As-Builts_-_Reference_Material.pdf
PDF 5 MB Posted
- Attached to
- Repair HVAC, Marine Reserve Center
- Solicitation number
- FA6606-19-B-A003
About this file
This document provides specifications for seismic protection and insulation of mechanical systems at the Marine Corps Reserve Training Center in Westover Air Force Base in Chicopee, Massachusetts. The specifications cover seismic bracing and insulation requirements for mechanical equipment, piping systems, and ductwork. Mechanical equipment such as boilers, air handling units, and pumps must be seismically protected according to standards. Piping for services such as domestic water, steam, and air conditioning must be insulated according to specified thicknesses depending on pipe size and operating temperature range. Ductwork for heating, cooling, and ventilation systems must also be insulated to minimum thicknesses outlined in the specifications. Insulation materials, jackets, adhesives and installation methods are defined to ensure systems are properly insulated for temperature control and condensation resistance.
As-Builts Reference Material
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amendment_FA660619BA0030001_signed.pdf | ||
| Wage_Determinations_7.5.19.docx | DOCX document | |
| Special_Standards_of_Responsibility.pdf | ||
| SOW_-_Replace_HVAC_B3505_7.8.19.pdf | ||
| Wage_Determinations_7.5.19.docx | DOCX document | |
| Solicitation_-_FA660619BA003_7.18.19.pdf | ||
| Submittal_Register_REPAIR_HVAC_B3505_7.17.19.xls | XLS spreadsheet | |
| 04--BID_SCHEDULE_(Draft_for_Contractor_Estimate).docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MARINE CORPS RESERVE TRAINING CENTER, WESTOVER AFB, CHICOPEE, MA 04000062
SECTION 15070A
SEISMIC PROTECTION FOR MECHANICAL EQUIPMENT
08/01
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by basic designation only.
U.S. ARMY CORPS OF ENGINEERS (USACE)
TI 809-04 (1998) Seismic Design for Buildings
SHEET METAL & AIR CONDITIONING CONTRACTORS' NATIONAL ASSOCIATION
(SMACNA)
SMACNA Seismic Restraint Mnl (1998) Seismic Restraint Manual Guidelines for Mechanical Systems
1.2 SYSTEM DESCRIPTION
1.2.1 General Requirements
The requirements for seismic protection measures described in this section shall be applied to the mechanical equipment and systems listed below.
Structural requirements shall be in accordance with Section 13080 SEISMIC
PROTECTION FOR MISCELLANEOUS EQUIPMENT.
1.2.2 Mechanical Equipment
Mechanical equipment to be seismically protected shall include the following items to the extent required on the drawings or in other sections of these specifications:
Boilers Expansion Air Separator Tanks Valves and Fittings for Piping Refrigerant Piping Air Handling Units Pumps with Motors Air Cooled Condensing units Ducts Unit Heaters Exhaust and Return Fans
1.2.3 Mechanical Systems
The following mechanical systems shall be installed as required on the drawings and other sections of these specifications and shall be seismically protected in accordance with this specification:
All Piping and ducts Inside the Building Except as Specifically Stated Below Under "Items Not Covered By This Section".
SECTION 15070a Page 1
1.2.4 Contractor Designed Bracing
The Contractor shall design the bracing in accordance with TI 809-04 and additional data furnished by the Contracting Officer. Resistance to lateral forces induced by earthquakes shall be accomplished without consideration of friction resulting from gravity loads. TI 809-04 uses parameters for the building, not for the equipment in the building;
therefore, corresponding adjustments to the formulas shall be required.
Loadings determined using TI 809-04 are based on strength design;
therefore, the AISC LRFD Specifications shall be used for the design. The bracing for the mechanical equipment and systems listed aboveshall be developed by the Contractor.
1.2.5 Items Not Covered By This Section
1.2.5.1 Items Requiring No Seismic Restraints
Seismic restraints are not required for the following items:
a. Gas piping less than 1inch inside diameter.
b. Piping in boiler and mechanical equipment rooms less than 1-1/4 inches inside diameter.
c. All other piping less than 2-1/2inches inside diameter.
d. Rectangular air handling ducts less than 6 square feet in cross sectional area.
e. Round air handling ducts less than 28 inches in diameter.
f. Piping suspended by individual hangers 12 inches or less in length from the top of pipe to the bottom of the supporting structural member where the hanger is attached, except as noted below.
g. Ducts suspended by hangers 12inches or less in length from the top of the duct to the bottom of the supporting structural member, except as noted below.
In exemptions f. and g. all hangers shall meet the length requirements. If the length requirement is exceeded by one hanger in the run, the entire run shall be braced. Interior piping and ducts not listed above shall be seismically protected in accordance with the provisions of this specification.
1.3 EQUIPMENT REQUIREMENTS
1.3.1 Rigidly Mounted Equipment
The following specific items of equipment: to be furnished under this contract shall be constructed and assembled to withstand the seismic forces specified in TI 809-04, Chapter 10. Each item of rigid equipment shall be entirely located and rigidly attached on one side only of a building expansion joint. Piping, duct, electrical conduit, etc., which cross the expansion joint shall be provided with flexible joints that are capable of accommodating displacements equal to the full width of the joint in both orthogonal directions.
SECTION 15070a Page 2
Boilers Air Cooled Condensing Units Air-Handling Units Roof mounted Exhaust and Supply Fans
1.4 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. The following shall be submitted in accordance with Section 01330 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Coupling and Bracing;
Flexible Couplings or Joints;
Equipment Requirements;
Contractor Designed Bracing; G, AE.
Detail drawings along with catalog cuts, templates, and erection and installation details, as appropriate, for the items listed.
Submittals shall be complete in detail; shall indicate thickness, type, grade, class of metal, and dimensions; and shall show construction details, reinforcement, anchorage, and installation with relation to the building construction.
SD-03 Product Data
Coupling and Bracing; G, AE Equipment Requirements; G, AE
Copies of the design calculations with the detail drawings.
Calculations shall be stamped by a registered engineer and shall verify the capability of structural members to which bracing is attached for carrying the load from the brace.
Contractor Designed Bracing; G, AE.
Copies of the design calculations with the drawings.
Calculations shall be approved, certified, stamped and signed by a registered Professional Engineer. Calculations shall verify the capability of structural members to which bracing is attached for carrying the load from the brace.
SD-07 Certificates
Flexible Ball Joints;
Flexible ball joints shall be certified to be suitable for the service intended by the manufacturer. Information verifying experience at not less than 3 locations of 2 years' satisfactory operation in a similar application shall be submitted.
PART 2 PRODUCTS
2.1 FLEXIBLE COUPLINGS
Flexible couplings shall have same pressure and temperature ratings as
SECTION 15070a Page 3 adjoining pipe.
2.2 FLEXIBLE BALL JOINTS
Flexible ball joints shall have cast or wrought steel casing and ball parts capable of 360-degree rotation with not less than 15-degree angular movement.
2.3 FLEXIBLE MECHANICAL JOINTS
a. Mechanical couplings for steel or cast iron pipe shall be of the sleeve type and shall provide a tight flexible joint under all reasonable conditions, such as pipe movement caused by expansion, contraction, slight settling or shifting of the ground, minor variations in trench gradients, and traffic vibrations. Where permitted in other sections of these specifications, joints utilizing split-half couplings with grooved or shouldered pipe ends may be used.
b. Sleeve-type couplings shall be used for joining plain-end pipe sections. The coupling shall consist of one steel middle ring, two steel followers, two gaskets, and necessary steel bolts and nuts to compress the gaskets.
2.4 MANUFACTURED BALL JOINTS
Manufactured ball joints shall be as recommended by the manufacturer for the intended use, and shall be approved by the Contracting Officer before installation.
2.5 SWAY BRACING MATERIALS
Sway bracing materials (e.g. rods, plates, rope, angles, etc.) shall be as specified in Section 13080 SEISMIC PROTECTION FOR MISCELLANEOUS EQUIPMENT.
PART 3 EXECUTION
3.1 COUPLING AND BRACING
Coupling installation shall conform to the details shown on the drawings.
Provisions of this paragraph apply to all piping within a 5 foot line around outside of building unless buried in the ground. Piping grouped for support on trapeze-type hangers shall be braced at the same intervals as determined by the smallest diameter pipe of the group. Bracing rigidly attached to pipe flanges, or similar, shall not be used where it would interfere with thermal expansion of piping.
3.2 BUILDING DRIFT
Joints capable of accommodating seismic displacements shall be provided for vertical piping between floors of the building, where pipes pass through a building seismic or expansion joint, or where rigidly supported pipes connect to equipment with vibration isolators. Horizontal piping across expansion joints shall accommodate the resultant of the drifts of each building unit in each orthogonal direction. For threaded piping, swing joints made of the same piping material shall be provided. For piping with manufactured ball joints the seismic drift shall be 0.015 feet per foot of height above the base where the seismic separation occurs; this drift value shall be used in place of the expansion given in the manufacturer's
SECTION 15070a Page 4 selection table.
3.3 FLEXIBLE COUPLINGS OR JOINTS
3.3.1 Building Piping
Flexible couplings or joints in building piping shall be provided at bottom of all pipe risers for pipe larger than 3-1/2 inches in diameter.
Flexible couplings or joints shall be braced laterally without interfering with the action of the flexible coupling or joint. Cast iron waste and vent piping need only comply with these provisions when caulked joints are used. Flexible bell and spigot pipe joints using rubber gaskets may be used at each branch adjacent to tees and elbows for underground waste piping inside of building to satisfy these requirements.
3.3.2 Underground Piping
Underground piping and 4 inch or larger conduit, except heat distribution system, shall have flexible couplings installed where the piping enters the building. The couplings shall accommodate [_____] inches of relative movement between the pipe and the building in any direction. Additional flexible couplings shall be provided where shown on the drawings.
3.4 PIPE SLEEVES
Pipe sleeves in interior non-fire rated walls shall be sized as indicated on the drawings to provide clearances that will permit differential movement of piping without the piping striking the pipe sleeve. Pipe sleeves in fire rated walls shall conform to the requirements in Section
07840 FIRESTOPPING.
3.5 SPREADERS
Spreaders shall be provided between adjacent piping runs to prevent contact during seismic activity whenever pipe or insulated pipe surfaces are less than 4 inches apart. Spreaders shall be applied at same interval as sway braces at an equal distance between the sway braces. If rack type hangers are used where the pipes are restrained from contact by mounting to the rack, spreaders are not required for pipes mounted in the rack. Spreaders shall be applied to surface of bare pipe and over insulation on insulated pipes utilizing high-density inserts and pipe protection shields in accordance with the requirements of Section 15080THERMAL INSULATION FOR
MECHANICAL SYSTEMS.
3.6 SWAY BRACES FOR PIPING
Sway braces shall be provided to prevent movement of the pipes under seismic loading. Braces shall be provided in both the longitudinal and transverse directions, relative to the axis of the pipe. The bracing shall not interfere with thermal expansion requirements for the pipes as described in other sections of these specifications.
3.6.1 Transverse Sway Bracing
Transverse sway bracing for steel and copper pipe shall be provided as specified in Section 13080 SEISMIC PROTECTION FOR MISCELLANEOUS EQUIPMENT.
All runs (length of pipe between end joints) shall have a minimum of two transverse braces. Transverse sway bracing for pipes of materials other than steel and copper shall be provided at intervals not to exceed the
SECTION 15070a Page 5 hanger spacing as specified in Section 15400 PLUMBING, GENERAL PURPOSE.
3.6.2 Longitudinal Sway Bracing
Longitudinal sway bracing shall be provided at 40 foot intervals unless otherwise indicated. All runs (length of pipe between end joints) shall have one longitudinal brace minimum. Sway braces shall be constructed in accordance with the drawings. Branch lines, walls, or floors shall not be used as sway braces.
3.6.3 Vertical Runs
Run is defined as length of pipe between end joints. Vertical runs of piping shall be braced at not more than 10 foot vertical intervals.
Braces for vertical runs shall be above the center of gravity of the segment being braced. All sway braces shall be constructed in accordance with the drawings. Sway branches shall not be connected to branch lines, walls, or floors.
3.6.4 Clamps and Hangers
Clamps or hangers on uninsulated pipes shall be applied directly to pipe.
Insulated piping shall have clamps or hangers applied over insulation in accordance with Section 15080 THERMAL INSULATION FOR MECHANICAL SYSTEMS.
3.7 SWAY BRACES FOR DUCTS
3.7.1 Braced Ducts
Bracing details and spacing for rectangular and round ducts shall be in accordance with SMACNA Seismic Restraint Mnl, including Appendix E.
However, the design seismic loadings for these items shall not be less than loadings obtained using the procedures in TI 809-04.
3.7.2 Unbraced Ducts
Hangers for unbraced ducts shall be attached to the duct within 2 inches of the top of the duct in accordance with SMACNA Seismic Restraint Mnl.
Unbraced ducts shall be installed with a 6 inch minimum clearance to vertical ceiling hanger wires.
-- End of Section --
SECTION 15070a Page 6
SECTION 15080A
THERMAL INSULATION FOR MECHANICAL SYSTEMS
04/01
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by basic designation only. At the discretion of the Government, the manufacturer of any material supplied will be required to furnish test reports pertaining to any of the tests necessary to assure compliance with the standard or standards referenced in this specification.
AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM)
ASTM A 580/A 580M (1998) Stainless Steel Wire
ASTM C 195 (1995) Mineral Fiber Thermal Insulating Cement
ASTM C 449/C 449M (1995) Mineral Fiber Hydraulic-Setting Thermal Insulating and Finishing Cement
ASTM C 518 (1998) Steady-State Heat Flux Measurements and Thermal Transmission Properties by Means of the Heat Flow Meter Apparatus
ASTM C 533 (1995) Calcium Silicate Block and Pipe Thermal Insulation
ASTM C 534 (1999) Preformed Flexible Elastomeric Cellular Thermal Insulation in Sheet and Tubular Form
ASTM C 547 (1995) Mineral Fiber Pipe Insulation
ASTM C 552 (2000) Cellular Glass Thermal Insulation
ASTM C 553 (1999) Mineral Fiber Blanket Thermal Insulation for Commercial and Industrial Applications
ASTM C 591 (1994) Unfaced Preformed Rigid Cellular Polyisocyanurate Thermal Insulation
ASTM C 610 (1999) Molded Expanded Perlite Block and Pipe Thermal Insulation
ASTM C 612 (2000) Mineral Fiber Block and Board Thermal Insulation
ASTM C 647 (1995) Properties and Tests of Mastics and Coating Finishes for Thermal Insulation
SECTION 15080a Page 1
ASTM C 665 (1998) Mineral-Fiber Blanket Thermal Insulation for Light Frame Construction and Manufactured Housing
ASTM C 795 (1992; R 1998el) Thermal Insulation for Use in Contact With Austenitic Stainless Steel
ASTM C 916 (1985; R 1996e1) Adhesives for Duct Thermal Insulation
ASTM C 920 (1998) Elastomeric Joint Sealants
ASTM C 921 (1989; R 1996) Determining the Properties of Jacketing Materials for Thermal Insulation
ASTM C 1126 (1998) Faced or Unfaced Rigid Cellular Phenolic Thermal Insulation
ASTM C 1136 (1995) Flexible, Low Permeance Vapor Retarders for Thermal Insulation
ASTM C 1290 (1995) Flexible Fibrous Glass Blanket Insulation Used to Externally Insulate HVAC Ducts
ASTM E 84 (2000a) Surface Burning Characteristics of Building Materials
ASTM E 96 (2000) Water Vapor Transmission of Materials
MANUFACTURERS STANDARDIZATION SOCIETY OF THE VALVE AND FITTINGS
INDUSTRY (MSS)
MSS SP-69 (1996) Pipe Hangers and Supports - Selection and Application
MIDWEST INSULATION CONTRACTORS ASSOCIATION (MICA)
MICA Insulation Stds (1993) National Commercial & Industrial Insulation Standards
1.2 SYSTEM DESCRIPTION
Field-applied insulation and accessories on mechanical systems shall be as specified herein; factory-applied insulation is specified under the piping, duct or equipment to be insulated. Field applied insulation materials required for use on Government-furnished items as listed in the SPECIAL CONTRACT REQUIREMENTS shall be furnished and installed by the Contractor.
1.3 GENERAL QUALITY CONTROL
1.3.1 Standard Products
Materials shall be the standard products of manufacturers regularly engaged in the manufacture of such products and shall essentially duplicate items that have been in satisfactory use for at least 2 years prior to bid
SECTION 15080a Page 2 opening.
1.3.2 Installer's Qualifications
Qualified installers shall have successfully completed three or more similar type jobs within the last 5 years.
1.3.3 Surface Burning Characteristics
Unless otherwise specified, insulation not covered with a jacket shall have a flame spread index no higher than 75 and a smoke developed index no higher than 150. Insulation systems which are located in air plenums, in ceiling spaces, and in attic spaces shall have a flame spread index no higher than 25 and a smoke developed index no higher than 50. Insulation materials located exterior to the building perimeter are not required to be fire-rated. Flame spread and smoke developed indexes shall be determined by ASTM E 84. Insulation shall be tested in the same density and installed thickness as the material to be used in the actual construction. Material supplied by a manufacturer with a jacket shall be tested as a composite material. Jackets , facings, and adhesives shall have a flame spread index no higher than 25 and a smoke developed index no higher than 50 when tested in accordance with ASTM E 84.
1.3.4 Identification of Materials
Packages or standard containers of insulation, jacket material, cements, adhesives, and coatings delivered for use, and samples required for approval shall have manufacturer's stamp or label attached giving the name of the manufacturer and brand, and a description of the material.
1.4 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. The following shall be submitted in accordance with Section 01330 SUBMITTAL PROCEDURES:
SD-04 Samples
Thermal Insulation Materials; AE.
A complete list of materials, including manufacturer's descriptive technical literature, performance data, catalog cuts, and installation instructions. The product number, k-value, thickness and furnished accessories for each mechanical system requiring insulation shall be included. Materials furnished under this section of the specification shall be submitted at one time.
After approval of materials and prior to applying insulation a booklet shall be prepared and submitted for approval. The booklet shall contain marked-up MICA Insulation Stds plates (or detail drawings showing the insulation material and insulating system) for each pipe, duct, or piece of equipment required to be insulated per this specification. The MICA plates shall be marked up showing the materials to be installed in accordance with the requirements of this specification for the specific insulation application. The Contractor shall submit all MICA Plates required to show the entire insulating system, including Plates required to
SECTION 15080a Page 3 show insulation penetrations, vessel bottom and top heads, legs, and skirt insulation as applicable. If the Contractor elects to submit detailed drawings instead of marked-up MICA Plates, the detail drawings shall show cut-away, section views, and details indicating each component of the insulation system and showing provisions for insulating jacketing, and sealing portions of the equipment. For each type of insulation installation on the drawings, provide a label which identifies each component in the installation (i.e., the duct, insulation, adhesive, vapor retarder, jacketing, tape, mechanical fasteners, etc.) Indicate insulation by type and manufacturer. Three copies of the booklet shall be submitted at the jobsite to the Contracting Officer. One copy of the approved booklet shall remain with the insulation Contractor's display sample and two copies shall be provided for Government use.
After approval of materials actual sections of installed systems properly insulated in accordance with the specification requirements shall be displayed. Such actual sections must remain accessible to inspection throughout the job and will be reviewed from time to time for controlling the quality of the work throughout the construction site. Each material used shall be identified, by indicating on an attached sheet the specification requirement for the material and the material by each manufacturer intended to meet the requirement. Display sample sections will be inspected at the jobsite by the Contracting Officer. Approved display sample sections shall remain on display at the jobsite during the construction period. Upon completion of construction, the display sample sections will be closed and sealed.
Pipe Insulation Display Sections: Display sample sections shall include as a minimum an elbow or tee, a valve, dielectric unions and flanges, a hanger with protection shield and insulation insert, or dowel as required, at support point, method of fastening and sealing insulation at longitudinal lap, circumferential lap, butt joints at fittings and on pipe runs, and terminating points for each type of pipe insulation used on the job, and for hot pipelines and cold pipelines, both interior and exterior, even when the same type of insulation is used for these services.
Duct Insulation Display Sections: Display sample sections for rigid and flexible duct insulation used on the job. A display section for duct insulation exposed to weather shall be protected by enclosing with a temporary covering.
1.5 STORAGE
Materials shall be delivered in the manufacturer's unopened containers.
Materials delivered and placed in storage shall be provided with protection from weather, humidity, dirt, dust and other contaminants. Insulation material and supplies that become dirty, dusty, wet, or otherwise contaminated may be rejected by the Contracting Officer.
PART 2 PRODUCTS
2.1 GENERAL MATERIALS
Materials shall be compatible and shall not contribute to corrosion, SECTION 15080a Page 4 soften, or otherwise attack surfaces to which applied in either the wet or dry state. Materials to be used on stainless steel surfaces shall meet ASTM C 795 requirements. Materials shall be asbestos free and conform to the following:
2.1.1 Adhesives
2.1.1.1 Acoustical Lining Insulation Adhesive
Adhesive shall be a nonflammable, fire-resistant adhesive conforming to ASTM C 916, Type I.
2.1.1.2 Mineral Fiber Insulation Cement
Cement shall be in accordance with ASTM C 195.
2.1.1.3 Lagging Adhesive
Lagging is the material used for thermal insulation, especially around a cylindrical object. This may include the insulation as well as the cloth/material covering the insulation. Lagging adhesives shall be nonflammable and fire-resistant and shall have a flame spread rating no higher than 25 and a smoke developed rating no higher than 50 when tested in accordance with ASTM E 84. Adhesive shall be pigmented white and be suitable for bonding fibrous glass cloth to faced and unfaced fibrous glass insulation board; for bonding cotton brattice cloth to faced and unfaced fibrous glass insulation board; for sealing edges of and bounding fibrous glass tape to joints of fibrous glass board; for bonding lagging cloth to thermal insulation; or for attaching fibrous glass insulation to metal surfaces. Lagging adhesives shall be applied in strict accordance with the manufacturer's recommendations.
2.1.2 Contact Adhesive
Adhesive may be dispersed in a nonhalogenated organic solvent or, dispersed in a nonflammable organic solvent which shall not have a fire point below 200 degrees F. The adhesive shall not adversely affect, initially or in service, the insulation to which it is applied, nor shall it cause any corrosive effect on metal to which it is applied. Any solvent dispersing medium or volatile component of the adhesive shall have no objectionable odor and shall not contain any benzene or carbon tetrachloride. The dried adhesive shall not emit nauseous, irritating, or toxic volatile matters or aerosols when the adhesive is heated to any temperature up to 212 degrees F.
The adhesive shall be nonflammable and fire resistant.
2.1.3 Caulking
ASTM C 920, Type S, Grade NS, Class 25, Use A.
2.1.4 Corner Angles
Nominal 0.016 inch aluminum 1 x 1 inch with factory applied kraft backing.
Aluminum shall be ASTM B 209, Alloy 3003, 3105, or 5005.
2.1.5 Finishing Cement
Mineral fiber hydraulic-setting thermal insulating cement ASTM C 449/C 449M.
All cements that may come in contact with Austenitic stainless steel must include testing per ASTM C 795.
SECTION 15080a Page 5
2.1.6 Fibrous Glass Cloth and Glass Tape
Fibrous glass cloth and glass tape shall have flame spread and smoke developed ratings of no greater than 25/50 when measured in accordance with ASTM E 84. Tape shall be 4 inch wide rolls.
2.1.7 Staples
Outward clinching type monel . Monel is a nickel rich alloy which has high strength, high ductility, and excellent resistance to corrosion.
2.1.8 Jackets
ASTM C 921, Type I, maximum moisture vapor transmission 0.02 perms, (measured before factory application or installation), minimum puncture resistance 50 Beach units on all surfaces except concealed ductwork, where a minimum puncture resistance of 25 Beach units is acceptable. Minimum tensile strength, 35 pound/inch width. ASTM C 921, Type II, minimum puncture resistance 25 Beach units, tensile strength minimum 20 pound/inch width. Jackets used on insulation exposed in finished areas shall have white finish suitable for painting without sizing. Based on the application, insulation materials which require factory applied jackets are mineral fiber, cellular glass, and phenolic foam. All non-metallic jackets shall have a maximum flame spread index of 25 and a maximum smoke developed index of 50 when tested in accordance with ASTM E 84.
2.1.8.1 White Vapor Retarder All Service Jacket (ASJ)
For use on hot/cold pipes, ducts, or equipment vapor retarder jackets used on insulation exposed in finished areas shall have white finish suitable for painting without sizing.
2.1.8.2 Aluminum Jackets
Aluminum jackets shall be corrugated, embossed or smooth sheet, 0.016 inch nominal thickness; ASTM B 209, Temper H14, Temper H16, Alloy 3003, 5005, or 3105 with factory applied moisture retarder. Corrugated aluminum jacket shall not be used outdoors. Aluminum jacket securing bands shall be Type 304 stainless steel, 0.015 inch thick, 1/2 inch wide for pipe under 12 inch diameter and 3/4 inch wide for pipe over 12 inch and larger diameter.
Aluminum jacket circumferential seam bands shall be 2 x 0.016 inch aluminum matching jacket material. Bands for insulation below ground shall be 3/4 x
0.020 inch) thick stainless steel, or fiberglass reinforced tape. The jacket may, at the option of the Contractor, be provided with a factory fabricated Pittsburg or "Z" type longitudinal joint. When the "Z" joint is used, the bands at the circumferential joints shall be designed by the manufacturer to seal the joints and hold the jacket in place.
2.1.8.3 Polyvinyl Chloride (PVC) Jackets
Polyvinyl chloride (PVC) jacket and fitting covers shall have high impact strength, UV resistant rating or treatment and moderate chemical resistance with minimum thickness 0.030 inch.
2.1.9 Vapor Retarder Coating
The vapor retarder coating shall be fire and water resistant and appropriately selected for either outdoor or indoor service. Color shall
SECTION 15080a Page 6 be white. The water vapor permeance of the compound shall be determined according to procedure B of ASTM E 96 utilizing apparatus described in ASTM E 96. The coating shall be a nonflammable, fire resistant type. All other application and service properties shall be in accordance with ASTM C 647.
2.1.9.1 Vapor Retarder Required
ASTM C 1136, Type I, maximum moisture vapor transmission 0.02 perms, minimum puncture resistance 50 Beach units on all surfaces except concealed ductwork, where Type II, maximum moisture vapor transmission 0.02 perms, a minimum puncture resistance of 25 Beach units is acceptable.
2.1.9.2 Vapor Retarder Not Required
ASTM C 1136, Type III, maximum moisture vapor transmission 0.10 perms, minimum puncture resistance 50 Beach units on all surfaces except ductwork, where Type IV, maximum moisture vapor transmission 0.10, a minimum puncture resistance of 25 Beach units is acceptable.
2.1.10 Wire
Soft annealed ASTM A 580/A 580M Type 302, 304 or 316 stainless steel, 16 or 18 gauge.
2.2 PIPE INSULATION MATERIALS
Insulation materials shall conform to EPA requirements in accordance with Section 01670 RECYCLED / RECOVERED MATERIALS. Pipe insulation materials shall be limited to those listed herein and shall meet the following requirements:
2.2.1 Aboveground Cold Pipeline
Insulation for minus 30 degrees to plus 60 degrees F for outdoor, indoor, exposed or concealed applications, shall be as follows:
a. Cellular Glass: ASTM C 552, Type II, and Type III. Supply the insulation with manufacturer's recommended factory applied jacket.
b. Flexible Elastomeric Cellular Insulation:ASTM C 534, Type I or II. Type II shall have vapor retarder skin on both sides of the insulation.
c. Phenolic Insulation: ASTM C 1126, Type III. Phenolic insulations shall comply with ASTM C 795 and with the ASTM C 665 paragraph Corrosiveness. Supply the insulation with manufacturer's recommended factory applied jacket.
d. Mineral Fiber: ASTM C 547
e. Polyisocyanurate Insulation: ASTM C 591, type I. Supply the insulation with manufacturer's recommended factory applied jacket.
2.2.2 Aboveground Hot Pipeline
Insulation for above 60 degrees F, for outdoor, indoor, exposed or concealed applications shall meet the following requirements. Supply the insulation with manufacturers recommended factory applied jacket.
SECTION 15080a Page 7
a. Mineral Fiber: ASTM C 547, Types I, II or III, supply the insulation with manufacturers recommended factory applied jacket.
b. Calcium Silicate: ASTM C 533, Type I indoor only, or outdoors above 250 degrees F pipe temperature.
c. Cellular Glass: ASTM C 552, Type II and Type III. Supply the insulation with manufacturers recommended factory applied jacket.
d. Flexible Elastomeric Cellular Insulation: ASTM C 534, Type I or II to 200 degrees F service.
e. Phenolic Insulation: ASTM C 1126 Type III to 250 F service shall comply with ASTM C 795. Supply the insulation with manufacturers recommended factory applied jacket.
f. Perlite Insulation: ASTM C 610
g. Polyisocyanurate Insulation: ASTM C 591, Type 1, to 300 degrees F service. Supply the insulation with manufacturer's recommended factory applied jacket.
2.2.3 Above Ground Dual Temperature Pipeline - Outdoor, Indoor - Exposed or Concealed
Selection of insulation for use over a dual temperature pipeline system shall be in accordance with the most limiting/restrictive case. Find an allowable material from paragraph PIPE INSULATION MATERIALS and determine the required thickness from the most restrictive case. Use the thickness listed in paragraphs INSULATION THICKNESS for cold & hot pipe applications.
2.2.4 Below ground Pipeline Insulation
For below ground pipeline insulation the following requirements shall be met.
2.2.4.1 Cellular Glass
ASTM C 552, type II.
2.3 DUCT INSULATION MATERIALS
Duct insulation materials shall be limited to those listed herein and shall meet the following requirements:
2.3.1 Rigid Mineral Fiber
ASTM C 612, Type IA, IB, II, III, & IV.
2.3.2 Flexible Mineral Fiber
ASTM C 553, Type I,or Type II up to 250 F. ASTM C 1290 Type III.
2.3.3 Cellular Glass
ASTM C 552, Type I.
2.3.4 Phenolic Foam
SECTION 15080a Page 8
ASTM C 1126 Type II, shall comply with ASTM C 795.
2.3.5 Flexible Elastomeric Cellular
ASTM C 534 Type II.
2.3.6 Polyisocyanurate
ASTM C 591, Type 1. Supply the insulation with manufacturer's recommended factory applied jacket.
2.4 EQUIPMENT INSULATION MATERIALS
Equipment insulation materials shall be limited to those listed herein and shall meet the following requirements:
2.4.1 Cold Equipment Insulation
For temperatures below 60 degrees F.
2.4.1.1 Cellular Glass
ASTM C 552, Type I, Type III, or Type IV as required.
2.4.1.2 Flexible Elastomeric Cellular Insulation
ASTM C 534, Type II.
2.4.1.3 Phenolic Foam
ASTM C 1126 Type II shall comply with ASTM C 795.
2.4.1.4 Polyisocyanurate Foam
ASTM C 591, Type I. Supply the insulation with manufacturer's factory applied jacket.
2.4.2 Hot Equipment Insulation
For temperatures above 60 degrees F.
2.4.2.1 Rigid Mineral Fiber
ASTM C 612, Type IA, IB, II, III, IV, or V as required for temperature encountered to 1800 degrees F.
2.4.2.2 Flexible Mineral Fiber
ASTM C 553, Type I, II, III, IV, V, VI or VII as required for temperature encountered to 1200 degrees F.
2.4.2.3 Calcium Silicate
ASTM C 533, Type I, indoors only, or outdoors above 250 degrees F. Pipe shape may be used on diesel engine exhaust piping and mufflers to 1200 degrees F.
2.4.2.4 Cellular Glass
SECTION 15080a Page 9
ASTM C 552, Type I, Type III, or Type IV as required.
2.4.2.5 Flexible Elastomeric Cellular Insulation
ASTM C 534, Type II, to 200 degrees F.
2.4.2.6 Phenolic Foam
ASTM C 1126 Type II to 250 degrees F shall comply with ASTM C 795.
2.4.2.7 Molded Expanded Perlite
ASTM C 610.
2.4.2.8 Polyisocyanurate Foam:
ASTM C 591, Type I. Supply the insulation with manufacturer's recommended factory applied jacket.
PART 3 EXECUTION
3.1 APPLICATION - GENERAL
Insulation shall only be applied to unheated and uncooled piping and equipment. Flexible elastomeric cellular insulation shall not be compressed at joists, studs, columns, ducts, hangers, etc. The insulation shall not pull apart after one hour period; any insulation found to pull apart after one hour shall be replaced.
3.1.1 Installation
Except as otherwise specified, material shall be installed in accordance with the manufacturer's written instructions. Insulation materials shall not be applied until tests specified in other sections of this specification are completed. Material such as rust, scale, dirt and moisture shall be removed from surfaces to receive insulation. Insulation shall be kept clean and dry. Insulation shall not be removed from its shipping containers until the day it is ready to use and shall be returned to like containers or equally protected from dirt and moisture at the end of each workday. Insulation that becomes dirty shall be thoroughly cleaned prior to use. If insulation becomes wet or if cleaning does not restore the surfaces to like new condition, the insulation will be rejected, and shall be immediately removed from the jobsite. Joints shall be staggered on multi layer insulation. Mineral fiber thermal insulating cement shall be mixed with demineralized water when used on stainless steel surfaces.
Insulation, jacketing and accessories shall be installed in accordance with MICA Insulation Stds standard plates except where modified herein or on the drawings.
3.1.2 Firestopping
Where pipes and ducts pass through fire walls, fire partitions, above grade floors, and fire rated chase walls, the penetration shall be sealed with fire stopping materials as specified in Section 07840 FIRESTOPPING.
3.1.3 Painting and Finishing
Painting shall be as specified in Section 09900 PAINTING, GENERAL.
SECTION 15080a Page 10
3.1.4 Installation of Flexible Elastomeric Cellular Insulation
Flexible elastomeric cellular insulation shall be installed with seams and joints sealed with rubberized contact adhesive. Insulation with pre-applied adhesive is not permitted. Flexible elastomeric cellular insulation shall not be used on surfaces greater than 200 degrees F. Seams shall be staggered when applying multiple layers of insulation. Insulation exposed to weather and not shown to have jacketing shall be protected with two coats of UV resistant finish as recommended by the manufacturer after the adhesive is dry. A brush coating of adhesive shall be applied to both butt ends to be joined and to both slit surfaces to be sealed. The adhesive shall be allowed to set until dry to touch but tacky under slight pressure before joining the surfaces. Insulation seals at seams and joints shall not be capable of being pulled apart one hour after application.
Insulation that can be pulled apart one hour after installation shall be replaced.
3.1.5 Welding
No welding shall be done on piping, duct or equipment without written approval of the Contracting Officer. The capacitor discharge welding process may be used for securing metal fasteners to duct.
3.1.6 Pipes/Ducts/Equipment which Require Insulation
Insulation is required on all pipes, ducts, or equipment, except for omitted items, as specified.
3.2 PIPE INSULATION INSTALLATION
3.2.1 Pipe Insulation
3.2.1.1 General
Pipe insulation shall be installed on aboveground hot and cold pipeline systems as specified below to form a continuous thermal retarder, including straight runs, fittings and appurtenances unless specified otherwise.
Installation shall be with full length units of insulation and using a single cut piece to complete a run. Cut pieces or scraps abutting each other shall not be used. Pipe insulation shall be omitted on the following:
a. Pipe used solely for fire protection.
b. Chromium plated pipe to plumbing fixtures. However, fixtures for use by the physically handicapped shall have the hot water supply and drain, including the trap, insulated where exposed.
c. Sanitary drain lines.
d. Air chambers.
3.2.1.2 Pipes Passing Through Walls, Roofs, and Floors
a. Pipe insulation shall be continuous through the sleeve.
b. An aluminum jacket with factory applied moisture retarder shall be provided over the insulation wherever penetrations require sealing.
c. Where penetrating interior walls, the aluminum jacket shall extend
SECTION 15080a Page 11
2 inches beyond either side of the wall and shall be secured on each end with a band.
d. Where penetrating floors, the aluminum jacket shall extend from a point below the backup material to a point 10 inches above the floor with one band at the floor and one not more than 1 inch from the end of the aluminum jacket.
e. Where penetrating waterproofed floors, the aluminum jacket shall extend from below the backup material to a point 2 inchesabove the flashing with a band 1 inch from the end of the aluminum jacket.
f. Where penetrating exterior walls, the aluminum jacket required for pipe exposed to weather shall continue through the sleeve to a point 2 inches beyond the interior surface of the wall.
g. Where penetrating roofs, pipe shall be insulated as required for interior service to a point flush with the top of the flashing and sealed with vapor retarder coating. The insulation for exterior application shall butt tightly to the top of flashing and interior insulation. The exterior aluminum jacket shall extend 2 inches down beyond the end of the insulation to form a counter flashing.
The flashing and counter flashing shall be sealed underneath with caulking.
h. For hot water pipes supplying lavatories or other similar heated service which requires insulation, the insulation shall be terminated on the backside of the finished wall. The insulation termination shall be protected with two coats of vapor barrier coating with a minimum total thickness of 1/16 inch applied with glass tape embedded between coats (if applicable). The coating shall extend out onto the insulation 2 inches and shall seal the end of the insulation. Glass tape seams shall overlap 1 inch.
Caulk the annular space between the pipe and wall penetration with approved fire stop material. Cover the pipe and wall penetration with a properly sized (well fitting) escutcheon plate. The escutcheon plate shall overlap the wall penetration at least 3/8 inch.
i. For domestic cold water pipes supplying lavatories or other similar cooling service which requires insulation, the insulation shall be terminated on the finished side of the wall (i.e., insulation must cover the pipe throughout the wall penetration).
The insulation shall be protected with two coats of vapor barrier coating with a minimum total thickness of 1/16 inch. The coating shall extend out onto the insulation 2 inches and shall seal the end of the insulation. Caulk the annular space between the outer surface of the pipe insulation and the wall penetration with an approved fire stop material having vapor retarder properties.
Cover the pipe and wall penetration with a properly sized (well fitting) escutcheon plate. The escutcheon plate shall overlap the wall penetration by at least 3/8 inch.
3.2.1.3 Pipes Passing Through Hangers
a. Insulation, whether hot or cold application, shall be continuous through hangers. All horizontal pipes 2 inchesand smaller shall be supported on hangers with the addition of a Type 40 protection shield to protect the insulation in accordance with MSS SP-69.
SECTION 15080a Page 12
Whenever insulation shows signs of being compressed, or when the insulation or jacket shows visible signs of distortion at or near the support shield, insulation inserts as specified below for piping larger than 2 inches shall be installed.
b. Horizontal pipes larger than 2 inches at 60 degrees F and above shall be supported on hangers in accordance with MSS SP-69, and Section 15400 PLUMBING, GENERAL PURPOSE.
c. Horizontal pipes larger than 2 inches and below 60 degrees F shall be supported on hangers with the addition of a Type 40 protection shield in accordance with MSS SP-69. An insulation insert of cellular glass or calcium silicate or perlite (above 80 F shall be installed above each shield. The insert shall cover not less than the bottom 180 degree arc of the pipe. Inserts shall be the same thickness as the insulation, and shall extend 2 inches on each end beyond the protection shield. When insulation inserts are required per the above, and the insulation thickness is less than 1 inch, wooden or cork dowels or blocks may be installed between the pipe and the shield to prevent the weight of the pipe from crushing the insulation, as an option to installing insulation inserts. The insulation jacket shall be continuous over the wooden dowel, wooden block, or insulation insert.
d. Vertical pipes shall be supported with either Type 8 or Type 42 riser clamps with the addition of two Type 40 protection shields in accordance with MSS SP-69 covering the 360 degree arc of the insulation. An insulation insert of cellular glass or calcium silicate shall be installed between each shield and the pipe. The insert shall cover the 360 degree arc of the pipe. Inserts shall be the same thickness as the insulation, and shall extend 2 inches on each end beyond the protection shield. When insulation inserts are required per the above, and the insulation thickness is less than 1 inch, wooden or cork dowels or blocks may be installed between the pipe and the shield to prevent the hanger from crushing the insulation, as an option instead of installing insulation inserts. The insulation jacket shall be continuous over the wooden dowel, wooden block, or insulation insert. The vertical weight of the pipe shall be supported with hangers located in a horizontal section of the pipe. When the pipe riser is longer than 30 feet, the weight of the pipe shall be additionally supported with hangers in the vertical run of the pipe which are directly clamped to the pipe, penetrating the pipe insulation. These hangers shall be insulated and the insulation jacket sealed as indicated herein for anchors in a similar service.
e. Inserts shall be covered with a jacket material of the same appearance and quality as the adjoining pipe insulation jacket, shall overlap the adjoining pipe jacket 1-1/2 inches, and shall be sealed as required for the pipe jacket. The jacket material used to cover inserts in flexible elastomeric cellular insulation shall conform to ASTM C 1136, Type 1, and is allowed to be of a different material than the adjoining insulation material.
3.2.1.4 Flexible Elastomeric Cellular Pipe Insulation
Flexible elastomeric cellular pipe insulation shall be tubular form for pipe sizes 6 inches and less. Type II sheet insulation used on pipes larger than 6 inches shall not be stretched around the pipe. On pipes
SECTION 15080a Page 13 larger than 12 inches, adhere insulation directly to the pipe on the lower 1/3 of the pipe. Seams shall be staggered when applying multiple layers of insulation. Sweat fittings shall be insulated with miter-cut pieces the same size as on adjacent piping. Screwed fittings shall be insulated with sleeved fitting covers fabricated from miter-cut pieces and shall be overlapped and sealed to the adjacent pipe insulation.
3.2.1.5 Pipes in high abuse areas.
In high abuse areas such as janitor closets and traffic areas in equipment rooms, kitchens, and mechanical rooms, welded PVC jackets shall be utilized. Pipe insulation to the 6 foot level shall be protected.
3.2.2 Aboveground Cold Pipelines
The following cold pipelines shall be insulated per Table I minus 30 degrees to plus 60 degrees F:
a. Domestic cold and chilled drinking water.
b. Make-up water.
c. Horizontal and vertical portions of interior roof drains.
d. Refrigerant suction lines.
g. Air conditioner condensate drains.
i. Exposed lavatory drains and domestic water lines serving plumbing fixtures for handicap persons.
3.2.2.1 Insulation Thickness
Insulation thickness for cold pipelines shall be determined using Table I.
Table I - Cold Piping Insulation Thickness Pipe Size (inches)
Runouts 1 in 1.25 - 2.5 - 5 - 8 in Type of up to & 2 in 4 in 6 in & Service Material 2 in* less larger
[Refrigerant CG 1.5 1.5 1.5 1.5 1.5 suction FC 1.0 1.0 1.0 1.0 1.0 piping PF 1.0 1.0 1.0 1.0 1.0
PC 1.0 1.0 1.0 1.0 1.0]
Cold domestic CG 1.5 1.5 1.5 1.5 1.5 1.5 water, above FC 3/8 3/8 3/8 3/8 3/8 3/8 and below PF 1.0 1.0 1.0 1.0 1.0 1.0 ceilings PC 1.0 1.0 1.0 1.0 1.0 1.0 & makeup water
Exposed FC 0.5 0.5 0.5 0.5 3/4 3/4 lavatory MF 0.5 1.0 1.0 1.5 1.5 1.5
SECTION 15080a Page 14
Table I - Cold Piping Insulation Thickness Pipe Size (inches)
Runouts 1 in 1.25 - 2.5 - 5 - 8 in Type of up to & 2 in 4 in 6 in & Service Material 2 in* less larger drains and domestic water lines serving& plumbing fixtures for handicap personnel
[Horizontal FC 0.5 0.5 0.5 0.5 0.5 & vertical PF 1.0 1.0 1.0 1.0 1.0 roof drain CG 1.5 1.5 1.5 1.5 1.5 leaders PC 1.0 1.0 1.0 1.0 1.0 (including underside of roof drain fitting)]
Air FC 3/8 0.5 0.5 N/A N/A conditioning PF 1.0 1.0 1.0 N/A N/A condensate PC 1.0 1.0 1.0 N/A N/A drain located inside building
*When runouts to terminal units exceed 12 feet, the entire length of runout shall be insulated like main feed pipe.
LEGEND:
PF - Phenolic Foam CG - Cellular Glass MF - Mineral Fiber FC - Flexible Elastomeric Cellular PC - Polyisocyanurate Foam
3.2.2.2 Jacket for Mineral Fiber, Cellular Glass, Phenolic Foam, and Polyisocyanurate Foam Insulated Pipe
Insulation shall be covered with a factory applied vapor retarder jacket or field applied seal welded PVC jacket. Insulation inside the building shown to be protected with an aluminum jacket shall have the insulation and vapor retarder jacket installed as specified herein. The aluminum jacket shall be installed as specified for piping exposed to weather, except sealing of the laps of the aluminum jacket is not required. In high abuse areas such as janitor closets and traffic areas in equipment rooms, kitchens, and mechanical rooms, aluminum jackets shall be utilized. Pipe insulation to the 6 ft level will be protected.
3.2.2.3 Insulation for Straight Runs (Mineral Fiber, Cellular Glass, Phenolic Foam and Polyisocyanurate Foam)
a. Insulation shall be applied to the pipe with joints tightly butted. All butted joints and ends shall be sealed with a vapor
SECTION 15080a Page 15 retarder coating.
b. Longitudinal laps of the jacket material shall overlap not less than 1-1/2 inches. Butt strips 3 inches wide shall be provided for circumferential joints.
c. Laps and butt strips shall be secured with adhesive and stapled on 4 inch centers if not factory self-sealing. If staples are used, they shall be sealed per paragraph 3.2.2.3 e.
d. Factory self-sealing lap systems may be used when the ambient temperature is between 40 degrees and 120 degrees F during installation. The lap system shall be installed in accordance with manufacturer's recommendations. Stapler shall be used only if specifically recommended by the manufacturer. Where gaps occur, the section shall be replaced or the gap repaired by applying adhesive under the lap and then stapling.
e. All Staples, including those used to repair factory self-seal lap systems, shall be coated with a vapor retarder coating. All seams, except those on factory self-seal systems shall be coated with vapor retarder coating.
f. Breaks and punctures in the jacket material shall be patched by wrapping a strip of jacket material around the pipe and securing it with adhesive, stapling, and coating with vapor retarder coating. The patch shall extend not less than 1-1/2 inches past the break.
g. At penetrations such as thermometers, the voids in the insulation shall be filled and sealed with vapor retarder coating.
3.2.2.4 Insulation for Fittings and Accessories
a. Pipe insulation shall be tightly butted to the insulation of the fittings and accessories. The butted joints and ends shall be coated with vapor retarder coating.
b. Precut or preformed insulation shall be placed around all fittings and accessories and shall conform to MICA plates except as modified herein: 5 for anchors; 10, 11, and 13 for fittings; 14 for valves; and 17 for flanges and unions. Insulation shall be the same insulation as the pipe insulation, including same density, thickness, and thermal conductivity. Where precut/preformed is unavailable, rigid preformed pipe insulation sections may be segmented into the shape required. Insulation of the same thickness and conductivity as the adjoining pipe insulation shall be used.