Question and Answer for Repair Various Lift Stations.pdf

PDF 118 KB Posted

Attached to
Repair Various Lift Stations, CCAFS Federal contract opportunity
Solicitation number
FA252120B0009
Issued by
Department of the Air Force Space Command

About this file

This document contains questions and answers regarding specifications for repairing various lift stations at Cape Canaveral Air Force Station in Florida. The solicitation calls for providing all labor, materials, and equipment to repair four lift stations at various locations on the base. One question asked about the material for air release valves, as the specifications require stainless steel but one drawing details a non-stainless steel option. The answer confirms contractors must follow the specifications requiring stainless steel valves, but also notes the drawing provides two alternative valve references that could be considered equal options.

View the file

Other files for this federal contract opportunity

Other files attached to Repair Various Lift Stations, CCAFS, newest first.
File Type Posted
OF 1419A (2 of 2).pdf PDF
OF 1419 (1 of 2).pdf PDF
SF30 Amendment 04.pdf PDF
Questions and Answers for Repair Various Lift Stations.pdf PDF
SF30 Amandment 03.pdf PDF
SF30 Amendment 02.pdf PDF
Atch 5a-Wage Rate Requirements WD FL20200001 (14Aug2020).pdf PDF
Atch 7- Image_Drawing of LS 47151 at Cx40.pdf PDF
Sign-in Sheet for 20B0009 Site Visit (18 Aug).pdf PDF
SF30 Amendment 01.pdf PDF
Solicitation - FA252120B0009.pdf PDF
Atch 6- Q_A Template.doc DOC document
Atch 5-Wage Rate Requirements FL20200001 (03Jul2020).pdf PDF
Solicitation - FA252120B0009.pdf PDF
Atch 1- Technical Specification.pdf PDF
Atch 2- Drawings.pdf PDF
Atch 4- HazWasteForm.doc DOC document
Atch 3- Green Procurement Form.pdf PDF
Show all 18

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Repair Various Lift Stations, Cape Canaveral AFS, FL Project No.: DBEH 12-1551

Solicitation No.: FA252120B0009

IFP Section 33 31 23.00 10 Paragraph 2.3.3.

Other (Specify): Air Release Valve

Question:

Specification Section 33 31 23.00 10 paragraph 2.3.3. does not specify material construction for the Air Release Valve Body. Drawings Sheets C-101, C-102, C-103 and C-104 all call for a Stainless-Steel Air Release Valve. Drawing sheet C-502 providing a detail for the above ground air release assembly calls for the Air Release Valve to be an AD025 P which is not a stainless steel body, please confirm that the air release valves can be non stainless steel as specified in the construction detail on sheet C-502 if supplying the ARI D025P Valve.

Answer:

Contractor is advised to follow the specifications, Section 33 31 23.00 10, Part 2.3.3.1 Automatic Air Release Valve (section referenced below).

Additionally, Drawing sheet C-502 provides two reference options: “ARI Model D-025, CRISPIN USL20 or Approved equal”