Attachment 2 - Evaluation Criteria.pdf

PDF 66 KB Posted

Attached to
Wet Burn Trainer Federal contract opportunity
Solicitation number
FA3030-20-Q-C099
Issued by
Department of the Air Force Air Education and Training Command

About this file

This document includes an evaluation criteria attachment and a related federal contract opportunity solicitation. The evaluation criteria attachment provides requirements for a wet burn house trainer project, including details on fuel types, safety rooms, systems, and applicable NFPA codes. The related federal contract opportunity is a solicitation from the Department of the Air Force for a wet burn house trainer. Interested vendors must provide a quotation by 13 March 2020 to the 17th Contracting Squadron at Goodfellow Air Force Base in Texas. The solicitation includes a site visit date and points of contact for any questions.

View the file

Other files for this federal contract opportunity

Other files attached to Wet Burn Trainer, newest first.
File Type Posted
Attachment 3 Revision 1 - Wet Burn Drawings Updated.pdf PDF
Attachment 1 Revision 1 - Statement of Work Updated.pdf PDF
Questions and Answers.pdf PDF
Attachment 3 - Wet Burn Drawings.pdf PDF
Attachment 1 - Statement of Work.pdf PDF
Combo.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Burn House (wet) Trainer Evaluation Criteria

Competency

Provide proof of completion of projects of this magnitude

Training Fires Fuel Type

Bedrooms X2 – Liquid propane

Kitchen – Liquid propane

Living room‐Liquid propane

Concealed Fire Prop – Liquid propane

Safety Systems

Interior Safety

Wired dead‐man device, Safety Pendent with controls for both high low fires and flashover

Gas detection sensors throughout (minimum one per burn room)

Heat sensors in burn rooms (minimum one per burn room)

Emergency shutoff push buttons at every room exit point

Ventilation/extraction system capable of one air change per minute/continuous duty @ 500 degrees F. Operate at purge flow when turned on and during emergency shutdowns, during this time only the propane detection system will be operational. Fan failure will initiate emergency shutdown.

Centralized Computer control system

Fire Safety System

Fail safe supply valve to close automatically in the event of electrical failure

Interlocked pilot light system monitoring designed to detect and monitor pilot flame

Fire safety shutoff valve dedicated at each fire, monitored by the interlocked system

Gas pressure monitor at the propane inlet, monitored by the interlocked system

Propane detection will be a dual drawn sample detection system. Monitored by the interlocked system

Applicable NFPA Codes

NFPA 54 – National Fuel Gas Code

NFPA 58 – LP Gas Storage and Use

NFPA 70 – National Electrical Codes

NFPA 1403 – Standard on Live Fire Training Evolutions

NFPA 1402 – Guide to Building Fire Service Training Centers