS. BEGIN ELEVATION
PROVIDE 20" DIA. PVC SCH. 40 PIPE WITH THRUST BLOCKS
TOWER) PROVIDE SLOPE TO BUILDING 262.
ELVATION IS 826.4 (SEE M101 FOR CONNECTION TO
BLOCKS AS PER MECHANICAL SPECIFICATIONS. BEGIN
PROVIDE 20" DIA. PVC SCH. 40 PIPE WITH THRUST
PROVIDE SLOPE TO BUILDING 262.
BULDING 262 ELEVATION 826.42 (VERIFY).
THRUST BLOCKS AS PER MECHANICAL SPECIFICATIONS.
PROVIDE CWS 20" DIA. PVC SCH. 40 PIPE WITH23
PROVIDE SLOPE TO BUILDING 262.
BULDING 262 ELEVATION 826.42 (VERIFY).
THRUST BLOCKS AS PER MECHANICAL SPECIFICATIONS.
PROVIDE CWR 20" DIA. PVC SCH. 40 PIPE WITH24
REFER TO SHEET C510 FOR DETAILS THIS AREA.
C I
V
IL
ENGIN
E E R
USAF
OF
DESIGN CHIEF
DATE
TEL 513 621 6211
W PAFB
WRIGHT-PATTERSON AIR FORCE BASE
88TH ABW
SEAL
* * * SUPPORT VALUE ENGINEERING - IT PAYS * * *
* * * SAFETY PAYS * * *
CHECKED P. BATTAGLIADRAWN K. ELLIOTTDESIGNED J. BENEDICT
S T
A T
E OF O
H
IO
P R
O F
E
S S
IONAL
E N
G I N
E E
R
R
E
GISTERE
D
E51255
BATTAGLIA
23 JUN 15
CW
CW
CW
CW CW CW
CW CW CW
N
GRAPHIC SCALE
0 10 20
CONTRACT: FA8601-12-D-0005
REPL COOLING TOWER F10262 F10266
PROJECT - ZHTV040019
K Z F
.0
F
U L L S
IZ
E P
R
IN
T
X
E le c t
M H
E v e r g r e e n r e s e r v e d p a r k
S ig n r iv a t e
R e t u ip in g
P ip in g
S u p p ly n c
W a lk
D o c k
D iv e
G r a s s
F .H y d
R e t u ip in g
C510
.8
.5
.9
.0
.0
.6
.8
.7
1211109
UTILITY PLAN & PROFILE
1190° BEND STA. 10+00.00
ASPHALT
TO THE FOLLOWING NOTES
CONSTRUCTION INCLUDES, BUT IS NOT LIMITED
CONSTRUCTION NOTES:
PROFILE
1"=5' VERT
SCALE 1"-10' HORZ
NEW 20" RETURN LINE (SUPPLY LINE SIMILAR)
.2
.0
PROTECT/SUPPORT EXISTING FIBER OPTICS DURING EXCAVATION.
PROTECT/SUPPORT EXISTING WATER MAIN DURING EXCAVATION.
ARE ASSUMED ELEVATIONS.
PRIOR TO EXCAVATION FOR PIPE REPLACEMENT. DEPTHS SHOWN
UNDERPIN CANOPY COLUMN, DOCK WALL AND AREA WELL
PROTECT/SUPPORT NEW 4" UNDER DRAIN DURING EXCAVATION
PROTECT/SUPPORT NEW 12" STORM LINE DURING EXCAVATION.
PROTECT/SUPPORT EXISTING 15" STORM LINE DURING EXCAVATION.
PROTECT/SUPPORT EXISTING ELECTRIC TELECOMWATER LINES DURING EXCAVATION.
VERIFY EXISTING ELECTRIC & TELECOM LINE PRIOR TO START OF CONSTRUCTION.
NEW 20" SUPPLY LINE
NEW 20" RETURN LINE 45° BEND STA. 11+14.94
1-1" WATER LEVEL PROBE CONDUIT (SEE SHEET ES01).
3-1" HVAC CONTROL CONDUITS &
2-3" ELECTRICAL CONDUITS CONCRETE ENCASED
AREA WELL
CONC STAIRS
45° BEND STA. 11+47.29
CONC WALK
CURB
EXIST 20" RETURN LINE
EXIST 20" SUPPLY LINE
EXIST DOCK WALL
AREA WELL
EXIST DOCK
BLDG STA. 11+68.66
NEW 2" WATER SERVICE
NEW 4" UNDERDRAIN
NEW 12" STORM LINE
6 5
EXIST ELEC & TELE COM LINES
EXIST FIBER OPTIC LINE
EXIST WATER MAIN
EXIST GRADE
AREA WELL
& FOUNDATION
DOCK CANOPY COLUMN
DOCK WALL
DOCK BLDG WALL
EXIST 15" STORM LINE
FOR DETAIL INSIDE BLDG SHEET M401
REFER TO MECHANICAL DRAWINGS
BASEMENT FLOOR 825.67
INV 826.42
20" RETURN AND SUPLLY
FIRST FLOOR 840.88
C I
V
IL
ENGIN
E E R
USAF
OF
DESIGN CHIEF
DATE
TEL 513 621 6211
W PAFB
WRIGHT-PATTERSON AIR FORCE BASE
88TH ABW
SEAL
* * * SUPPORT VALUE ENGINEERING - IT PAYS * * *
* * * SAFETY PAYS * * *
CHECKED P. BATTAGLIADRAWN K. ELLIOTTDESIGNED J. BENEDICT
S T
A T
E OF O
H
IO
P R
O F
E
S S
IONAL
E N
G I N
E E
R
R
E
GISTERE
D
E51255
BATTAGLIA
23 JUN 15
1'-6"
1":1'
THE PROJECT IS LOCATED MAY BE SUBSTITUTED.
STANDARD CURB SHAPE OF THE STATE IN WHICH
NOTE:
FINISHED GRADE
2" RADIUS (SEE NOTE)
IS MAINTAINED.
A MINIMUM THICKNESS OF 7"
SUBSURFACE COURSES PROVIDED
PARALLEL TO THE SLOPE OF
GUTTER MAY BE CONSTRUCTED
THE BOTTOM OF THE CURB AND
SUBGRADE
COMPACTED
1'-6"6"
4"
PAVEMENT
CURB
S A
W C
U T
DROPPED CURB DETAIL
PAVEMENT
EXISTING
PROPOSED GRADE
SLOPE TO CB
4" UNDER DRAIN
8"
6" MIN.
METAL EDGING
LANDSCAPE FABRIC
M
IN
3" WASHED GRAVEL
CURB
NOT TO SCALE
8"-ITEM 304 (ODOT) AGGREGATE BASE
ITEM 204 (ODOT) SUBGRADE COMPACTION
LAYDOWN AREA DETAIL
TOPSOIL
O.D. + 8" MIN
SEED OR SOD
PAVED AREA
SAW CUT AND SEAL EXISTING
6"
MATERIAL (12" LAYERS)
COMPACTED EXCAVATED
(8" MAX LAYERS) OR
STRUCTURAL BACKFILL
COMPLETE COMPACTED
M43 100% CRUSHED STONE)
(COMPACTED AASHTO
PIPE BEDDING
O.D. +16" (MAX)
TRENCH WIDTH
6"
I
E
6"
4" MIN
V A
R I A
B L
E
PIPE BEDDING & TRENCH
NOT TO SCALE
PIPE BEDDING MATERIALS
DIAMETER
M43 SIZE
AASHTO
GREATER THAN 30"
15"-30"
LESS THAN 15"
NO.57
NO.67
NO.8
R/W
OUTSIDE
R/W
INSIDE
COURSE ON 10" AGGREGATE BASE.
4. ALL SURFACE RESTORATION SHALL BE 2-2" COURSES OF ASPHALT SURFACE
SHALL BE CLEANED AF ALL DIRT, MUD AND DEBRIS.
3. DURING CONSTRUCTION AND UPON COMPLETION OF THE WORK THE AREA
INSURE AGAINST SETTLEMENT.
2. ALL BACKFILL MATERIAL SHALL BE COMPACTED IN UNIFORM LAYERS TO
WITH THE CONTRUCTION DRAWINGS.
DEVICES AND THE MAINTENANCE OF TRAFFIC PLAN SHALL BE IN ACCORDANCE
1. TRAFFICE SHALL BE MAINTAINED AT ALL TIMES. ALL TRAFFIC CONTROL
NOTE:
CONTRACT: FA8601-12-D-0005
REPL COOLING TOWER F10262 F10266
PROJECT - ZHTV040019
K Z F
.0
F
U L L S
IZ
E P
R
IN
T
X
MOW STRIP DETAIL
CURB AND GUTTER
C600
DETAILS
C I
V
IL
ENGIN
E E R
USAF
OF
DESIGN CHIEF
DATE
TEL 513 621 6211
W PAFB
WRIGHT-PATTERSON AIR FORCE BASE
88TH ABW
SEAL
* * * SUPPORT VALUE ENGINEERING - IT PAYS * * *
* * * SAFETY PAYS * * *
CHECKED P. BATTAGLIADRAWN K. ELLIOTTDESIGNED J. BENEDICT
S T
A T
E OF O
H
IO
P R
O F
E
S S
IONAL
E N
G I N
E E
R
R
E
GISTERE
D
E51255
BATTAGLIA
23 JUN 15
GRATE
B
C
AB
SECTION A-A SECTION B-B
AA A
B
B B
CCC
B A
CONST. JOINT
PERMISSIBLE
A
PLANSECTION C-C
FLOWLINE
NOTES
ROUNDED ‚" RADII
ALL GRATE EDGES TO BE
GRATE
FLOWLINE
GRATE
CONST. JOINT
PERMISSIBLE
V A
R
IA
B L
P T
H
M A
X
2'-0"8" 8" 8" 2'-0"
2'-3•"
8"
8"
2'-0"
8"
BOTTOM SHAPED TO DRAIN
PLACED ON TOP OF IT WITH THE
SEPARATELY AND THE OUTLET PIPE
BOTTOM SLAB MAY BE PRECAST
" 2
1" 2"
1"
‚"2'-3•"2'-3•"‚" ‚"
1"
2‚"2‚"
8" 8"
WITH GROUT.
FIELD CUT. THE INTERSTITIAL SPACE SHALL BE FILLED
PIPE BEING SUPPLIED PLUS 2" WHEN FABRICATED OR
OPENINGS: PIPE OPENINGS SHALL BE THE O.D. OF THE
ARE AT THE TOP CENTER OF THE GRATE.
LOCATION AND ELEVATION: LOCATION AND ELEVATION
SHALL NOT BE USED TO ADJUST THE TOP ELEVATION.
ELEVATION SPECIFIED IN THE PLANS. LAYERS OF BRICK
BE PLACED ON THE BASE TO PROVIDE THE GRATE
SHALL BE SET DEEP ENOUGH SO THAT THE TOP CAN
PRECAST BASE: IF A PRECAST BASE IS USED, IT
SECTION 03307A.
MEET THE REQUIREMENTS OF SPECIFICATION
CONCRETE: CAST-IN PLACE CONCRETE SHALL
WITHOUT DAMAGE.
SUFFICIENTLY TO PERMIT SHIPPING AND HANDLING
A MINIMUM THICKNESS OF 6" AND BE REINFORCED
THICKNESS OF 8". PRECAST WALLS SHALL HAVE
WALLS: CAST-IN-PLACE WALLS HAVE A NOMINAL
NO. 5110 TYPE M3 OR APPROVED EQUALS.
GRATE: NEENAH NO. R-4859-C OR EAST JORDAN
CONCRETE JOINT
CONCRETE JOINT
CONCRETE JOINT
CONCRETE JOINT
3.00'
.2
7.30'
.8
4.50'
.0
14.10'12.00'12.00' 12.00'12.00'
.2
12.00'
CONTRACT: FA8601-12-D-0005
REPL COOLING TOWER F10262 F10266
PROJECT - ZHTV040019
K Z F
.0
F
U L L S
IZ
E P
R
IN
T
X
C601
DETAILS
IRON GRATE
WOVEN MONOFILAMENT
IRON GRATE
DANDY BAG
TM
MAINTENANCE:
IP
TM
DANDY BAG
TM
FEDERAL GUIDELINES
30 SIEVE SIZE MEETS
UNIT WITH GRATE
MOVEMENT OF
ALLOW EASY
LIFTING STRAPS
needed.
inside envelope as fine material from point shovel. Remove broom or square needed with stiff surface of unit as sediment from
Remove dried
CATCH BASIN:
TO INSPECT
unit.
basin and replace inspect catch grate inside, Remove unit with
AND CURB APPEAL.
WITH INLET FOR SAFTY
DANDY BAG LAYS FLUSH
OF STORM SEWER AND PRIOR TO PAVING OPERATIONS.
TO BE USED ON ALL STRUCTURES AFTER INSTALLATION
NOT TO SCALE
INLET SEDIMENT FILTER
DANDY BAG DROP
CB (APPROVED FOR USE IN GRASS AREAS ONLY)
CONCRETE SIDEWALK DETAIL
SECTION A-A
PLAN VIEW
A
A
AROUND ALL EXPOSED SURFACES.
3. PROVIDE A MINIMUM OF 2" EDGING
500, CAST-IN-PLACE CONCRETE.
2. CONCRETE SHALL CONFORM TO ITEM
EXPOSED SURFACES.
1. PROVIDE BROOM FINISH TO ALL
NOTES:
REQUIRED
DOWN AS
SLOPE UP OR
CLASS "A" CONCRETE
5'-0"
40'-0"
CURB
VARIABLE
B/W
SLOPE=1/4" PER 1'-0"
1" JOINTER CUTS
EXPANSION JOINT
PREMOLDED EXPANSION JOINT
PREMOLDED
AGGREGATE BASE
VARIABLE
1'-0" 4'-0" OR 5'-0"
SECTION C-C
7"
6'-0"
7"
5"4'-0"5"
V A
R I
STANDARD MANHOLE DETAIL
INCLUDING MORTAR JOINT
COLLAR LIMITED TO 3"
PRECASTING ADJUSTING
STEPS (#3 STEEL ROD)
PLASTIC COATED MANHOLE
O-RING GASKET
P.V.C. OR A.B.S. PIPE
TO BE USED WITH
RUBBER WATER STOPS
OF EXCAVATION
EXTEND TO LIMITS
CONCRETE CRADLE TO
AT 8" C/C EACH WAY
REINFORCE WITH #4 BARS
M F
G 'S
T
A N
D A
R D
(O P
E N I
O
B
EITHER ROUND OR SQUARE
BOTTOM OF SLAB MAY BE
CONCRETE CRADLE
JOINT AT THE END OF
CONCRETE CRADLE
STEPS TO BE ALIGNED
NEENAH R-1762 OR EQUAL
MANHOLE FRAME AND COVER
MORTAR BED
FULL PORTLAND CEMENT
SET FRAME CASTING IN
BE IN 6" LIFTS FROM UNDISTURBED SOIL.
OF STANDARD PROCTOR COMPACTION TO
SOIL OR FILL MATERIAL COMPACTED TO 90%
FOUNDATION TO BE ON UNDISTURBED
OF 6" BED OF #9 CRUSHED STONE.
M.H. TO BE SET ON FOUNDATION
NOTE:
RINGS
PRECAST CONCRETE
WITH INTERIOR WALL
PIPE CUT FLUSH
BED OF #9 CRUSHED STONE
CONCRETE CRADLE ON 6"
FLO
W 4"
1. SET THE STAKES
4"
FLO
W
2. EXCAVATE A 4" X 4" TRENCH UPSLOPE
ALONG THE LINE OF STAKES.
FLO
W
3. STAPLE FILTER MATERIAL TO STAKES
AND EXTEND IT ITO THE TRENCH.
FLO
W
4. BACKFILL AND COMPACT THE
EXCAVATED SOIL.
CONSTRUCTION OF A
FILTER BARRIER (SILT FENCE)
SF
CONCRETE JOINT PLAN
C I
V
IL
ENGIN
E E R
USAF
OF
DESIGN CHIEF
DATE
TEL 513 621 6211
W PAFB
WRIGHT-PATTERSON AIR FORCE BASE
88TH ABW
SEAL
* * * SUPPORT VALUE ENGINEERING - IT PAYS * * *
* * * SAFETY PAYS * * *
CHECKED P. BATTAGLIADRAWN K. ELLIOTTDESIGNED J. BENEDICT
CORRECTED FINAL
23 JUN 15
S101
S101
"A" "A" "A" "A""B"
"A" "A" "A" "A""B"
S101
A
S101
A
S101
APPROVED EQUAL
BY VULCRAFT OR
(18 GA.) ROOF DECK
GALVANIZED 3N18
SPAN DIRECTION OF
B
S102
SCALE: „" = 1'-0"
COOLING TOWER SUPPORT LAYOUT FOUNDATION & FRAMING PLAN
HS
S1
2X1
2XŠ
(T
YP.
ON SITE DRAWINGS
DETERMINED BASED
LOCATIONS TO BE
S102
2.5
S102
2.6
W. PETERSONS. MITCHELL
S T
A
TE OFO
H
Ol
P R
O
FESSONAL ENG
N
E E R
R
EGSTE
ER
D
DAVID
M.
SCHIERLOH
E-50243
CONTRACT: FA8601-12-D-0005
REPL COOLING TOWER F10262 F10266
PROJECT - ZHTV040019
K Z F
.0
F
U L L S
IZ
E P
R
IN
T
X
NOTE:
NOTE:NOTE:
S100
STRUCTURAL DETAILS
Ž
Ž
4'-0„"12'-0"14'-1•"11'-11•"11'-11•"4'-6"11'-11•"11'-11•"8'-4„"
90'-9Ž"
20'-0" MAX.
3'-6"6" 6"
TO EXCEED 20'-0"
COLUMN SPACING NOT
(SIM.)
BEAM X 26'-0" LONG (TYP.)
W6X25 GALVANIZED
(TYP. 12 LOCATIONS)
1'-6" SQ. CONC. PIERS
STEEL BEAMS SHALL BE FRAMED FLUSH & LEVEL
THE TOP SURFACE OF THE SUPPORTING
(TYP.)
ANY CONFLICTS AT FOOTINGS
MECHANICAL & TOWER MANUFACTURER FOR
COORDINATE AS-NEEDED BETWEEN STRUCTURAL,
BUILDING
CHEMICAL
HAND)
(OPP.
W6X25 GALVANIZED BEAM
(BY OTHERS)
FIBERGLASS GRATING
@ 1'-6" O.C. E.W.
SLAB-ON-GRADE W/#4 BARS
6" REINFORCED CONCRETE
SCREEN WALL (TYP.)
OUTSIDE FACE OF
(BY OTHERS)
DOOR FRAMING
ATTACHMENT (BY OTHERS) (TYP.)
GALVANIZED C5X6.7 FOR RAILING
C I
V
IL
ENGIN
E E R
USAF
OF
DESIGN CHIEF
DATE
TEL 513 621 6211
W PAFB
WRIGHT-PATTERSON AIR FORCE BASE
88TH ABW
SEAL
* * * SUPPORT VALUE ENGINEERING - IT PAYS * * *
* * * SAFETY PAYS * * *
CHECKED P. BATTAGLIADRAWN K. ELLIOTTDESIGNED J. BENEDICT
CORRECTED FINAL
23 JUN 15
NOT TO SCALE
SLEEVE DETAIL
A
NOT TO SCALE
DETAIL
S100 NOT TO SCALE
EMBEDDED PLATE DETAIL
NOT TO SCALE
SECTION
S100
ELEV. 97'-6"
TOP/FTG.
2.1
NOT TO SCALE
SECTION
S100
ELEV. 97'-6"
TOP/FTG.
2.2
NOT TO SCALE
SECTION
S100
S101
NOT TO SCALE
SECTION
S100
NOT TO SCALE
SECTION
S101
ELEV. 100'-0"
TOP/SLAB
ELEV. 100'-0"
TOP/SLAB
ELEV. VARIES
TOP/SLAB
NOT TO SCALE
TYP. W6X25 BEAM DETAILS
T/PIER
ELEV. VARIES
TOP/SLAB
@ 115'-0"
T/SCREEN
@ 114'-0"
T/COLUMN
FIN. FLOOR ELEV. VARIES
103'-6"
2'-0"
" 2'-0"
S. MITCHELL W. PETERSON
S T
A
TE OFO
H
Ol
P R
O
FESSONAL ENG
N
E E R
R
EGSTE
ER
D
DAVID
M.
SCHIERLOH
E-50243
CONTRACT: FA8601-12-D-0005
REPL COOLING TOWER F10262 F10266
PROJECT - ZHTV040019
K Z F
.0
F
U L L S
IZ
E P
R
IN
T
X
NOTE:
PLAN
NOTE:
NOTE:
S101
STRUCTURAL DETAILS
1'-1"
10"
1'-1"
1•" 1•"
6•" 6•"
TYP
TYP
S P
A C
IN
B
T W
E
IR
T S
M A
X
2'-6"
2'-0"
8" 8" 8"
C L
R
2'-0"
8" 8" 8"
C L
R
C L
R
1'-6"
3" CLR.
M
IN
11'-8ƒ"1'-0•" 11'-8ƒ" 1'-0•"
6"6" 6" 6"
5•"
6"
2ƒ"2ƒ"
6"
W6X25 X 26'-0"
E N
G R
F
IL
L
M
IN
(TYP.)
3" CLR.
IE
O .C
O .C
M A
X
1'-3" 1'-3"
‰ 6EMBEDED ¾
BEAM TO
C L
R
C L
R
D
M
IN
V A
R
¾•X13X1'-1"
(TYP. 4 SIDES)
¾ …X12†X6'-0"
BAR ANCHOR
A496 DEFORMED
•"¿X2'-0"
½ PIER
BEAM
BEAM
CHANNEL
¾ (TYP.)
STIFFENER
FLANGES
COPE
SHOWN FOR CLARITY
PIER & GRATING NOT
•"¿X6" STUDS
¾…X13X1'-1"
GALVANIZED
½ Œ"¿ HOLES
ALONG PERIMETER)
HSS8X6X‰ (TYP.
(SUPPLIED BY MANUF.)
ALUM. VERTICAL SUPPORTS
@ COLUMN LOCATIONS)
HSS12X12XŠ (TYP.
ALONG PERIMETER)
HSS8X6X‰ (TYP.
CENTERED ON FOOTING
HSS12X12XŠ
WALL
SCREEN
FINISH GRADE
CONCRETE SLAB
(T Y
P
(SEE PLAN)
INTERIOR CONCRETE SLAB
2-#5 CONT. TOP & BOTTOM
BOND BREAKER
AT PERIMETER WALL FOR
TURN UP VAPOR BARRIER
W/ 32" MIN. LAP
IN GROUTED CELL
W/ #5 @ 1'-4" O.C.
8" SPLIT-FACE CMU
(T Y
P
(SEE PLAN)
INTERIOR CONCRETE SLAB
2-#5 CONT. TOP & BOTTOM
BOND BREAKER
AT PERIMETER WALL FOR
TURN UP VAPOR BARRIER CMU (BEYOND)
8" SPLIT-FACE
#4 BENT BAR @ 1'-4" O.C. #4 BENT BAR @ 1'-4" O.C.
REINFORCING STEEL
½ FTG. & PIER
IN PIER
EA. VERTICAL BAR
#5 BENT BAR @
2'-0"
1'-6" SQ. PIER (TYP.)
#4 TIES @ 1'-0" O.C.
(TYP.)
W/ 32" MIN. LAP
#5 VERTICAL BARS
CONCRETE FROM ENTERING SLEEVE
TIME OF CASTING TO PREVENT
SEAL OFF TOP OF SLEEVE @
EXTERIOR SLAB
FIN. SLAB ELEV.
MATERIAL
•" THICK COMPRESSIBLE
BURIED 14'-8" DEEP
FOOTING, 2'-6" DIA.,
CIRCULAR COLUMN
½ BEAM
EACH SIDE OF WEB
½ OF ‚" STIFFENER PLATE
½ OF ‚" STIFFENER PLATE EACH SIDE OF WEB
4.6 ANCHOR BOLTS (TYP. U.N.O.)
ASTM A307 OR M20 GRADE
½ OF HOLES FOR ƒ"¿
EXTERIOR SLAB
FULL HEIGHT OF PIER
7-#6 SPACED EVENLY,
ADDITIONAL #4 TIE
BEAM
PLATE CENTERED ON PIER
EMBEDDED GALVANIZED
STIFFENER ¾ (TYP.)
12-#5 VERTICAL BARS
#4 TIES
6" CONC. SLAB
TOUCH UP WELDS W/ ZINC RICH PAINT
8"
FOUNDATION WALLFOUNDATION WALL
8"
#4 BENT BAR @ 1'-6" O.C. E.W. #4 BENT BAR @ 1'-6" O.C. E.W.
‚" CAP PLATE
CENTERED IN FOOTING
COLUMN SLEEVE
½ FOOTING & COLUMN
NEEDED
WINDOW AS
W/ 2" DRAINAGE
CONCRETE CURB
1'-9" X 6"
CONTINUOUS
C I
V
IL
ENGIN
E E R
USAF
OF
DESIGN CHIEF
DATE
TEL 513 621 6211
W PAFB
WRIGHT-PATTERSON AIR FORCE BASE
88TH ABW
SEAL
* * * SUPPORT VALUE ENGINEERING - IT PAYS * * *
* * * SAFETY PAYS * * *
CHECKED P. BATTAGLIADRAWN K. ELLIOTTDESIGNED J. BENEDICT
CORRECTED FINAL
23 JUN 15
NOT TO SCALE
SECTION
S202
2.3
S T
N
S
H
S
X
X
S T
N
S
S
X
X
S T
N
S
S
X
X
S T
N
S
S
X
X
ELEV. 100'-0"
TOP/SLAB
2'-0"
2'-0"
NOT TO SCALE
SECTION
S102
2.4
S102
2.3
S102
2.3
S102
2.3
S102
2.4
S101
2.1
S101
2.1
S101
2.2
S101
2.1
B
NOT TO SCALE
DETAIL
S100
S102
C
OF TRENCH W/ EPOXY
COAT WALLS AND BASE
CONCRETE PAD
REINFORCED
7'-0" X 7'-0"
REINFORCING @ PAD
E.W. TOP & BOTTOM, TYP.
#5 BARS @ 1'-6" O.C.
NOT TO SCALE
SECTION
S102
C
W/ ZINC RICH PAINT
TOUCH UP WELDS
W/ ZINC RICH PAINT
TOUCH UP WELDS
NOT TO SCALE
SECTION
S100
2.6
NOT TO SCALE
SECTION
S100
2.5
JAMB REINFORCEMENT DETAIL CORNER DETAIL
SCALE: NOT TO SCALE
MASONRY DETAILS
JAMB REINFORCEMENT DETAIL
C.M.U. LINTEL
SCALE: NOT TO SCALE
LINTEL DETAIL
C.M.U. LINTEL
S T
A
TE OFO
H
Ol
P R
O
FESSONAL ENG
N
E E R
R
EGSTE
ER
D
DAVID
M.
SCHIERLOH
E-50243
CONTRACT: FA8601-12-D-0005
REPL COOLING TOWER F10262 F10266
PROJECT - ZHTV040019
K Z F
.0
F
U L L S
IZ
E P
R
IN
T
X
NOTE:
NOTE:
NOTE:
LINTEL NOTES:
S102
STRUCTURAL DETAILS
S. MITCHELL W. PETERSON
GUIDELINES FOR MIXING/INSTALLATION.
ARE TO BE WATER-TIGHT. USE MFR.S
LOCATIONS WHERE CONCRETE SURFACES
PROVIDE XYPEX ADMIXTURE C-500 IN ALL
NOTE:
1'-10…"7'-0"1'-10…"
12'-0"
1'-6"4'-0"1'-6"
4'-2"
2" 2"
1'-0"
8"2" 2"
6"6"
TYP ‰ 3
6" O.C.
6" O.C.
MASONRY OPENINGJAMB WIDTH MASONRY OPENINGJAMB WIDTH
SEE NOTE 2
MASONRY OPENING WIDTH
SEE NOTE 2
(BY OTHERS)
1" FIBERGLASS GRATING
@ 1'-6" O.C. MAX.
MIN. 3•" EMBEDMENT
•"¿ ANCHOR RODS WITH
HIT-HY 200 + HAS-R 316
ALONG TRENCH @ WALL
STN/STL L4X2X…", CONT.
2'-0" O.C. (TYP.)
W/•"¿X4" STUD @
STN/STL L2X1‚X‚"
(BY OTHERS)
1" FIBERGLASS GRATING
STN/STL HSS4X4X‚"
7'-0X7'-0" RC PAD
MAX., TYP. @ PERIMETER
#4 BENT BAR @ 1'-6"
@ 1'-6" MAX.
#4 BENT BAR
O.C. E.W.
#4 BARS @ 1'-6"
O.C. E.W.
#4 BARS @ 1'-6"
L6X4
PAD)
2'-0" O.C. (TYP. AROUND
W/•"¿X4" STUD @
STN/STL L2X1‚X‚"
LIVE LOAD)
(MIN. RATING 60 PSF
(BY OTHERS)
FIBERGLASS GRATING
L6X4X…X1'-0"
STN/STL
STN/STL HSS4X4X‚"
STEEL DECK
3"-18 GA. GALV.
•"¿X5 STUDS @ 1'-6" O.C.
CONT. ¾ ‚X4" W/
W/2-#5 CONT.
BOND BEAM
BOND BEAM
EXTEND INTO
#5 @ 1'-4" O.C.
1'-4" 0.C.
REINFORCING @
HORIZONTAL JOINT
STEEL DECK
3"-18 GA. GALV.
•"¿X5 STUDS @ 1'-6" O.C.
CONT. ¾ ‚X4" W/
W/2-#5 CONT.
BOND BEAM
BOND BEAM
EXTEND INTO
#5 @ 1'-4" O.C.
1'-4" 0.C.
REINFORCING @
HORIZONTAL JOINT
GROUTED CELL
#5 CENTERED IN
UP TO 4'-0" IN WIDTH
FOR MASONRY OPENINGS
UP TO 9'-0" IN WIDTH
FOR MASONRY OPENINGS
MIN EMBEDMENT
ANCHOR RODS W/ 3•"
HIT-HY 200 + HAS •"¿
½ Œ"¿ HOLES FOR
CMU WALL
REINFORCING
W/ 2-#5 CONT.
8" DEEP LINTEL
UP TO 4'-0" IN WIDTH
FOR MASONRY OPENINGS
OPENING
MASONRY
TOP OF
8" OR 16" LINTEL
(TYP. @ ALL C.M.U. WALL OPENINGS)
REINFORCING
JAMB
JAMB
SPANS GREATER THAN 8'-0" U.N.O.
LINTELS SHALL HAVE A MINIMUM BEARING OF 8" FOR SPANS UP TO 8'-0" AND 1'-4" FOR 2.
OR PLUMBING OPENING IN A MASONRY WALL WITH A WIDTH EQUAL TO OR GREATER THAN 1'-0".
ARCHITECTURAL DRAWINGS. IN ADDITION, LINTELS ARE REQUIRED FOR ANY MECHANICAL, ELECTRICAL, LINTELS SHALL BE PROVIDED FOR ALL OPENINGS AS INDICATED ON THE STRUCTURAL AND1.
BOTTOM)
(2 TOP & 2
W/ 4-#5 CONT.
16" DEEP LINTEL
UP TO 9'-0" IN WIDTH
FOR MASONRY OPENINGS
CMU WALL
OPENING
MASONRY
TOP OF
AAD
AAV
ACM
AD
AF
AFF
AFG
AL
ALV
AP
AS
ATV
AV
AMPERE
AUTOMATIC AIR DAMPER
AUTOMATIC AIR VENT
AIR COMPRESSOR
AREA DRAIN
AIR FILTER
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
ALUMINUM
ALARM VALVE
ACCESS PANEL
AIR SEPARATOR
ATMOSPHERIC VENT
AIR VENT
BDD
BFP
BHP
BOD
BOP
BOT
BTU
BTUH
BACKFLOW PREVENTER
BRAKE HORSEPOWER
BOTTOM OF DUCT
BOTTOM OF PIPE
BOTTOM
BRITISH THERMAL UNIT
BRITISH THERMAL UNIT PER HOUR
CA
CB
CF
CFH
CFM
CH
CHR
CHS
CI
CIP
CKV
CO
COMP
CR
CT
C
CWR
CWS
COMPRESSED AIR
CATCH BASIN
CHEMICAL FEED
CUBIC FEET PER HOUR
CUBIC FEET PER MINUTE
CHILLER
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CAST IRON
CAST IRON PIPE
CHECK VALVE
CLEANOUT
COMPRESSOR
CONDENSATE RETURN (STEAM)
COOLING TOWER
COPPER
COEFFICIENT, VALVE FLOW
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
DB ****
DB ****
DCW
DHW
DHWR
DHWS
DIA
DM
DN
DPI
DPS
DPT
DPR
DWG
DECIBEL
DOMESTIC COLD WATER
DOMESTIC HOT WATER
DOMESTIC HOT WATER RETURN
DOMESTIC HOT WATER SUPPLY
DIAMETER
DAMPER MOTOR
DOWN
DIFFERENTIAL PRESSURE INDICATOR
DIFFERENTIAL PRESSURE SWITCH
DIFFERENTIAL PRESSURE TRANSMITTER
DAMPER
DRAWING
EA
EF
EFF
ESEW
ET
EWT
EXH
EXHAUST AIR
EXHAUST AIR FAN
EFFICIENCY
EMERGENCY SHOWER & EYE WASH
EXPANSION TANK
ENTERING WATER TEMPERATURE
EXHAUST
EXISTING
FE
FLEX
FLR
FPM
FPS
FS
FT
FAHRENHEIT TEMPERATURE
FLOOR DRAIN
FIRE EXTINGUISHER
FLEXIBLE CONNECTOR
FLOOR
FEET PER MINUTE
FEET PER SECOND
FLOW SWITCH
FEET
GA
GAL
GALV
GCO
GPM
GAUGE OR GAGE
GALLON
GALVANIZED
GRADE CLEANOUT
GALLONS PER MINUTE
HB
HP
HPC
HPS
HR
HTG
HX
HZ
HOSE BIBB
HORSEPOWER
HIGH PRESSURE CONDENSATE RETURN
HIGH PRESSURE STEAM SUPPLY
HOUR
HEATING
HEAT EXCHANGER
HERTZ
IA
ID
IE
IN
INV
INSTRUMENT COMPRESSED AIR
INSIDE DIAMETER
INVERT ELEVATION
INCHES
INVERT
KW
KWH
KILOWATT
KILOWATT-HOUR
M
MAV
MAX
MBH
MECH
MIN
MR
MAIN CONTROL AIR SUPPLY
MANUAL AIR VENT
MAXIMUM
MECHANICAL
MINIMUM
MOP RECEPTOR
NO
NPSH
NTS
NORMALLY CLOSED
NORMALLY OPEN
NET POSITIVE SUCTION HEAD
NOT TO SCALE
OAWB
OD
OS&Y
OUTSIDE DIAMETER
OUTSIDE SCREW & YOKE
PH
PI
PRS
PRV
PSF
PSI
PSIA
PSIG
PRESSURE GAUGE
PHASE
PRESSURE INDICATOR
PRESSURE REDUCING STATION
PRESSURE REDUCING VALVE
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
POUNDS PER SQUARE INCH - ABSOLUTE
POUNDS PER SQUARE INCH - GAUGE
SAN
SCH
SPRK
SQIN
SR
SV
SANITARY SEWER
SCHEDULE
SQUARE FOOT
STATIC PRESSURE
SPRINKLER
SQUARE INCHES
SUPPLY RISER
STAINLESS STEEL
SERVICE SINK
STORM SEWER
SAFETY VALVE
T
T&PV
TCP
TCV
TEMP
TK
TOD
TOP
TW
TYP
THERMOSTAT
TEMPERATURE & PRESSURE RELIEF VALVE
TEMPERATURE CONTROL PANEL
TEMPERATURE CONTROL VALVE
TEMPERATURE
TANK
TOP OF DUCT
TOP OF PIPE
TREATED WATER
TYPICAL
UG
UH
UNDERGROUND
UNIT HEATER
V ****
V ****
VCP
VEL
VTR
VENT
VOLT
VITRIFIED CLAY PIPE
VELOCITY
VENT THROUGH ROOF
BACK DRAFT DAMPER
DRY-BULB TEMPERATURE
F
FREEZEPROOF WALL HYDRANT
OUTSIDE AIR WET-BULB TEMPERATURE
RM
RPM
ROOM
REVOLUTIONS PER MINUTE
WET-BULB TEMPERATUREWB
STANDARD MECHANICAL ABBREVIATIONS
DRAWING NOTE HEX
GENERAL SYMBOLS
DETAIL OUTLINE
DETAIL OR SECTION BUBBLEA
M3
USE "LETTERS" FOR SECTIONS
USE "NUMBERS" FOR DETAILS
AHU-1 EQUIPMENT MARK NUMBER
SHEET NUMBER WHERE SECTION/DETAIL IS SHOWN
SANITARY WASTE STACK AND VENT NUMBER
COLD WATER
HOT WATER
HOT WATER RETURN
VENT PIPING
S1
FLOOR PENETRATION LINE (ISOMETRIC)
VENT THRU ROOF (ISOMETRIC)
PLUMBING SYMBOLS
WATER ISOMETRIC NUMBER
FLOOR DRAIN W/ TRAP
(ABV)
(ABV=TYPE; SEE ABBREVIATIONS)
FLOOR OR GRADE CLEANOUT
BALL VALVE
BUTTERFLY VALVE
GATE VALVE
GLOBE VALVE
RELIEF VALVE
45 DEGREE DROP
PIPE ELBOW DOWN
PIPE ELBOW UP
PRESSURE REDUCING VALVE
CHECK VALVE
CALIBRATED BALANCING VALVE
STRAINER
UNION
FLEXIBLE CONNECTION
O.S. & Y VALVE
PIPE TEE DOWN
PIPE TEE UP
BLOW-OFF STRAINER
ABBREVIATION OF PIPE CONTENTS
AUTOMATIC AIR VENT
PUMP
ABBREVIATION OF ITEM
ABBREVIATION OF ITEM
THERMOMETER
ABV
ABV.
PIPING SYMBOLS
AAV
MAV
MANUAL AIR VENT
PIPE CAP
PITCH OF PIPE (R = RISE; D = DROP)
IN DIRECTION OF FLOW
R
ABV.
HVAC DUCTWORK SYMBOLS
UNIT HEATER, HORIZONTAL THROW
ELECTRIC MOTOR, VALVE ACTUATOR
C
NC
NO
THREE-WAY CONTROL VALVE
(C=CLOSED; NC=NORMALLY CLOSED; NO=NORMALLY OPEN)
STANDARD MECHANICAL SYMBOLS
HVAC CONTROL SYMBOLS
PUMP
EXIST
ATP AUTOMATIC TRAP PRIMER
SS****
SS****
NOTES:
AND ABBREVIATIONS AND APPLIES TO THE SET OF
DRAWINGS TO THE EXTENT APPLICABLE.
B. **** INDICATES MULTIPLE ABBREVIATIONS. REFER
PRESSURE/TEMPERATURE PORT
PUMP SUCTION DIFFUSER
PSD
A. THIS LEGEND IS COMPOSED OF STANDARD SYMBOLS
ROOM THERMOSTAT
T
HOR HORIZONTAL
CHP CHILLED WATER PUMP
V
EAT ENTERING AIR TEMPERATURE
FCO FLOOR CLEANOUT
PRESSURE DROP OR DIFFERENTIAL
OAT OUTSIDE AIR TEMPERATURE
NC**** NOISE CRITERIA
NC****
N/A NOT APPLICABLE
P****
P****
P/T PRESSURE/TEMPERATURE
PRESS PRESSURE
MCA MINIMUM CIRCUIT AMPS
MUW
MAKEUP WATER
SAT SUPPLY AIR TEMPERATURE
SPL SOUND POWER LEVEL
SPEC SPECIFICATION
SQ SQUARE
STD STANDARD
SUCT SUCTION
TEMPERATURE DIFFERENCE
U U FACTOR
VERT
VOL VOLUME
VERTICAL
ONE THOUSAND BRITISH THERMAL
UNITS PER HOUR
H
O
WATER
TO THE DRAWINGS FOR EXACT MEANING.
RPBFP REDUCED PRESSURE BACK FLOW PREVENTER
PIPING
OR
OR
TWO-WAY CONTROL VALVE ( BUTTERFLY)
TWO-WAY CONTROL VALVE (GLOBE OR GATE)
CU
FD
FPWH
LINEAR FOOT
LEAVING WATER TEMPERATURE
LF
LWT
LOUVERL
LAT LEAVING AIR TEMPERATURE
PD
SF
SP
ST
TD
THERMAL WELL
EXISTING TO REMAIN
REMOVE (DEMOLITION DRAWINGS)
NEW WORK (NEW WORK DRAWINGS)
FLEXIBLE CONNECTOR
POINT OF NEW WORK CONNECTION
COORDINATOR ENGINEERING CHIEF
DATE REVISION BY
NO. DATE NO. REVISION BY
C
I
V
I
L
E N
G
I
N
E
E
R
US AF
OF
DESIGN CHIEF
DATEDRAWNDESIGNED CHECKED
CONTRACT: FA8601-12-D-0005PROJECT - ZHTV040019
WPAFB
WRIGHT-PATTERSON AIR FORCE BASE
23 JUN 15
88TH ABW
SEAL
K Z
F
CORRECTED FINAL
F U
Z
E
P
R I N
X
M
FD
FD
FD
FD
FD
CH-3
CH-2
CH-1
FD
FD
FD
FD
FD
FD
51x23 W/
INSULATION
51x23 W/
INSULATION
ELECTRICAL MAIN
DISTRIBUTION PANEL
(MDP)
ELECTRICAL MOTOR
CONTROL PANEL (MCC-2)
CHILLER 3
POWER PANEL
CHILLER 2
POWER PANEL
CHILLER 1
POWER PANEL
8" (BOP 10'-5"AFF)
8" (BOP 8'-8"AFF)
12"
12"
8"
8"
16" (BOP 10'-0"AFF)
12"
6"
6"
10" 10"
8" FROM BLDG 266
8" TO BLDG 266
TO BLDG 262 BASEMENT W.
FROM BLDG 262 BASEMENT W.
FD
(BOD 7'-8"
AFF)
(BOD 7'-8"
AFF)
8"
10"
12"
12"
03 16
04 16
04 16
04 16
DN
7'-10" BOP
CHR
VENTILATION
DUCT (TYP)
CONCRETE
PAD (TYP)
16" (BOP
8'-10"AFF)
12" (BOP 10'-0" AFF)
12" (BOP
10'-0" AFF)
8" (BOP
10'-2" AFF)
TO BLDG 262 BASEMENT E.
FROM BLDG 262 BASEMENT E.
8" (BOP 9'-1" AFF)
12" (BOP 10'-3" AFF)
12" (BOP 10'-3" AFF)
10"
20" (BOP 8'-3" AFF)
CONDENSER
WATER RETURN
20" (BOP 0'-8" AFF)
CONDENSER
WATER SUPPLY
10" CHS & CHR UP TO
1ST & 2ND FLOORS
OF BLDG 262
(BOP 10'-3" AFF)
UH
12" (BOP 8'-6" AFF)
EXISTING PIPING
BOP 9'-2"
CHR
CHS
UH
CHS
UTILITY SINK
FD
FD
CHR
REDLIGHT
WARNING SIGN
FLOOR
TRENCH
W/COVER
(TYP)
CHEMICAL
TANKS (TYP)
CONCRETE
PAD (TYP)
CONCRETE
PAD (TYP)
3"
3"
TO COOLING TOWERS
CHP-1
CHP-2
CHP-4
CHP-3
CWP-1
CWP-4
(STANDBY)
CWP-2
CWP-3
10" UP TO BLDG. 262
FIRST AND SECOND
FLOOR
CHR
CHS
CHS
CHR
CHS
CHR
CHS
CHS
CHR
CHR
CWR
CWS
CWS
CWR
CWS
CWR
ELECTRICAL MOTOR
CONTROL PANEL (MCC-1)
RUPTURE DISC
RELIEF PIPING
12"
12" (TYP)
8" (TYP)
DN
COORDINATOR ENGINEERING CHIEF
DATE REVISION BY
NO. DATE NO. REVISION BY
C
I
V
I
L
E N
G
I
N
E
E
R
US AF
OF
DESIGN CHIEF
DATEDRAWNDESIGNED CHECKED
CONTRACT: FA8601-12-D-0005PROJECT - ZHTV040019
WPAFB
WRIGHT-PATTERSON AIR FORCE BASE
23 JUN 15
88TH ABW
SEAL
K Z
CORRECTED FINAL
F U
Z
E
P
R I N
X
PARTIAL ENLARGED BASEMENT FLOOR PLAN
BUILDING 10262 CHILLER PLANT
01 CONDENSER WATER PUMP: B&G MODEL VSCS-F-9.5-BF-RHR,
1800 GPM, 60 FT. HEAD, 40 HP, 460 VOLT, 3 PHASE
02 CONDENSER WATER PUMP: B&G MODEL VSCS-F-11-BF-RHR,
3900 GPM, 77 FT. HEAD, 100 HP, 460 VOLT, 3 PHASE
03 CHILLED WATER PUMP: B&G MODEL VSC-11.25-BF-C-RHR,
1440 GPM, 125 FT. HEAD, 75 HP, 460 VOLT, 3 PHASE
04 CHILLED WATER PUMP: B&G MODEL VSC-12.75-BF-O-RHR,
3120 GPM, 150 FT. HEAD, 200 HP, 460 VOLT, 3 PHASE
05 CHILLER: YORK MODEL YKN43G4-CTL-YDHA-41DD, NOMINAL 596 TON
(R22 REFRIGERANT).
06 CHILLER: YORK MODEL YKQ4R3H2-DBC-YDHB-57DD, NOMINAL 1300 TON
(R22 REFRIGERANT).
07 AIR SEPARATOR WITH MAKE UP WATER CONNECTION
08 EXPANSION TANK
09 CHILLED WATER CHEMICAL SHOT FEEDER
10 EXHAUST FAN
11 CONDENSER WATER BLOW DOWN. DISCONNECT FROM CONDENSER WATER PIPING AND SAVE FOR
RECONNECTION TO NEW PIPING.
12 STRAINER, BUTTERFLY VALVE AND FLEX, IN VERTICAL SUPPLY WATER PIPE.
13 FLEX AND BUTTERFLY VALVE IN RETURN WATER PIPE WITH GAUGE & THERMOMETER.
14 BUTTERFLY VALVE FLEX AND SUCTION DIFFUSER IN PUMP SUCTION PIPE.
15 BUTTERFLY VALVE AND FLEX IN PUMP SUCTION VERTICAL PIPE.
16 FLEX AND TRIPLE DUTY VALVE IN PUMP DISCHARGE VERTICAL PIPE.
17 AIR COMPRESSOR
18 AIR DRYER
19 COMPRESSED AIR TANK
20 BUTTERFLY VALVE (NORMALLY CLOSED).
21 18" BYPASS PIPE WITH MOTOR OPERATED BUTTERFLY VALVE IN VERTICAL.
22 BALANCING VALVE.
23 3" WATER SUPPLY WITH 3" REDUCED PRESSURE BACK FLOW PREVENTER.
24 2" REDUCED PRESSURE BACK FLOW PREVENTER FOR CHILLED WATER MAKE UP.
25 CONDENSER WATER TREATMENT RACKED ON WALL AND FLOOR MOUNTED TANKS
AND FILL SYSTEM WITH 2" AND 3" REDUCED PRESSURE BACK FLOW PREVENTERS.
26 TRANE REFRIGERANT MONITOR PANEL MG MODEL WITH RED LIGHT.
27 LAKOS FILTERS TBX-0400-SRV, 400 GPM & 7.5 HP, 460V, 3 PH.
28 BUTTERFLY VALVE IN VERTICAL PIPE.
29 BUTTERFLY VALVE IN VERTICAL PIPE WITH GAUGE.
30 COMBO EMERGENCY EYEWASH / SHOWER.
31 3" WELDED PIPE DOWN TO RELIEF VALVES WITH FLEX CONNECTOR IN VERTICAL.
32 BUTTERFLY VALVE IN VERTICAL.
33 YORK RECYCLING / STORAGE TANK ON WHEELS.
34 LOCATED OUTSIDE ROOM IN CORRIDOR. BOTH DEVICES ARE TO REMAIN AND ARE PART OF
REFRIGERANT MONITORING SYSTEM.
EXISTING EQUIPMENT AND NEW WORK, ETC. INFORMATION
LIGHT LINE WORK IS EXISTING TO REMAIN
DARK DASHED LINE WORK IS DEMOLITION
LEGEND
COOLING TOWER BASIN
FILTER / SWEEPER SYSTEM
SUPPLY AND RETURN PIPING
EF-1
VFD'S FOR COOLING TOWER FANS - MOUNT ON WALL
WITH WALL BRACKETS. MAINTAIN NEC CLEARANCES
LOCKED INLET
CAP AND
CONNECTOR
COORDINATE EXACT MOUNTING HEIGHT
ABOVE GRADE WITH TANK HEIGHT
AND WATER TREATMENT COMPANY.
2" PVC ACID TANK FILL LINE
4" VTR -PROVIDE 180°
TERMINATION
ELECTRIC WATER HEATER -
MOUNT ON WALL WITH WALL BRACKET
CHEMICAL TANKS AND CHEMICALS (TYP). CONTACT
LOMBARDI WATER AND JOE KAUSLICK @ 1-937-603-6514.
COORDINATE LOCATION WITH LOMBARDI WATER .
TIE INTO TOP OF TANK
UH-1
UH-2
2"
BACKFLOW PREVENTER RPBFP-1
4"Ø PVC PIPING SLEEVES FOR
CHEMICAL PIPING - REFER TO
SCHEMATIC ON DRAWING M.501
L-1
MOUNT HIGH ON WALL
20" CONDENSER
WATER RETURN (UG)
REFER TO SITE UTILITY
PLAN FOR CONTINUATION
REFER TO SITE UTILITY
PLAN FOR CONTINUATION
2"
FPWH-1
HB-1
EMERGENCY EYE WASH & SHOWER
CT #4
SOLIDS
RECOVERY
VESSEL
ACID CHEMICAL TANK . CONTACT LOMBARDI
WATER AND JOE KAUSLICK @ 1-937-603-6514
2" DOMESTIC COLD WATER (UG)-
REFER TO SITE UTILITY
PLAN FOR CONTINUATION
6" DRAIN PIPING TO
SANITARY SEWER (UG)-
REFER TO SITE UTILITY
PLAN FOR CONTINUATION
CT #3
CT #2
CT #1
CO
ACCESS DOOR
PLATFORM (TYP)
SINGLE POINT ELECTRIC
CONNECTION TO CONTROL
PANEL (TYP)
PROVIDE RUBBER IN SHEAR PAD
BETWEEN TOWER SUPPORT BEAM
& BOTTOM OF TOWER. REFER
TO STRUCTURAL DRAWINGS
FOR SUPPORT INFORMATION
4" SWEEPER
PIPING INLET (TYP)
4" SWEEPER
PIPING OUTLET (TYP)
4" Ø DRAIN
UG (TYP)
12" Ø UG
(TYP)
16" Ø UG (TYP)
12" Ø
(TYP)
12" Ø
(TYP)
12" Ø (TYP)
STAIRS TO PLATFORM. STAIRS SHALL BE
CONSTRUCTED OF NON-CORROSIVE
MATERIAL WITH NON- SLIP STEPS AND SHALL
BE PROVIDED WITH 2 RUNG RAILINGS.
SWEEPER PIPING DISTRIBUTION
& NOZZLES, ETC. ARE LOCATED
IN TOWER BASIN (TYP)
CONCRETE SUPPORT PIER
(TYP). REFER TO STRUCTURAL
DRAWINGS FOR SUPPORT
INFORMATION.
LADDER WITH SPRING LOADED AUTOMATIC
CLOSING GATE AT TOP. MECHANICAL CONTRACTOR
TO FURNISH AND FIELD INSTALL AN ANSI Z359
COMPLIANT RIGID RAIL LADDER CLIMBING SYSTEM
IN LIEU OF A CAGE. FURNISH TWO COMPATIBLE
CARRIERS WITH EACH SYSTEM. (TYP)
SINGLE POINT CWR INLET
BOTTOM OUTLET (TYP)
EQUALIZER HEADER
PIPING BOTTOM
CONNECTION (TYP)
SINGLE POINT CWS OUTLET
BOTTOM CONNECTION (TYP)
FLEX CONNECTOR (TYP)
SHUT OFF
VALVE (TYP)
CONTINUOUS PERIMETER WALKWAY AND
SAFETY RAILINGS ACROSS TOWERS AND
BETWEEN TOWERS SHALL BE PROVIDED
WITH COOLING TOWER PACKAGE.
6" Ø UG
TO CT #1 & #2
TO CT #3 & #4
20" CONDENSER
WATER SUPPLY (UG)
DISCONNECT SWITCH (TYP)
1 1/2"
3/4"
COMBO DRAIN AND
OVERFLOW CONNECTION (TYP)
DN TO
UG (TYP)
PIPING
DN (TYP)
03 03
PIPING LOCATED
BELOW TOWER (TYP)
(TYP)
M301
M
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
PLATFORM WALKWAY. REFER
TO STRUCTURAL DRAWINGS
FOR SUPPORT INFORMATION.
5'-0"
COORDINATOR ENGINEERING CHIEF
DATE REVISION BY
NO. DATE NO. REVISION BY
C
I
V
I
L
E N
G
I
N
E
E
R
US AF
OF
DESIGN CHIEF
DATEDRAWNDESIGNED CHECKED
CONTRACT: FA8601-12-D-0005PROJECT - ZHTV040019
WPAFB
WRIGHT-PATTERSON AIR FORCE BASE
23 JUN 15
88TH ABW
SEAL
K Z
CORRECTED FINAL
F U
Z
E
P
R I N
X
FLOOR PLAN
MECHANICAL
A ALL WORK AND EQUIPMENT SHALL CONFORM WITH THE REQUIREMENTS
OF THE OHIO & INTERNATIONAL MECHANICAL AND BUILDING CODES
B THE MECHANICAL CONTRACTORS AND EQUIPMENT SUPPLIERS SHALL
COMPARE THE ELECTRICAL POWER REQUIREMENTS OF THE INTENDED
EQUIPMENT WITH POWER FEEDERS TO THE EQUIPMENT SHOWN ON THE
ELECTRICAL DRAWINGS. VERIFY ADEQUACY AND COMPATIBILITY OF
VOLTAGE, PHASE, WIRING CAPACITY, NUMBER AND SIZE OF CONDUCTORS
(VERSUS EQUIPMENT CONNECTION POINTS), FUSING AND OTHER
INFORMATION ON THE ELECTRICAL AND MECHANICAL DRAWINGS TO THAT
REQUIRED FOR THE EQUIPMENT. IF THE SELECTED EQUIPMENT REQUIRES
REVISION OF THE ELECTRICAL, ADDED COST MUST BE BORNE BY THE
MECHANICAL CONTRACTOR.
C TRANSFORMERS, CONTROLS, AND CONTROL WIRING REQUIRED FOR ALL
MECHANICAL SYSTEMS SHALL BE FURNISHED AND INSTALLED BY THE
MECHANICAL CONTRACTOR.
D ALL MECHANICAL EQUIPMENT SHALL BE INSTALLED ACCORDING TO
MANUFACTURER'S RECOMMENDATIONS.
E ALL REQUIRED CONTROL WIRING NOT SHOWN ON THE ELECTRICAL
DRAWINGS SHALL BE INCLUDED AS PART OF THE MECHANICAL WORK.
F CONTRACTOR SHALL COORDINATE THE INSTALLATION OF ALL MECHANICAL
EQUIPMENT, ETC. TO FIT WITHIN THE SPACE ALLOWED BY THE
ARCHITECTURAL AND STRUCTURAL CONDITIONS. CUTTING OR OTHERWISE
ALTERING ANY STRUCTURAL MEMBERS SHALL NOT BE PERMITTED.
G CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AFFECTING THIS
SCOPE OF WORK PRIOR TO PERFORMING WORK.
H FOR PURPOSES OF CLEARNESS AND LEGIBILITY, DRAWINGS ARE
ESSENTIALLY DIAGRAMMATIC ALTHOUGH SIZE AND LOCATION OF
EQUIPMENT ARE SHOWN TO SCALE WHEREVER POSSIBLE.
I ALL PIPING SHALL BE APPROPRIATELY LABELED PER WPAFB FACILITY
STANDARDS (ANSI A13.1).
J SEISMIC DATA:
SEISMIC DESIGN CATEGORY = B. SEISMIC RESTRAINTS ARE NOT REQUIRED.
K REFER TO SPECIFICATIONS FOR ALL INSULATION REQUIREMENTS FOR
PIPING.
L PRIOR TO START OF CONSTRUCTION THE GOVERNMENT, 88CEG/CEMME
@ 257-4514, SHALL BE CONTACTED AND AFFORDED THE OPPORTUNITY TO
REMOVE ANY CONTROLS IT DEEMS SALVAGEABLE; ESPECIALLY THE
EXISTING METASYS CONTROL AND STAEFA CONTROL DEVICES.
M REFER TO ARCHITECTURAL DRAWING G-001 FOR ENVIRONMENTAL NOTES
APPLICABLE TO THIS PROJECT.
N ALL EXISTING PIPING, EQUIPMENT, ETC. IS TO REMAIN UNLESS NOTED
OTHERWISE.
O AFTER CONSTRUCTION, THE AFFECTED HYDRONIC SYSTEM SHALL BE
TESTED, ADJUSTED, AND BALANCED TO DELIVER THE QUANTITIES SHOWN
ON THE DRAWINGS AND A REPORT SUBMITTED TO THE WPAFB PROJECT
MANAGER.
P ALL EQUIPMENT SHALL BE INSTALLED TO MAINTAIN ALL CODE,
MANUFACTURER, AND MAINTENANCE CLEARANCES. VERIFY SPECIFIC
LOCATION AND ORIENTATION OF EACH UNIT PRIOR TO INSTALLATION.
Q ANY CHANGES FROM THE BASIS OF DESIGN EQUIPMENT SELECTIONS WILL
REQUIRE THE CONTRACTOR TO MAKE ALL ADJUSTMENTS NECESSARY FOR
SELECTED EQUIPMENT.
R ALL PIPING ABOVE GROUND THAT CONNECTS TO THE COOLING TOWERS
SHALL BE PROVIDED WITH HEAT TRACING AND INSULATION. REFER TO
SPECIFICATIONS AND PIPING SCHEMATIC.
S CONTRACTOR SHALL INSTALL ALL MECHANICAL EQUIPMENT ITEMS, PIPING,
WIRING, ETC. SHIPPED LOOSE PER THE MANUFACTURE'S
RECOMMENDATIONS.
T REFER TO ELECTRICAL DRAWINGS FOR MECHANICAL - ELECTRICAL
COORDINATION SCHEDULE FOR EQUIPMENT INFORMATION.
GENERAL NOTES
(APPLIES TO ALL "M" SERIES DRAWINGS)
DRAWING NOTES
01 REFER TO DRAWING M801 AND M802 FOR SWEEPER PIPING SCHEMATIC.
02 PROVIDE THRUST BLOCKS. LOCATED AND SIZED PER PIPING
MANUFACTURER'S RECOMMENDATIONS.
03 TWO POSITION AUTOMATIC CONTROL VALVE.
04 SQUARE COLUMN FOOTING AT EACH COLUMN - REFER TO STRUCTURAL
DRAWINGS.
05 PROVIDE HEAT TRACING AND INSULATION.
06 IN PIPING EXCAVATION PROVIDE YELLOW WARNING TAPE AND TRACER
WIRE FOR PVC PIPING.
CT #4
CT #3
CT #2
CT #1
TOWER
RAILING (TYP)
INTEGRAL TOWER
DISTRIBUTION
HEADER PIPING (TYP)
WALKWAY (TYP)
PLATFORM (TYP)
16" CONDENSER
WATER SUPPLY (TYP)
CONCRETE
SLAB (TYP)
12" CONDENSER
WATER RETURN (TYP)
SWEEPER
PIPING (TYP)
DRAIN
PIPING (TYP)
GRATING
PLATFORM
SUPPORT
PIER (TYP)
12" EQUALIZER
PIPING
PIPE SUPPORT
STAND (TYP)
SUPPORT
BEAM (TYP)
LADDER WITH SPRING LOADED AUTOMATIC
CLOSING GATE AT TOP. MECHANICAL CONTRACTOR
TO FURNISH AND FIELD INSTALL AN ANSI Z359
COMPLIANT RIGID RAIL LADDER CLIMBING SYSTEM
IN LIEU OF A CAGE. FURNISH TWO COMPATIBLE
CARRIERS WITH EACH SYSTEM. (TYP)
INTEGRAL TOWER
DISTRIBUTION
HEADER PIPING (TYP)
TOWER
RAILING (TYP)
TOWER
CONTROL
PANEL
TOWER
DISCONNECT
SWITCH
PLATFORM
20" CONDENSER
WATER SUPPLY
PIPE SUPPORT
STAND (TYP)
16" 12"
20" CONDENSER
WATER RETURN
GRADE
STEEL BEAM
(TYP)
CONCRETE SLAB
CONCRETE PIER (TYP)
LADDER WITH SPRING LOADED AUTOMATIC
CLOSING GATE AT TOP. MECHANICAL CONTRACTOR
TO FURNISH AND FIELD INSTALL AN ANSI Z359
COMPLIANT RIGID RAIL LADDER CLIMBING SYSTEM
IN LIEU OF A CAGE. FURNISH TWO COMPATIBLE
CARRIERS WITH EACH SYSTEM. (TYP)
PROVIDE HOSE, HOSE CONNECTORS, SHUTOFF VALVES
TO EACH RENTAL CHILLER, MANIFOLD TOGETHER AND
PROVIDE TEMPORARY SUPPLY AND RETURN PIPING INTO
BUILDING. REFER TO M401 FOR CONTINUATION.
LOCATION FOR RENTAL CHILLERS AND ACCESSORIES AND MANIFOLD PIPING.
REFER TO DRAWING M401 FOR CONTINUATION OF PIPING.
CONSTRUCTION
AREA FENCE
REFER TO C500
FOR CONTINUATION
20" CONDENSER RETURN PIPING
20" CONDENSER SUPPLY PIPING
COORDINATOR ENGINEERING CHIEF
DATE REVISION BY
NO. DATE NO. REVISION BY
C
I
V
I
L
E N
G
I
N
E
E
R
US AF
OF
DESIGN CHIEF
DATEDRAWNDESIGNED CHECKED
CONTRACT: FA8601-12-D-0005PROJECT - ZHTV040019
WPAFB
WRIGHT-PATTERSON AIR FORCE BASE
23 JUN 15
88TH ABW
SEAL
K Z
CORRECTED FINAL
F U
Z
E
P
R I N
X
SECTION
COOLING TOWER
SECTION
COOLING TOWER
PARTIAL SITE PLAN
RENTAL PACKAGE AIR COOLED OUTDOOR CHILLERS INFORMATION
PROVIDE NOMINAL 1000 TON CAPACITY RENTAL AIR COOLED CHILLERS COMPLETE WITH:
HOSE BOX AND HOSE SECTIONS
FLANGE ADAPTERS.
COUPLINGS
PUMP
CABLE BOX
MANIFOLD PIPING AT EXTERIOR
CHILLED WATER PIPING FROM RENTAL CHILLER MANIFOLD INTO BUILDING AND CONNECT TO EXISTING
SYSTEM.
MISCELLANEOUS
REFER TO SITE DRAWINGS AND PARTIAL MECHANICAL BELOW PLAN FOR APPROXIMATE LOCATION OF
OUTDOOR RENTAL EQUIPMENT.
THE CHILLER PACKAGES ARE TO BE USED TO PROVIDE CHILLED WATER TO THE BUILDING WHEN EXISTING
COOLING TOWERS ARE SHUTDOWN AND CONDENSER WATER PIPING TIE IN CONNECTIONS ARE PROVIDED
TO EXISTING PIPING IN THE BUILDING.
REFER TO CIVIL SITE PLAN PHASING DESCRIPTION FOR THE PROJECT.
M
FD
FD
FD
FD
FD
CH-3
CH-2
CH-1
FD
FD
FD
FD
FD
FD
51x23 W/
INSULATION
51x23 W/
INSULATION
ELECTRICAL MAIN
DISTRIBUTION PANEL
(MDP)
ELECTRICAL MOTOR
CONTROL PANEL (MCC-2)
CHILLER 3
POWER PANEL
CHILLER 2
POWER PANEL
CHILLER 1
POWER PANEL
8" (BOP 10'-5"AFF)
8" (BOP 8'-8"AFF)
12"
12"
8"
8"
16" (BOP 10'-0"AFF)
12"
6"
6"
10" 10"
8" FROM BLDG 266
8" TO BLDG 266
TO BLDG 262 BASEMENT W.
FROM BLDG 262 BASEMENT W.
FD
(BOD 7'-8"
AFF)
(BOD 7'-8"
AFF)
8"
10"
12"
12"
03 16
04 16
04 16
04 16
DN
7'-10" BOP
CHR
VENTILATION
DUCT (TYP)
CONCRETE
PAD (TYP)
16" (BOP
8'-10"AFF)
12" (BOP 10'-0" AFF)
12" (BOP
10'-0" AFF)
8" (BOP
10'-2" AFF)
TO BLDG 262 BASEMENT E.
FROM BLDG 262 BASEMENT E.
8" (BOP 9'-1" AFF)
12" (BOP 10'-3" AFF)
12" (BOP 10'-3" AFF)
10"
20" (BOP 8'-3" AFF)
CONDENSER
WATER RETURN
20" (BOP 0'-8" AFF)
CONDENSER
WATER SUPPLY
10" CHS & CHR UP TO
1ST & 2ND FLOORS
OF BLDG 262
(BOP 10'-3" AFF)
UH
12" (BOP 8'-6" AFF)
EXISTING PIPING
BOP 9'-2"
CHR
CHS
UH
CHS
UTILITY SINK
FD
FD
CHR
REDLIGHT
WARNING SIGN
FLOOR
TRENCH
W/COVER
(TYP)
CONCRETE
PAD (TYP)
CONCRETE
PAD (TYP)
3"
3"
TO COOLING TOWERS
CHP-1
CHP-2
CHP-4
CHP-3
CWP-1
CWP-4
(STANDBY)
CWP-2
CWP-3
10" UP TO BLDG. 262
FIRST AND SECOND
FLOOR
CHR
CHS
CHS
CHR
CHS
CHR
CHS
CHS
CHR
CHR
CWR
CWS
CWS
CWR
CWS
CWR
ELECTRICAL MOTOR
CONTROL PANEL (MCC-1)
RUPTURE DISC
RELIEF PIPING
40 41
TYP
12"
TYP
DN
12"
12"
PROVIDE SHUTOFF
VALVE (TYP)
8"
12"
12"
12"
12"
COORDINATOR ENGINEERING CHIEF
DATE REVISION BY
NO. DATE NO. REVISION BY
C
I
V
I
L
E N
G
I
N
E
E
R
US AF
OF
DESIGN CHIEF
DATEDRAWNDESIGNED CHECKED
CONTRACT: FA8601-12-D-0005PROJECT - ZHTV040019
WPAFB
WRIGHT-PATTERSON AIR FORCE BASE
23 JUN 15
88TH ABW
SEAL
K Z
CORRECTED FINAL
F U
Z
E
P
R I N
X
PARTIAL ENLARGED BASEMENT FLOOR PLAN
BUILDING 10262 CHILLER PLANT
01 CONDENSER WATER PUMP: B&G MODEL VSCS-F-9.5-BF-RHR,
1800 GPM, 60 FT. HEAD, 40 HP, 460 VOLT, 3 PHASE
02 CONDENSER WATER PUMP: B&G MODEL VSCS-F-11-BF-RHR,
3900 GPM, 77 FT. HEAD, 100 HP, 460 VOLT, 3 PHASE
03 CHILLED WATER PUMP: B&G MODEL VSC-11.25-BF-C-RHR,
1440 GPM, 125 FT. HEAD, 75 HP, 460 VOLT, 3 PHASE
04 CHILLED WATER PUMP: B&G MODEL VSC-12.75-BF-O-RHR,
3120 GPM, 150 FT. HEAD, 200 HP, 460 VOLT, 3 PHASE
05 CHILLER: YORK MODEL YKN43G4-CTL-YDHA-41DD, NOMINAL 596 TON
(R22 REFRIGERANT).
06 CHILLER: YORK MODEL YKQ4R3H2-DBC-YDHB-57DD, NOMINAL 1300 TON
(R22 REFRIGERANT).
07 AIR SEPARATOR WITH MAKE UP WATER CONNECTION
08 EXPANSION TANK
09 CHILLED WATER CHEMICAL SHOT FEEDER
10 EXHAUST FAN
11 CONDENSER WATER BLOW DOWN.
12 STRAINER, BUTTERFLY VALVE AND FLEX, IN VERTICAL SUPPLY WATER PIPE.
13 FLEX AND BUTTERFLY VALVE IN RETURN WATER PIPE WITH GAUGE & THERMOMETER.
14 BUTTERFLY VALVE FLEX AND SUCTION DIFFUSER IN PUMP SUCTION PIPE.
15 BUTTERFLY VALVE AND FLEX IN PUMP SUCTION VERTICAL PIPE.
16 FLEX AND TRIPLE DUTY VALVE IN PUMP DISCHARGE VERTICAL PIPE.
17 AIR COMPRESSOR
18 AIR DRYER
19 COMPRESSED AIR TANK
20 BUTTERFLY VALVE (NORMALLY CLOSED).
21 18" BYPASS PIPE WITH MOTOR OPERATED BUTTERFLY VALVE IN VERTICAL.
22 10" BALANCING VALVE. SET @ 1800 GPM.
23 3" WATER SUPPLY WITH 3" REDUCED PRESSURE BACK FLOW PREVENTER.
24 2" REDUCED PRESSURE BACK FLOW PREVENTER FOR CHILLED WATER MAKE UP.
25 CONDENSER WATER TREATMENT RACKED ON WALL AND FLOOR MOUNTED TANKS
AND FILL SYSTEM WITH 2" AND 3" REDUCED PRESSURE BACK FLOW PREVENTERS.
26 TRANE REFRIGERANT MONITOR PANEL MG MODEL WITH RED LIGHT.
27 LAKOS FILTERS TBX-0400-SRV, 400 GPM & 7.5 HP, 460V, 3 PH.
28 BUTTERFLY VALVE IN VERTICAL PIPE.
29 BUTTERFLY VALVE IN VERTICAL PIPE WITH GAUGE.
30 COMBO EMERGENCY EYEWASH / SHOWER.
31 3" WELDED PIPE DOWN TO RELIEF VALVES WITH FLEX CONNECTOR IN VERTICAL.
32 BUTTERFLY VALVE IN VERTICAL.
33 YORK RECYCLING / STORAGE TANK ON WHEELS.
34 LOCATED OUTSIDE ROOM IN CORRIDOR. BOTH DEVICES ARE TO REMAIN AND ARE PART OF
REFRIGERANT MONITORING SYSTEM.
35 ROUTE TEMPORARY 12" CHS & CHR PIPING OUT TO RENTAL CHILLERS AND PROVIDE PIPING MANIFOLDS
CONNECTING HOSES FROM EACH CHILLER INTO MANIFOLDS. PROVIDE SHUTOFF VALVES TO EACH
CONNECTION. REFER TO SITE PLAN…