Other files attached to Oven Control Upgrades, newest first.
File Type Posted
SOW_Oven_Control_Upgrade_Revised.pdf PDF
FA8125-17-R-0002_Q&A.docx DOCX document
A01_FA8125-17-R-0002.pdf PDF
Compiled_FA8125-17-R-0002.pdf PDF
Appendix_D.docx DOCX document
SOW_Oven_Control_Upgrade.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Appendix D 2 February 2017

Appendix ‐ 1

Table 1.0 – Monitoring Parameters for Ovens

Equipment Parameter Gauge Installed

Range Alarm Type

Failure Mode

Comment

Booth Control Panel Y No Power Email No Power

Monitoring‐‐> Power

Booth Temperature Y Within range of specific oven and recipe

Email Out OF Range

Monitoring ‐‐> Heater

Booth Blower Fan 1

RPM

Y 1800>Run<2200 Email Out OF Range

Monitor for potential Motor issues

Booth Blower Fan 1 Vibe.

Y >70 Hz Email High Monitor for potential motor issues

Booth Blower Fan 2

RPM

Y 1800>Run<2200 Email Out OF Range

Monitor for potential Motor issues

Booth Blower Fan 2 Vibe.

Y >70 Hz Email High Monitor for potential motor issues

Booth Exhaust Motor

RPM

Y 1800>Run<2200 Email Out OF Range

Monitor for potential Motor issues

Booth Exhaust Motor Vibe.

Y >70 Hz Email High Monitor for potential Motor issues

Booth Exhaust Motor Temp.

Y >185' F Email High Monitor for potential Motor issues

Booth Exhaust Fan

SB‐2 RPM

Y 1800>Run<2200 Email Out OF Range

Monitor for potential fan issues

Booth Exhaust Fan SB‐2 Temp.

Y >185' F Email High Monitor for potential fan issues

Booth Exhaust Fan SB‐2 Vibe.

Y >70 Hz Email High Monitor for potential motor issues

NOTE: Photos provided from October 2016. Monitoring Parameters updated 2 February 2017.

Appendix ‐ 2

Picture 1 – OC12184 Outside Panel

Appendix ‐ 3

Picture 2 – OC12184 Outside Panel

Appendix ‐ 4

Picture 3 – OC19627 Outside Panel

Appendix ‐ 5

Picture 4 – OC19627 Inside Panel

Appendix ‐ 6

Picture 5 – OC19627 Inside Panel

Appendix ‐ 7

Picture 6 – OC21102 Outside Panel

Appendix ‐ 8

Picture 7 – OC21102 Outside Panel

Appendix ‐ 9

Picture 8 – OC21103 Inside Panel

Appendix ‐ 10

Picture 9 – OC21153 Outside Panel