Attachment 2 - Evaluation Criteria.pdf
PDF 66 KB Posted
- Attached to
- Wet Burn Trainer Federal contract opportunity
- Solicitation number
- FA3030-20-Q-C099
About this file
This document includes an evaluation criteria attachment and a related federal contract opportunity solicitation. The evaluation criteria attachment provides requirements for a wet burn house trainer project, including details on fuel types, safety rooms, systems, and applicable NFPA codes. The related federal contract opportunity is a solicitation from the Department of the Air Force for a wet burn house trainer. Interested vendors must provide a quotation by 13 March 2020 to the 17th Contracting Squadron at Goodfellow Air Force Base in Texas. The solicitation includes a site visit date and points of contact for any questions.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment 3 Revision 1 - Wet Burn Drawings Updated.pdf | ||
| Attachment 1 Revision 1 - Statement of Work Updated.pdf | ||
| Questions and Answers.pdf | ||
| Attachment 3 - Wet Burn Drawings.pdf | ||
| Attachment 1 - Statement of Work.pdf | ||
| Combo.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Burn House (wet) Trainer Evaluation Criteria
Competency
Provide proof of completion of projects of this magnitude
Training Fires Fuel Type
Bedrooms X2 – Liquid propane
Kitchen – Liquid propane
Living room‐Liquid propane
Concealed Fire Prop – Liquid propane
Safety Systems
Interior Safety
Wired dead‐man device, Safety Pendent with controls for both high low fires and flashover
Gas detection sensors throughout (minimum one per burn room)
Heat sensors in burn rooms (minimum one per burn room)
Emergency shutoff push buttons at every room exit point
Ventilation/extraction system capable of one air change per minute/continuous duty @ 500 degrees F. Operate at purge flow when turned on and during emergency shutdowns, during this time only the propane detection system will be operational. Fan failure will initiate emergency shutdown.
Centralized Computer control system
Fire Safety System
Fail safe supply valve to close automatically in the event of electrical failure
Interlocked pilot light system monitoring designed to detect and monitor pilot flame
Fire safety shutoff valve dedicated at each fire, monitored by the interlocked system
Gas pressure monitor at the propane inlet, monitored by the interlocked system
Propane detection will be a dual drawn sample detection system. Monitored by the interlocked system
Applicable NFPA Codes
NFPA 54 – National Fuel Gas Code
NFPA 58 – LP Gas Storage and Use
NFPA 70 – National Electrical Codes
NFPA 1403 – Standard on Live Fire Training Evolutions
NFPA 1402 – Guide to Building Fire Service Training Centers