Atch_4 _Total_Dynamic_Head_Calc _Data_Sheet _and_Pictures.pdf

PDF 1 MB Posted

Attached to
Repair Well #5, Pump 4, and Motor Federal contract opportunity
Solicitation number
FA4620-14-T-A157
Issued by
Department of the Air Force Air Mobility Command

About this file

Attachment 4 Total Dynamic Head Data Sheet and Pictures

View the file

Other files for this federal contract opportunity

Other files attached to Repair Well #5, Pump 4, and Motor, newest first.
File Type Posted
FA4620-14-T-A157-0001.pdf PDF
Amendment_1 _Atch_1.docx DOCX document
Atch_2 _STD_Comm_Warranty_Clause.pdf PDF
Atch_1 _SOW_Dated_8_July_2014.pdf PDF
FA4620-14-T-A157.pdf PDF
Atch_3 _WD_05-2565_(Rev_13).pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TOTAL DYNAMIC HEAD (TDH) CALCULATION

FOR FAIRCHILD AFB FT WRIGHT WELLFIELD’S PUMP 4 WELL 5

1. Applicable excerpts from the Fairchild AFB Water System Plan:

1286801621A Typewritten Text

RFQ FA4620-14-T-A157

Attachment #4

Design Point = 455 gpm @ 760 feet of Total Dynamic Head:

2. Total Dynamic Head (TDH) = (Elevation Head) + (Pressure Head) + (Friction Loss) Elevation Head (ft) = [(2,391-1,697-32) ft] = 662 ft.

Pressure Head (ft) = [Backpressure from Pump 3 Well 5, Pump 5, Well 5; Well 6; and Well 7] = = ? (variable) Friction Loss (ft) = [< (0.4 ft loss/100 ft. of pipe)(25,233 ft)] = 101 ft TOTAL DYNAMIC HEAD (TDH) = (662 + ? + 101) ft = 763 feet

Atch 4, Total Dynamic Head and Data Sheet