FA4809-10-R-0004 SJAFB NC Atch 1 Appendix D - SECTION 16721.docx

DOCX document 36 KB Posted

Attached to
Multiple Award Construction Contract (MACC)
Solicitation number
FA480910R0004
Issued by

About this file

Atch 1 Appendix D to SOW

View the file

Other files

File Type Posted
95 ID2 - 30Sep2010.pdf PDF
Landscape.dwt —
SJAFB wiring policy.doc DOC document
Bldg 3803 2nd floor.ppt PPT presentation
3803-2.dwg DWG drawing
border.dwg DWG drawing
Tsaec4.lin —
3803-1.dwg DWG drawing
c1site.dwg DWG drawing
Amendment 0005.doc DOC document
E4PLAN.DWG DWG drawing
E2DEMO.DWG DWG drawing
Drawer4_20100716_0022.PDF PDF
E1DEMO.DWG DWG drawing
Drawer4_20100716_0006.PDF PDF
Drawer4_20100716_0011.PDF PDF
Drawer4_20100716_0021.PDF PDF
Drawer4_20100716_0002.PDF PDF
Atch 5.1 pg 42 VKAG 84-1076 E-7.pdf PDF
Atch 5.1 pg 100 3803 FA-5.pdf PDF
FA4809-10-R-0004 SJAFB NC Atch 5 Atch 2 Blank 3052.xls XLS spreadsheet
Solicitation No. FA4809-10-R-0004 Multiple Award Construction Contract.doc DOC document
Atch 5.1 pg 45 VKAG 84-1076 M-2.pdf PDF
Atch 5.1 pg 11 25-06-02_12.pdf PDF
Atch 5.1 pg 12 25-06-02_13.pdf PDF
Atch 5.1 pg 17 VKAG 81-0103.pdf PDF
Atch 5.1 pg 14 SJ 60-1 SHT1.pdf PDF
FA4809-10-R-0004 SJAFB NC Atch 2.8 Wage Det. - NC100022 —
FA4809-10-R-0004 SJAFB NC Appendix E - Architectural Compatability 18 Dec A2003.pdf PDF
Atch 5.1 pg 50 VKAG 84-1076 P-4.pdf PDF
Atch 5.1 pg 83 VKAG 96-1104 A-2.PDF PDF
Atch 5.1 pg 57 VKAG 86-1006 A-1.pdf PDF
Atch 5.1 pg 23 VKAG 84-1076 A-1.pdf PDF
FA4809-10-R-0004 SJAFB NC Atch 5.1 pg 3 25-06-02_4.pdf PDF
Atch 5.1 pg 19 VKAG 81-0103 3.pdf PDF
Atch 5.1 pg 52 VKAG 85-1009 1.pdf PDF
Atch 5.1 pg 59 VKAG 86-1006 A-3.pdf PDF
Atch 5.1 pg 54 VKAG 85-1009 3.pdf PDF
Atch 5.1 pg 79 VKAG 95-4004 A-1.pdf PDF
Atch 5.1 pg 56 VKAG 86-1006.pdf PDF
Atch 5.1 pg 16 SJ 60-1 SHT3.pdf PDF
Atch 5.1 pg 53 VKAG 85-1009 2.pdf PDF
Atch 5.1 pg 101 3804 COVERSHEET.pdf PDF
Atch 5.1 pg 74 VKAG 93-4002 E-3.pdf PDF
Atch 5.1 pg 38 VKAG 84-1076 E-4R.pdf PDF
Atch 5.1 pg 39 VKAG 84-1076 E-5R.pdf PDF
Atch 5.1 pg 20 VKAG 81-0103 4.pdf PDF
Atch 5.1 pg 40 VKAG 84-1076 E-6.pdf PDF
Atch 5.1 pg 21 VKAG 84-1060 E-13.pdf PDF
Atch 5.1 pg 77 VKAG 94-4001 A-2.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FA4809-10-R-0004

Attachment 1

SECTION 16721

FIRE DETECTION, ALARM AND RADIO TYPE REPORTING SYSTEM

1. REFERENCES

1.1 The publications listed below form a part of this specification to the extent referenced.

The publications are referred to in the text by basic designation only. All publications shall be referred to in their latest edition, including any revisions thereof.

1.2 American National Standards Institute (ANSI)

ANSI C62-41Recommended Practice for Surge Voltage in
Low-Voltage AC Power Circuits

1.3 Factory Mutual System (FM)

FM P7825 Approval Guide

1.4 National Fire Protection Association (NFPA)

NFPA 70 National Electrical Code

NFPA 72 National Fire Alarm Code

NFPA 72HTesting Procedures for Local, Auxiliary, Remote
Stations and Proprietary Protective Signaling Systems

NFPA 78 Lighting Protection Code

NFPA 90A Installation of Air Conditioning and Ventilating Systems

1.5 UNDERWRITERS LABORATORIES, INC. (UL)

UL 04 Fire Protection Equipment Directory

UL 06 Rigid Metal Conduit

UL 38Manually Actuated Signaling Boxes for Use with
Fire-Protective Signaling Systems
UL 228Door Closures-Holders, with or without
Integral Smoke Detectors

UL 268 Smoke Detectors for Fire Protective Signaling Systems

UL 268A Smoke Detectors for Duct Application

UL 464 Audible Signal Appliances

UL 467 Grounding and Bonding Equipment

UL 521 Heat Detectors for Fire Protective Signaling Systems

UL 797 Electrical Metallic Tubing

UL 864 Control Units for Fire Protective Signaling Systems

2. GENERAL REQUIREMENTS

2.1 Standard Products: Material and equipment shall be the standard products of a manufacturer regularly engaged in the manufacture of the products and shall essentially duplicate items that have been in satisfactory use for at least two years prior to bid opening. Equipment shall be supported by a service organization that can provide repair service within 24 hours. The system/panel/parts/software provided shall be non-proprietary, meaning that all operation, programming, reprogramming, and maintenance can be completed by base shop personnel once acceptance testing is completed. There shall be no need for the base maintenance personnel to contact an outside maintainer for service once the system warranty period is over. Sources of parts shall be provided in the operation and maintenance manuals. Training on all aspects of the system shall be provided per the paragraph for training.

2.2 Nameplates: Major components of equipment shall have the manufacturer’s name, address, type or style, voltage and current rating, and catalog number on a non-corrosive and non-heat sensitive plate which is securely attached to the equipment.

2.3 Keys and Locks: See Contract Para C-103.

2.4 Tags: Tags with stamped identification number shall be furnished for keys and locks on a key ring and given to the Contracting Officer.

2.5 Verification of Dimensions: The Contractor shall become familiar with all details of the work, verify all dimensions in the field, and shall advise the Contracting Officer of any discrepancy before performing the work.

2.6 Compliance: The fire detection and internal alarm system shall be configured in accordance with NFPA 72. The equipment furnished shall be compatible and be UL Listed or FM approved or approved or listed by a nationally recognized testing laboratory in accordance with the applicable NFPA Standards.

2.7 Manufacturer’s Services: Services of a manufacturer’s representative who is certified in the installation, maintenance, adjustment, operation, and repair, of the equipment specified shall be provided. The representative shall supervise the installation, adjustment, and testing of the equipment.

2.8 Delivery and Storage: All equipment delivered and placed in storage shall be protected from the weather, humidity and temperature variations, dirt, dust, and other contaminates.

3. SYSTEM DESIGN

3.1 Operation: System shall be a complete, supervised Monaco M-2 Type Fire Alarm System. The system shall be activated into the alarm mode by actuation of any alarm-initiating device. The system shall remain in the alarm mode until initiating device is reset and the fire alarm control panel is manually reset and restored to normal. Electrical supervision shall be Style D, in accordance with NFPA 72. Indicating appliance circuits shall be Style X in accordance with NFPA 72. All circuits shall be capable of operating under a single ground or open condition, as specified in NFPA 72. All textual, audible and visual devices and systems shall comply with NFPA 72.

3.2 Operational Features: The system shall have the following features:

3.2.1 Two Class A (Style D) or four (4) Class B (Style B) alarm initiating (zone) circuits for connection of detection devices such as two-wire or four-wire automatic detectors and manual pull stations.

3.2.2 Two (2) auxiliary zone circuits for connection of non-powered alarm initiating devices such as tamper switches, heat detectors, or manual pull stations.

3.2.3 Expandable to 62 zones (including auxiliary input zones); zones may be Class A and Class B combinations.

3.2.4 Two (2) Class A, (Style Z) or four (4) Class B (Style Y) indicating (bell) circuits for connection of audible and visual alarm evacuation signaling devices; each circuit may be programmed as silenceable or non-silenceable. When Class A is selected, two circuits are provided; one circuit operates for common alarms and one circuit is programmable for specific zone alarms or for common alarm operation. When Class B is selected, four (4) circuits are available; two (2) provide common alarm indications and tow (2) are programmable for specific zone alarms or for common alarm operation.

3.2.5 Zone programming capability, which allows entry of a zone identification number, thirteen character description and type. Each zone is programmed for standard, supervisory, verification, positive alarm sequence, or water-flow alarm operation; the auxiliary zones may also be programmed for tamper or for publicly accessible manual pull station.

3.2.6 An auxiliary alarm output which is used in conjunction with zones that are programmed for water-flow alarm, positive alarm sequence or publicly accessible manual pull station operation.

3.2.7 An auxiliary alarm output which provides 1 Amp, 24 volt, DC power.

3.2.8 One (1) Form C (24 Vdc) auxiliary relay, programmable to operate with one or more zones.

3.2.9 A Liquid Crystal Display (LCD), an 18-digit keypad, and pass-code-controlled configuration menus to aid installation, response and maintenance personnel with set-up, alarm and trouble response, system testing and troubleshooting.

3.2.10 LED’s which identify AC power and battery status, common alarm, common trouble, message transmission, carrier detect, messages received, disconnected transmitter and M-1 fault conditions; the LCD displays alarm/trouble locations and the zone descriptions or the panel trouble condition.

3.2.11 Switches for silencing the audible alert, acknowledging alarms and trouble conditions, normalizing the panel, restarting the transmitter, testing LED operation and performing drill tests.

3.2.12 Walk test and transmitter disable functions built-in; individual zones may be disabled at the panel.

3.2.13 An on-board phone plug-type connector for connection of a computer to download pre-configured data to M-1 units or to a terminal for display of menus for programming and testing.

3.2.14 AC power failures, tamper input activation’s and battery faults are specifically reported to the central D-500 with the M-1 address. A battery fault report indicates a disconnected battery, or high or low battery charging voltage; the specific condition is displayed on the LCD. Low battery shut down circuitry prevents complete battery discharge.

3.2.15 Status reports in response to central supervising station scheduled or user initiated interrogations.

3.2.16 On-board radio interrupt circuitry which turns off the transmitter if it outputs a continuous signal for more than 30 seconds. A trouble alarm silence switch shall be provided which will silence the trouble buzzer, but will not extinguish the trouble indicator lamp. After the system returns to normal operating conditions, the trouble buzzer shall again sound until the silencing switch returns to normal position, unless automatic trouble reset is provided.

3.2.17 4-Watts RF output power

3.2.18 An alarm condition on a circuit shall automatically deactivate the air handling units throughout the building.

3.2.19 Trouble buzzer and trouble lamp (light emitting diode or neon light) to activate upon a single break, open, or ground fault condition which prevents the required normal operation of the system. The trouble signal shall also operate upon loss of primary power © supply, low battery voltage, removal of alarm zone modules, and disconnection of the circuit used for transmitting alarm signals off premises.

3.2.20 Electrical supervision of the primary power (AC) supply, battery voltage, placement of alarm zone modules within the control panel, and transmitter tripping circuit integrity.

3.2.21 Transmitter disconnect switch to allow testing and maintenance of the system without activating the transmitter.

3.2.22 Excavation alarm silencing switch or switches which, when activated, will silence alarm devices, but will not affect the zone indicating lamp not the operation of the transmitter. This switch shall be overridden upon activation of a subsequent alarm from an unalarmed zone and the alarm devices will be activated.

3.2.23 Electrical supervision of circuits used for supervisory signal services. Supervision shall detect all opens, shorts and grounds.

3.2.24 Zones for alarm initiating circuits shall be arranged as indicated on the contract drawings.

3.3 Alarm Functions: An alarm condition on a circuit shall automatically initiate the following functions:

3.3.1 Transmission of a signal over the station fire reporting system.

3.3.2 Visual indication of the alarmed zone on the fire reporting system.

3.3.3 Continuous sounding of alarm indicating devices throughout the building.

3.3.4 Closure of doors held open by electromagnetic devices (detectors with door holders).

3.3.5 Operation of the smoke control system.

3.3.6 Deactivation of the air handling units throughout the building.

3.4 Primary Power: Operating power shall be single phase taken from the building electric service as specified. Circuit breaker shall be provided with key lock. Transfer from normal to emergency power or restoration from emergency to normal power shall not prevent transmission of a signal via the fire reporting system upon operation of any initiating circuit. Circuit disconnecting means shall be clearly marked “Fire Alarm Circuit.”

3.5 Battery Backup Power: Battery backup power shall be through use of rechargeable, sealed-type storage batteries and battery charger.

4. SUBMITTALS

4.1 Shop Drawings: Shop Drawings shall be submitted and shall consist of a complete set of equipment and materials, including manufacturer’s descriptive and technical literature; performance charts and curves; catalog cuts; and installation instructions. Detail drawings shall also contain complete wiring and schematic diagrams and any other details required to demonstrate that the system has been coordinated and will properly function as a unit. Drawings shall show proposed layout and anchorage of equipment and appurtenances, and equipment relationship to other parts of the work including clearances for maintenance and operation. The Contractor shall provide battery calculations for the fire alarm system.

4.2 Test Reports: Upon completion and testing of the installed system, test reports shall be submitted in booklet form showing all field tests performed to prove compliance with the specified performance criteria. Each test report shall indicate the final position of controls.

4.3 Operation and Maintenance Manuals

4.3.1 The Contractor shall furnish the Contracting Officer three (3) complete copies of operating instructions outlining step-by-step procedures required for system start up, operation, and shut down. The instructions shall include the manufacturer’s name, model number, service manual, parts list, and brief description of all equipment and their basic operating features.

4.3.2 The Contractor shall furnish the Contracting Officer three (3) copies of maintenance instructions listing routine maintenance procedures, possible breakdowns and repair, and troubleshooting guide. The instructions shall include conduit layout, equipment layout and simplified wiring, and control diagrams of the system as installed.

4.4 Spare Parts Data: After approval of the shop drawings the Contractor shall furnish spare parts data for each different item of materials and equipment specified. The data shall include a complete list of parts and supplies, with current unit prices and source of supply, and a list of the parts recommended by the manufacturer to be replaced after three (3) years of service.

4.5 As-Built Drawings: PRIOR TO PERFORMANCE AND ACCEPTANCE TESTING, the Contractor shall submit two (2) legible copies of all fire alarm drawings showing the “as-built” system. Drawings shall include floor plans showing interconnection of all components along with a legend indicating the manufacturer of each type of device installed.

4.6 Training: The certified fire alarm Contractor shall provide a minimum of eight (8) hours training to the Civil Engineering Alarm Shop and Fire Department personnel. The Contractor shall provide two (2) weeks advance notice to the Contracting Officer.

5. OVER-VOLTAGE AND SURGE PROTECTION

5.1 Power Line Surge Protection: All equipment connected to alternating current circuits shall be protected from power line surges. Equipment shall meet requirements of ANSI C62.41. Fuses shall not be used for surge protection.

6. DELIVERY AND STORAGE

6.1 All equipment delivered and placed in storage shall be stored with protection from the weather, humidity and temperature variation, dirt and dust, and any other contaminants.

PART II – PRODUCTS

7. CONTROL PANEL

7.1 The fire alarm control panel shall be a low voltage, automatic, integrated transceiver/fire alarm control panel, Model M-2, as manufactured by Monaco Enterprises, Inc., of Spokane, Washington. The control panel shall comply with the applicable requirements of UL 864. Panel shall be modular, installed in a surface mounted steel cabinet with hinged door and cylinder lock. Control panel shall be a neat, compact assembly containing all components and equipment required to provide the specified operating and supervisory functions of the system. The panel shall have prominent rigid plastic or metal identification plates for all lamps, zones, controls, meters, fuses, and switches. Nameplates for fuses shall also include ampere rating. Separate alarm and trouble lamp shall be provided for each zone alarm initiating circuit, located on exterior of cabinet door or be visible through the cabinet door. Control panel switches shall be within the locked cabinet. A suitable means shall be provided for testing the control panel visual indicating devices (meters or lamps). Meters and lamps shall be plainly visible when the cabinet of the control unit is closed. Initiating circuits shall have plug-in cards or modules for ease of servicing. Modules or cards shall be removable without disconnecting wiring. Signals shall be provided to indicate, by zone, any alarm, supervisory or trouble condition on the system. Each initiating circuit shall be powered and supervised so that a signal on one zone does not prevent the receipt of signals from other zones. Loss of power, including any or all batteries, shall not require the reloading of a program from any source. Upon restoration of power, start-up shall be immediate, automatic, and shall not require any manual operation. The loss of primary power or the sequence of applying primary or emergency power shall not affect the transmission of alarm, supervisory or trouble signals. Enclosures shall be provided with ample gutter space to allow proper clearance between the enclosure and live parts of the panel equipment. If more than one modular unit is required to form a control panel, the units shall be installed in a single enclosure large enough to accommodate all units.

7.2 Radio Fire Alarm Transceiver: The transceiver shall be compatible with the radio fire alarm base station located at the base fire department. Transceiver units separate from the alarm panel shall be a Monaco BT-XM type. It shall be all solid state and comply with all applicable portions of FCC Part 15 governing type acceptance. All transmitters of a common configuration shall be interchangeable with the other devices furnished by the manufacturer. Each transmitter shall be the manufacturer’s current commercial product completely assembled, wired, tested at the factory and delivered ready for installation operation.

7.2.1 Frequency: The transmitter shall operate on a frequency as coordinated with the Base Fire Department.

7.2.2 Power : Transmitter shall be powered by 120 VAC, and sealed nickle-cadium type batteries requiring no additional water. Transmitter shall automatically switch to battery backup with no interruption of service. Upon restoration of normal power, the transmitter shall automatically transfer back to commercial power with no interruption or alarm activation. Power transient filtering shall be provided in accordance with manufacturer’s recommendations.

7.2.3 Memory: Transmitter shall have memory capability. Multiple, simultaneous alarms shall not result in the loss of any messages. All messages shall be stored until they are transmitted.

7.2.4 Message Designation: Message designation shall be in accordance with the following:

a. Master messages shall be transmitted upon automatic actuation of the transmitter. The building and zone causing actuation shall be individually identified as part of this transmission.

b. Test messages shall be capable of both manual and automatic actuation. Actuation of the “Test” message designation, regardless of initiating means, shall cause no less than one complete message to be sent.

c. Tamper message shall be automatically transmitted when a tamper switch is tripped in the transmitter housing.

d. Trouble message shall be automatically transmitted in the event of a failure in excess of one (1) minute of the main operating power source of the transmitter.

7.2.5 Transmitter Housing: The housing shall be fabricated from corrosion resistant cast metal or suitable substitute which has the physical strength sufficient to ward off physical damage normally expected to be received by vandalism. The housing shall be sealed against the entry of moisture, dust, dirt, insects, and other foreign objects.

7.2.6 Mounting: Transmitter housing shall be designed for universal mounting on walls, poles, or pedestals. Mounting shall utilize either lag bolt, anchor bolts, stainless steel banding, mounting brackets, or a shackle/bolt combination, as applicable to the specific installation.

7.2.7 Environmental Requirement: The transmitter shall be designed for reliable outside operation in an ambient temperature range of –22 degrees F to +140 degrees F. Transmitters shall be corrosion resistant and designed for reliable operation under adverse climatic conditions including 130 mph winds, ice, rain, and snow storms.

7.3 Antenna: The antenna system shall utilize vertical polarization antennas, communication links between transmitters/receivers, and antennas, and matching networks as needed for the proper coverage. The antenna system shall be either omni-directional or shaped-coverage as selected by the contractor based on topography. The antenna system and cabling shall be furnished to provide adequate system gain. The antenna shall be capable of withstanding the environmental conditions of 130 mph wind and 1 inch radial ice without failure. Lightning protection shall comply with NFPA 78

7.3.1 The Contractor shall provide and install an antenna assembly, antenna wall-mount bracket, lightning arrestor kit, coaxial cable and connector. The Contractor shall refer to drawings for detail of antenna installation, manufacturer, and part numbers. The Contractor shall coordinate with Contracting Officer for exact location of installation.

7.4 Circuit Connections: Circuit conductors entering or leaving the panel shall be connected to screw-type terminals with each terminal marked for identification.

7.5 Storage Batteries: Storage batteries shall be provided and shall be sealed, lead-calcium types requiring no additional water. The batteries shall have ample capacity, with primary power disconnected, to operate the fire alarm system for a period of 60 hours. Following this period of operation via batteries, the batteries shall have ample capacity to operate all components of the system, including all alarm signaling devices in the total alarm mode for a period of 15 minutes.

Batteries shall be sized to deliver 50 percent more ampere/hours than required for the calculated capacities. Battery cabinet shall be a separate compartment within the control panel cabinet.

7.6 Battery Charger: Battery charger shall be completely automatic, with high/low charging rate, capable of restoring the batteries from full discharge to full change within 8 hours. A separate ammeter shall be provided to indicating rate of charge. A separate voltmeter shall be provided to indicate the state of battery charge. Pilot light shall indicate when batteries are manually placed on a high rate of charge as part of the unit assembly if a high rate switch is provided.

7.7 Manual Fire Alarm Stations. Manual fire alarm stations shall conform to the applicable requirements of UL 38. Manual stations shall be connected into alarm initiating circuits. Stations shall be single action type. Stations shall be finished in red, with raised letter operating instructions of contrasting color. Stations requiring the breaking of glass or plastic panels for operation are not acceptable. Stations employing glass rods are not acceptable. The use of a key or wrench shall be required to reset the station. Gravity or mercury switches are not acceptable. Switches and contacts shall be rated for the voltage and current upon which they shall operate. Stations shall have a separate screw terminal for each conductor. Where boxes must be surface mounted, boxes shall be painted the same color as the fire alarm manual stations.

8. FIRE DETECTING DEVICES

8.1 Fire detecting devices shall comply with the applicable requirements of NFPA 72, NFPA 90A, UL 268, and UL 521. The detectors shall be provided as indicated. Detector base shall have terminals for making connections. No solder connections will be allowed. Detectors shall be connected into alarm initiating circuits.

8.2 Heat Detectors. Heat detectors shall be as indicated. Detectors shall be rated for a minimum of 50 foot spacing (smooth ceiling rated) in accordance with UL 521. Detector coverage shall be 2500 square feet minimum, with maximum distance from wall of 25 feet minimum. (Detectors located in areas subject to moisture or exterior atmospheric conditions or hazardous locations as defined by NFPA 70, shall be types approved for such locations.) Detectors shall have screw terminals for making all wiring connections. Detectors shall be of the low profile type.

8.2.1 Fixed Temperature Detectors. Fixed temperature detectors shall be outlet box mounted and supported independently of wiring connections. Unless otherwise indicated, detectors shall have a specific temperature setting of 135 degrees F. Detectors located in mechanical/electrical rooms or other areas with unconditioned air shall be rated for 194 degrees F.

8.2.2 Combination Fixed-Temperature and Rate-of-Rise Detectors. Detectors shall be outlet box mounted and supported independently of wiring connections. Contacts shall be self-resetting after response to rate-of-rise principle. Under fixed temperature actuation, the detector shall have a permanent external indication which is readily visible.

8.3 Smoke Detectors. Detectors shall be designed for detection of abnormal smoke densities by the ionization principle. Detectors shall contain a visible indicator lamp that shows when the unit is in alarm condition. Detectors shall not be adversely affected by vibration or pressure. Detectors shall be the plug-in type in which the detector base contains terminals for making all wiring connections. Detectors that are in concealed (above false ceilings, etc) locations shall be provided with a remote visible indicator lamp.

8.3.1 Ionization Detectors. Ionization detectors with a dual chamber shall be responsive to both invisible and visible particles of combustion. One chamber shall be a reference chamber and the second a sampling chamber. Detectors containing radium shall not be provided. Detectors shall not cause an alarm condition due to anticipated fluctuations in relative humidity. Detector shall require no replacement or readjustment to restore it to normal operation after an alarm condition. Each detector shall be capable of withstanding ambient air velocity up to 2000 fpm in accordance with UL 268.

8.3.2 Duct Smoke Detectors. Detectors shall have a duct housing, mounted exterior to the duct, with perforated sampling tubes. Activation of a detector shall cause shutdown of the associated air-handling unit. Detectors shall be rated for the air velocity to be expected. Detectors shall be mounted in readily accessible locations. Detectors shall be capable of activating a remote indicating lamp on a remote annunciator.

8.4 Combination Smoke and Heat Detectors. Combination smoke and heat detectors shall have an audible device (self-contained) and be designed for detection of abnormal smoke densities by the photoelectric principle and abnormal heat by a fixed temperature sensor. Detectors shall be provided with an LED light source. Failure of the LED shall not cause an alarm condition and the sensitivity shall be factory set at a nominal 3 percent and require no field adjustments of any kind. The audible devices shall have a sound output of at least 85 dBA at 10 feet. Detectors shall also be integral with a heat sensor rated at 135 degrees F. Detectors shall contain a visible indicator lamp that shows when the unit is in alarm condition and not be adversely affected by vibration or pressure. Detectors shall be the plug-in type in which the detector base contains terminals for making all wiring connections.

8.5 Infrared (IR) Single Frequency Flame Detector. The IR detector shall be sensitive to the 41,000 to 47,000 Angstroms range. The detector shall consist of two IR sensors. One will trigger an alarm when an intense IR signal is received. The other IR sensor will trigger for an appropriate flame flicker frequency that exceeds a lower IR intensity. Detectors shall operate on dc over electrically supervised wiring circuits. Loss of power to the detector shall result in a trouble signal. The flame detector shall have self-test capability. The self-test shall allow each detector to be individually tested.

8.6 Infrared (IR) Dual Frequency Flame Detector. The IR detector shall consist of two or more IR sensors, each selected for a different IR frequency. The primary sensor shall be sensitive to the 41,000 to 47,000 Angstroms range. Secondary sensors are tuned to different IR wavelengths to null out the effect of black body radiation to the primary sensor. Detectors shall operate on dc over electrically supervised wiring circuits. Loss of power to the detector shall result in a trouble signal. The flame detector shall have self-test capability. The self-test feature shall allow each detector to be individually tested.

8.7 Ultraviolet (UV) Flame Detectors. The UV detector has a fast response time and usually is not affected by rain, wind, snow, high humidity, or temperature and pressure extremes. UV units will produce false alarms if they are exposed to arc welding or X and gamma radiation. They can also be blinded by oil film or smoke. UV flame detectors that are used in dirty and dusty environments may be equipped with automatic self-test and self-cleaning devices. The cleaning device uses a stream of clean air across the lens surface to minimize the buildup of contaminants.

8.8 Combination UV/IR Flame Detector. The UV/IR detector shall provide discrimination against false alarms by requiring both UV and Ir flame detection before an alarm is sent. The UV sensor shall be sensitive in the range of 1850 to 2650 Angstroms only. The detectors shall operate on dc over electrically supervised wiring circuits. Loss of power to the detector shall result in a trouble signal. The flame detector shall have self-test capability. The self-test shall allow each detector to be individually tested.

9.0 NOTIFICATION APPLIANCES

9.1 Audible appliances shall be heavy duty and conform to the applicable requirements of UL 464. Devices shall be connected into alarm indicating circuits. All devices shall have separator screw terminals for each conductor.

9.2 Alarm Bells. Bells shall be surface mounted or recessed as coordinated with Contracting Officer. Bells shall be suitable for use in an electrically supervised circuit. Bells shall be the underdome type producing a sound output rating of at least 85 dBA at 10 feet. Bells used in exterior locations shall be specifically listed or approved for outdoor use and provided with metal housing and protective grilles. Single stroke, electrically operated, supervised, solenoid bells shall be used.

9.3 Alarm Horns. Horns shall be recessed. Horns shall be vibrating type suitable for use in an electrically supervised circuit and with a sound output rating of at least 85 dBA at 10 feet. Horns used in exterior locations shall be specifically listed for outdoor use and shall be provided with metal housing and protective grilles. Color shall be coordinated with Contracting Officer on a per task order basis.

9.4 Combination Audible/Visual Notification Appliances. Combination audible/visual appliances shall be factory assembled. Units shall be suitable for use in an electrically supervised circuit and shall have a sound output rating of at least 85 dBA at 10 feet. Visual indication shall be accomplished by high intensity optic lens and flash tubes. Color shall be coordinated with Contracting Officer on a per task order basis.

9.5 Chimes. Chimes shall be electrically operated, supervised, single stroke, heavy-duty type with (tempered) (polished) (chrome-plated) tone bar and resonator to sound fire alarm code signals. Chimes shall have a minimum sound rating of 80 dBA at 10 feet.

10. ANNUNCIATION EQUIPMENT

10.1 Annunciator Panel. Panel shall be part of the fire alarm control panel. A visual annunciator shall be provided for each zone and spare zone as indicated. Each lamp shall provide specific identification of the zone by means of a permanently attached rigid plastic or metal sign with either raised or engraved letters. Zone identification shall consist of word description of the zone.

11. FIRE DETECTION AND ALARM SYSTEM PERIPHERAL EQUIPMENT

11.1 Electromagnetic Door Hold-Open Devices. Devices shall be attached to the walls unless otherwise indicated. Devices shall comply with the appropriate requirements of UL 228. Devices shall operate on power from the fire alarm control panel. Compatible magnetic component shall be attached to the door. Under normal conditions, the magnets shall attract and hold the doors open. When magnets are de-energized, they shall release the doors. Magnets shall have a holding force of approximately 25 pounds. Devices shall be UL or FM-01 approved. Housing finish for device shall match door hardware. Operation shall be fail-safe with no moving parts.

11.2 Conduit shall comply with UL 06 and UL 797.

11.3 Wiring. All wiring shall be copper. Wiring for strobe light circuits shall be shielded No. 12 AWG minimum. Wiring for 120V AC power shall be No. 12 AWG minimum. Wiring for low voltage dc circuits shall be No. 14 AWG minimum. Power wiring and control wiring shall be isolated. All wiring shall conform to NFPA 70. All conductors shall be color coded. Wiring code color shall remain uniform throughout the circuit. Pigtail or T-tap connections are unacceptable.

11.4 Special Tools and Spare Parts. Special tools necessary for the maintenance of the equipment shall be furnished. Two spare sets of fuses of each type and size required and five spare lamps and LED's of each type shall be furnished. Two percent of the total number of each detector, but no less than two each, shall be furnished.

PART 3: EXECUTION

12. INSTALLATION

12.1 All work shall be installed as shown and in accordance with the manufacturer's diagrams and recommendations, unless otherwise specified.

12.2 Power Supply for System. A single dedicated branch-circuit connection for supplying power to each building system shall be provided. Emergency power supply shall be automatically transferred upon failure of the normal power supply. The power disconnect shall be separate from the circuit breaker. The “disconnect” shall be the type that can be locked in the "on" position.

12.3 Wiring. Wiring for systems shall be installed in 3/4 inch minimum diameter conduit; however, the wiring for the fire alarm system shall not be installed in conduits, junction boxes, or outlet boxes with conductors of lighting and power systems. No more than one conductor shall be installed under any screw terminal. All circuit conductors entering or leaving any mounting box, outlet box enclosure or cabinet shall be connected to terminals with each terminal marked in accordance with the wiring diagram for identification. Connections shall be made with either crimp-on terminal spade lugs or with approved pressure type terminal blocks. The use of wire nut type connectors are prohibited in the system. All wiring within any control equipment shall be readily accessible without removing any component parts. The fire alarm equipment manufacturer's representative shall be present for the connection of wiring to the control panel.

12.4 Control Panel. The control panel and its assorted components shall be mounted so that no part of the enclosing cabinet is less than 12 inches above the finished floor nor more than 78 inches above the finished floor. All manually operable controls shall be at least 3 feet and less than 5 feet above the finished floor. Panel shall be installed to comply with the requirements of UL 864. Unless otherwise indicated panel shall be installed on a 3/4 inch thick plywood backboard. Backboard shall be finished with two coats of varnish. Space shall be reserved on backboard for transmitter by others.

12.5 Detectors. Detectors shall be installed in accordance with NFPA 72E. Detectors shall be at least 12 inches from any part of lighting fixtures. Detectors shall be located at least 3 feet from diffusers of air handling systems. Each detector shall be provided with appropriate mounting hardware as required by its mounting location. Detectors which mount in free space shall be mounted directly to the end of the stubbed down rigid conduit drop. Conduit drops shall be firmly secured to minimize detector sway. Where length of conduit drop from ceiling or wall surface exceeds 3 feet, sway bracing shall be provided.

12.6 Notification Appliances. Devices shall be mounted a minimum of 8 feet above the finished floor unless limited by ceiling height or otherwise indicated.

12.7 Grounding. Grounding shall be provided to building ground.

13. TESTING

13.1 The contractor shall notify the Contracting Officer 30 days before the performance and acceptance tests are to be conducted. The installer shall provide the completed NFPA 72 form and as-builts no later than one week before the final acceptance testing. The installer shall start the battery test 48 hours prior beginning the final acceptance testing. The first test to be done at the final acceptance test will be full system alarm on battery power for time period required in NFPA 72. If system passes the battery test, then the remaining portion of the testing shall continue on A/C power, otherwise testing shall be rescheduled per the preceding procedure after battery deficiencies are corrected.

The tests shall be performed in the presence of the Contracting Officer under the supervision of the fire alarm system manufacturer's qualified representative. The contractor shall furnish all instruments and personnel required for the tests.

13.2 Preliminary Tests. Upon completion of the installation, the system shall be subjected to functional and operational performance tests including tests of each installed initiating and notification appliance. Tests shall include the meggering of all system conductors to determine that the system is free from grounded, shorted and open circuits. The Megger test shall be conducted prior to the installation of fire alarm equipment. Smoke detector bases shall be equipped with jumpers for the Megger test. If deficiencies are found, corrections shall be made and the system shall be re-tested to assure that it is functional.

13.3 Acceptance Test. The testing shall be in accordance with NFPA 72H and shall verify that all previous deficiencies have been corrected. The test shall include the following:

13.3.1 Test of each function of the control panel.

13.3.2 Test of each circuit in both trouble and normal modes.

13.3.3 Test of alarm initiating devices in both normal and trouble conditions.

13.3.4 Test of each control circuit and device.

13.3.5 Test of each alarm notification appliance.

13.3.6 Test of the battery charger and batteries.

13.3.7 Complete operational tests under emergency power supply.

13.3.8 Visual inspection of all wiring connections.

13.3.9 Opening the circuit at each alarm initiating and indicating device to test the wiring supervisory feature.

Excerpt from UFC-600-1 Plans and Calculations. For new systems or modified systems, working plans and calculations must be prepared and submitted for approval by a registered professional fire protection engineer or an individual that has obtained National Institute for Certification in Engineering Technologies, Automatic Sprinkler Systems, Level III certification (minimum) or Special Hazards Suppression Systems, Level IV certification, in accordance with the applicable NFPA code. Submit the fire extinguishing system construction (shop) drawings to the appropriate components designated Fire Protection Engineer.

TABLE 4-1

Sprinkler System and Water Supply Design Requirements for Sprinklered Facilities

OCCUPANCY

CLASSIFICATIONa

SPRINKLER SYSTEM
HOSE STREAM ALLOWANCE

L/Min (GPM)

DURATION

OF SUPPLY

Minutes

DESIGN DENSITY

L/min/m² (GPM/ft²)

DESIGN AREA

m² (ft²)

Light Hazard
4.1 (0.10)
280b (3000)b
950 (250)
60

Ordinary Hazard Group 1

6.1 (0.15)
280b (3000)b
1900 (500)
60

Ordinary Hazard Group 2

8.2 (0.20)
280b (3000)b
1900 (500)
90

Extra Hazard Group 1

12.2 (0.30)
280 (3000)
2840 (750)
120

Extra Hazard Group 2

16.3 (0.40)
280 (3000)
2840 (750)
120

a Refer to Appendix C for occupancy hazard classification.

b Where listed quick-response sprinklers are used throughout the system, the design area in Table 4-1 may be permitted to be reduced without revising the density as permitted in NFPA 13 except for facilities that are required to comply with UFC 4-010-01, DoD Minimum Antiterrorism Standards for Buildings.

Note: The protection requirements identified in Table 4-1 are based on standard commercial practices followed throughout civilian industry for highly protected risk (HPR) properties. Table 4-1 represents the minimum requirements necessary to establish minimum comprehensive life, mission, and property loss prevention. Table 4-1 was adapted as a result from detailed studies by Factory Mutual of loss experience from 1956 to 1965, loss experience in selected occupancies from 1966 to 1977 and from 1981-1990, and fire test data.

4-2.3.2 Sprinkler Design Area Adjustments.

4-2.3.2.1 For dry pipe systems, the design area of sprinkler operation in Table 4-1 must be increased by 30 percent per NFPA 13.

4-2.3.2.2 The design areas in Table 4-1 must be increased by 30% for sloped ceilings that exceed a pitch of one in six.

4-2.3.3 The use of quick response automatic sprinklers (QRAS) is limited to wet systems.

4-2.3.4 Hydraulic Calculations. New sprinkler systems protecting areas of 139 m² (1,500 ft²) and greater must be designed using hydraulic calculations. Use of pipe schedule designs is strongly discouraged for any sprinkler system. Required discharge densities and areas of discharge operation are given in Table 4-1. Calculations must follow the format of NFPA 13. Pipe friction losses and equivalent lengths of pipe for fittings and valves must be in accordance with NFPA 13.

Note: Additions to existing pipe schedule systems may be designed using the pipe schedule method.

4-2.3.4.1 The designer (a fire protection engineer) will provide hydraulic calculations demonstrating that the design will provide an adequate water supply for the fire extinguishing systems. Hydraulic calculations will be submitted no later than the 35 percent design submission. Calculations must be based on recent water flow test data.