General Question and Answer for FBO.doc
DOC document 33 KB Posted
- Attached to
- 250 kW Motor Generator Set Federal contract opportunity
- Solicitation number
- FA8533-08-R-25855
About this file
QUESTION AND ANSWER FOR INTERESTED SOURCES
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment 0002.doc | DOC document | |
| Amendment 0001.doc | DOC document | |
| DD1423 ELIN C001 TMCR.pdf - - 01-14-2009.pdf | ||
| RFP FA8533-08-R-25855.doc | DOC document | |
| StatementWork_0825855_00_1.doc - - 01-14-2009.doc | DOC document | |
| Attachment 3_Tracking Record.doc - - 01-20-2009.doc | DOC document | |
| Attachment 5_Client Auth Ltr.doc - - 01-20-2009.doc | DOC document | |
| DD1423 ELIN's D001 D002 Provisioning.pdf - - 01-22-2009.pdf | ||
| Attachment 4_Transmittal Ltr.doc - - 01-20-2009.doc | DOC document | |
| DD1423 ELIN's A001-3 B001-6 E001-2 F001-3.pdf - - 01-23-2009.pdf | ||
| PD_07WRGBZOENF7.doc - - 01-14-2009.doc | DOC document | |
| Attachment 2_Performance Questionnaire.doc - - 01-20-2009.doc | DOC document | |
| AFMC Form 158.pdf - - 02-20-2009.pdf | ||
| Attachment 6_Quantity Ranges.doc - - 02-06-2009.doc | DOC document | |
| Attachment 1_FACTS Sheet.doc - - 01-20-2009.doc | DOC document |
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REQUEST FOR PROPOSAL (RFP) FA8533-08-R-25855
250 kW MOTOR GENERATOR PROGRAM
QUESTION AND ANSWER FOR
INTERESTED SOURCES
The 642d Combat Sustainment Group Major Programs Contracting Office received the following question on the above referenced RFP. Recognizing the answer’s benefit for all interested sources, the following information is provided on FedBizOpps.
Question:
Paragraph 4.5.2.4 of the PD requires the MG set to be tested in accordance with MIL-STD-70C Method 505.3c for over speed verification.
Since the Motor on the MG set is a synchronous motor, the speed is determined by the incoming frequency. Since utility power is at 60HZ, this would translate to 1200 RPM of the MG. In order to do the over speed test the MG needs to be at 1500 RPM which would require the incoming utility power to be 75HZ. No one can control the incoming utility frequency, except the utility.
Please advise if the Air Force still requires the test?
Answer:
Paragraph 4.6.2.4 (Overspeed) states, "The generator shall be tested in accordance with MIL-STD-705C, Method 505.3c to verify compliance with 3.2", which is 125% for 15 minutes (reference paragraph 3.2). Note this is a test of the generator only, not the motor, and the premise of the test is to verify correct balance of the rotating parts of the generator. This test (along with the other tests and inspections of 4.6.2.1 of 4.6.2.7) does not have to be performed at the prime contractors facility on the completed motor generator set but may be performed at the motor/generator manufacturers facility on the subcomponents. Note that the motor may or may not be attached (depending on the design configuration) for the test and that test requires the generator to produce 115/200 VAC at 400 Hz but there is no electrical load applied for the entire test duration. A variable frequency electrical or mechanical power source connected to the generator rotor is highly recommended, because as stated below, the utility power source frequency will not be changing 25%.
Point of Contact: Kyle Hering, 642 CBSG/GBKBB, Robins AFB GA (478) 222-1891