FA2521-15-B-0003_REVISED_Sheet_-_E-101_-_REV_ELECTRICAL_PLAN.pdf

PDF 326 KB Posted

Attached to
Repair Pass & ID Facility 1068, CCAFS Federal contract opportunity
Solicitation number
FA2521-15-B-0003
Issued by
Department of the Air Force Space Command

About this file

FA2521-15-B-0003 Amendment 1 Revised Drawing Sheet E-101 Revised Electrical Plan

View the file

Other files for this federal contract opportunity

Other files attached to Repair Pass & ID Facility 1068, CCAFS, newest first.
File Type Posted
15-B-0003_Abstract_of_Bids.pdf PDF
FA2521-15-B-0003_Solicitation_Amendment_3.pdf PDF
DBWD_3_Apr_15.pdf PDF
FA2521-15-B-0003_Solicitation_Amendment_2.pdf PDF
FA2521-15-B-0003_Solicitation_Amendment_1.pdf PDF
Davis_Bacon_Wage_Determination_20_Mar_15.pdf PDF
FA2521-15-B-0003_Solicitation_Questions_with_Resposnes.pdf PDF
15-B-0003_Prebid_Site_Visit_Sign_In_Roster.pdf PDF
Attch_2_-_Project_Specifications.pdf PDF
Attch_3_-_GPP_Certification.pdf PDF
Attch_4_-_DBA_WD_27_Feb_15.pdf PDF
Attch_6_-_CECC_Form_3052.xls XLS spreadsheet
Attch_7_-_Questions_ _Answers_Template.docx DOCX document
Attch_1_-_Project_Drawings.pdf PDF
FA2521-15-B-0003.pdf PDF
Attch_5_-_Haz_Waste_Form.doc DOC document
Show all 16

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

R

EF

G

FC

I G

FC

I

G

FC

I G

FC

I

(TYP)

PI-28PI-26

PI-24

PI-1

TELEPHONE/LAN OUTLET, (4) RJ-45

DUPLEX RECEPTACLE, 20A

QUAD RECEPTACLE, 20A

PANEL BOARD, 208/120V

LEGEND-ELECTRICAL

BRANCH CIRCUIT CONDUIT RUN.

ARROW INDICATES HOME RUN,

MINIMUM CONDUIT SIZE SHALL BE 3/4".

HOMERUNS LONGER THAN 100' SHALL

USE #10 CONDUCTOR (MIN).

O ne id a

To ta l I nt eg ra te d

En te rp ris es R

AE

IS

R

AN

G E

AR

C

H

IT

EC

T-

EN

G

IN

EE

R

IN

SP

EC

TI

O

N S

ER

VI

C

ES

SHEET

IDENTIFICATION

1 2 3 4 5

D R

AW

N

B Y:

D

ES

I G N

B Y:

SB

M

T

BY

S

IZ

E :

FI

LE

N

A M

E:

IS

SU

E D

A

TE

C O

N

TR

AC

T

N O

S O

LI

C

IT

AT

IO

N

N O

C

KD

B

Y:

" x

4"

D

C

B

A

FI

LE

N U

M

BE

R

P

LO

T

SC

A

LE

P

LO

T D

AT

E:

SHEET OF

U

SA

F

TH

C

IV

IL

E N

G

IN

EE

R

S Q

U

AD

R O

N C

O N

TR

AC

T N

O

FA

-1

3- D

-0

- 0

C C

AF

S, F L

/4

'-0

3/

/ 2

3:

: 1

PM

R

EP

A

IR

V

IS

IT

O

R C

O N T

RO

L

CE

N

T E R

FA

C

IL

IT

Y

, C C

A F S

/1

7/

FA

-1

3- D

-0

J.

K

EL

LE

Y

J.

K

EL

LE

Y

G . B

EA

R

D

D

BE

H

0-

.rv t

E-101

A . R

O M

AN

EL

EC

TR

IC

A L P

LA

N

D

BE

H

0-

E E -

1-

1/4" = 1'-0"E-101

1 ELECTRICAL PLAN

FLAG NOTES:

1. PROVIDE NEW PATCH PANEL TO TERMINATE NEW CAT 6 CABLES.

2. EXISTING TELEPHONE TERMINAL CABINET.

3. NEW COMMUNICATION OUTLET. PROVIDE CAT 6 CABLE FROM THE OUTLET

TO THE EXISTING LAN RACK.

4. REMOVE EXISTING DURESS BUTTONS AND WIRING FROM EXISTING

CABINETRY AND INSTALL IN NEW CABINETRY. COORDINATE LOCATION OF

DURESS BUTTONS WITH THE FACILITY MANAGER.

5. EXISTING SQUARE D PANEL P1. INSTALL 4 NEW 1-POLE 20A BREAKERS IN

POSITIONS, 22, 24, 26 AND 30 TO FEED RECEPTACLES AS INDICATED ON THE

PLANS.

6. DURING CONSTRUCTION PROVIDE 2 LAN OUTLETS AND 2 PHONE

OUTLETS IN THIS AREA TO ALLOW USERS TO SETUP COMPUTER

STATIONS FOR BADGING. COORDINATE EXACT LOCATION WITH USER.

7. LCN 8310-856 WALL MOUNTED ACTUATOR

GENERAL NOTES - ELECTRICAL

1. IT IS THE INTENT OF THESE CONTRACT DRAWINGS TO PROVIDE A

COMPLETE AND WORKABLE FACILITY.

2 DESIGN DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL

OFFSETS, BENDS, ELBOWS, OR OTHER SPECIFIC ELEMENTS THAT MAY

BE REQUIRED FOR PROPER INSTALLATION OF THE WORK. SUCH WORK

SHALL BE VERIFIED AT THE SITE. ADDITIONAL BENDS, OFFSETS, AND

CONDUIT AS REQUIRED BY VERTICAL AND HORIZONTAL EQUIPMENT

LOCATIONS OR OTHER JOB CONDITIONS, SHALL BE PROVIDED TO

COMPLETE THE WORK AT NO ADDITIONAL COST TO THE GOVERNMENT.

3. EXCEPT WHERE SHOWN IN DIMENSIONAL DETAIL, THE LOCATIONS OF

EQUIPMENT SHOWN ON PLANS ARE APPROXIMATE. SUCH ITEMS

SHALL BE PLACED TO ELIMINATE INTERFERENCE WITH OTHER

EQUIPMENT. THE EXACT LOCATIONS SHALL BE DETERMINED IN THE

FIELD.

4. ALL WORK SHALL BE IN ACCORDANCE WITH THE 2014 EDITION OF THE

NATIONAL ELECTRICAL CODE NFPA 70.

5. MATERIALS SHALL BE LISTED BY THE UNDERWRITER'S LABORATORIES,

INC. OR ANOTHER APPROVED/CERTIFIED TESTING LABORATORY.

SHOULD PLANS AND CODES CONFLICT, CONTACT THE CONTRACTING

OFFICER. MAKE NO CHANGES, EVEN IN CASE OF CONFLICT, WITHOUT

FIRST OBTAINING THE APPROVAL OF THE CONTRACTING OFFICER.

6. A GREEN, COPPER GROUND WIRE SHALL BE INSTALLED IN ALL

CONDUIT SYSTEMS AND SHALL BE BONDED TO ALL ENCLOSURES,

BOXES, AND EQUIPMENT. RECEPTACLES WITH GREEN WIRE SHALL BE

BONDED TO BOX THEN TO RECEPTACLE SUCH THAT REMOVAL OF

RECEPTACLE DEVICE SHALL NOT INTERRUPT GREEN WIRE BOND TO

METALLIC BOX OR ENCLOSURE.

7. BONDING JUMPERS SHALL BE USED TO BOND CONDUIT TO

ENCLOSURES, BOXES, AND EQUIPMENT WHERE CONCENTRIC OR

ECCENTRIC KNOCKOUTS ARE USED.

8. EQUIPMENT SIZES INDICATED ARE MINIMUM, BEFORE INSTALLING ANY

WIRE OR CONDUIT, THE CONTRACTOR SHALL OBTAIN THE EXACT

EQUIPMENT REQUIREMENTS AND SHALL INSTALL WIRE, CONDUIT,

CIRCUIT BREAKERS AND OTHER ITEMS OF THE CORRECT SIZE FOR THE

EQUIPMENT ACTUALLY INSTALLED. HOWEVER, WIRE AND CONDUIT

SIZES FOR THE EQUIPMENT SHALL BE TAKEN AS A MINIMUM AND SHALL

NOT BE REDUCED WITHOUT WRITTEN APPROVAL.

9. THE INSTALLATION OF THE ELECTRICAL WORK SHALL BE

COORDINATED WITH THE WORK OF THE OTHER TRADES.

10. THE INSTALLATION SHALL BE ACCOMPLISHED BY WORKERS SKILLED IN

THIS TYPE OF WORK. THE INSTALLATION SHALL BE MADE SO THAT

THERE IS NO DEGRADATION OF THE DESIGNED FIRE RATINGS.

11. THE CONTRACTOR SHALL INSTALL HIS WORK IN SUCH A MANNER AND

AT SUCH A TIME AS WILL REQUIRE A MINIMUM OF CUTTING AND

PATCHING OF THE BUILDING STRUCTURE.

THE CONTRACTOR SHALL INSTALL HIS WORK IN SUCH A MANNER AND

AT SUCH A TIME AS WILL REQUIRE A MINIMUM OF CUTTING AND

PATCHING OF THE BUILDING STRUCTURE.

12. PROVIDE, AS USED HERE ON THE DRAWINGS, IS AN ALL-INCLUSIVE

TERM REQUIRING CONTRACTOR TO FURNISH, INSTALL, WIRE, AND

CONNECT ALL SPECIFIED EQUIPMENT AS WELL AS COMPONENTS,

ACCESSORIES, WIRING, AND MOUNTING HARDWARE TO INSURE THAT

SPECIFIED EQUIPMENT FUNCTIONS TO MEET SYSTEM(S)

REQUIREMENTS.

13. WHERE NEW-TO-EXISTNG CONNECTIONS ARE INDICATED, THE

CONTRACTOR SHALL PROVIDE ALL MATERIALS (JUNCTION BOXES,

CONDUIT, WIRE, AND CONNECTIONS) AND LABOR REQUIRED TO MAKE

THE CONNECTIONS.

14. UNLESS OTHERWISE NOTED, ALL POWER CIRCUIT CONDUCTORS

SHALL BE COPPER AND MINIMUM #12AWG. CONDUITS SHALL BE 3/4"

MINIMUM.

15. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROTECT

EXISTING UTILITIES FROM DAMAGE. THE CONTRACTOR SHALL BEAR

ALL EXPENSE FOR REPAIR OR REPLACEMENT OF THE UTILITIES OR

OTHER PROPERTY DAMAGED BY OPERATIONS IN CONJUNCTION WITH

THE COMPLETION OF THIS WORK.

16. ALL BOLTS, NUTS, WASHERS, ETC. USED FOR GROUNDING AND

BONDING CONNECTIONS SHALL BE COPPER. CONTRACTOR SHALL

UTILIZE CONNECTORS TO PREVENT GALVANIC ACTION.

17. FINAL ACCEPTANCE WILL DEPEND UPON SATISFACTORY

PERFORMANCE OF EQUIPMENT. NO CONDUCTOR SHALL BE

ENERGIZED UNTIL THE INSTALLATION HAS BEEN APPROVED.

18. ALL EXPOSED ELECTRICAL CONDUIT VULNERABLE TO MECHANICAL

DAMAGE SHALL BE RIGID GALVANIZED STEEL, UNLESS NOTED

OTHERWISE. ALL OTHER CONDUIT INSIDE FACILITY SHALL BE

ELECTRICAL METALLIC TUBE (EMT).

19. CONDUITS SHALL BE SUPPORTED BY SUITABLE CLAMPS, HANGERS OR

STRAPS TO PROVIDE A RIGID INSTALLATION. CONDUIT SUPPORTS

SHALL NOT BE FASTENED OR ATTACHED TO OTHER PIPES.

PERFORATED STRAP HANGERS WILL NOT BE ALLOWED. EMPTY

CONDUIT SHALL BE THOROUGHLY SWABBED OUT WITH DRY SWAB TO

REMOVE MOISTURE AND DEBRIS BEFORE WIRE IS DRAWN IN. END OF

CONDUIT SHALL BE TIGHTLY PLUGGED UNTIL WIRE IS PULLED. NO

CONDUIT SHALL BE LOCATED TO IMPAIR THE STRENGTH OF

STRUCTURAL MEMBERS. MAKE CHANGES IN DIRECTION OF RUNS WITH

SYMMETRICAL BENDS. MAKE FIELD MADE BENDS AND OFFSETS WITH

HICKEY OR CONDUIT BENDING MACHINE. DO NOT INSTALL CRUSHED

OR DEFORMED CONDUITS. AVOID TRAPPED CONDUITS. PREVENT

PLASTER, DIRT, OR TRASH FROM LODGING IN CONDUIT, BOXES, AND

FITTINGS. FREE CLOGGED CONDUITS OF OBSTRUCTIONS.

20. IN ACCORDANCE WITH NFPA 70, GROUND EXPOSED, NON CURRENT

CARRYING METALLIC PARTS OF ELECTRICAL EQUIPMENT, METALLIC

RACEWAY SYSTEMS, GROUNDING CONDUCTOR IN METALLIC

RACEWAYS.

21. FASTEN CONDUITS TO SHEET METAL BOXES AND CABINETS WITH TWO

LOCKNUTS WHERE REQUIRED BY NFPA 70, WHERE INSULATED

BUSHINGS ARE USED, AND WHERE BUSHINGS CANNOT BE BROUGHT

INTO FIRM CONTACT WITH THE BOX; OTHERWISE, USE MINIMUM

SINGLE LOCKNUT AND BUSHING. LOCKNUTS SHALL HAVE SHARP

EDGES FOR DIGGING INTO WALLS OF METAL ENCLOSURE. INSTALL

BUSHINGS ON ENDS OF CONDUITS, AND PROVIDE INSULATING TYPE

WHERE REQUIRED BY NFPA 70.

22. THE CORRIDOR AND MECHANICAL ROOM WALLS AND CEILING ARE FIRE

RATED. PENETRATIONS THROUGH THE WALLS SHALL BE A MINIMUM

OF 0.5" DIAMETER LARGER THAN THE CONDUIT REQUIRED TO

PENETRATE THE WALL. PROVIDE A FIRESTOP MATERIAL PER

REQUIREMENTS BELOW. CONDUIT THROUGH THE SLEEVE SHALL BE

GALVANIZED RIGID STEEL AND SHALL EXTEND A MINIMUM OF 18"

BEYOND THE SLEEVE OF BOTH SIDES.

23. PROVIDE AND INSTALL AT WALL OR FLOOR PENETRATIONS A

PERMANENT FIRESTOP SYSTEM. THE SYSTEM SHALL CONSIST OF A

WATERBASED FIRESTOP COMPOUND AS THE FILL, VOID, OR CAVITY

MATERIAL ALONG WITH APPROPRIATE DAMMING MATERIAL (AS PER

MANUFACTURER'S INSTRUCTIONS). THE FIRESTOP COMPOUND SHALL

NOT CONTAIN ANY SOLVENTS, INORGANIC FIBERS, OR SILICONE

COMPOUNDS AND SHALL NOT REQUIRE HEAT TO ACTIVATE THE SEAL.

THE FIRESTOP COMPOUND SHALL BE ONE-PART MATERIALS,

REQUIRING NO CRITICAL MIXING. THE PENETRATION SEAL MATERIAL

MUST BE UNAFFECTED BY MOISTURE AND MUST MAINTAIN THE

INTEGRITY OF THE FLOOR OR WALL ASSEMBLY FOR ITS RATED TIME

PERIOD WHEN TESTED IN ACCORDANCE WITH ASTM E84. THE SYSTEM

SHALL BE UL CLASSIFIED AND INSTALLED TO PROVIDE A 2 HOUR FIRE

RATING. THE PENETRATION FIRE STOP MATERIAL SHALL BE

FLAME-SAFE FS1900 SERIES COMPOUND AS MANUFACTURED BY

GRACE CONSTRUCTION PRODUCTS OR EQUAL.

A - AMPERE, AMPS

AFC - ABOVE FINISHED COUNTER

AFF - ABOVE FINISHED FLOOR

AFG - ABOVE FINISHED GRADE

AHU - AIR HANDLING UNIT

AIC - AMPS INTERRUPTING CAPACITY

AUX - AUXILIARY

BFF - BELOW FINISHED FLOOR

BFG - BELOW FINISHED GRADE

BIL - BASIC INSULATION IMPULSE LEVEL

C, CDT - CONDUIT

CB - CIRCUIT BREAKER

CF - COMPACT FLUORESCENT

CFM - CUBIC FEET PER MINUTE

CKT - CIRCUIT

CLG - CEILING

CONC - CONCRETE

CONT - CONTINUED, CONTINUATION, CONTROL

CU - COPPER

DIA (�) - DIAMETER

DIM - DIMENSION

DISC - DISCONNECT

DN - DOWN

DWG - DRAWING

EA - EACH

EL - ELEVATION

ELEC - ELECTRIC

EMT - ELECTRICAL METALLIC TUBING

EOP - EDGE OF PAVEMENT

EXH - EXHAUST

FA - FIRE ALARM

FACP - FIRE ALARM CONTROL PANEL

FL - FLOOR

FLA - FULL LOAD AMPS

FLEX - FLEXIBLE

FT - FEET

GFI - GROUND FAULT INTERRUPTER

GND - GROUND

HDWR - HARDWARE

HORIZ - HORIZONTAL

HP - HORSEPOWER

HTR - HEATER

HWG - HEAVY WALL GALVANIZED CONDUIT

I - CURRENT

ID - INSIDE DIAMETER

IN - INCH, INCHES

kV, KV - KILOVOLTS

KW - KILOWATT

LB - POUND

LF - LINEAR FEET

LPS - LOW PRESSURE SODIUM

LV - LOW VOLTAGE

MCM - THOUSAND CIRCULAR MILS

MECH - MECHANICAL

MCP - MOTOR CIRCUIT PROTECTION

MH - MANHOLE

M.O. - MOTOR OPERATED

MPS - MANUAL PULL STATION

MTR - MOTOR

N/A - NOT APPLICABLE

NC - NORMALLY CLOSED

NIC - NOT IN CONTRACT

NO - NORMALLY OPEN

NTS - NOT TO SCALE

O2, 0 - OXYGEN

OA - OUTSIDE AIR

OC - ON CENTER

OD - OUTSIDE DIAMETER

OPP - OPPOSITE

OVHD - OVERHEAD

PB - PULL BOX, PUSH BUTTON

PL - PLACES

PNL - PANEL, PANELBOARD

PRESS - PRESSURE

PRV - POWERED ROOF VENT

PVC - POLYVINYL CHLORIDE

QTY - QUANTITY

R - RESISTANCE

REF - REFERENCE

RGS - RIGID GALVANIZED STEEL

RM - ROOM

SAN - SANITARY

SE - SERVICE ENTRANCE

SHT - SHEET

SIG - SIGNAL (INDICATING) CIRCUIT

SQ - SQUARE FOOT, SQUARE FEET

SS - STAINLESS STEEL

SW - SWITCH

SYS - SYSTEM

TEMP - TEMPERATURE

THK - THICK

TMCB - THERMAL MAGNETIC CIRCUIT BREAKER

TRANSF - TRANSFORMER

TTB - TELEPHONE TERMINAL BOARD

TYP - TYPICAL

UF - UNDER FLOOR

UG - UNDERGROUND

UON - UNLESS OTHERWISE NOTED

VERT - VERTICAL

W - WATT

W/ - WITH

W/O - WITHOUT

WH - WATER HEATER

WP - WEATHERPROOF

WTR - WATER

XFMR - TRANSFORMER

Sheets
E-101 - ELECTRICAL PLAN