Attachment_7_-_Questions_and_Answers_part_2.docx

DOCX document 15 KB Posted

Attached to
Replace Highbay Lights Multiple Buildings Federal contract opportunity
Solicitation number
FA4528-17-R-0003
Issued by
Department of the Air Force Global Strike Command

About this file

Attachment 7a - Final Questions and Answers

View the file

Other files for this federal contract opportunity

Other files attached to Replace Highbay Lights Multiple Buildings, newest first.
File Type Posted
SF30_Hubzone.pdf PDF
17-R-0003-0004.pdf PDF
Attachment_7_-_Revised_Questions_and_Answers.docx DOCX document
sf30.pdf PDF
AF66_Submittal_Register_revision_3.pdf PDF
14-0031_Specifications_revision_7_(with_amendments).pdf PDF
Attachment_14-_Building_970.pdf PDF
Attachment_7_-_Revised_Questions_and_Answers.docx DOCX document
Attachment_10_-_Building_545.pdf PDF
Attachment_13_-_Building_867.pdf PDF
Attachment_9_-_Building_455.pdf PDF
Attachment_12_-_Building_837.pdf PDF
FA4528-17-R-0003_Amendment_2.docx DOCX document
Attachment_1_-_Revised_Specifications.pdf PDF
Attachment_11_-_Building_765.pdf PDF
SF_-30.pdf PDF
BuildingFixture_Heights.docx DOCX document
14-0031_Specifications_revision_5_(with_amendments).pdf PDF
970.dwg DWG drawing
455.dwg DWG drawing
AF66_Submittal_Register_revision_2_(with_amendments).pdf PDF
837.dwg DWG drawing
Combined_14-0031_revision_2_(with_amendments).pdf PDF
545.dwg DWG drawing
14-0031_AS_BUILTS.pdf PDF
867.dwg DWG drawing
761.dwg DWG drawing
Attachment_7_-_Questions_and_Answers.docx DOCX document
Attachment_3_-_Drawings_14-0031.pdf PDF
Attachment_2_-_Submittal_Register.pdf PDF
Attachment_6_-_Financial_Responsibility.docx DOCX document
Attachment_4_-_WD.pdf PDF
Attachment_5_-_Past_Performance_Information_Form.docx DOCX document
FA4528-17-R-0003.pdf PDF
Attachment_1_-_Specification_14-0031.pdf PDF
Show all 35

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Pre-Proposal Offeror Questions and Government Responses QJVF 14-0031, Replace Highbay Lights Multi Bldgs

FA4528-17-R-0003

Attachment 7a 14 April 2017

1. Building 545 has high bays and strip fixtures in the vehicle area. I assume we are replacing the high bay fixtures and not replacing the strip fixtures. Is this correct?

Correct, only high bay fixtures.

2. Also the lighting in the office at Area E and the strip lighting above it were not lined out in REV 2 but I did not think those were included. Please clarify if they are since they are not high bays.

Only high bay fixtures.

3. In Building 837. I count 83 high bay fixture we are replacing. Given the layout on the record drawing looks uneven, is this count and layout correct since we are changing one for one?

See specifications for accuracy of as-built drawings.

4. What are the allowable shutdown schedules for switch overs?

See Specifications

5. Who is responsible for providing the design drawings?

See Specifications

6. Has an environmental site assessment been completed and if so can it be provided?

None will be provided.

7. Are there any know environmental hazards?

No.

8. Who is providing the record drawings for solicitations FA4528-17-R-0003 and FA4528-17-R-0004 as shown is specifications section 01 78 00 1.2.2 See Specifications

9. Why are the two solicitations being separated and not included as one?

N/A

10. Will the Government be requiring the electrical equipment to be painted as identified in section 26 00 00 3.1?

See Specifications

11. Where are the source drawing identified in section 01 37 00 1.5.2 See Specifications

12. Will the Government be requiring full compliance with the EM385 as stated in the specifications?

Yes

13. Will access to each site be escorted or will the contractor be allowed to be badged?

Sites on the flight line will be escorted.

14. What time restraints for access should be allowed for entry from the front gate to each project site?

Various.

15. What are the access routes are available to each project site?

Will be addressed at Pre-construction meeting.

16. What specific perimeter area lighting of buildings are required to be replaced?

See Drawings

17. Can a lighting operation plan be provided for each building?

No

18. Where is the specification section in regards to raceways?

Follow NEC 2017

19. Is there a typical connection detail preferred for fixture connection? Plug in or hard wired?

No.

20. What fixtures are required to be explosion proof?

None.

21. Is there a preferred hanger attachment for each fixture?

No.

22. What are the normal work hours/days allowed?

See specification Addendum.

23. What are no work days?

See Specifications

24. What is the holiday schedule where the contractor would be limited from working?

See Specifications.

25. Will aircraft be removed from work zones as the contractor needs access to the bays?

Yes.

26. What are the minimum credentials for the design professional?

See Specifications.

File details come from the government source that posted it. Updated .