Questions and Answers - FA303019BA004.pdf
PDF 9 KB Posted
- Attached to
- Construct Dry Burn Training facility Federal contract opportunity
- Solicitation number
- FA303019BA004
About this file
Questions and Answers - FA303019BA004
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Site Visit Record of Attendance.pdf | ||
| Solicitation Amendment FA303019BA0040001 SF 30.pdf | ||
| Attach_4_-_Insurance_Requirements_Compliance.pdf | ||
| Attach_3_-_Form_66_-_Dry_Burn_Training_Facility.pdf | ||
| Solicitation_-_FA303019BA004.pdf | ||
| Attach_2_-_Design_Drawings_-_Dry_Burn_Training_Facility_-_Part_2.pdf | ||
| Attach_2_-_Design_Drawings_-_Dry_Burn_Training_Facility_-_Part_1.pdf | ||
| Attach_5_-_Base_Access_Request_Letter_Template.pdf | ||
| Attach_1_-_Specifications_-_Dry_Burn_Training_Facility.pdf | ||
| Attach_6_-_DBA_Wage_Determination_TX190282.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FA303019BA004 – Construct Dry Burn Training facility
Questions and Answers
Question 1: The specifications call for a dry pipe sprinkler system. The plans do not show a service entrance or location of the backflow preventer. Since it is noted that the system is for demonstration only and is not intended for life safety, do we need to have to have a service entrance and backflow preventer?
Answer: This is facility is for fire fighter training purposes only. A service entrance and black flow is not required.
Question 2: There appear to be 4 fire extinguishers shown but there is no specification for them.
Are fire extinguishers to be furnished and installed by the contractor or will they be installed by the end user?
Answer: Contractor is not responsible for providing the fire extinguishers. The government will provide them.
Question 3: We are missing the spec: Gas Fired training systems SECTION 11 00 00.
Please confirm it is not in the contract.
Answer: This section is not required for this acquisition as this facility is a try training facility and will have no Gas fire training systems included.