Attachment_2_Drawings.pdf
PDF 772 KB Posted
- Attached to
- Replace Generators - Phase C Federal contract opportunity
- Solicitation number
- FA4417-16-R-0013
About this file
Attachment 2 Drawings FA4417-16-R-0013 Replace Generators Multiple Buildings - Phase C
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FA4417-16-R-0013_Q A_with_responses_18_Apr_16.docx | DOCX document | |
| FA4417-16-R-0013_Site_Visit_Minutes.pdf | ||
| FA4417-16-R-0013_Site_Visit_Attendees.pdf | ||
| Attachment_4_Schedule_of_Wage_Rates.pdf | ||
| Attachment_1_Specifications.pdf | ||
| Solicitation_FA4417-16-R-0013.pdf | ||
| Attachment_6_Financial_Reference_Sheet.pdf | ||
| Attachment_3_SGFP_Listing.pdf | ||
| Attachment_5_Past_Present_Performance_Questionnaire.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
unk
L e t o u r n e a u
C i r c l e
L e t o u r n e a u
C i r c l e
F o x x
A v e n u e
Tully Street
S i m p s o n e n u e
Tully Street
R e d
H o r s e
R o a d
Tupelo Circle
Bakke Street
M a y
S t r e e t
Bakke Street
R e d
H r s
R a d
Grimm Lane
Hume Drive
Bland Street
Galvan Street
Hume Drive
Lewis Drive
Hodges Street
Walters Drive
H u m
D r i v e
A c h i v e
H a r r i s i v e
Hume Drive
McIntosh Court
US98
O N e i l
A v e n u e
In d e p e n d e n c e
R o a d
US98
C o d y
A v e n u e
Purcell Drive
C a m p a i g r e e t
Whitbeck Street
Gelshlager Street
Clark Road
Hume Drive
Schmauss Lane
W e a v e n u e
US98
M cM illa n S tre et
C o r l w a d
W a l k p
W y
I n d e p e n d e n c a d
Bedel Street
B e n n e t t
A v e n u e
Frazier Street
C r u z
A v e n u e
Red Horse Road
C r u z
A v e n u e
T u l l r e e t
T u l l y
S t r e e t
Bedel Street
W e s t f a
C r c l e
H a m b
P a c e
R r a d
Tully Street
L u ka sik A ve n u e
C o e n u e
K e r w o o d
R o a d
US98
Lielmanis Avenue
H o w l t e y
US98
M a i n t e n a n a
T u l r e e t
US98
H a r t s r e e t
M c
C l e r e e t
T e r e n u e
I n d e p e n d e n a d
M i t c h e l l
R o a d
Bartley Street
D o w n s
R o a d
90918
92470
90308
92006
92007
90600
92431
92081
90101
90761
91048
99045
91307
90325
90637
90106
92469
90359
91159
92427
92550
91400
90030
92085
91265
90053
92046
90225
99061
99029
99118
90815
91301
90880
92093
91148
91303
99042
92429
91364
90366
91056
99500
90304
91254
90051
90531
99030
91045
90636
90062
92449
92519
90115
90370
90064
92403
90713
90326
92028
92019
92021
91047
90525
90806
90138
92060
90352
91029
90371
90137
92472
90748
90822
90128
90618
90035
90619
90532
90369
92065
90935
92438
90033
90702
91255
91520
90521
92091
90510
99142
90302
90345
90232
92404
90382
92080
90617
92059
91137
92513
90003
92057
92042
92043
92037
92551
92017
92016
92107
91142
90300
90374
92546
92084
90048
99116
92099
99059
90621
92105
90339
91300
90008
92102
91163
90347
92098
90358
90825
99022
99145
99126
99044
90390
99056
99055
99083
99007
99105
91016
90552
99060
90131
99001
99998
90950
92090
92050
90334
91050
91363
91130
90337
92538
92061 92082
90049
90375
90229
90707
92052
92035
90615
92406
90105
90616
90928
99160
99999
99068
90635
91039
91009
90015
92432
92039
90121
91031
90801
90610
92275
92420
90759
92430
91151
91023
91140
92011
91037
90802
99043
91055
91252
92013
92000
90703
92528
92455
90005
90084
92024
92069
90328
90731
90372
92032
92030
90717
90145
91054
92436
91155
90346
90606
92452
92451
90378
92022
91012
90001
90223
90642
90054
90377
92040
92027
92026
91146
90230
90817
92055
92010
92072
92076
92071
92068
92058
90058
91053
90333
90320
90827
92004
92100
99115
90207
92522
92087
91104
91103
90580
91105
92437
90809
91330
92553
90701
92548
90327
92435
90626
92549
92001
92008
92051
90724
91122
92434
90511
92009
92461
90085
90609
99023
99716
99717
99718
99719
99127
99051
99999
99999
99999
99025
99024
92005
90315
90210
99067
92034
91032
92023
99058
92505
90522
90509
90747
92089
91154
90330
92426
92419
92463
92501
99535
99150
92516
92541
90607
99104
99090
99048
99020
99106
99107
90340
90075
90577
92048
90711
92094
91133
90523
91112
92424
90388
99057
91510
99041
90068
90069
90629
90392
92064
90037
90141
99004
90362
92537
90613
90134
92014
92529
90052
91162
90951
92464
92025
92446
92515
91161
90381
90387
99112
92103
99053
99038
91057
90729
99094
99146
92502
92450
92033
91034
91132
91030
91152
92556
90076
91145
90911
90102
92441
92471
90023
90357
90111
90070
92054
90601
92527
91099
92407
92015
92400
92425
92079
91109
90914
91156
90811
90743
91007
91360
91325
90081
90833
92038
92533
99137
92095
90368
91052
91164
90742
92083
92555
92514
90823
90627
90810
92047
90361
99010
90714
90763
90109
92503
90329
91106
91135
91310
92460
92428
91266
99117
91500
92044
90213
92012
92036
92539
90039
90073
90074
91035
90505
92466
91120
91601
90926
91025
91603
91365
99158
99054
92562
99999
99999
99019
90535
91351
99126
92062
91020
90036
90518
91370
92088
92063
92544
90402
90140
92521
99031
92473
91361
92518
92433
91027
91024
91515
92523
90318
92545
90373
90343
91147
92445
92530
90117
92092
90705
90517
92511
90331
92444
90079
91000
92401
91033
99098
90838
91538
91119
91114
90203
92045
90632
90720
92067
92097
92543
92506
92535
92524
92070
92056
92053
92041
92104
92106
92074
91268
92459
92508
91036
90624
92517
90625
91260
90553
90638
90066
90061
90057
91028
91021
92525
92440
99141
90816
92468
91144
90034
90755
90310
90220
92086
90551
90317
90050
90367
90323
92402
92467
90055
92018
91257
90029
92020
92002
92003
92073
90519
99065
92101
92463
90712
91013
92442
99902
92096
90135
91049
90829
92465
92408
90231
90603
91250
90322
92507
92066
90718
92049
90501
90640
90353
91041
92542
91153
92552
90002
92108
92276
92531
90700
92439
90113
92564
91302
90812
90708
91126
90010
92077
90060
91136
91042
90332
91258
91113
90630
90206
90421
90028
92075
92078
92031
92500
91259
91262
90067
90059
92485
92509
92536
90349
90065
90612
99049
90228
90319
90221
91625
92418
99005
91141
90336
99009
90502
90412
90038
92540
90202
92557
91537
90503
90021
99077
99154
90628
92547
90506
91101
90507
90380
90379
91149
91124
29075
29075
29075
29075
90396
90396
29073
29073
90534
90581
90734
91038
91043
29077
29077
W a l k p y
90512
90513
90513
90512
90360
90363
90351
92479
92478
92477
91264
91263
91261
91041
90813
90757
90749
90626
99121
90524
99103
90364
90356
90083
30041
D o w a d
90611
90500
90508
90311
90086
M
Y
T
R
E
E
T
91058
91059
99958
90917
90905
90306
91168
91107
91157
90534
90536
90800
Kissam Street
90727
30007
99326
LOCATION MAP
N.T.S.
LOCATION MAP & INDEX OF DRAWINGS
ELECTRICAL PLANS - LIFT STATION 90007
T-1
E-1
E-2
E-3
E-4
SHEET # TITLE
INDEX OF DRAWINGS
MAIN GATE
HAUL ROUTE
E-5
E-6
E-7
REPLACE GENERATOR 5 YEAR PLAN
MULTIPLE BUILDINGS
(BUILDINGS 90007, 90020, 90027, 90043, 90056, 90215, 90355 & 91350)
HURLBURT FIELD, FLORIDA
FTEV 13-1049C
ELECTRICAL PLANS - BUILDING 90020
ELECTRICAL PLANS - LIFT STATION 90027
ELECTRICAL PLANS - BUILDING 90043
ELECTRICAL PLANS - BUILDING 90056
ELECTRICAL PLANS - BUILDING 90215
POWER PRODUCTION SHOP
BUILDING 90043
BUILDING 90056
BUILDING 90215
BUILDING 90355
BUILDING 91350
BUILDING 90020
E-8
ELECTRICAL PLANS - BUILDING 90355
ELECTRICAL PLANS - BUILDING 91350
LIFT STATION 90007
LIFT STATION 90027
GENERAL NOTES:
1. ENSURE THAT NO WASTEWATER ASSOCIATED WITH THE POURING OF ANY CONCRETE IS
DISCHARGED TO SURFACE WATERS OF THE STATE (E.G.: WETLANDS, STORMWATER SYSTEMS, ETC.)
2. TO ENSURE THE REQUIREMENTS OF THE CLEAN AIR ACT AND AFI 32-7040 ARE MET, ALL GENERATOR
INFORMATION, INCLUDING ANY RUN-TIMES ASSOCIATED WITH THE INSTALLATION, MUST BE ENTERED
INTO THE AIR PROGRAM INFORMATION MANAGEMENT SYSTEM (APIMS). THIS INFORMATION AND DATA
MUST BE REPORTED TO MR. BARRY L. WOODS, 1 SOCES/CEIE, (850) 884-4652.
3. CONSTRUCTION AT EACH INDIVIDUAL BUILDING SHALL BE ACCOMPLISHED INDIVIDUALLY. THE
COMPLETE REMOVAL, CONSTRUCTION, REINSTALLATION, TESTING, AND GOVERNMENT ACCEPTANCE
OF EACH BUILDING SHALL BE COMPLETED BEFORE THE CONTRACTOR WILL BE ALLOWED TO START
CONSTRUCTION AT THE NEXT BUILDING.
4. POWER OUTAGES REQUIRED FOR CONSTRUCTION ACTIVITIES TO THE ELECTRICAL SERVICES TO
FACILITIES SHALL NOT EXCEED 12 HOURS AT A TIME.
5. THE CONTRACTOR SHALL PROVIDE FACTORY CERTIFIED GENERATOR START-UP PERSONNEL TO
PERFORM FACTORY START-UP IN ORDER TO BEGIN FACTORY WARRANTY.
6. WORK IS AUTHORIZED ON WEEKEND WITH PRIOR APPROVAL.
7. ENSURE CLEARANCES AROUND GENERATOR ARE AT LEAST 48” AT CONSTRUCTION COMPLETION.
8. FOR GENERATORS 250KW AND ABOVE THE CONTRACTOR SHALL PROVIDE 4” BOX BEAMS UNDER THE
GENERATOR TO PROVIDE CLEARANCE.
9. CONTROL WIRING IS CAT 5 CABLE.
MULTIPLE
T-1
3 FEB 2015
OF 9
FTEV 13-1049C
JRH/EWW
JRH
L O
C A
T I O
N
M
P
I N
D E
X
O
F
D
R A
W I N
G
EXISTING 104 A., 3 P. AUTOMATIC TRANSFER SWITCH
EXISTING MAIN DISCONNECT SWITCH
EXISTING LIFT STATION CONTROL PANEL
REMOVE EXISTING 20 KW GENERATOR SET.
E
U
S
J
EXISTING 104 A., 3 P. AUTOMATIC TRANSFER SWITCH
EXISTING MAIN DISCONNECT SWITCH
EXISTING LIFT STATION CONTROL PANEL
E
U
S
ELECTRICAL PLAN - LIFT STATION 90007 - NEW WORK
SCALE: 1/4" = 1'-0"
ELECTRICAL PLAN - LIFT STATION 90007 - DEMOLITION
SCALE: 1/4" = 1'-0"
INSTALL NEW 20 KW GENERATOR SET.
NO SCALE
SINGLE LINE DIAGRAM - DEMOLITION
G
REMOVE EXISTING 20 KW
EMERGENCY GENERATOR SET.
EXISTING 104 A., 3 P.
AUTOMATIC TRANSFER SWITCH
EUS
EXISTING UNDERGROUND SECONDARY
TO REMAIN.
EUS
EXISTING MAIN
DISCONNECT SWITCH
EXISTING LIFT STATION
CONTROL PANEL
EXISTING CONTROL WIRING & CONDUIT TO REMAIN.
NO SCALE
SINGLE LINE DIAGRAM - NEW WORK
G
EXISTING 104 A., 3 P.
AUTOMATIC TRANSFER SWITCH
EUS
EXISTING UNDERGROUND SECONDARY
TO REMAIN.
EUS
EXISTING MAIN
DISCONNECT SWITCH
EXISTING LIFT STATION
CONTROL PANEL
EXISTING CONTROL WIRING & CONDUIT TO REMAIN.
NEW 20 KW/25 KVA, 480Y/277 V., 3Ø
EMERGENCY GENERATOR SET.
INSTALL NEW SCADA WIRING IN 3/4" RIGID GALV. STEEL CONDUIT.
ATTACH CONDUIT TO EXISTING CONCRETE PAD.
INSTALL NEW 2 # 12 & 1 # 12 GND. - 1/2" RIGID GALV. STEEL CONDUIT.
ATTACH CONDUIT TO EXISTING CONCRETE PAD.
FUEL TANK SIZING CALCULATION:
METERED LOAD ON EXISTING GENERATOR SET IS 17 KW.
NEW GENERATOR SET RATED AT 20 KW WILL BE LOADED AT 85%.
GENERATOR SET FUEL CONSUMPTION AT FULL LOAD IS 1.81 GPH.
72 HOUR FUEL CONSUMPTION AT FULL LOAD IS 130 GALLONS.
GENERATOR SET FUEL CONSUMPTION AT 75% IS 1.38 GPH.
72 HOUR FUEL CONSUMPTION AT 75% IS 99 GALLONS.
THE LARGEST FUEL TANK AVAILABLE FOR THE 20 KW GENERATOR SET W/ WEATHER PROTECTIVE
ENCLOSURE IS 91 GALLONS.
91 GALLONS AT 100% FUEL CONSUMPTION WILL PROVIDE APPROXIMATELY 50 HOURS OF BACKUP POWER.
BASIS OF DESIGN:
CUMMINS 20 KW C20 D6 W/ 91 GALLON SUB-BASE DIESEL FUEL TANK & WEATHER PROTECTIVE ENCLOSURE.
PHYSICAL DIMENSIONS: 65.7" LONG X 34" WIDE X 74" HIGH.
GENERAL NOTES:
1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT
FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY
THE CONTRACTOR.
2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO BE
DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER SWITCHES
THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER PRODUCTION SHOP. THE
CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO A LOCATION ON HURLBURT
FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.
3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER
SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.
4. THE CONTRACTOR SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS AND DISPOSE
OF PROPERLY.
5. THE GOVERNMENT WILL FILL THE DIESEL FUEL TANKS WITH FUEL AFTER THE CONTRACTOR HAS INSTALLED THE
NEW GENERATOR SETS, AND PRIOR TO TESTING OF THE GENERATOR SETS.
EMERGENCY POWER FEEDER NOTE:
RECONNECT EXISTING EMERGENCY POWER FEEDER TO NEW GENERATOR CIRCUIT BREAKER. IN THE EVENT THAT
THE EXISTING FEEDER IS NOT LONG ENOUGH TO REACH THE NEW CIRCUIT BREAKER, REMOVE THE EXISTING
FLEXIBLE CONDUITS BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS
WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE
NEW CONDUCTORS TO THE CIRCUIT BREAKER.
120 VOLT CIRCUIT NOTE:
INSTALL NEW 120 VOLT CIRCUIT CONDUIT & WIRING FROM EXISTING CIRCUIT BREAKER IN PANELBOARD TO NEW
GENERATOR SET. EXTEND 2 # 12 & 1 # 12 GND. - 1/2" RIGID GALV. STEEL CONDUIT EXPOSED ACROSS CONCRETE
PAD. INSTALL WEATHERPROOF "LB" FITTING FOR CONDUIT ENTRY INTO GENERATOR SUB-BASE FUEL TANK.
SCADA WIRING NOTE:
INSTALL NEW SCADA CONDUIT & WIRING FROM EXISTING SCADA ENCLOSURE TO NEW GENERATOR SET. EXTEND
SCADA WIRING IN 3/4" RIGID GALV. STEEL CONDUIT EXPOSED ACROSS CONCRETE PAD. INSTALL WEATHERPROOF
"LB" FITTING FOR CONDUIT ENTRY INTO GENERATOR SUB-BASE FUEL TANK. EXISTING SCADA CABLES MAY BE
REUSED IF THEY ARE LONG ENOUGH TO REACH THE NEW GENERATOR SET.
CONTROL WIRING NOTE:
RECONNECT EXISTING CONTROL WIRING CONDUCTORS TO THE NEW GENERATOR CONTROLLER. EXISTING
CONTROL CIRCUIT IS RUN IN ELECTRICAL NON-METALLIC TUBING INSTALLED IN SAME CONDUIT W/ EMERGENCY
POWER FEEDER. IN THE EVENT THAT THE EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE NEW
CONTROLLER, REMOVE THE EXISTING ENT CONDUIT, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS
WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE
NEW CONDUCTORS TO THE CONTROLLER.
PLAN VIEW - NEW SUB-BASE FUEL TANK
N.T.S.
NEW GENERATOR ELEVATION
N.T.S.
WORK NOTES:
1 EXISTING EMERGENCY POWER FEEDER TO TRANSFER SWITCH. SEE "EMERGENCY POWER FEEDER NOTE,"
THIS SHEET.
NEW 120 VOLT CIRCUIT. SEE "120 VOLT CIRCUIT NOTE," THIS SHEET.
REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING GENERATOR SET.
MOUNT ON SIDE OF GENERATOR BREAKER ENCLOSURE & RECONNECT TO EXISTING 120 VOLT CIRCUIT.
NEW SCADA WIRING & CONDUIT FROM GENERATOR SET TO EXISTING SCADA ENCLOSURE. SEE "SCADA
WIRING NOTE," THIS SHEET.
5 EXISTING CONTROL WIRING & CONDUIT. SEE "CONTROL WIRING NOTE," THIS SHEET.
FUEL TANK
CONDUIT ENTRY OPENING
OUTLINE OF GENERATOR
CIRCUIT BREAKER
LOCATE NEW GENERATOR SET SO THAT EXISTING
CONDUITS FALL WITHIN THE CONDUIT ENTRY
OPENING BELOW THE GENERATOR CIRCUIT BREAKER.
EXISTING SCADA ENCLOSUREEXISTING SCADA ENCLOSURE
REMOVE EXISTING 120 VOLT CONDUIT & WIRING AND EXISTING SCADA
CONDUIT & WIRING. SEE NEW WORK PLAN, THIS SHEET.
90007
E-1
E L E
C T
R I C
A L
P
L A
I F
T
S
T A
T I O
N
3 FEB 2015
REMOVE EXISTING 350 KW GENERATOR SET.
ELECTRICAL PLAN - BUILDING 90020 - DEMOLITION
SCALE: 1/8" = 1'-0"
E
U
S
NO SCALE
SINGLE LINE DIAGRAM - DEMOLITION
NO SCALE
SINGLE LINE DIAGRAM - NEW WORK
G
EXISTING
PANEL
"EM"
INTERCEPT EXISTING SECONDARY FEEDER BELOW
GRADE & EXTEND TO NEW GENERATOR SET. SEE
"EMERGENCY POWER FEEDER NOTE," THIS SHEET.
EXISTING 600 A., 4 POLE AUTOMATIC
TRANSFER SWITCH
EXISTING PULL BOX
EXISTING PANEL "EM"
EXISTING SWITCHBOARD "MDP"
EXISTING SCADA EQUIPMENT
NEW 300 KW GENERATOR SET.
ELECTRICAL PLAN - BUILDING 90020 - NEW WORK
SCALE: 1/8" = 1'-0"
E
U
S
EXISTING 600 A., 4 POLE AUTOMATIC
TRANSFER SWITCH
EXISTING PULL BOX
EXISTING PANEL "EM"
EXISTING SWITCHBOARD "MDP"
EXISTING SCADA EQUIPMENT
EXISTING PAD MOUNTED TRANSFORMEREXISTING PAD MOUNTED TRANSFORMER
REMOVE EXISTING CATWALK & TURN OVER TO GOVERNMENT.
POUR NEW CONCRETE PAD EXTENSION ON
EXISTING CONCRETE PAD TO ACCOMMODATE
SIZE OF NEW GENERATOR. SEE LARGE SCALE
PLAN, THIS SHEET.
PLAN - GENERATOR CONCRETE PAD
SCALE: 1/4" = 1'-0"
EXISTING CONCRETE SLAB
EXISTING CONCRETE GENERATOR PAD
EXISTING CONCRETE BLOCK WALL
G
EXISTING
PANEL
"EM"
EUS
INTERCEPT EXISTING UNDERGROUND
SECONDARY - SEE NEW WORK.
EXISTING NORMAL FEEDER TO 600 A., 3 P.
BKR. IN EXISTING MAIN SWITCHBOARD "MDP."
EXISTING 600 A., 4 POLE AUTOMATIC
TRANSFER SWITCH.
REMOVE EXISTING 350 KW GENERATOR SET.
EXISTING NORMAL FEEDER TO 600 A., 3 P.
BKR. IN EXISTING MAIN SWITCHBOARD "MDP."
EXISTING 600 A., 4 POLE AUTOMATIC
TRANSFER SWITCH.
NEW 300 KW/375 KVA, 480Y/277 V., 3Ø
EMERGENCY GENERATOR SET.
FUEL TANK SIZING CALCULATION:
METERED LOAD ON EXISTING GENERATOR SET IS 75 KW.
NEW GENERATOR SET RATED AT 300 KW WILL BE LOADED AT 25%.
GENERATOR SET FUEL CONSUMPTION AT FULL LOAD IS 23.1 GPH.
72 HOUR FUEL CONSUMPTION AT FULL LOAD IS 1663 GALLONS.
GENERATOR SET FUEL CONSUMPTION AT 25% IS APPROXIMATELY 6.8 GPH.
72 HOUR FUEL CONSUMPTION AT 25% IS APPROXIMATELY 490 GALLONS.
NEW SUB-BASE FUEL TANK SHALL HAVE 500 GALLON CAPACITY.
500 GALLONS AT 25% FUEL CONSUMPTION WILL PROVIDE APPROXIMATELY 74 HOURS OF BACKUP POWER
GENERAL NOTES:GENERAL NOTES:
1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT
FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY
THE CONTRACTOR.
2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO
BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER
SWITCHES THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER
PRODUCTION SHOP. THE CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO
A LOCATION ON HURLBURT FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.
3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER
SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.
4. THE CONTRACTOR SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS AND
DISPOSE OF PROPERLY.
5. THE GOVERNMENT WILL FILL THE DIESEL FUEL TANKS WITH FUEL AFTER THE CONTRACTOR HAS INSTALLED
THE NEW GENERATOR SETS, AND PRIOR TO TESTING OF THE GENERATOR SETS.
BASIS OF DESIGN:
CUMMINS 300 KW DQDAC W/ 500 GALLON SUB-BASE DIESEL FUEL TANK & WEATHER PROTECTIVE ENCLOSURE.
PHYSICAL DIMENSIONS: 188" LONG X 82" WIDE X 108" HIGH.
WORK NOTES:
5 CONTROL WIRING & CONDUIT. SEE "CONTROL WIRING NOTE," THIS SHEET.
1 EMERGENCY POWER FEEDER TO TRANSFER SWITCH. SEE "EMERGENCY POWER FEEDER NOTE," THIS SHEET.
2 SCADA WIRING & CONDUIT. SEE "SCADA WIRING NOTE," THIS SHEET.
3 120 VOLT CIRCUIT. SEE "120 VOLT CIRCUIT NOTE," THIS SHEET.
4 REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING GENERATOR SET. MOUNT ON SIDE
OF GENERATOR BREAKER ENCLOSURE & CONNECT TO 120 VOLT CIRCUIT.
EMERGENCY POWER FEEDER NOTE:
INTERCEPT EXISTING CONDUITS BELOW CONCRETE SLAB & EXTEND NEW CONDUITS UP SIDE OF GENERATOR.
INSTALL WEATHERPROOF "LB" FITTINGS & EXTEND CONDUITS INTO GENERATOR SET THROUGH SKID. PULL IN
NEW WIRING FROM EXISTING AUTOMATIC TRANSFER SWITCH TO NEW GENERATOR SET VIA EXISTING PULL BOX.
NEW WIRING AND CONDUIT SHALL BE TWO (2) PARALLEL CIRCUITS OF 4 - 350 MCM & 1 # 1 GND. - 3" C., EACH.
120 VOLT CIRCUIT NOTE:
INTERCEPT EXISTING 120 VOLT CIRCUIT CONDUIT BELOW CONCRETE SLAB & EXTEND NEW CONDUIT UP TO 4"
SQUARE WEATHERPROOF JUNCTION BOX. EXTEND CONDUIT FROM JUNCTION BOX UP SIDE OF GENERATOR, INSTALL WEATHERPROOF "LB" FITTING & EXTEND CONDUIT INTO GENERATOR SET THROUGH SKID. PULL
EXISTING 120 VOLT WIRING BACK INTO JUNCTION BOX & SPLICE TO NEW WIRING. NEW WIRING AND CONDUIT
SHALL BE 2 # 12 & 1 # 12 GND. - 1/2" C.
SCADA WIRING NOTE:
INTERCEPT EXISTING SCADA CIRCUIT CONDUIT ABOVE CONCRETE SLAB & EXTEND NEW CONDUIT UP SIDE OF
GENERATOR. INSTALL WEATHERPROOF "LB" FITTING & EXTEND CONDUIT INTO GENERATOR SET THROUGH SKID.
PULL NEW SCADA WIRING FROM EXISTING SCADA ENCLOSURE TO NEW GENERATOR SET. NEW WIRING AND
CONDUIT SHALL BE (2) 4 PAIR, # 24 AWG SHIELDED TWISTED PAIR CAT. 6 CABLES IN 3/4" C.
CONTROL WIRING NOTE:
INTERCEPT EXISTING CONTROL WIRING CIRCUIT CONDUIT BELOW CONCRETE SLAB & EXTEND NEW CONDUIT UP
TO 4" SQUARE WEATHERPROOF JUNCTION BOX. EXTEND CONDUIT FROM JUNCTION BOX UP SIDE OF
GENERATOR, INSTALL WEATHERPROOF "LB" FITTING & EXTEND CONDUIT INTO GENERATOR SET THROUGH SKID.
PULL EXISTING 120 VOLT WIRING BACK INTO JUNCTION BOX & SPLICE TO NEW WIRING.
2'-0" 2'-0"
5'-3"
EXISTING CONCRETE GENERATOR PAD
OUTLINE OF NEW GENERATOR SET
OUTLINE OF NEW 16" THICK (MIN.)
3500 PSI CONCRETE PAD
INTERCEPT EXISTING CONTROL
WIRING & CONDUIT - SEE NEW WORK.
EUS
INTERCEPT EXISTING CONTROL WIRING
& CONDUIT BELOW GRADE & EXTEND TO
NEW GENERATOR SET. SEE "CONTROL
WIRING NOTE," THIS SHEET.
NEW GENERATOR ELEVATION
N.T.S.
PLAN VIEW - NEW SUB-BASE FUEL TANK
N.T.S.
FUEL TANK
OUTLINE OF GENERATOR
CIRCUIT BREAKER
90020
E-2
E L E
C T
R I C
A L
P
L A
B
U I L D
I N
G
3 FEB 2015
EXISTING 225 A., 3 POLE AUTOMATIC
TRANSFER SWITCH.
E
U
S
EXISTING SCADA EQUIPMENT
REMOVE EXISTING 15 KW GENERATOR SET.
EXISTING LIFT STATION CONTROL PANEL
ELECTRICAL PLAN - LIFT STATION 90027 - NEW WORK
SCALE: 1/4" = 1'-0"
ELECTRICAL PLAN - LIFT STATION 90027 - DEMOLITION
SCALE: 1/4" = 1'-0"
EXISTING 225 A., 3 POLE AUTOMATIC
TRANSFER SWITCH.
E
U
S
EXISTING SCADA EQUIPMENT
INSTALL NEW 15 KW GENERATOR SET.
EXISTING LIFT STATION CONTROL PANEL
EXISTING MAIN DISCONNECT SWITCHEXISTING MAIN DISCONNECT SWITCH
NO SCALE
SINGLE LINE DIAGRAM - DEMOLITION
G
REMOVE EXISTING 15 KW
EMERGENCY GENERATOR SET.
EXISTING 225 A., 3 P.
AUTOMATIC TRANSFER SWITCH
EUS
EXISTING UNDERGROUND SECONDARY
TO REMAIN.
EUS
EXISTING MAIN
DISCONNECT SWITCH
EXISTING LIFT STATION
CONTROL PANEL
EXISTING CONTROL WIRING & CONDUIT TO REMAIN.
NO SCALE
SINGLE LINE DIAGRAM - NEW WORK
G
EXISTING 225 A., 3 P.
AUTOMATIC TRANSFER SWITCH
EUS
EXISTING UNDERGROUND SECONDARY
TO REMAIN.
EUS
EXISTING MAIN
DISCONNECT SWITCH
EXISTING LIFT STATION
CONTROL PANEL
EXISTING CONTROL WIRING & CONDUIT TO REMAIN.
NEW 15 KW/18.75 KVA, 208Y/120 V., 3Ø
EMERGENCY GENERATOR SET.
WORK NOTES:
5 EXISTING CONTROL WIRING & CONDUIT. SEE "CONTROL WIRING NOTE," THIS SHEET.
1 EXISTING EMERGENCY POWER FEEDER TO TRANSFER SWITCH. SEE "EMERGENCY POWER FEEDER NOTE," THIS SHEET.
2 EXISTING SCADA WIRING & CONDUIT. SEE "SCADA WIRING NOTE," THIS SHEET.
3 EXISTING 120 VOLT CIRCUIT. SEE "120 VOLT CIRCUIT NOTE," THIS SHEET.
4 REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING GENERATOR SET. MOUNT ON SIDE
OF GENERATOR BREAKER ENCLOSURE & RECONNECT TO EXISTING 120 VOLT CIRCUIT.
BASIS OF DESIGN:
CUMMINS 15 KW C15 D6 W/ 91 GALLON SUB-BASE DIESEL FUEL TANK & WEATHER PROTECTIVE ENCLOSURE.
PHYSICAL DIMENSIONS: 65.7" LONG X 34" WIDE X 61" HIGH.
NEW GENERATOR ELEVATION
N.T.S.
PLAN VIEW - NEW SUB-BASE FUEL TANK
N.T.S.
FUEL TANK
CONDUIT ENTRY OPENING
OUTLINE OF GENERATOR
CIRCUIT BREAKER
LOCATE NEW GENERATOR SET SO THAT EXISTING
CONDUITS FALL WITHIN THE CONDUIT ENTRY OPENING
BELOW THE GENERATOR CIRCUIT BREAKER.
EMERGENCY POWER FEEDER NOTE:
RECONNECT EXISTING EMERGENCY POWER FEEDER TO NEW GENERATOR CIRCUIT BREAKER. IN THE EVENT
THAT THE EXISTING FEEDER IS NOT LONG ENOUGH TO REACH THE NEW CIRCUIT BREAKER, REMOVE THE
EXISTING FLEXIBLE CONDUIT CONNECTION BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE
EXISTING CONDUCTORS WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER
SPLICES, AND EXTEND THE NEW CONDUCTORS TO THE CIRCUIT BREAKER.
120 VOLT CIRCUIT NOTE:
RECONNECT EXISTING 120 VOLT POWER CIRCUIT TO THE DUPLEX RECEPTACLE. IN THE EVENT THAT THE
EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE RECEPTACLE, REMOVE THE EXISTING FLEXIBLE
CONDUIT CONNECTION BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE EXISTING
CONDUCTORS WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND
EXTEND THE NEW CONDUCTORS TO THE DUPLEX RECEPTACLE.
SCADA WIRING NOTE:
RECONNECT EXISTING SCADA WIRING TO NEW GENERATOR CONTROLLER.
GENERAL NOTES:
1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT
FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY
THE CONTRACTOR.
2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO
BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER SWITCHES
THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER PRODUCTION SHOP. THE
CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO A LOCATION ON HURLBURT
FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.
3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER
SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.
4. THE CONTRACTOR SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS AND DISPOSE
OF PROPERLY.
5. THE GOVERNMENT WILL FILL THE DIESEL FUEL TANKS WITH FUEL AFTER THE CONTRACTOR HAS INSTALLED
THE NEW GENERATOR SETS, AND PRIOR TO TESTING OF THE GENERATOR SETS.
CONTROL WIRING NOTE:
RECONNECT EXISTING CONTROL WIRING CONDUCTORS TO THE NEW GENERATOR CONTROLLER. IN THE EVENT
THAT THE EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE NEW CONTROLLER, REMOVE THE EXISTING
FLEXIBLE CONDUIT, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS WITH BUTT TYPE COMPRESSION
SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW CONDUCTORS TO THE
CONTROLLER.
FUEL TANK SIZING CALCULATION:
METERED LOAD ON EXISTING GENERATOR SET IS 10 KW.
NEW GENERATOR SET RATED AT 15 KW WILL BE LOADED AT 66%.
GENERATOR SET FUEL CONSUMPTION AT FULL LOAD IS 1.38 GPH.
72 HOUR FUEL CONSUMPTION AT FULL LOAD IS 99 GALLONS.
GENERATOR SET FUEL CONSUMPTION AT 75% IS 1.07 GPH.
72 HOUR FUEL CONSUMPTION AT 75% IS 76 GALLONS.
THE LARGEST FUEL TANK AVAILABLE FOR THE 15 KW GENERATOR SET W/ WEATHER PROTECTIVE
ENCLOSURE IS 91 GALLONS.
91 GALLONS AT 75% FUEL CONSUMPTION WILL PROVIDE APPROXIMATELY 85 HOURS OF BACKUP POWER.
90027
E-3
E L E
C T
R I C
A L
P
L A
I F
T
S
T A
T I O
N
3 FEB 2015
EXISTING 225 A., 4 POLE AUTOMATIC
TRANSFER SWITCH.
BUILDING 90043
EXISTING MAIN DISCONNECT SWITCH
EXISTING PANELBOARD
EXISTING SCADA EQUIPMENT
REMOVE EXISTING 35 KW GENERATOR SET.
EXISTING 225 A., 4 POLE AUTOMATIC
TRANSFER SWITCH.
BUILDING 90043
EXISTING MAIN DISCONNECT SWITCH
EXISTING PANELBOARD
EXISTING SCADA EQUIPMENT
INSTALL NEW 20 KW GENERATOR SET.
ELECTRICAL PLAN - BUILDING 90043 - DEMOLITION
SCALE: 1/4" = 1'-0"
ELECTRICAL PLAN - BUILDING 90043 - NEW WORK
SCALE: 1/4" = 1'-0"
INSTALL CONTROL WIRING - 1/2" PVC, SCH. 80
CONDUIT FROM EXISTING AUTOMATIC
TRANSFER SWITCH TO GENERATOR SET.
INSTALL NEW SCADA WIRING - 3/4" PVC, SCH. 80 CONDUIT
FROM SCADA ENCLOSURE TO NEW GENERATOR SET.
NO SCALE
SINGLE LINE DIAGRAM - DEMOLITION
G
REMOVE EXISTING 35 KW
EMERGENCY GENERATOR SET.
EXISTING 225 A., 4 P.
AUTOMATIC TRANSFER SWITCH
EUS
EXISTING UNDERGROUND SECONDARY
TO REMAIN.
EUS
EXISTING MAIN
DISCONNECT SWITCH
EXISTING PANELBOARD
REMOVE EXISTING CONTROL WIRING & CONDUIT.
NO SCALE
SINGLE LINE DIAGRAM - NEW WORK
G
EXISTING 225 A., 3 P.
AUTOMATIC TRANSFER SWITCH
EUS
EXISTING UNDERGROUND SECONDARY
TO REMAIN.
EUS
EXISTING MAIN
DISCONNECT SWITCH
NEW CONTROL WIRING & CONDUIT.
NEW 20 KW/25 KVA, 208Y/120 V., 3Ø
EMERGENCY GENERATOR SET.
EXISTING PANELBOARD
E
U
S
E
U
S
REMOVE EXISTING CONTROL WIRING &
CONDUIT FROM GENERATOR SET TO
AUTOMATIC TRANSFER SWITCH.
REMOVE EXISTING SCADA WIRING & CONDUIT FROM
GENERATOR SET TO SCADA EQUIPMENT ENCLOSURE.
FUEL TANK SIZING CALCULATION:
METERED LOAD ON EXISTING GENERATOR SET IS 12 KW.
NEW GENERATOR SET RATED AT 20 KW WILL BE LOADED AT 60%.
GENERATOR SET FUEL CONSUMPTION AT FULL LOAD IS 1.81 GPH.
72 HOUR FUEL CONSUMPTION AT FULL LOAD IS 130 GALLONS.
GENERATOR SET FUEL CONSUMPTION AT 50% IS 0.97 GPH.
72 HOUR FUEL CONSUMPTION AT 50% IS 70 GALLONS.
THE LARGEST FUEL TANK AVAILABLE FOR THE 20 KW GENERATOR SET W/ WEATHER PROTECTIVE
ENCLOSURE IS 91 GALLONS.
91 GALLONS AT 50% FUEL CONSUMPTION WILL PROVIDE APPROXIMATELY 88 HOURS OF BACKUP POWER.
BASIS OF DESIGN:
CUMMINS 20 KW C20 D6 W/ 91 GALLON SUB-BASE DIESEL FUEL TANK & WEATHER PROTECTIVE ENCLOSURE.
PHYSICAL DIMENSIONS: 65.7" LONG X 34" WIDE X 74" HIGH.
GENERAL NOTES:
1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT
FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY
THE CONTRACTOR.
2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO BE
DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER SWITCHES
THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER PRODUCTION SHOP. THE
CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO A LOCATION ON HURLBURT
FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.
3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER
SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.
4. THE CONTRACTOR SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS AND DISPOSE
OF PROPERLY.
5. THE GOVERNMENT WILL FILL THE DIESEL FUEL TANKS WITH FUEL AFTER THE CONTRACTOR HAS INSTALLED THE
NEW GENERATOR SETS, AND PRIOR TO TESTING OF THE GENERATOR SETS.
EMERGENCY POWER FEEDER NOTE:
RECONNECT EXISTING EMERGENCY POWER FEEDER TO NEW GENERATOR CIRCUIT BREAKER. IN THE EVENT THAT
THE EXISTING FEEDER IS NOT LONG ENOUGH TO REACH THE NEW CIRCUIT BREAKER, REMOVE THE EXISTING
FLEXIBLE CONDUITS BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS
WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE
NEW CONDUCTORS TO THE CIRCUIT BREAKER.
120 VOLT CIRCUIT NOTE:
RECONNECT EXISTING120 VOLT CIRCUIT TO THE DUPLEX RECEPTACLE. IN THE EVENT THAT THE EXISTING CIRCUIT
IS NOT LONG ENOUGH TO REACH THE RECEPTACLE, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS
WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE
NEW CONDUCTORS TO THE DUPLEX RECEPTACLE.
SCADA WIRING NOTE:
INSTALL NEW SCADA CONDUIT & WIRING FROM EXISTING SCADA ENCLOSURE TO NEW GENERATOR SET. EXTEND
SCADA WIRING IN 3/4" PVC, SCH. 40 CONDUIT BELOW GRADE & RIGID GALV. STEEL CONDUIT ABOVE GRADE. INSTALL
WEATHERPROOF "LB" FITTING FOR CONDUIT ENTRY INTO GENERATOR SUB-BASE FUEL TANK. EXISTING SCADA
CABLES MAY BE REUSED IF THEY ARE LONG ENOUGH TO REACH THE NEW GENERATOR SET.
CONTROL WIRING NOTE:
INSTALL NEW CONTROL WIRING & CONDUIT FROM THE EXISTING AUTOMATIC TRANSFER SWITCH TO NEW
GENERATOR SET. EXTEND CONTROL WIRING IN 1/2" PVC, SCH. 40 CONDUIT BELOW GRADE & RIGID GALV. STEEL
CONDUIT ABOVE GRADE. INSTALL WEATHERPROOF "LB" FITTING FOR CONDUIT ENTRY INTO GENERATOR SUB-BASE
FUEL TANK. QUANTITY AND SIZE OF CONTROL WIRING SHALL BE IN ACCORDANCE WITH THE GENERATOR
MANUFACTURER'S REQUIREMENTS.
PLAN VIEW - NEW SUB-BASE FUEL TANK
N.T.S.
NEW GENERATOR ELEVATION
N.T.S.
WORK NOTES:
1 EXISTING EMERGENCY POWER FEEDER TO TRANSFER SWITCH. SEE "EMERGENCY POWER FEEDER NOTE,"
THIS SHEET.
EXISTING 120 VOLT CIRCUIT. SEE "120 VOLT CIRCUIT NOTE," THIS SHEET.
REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING GENERATOR SET.
MOUNT ON SIDE OF GENERATOR BREAKER ENCLOSURE & RECONNECT TO EXISTING 120 VOLT CIRCUIT.
NEW SCADA WIRING & CONDUIT FROM GENERATOR SET TO EXISTING SCADA ENCLOSURE. SEE "SCADA
WIRING NOTE," THIS SHEET.
5 NEW CONTROL WIRING & CONDUIT. SEE "CONTROL WIRING NOTE," THIS SHEET.
FUEL TANK
CONDUIT ENTRY OPENING
OUTLINE OF GENERATOR
CIRCUIT BREAKER
2 5
90043
E-4
E L E
C T
R I C
A L
P
L A
U I L D
I N
G
3 FEB 2015
ELECTRICAL PLAN - BUILDING 90056 - DEMOLITION
SCALE: 1/4" = 1'-0"
ELECTRICAL PLAN - BUILDING 90056 - NEW WORK
SCALE: 1/4" = 1'-0"
EUS
E
U
S
REMOVE EXISTING 100 KW GENERATOR SET.
REMOVE EXISTING FUEL PIPING
REMOVE EXISTING 400 A., 3 POLE
AUTOMATIC TRANSFER SWITCH.
EXISTING MAIN DISCONNECT SWITCH EXISTING MAIN DISCONNECT SWITCH
REMOVE EXISTING LOADCENTER &
REINSTALL ON NEW TRANSFER SWITCH.
INSTALL NEW 80 KW GENERATOR SET.
INSTALL NEW 400 A., 4 P. AUTOMATIC TRANSFER SWITCH W/ BYPASS/ISOLATION.
NO SCALE
SINGLE LINE DIAGRAM - DEMOLITION
NEW 80 KW/100 KVA, 208Y/120 V., 3Ø
EMERGENCY GENERATOR SET.
G
REMOVE EXISTING 100 KW
EMERGENCY GENERATOR SET.
EXISTING
MAIN
PANEL
REMOVE EXISTING 400 A., 3 P.
AUTOMATIC TRANSFER SWITCH.
EUS EUS
EUS
EXISTING PAD MOUNTED
TRANSFORMER
EXISTING 400 A., 3 P. MAIN
DISCONNECT SWITCH.
EXISTING UNDERGROUND SECONDARY TO REMAIN.
REMOVE EXISTING CONTROL WIRING. REMOVE EXPOSED
CONDUIT & ABANDON CONDUIT WHERE BELOW GRADE.
NO SCALE
SINGLE LINE DIAGRAM - NEW WORK
G
EXISTING
MAIN
PANEL
EUS EUS
EXISTING PAD MOUNTED
TRANSFORMER
EXISTING 400 A., 3 P. MAIN
DISCONNECT SWITCH.
NEW 400 A., 4 P. AUTOMATIC TRANSFER
SWITCH W/ BYPASS/ISOLATION.
EXISTING SECONDARY TO
REMAIN.
EXISTING PAD MOUNTED TRANSFORMER
EUS
EXISTING PAD MOUNTED TRANSFORMER
REINSTALL EXISTING LOADCENTER
& EXTEND NEW 120 VOLT CIRCUIT
TO NEW GENERATOR SET.
BASIS OF DESIGN:
CUMMINS 80 KW DSFAE W/ 140 GALLON SUB-BASE DIESEL TANK & WEATHER PROTECTIVE ENCLOSURE.
PHYSICAL DIMENSIONS: 83" LONG X 40" WIDE X 73" HIGH.
GENERAL NOTES:
1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT
FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY
THE CONTRACTOR.
2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO
BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER SWITCHES
THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER PRODUCTION SHOP.
THE CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO A LOCATION ON
HURLBURT FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.
3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER
SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.
4. THE CONTRACTOR SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS AND
DISPOSE OF PROPERLY.
E
U
S
EXISTING UNDERGROUND SECONDARY TO REMAIN.
INSTALL NEW CONTROL WIRING IN 1" RIGID GALV.
STEEL CONDUIT EXPOSED ON CONCRETE SLAB.
EXISTING SECONDARY TO
REMAIN.
EXISTING UNDERGROUND SECONDARY TO REMAIN.EXISTING UNDERGROUND SECONDARY TO REMAIN.
E
U
S
WORK NOTES:
1 NEW EMERGENCY POWER FEEDER TO TRANSFER SWITCH. SEE "EMERGENCY POWER FEEDER NOTE," THIS
SHEET.
NEW 120 VOLT CIRCUIT. SEE "120 VOLT CIRCUIT NOTE," THIS SHEET.
REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING GENERATOR SET. MOUNT
ON SIDE OF GENERATOR BREAKER ENCLOSURE & CONNECT TO NEW 120 VOLT CIRCUIT.
NEW CONTROL WIRING & CONDUIT. SEE "CONTROL WIRING NOTE," THIS SHEET.
PLAN VIEW - NEW GENERATOR SET
N.T.S.
OUTLINE OF GENERATOR
CIRCUIT BREAKER
TERMINATE NEW CONDUITS WITHIN
THE CONDUIT ENTRY OPENING BELOW
THE GENERATOR CIRCUIT BREAKER.
NEW GENERATOR ELEVATION
N.T.S.
EMERGENCY POWER FEEDER NOTE:
INSTALL NEW EMERGENCY POWER FEEDER FROM NEW GENERATOR CIRCUIT BREAKER TO AUTOMATIC TRANSFER
SWITCH. NEW FEEDER SHALL BE INSTALLED EXPOSED ON THE EXISTING CONCRETE SLAB. SEE "SINGLE LINE DIAGRAM
- NEW WORK," THIS SHEET. REMOVE THE EXISTING FLEXIBLE CONDUIT CONNECTION AND CONDUIT EXPOSED ABOVE
THE CONCRETE SLAB. REMOVE EXISTING WIRING BACK TO EXISTING AUTOMATIC TRANSFER SWITCH.
120 VOLT CIRCUIT NOTE:
INSTALL NEW 120 VOLT CIRCUIT WIRING AND CONDUIT (2 # 12 & 1 # 12 GND. - 1/2" RIGID GALV. STEEL CONDUIT) FROM
THE EXISTING LOADCENTER TO THE NEW GENERATOR SET EXPOSED ON THE EXISTING CONCRETE SLAB. CONNECT
NEW 120 VOLT POWER CIRCUIT TO THE DUPLEX RECEPTACLE IN THE GENERATOR SET ENCLOSURE. REMOVE THE
EXISTING CONDUIT EXPOSED ABOVE THE CONCRETE SLAB & REMOVE EXISTING 120 VOLT WIRING BACK TO THE
EXISTING LOADCENTER.
CONTROL WIRING NOTE:
INSTALL NEW CONTROL WIRING AND CONDUIT FROM THE NEW AUTOMATIC TRANSFER SWITCH TO THE NEW
GENERATOR CONTROLLER. NEW CONDUIT SHALL BE INSTALLED EXPOSED ON THE EXISTING CONCRETE SLAB. SEE
"SINGLE LINE DIAGRAM - NEW WORK," THIS SHEET. REMOVE THE EXISTING CONTROL WIRING FROM THE GENERATOR
SET TO THE EXISTING AUTOMATIC TRANSFER SWITCH. REMOVE THE EXISTING CONDUIT EXPOSED ABOVE THE
CONCRETE SLAB.
FUEL TANK SIZING CALCULATION:
METERED LOAD ON EXISTING GENERATOR SET IS 50 KW.
NEW GENERATOR SET RATED AT 80 KW WILL BE LOADED AT 63%.
GENERATOR SET FUEL CONSUMPTION AT FULL LOAD IS 6.9 GPH.
48 HOUR FUEL CONSUMPTION AT FULL LOAD IS 331 GALLONS.
GENERATOR SET FUEL CONSUMPTION AT 75% IS 5.5 GPH.
48 HOUR FUEL CONSUMPTION AT 75% IS 264 GALLONS.
THE LARGEST FUEL TANK AVAILABLE FOR THE 80 KW GENERATOR SET W/ WEATHER PROTECTIVE
ENCLOSURE IS 140 GALLONS.
140 GALLONS AT 75% FUEL CONSUMPTION WILL PROVIDE APPROXIMATELY 25 HOURS OF BACKUP POWER.
REMOVE EXISTING SECONDARY WIRING. REMOVE EXPOSED
CONDUIT & ABANDON CONDUIT WHERE BELOW GRADE.
INSTALL NEW 4 - 500 MCM & 1 # 2 GND. - 3 1/2"" RIGID GALV.
STEEL CONDUIT EXPOSED ON CONCRETE SLAB.
RECONNECT EXISTING UNDERGROUND SECONDARY FEEDER TO NEW AUTOMATIC
TRANSFER SWITCH. IN THE EVENT THAT THE EXISTING FEEDER IS NOT LONG ENOUGH
TO REACH THE NEW LUGS, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS
WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER
SPLICES AND EXTEND THE NEW CONDUCTORS TO THE NEW TRANSFER SWITCH LUGS.
REMOVE EXISTING 340 GALLON FUEL STORAGE TANK &
TURN OVER TO GOVERNMENT. DELIVER TANK TO A
LOCATION ON HURLBURT FIELD AS DESIGNATED BY
THE POWER PRODUCTION SHOP.
5 INSTALL NEW 1 5/8" X 1 5/8" 12 GAUGE GALVANIZED STEEL CHANNELS ON CONRETE SLAB W/ MASONRY ANCHORS
& CONNECT NEW CONDUITS TO CHANNELS WITH CONDUIT STRAPS.
90056
E-5
E L E
C T
R I C
A L
P
L A
U I L D
I N
G
3 FEB 2015
ELECTRICAL PLAN - BUILDING 90215 - DEMOLITION
SCALE: 1/8" = 1'-0"
ELECTRICAL PLAN - BUILDING 90215 - NEW WORK
SCALE: 1/8" = 1'-0"
E
U
S
E
U
S
REMOVE EXISTING 250 KW GENERATOR SET.
EXISTING FUEL STORAGE TANK
EXISTING FUEL STORAGE TANK
EXISTING FUEL PIPING
EXISTING 800 A., 3 P. MAIN BREAKER
EXISTING PAD MOUNTED TRANSFORMER
EXISTING MAIN PANEL
EXISTING 800 A., 4 P. AUTOMATIC
TRANSFER SWITCH
EXISTING 800 A., 3 P. MAIN BREAKER
EXISTING PAD MOUNTED TRANSFORMER
EXISTING MAIN PANEL
EXISTING 800 A., 4 P. AUTOMATIC
TRANSFER SWITCH
INSTALL NEW 175 KW GENERATOR SET.
NO SCALE
SINGLE LINE DIAGRAM - DEMOLITION
EXISTING PAD MOUNTED
TRANSFORMER
G
EUS
EUS
EXISTING UNDERGROUND SECONDARY
TO REMAIN.
EXISTING 800 A., 4 P. AUTOMATIC
TRANSFER SWITCH.
REMOVE EXISTING 250 KW GENERATOR SET.
EXISTING 800 A., 3 P.
MAIN BREAKER
EXISTING
MAIN
PANEL
NO SCALE
SINGLE LINE DIAGRAM - NEW WORK
EXISTING PAD MOUNTED
TRANSFORMER
G
EUS
EUS
EXISTING UNDERGROUND SECONDARY
TO REMAIN.
EXISTING 800 A., 4 P. AUTOMATIC
TRANSFER SWITCH.
EXISTING 800 A., 3 P.
MAIN BREAKER
EXISTING
MAIN
PANEL
NEW 175 KW/218.75 KVA, 208Y/120 V., 3Ø
EMERGENCY GENERATOR SET.
BASIS OF DESIGN:
CUMMINS 175 KW DSGAD W/ WEATHER PROTECTIVE ENCLOSURE.
PHYSICAL DIMENSIONS: 105" LONG X 43" WIDE X 68" HIGH.
GENERAL NOTES:
1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT
FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY
THE CONTRACTOR.
2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO
BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER
SWITCHES THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER
PRODUCTION SHOP. THE CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO
A LOCATION ON HURLBURT FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.
3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER
SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.
4. THE CONTRACTOR SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS AND
DISPOSE OF PROPERLY.
WORK NOTES:
1 EXISTING EMERGENCY POWER FEEDER TO TRANSFER SWITCH. SEE "EMERGENCY POWER FEEDER NOTE,"
THIS SHEET.
EXISTING 120 VOLT CIRCUIT. SEE "120 VOLT CIRCUIT NOTE," THIS SHEET.
REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING GENERATOR SET.
MOUNT ON SIDE OF GENERATOR BREAKER ENCLOSURE & RECONNECT TO EXISTING 120 VOLT CIRCUIT.
EXISTING CONTROL WIRING & CONDUIT. SEE "CONTROL WIRING NOTE," THIS SHEET.
PLAN VIEW - NEW GENERATOR SET
OUTLINE OF GENERATOR
CIRCUIT BREAKER
LOCATE NEW GENERATOR SET SO THAT EXISTING
CONDUITS FALL WITHIN THE CONDUIT ENTRY OPENING
BELOW THE GENERATOR CIRCUIT BREAKER.
NEW GENERATOR ELEVATION
N.T.S.
EMERGENCY POWER FEEDER NOTE:
RECONNECT EXISTING EMERGENCY POWER FEEDER TO NEW GENERATOR CIRCUIT BREAKER. IN THE EVENT
THAT THE EXISTING FEEDER IS NOT LONG ENOUGH TO REACH THE NEW CIRCUIT BREAKER, REMOVE THE
EXISTING FLEXIBLE CONDUIT CONNECTION BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO
THE EXISTING CONDUCTORS WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION
OVER SPLICES, AND EXTEND THE NEW CONDUCTORS TO THE CIRCUIT BREAKER.
120 VOLT CIRCUIT NOTE:
RECONNECT EXISTING 120 VOLT POWER CIRCUIT TO THE DUPLEX RECEPTACLE. IN THE EVENT THAT THE
EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE RECEPTACLE, REMOVE THE EXISTING FLEXIBLE
CONDUIT CONNECTION BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE EXISTING
CONDUCTORS WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW CONDUCTORS TO THE DUPLEX RECEPTACLE.
CONTROL WIRING NOTE:
RECONNECT EXISTING CONTROL WIRING CONDUCTORS TO THE NEW GENERATOR CONTROLLER. IN THE
EVENT THAT THE EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE NEW CONTROLLER, REMOVE THE
EXISTING FLEXIBLE CONDUIT, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS WITH BUTT TYPE
COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW
CONDUCTORS TO THE CONTROLLER.
EXISTING FUEL PIPING - EXTEND TO NEW FUEL PIPING
CONNECTION POINTS IN NEW GENERATOR SET.
N.T.S.
90215
E-6
E L E
C T
R I C
A L
P
L A
U I L D
I N
G
3 FEB 2015
REMOVE EXISTING 150 KW GENERATOR SET.
ELECTRICAL PLAN - BUILDING 90355 - DEMOLITION
SCALE: 1/4" = 1'-0"
ELECTRICAL PLAN - BUILDING 90355 - NEW WORK
SCALE: 1/4" = 1'-0"
NO SCALE
SINGLE LINE DIAGRAM - DEMOLITION
G
REMOVE EXISTING 150 KW
EMERGENCY GENERATOR SET.
EXISTING 400 A., 4 P.
AUTOMATIC TRANSFER SWITCH
EUS
EXISTING UNDERGROUND SECONDARY
TO REMAIN.
EXISTING MAIN
DISCONNECT SWITCH
NO SCALE
SINGLE LINE DIAGRAM - NEW WORK
BUILDING 90355
J
EXISTING FUEL STORAGE TANK
EXISTING FUEL PIPING
EXISTING MAIN DISCONNECT SWITCH
EXISTING PAD MOUNTED TRANSFORMER
E
U
S
EXISTING 400 A., 4 P.
AUTOMATIC TRANSFER SWITCH
INSTALL NEW 150 KW GENERATOR SET.
BUILDING 90355
J
EXISTING FUEL STORAGE TANK
EXISTING MAIN DISCONNECT SWITCH
EXISTING PAD MOUNTED TRANSFORMER
E
U
S
EXISTING 400 A., 4 P.
AUTOMATIC TRANSFER SWITCH
EXISTING SECONDARY
TO BUILDING 90355
REMOVE EXISTING EXPOSED 4 # 4 & 1 # 4 GND. IN 2" PVC CONDUIT
EXISTING EXPOSED CONTROL WIRING & CONDUIT
G
EXISTING 400 A., 4 P.
AUTOMATIC TRANSFER SWITCH
EUS
EXISTING UNDERGROUND SECONDARY
TO REMAIN.
EXISTING MAIN
DISCONNECT SWITCH
EXISTING SECONDARY
TO BUILDING 90355
INSTALL 4 - 250 MCM & 1 # 4 GND. - 3" RIGID GALV. STEEL CONDUIT
EXISTING EXPOSED CONTROL WIRING & CONDUIT
NEW 150 KW/187.5 KVA, 480Y/277 V., 3Ø
EMERGENCY GENERATOR SET.
REMOVE EXISTING SECONDARY CONDUIT &
WIRING EXPOSED ON CONCRETE SLAB.
INSTALL NEW SECONDARY CONDUIT &
WIRING EXPOSED ON CONCRETE SLAB.
BASIS OF DESIGN:
CUMMINS 150 KW DSGAC W/ WEATHER PROTECTIVE ENCLOSURE.
PHYSICAL DIMENSIONS: 105" LONG X 43" WIDE X 68" HIGH.
GENERAL NOTES:
1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT
FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY
THE CONTRACTOR.
2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO
BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER SWITCHES
THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER PRODUCTION SHOP. THE
CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO A LOCATION ON HURLBURT
FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.
3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER
SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.
4. THE CONTRACTOR SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS AND DISPOSE
OF PROPERLY.
WORK NOTES:
1 INSTALL NEW EMERGENCY POWER FEEDER TO TRANSFER SWITCH. SEE "EMERGENCY POWER FEEDER
NOTE," THIS SHEET.
EXISTING 120 VOLT CIRCUIT. SEE "120 VOLT CIRCUIT NOTE," THIS SHEET.
REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING GENERATOR SET.
MOUNT ON SIDE OF GENERATOR BREAKER ENCLOSURE & RECONNECT TO EXISTING 120 VOLT CIRCUIT.
EXISTING CONTROL WIRING & CONDUIT. SEE "CONTROL WIRING NOTE," THIS SHEET.
PLAN VIEW - NEW GENERATOR SET
OUTLINE OF GENERATOR
CIRCUIT BREAKER
LOCATE NEW GENERATOR SET SO THAT EXISTING
CONDUITS FALL WITHIN THE CONDUIT ENTRY OPENING
BELOW THE GENERATOR CIRCUIT BREAKER.
NEW GENERATOR ELEVATION
N.T.S.
EMERGENCY POWER FEEDER NOTE:
INSTALL NEW EMERGENCY POWER FEEDER FROM EXISTING AUTOMATIC TRANSFER SWITCH TO NEW
GENERATOR SET. SEE "SINGLE LINE DIAGRAM - NEW WORK," THIS SHEET.
120 VOLT CIRCUIT NOTE:
RECONNECT EXISTING 120 VOLT POWER CIRCUIT TO THE DUPLEX RECEPTACLE. IN THE EVENT THAT THE
EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE RECEPTACLE, REMOVE THE EXISTING FLEXIBLE
CONDUIT CONNECTION BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE EXISTING
CONDUCTORS WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND
EXTEND THE NEW CONDUCTORS TO THE DUPLEX RECEPTACLE.
CONTROL WIRING NOTE:
RECONNECT EXISTING CONTROL WIRING CONDUCTORS TO THE NEW GENERATOR CONTROLLER. IN THE EVENT
THAT THE EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE NEW CONTROLLER, REMOVE THE EXISTING
FLEXIBLE CONDUIT, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS WITH BUTT TYPE COMPRESSION
SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW CONDUCTORS TO THE
CONTROLLER.
N.T.S.
EXISTING FUEL PIPING - EXTEND TO NEW FUEL PIPING
CONNECTION POINTS IN NEW GENERATOR SET.
90355
E-7
E L E
C T
R I C
A L
P
L A
U I L D
I N
G
3 FEB 2015
EXISTING MAIN DISCONNECT SWITCH
EXISTING 400 A., 4 P.
AUTOMATIC TRANSFER SWITCH
EXISTING PAD MOUNTED TRANSFORMER
ELECTRICAL PLAN - BUILDING 91350 - DEMOLITION
SCALE: 1/4" = 1'-0"
ELECTRICAL PLAN - BUILDING 91350 - NEW WORK
SCALE: 1/4" = 1'-0"
EXISTING MAIN DISCONNECT SWITCH
EXISTING 400 A., 4 P.
AUTOMATIC TRANSFER SWITCH
EXISTING PAD MOUNTED TRANSFORMER
NO SCALE
SINGLE LINE DIAGRAM - DEMOLITION
NEW 100 KW/125 KVA, 208Y/120 V., 3Ø
EMERGENCY GENERATOR SET.
G
EXISTING
MAIN
PANEL
EUS EUS
EUS
EXISTING 400 A., 3 P. MAIN
DISCONNECT SWITCH.
NO SCALE
SINGLE LINE DIAGRAM - NEW WORK
EXISTING EXPOSED
SECONDARY TO REMAIN.
EXISTING UNDERGROUND SECONDARY
TO REMAIN.
EXISTING UNDERGROUND SECONDARY
TO REMAIN.
EXISTING 400 A., 4 P.
AUTOMATIC TRANSFER SWITCH.
REMOVE EXISTING 60 KW
GENERATOR SET.
G
EXISTING
MAIN
PANEL
EUS EUS
EUS
EXISTING 400 A., 3 P. MAIN
DISCONNECT SWITCH.
EXISTING EXPOSED
SECONDARY TO REMAIN.
EXISTING UNDERGROUND SECONDARY
TO REMAIN.
EXISTING UNDERGROUND SECONDARY
TO REMAIN.
EXISTING 400 A., 4 P.
AUTOMATIC TRANSFER SWITCH.
REMOVE EXISTING 60 KW GENERATOR SET.
E
U
S
E
U
S
INSTALL NEW 100 KW GENERATOR SET.
BASIS OF DESIGN:
CUMMINS 100 KW DSGAA W/ 309 GALLON SUB-BASE DIESEL FUEL TANK & WEATHER PROTECTIVE ENCLOSURE.
PHYSICAL DIMENSIONS: 105" LONG X 44" WIDE X 88" HIGH.
GENERAL NOTES:
1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT
FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY
THE CONTRACTOR.
2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO
BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER SWITCHES
THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER PRODUCTION SHOP. THE
CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO A LOCATION ON HURLBURT
FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.
3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER
SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.
4. THE CONTRACTOR SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS AND DISPOSE
OF PROPERLY.
WORK NOTES:
1 EXISTING EMERGENCY POWER FEEDER TO TRANSFER SWITCH. SEE "EMERGENCY POWER FEEDER NOTE,"
THIS SHEET.
EXISTING 120 VOLT CIRCUIT. SEE "120 VOLT CIRCUIT NOTE," THIS SHEET.
REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING GENERATOR SET.
MOUNT ON SIDE OF GENERATOR BREAKER ENCLOSURE & RECONNECT TO EXISTING 120 VOLT CIRCUIT.
EXISTING CONTROL WIRING & CONDUIT. SEE "CONTROL WIRING NOTE," THIS SHEET.
EMERGENCY POWER FEEDER NOTE:
RECONNECT EXISTING EMERGENCY POWER FEEDER TO NEW GENERATOR CIRCUIT BREAKER. IN THE EVENT
THAT THE EXISTING FEEDER IS NOT LONG ENOUGH TO REACH THE NEW CIRCUIT BREAKER, REMOVE THE
EXISTING FLEXIBLE CONDUITS BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE EXISTING
CONDUCTORS WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND
EXTEND THE NEW CONDUCTORS TO THE CIRCUIT BREAKER.
120 VOLT CIRCUIT NOTE:
RECONNECT EXISTING 120 VOLT POWER CIRCUIT TO THE DUPLEX RECEPTACLE. IN THE EVENT THAT THE
EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE RECEPTACLE, REMOVE THE EXISTING FLEXIBLE
CONDUIT CONNECTION BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE EXISTING
CONDUCTORS WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND
EXTEND THE NEW CONDUCTORS TO THE DUPLEX RECEPTACLE.
CONTROL WIRING NOTE:
RECONNECT EXISTING CONTROL WIRING CONDUCTORS TO THE NEW GENERATOR CONTROLLER. IN THE EVENT
THAT THE EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE NEW CONTROLLER, REMOVE THE EXISTING
FLEXIBLE CONDUIT, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS WITH BUTT TYPE COMPRESSION
SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW CONDUCTORS TO THE
CONTROLLER.
FUEL TANK
CONDUIT ENTRY OPENING
OUTLINE OF GENERATOR
CIRCUIT BREAKER
LOCATE NEW GENERATOR SET SO THAT EXISTING
CONDUITS FALL WITHIN THE CONDUIT ENTRY OPENING
BELOW THE GENERATOR CIRCUIT BREAKER.
CONDUIT ENTRY OPENING
FUEL TANK SIZING CALCULATION:
METERED LOAD ON EXISTING GENERATOR SET IS 90 KW.
NEW GENERATOR SET RATED AT 100 KW WILL BE LOADED AT 90%.
GENERATOR SET FUEL CONSUMPTION AT FULL LOAD IS 8.87 GPH.
72 HOUR FUEL CONSUMPTION AT FULL LOAD IS 638 GALLONS.
THE LARGEST FUEL TANK AVAILABLE FOR THE 100 KW GENERATOR SET W/ WEATHER PROTECTIVE ENCLOSURE IS 309 GALLONS.
309 GALLONS AT 100% FUEL CONSUMPTION WILL PROVIDE APPROXIMATELY 34.8 HOURS OF BACKUP POWER.
PLAN VIEW - NEW SUB-BASE FUEL TANK
NEW GENERATOR ELEVATION