Specification_for_Transformer_Build_with_Pictures.pdf
PDF 10 MB Posted
- Attached to
- Pad Mounts Federal contract opportunity
- Solicitation number
- FA4801-19-Q-1010A
About this file
Specifications and Pictures
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Questions_Set_2.pdf | ||
| Questions_Set_1.pdf | ||
| COMBO_Pad_Mounts_A.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Specifications for Transformer Build Three Phase Pad Mount 3750 kVA transformer – 2 each
HV: 4160/2400
LV: 480/277
Primary Bushings: Dead Front (600 amp 1 piece dead breaking bushings) – Radial Feed (Picture of connection elbow below)
Secondary Bushings: Need to feed out to Load Bank (10 input connections per phase on load bank and 4 ground connections on load bank)
Degree Rise: 65 C
Frequency: 60 hz
Impedance: Standard
Elevation: 4200 feet
Configuration: (Generator is WYE and Loadbank is Delta)
Cable: 1/0, 5 Kilovolt aluminum cable with concentric neutral (used to connect generator to PSC and PSC to transformer)
Windings: Copper
Additional Specs: Pressure Relief Valve, Pressure Gauge, Temperature Gauge, Liquid Level Guage, Drain and Sampler Valve
** To Include Delivery**
Load Bank Specs
Model/Part#: Avtron 5000 series (K975A/D39939)
480 Volts, 60 Hz, 2500 kW
10 cables per phase/400 amps max per terminal
4 cables for ground
Connections: Cam-type quick-connect male cable receptacles are securely mounted to the cool air intake side of the load bank.
One-Line Diagram
--Pictures of Connections & Equipment Attached—
BEAR Power Unit
MEP-12
IBEAR
High Voltage 1/0 5kV Cable
Primary Switching
Center
High Voltage 1/0 5kV Cable
Transformer Cables Loadbank
Pictures Table of Contents
Picture 1 – Loadbank Data Plate
Picture 2 – Loadbank Phase Terminal Connection
Picture 3 – BEAR Power Unit Output Terminals
Picture 4 – IBEAR Output Terminals
Picture 5 – MEP 12 Output Terminals
Picture 6 – 600 Amp Elbow connection on 1/0, 5 Kilovolt aluminum high voltage cable
Picture 7 – Primary Switching Center (PSC) Data Plate
Picture 8 – PSC Output Terminals (Input Terminals are the same)
Picture 9 – PSC Breaker Data Plate
Picture 10 – PSC Breaker
Page 13 – 17 – Loadbank Schematics
ASCO
| Specifications for Transformer Build |
| Transformer Build Specs with pics |
| Loadbank Data Plate |
| Loadbank Terminals |
| BEAR Power Unit Terminals |
| IBEAR Terminals |
| MEP12 Terminals |
| HV Cable Terminal |
| Data Plate PSC |
| PSC Input Output2 |
| PSC Breaker Data Plate |
| PSC Breaker |
| Loadbank Schematics |