Attachment 2 Drawings FA4417-16-R-0013 Replace Generators Multiple Buildings - Phase C

View the file

Other files for this federal contract opportunity

Other files attached to Replace Generators - Phase C, newest first.
File Type Posted
FA4417-16-R-0013_Q A_with_responses_18_Apr_16.docx DOCX document
FA4417-16-R-0013_Site_Visit_Minutes.pdf PDF
FA4417-16-R-0013_Site_Visit_Attendees.pdf PDF
Attachment_4_Schedule_of_Wage_Rates.pdf PDF
Attachment_1_Specifications.pdf PDF
Solicitation_FA4417-16-R-0013.pdf PDF
Attachment_6_Financial_Reference_Sheet.pdf PDF
Attachment_3_SGFP_Listing.pdf PDF
Attachment_5_Past_Present_Performance_Questionnaire.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

unk

L e t o u r n e a u

C i r c l e

L e t o u r n e a u

C i r c l e

F o x x

A v e n u e

Tully Street

S i m p s o n e n u e

Tully Street

R e d

H o r s e

R o a d

Tupelo Circle

Bakke Street

M a y

S t r e e t

Bakke Street

R e d

H r s

R a d

Grimm Lane

Hume Drive

Bland Street

Galvan Street

Hume Drive

Lewis Drive

Hodges Street

Walters Drive

H u m

D r i v e

A c h i v e

H a r r i s i v e

Hume Drive

McIntosh Court

US98

O N e i l

A v e n u e

In d e p e n d e n c e

R o a d

US98

C o d y

A v e n u e

Purcell Drive

C a m p a i g r e e t

Whitbeck Street

Gelshlager Street

Clark Road

Hume Drive

Schmauss Lane

W e a v e n u e

US98

M cM illa n S tre et

C o r l w a d

W a l k p

W y

I n d e p e n d e n c a d

Bedel Street

B e n n e t t

A v e n u e

Frazier Street

C r u z

A v e n u e

Red Horse Road

C r u z

A v e n u e

T u l l r e e t

T u l l y

S t r e e t

Bedel Street

W e s t f a

C r c l e

H a m b

P a c e

R r a d

Tully Street

L u ka sik A ve n u e

C o e n u e

K e r w o o d

R o a d

US98

Lielmanis Avenue

H o w l t e y

US98

M a i n t e n a n a

T u l r e e t

US98

H a r t s r e e t

M c

C l e r e e t

T e r e n u e

I n d e p e n d e n a d

M i t c h e l l

R o a d

Bartley Street

D o w n s

R o a d

90918

92470

90308

92006

92007

90600

92431

92081

90101

90761

91048

99045

91307

90325

90637

90106

92469

90359

91159

92427

92550

91400

90030

92085

91265

90053

92046

90225

99061

99029

99118

90815

91301

90880

92093

91148

91303

99042

92429

91364

90366

91056

99500

90304

91254

90051

90531

99030

91045

90636

90062

92449

92519

90115

90370

90064

92403

90713

90326

92028

92019

92021

91047

90525

90806

90138

92060

90352

91029

90371

90137

92472

90748

90822

90128

90618

90035

90619

90532

90369

92065

90935

92438

90033

90702

91255

91520

90521

92091

90510

99142

90302

90345

90232

92404

90382

92080

90617

92059

91137

92513

90003

92057

92042

92043

92037

92551

92017

92016

92107

91142

90300

90374

92546

92084

90048

99116

92099

99059

90621

92105

90339

91300

90008

92102

91163

90347

92098

90358

90825

99022

99145

99126

99044

90390

99056

99055

99083

99007

99105

91016

90552

99060

90131

99001

99998

90950

92090

92050

90334

91050

91363

91130

90337

92538

92061 92082

90049

90375

90229

90707

92052

92035

90615

92406

90105

90616

90928

99160

99999

99068

90635

91039

91009

90015

92432

92039

90121

91031

90801

90610

92275

92420

90759

92430

91151

91023

91140

92011

91037

90802

99043

91055

91252

92013

92000

90703

92528

92455

90005

90084

92024

92069

90328

90731

90372

92032

92030

90717

90145

91054

92436

91155

90346

90606

92452

92451

90378

92022

91012

90001

90223

90642

90054

90377

92040

92027

92026

91146

90230

90817

92055

92010

92072

92076

92071

92068

92058

90058

91053

90333

90320

90827

92004

92100

99115

90207

92522

92087

91104

91103

90580

91105

92437

90809

91330

92553

90701

92548

90327

92435

90626

92549

92001

92008

92051

90724

91122

92434

90511

92009

92461

90085

90609

99023

99716

99717

99718

99719

99127

99051

99999

99999

99999

99025

99024

92005

90315

90210

99067

92034

91032

92023

99058

92505

90522

90509

90747

92089

91154

90330

92426

92419

92463

92501

99535

99150

92516

92541

90607

99104

99090

99048

99020

99106

99107

90340

90075

90577

92048

90711

92094

91133

90523

91112

92424

90388

99057

91510

99041

90068

90069

90629

90392

92064

90037

90141

99004

90362

92537

90613

90134

92014

92529

90052

91162

90951

92464

92025

92446

92515

91161

90381

90387

99112

92103

99053

99038

91057

90729

99094

99146

92502

92450

92033

91034

91132

91030

91152

92556

90076

91145

90911

90102

92441

92471

90023

90357

90111

90070

92054

90601

92527

91099

92407

92015

92400

92425

92079

91109

90914

91156

90811

90743

91007

91360

91325

90081

90833

92038

92533

99137

92095

90368

91052

91164

90742

92083

92555

92514

90823

90627

90810

92047

90361

99010

90714

90763

90109

92503

90329

91106

91135

91310

92460

92428

91266

99117

91500

92044

90213

92012

92036

92539

90039

90073

90074

91035

90505

92466

91120

91601

90926

91025

91603

91365

99158

99054

92562

99999

99999

99019

90535

91351

99126

92062

91020

90036

90518

91370

92088

92063

92544

90402

90140

92521

99031

92473

91361

92518

92433

91027

91024

91515

92523

90318

92545

90373

90343

91147

92445

92530

90117

92092

90705

90517

92511

90331

92444

90079

91000

92401

91033

99098

90838

91538

91119

91114

90203

92045

90632

90720

92067

92097

92543

92506

92535

92524

92070

92056

92053

92041

92104

92106

92074

91268

92459

92508

91036

90624

92517

90625

91260

90553

90638

90066

90061

90057

91028

91021

92525

92440

99141

90816

92468

91144

90034

90755

90310

90220

92086

90551

90317

90050

90367

90323

92402

92467

90055

92018

91257

90029

92020

92002

92003

92073

90519

99065

92101

92463

90712

91013

92442

99902

92096

90135

91049

90829

92465

92408

90231

90603

91250

90322

92507

92066

90718

92049

90501

90640

90353

91041

92542

91153

92552

90002

92108

92276

92531

90700

92439

90113

92564

91302

90812

90708

91126

90010

92077

90060

91136

91042

90332

91258

91113

90630

90206

90421

90028

92075

92078

92031

92500

91259

91262

90067

90059

92485

92509

92536

90349

90065

90612

99049

90228

90319

90221

91625

92418

99005

91141

90336

99009

90502

90412

90038

92540

90202

92557

91537

90503

90021

99077

99154

90628

92547

90506

91101

90507

90380

90379

91149

91124

29075

29075

29075

29075

90396

90396

29073

29073

90534

90581

90734

91038

91043

29077

29077

W a l k p y

90512

90513

90513

90512

90360

90363

90351

92479

92478

92477

91264

91263

91261

91041

90813

90757

90749

90626

99121

90524

99103

90364

90356

90083

30041

D o w a d

90611

90500

90508

90311

90086

M

Y

T

R

E

E

T

91058

91059

99958

90917

90905

90306

91168

91107

91157

90534

90536

90800

Kissam Street

90727

30007

99326

LOCATION MAP

N.T.S.

LOCATION MAP & INDEX OF DRAWINGS

ELECTRICAL PLANS - LIFT STATION 90007

T-1

E-1

E-2

E-3

E-4

SHEET # TITLE

INDEX OF DRAWINGS

MAIN GATE

HAUL ROUTE

E-5

E-6

E-7

REPLACE GENERATOR 5 YEAR PLAN

MULTIPLE BUILDINGS

(BUILDINGS 90007, 90020, 90027, 90043, 90056, 90215, 90355 & 91350)

HURLBURT FIELD, FLORIDA

FTEV 13-1049C

ELECTRICAL PLANS - BUILDING 90020

ELECTRICAL PLANS - LIFT STATION 90027

ELECTRICAL PLANS - BUILDING 90043

ELECTRICAL PLANS - BUILDING 90056

ELECTRICAL PLANS - BUILDING 90215

POWER PRODUCTION SHOP

BUILDING 90043

BUILDING 90056

BUILDING 90215

BUILDING 90355

BUILDING 91350

BUILDING 90020

E-8

ELECTRICAL PLANS - BUILDING 90355

ELECTRICAL PLANS - BUILDING 91350

LIFT STATION 90007

LIFT STATION 90027

GENERAL NOTES:

1. ENSURE THAT NO WASTEWATER ASSOCIATED WITH THE POURING OF ANY CONCRETE IS

DISCHARGED TO SURFACE WATERS OF THE STATE (E.G.: WETLANDS, STORMWATER SYSTEMS, ETC.)

2. TO ENSURE THE REQUIREMENTS OF THE CLEAN AIR ACT AND AFI 32-7040 ARE MET, ALL GENERATOR

INFORMATION, INCLUDING ANY RUN-TIMES ASSOCIATED WITH THE INSTALLATION, MUST BE ENTERED

INTO THE AIR PROGRAM INFORMATION MANAGEMENT SYSTEM (APIMS). THIS INFORMATION AND DATA

MUST BE REPORTED TO MR. BARRY L. WOODS, 1 SOCES/CEIE, (850) 884-4652.

3. CONSTRUCTION AT EACH INDIVIDUAL BUILDING SHALL BE ACCOMPLISHED INDIVIDUALLY. THE

COMPLETE REMOVAL, CONSTRUCTION, REINSTALLATION, TESTING, AND GOVERNMENT ACCEPTANCE

OF EACH BUILDING SHALL BE COMPLETED BEFORE THE CONTRACTOR WILL BE ALLOWED TO START

CONSTRUCTION AT THE NEXT BUILDING.

4. POWER OUTAGES REQUIRED FOR CONSTRUCTION ACTIVITIES TO THE ELECTRICAL SERVICES TO

FACILITIES SHALL NOT EXCEED 12 HOURS AT A TIME.

5. THE CONTRACTOR SHALL PROVIDE FACTORY CERTIFIED GENERATOR START-UP PERSONNEL TO

PERFORM FACTORY START-UP IN ORDER TO BEGIN FACTORY WARRANTY.

6. WORK IS AUTHORIZED ON WEEKEND WITH PRIOR APPROVAL.

7. ENSURE CLEARANCES AROUND GENERATOR ARE AT LEAST 48” AT CONSTRUCTION COMPLETION.

8. FOR GENERATORS 250KW AND ABOVE THE CONTRACTOR SHALL PROVIDE 4” BOX BEAMS UNDER THE

GENERATOR TO PROVIDE CLEARANCE.

9. CONTROL WIRING IS CAT 5 CABLE.

MULTIPLE

T-1

3 FEB 2015

OF 9

FTEV 13-1049C

JRH/EWW

JRH

L O

C A

T I O

N

M

P

I N

D E

X

O

F

D

R A

W I N

G

EXISTING 104 A., 3 P. AUTOMATIC TRANSFER SWITCH

EXISTING MAIN DISCONNECT SWITCH

EXISTING LIFT STATION CONTROL PANEL

REMOVE EXISTING 20 KW GENERATOR SET.

E

U

S

J

EXISTING 104 A., 3 P. AUTOMATIC TRANSFER SWITCH

EXISTING MAIN DISCONNECT SWITCH

EXISTING LIFT STATION CONTROL PANEL

E

U

S

ELECTRICAL PLAN - LIFT STATION 90007 - NEW WORK

SCALE: 1/4" = 1'-0"

ELECTRICAL PLAN - LIFT STATION 90007 - DEMOLITION

SCALE: 1/4" = 1'-0"

INSTALL NEW 20 KW GENERATOR SET.

NO SCALE

SINGLE LINE DIAGRAM - DEMOLITION

G

REMOVE EXISTING 20 KW

EMERGENCY GENERATOR SET.

EXISTING 104 A., 3 P.

AUTOMATIC TRANSFER SWITCH

EUS

EXISTING UNDERGROUND SECONDARY

TO REMAIN.

EUS

EXISTING MAIN

DISCONNECT SWITCH

EXISTING LIFT STATION

CONTROL PANEL

EXISTING CONTROL WIRING & CONDUIT TO REMAIN.

NO SCALE

SINGLE LINE DIAGRAM - NEW WORK

G

EXISTING 104 A., 3 P.

AUTOMATIC TRANSFER SWITCH

EUS

EXISTING UNDERGROUND SECONDARY

TO REMAIN.

EUS

EXISTING MAIN

DISCONNECT SWITCH

EXISTING LIFT STATION

CONTROL PANEL

EXISTING CONTROL WIRING & CONDUIT TO REMAIN.

NEW 20 KW/25 KVA, 480Y/277 V., 3Ø

EMERGENCY GENERATOR SET.

INSTALL NEW SCADA WIRING IN 3/4" RIGID GALV. STEEL CONDUIT.

ATTACH CONDUIT TO EXISTING CONCRETE PAD.

INSTALL NEW 2 # 12 & 1 # 12 GND. - 1/2" RIGID GALV. STEEL CONDUIT.

ATTACH CONDUIT TO EXISTING CONCRETE PAD.

FUEL TANK SIZING CALCULATION:

METERED LOAD ON EXISTING GENERATOR SET IS 17 KW.

NEW GENERATOR SET RATED AT 20 KW WILL BE LOADED AT 85%.

GENERATOR SET FUEL CONSUMPTION AT FULL LOAD IS 1.81 GPH.

72 HOUR FUEL CONSUMPTION AT FULL LOAD IS 130 GALLONS.

GENERATOR SET FUEL CONSUMPTION AT 75% IS 1.38 GPH.

72 HOUR FUEL CONSUMPTION AT 75% IS 99 GALLONS.

THE LARGEST FUEL TANK AVAILABLE FOR THE 20 KW GENERATOR SET W/ WEATHER PROTECTIVE

ENCLOSURE IS 91 GALLONS.

91 GALLONS AT 100% FUEL CONSUMPTION WILL PROVIDE APPROXIMATELY 50 HOURS OF BACKUP POWER.

BASIS OF DESIGN:

CUMMINS 20 KW C20 D6 W/ 91 GALLON SUB-BASE DIESEL FUEL TANK & WEATHER PROTECTIVE ENCLOSURE.

PHYSICAL DIMENSIONS: 65.7" LONG X 34" WIDE X 74" HIGH.

GENERAL NOTES:

1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT

FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY

THE CONTRACTOR.

2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO BE

DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER SWITCHES

THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER PRODUCTION SHOP. THE

CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO A LOCATION ON HURLBURT

FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.

3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER

SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.

4. THE CONTRACTOR SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS AND DISPOSE

OF PROPERLY.

5. THE GOVERNMENT WILL FILL THE DIESEL FUEL TANKS WITH FUEL AFTER THE CONTRACTOR HAS INSTALLED THE

NEW GENERATOR SETS, AND PRIOR TO TESTING OF THE GENERATOR SETS.

EMERGENCY POWER FEEDER NOTE:

RECONNECT EXISTING EMERGENCY POWER FEEDER TO NEW GENERATOR CIRCUIT BREAKER. IN THE EVENT THAT

THE EXISTING FEEDER IS NOT LONG ENOUGH TO REACH THE NEW CIRCUIT BREAKER, REMOVE THE EXISTING

FLEXIBLE CONDUITS BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS

WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE

NEW CONDUCTORS TO THE CIRCUIT BREAKER.

120 VOLT CIRCUIT NOTE:

INSTALL NEW 120 VOLT CIRCUIT CONDUIT & WIRING FROM EXISTING CIRCUIT BREAKER IN PANELBOARD TO NEW

GENERATOR SET. EXTEND 2 # 12 & 1 # 12 GND. - 1/2" RIGID GALV. STEEL CONDUIT EXPOSED ACROSS CONCRETE

PAD. INSTALL WEATHERPROOF "LB" FITTING FOR CONDUIT ENTRY INTO GENERATOR SUB-BASE FUEL TANK.

SCADA WIRING NOTE:

INSTALL NEW SCADA CONDUIT & WIRING FROM EXISTING SCADA ENCLOSURE TO NEW GENERATOR SET. EXTEND

SCADA WIRING IN 3/4" RIGID GALV. STEEL CONDUIT EXPOSED ACROSS CONCRETE PAD. INSTALL WEATHERPROOF

"LB" FITTING FOR CONDUIT ENTRY INTO GENERATOR SUB-BASE FUEL TANK. EXISTING SCADA CABLES MAY BE

REUSED IF THEY ARE LONG ENOUGH TO REACH THE NEW GENERATOR SET.

CONTROL WIRING NOTE:

RECONNECT EXISTING CONTROL WIRING CONDUCTORS TO THE NEW GENERATOR CONTROLLER. EXISTING

CONTROL CIRCUIT IS RUN IN ELECTRICAL NON-METALLIC TUBING INSTALLED IN SAME CONDUIT W/ EMERGENCY

POWER FEEDER. IN THE EVENT THAT THE EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE NEW

CONTROLLER, REMOVE THE EXISTING ENT CONDUIT, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS

WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE

NEW CONDUCTORS TO THE CONTROLLER.

PLAN VIEW - NEW SUB-BASE FUEL TANK

N.T.S.

NEW GENERATOR ELEVATION

N.T.S.

WORK NOTES:

1 EXISTING EMERGENCY POWER FEEDER TO TRANSFER SWITCH. SEE "EMERGENCY POWER FEEDER NOTE,"

THIS SHEET.

NEW 120 VOLT CIRCUIT. SEE "120 VOLT CIRCUIT NOTE," THIS SHEET.

REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING GENERATOR SET.

MOUNT ON SIDE OF GENERATOR BREAKER ENCLOSURE & RECONNECT TO EXISTING 120 VOLT CIRCUIT.

NEW SCADA WIRING & CONDUIT FROM GENERATOR SET TO EXISTING SCADA ENCLOSURE. SEE "SCADA

WIRING NOTE," THIS SHEET.

5 EXISTING CONTROL WIRING & CONDUIT. SEE "CONTROL WIRING NOTE," THIS SHEET.

FUEL TANK

CONDUIT ENTRY OPENING

OUTLINE OF GENERATOR

CIRCUIT BREAKER

LOCATE NEW GENERATOR SET SO THAT EXISTING

CONDUITS FALL WITHIN THE CONDUIT ENTRY

OPENING BELOW THE GENERATOR CIRCUIT BREAKER.

EXISTING SCADA ENCLOSUREEXISTING SCADA ENCLOSURE

REMOVE EXISTING 120 VOLT CONDUIT & WIRING AND EXISTING SCADA

CONDUIT & WIRING. SEE NEW WORK PLAN, THIS SHEET.

90007

E-1

E L E

C T

R I C

A L

P

L A

I F

T

S

T A

T I O

N

3 FEB 2015

REMOVE EXISTING 350 KW GENERATOR SET.

ELECTRICAL PLAN - BUILDING 90020 - DEMOLITION

SCALE: 1/8" = 1'-0"

E

U

S

NO SCALE

SINGLE LINE DIAGRAM - DEMOLITION

NO SCALE

SINGLE LINE DIAGRAM - NEW WORK

G

EXISTING

PANEL

"EM"

INTERCEPT EXISTING SECONDARY FEEDER BELOW

GRADE & EXTEND TO NEW GENERATOR SET. SEE

"EMERGENCY POWER FEEDER NOTE," THIS SHEET.

EXISTING 600 A., 4 POLE AUTOMATIC

TRANSFER SWITCH

EXISTING PULL BOX

EXISTING PANEL "EM"

EXISTING SWITCHBOARD "MDP"

EXISTING SCADA EQUIPMENT

NEW 300 KW GENERATOR SET.

ELECTRICAL PLAN - BUILDING 90020 - NEW WORK

SCALE: 1/8" = 1'-0"

E

U

S

EXISTING 600 A., 4 POLE AUTOMATIC

TRANSFER SWITCH

EXISTING PULL BOX

EXISTING PANEL "EM"

EXISTING SWITCHBOARD "MDP"

EXISTING SCADA EQUIPMENT

EXISTING PAD MOUNTED TRANSFORMEREXISTING PAD MOUNTED TRANSFORMER

REMOVE EXISTING CATWALK & TURN OVER TO GOVERNMENT.

POUR NEW CONCRETE PAD EXTENSION ON

EXISTING CONCRETE PAD TO ACCOMMODATE

SIZE OF NEW GENERATOR. SEE LARGE SCALE

PLAN, THIS SHEET.

PLAN - GENERATOR CONCRETE PAD

SCALE: 1/4" = 1'-0"

EXISTING CONCRETE SLAB

EXISTING CONCRETE GENERATOR PAD

EXISTING CONCRETE BLOCK WALL

G

EXISTING

PANEL

"EM"

EUS

INTERCEPT EXISTING UNDERGROUND

SECONDARY - SEE NEW WORK.

EXISTING NORMAL FEEDER TO 600 A., 3 P.

BKR. IN EXISTING MAIN SWITCHBOARD "MDP."

EXISTING 600 A., 4 POLE AUTOMATIC

TRANSFER SWITCH.

REMOVE EXISTING 350 KW GENERATOR SET.

EXISTING NORMAL FEEDER TO 600 A., 3 P.

BKR. IN EXISTING MAIN SWITCHBOARD "MDP."

EXISTING 600 A., 4 POLE AUTOMATIC

TRANSFER SWITCH.

NEW 300 KW/375 KVA, 480Y/277 V., 3Ø

EMERGENCY GENERATOR SET.

FUEL TANK SIZING CALCULATION:

METERED LOAD ON EXISTING GENERATOR SET IS 75 KW.

NEW GENERATOR SET RATED AT 300 KW WILL BE LOADED AT 25%.

GENERATOR SET FUEL CONSUMPTION AT FULL LOAD IS 23.1 GPH.

72 HOUR FUEL CONSUMPTION AT FULL LOAD IS 1663 GALLONS.

GENERATOR SET FUEL CONSUMPTION AT 25% IS APPROXIMATELY 6.8 GPH.

72 HOUR FUEL CONSUMPTION AT 25% IS APPROXIMATELY 490 GALLONS.

NEW SUB-BASE FUEL TANK SHALL HAVE 500 GALLON CAPACITY.

500 GALLONS AT 25% FUEL CONSUMPTION WILL PROVIDE APPROXIMATELY 74 HOURS OF BACKUP POWER

GENERAL NOTES:GENERAL NOTES:

1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT

FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY

THE CONTRACTOR.

2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO

BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER

SWITCHES THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER

PRODUCTION SHOP. THE CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO

A LOCATION ON HURLBURT FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.

3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER

SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.

4. THE CONTRACTOR SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS AND

DISPOSE OF PROPERLY.

5. THE GOVERNMENT WILL FILL THE DIESEL FUEL TANKS WITH FUEL AFTER THE CONTRACTOR HAS INSTALLED

THE NEW GENERATOR SETS, AND PRIOR TO TESTING OF THE GENERATOR SETS.

BASIS OF DESIGN:

CUMMINS 300 KW DQDAC W/ 500 GALLON SUB-BASE DIESEL FUEL TANK & WEATHER PROTECTIVE ENCLOSURE.

PHYSICAL DIMENSIONS: 188" LONG X 82" WIDE X 108" HIGH.

WORK NOTES:

5 CONTROL WIRING & CONDUIT. SEE "CONTROL WIRING NOTE," THIS SHEET.

1 EMERGENCY POWER FEEDER TO TRANSFER SWITCH. SEE "EMERGENCY POWER FEEDER NOTE," THIS SHEET.

2 SCADA WIRING & CONDUIT. SEE "SCADA WIRING NOTE," THIS SHEET.

3 120 VOLT CIRCUIT. SEE "120 VOLT CIRCUIT NOTE," THIS SHEET.

4 REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING GENERATOR SET. MOUNT ON SIDE

OF GENERATOR BREAKER ENCLOSURE & CONNECT TO 120 VOLT CIRCUIT.

EMERGENCY POWER FEEDER NOTE:

INTERCEPT EXISTING CONDUITS BELOW CONCRETE SLAB & EXTEND NEW CONDUITS UP SIDE OF GENERATOR.

INSTALL WEATHERPROOF "LB" FITTINGS & EXTEND CONDUITS INTO GENERATOR SET THROUGH SKID. PULL IN

NEW WIRING FROM EXISTING AUTOMATIC TRANSFER SWITCH TO NEW GENERATOR SET VIA EXISTING PULL BOX.

NEW WIRING AND CONDUIT SHALL BE TWO (2) PARALLEL CIRCUITS OF 4 - 350 MCM & 1 # 1 GND. - 3" C., EACH.

120 VOLT CIRCUIT NOTE:

INTERCEPT EXISTING 120 VOLT CIRCUIT CONDUIT BELOW CONCRETE SLAB & EXTEND NEW CONDUIT UP TO 4"

SQUARE WEATHERPROOF JUNCTION BOX. EXTEND CONDUIT FROM JUNCTION BOX UP SIDE OF GENERATOR, INSTALL WEATHERPROOF "LB" FITTING & EXTEND CONDUIT INTO GENERATOR SET THROUGH SKID. PULL

EXISTING 120 VOLT WIRING BACK INTO JUNCTION BOX & SPLICE TO NEW WIRING. NEW WIRING AND CONDUIT

SHALL BE 2 # 12 & 1 # 12 GND. - 1/2" C.

SCADA WIRING NOTE:

INTERCEPT EXISTING SCADA CIRCUIT CONDUIT ABOVE CONCRETE SLAB & EXTEND NEW CONDUIT UP SIDE OF

GENERATOR. INSTALL WEATHERPROOF "LB" FITTING & EXTEND CONDUIT INTO GENERATOR SET THROUGH SKID.

PULL NEW SCADA WIRING FROM EXISTING SCADA ENCLOSURE TO NEW GENERATOR SET. NEW WIRING AND

CONDUIT SHALL BE (2) 4 PAIR, # 24 AWG SHIELDED TWISTED PAIR CAT. 6 CABLES IN 3/4" C.

CONTROL WIRING NOTE:

INTERCEPT EXISTING CONTROL WIRING CIRCUIT CONDUIT BELOW CONCRETE SLAB & EXTEND NEW CONDUIT UP

TO 4" SQUARE WEATHERPROOF JUNCTION BOX. EXTEND CONDUIT FROM JUNCTION BOX UP SIDE OF

GENERATOR, INSTALL WEATHERPROOF "LB" FITTING & EXTEND CONDUIT INTO GENERATOR SET THROUGH SKID.

PULL EXISTING 120 VOLT WIRING BACK INTO JUNCTION BOX & SPLICE TO NEW WIRING.

2'-0" 2'-0"

5'-3"

EXISTING CONCRETE GENERATOR PAD

OUTLINE OF NEW GENERATOR SET

OUTLINE OF NEW 16" THICK (MIN.)

3500 PSI CONCRETE PAD

INTERCEPT EXISTING CONTROL

WIRING & CONDUIT - SEE NEW WORK.

EUS

INTERCEPT EXISTING CONTROL WIRING

& CONDUIT BELOW GRADE & EXTEND TO

NEW GENERATOR SET. SEE "CONTROL

WIRING NOTE," THIS SHEET.

NEW GENERATOR ELEVATION

N.T.S.

PLAN VIEW - NEW SUB-BASE FUEL TANK

N.T.S.

FUEL TANK

OUTLINE OF GENERATOR

CIRCUIT BREAKER

90020

E-2

E L E

C T

R I C

A L

P

L A

B

U I L D

I N

G

3 FEB 2015

EXISTING 225 A., 3 POLE AUTOMATIC

TRANSFER SWITCH.

E

U

S

EXISTING SCADA EQUIPMENT

REMOVE EXISTING 15 KW GENERATOR SET.

EXISTING LIFT STATION CONTROL PANEL

ELECTRICAL PLAN - LIFT STATION 90027 - NEW WORK

SCALE: 1/4" = 1'-0"

ELECTRICAL PLAN - LIFT STATION 90027 - DEMOLITION

SCALE: 1/4" = 1'-0"

EXISTING 225 A., 3 POLE AUTOMATIC

TRANSFER SWITCH.

E

U

S

EXISTING SCADA EQUIPMENT

INSTALL NEW 15 KW GENERATOR SET.

EXISTING LIFT STATION CONTROL PANEL

EXISTING MAIN DISCONNECT SWITCHEXISTING MAIN DISCONNECT SWITCH

NO SCALE

SINGLE LINE DIAGRAM - DEMOLITION

G

REMOVE EXISTING 15 KW

EMERGENCY GENERATOR SET.

EXISTING 225 A., 3 P.

AUTOMATIC TRANSFER SWITCH

EUS

EXISTING UNDERGROUND SECONDARY

TO REMAIN.

EUS

EXISTING MAIN

DISCONNECT SWITCH

EXISTING LIFT STATION

CONTROL PANEL

EXISTING CONTROL WIRING & CONDUIT TO REMAIN.

NO SCALE

SINGLE LINE DIAGRAM - NEW WORK

G

EXISTING 225 A., 3 P.

AUTOMATIC TRANSFER SWITCH

EUS

EXISTING UNDERGROUND SECONDARY

TO REMAIN.

EUS

EXISTING MAIN

DISCONNECT SWITCH

EXISTING LIFT STATION

CONTROL PANEL

EXISTING CONTROL WIRING & CONDUIT TO REMAIN.

NEW 15 KW/18.75 KVA, 208Y/120 V., 3Ø

EMERGENCY GENERATOR SET.

WORK NOTES:

5 EXISTING CONTROL WIRING & CONDUIT. SEE "CONTROL WIRING NOTE," THIS SHEET.

1 EXISTING EMERGENCY POWER FEEDER TO TRANSFER SWITCH. SEE "EMERGENCY POWER FEEDER NOTE," THIS SHEET.

2 EXISTING SCADA WIRING & CONDUIT. SEE "SCADA WIRING NOTE," THIS SHEET.

3 EXISTING 120 VOLT CIRCUIT. SEE "120 VOLT CIRCUIT NOTE," THIS SHEET.

4 REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING GENERATOR SET. MOUNT ON SIDE

OF GENERATOR BREAKER ENCLOSURE & RECONNECT TO EXISTING 120 VOLT CIRCUIT.

BASIS OF DESIGN:

CUMMINS 15 KW C15 D6 W/ 91 GALLON SUB-BASE DIESEL FUEL TANK & WEATHER PROTECTIVE ENCLOSURE.

PHYSICAL DIMENSIONS: 65.7" LONG X 34" WIDE X 61" HIGH.

NEW GENERATOR ELEVATION

N.T.S.

PLAN VIEW - NEW SUB-BASE FUEL TANK

N.T.S.

FUEL TANK

CONDUIT ENTRY OPENING

OUTLINE OF GENERATOR

CIRCUIT BREAKER

LOCATE NEW GENERATOR SET SO THAT EXISTING

CONDUITS FALL WITHIN THE CONDUIT ENTRY OPENING

BELOW THE GENERATOR CIRCUIT BREAKER.

EMERGENCY POWER FEEDER NOTE:

RECONNECT EXISTING EMERGENCY POWER FEEDER TO NEW GENERATOR CIRCUIT BREAKER. IN THE EVENT

THAT THE EXISTING FEEDER IS NOT LONG ENOUGH TO REACH THE NEW CIRCUIT BREAKER, REMOVE THE

EXISTING FLEXIBLE CONDUIT CONNECTION BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE

EXISTING CONDUCTORS WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER

SPLICES, AND EXTEND THE NEW CONDUCTORS TO THE CIRCUIT BREAKER.

120 VOLT CIRCUIT NOTE:

RECONNECT EXISTING 120 VOLT POWER CIRCUIT TO THE DUPLEX RECEPTACLE. IN THE EVENT THAT THE

EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE RECEPTACLE, REMOVE THE EXISTING FLEXIBLE

CONDUIT CONNECTION BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE EXISTING

CONDUCTORS WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND

EXTEND THE NEW CONDUCTORS TO THE DUPLEX RECEPTACLE.

SCADA WIRING NOTE:

RECONNECT EXISTING SCADA WIRING TO NEW GENERATOR CONTROLLER.

GENERAL NOTES:

1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT

FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY

THE CONTRACTOR.

2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO

BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER SWITCHES

THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER PRODUCTION SHOP. THE

CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO A LOCATION ON HURLBURT

FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.

3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER

SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.

4. THE CONTRACTOR SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS AND DISPOSE

OF PROPERLY.

5. THE GOVERNMENT WILL FILL THE DIESEL FUEL TANKS WITH FUEL AFTER THE CONTRACTOR HAS INSTALLED

THE NEW GENERATOR SETS, AND PRIOR TO TESTING OF THE GENERATOR SETS.

CONTROL WIRING NOTE:

RECONNECT EXISTING CONTROL WIRING CONDUCTORS TO THE NEW GENERATOR CONTROLLER. IN THE EVENT

THAT THE EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE NEW CONTROLLER, REMOVE THE EXISTING

FLEXIBLE CONDUIT, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS WITH BUTT TYPE COMPRESSION

SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW CONDUCTORS TO THE

CONTROLLER.

FUEL TANK SIZING CALCULATION:

METERED LOAD ON EXISTING GENERATOR SET IS 10 KW.

NEW GENERATOR SET RATED AT 15 KW WILL BE LOADED AT 66%.

GENERATOR SET FUEL CONSUMPTION AT FULL LOAD IS 1.38 GPH.

72 HOUR FUEL CONSUMPTION AT FULL LOAD IS 99 GALLONS.

GENERATOR SET FUEL CONSUMPTION AT 75% IS 1.07 GPH.

72 HOUR FUEL CONSUMPTION AT 75% IS 76 GALLONS.

THE LARGEST FUEL TANK AVAILABLE FOR THE 15 KW GENERATOR SET W/ WEATHER PROTECTIVE

ENCLOSURE IS 91 GALLONS.

91 GALLONS AT 75% FUEL CONSUMPTION WILL PROVIDE APPROXIMATELY 85 HOURS OF BACKUP POWER.

90027

E-3

E L E

C T

R I C

A L

P

L A

I F

T

S

T A

T I O

N

3 FEB 2015

EXISTING 225 A., 4 POLE AUTOMATIC

TRANSFER SWITCH.

BUILDING 90043

EXISTING MAIN DISCONNECT SWITCH

EXISTING PANELBOARD

EXISTING SCADA EQUIPMENT

REMOVE EXISTING 35 KW GENERATOR SET.

EXISTING 225 A., 4 POLE AUTOMATIC

TRANSFER SWITCH.

BUILDING 90043

EXISTING MAIN DISCONNECT SWITCH

EXISTING PANELBOARD

EXISTING SCADA EQUIPMENT

INSTALL NEW 20 KW GENERATOR SET.

ELECTRICAL PLAN - BUILDING 90043 - DEMOLITION

SCALE: 1/4" = 1'-0"

ELECTRICAL PLAN - BUILDING 90043 - NEW WORK

SCALE: 1/4" = 1'-0"

INSTALL CONTROL WIRING - 1/2" PVC, SCH. 80

CONDUIT FROM EXISTING AUTOMATIC

TRANSFER SWITCH TO GENERATOR SET.

INSTALL NEW SCADA WIRING - 3/4" PVC, SCH. 80 CONDUIT

FROM SCADA ENCLOSURE TO NEW GENERATOR SET.

NO SCALE

SINGLE LINE DIAGRAM - DEMOLITION

G

REMOVE EXISTING 35 KW

EMERGENCY GENERATOR SET.

EXISTING 225 A., 4 P.

AUTOMATIC TRANSFER SWITCH

EUS

EXISTING UNDERGROUND SECONDARY

TO REMAIN.

EUS

EXISTING MAIN

DISCONNECT SWITCH

EXISTING PANELBOARD

REMOVE EXISTING CONTROL WIRING & CONDUIT.

NO SCALE

SINGLE LINE DIAGRAM - NEW WORK

G

EXISTING 225 A., 3 P.

AUTOMATIC TRANSFER SWITCH

EUS

EXISTING UNDERGROUND SECONDARY

TO REMAIN.

EUS

EXISTING MAIN

DISCONNECT SWITCH

NEW CONTROL WIRING & CONDUIT.

NEW 20 KW/25 KVA, 208Y/120 V., 3Ø

EMERGENCY GENERATOR SET.

EXISTING PANELBOARD

E

U

S

E

U

S

REMOVE EXISTING CONTROL WIRING &

CONDUIT FROM GENERATOR SET TO

AUTOMATIC TRANSFER SWITCH.

REMOVE EXISTING SCADA WIRING & CONDUIT FROM

GENERATOR SET TO SCADA EQUIPMENT ENCLOSURE.

FUEL TANK SIZING CALCULATION:

METERED LOAD ON EXISTING GENERATOR SET IS 12 KW.

NEW GENERATOR SET RATED AT 20 KW WILL BE LOADED AT 60%.

GENERATOR SET FUEL CONSUMPTION AT FULL LOAD IS 1.81 GPH.

72 HOUR FUEL CONSUMPTION AT FULL LOAD IS 130 GALLONS.

GENERATOR SET FUEL CONSUMPTION AT 50% IS 0.97 GPH.

72 HOUR FUEL CONSUMPTION AT 50% IS 70 GALLONS.

THE LARGEST FUEL TANK AVAILABLE FOR THE 20 KW GENERATOR SET W/ WEATHER PROTECTIVE

ENCLOSURE IS 91 GALLONS.

91 GALLONS AT 50% FUEL CONSUMPTION WILL PROVIDE APPROXIMATELY 88 HOURS OF BACKUP POWER.

BASIS OF DESIGN:

CUMMINS 20 KW C20 D6 W/ 91 GALLON SUB-BASE DIESEL FUEL TANK & WEATHER PROTECTIVE ENCLOSURE.

PHYSICAL DIMENSIONS: 65.7" LONG X 34" WIDE X 74" HIGH.

GENERAL NOTES:

1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT

FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY

THE CONTRACTOR.

2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO BE

DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER SWITCHES

THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER PRODUCTION SHOP. THE

CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO A LOCATION ON HURLBURT

FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.

3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER

SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.

4. THE CONTRACTOR SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS AND DISPOSE

OF PROPERLY.

5. THE GOVERNMENT WILL FILL THE DIESEL FUEL TANKS WITH FUEL AFTER THE CONTRACTOR HAS INSTALLED THE

NEW GENERATOR SETS, AND PRIOR TO TESTING OF THE GENERATOR SETS.

EMERGENCY POWER FEEDER NOTE:

RECONNECT EXISTING EMERGENCY POWER FEEDER TO NEW GENERATOR CIRCUIT BREAKER. IN THE EVENT THAT

THE EXISTING FEEDER IS NOT LONG ENOUGH TO REACH THE NEW CIRCUIT BREAKER, REMOVE THE EXISTING

FLEXIBLE CONDUITS BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS

WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE

NEW CONDUCTORS TO THE CIRCUIT BREAKER.

120 VOLT CIRCUIT NOTE:

RECONNECT EXISTING120 VOLT CIRCUIT TO THE DUPLEX RECEPTACLE. IN THE EVENT THAT THE EXISTING CIRCUIT

IS NOT LONG ENOUGH TO REACH THE RECEPTACLE, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS

WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE

NEW CONDUCTORS TO THE DUPLEX RECEPTACLE.

SCADA WIRING NOTE:

INSTALL NEW SCADA CONDUIT & WIRING FROM EXISTING SCADA ENCLOSURE TO NEW GENERATOR SET. EXTEND

SCADA WIRING IN 3/4" PVC, SCH. 40 CONDUIT BELOW GRADE & RIGID GALV. STEEL CONDUIT ABOVE GRADE. INSTALL

WEATHERPROOF "LB" FITTING FOR CONDUIT ENTRY INTO GENERATOR SUB-BASE FUEL TANK. EXISTING SCADA

CABLES MAY BE REUSED IF THEY ARE LONG ENOUGH TO REACH THE NEW GENERATOR SET.

CONTROL WIRING NOTE:

INSTALL NEW CONTROL WIRING & CONDUIT FROM THE EXISTING AUTOMATIC TRANSFER SWITCH TO NEW

GENERATOR SET. EXTEND CONTROL WIRING IN 1/2" PVC, SCH. 40 CONDUIT BELOW GRADE & RIGID GALV. STEEL

CONDUIT ABOVE GRADE. INSTALL WEATHERPROOF "LB" FITTING FOR CONDUIT ENTRY INTO GENERATOR SUB-BASE

FUEL TANK. QUANTITY AND SIZE OF CONTROL WIRING SHALL BE IN ACCORDANCE WITH THE GENERATOR

MANUFACTURER'S REQUIREMENTS.

PLAN VIEW - NEW SUB-BASE FUEL TANK

N.T.S.

NEW GENERATOR ELEVATION

N.T.S.

WORK NOTES:

1 EXISTING EMERGENCY POWER FEEDER TO TRANSFER SWITCH. SEE "EMERGENCY POWER FEEDER NOTE,"

THIS SHEET.

EXISTING 120 VOLT CIRCUIT. SEE "120 VOLT CIRCUIT NOTE," THIS SHEET.

REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING GENERATOR SET.

MOUNT ON SIDE OF GENERATOR BREAKER ENCLOSURE & RECONNECT TO EXISTING 120 VOLT CIRCUIT.

NEW SCADA WIRING & CONDUIT FROM GENERATOR SET TO EXISTING SCADA ENCLOSURE. SEE "SCADA

WIRING NOTE," THIS SHEET.

5 NEW CONTROL WIRING & CONDUIT. SEE "CONTROL WIRING NOTE," THIS SHEET.

FUEL TANK

CONDUIT ENTRY OPENING

OUTLINE OF GENERATOR

CIRCUIT BREAKER

2 5

90043

E-4

E L E

C T

R I C

A L

P

L A

U I L D

I N

G

3 FEB 2015

ELECTRICAL PLAN - BUILDING 90056 - DEMOLITION

SCALE: 1/4" = 1'-0"

ELECTRICAL PLAN - BUILDING 90056 - NEW WORK

SCALE: 1/4" = 1'-0"

EUS

E

U

S

REMOVE EXISTING 100 KW GENERATOR SET.

REMOVE EXISTING FUEL PIPING

REMOVE EXISTING 400 A., 3 POLE

AUTOMATIC TRANSFER SWITCH.

EXISTING MAIN DISCONNECT SWITCH EXISTING MAIN DISCONNECT SWITCH

REMOVE EXISTING LOADCENTER &

REINSTALL ON NEW TRANSFER SWITCH.

INSTALL NEW 80 KW GENERATOR SET.

INSTALL NEW 400 A., 4 P. AUTOMATIC TRANSFER SWITCH W/ BYPASS/ISOLATION.

NO SCALE

SINGLE LINE DIAGRAM - DEMOLITION

NEW 80 KW/100 KVA, 208Y/120 V., 3Ø

EMERGENCY GENERATOR SET.

G

REMOVE EXISTING 100 KW

EMERGENCY GENERATOR SET.

EXISTING

MAIN

PANEL

REMOVE EXISTING 400 A., 3 P.

AUTOMATIC TRANSFER SWITCH.

EUS EUS

EUS

EXISTING PAD MOUNTED

TRANSFORMER

EXISTING 400 A., 3 P. MAIN

DISCONNECT SWITCH.

EXISTING UNDERGROUND SECONDARY TO REMAIN.

REMOVE EXISTING CONTROL WIRING. REMOVE EXPOSED

CONDUIT & ABANDON CONDUIT WHERE BELOW GRADE.

NO SCALE

SINGLE LINE DIAGRAM - NEW WORK

G

EXISTING

MAIN

PANEL

EUS EUS

EXISTING PAD MOUNTED

TRANSFORMER

EXISTING 400 A., 3 P. MAIN

DISCONNECT SWITCH.

NEW 400 A., 4 P. AUTOMATIC TRANSFER

SWITCH W/ BYPASS/ISOLATION.

EXISTING SECONDARY TO

REMAIN.

EXISTING PAD MOUNTED TRANSFORMER

EUS

EXISTING PAD MOUNTED TRANSFORMER

REINSTALL EXISTING LOADCENTER

& EXTEND NEW 120 VOLT CIRCUIT

TO NEW GENERATOR SET.

BASIS OF DESIGN:

CUMMINS 80 KW DSFAE W/ 140 GALLON SUB-BASE DIESEL TANK & WEATHER PROTECTIVE ENCLOSURE.

PHYSICAL DIMENSIONS: 83" LONG X 40" WIDE X 73" HIGH.

GENERAL NOTES:

1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT

FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY

THE CONTRACTOR.

2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO

BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER SWITCHES

THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER PRODUCTION SHOP.

THE CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO A LOCATION ON

HURLBURT FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.

3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER

SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.

4. THE CONTRACTOR SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS AND

DISPOSE OF PROPERLY.

E

U

S

EXISTING UNDERGROUND SECONDARY TO REMAIN.

INSTALL NEW CONTROL WIRING IN 1" RIGID GALV.

STEEL CONDUIT EXPOSED ON CONCRETE SLAB.

EXISTING SECONDARY TO

REMAIN.

EXISTING UNDERGROUND SECONDARY TO REMAIN.EXISTING UNDERGROUND SECONDARY TO REMAIN.

E

U

S

WORK NOTES:

1 NEW EMERGENCY POWER FEEDER TO TRANSFER SWITCH. SEE "EMERGENCY POWER FEEDER NOTE," THIS

SHEET.

NEW 120 VOLT CIRCUIT. SEE "120 VOLT CIRCUIT NOTE," THIS SHEET.

REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING GENERATOR SET. MOUNT

ON SIDE OF GENERATOR BREAKER ENCLOSURE & CONNECT TO NEW 120 VOLT CIRCUIT.

NEW CONTROL WIRING & CONDUIT. SEE "CONTROL WIRING NOTE," THIS SHEET.

PLAN VIEW - NEW GENERATOR SET

N.T.S.

OUTLINE OF GENERATOR

CIRCUIT BREAKER

TERMINATE NEW CONDUITS WITHIN

THE CONDUIT ENTRY OPENING BELOW

THE GENERATOR CIRCUIT BREAKER.

NEW GENERATOR ELEVATION

N.T.S.

EMERGENCY POWER FEEDER NOTE:

INSTALL NEW EMERGENCY POWER FEEDER FROM NEW GENERATOR CIRCUIT BREAKER TO AUTOMATIC TRANSFER

SWITCH. NEW FEEDER SHALL BE INSTALLED EXPOSED ON THE EXISTING CONCRETE SLAB. SEE "SINGLE LINE DIAGRAM

- NEW WORK," THIS SHEET. REMOVE THE EXISTING FLEXIBLE CONDUIT CONNECTION AND CONDUIT EXPOSED ABOVE

THE CONCRETE SLAB. REMOVE EXISTING WIRING BACK TO EXISTING AUTOMATIC TRANSFER SWITCH.

120 VOLT CIRCUIT NOTE:

INSTALL NEW 120 VOLT CIRCUIT WIRING AND CONDUIT (2 # 12 & 1 # 12 GND. - 1/2" RIGID GALV. STEEL CONDUIT) FROM

THE EXISTING LOADCENTER TO THE NEW GENERATOR SET EXPOSED ON THE EXISTING CONCRETE SLAB. CONNECT

NEW 120 VOLT POWER CIRCUIT TO THE DUPLEX RECEPTACLE IN THE GENERATOR SET ENCLOSURE. REMOVE THE

EXISTING CONDUIT EXPOSED ABOVE THE CONCRETE SLAB & REMOVE EXISTING 120 VOLT WIRING BACK TO THE

EXISTING LOADCENTER.

CONTROL WIRING NOTE:

INSTALL NEW CONTROL WIRING AND CONDUIT FROM THE NEW AUTOMATIC TRANSFER SWITCH TO THE NEW

GENERATOR CONTROLLER. NEW CONDUIT SHALL BE INSTALLED EXPOSED ON THE EXISTING CONCRETE SLAB. SEE

"SINGLE LINE DIAGRAM - NEW WORK," THIS SHEET. REMOVE THE EXISTING CONTROL WIRING FROM THE GENERATOR

SET TO THE EXISTING AUTOMATIC TRANSFER SWITCH. REMOVE THE EXISTING CONDUIT EXPOSED ABOVE THE

CONCRETE SLAB.

FUEL TANK SIZING CALCULATION:

METERED LOAD ON EXISTING GENERATOR SET IS 50 KW.

NEW GENERATOR SET RATED AT 80 KW WILL BE LOADED AT 63%.

GENERATOR SET FUEL CONSUMPTION AT FULL LOAD IS 6.9 GPH.

48 HOUR FUEL CONSUMPTION AT FULL LOAD IS 331 GALLONS.

GENERATOR SET FUEL CONSUMPTION AT 75% IS 5.5 GPH.

48 HOUR FUEL CONSUMPTION AT 75% IS 264 GALLONS.

THE LARGEST FUEL TANK AVAILABLE FOR THE 80 KW GENERATOR SET W/ WEATHER PROTECTIVE

ENCLOSURE IS 140 GALLONS.

140 GALLONS AT 75% FUEL CONSUMPTION WILL PROVIDE APPROXIMATELY 25 HOURS OF BACKUP POWER.

REMOVE EXISTING SECONDARY WIRING. REMOVE EXPOSED

CONDUIT & ABANDON CONDUIT WHERE BELOW GRADE.

INSTALL NEW 4 - 500 MCM & 1 # 2 GND. - 3 1/2"" RIGID GALV.

STEEL CONDUIT EXPOSED ON CONCRETE SLAB.

RECONNECT EXISTING UNDERGROUND SECONDARY FEEDER TO NEW AUTOMATIC

TRANSFER SWITCH. IN THE EVENT THAT THE EXISTING FEEDER IS NOT LONG ENOUGH

TO REACH THE NEW LUGS, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS

WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER

SPLICES AND EXTEND THE NEW CONDUCTORS TO THE NEW TRANSFER SWITCH LUGS.

REMOVE EXISTING 340 GALLON FUEL STORAGE TANK &

TURN OVER TO GOVERNMENT. DELIVER TANK TO A

LOCATION ON HURLBURT FIELD AS DESIGNATED BY

THE POWER PRODUCTION SHOP.

5 INSTALL NEW 1 5/8" X 1 5/8" 12 GAUGE GALVANIZED STEEL CHANNELS ON CONRETE SLAB W/ MASONRY ANCHORS

& CONNECT NEW CONDUITS TO CHANNELS WITH CONDUIT STRAPS.

90056

E-5

E L E

C T

R I C

A L

P

L A

U I L D

I N

G

3 FEB 2015

ELECTRICAL PLAN - BUILDING 90215 - DEMOLITION

SCALE: 1/8" = 1'-0"

ELECTRICAL PLAN - BUILDING 90215 - NEW WORK

SCALE: 1/8" = 1'-0"

E

U

S

E

U

S

REMOVE EXISTING 250 KW GENERATOR SET.

EXISTING FUEL STORAGE TANK

EXISTING FUEL STORAGE TANK

EXISTING FUEL PIPING

EXISTING 800 A., 3 P. MAIN BREAKER

EXISTING PAD MOUNTED TRANSFORMER

EXISTING MAIN PANEL

EXISTING 800 A., 4 P. AUTOMATIC

TRANSFER SWITCH

EXISTING 800 A., 3 P. MAIN BREAKER

EXISTING PAD MOUNTED TRANSFORMER

EXISTING MAIN PANEL

EXISTING 800 A., 4 P. AUTOMATIC

TRANSFER SWITCH

INSTALL NEW 175 KW GENERATOR SET.

NO SCALE

SINGLE LINE DIAGRAM - DEMOLITION

EXISTING PAD MOUNTED

TRANSFORMER

G

EUS

EUS

EXISTING UNDERGROUND SECONDARY

TO REMAIN.

EXISTING 800 A., 4 P. AUTOMATIC

TRANSFER SWITCH.

REMOVE EXISTING 250 KW GENERATOR SET.

EXISTING 800 A., 3 P.

MAIN BREAKER

EXISTING

MAIN

PANEL

NO SCALE

SINGLE LINE DIAGRAM - NEW WORK

EXISTING PAD MOUNTED

TRANSFORMER

G

EUS

EUS

EXISTING UNDERGROUND SECONDARY

TO REMAIN.

EXISTING 800 A., 4 P. AUTOMATIC

TRANSFER SWITCH.

EXISTING 800 A., 3 P.

MAIN BREAKER

EXISTING

MAIN

PANEL

NEW 175 KW/218.75 KVA, 208Y/120 V., 3Ø

EMERGENCY GENERATOR SET.

BASIS OF DESIGN:

CUMMINS 175 KW DSGAD W/ WEATHER PROTECTIVE ENCLOSURE.

PHYSICAL DIMENSIONS: 105" LONG X 43" WIDE X 68" HIGH.

GENERAL NOTES:

1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT

FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY

THE CONTRACTOR.

2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO

BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER

SWITCHES THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER

PRODUCTION SHOP. THE CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO

A LOCATION ON HURLBURT FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.

3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER

SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.

4. THE CONTRACTOR SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS AND

DISPOSE OF PROPERLY.

WORK NOTES:

1 EXISTING EMERGENCY POWER FEEDER TO TRANSFER SWITCH. SEE "EMERGENCY POWER FEEDER NOTE,"

THIS SHEET.

EXISTING 120 VOLT CIRCUIT. SEE "120 VOLT CIRCUIT NOTE," THIS SHEET.

REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING GENERATOR SET.

MOUNT ON SIDE OF GENERATOR BREAKER ENCLOSURE & RECONNECT TO EXISTING 120 VOLT CIRCUIT.

EXISTING CONTROL WIRING & CONDUIT. SEE "CONTROL WIRING NOTE," THIS SHEET.

PLAN VIEW - NEW GENERATOR SET

OUTLINE OF GENERATOR

CIRCUIT BREAKER

LOCATE NEW GENERATOR SET SO THAT EXISTING

CONDUITS FALL WITHIN THE CONDUIT ENTRY OPENING

BELOW THE GENERATOR CIRCUIT BREAKER.

NEW GENERATOR ELEVATION

N.T.S.

EMERGENCY POWER FEEDER NOTE:

RECONNECT EXISTING EMERGENCY POWER FEEDER TO NEW GENERATOR CIRCUIT BREAKER. IN THE EVENT

THAT THE EXISTING FEEDER IS NOT LONG ENOUGH TO REACH THE NEW CIRCUIT BREAKER, REMOVE THE

EXISTING FLEXIBLE CONDUIT CONNECTION BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO

THE EXISTING CONDUCTORS WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION

OVER SPLICES, AND EXTEND THE NEW CONDUCTORS TO THE CIRCUIT BREAKER.

120 VOLT CIRCUIT NOTE:

RECONNECT EXISTING 120 VOLT POWER CIRCUIT TO THE DUPLEX RECEPTACLE. IN THE EVENT THAT THE

EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE RECEPTACLE, REMOVE THE EXISTING FLEXIBLE

CONDUIT CONNECTION BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE EXISTING

CONDUCTORS WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW CONDUCTORS TO THE DUPLEX RECEPTACLE.

CONTROL WIRING NOTE:

RECONNECT EXISTING CONTROL WIRING CONDUCTORS TO THE NEW GENERATOR CONTROLLER. IN THE

EVENT THAT THE EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE NEW CONTROLLER, REMOVE THE

EXISTING FLEXIBLE CONDUIT, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS WITH BUTT TYPE

COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW

CONDUCTORS TO THE CONTROLLER.

EXISTING FUEL PIPING - EXTEND TO NEW FUEL PIPING

CONNECTION POINTS IN NEW GENERATOR SET.

N.T.S.

90215

E-6

E L E

C T

R I C

A L

P

L A

U I L D

I N

G

3 FEB 2015

REMOVE EXISTING 150 KW GENERATOR SET.

ELECTRICAL PLAN - BUILDING 90355 - DEMOLITION

SCALE: 1/4" = 1'-0"

ELECTRICAL PLAN - BUILDING 90355 - NEW WORK

SCALE: 1/4" = 1'-0"

NO SCALE

SINGLE LINE DIAGRAM - DEMOLITION

G

REMOVE EXISTING 150 KW

EMERGENCY GENERATOR SET.

EXISTING 400 A., 4 P.

AUTOMATIC TRANSFER SWITCH

EUS

EXISTING UNDERGROUND SECONDARY

TO REMAIN.

EXISTING MAIN

DISCONNECT SWITCH

NO SCALE

SINGLE LINE DIAGRAM - NEW WORK

BUILDING 90355

J

EXISTING FUEL STORAGE TANK

EXISTING FUEL PIPING

EXISTING MAIN DISCONNECT SWITCH

EXISTING PAD MOUNTED TRANSFORMER

E

U

S

EXISTING 400 A., 4 P.

AUTOMATIC TRANSFER SWITCH

INSTALL NEW 150 KW GENERATOR SET.

BUILDING 90355

J

EXISTING FUEL STORAGE TANK

EXISTING MAIN DISCONNECT SWITCH

EXISTING PAD MOUNTED TRANSFORMER

E

U

S

EXISTING 400 A., 4 P.

AUTOMATIC TRANSFER SWITCH

EXISTING SECONDARY

TO BUILDING 90355

REMOVE EXISTING EXPOSED 4 # 4 & 1 # 4 GND. IN 2" PVC CONDUIT

EXISTING EXPOSED CONTROL WIRING & CONDUIT

G

EXISTING 400 A., 4 P.

AUTOMATIC TRANSFER SWITCH

EUS

EXISTING UNDERGROUND SECONDARY

TO REMAIN.

EXISTING MAIN

DISCONNECT SWITCH

EXISTING SECONDARY

TO BUILDING 90355

INSTALL 4 - 250 MCM & 1 # 4 GND. - 3" RIGID GALV. STEEL CONDUIT

EXISTING EXPOSED CONTROL WIRING & CONDUIT

NEW 150 KW/187.5 KVA, 480Y/277 V., 3Ø

EMERGENCY GENERATOR SET.

REMOVE EXISTING SECONDARY CONDUIT &

WIRING EXPOSED ON CONCRETE SLAB.

INSTALL NEW SECONDARY CONDUIT &

WIRING EXPOSED ON CONCRETE SLAB.

BASIS OF DESIGN:

CUMMINS 150 KW DSGAC W/ WEATHER PROTECTIVE ENCLOSURE.

PHYSICAL DIMENSIONS: 105" LONG X 43" WIDE X 68" HIGH.

GENERAL NOTES:

1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT

FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY

THE CONTRACTOR.

2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO

BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER SWITCHES

THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER PRODUCTION SHOP. THE

CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO A LOCATION ON HURLBURT

FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.

3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER

SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.

4. THE CONTRACTOR SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS AND DISPOSE

OF PROPERLY.

WORK NOTES:

1 INSTALL NEW EMERGENCY POWER FEEDER TO TRANSFER SWITCH. SEE "EMERGENCY POWER FEEDER

NOTE," THIS SHEET.

EXISTING 120 VOLT CIRCUIT. SEE "120 VOLT CIRCUIT NOTE," THIS SHEET.

REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING GENERATOR SET.

MOUNT ON SIDE OF GENERATOR BREAKER ENCLOSURE & RECONNECT TO EXISTING 120 VOLT CIRCUIT.

EXISTING CONTROL WIRING & CONDUIT. SEE "CONTROL WIRING NOTE," THIS SHEET.

PLAN VIEW - NEW GENERATOR SET

OUTLINE OF GENERATOR

CIRCUIT BREAKER

LOCATE NEW GENERATOR SET SO THAT EXISTING

CONDUITS FALL WITHIN THE CONDUIT ENTRY OPENING

BELOW THE GENERATOR CIRCUIT BREAKER.

NEW GENERATOR ELEVATION

N.T.S.

EMERGENCY POWER FEEDER NOTE:

INSTALL NEW EMERGENCY POWER FEEDER FROM EXISTING AUTOMATIC TRANSFER SWITCH TO NEW

GENERATOR SET. SEE "SINGLE LINE DIAGRAM - NEW WORK," THIS SHEET.

120 VOLT CIRCUIT NOTE:

RECONNECT EXISTING 120 VOLT POWER CIRCUIT TO THE DUPLEX RECEPTACLE. IN THE EVENT THAT THE

EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE RECEPTACLE, REMOVE THE EXISTING FLEXIBLE

CONDUIT CONNECTION BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE EXISTING

CONDUCTORS WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND

EXTEND THE NEW CONDUCTORS TO THE DUPLEX RECEPTACLE.

CONTROL WIRING NOTE:

RECONNECT EXISTING CONTROL WIRING CONDUCTORS TO THE NEW GENERATOR CONTROLLER. IN THE EVENT

THAT THE EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE NEW CONTROLLER, REMOVE THE EXISTING

FLEXIBLE CONDUIT, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS WITH BUTT TYPE COMPRESSION

SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW CONDUCTORS TO THE

CONTROLLER.

N.T.S.

EXISTING FUEL PIPING - EXTEND TO NEW FUEL PIPING

CONNECTION POINTS IN NEW GENERATOR SET.

90355

E-7

E L E

C T

R I C

A L

P

L A

U I L D

I N

G

3 FEB 2015

EXISTING MAIN DISCONNECT SWITCH

EXISTING 400 A., 4 P.

AUTOMATIC TRANSFER SWITCH

EXISTING PAD MOUNTED TRANSFORMER

ELECTRICAL PLAN - BUILDING 91350 - DEMOLITION

SCALE: 1/4" = 1'-0"

ELECTRICAL PLAN - BUILDING 91350 - NEW WORK

SCALE: 1/4" = 1'-0"

EXISTING MAIN DISCONNECT SWITCH

EXISTING 400 A., 4 P.

AUTOMATIC TRANSFER SWITCH

EXISTING PAD MOUNTED TRANSFORMER

NO SCALE

SINGLE LINE DIAGRAM - DEMOLITION

NEW 100 KW/125 KVA, 208Y/120 V., 3Ø

EMERGENCY GENERATOR SET.

G

EXISTING

MAIN

PANEL

EUS EUS

EUS

EXISTING 400 A., 3 P. MAIN

DISCONNECT SWITCH.

NO SCALE

SINGLE LINE DIAGRAM - NEW WORK

EXISTING EXPOSED

SECONDARY TO REMAIN.

EXISTING UNDERGROUND SECONDARY

TO REMAIN.

EXISTING UNDERGROUND SECONDARY

TO REMAIN.

EXISTING 400 A., 4 P.

AUTOMATIC TRANSFER SWITCH.

REMOVE EXISTING 60 KW

GENERATOR SET.

G

EXISTING

MAIN

PANEL

EUS EUS

EUS

EXISTING 400 A., 3 P. MAIN

DISCONNECT SWITCH.

EXISTING EXPOSED

SECONDARY TO REMAIN.

EXISTING UNDERGROUND SECONDARY

TO REMAIN.

EXISTING UNDERGROUND SECONDARY

TO REMAIN.

EXISTING 400 A., 4 P.

AUTOMATIC TRANSFER SWITCH.

REMOVE EXISTING 60 KW GENERATOR SET.

E

U

S

E

U

S

INSTALL NEW 100 KW GENERATOR SET.

BASIS OF DESIGN:

CUMMINS 100 KW DSGAA W/ 309 GALLON SUB-BASE DIESEL FUEL TANK & WEATHER PROTECTIVE ENCLOSURE.

PHYSICAL DIMENSIONS: 105" LONG X 44" WIDE X 88" HIGH.

GENERAL NOTES:

1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT

FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY

THE CONTRACTOR.

2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO

BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER SWITCHES

THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER PRODUCTION SHOP. THE

CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO A LOCATION ON HURLBURT

FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.

3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER

SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.

4. THE CONTRACTOR SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS AND DISPOSE

OF PROPERLY.

WORK NOTES:

1 EXISTING EMERGENCY POWER FEEDER TO TRANSFER SWITCH. SEE "EMERGENCY POWER FEEDER NOTE,"

THIS SHEET.

EXISTING 120 VOLT CIRCUIT. SEE "120 VOLT CIRCUIT NOTE," THIS SHEET.

REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING GENERATOR SET.

MOUNT ON SIDE OF GENERATOR BREAKER ENCLOSURE & RECONNECT TO EXISTING 120 VOLT CIRCUIT.

EXISTING CONTROL WIRING & CONDUIT. SEE "CONTROL WIRING NOTE," THIS SHEET.

EMERGENCY POWER FEEDER NOTE:

RECONNECT EXISTING EMERGENCY POWER FEEDER TO NEW GENERATOR CIRCUIT BREAKER. IN THE EVENT

THAT THE EXISTING FEEDER IS NOT LONG ENOUGH TO REACH THE NEW CIRCUIT BREAKER, REMOVE THE

EXISTING FLEXIBLE CONDUITS BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE EXISTING

CONDUCTORS WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND

EXTEND THE NEW CONDUCTORS TO THE CIRCUIT BREAKER.

120 VOLT CIRCUIT NOTE:

RECONNECT EXISTING 120 VOLT POWER CIRCUIT TO THE DUPLEX RECEPTACLE. IN THE EVENT THAT THE

EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE RECEPTACLE, REMOVE THE EXISTING FLEXIBLE

CONDUIT CONNECTION BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE EXISTING

CONDUCTORS WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND

EXTEND THE NEW CONDUCTORS TO THE DUPLEX RECEPTACLE.

CONTROL WIRING NOTE:

RECONNECT EXISTING CONTROL WIRING CONDUCTORS TO THE NEW GENERATOR CONTROLLER. IN THE EVENT

THAT THE EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE NEW CONTROLLER, REMOVE THE EXISTING

FLEXIBLE CONDUIT, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS WITH BUTT TYPE COMPRESSION

SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW CONDUCTORS TO THE

CONTROLLER.

FUEL TANK

CONDUIT ENTRY OPENING

OUTLINE OF GENERATOR

CIRCUIT BREAKER

LOCATE NEW GENERATOR SET SO THAT EXISTING

CONDUITS FALL WITHIN THE CONDUIT ENTRY OPENING

BELOW THE GENERATOR CIRCUIT BREAKER.

CONDUIT ENTRY OPENING

FUEL TANK SIZING CALCULATION:

METERED LOAD ON EXISTING GENERATOR SET IS 90 KW.

NEW GENERATOR SET RATED AT 100 KW WILL BE LOADED AT 90%.

GENERATOR SET FUEL CONSUMPTION AT FULL LOAD IS 8.87 GPH.

72 HOUR FUEL CONSUMPTION AT FULL LOAD IS 638 GALLONS.

THE LARGEST FUEL TANK AVAILABLE FOR THE 100 KW GENERATOR SET W/ WEATHER PROTECTIVE ENCLOSURE IS 309 GALLONS.

309 GALLONS AT 100% FUEL CONSUMPTION WILL PROVIDE APPROXIMATELY 34.8 HOURS OF BACKUP POWER.

PLAN VIEW - NEW SUB-BASE FUEL TANK

NEW GENERATOR ELEVATION

N.T.S.

EXISTING CURB

EXISTING CONCRETE BLOCK WALL

EXISTING CURB

EXISTING CONCRETE BLOCK WALL

91350

E-8

E L E

C T

R I C

A L

P

L A

U I L D

I N

G

3 FEB 2015