Attchmt_2_Specs_Tents.docx

DOCX document 16 KB Posted

Attached to
Small Shelters Federal contract opportunity
Solicitation number
FA5000-19-Q-0011
Issued by
Department of the Air Force Pacific Air Forces

About this file

Salients

View the file

Other files for this federal contract opportunity

Other files attached to Small Shelters, newest first.
File Type Posted
RFQ.docx DOCX document
Attachment_1_Pricing_Schedule.docx DOCX document
Questions_Regarding_SShelters.docx DOCX document
Attchmt_2_Specs_Tents.docx DOCX document
Questions_Regarding_SShelters.docx DOCX document
RFQ.docx DOCX document
Attchmt_2_Specs_Tents.docx DOCX document
Attachment_1_Pricing_Schedule.docx DOCX document
RFQ.docx DOCX document
Attachment_1_Pricing_Schedule.docx DOCX document
Attchmt_2_Specs_Tents.docx DOCX document
RFQ.docx DOCX document
RFQ.docx DOCX document
Attachment_1_Pricing_Schedule.docx DOCX document
Show all 14

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment 2 Alaska Small Shelter Systems, Version 2 (P/N: AK-2032.5-V280) OR EQUAL in accordance with the following minimum specifications:

· General

· Size: 20’ wide x 32.5’ long x 10’ high (Quonset Shape)

· Color: Tan or Green

· Frame:

· Shelter shall have aluminimum frame, with no poles in the center of the shelter

· Shall be corrosion resistant

· Shelter:

· Shall include at least 30” wide x 80” high personnel door

· Shall include at least 14 insulated windows

· Shall have fire resistant fabric that meets NFPA 701 and ASTM D6413

· Shall be designed to allow one shelter to attach to another shelter

· Ends:

· End base frame sections shall be removable so it can be used to connect other shelters

· Shall include two sets of 18” diameter ECU/HVAC ports

· Floor:

· Shall have non-slip vinyl floor

· Shall attach and seal to the cover and end walls

· Electrical:

· Single-phase power distribution box

· 2 EA Ground-fault circuit interrupter (GFCI) 20-amp breakers

· 2 EA 20-amp breakers

· 4 EA Twist lock cable connectors

· 1 EA Light switch

· At least 2 EA outlet lines with 12 receptacles per line, with a total of 24 outlets

· At least 6 EA incandescent light bulbs

· At least 1 EA 50’ power cable

· Shall withstand at least 60 mph wind load per ASCE 7-10

· Shall meet at least 20 psf ground snow load per ASCE 7-10