Questions_&_Answers.pdf

PDF 15 KB Posted

Attached to
Reverse Osmosis Installation Federal contract opportunity
Solicitation number
FA486118RC010
Issued by
Department of the Air Force Air Combat Command

About this file

Answers to questions.

View the file

Other files for this federal contract opportunity

Other files attached to Reverse Osmosis Installation, newest first.
File Type Posted
Request_for_Quote_-_FBO_Amendment_02.pdf PDF
Request_for_Quote_-_FBO_Amendment_01.pdf PDF
Request_for_Quote_-_FBO.pdf PDF
Statement_of_Work.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Questions & Answers

1. Does the customer have existing Reverse Osmosis systems that will need to be installed, or are they procuring RO systems with installation?

a. The customer is looking to procure 9 Reverse Osmosis Systems and have them installed.

2. What is the size and flow rate of the systems?

a. 300 Gallons per day.

3. What is the technical information on incoming feed water as well as quality requirements of the water after the pass-through (e.g. water purity level)

a. PH of 6.8-7.2 and restore about 15-30 PPM during the RO process.

4. What is the storage capacity of the system?

a. We require a bladder tank of 80 gallons.

5. Do you require any special features (i.e. pump, purity monitoring, digital read-out?)

a. Components are as follows:

i. Backwashing Carbon Filter

ii. Anti-scalant Component

iii. RO Component

iv. Atmospheric Tank

v. Distribution and re-pressurization Pump

vi. Ultraviolet Disinfection

vii. Micron Post Filter

viii. Deionization Cartridges

ix. Quality Light

x. Digital Readout

6. Is a water distillation system acceptable to use instead of reverse osmosis?

a. Distillation will require a boiling tank which is unauthorized in the building work center.