Bldg-680_WO58149_Lead_Paint.xlsx

XLSX spreadsheet 54 KB Posted

Attached to
Bldg. 680 Construct Classroom Addition Federal contract opportunity
Solicitation number
FA8201-16-B-0003
Issued by
Department of the Air Force Materiel Command Lifecycle Management Center Hill Air Force Base

About this file

Bldg. 680 Lead Paint Survey

View the file

Other files for this federal contract opportunity

Other files attached to Bldg. 680 Construct Classroom Addition, newest first.
File Type Posted
B680_Solit__Amend_02.docx DOCX document
Final_Contractor_Q_and_A_B680 _31May2016r1.docx DOCX document
Final_Contractor_Q_and_A_B680 _31May2016r1.docx DOCX document
IMG_0543.JPG JPG image
IMG_0544.JPG JPG image
IMG_0534.JPG JPG image
IMG_0549.JPG JPG image
Bldg._680_Amend_01.docx DOCX document
IMG_0531.JPG JPG image
IMG_0533.JPG JPG image
IMG_0550.JPG JPG image
IMG_0535.JPG JPG image
IMG_0529.JPG JPG image
IMG_0536.JPG JPG image
Bldg_680_-_Site_Visit_Attendance_Record_-_19_May_2016.pdf PDF
IMG_0541.JPG JPG image
IMG_0539.JPG JPG image
IMG_0547.JPG JPG image
IMG_0532.JPG JPG image
IMG_0542.JPG JPG image
IMG_0537.JPG JPG image
IMG_0545.JPG JPG image
IMG_0528.JPG JPG image
IMG_0530.JPG JPG image
IMG_0540.JPG JPG image
IMG_0546.JPG JPG image
IMG_0538.JPG JPG image
IMG_0548.JPG JPG image
Specifications_Building_680_KRSM_152043.pdf PDF
BASE_FACILITY_DESIGN_STANDARD.docx DOCX document
Specifications_Table_of_Contents_Building_680_KRSM_152043.pdf PDF
Bldg-680_WO58149_Asbestos.xlsx XLSX spreadsheet
TAB_K__1_Aug_11.pdf PDF
Storm_Water_Pollution_Prevention_Plan_Building_680_KRSM_152043.pdf PDF
H680K152043_Design_Analysis_Final.pdf PDF
APPENDIX_C_MASTER_ON_or_OFF_BASE_UPDATED_March_2015.docx DOCX document
UT104.txt TXT text file
BLDG_680_Solicitaion_r4.docx DOCX document
Drawing_Schedule_Building_680_KRSM_152043.doc DOC document
Drawings_Building_680_KRSM_152043.pdf PDF
BLDG_680_SECTION_J.docx DOCX document
Show all 41

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Report

DEPARTMENT OF THE AIR FORCE
75TH CIVIL ENGINEERING (CEOHA)
HILL AIR FORCE BASE, UTAH
REQUESTER:Terry HessDATE:21-March-2016
ORGANIZATION:309 AMXG/EN
FROM:75TH CES/CEOHA
SUBJECT:Lead Based Paint (LBP) Survey,Building680
WORK ORDER:58149
SCOPE OF WORK:Construct Classroom Addition.

Re-Inspection Date: 28-May-2015 Inspector: Traver Andreasen (Utah Certified Lead Inspector #PB-2085)

Niton used for this inspection: XRF Analyzer XL2 600 (Serial #56999)

Building680
Built in:2005
1-Lead based paint was non-detected. Please refer to specific results of this inspection; see attachment 1.
2-Limited lead-based paint identification has been completed for,Building680
It is possible that lead based paint could be encountered during any renovation project. Additional identification for lead based paint on other building components may be required. The facility manager should ensure that these components are surveyed for lead as well, to meet OSHA Standard 29 CFR 1926.62 construction requirements for lead.

3-The U.S. Department of Housing and Urban Development defines Lead-based paint as any paint, varnish, stain, or other applied coating that has 1mg/cm2 as measured by an X-ray Fluorescence (XRF) Analyzer or laboratory analysis or 0.5 percent by weight (5,000ug/g by dry weight) by laboratory analysis, or more of lead. All other components tested were less than 1 mg/cm2.

4-Any effort to disturb lead paint can create lead dust. Please ensure that appropriate abatement, cleanup, and disposal will be accomplished and that the appropriate safety measures are taken IAW 29 CFR 1926.62. If you have any questions please feel free to call Nickolas King at 586-7094.

Inspector: Traver Andreasen (Utah Certified Lead Inspector #PB-2085)

Niton: XRF Analyzer XL2 600 (Serial #56999)

Refer to "Readings" tab for all readings.

Building: 680

Construct additional classroomsWO#:58149
21 March 2016

1500 Hours

Readings

Building:680Inspector:Traver Andreasen
Date:21-March-2016PB # :PB-2085
Time:0700
Work Order:58149
Pre CalibrationPbL (mg/cm2)PbL (+/-)Model#Serial #Post CalibrationPbL (mg/cm2)PbL (+/-)
Cal. StandardXRF Analyzer XL2 600 (Serial #56999)Cal. Standard
11551.001.04 +/- 0.0612121.011.04 +/- 0.06
11561.0112130.98
11570.9912141.00
Average:1.00Average:1.00
XL NumberRoomSideStructureConditionSubstrateColorPbL(mg/cm2)NEG/POS
1158HangarSouthFloorGoodConcreteYellow0.00NEG
1159Exterior Room 121WestWallGoodDrywallWhite0.00NEG
1160123SouthWallGoodDrywallTan0.00NEG
1161123SouthDoor jambGoodMetalBrown0.00NEG
1162Dock E-1South12" Floor CircleGoodConcreteYellow0.00NEG
1163Dock E-1South6" Floor LineGoodConcreteYellow0.00NEG
1164Dock E-1WestStructural SteelGoodMetalGrey0.00NEG
1165Dock E-1WestStairGoodMetalYellow0.03NEG
1166Dock E-1WestHandrailGoodMetalGrey0.00NEG
1167109NorthStructural SteelGoodMetalWhite0.00NEG
1168109WestWallGoodBlockWhite0.00NEG
1169109CenterFloorGoodConcreteGrey0.00NEG
1170109North2" Floor LineGoodConcreteGrey0.01NEG
1171HangarWestPipeGoodMetalWhite0.00NEG
1172Dock E-4West2" Floor LineGoodConcreteWhite0.00NEG
1173Dock E-4West2" Floor LineGoodConcreteGreen0.00NEG
1174Dock E-4South12" Floor CircleGoodConcreteGreen0.00NEG
1175Dock E-4Center6" Floor LineGoodConcreteGreen0.00NEG
1176Dock E-4Center6" Floor LineGoodConcreteOrange0.00NEG
1177Dock E-4EastStair jackGoodMetalGrey0.00NEG
1178Dock E-4WestHandrailGoodMetalYellow0.01NEG
1179Dock E-4CenterFloorGoodMetalGrey0.00NEG
1180124NorthWindow FrameGoodWoodBlack0NEG
1181124WestFloorGoodConcreteRed0.00NEG
1182124NorthWindow SillGoodWoodBlack0.00NEG
1183124NorthWindow SillGoodMetalBlack0.00NEG
1184HangarCenterFloorGoodConcreteYellow0.00NEG
1185Dock E-3North16" Floor LineGoodMetalDark Blue0NEG
Building:680Inspector:Traver Andreasen
Date:18-May-2015PB # :PB-2085
Time:0700
Work Order:58149
Pre CalibrationPbL (mg/cm2)PbL (+/-)Model#Serial #Post CalibrationPbL (mg/cm2)PbL (+/-)
Cal. StandardXRF Analyzer XL2 600 (Serial #56999)Cal. Standard
11551.001.04 +/- 0.0612121.011.04 +/- 0.06
11561.0112130.98
11570.9912141.00
Average:1.00Average:1.00
XL NumberRoomSideStructureConditionSubstrateColorPbL(mg/cm2)NEG/POS
1186Dock E-3North2" Floor SquareGoodMetalLight Blue0.00NEG
1187Dock E-3North2" Floor SquareGoodMetalGreen0.00NEG
1188Dock E-3North2" Floor SquareGoodMetalOrange0.03NEG
1189Dock E-3NorthElevatorGoodMetalBlue0.00NEG
1190Dock E-2WestFloorGoodMetalYellow0.00NEG
1191Dock E-2WestStructural SteelGoodMetalYellow0.00NEG
1192105SouthStructural SteelGoodMetalBlue0.00NEG
1193106WestDoorGoodMetalBlue0.00NEG
1194107WestFloorGoodConcreteGrey0.00NEG
1195104WestDoor JambGoodMetalBlue0.00NEG
1196HangarEastLadderGoodMetalWhite0.00NEG
1197Men's Restroom 1West4" Wall TileGoodCeramicBlue0.00NEG
1198Men's Restroom 2South4" Wall TileGoodCeramicGrey0.00NEG
1199East Office HallNorthWallGoodBlockBlue0.00NEG
1200Men's Restroom 2SouthCeilingGoodDrywallWhite0.00NEG
1201ExteriorWestDoorGoodMetalBrown0.00NEG
1202ExteriorWestDoor jambGoodMetalBrown0.00NEG
1203ExteriorWestRoll-Up Door jambGoodMetalBrown0.01NEG
1204ExteriorWestRoll-Up Door jambGoodMetalBrown0.00NEG
Traver Andreasen (Utah Certified Lead Inspector #PB-2085)
Chase Johnson (Utah Certified Lead Inspector #PB-2125)
Nickolas King (Utah Certified Lead Inspector #PB-1244)
XRF Analyzer XL3t 300 (Serial #30660)
XRF Analyzer XL2 600 (Serial #56999)