Contractor_Q A.docx

DOCX document 12 KB Posted

Attached to
AMFF Blast Booth Robot Blasters - Depaint Federal contract opportunity
Solicitation number
FA8571-16-T-0030
Issued by
Department of the Air Force Materiel Command Lifecycle Management Center Robins Air Force Base

About this file

Contractor Q A/Clarification

View the file

Other files for this federal contract opportunity

Other files attached to AMFF Blast Booth Robot Blasters - Depaint, newest first.
File Type Posted
AMFF_First_Floor_Plan_and_Sector_1_Floor_Plan.pdf PDF
Updated_Purchase_Description.pdf PDF
Purchase_Description.pdf PDF
Brand_Name_J A_-_Redacted.pdf PDF
Shop_Photos.pdf PDF
CDRLs_A005-_Training.pdf PDF
CDRLs_A006-_Acceptance_Test_Plan.pdf PDF
CDRLs_A004-_Chart.pdf PDF
FAR_Certifications.pdf PDF
CDRLs_A001-_Contractor's_Standard_Operating_Procedures.pdf PDF
CDRLs_A002-_Mishap.pdf PDF
Robotic_Depaint_Combined_Synopsis-Solicitation.pdf PDF
CDRLs_A003-_COTS.pdf PDF
Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Contractor Q&A

3.4. Robot Support Structure:

A. The robot shall be mounted from the ceiling of the booth. A sketch of the booth is located in Appendix A.

B. If required to support the robot and associated hardware, the contractor shall design and install a structure external to the existing booth to support the selected robot and hardware.

Question: Empire will not want anything mounted to their booth ceiling, it would need to be PE confirmed, and an external structure will not access the inside of the booth. Do you mean an internal structure to support the robot in the booth?

Answer:

-Empire will not want anything mounted to their booth ceiling - The warranty on the booths has expired, the booth is property of the US Air Force.

-It would need to be PE confirmed - OK -An external structure will not access the inside of the booth - The intent was to have an external structure that strengthened/support the ceiling of the booth, thus allowing for the robot to be mounted.

-Do you mean an internal structure to support the robot in the booth - The problem with an internal structure is two-fold. First, the floor inside the booth is part of the media recovery system and was not designed to handle that load, and could interfere with the recovery of media. Second, an internal structure would take up space in the booth.