Soliciation FA4877-17-Q-0066 Crane and Hoist Certification/Inspection

Questions and Answers

1. In section 1-1-2-2, it states that magnetic particle testing is required during annual load tests. Can another form of NDI be used, such as dye penetrate testing? Also, do the hooks have to be removed during NDI testing?

Yes, provided the Dye Penetrating Test is quantifiable to the results of Magnetic Particle Test. No, Hooks are not required to be removed for testing.

2. In section 1-1-2-3, it states that the date of load test must be stenciled onto the crane. Can a sticker be substituted for the stenciling?

Yes, Most contractors use stickers or metal tags.