Construct Pad for AGE Tank -FA6670-15-R-0003

Questions and Answers, Set 1, dated 16 July 2015

1) Q – Can you provide specs on the tank to be provided by the government?

A – Please see attached drawings for tank details.

2) Q – What are the electrical requirements needed to power the tank pump?

A – Electrical requirements for the tank pump are 110 single phase power. Max draw from the pump is 11.4 amps.

3) Q – Are there going to be grounding lugs on the tank base?

A – Yes, there are grounding lugs on the tank base as shown in attached drawings.

4) Q – For lighting, what type of pole is preferred? (Steel, aluminum, wood, etc)

A – A painted square aluminum pole is preferred.

5) Q – Is there a specific wind rating that is a base standard for the lighting?

A – The Architect/Engineer is to design lighting in accordance with applicable UFC and UFGS.

6) Q – What type of light is preferred?

A – An LED fixture meeting UFC and UFGS Section 26 56 00 is preferred.