FA2521-15-B-0003_REVISED_Sheet_-_E-101_-_REV_ELECTRICAL_PLAN.pdf
PDF 326 KB Posted
- Attached to
- Repair Pass & ID Facility 1068, CCAFS Federal contract opportunity
- Solicitation number
- FA2521-15-B-0003
About this file
FA2521-15-B-0003 Amendment 1 Revised Drawing Sheet E-101 Revised Electrical Plan
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 15-B-0003_Abstract_of_Bids.pdf | ||
| FA2521-15-B-0003_Solicitation_Amendment_3.pdf | ||
| DBWD_3_Apr_15.pdf | ||
| FA2521-15-B-0003_Solicitation_Amendment_2.pdf | ||
| FA2521-15-B-0003_Solicitation_Amendment_1.pdf | ||
| Davis_Bacon_Wage_Determination_20_Mar_15.pdf | ||
| FA2521-15-B-0003_Solicitation_Questions_with_Resposnes.pdf | ||
| 15-B-0003_Prebid_Site_Visit_Sign_In_Roster.pdf | ||
| Attch_2_-_Project_Specifications.pdf | ||
| Attch_3_-_GPP_Certification.pdf | ||
| Attch_4_-_DBA_WD_27_Feb_15.pdf | ||
| Attch_6_-_CECC_Form_3052.xls | XLS spreadsheet | |
| Attch_7_-_Questions_ _Answers_Template.docx | DOCX document | |
| Attch_1_-_Project_Drawings.pdf | ||
| FA2521-15-B-0003.pdf | ||
| Attch_5_-_Haz_Waste_Form.doc | DOC document |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
R
EF
G
FC
I G
FC
I
G
FC
I G
FC
I
(TYP)
PI-28PI-26
PI-24
PI-1
TELEPHONE/LAN OUTLET, (4) RJ-45
DUPLEX RECEPTACLE, 20A
QUAD RECEPTACLE, 20A
PANEL BOARD, 208/120V
LEGEND-ELECTRICAL
BRANCH CIRCUIT CONDUIT RUN.
ARROW INDICATES HOME RUN,
MINIMUM CONDUIT SIZE SHALL BE 3/4".
HOMERUNS LONGER THAN 100' SHALL
USE #10 CONDUCTOR (MIN).
O ne id a
To ta l I nt eg ra te d
En te rp ris es R
AE
IS
R
AN
G E
AR
C
H
IT
EC
T-
EN
G
IN
EE
R
IN
SP
EC
TI
O
N S
ER
VI
C
ES
SHEET
IDENTIFICATION
1 2 3 4 5
D R
AW
N
B Y:
D
ES
I G N
B Y:
SB
M
T
BY
S
IZ
E :
FI
LE
N
A M
E:
IS
SU
E D
A
TE
C O
N
TR
AC
T
N O
S O
LI
C
IT
AT
IO
N
N O
C
KD
B
Y:
" x
4"
D
C
B
A
FI
LE
N U
M
BE
R
P
LO
T
SC
A
LE
P
LO
T D
AT
E:
SHEET OF
U
SA
F
TH
C
IV
IL
E N
G
IN
EE
R
S Q
U
AD
R O
N C
O N
TR
AC
T N
O
FA
-1
3- D
-0
- 0
C C
AF
S, F L
/4
'-0
3/
/ 2
3:
: 1
PM
R
EP
A
IR
V
IS
IT
O
R C
O N T
RO
L
CE
N
T E R
FA
C
IL
IT
Y
, C C
A F S
/1
7/
FA
-1
3- D
-0
J.
K
EL
LE
Y
J.
K
EL
LE
Y
G . B
EA
R
D
D
BE
H
0-
.rv t
E-101
A . R
O M
AN
EL
EC
TR
IC
A L P
LA
N
D
BE
H
0-
E E -
1-
1/4" = 1'-0"E-101
1 ELECTRICAL PLAN
FLAG NOTES:
1. PROVIDE NEW PATCH PANEL TO TERMINATE NEW CAT 6 CABLES.
2. EXISTING TELEPHONE TERMINAL CABINET.
3. NEW COMMUNICATION OUTLET. PROVIDE CAT 6 CABLE FROM THE OUTLET
TO THE EXISTING LAN RACK.
4. REMOVE EXISTING DURESS BUTTONS AND WIRING FROM EXISTING
CABINETRY AND INSTALL IN NEW CABINETRY. COORDINATE LOCATION OF
DURESS BUTTONS WITH THE FACILITY MANAGER.
5. EXISTING SQUARE D PANEL P1. INSTALL 4 NEW 1-POLE 20A BREAKERS IN
POSITIONS, 22, 24, 26 AND 30 TO FEED RECEPTACLES AS INDICATED ON THE
PLANS.
6. DURING CONSTRUCTION PROVIDE 2 LAN OUTLETS AND 2 PHONE
OUTLETS IN THIS AREA TO ALLOW USERS TO SETUP COMPUTER
STATIONS FOR BADGING. COORDINATE EXACT LOCATION WITH USER.
7. LCN 8310-856 WALL MOUNTED ACTUATOR
GENERAL NOTES - ELECTRICAL
1. IT IS THE INTENT OF THESE CONTRACT DRAWINGS TO PROVIDE A
COMPLETE AND WORKABLE FACILITY.
2 DESIGN DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL
OFFSETS, BENDS, ELBOWS, OR OTHER SPECIFIC ELEMENTS THAT MAY
BE REQUIRED FOR PROPER INSTALLATION OF THE WORK. SUCH WORK
SHALL BE VERIFIED AT THE SITE. ADDITIONAL BENDS, OFFSETS, AND
CONDUIT AS REQUIRED BY VERTICAL AND HORIZONTAL EQUIPMENT
LOCATIONS OR OTHER JOB CONDITIONS, SHALL BE PROVIDED TO
COMPLETE THE WORK AT NO ADDITIONAL COST TO THE GOVERNMENT.
3. EXCEPT WHERE SHOWN IN DIMENSIONAL DETAIL, THE LOCATIONS OF
EQUIPMENT SHOWN ON PLANS ARE APPROXIMATE. SUCH ITEMS
SHALL BE PLACED TO ELIMINATE INTERFERENCE WITH OTHER
EQUIPMENT. THE EXACT LOCATIONS SHALL BE DETERMINED IN THE
FIELD.
4. ALL WORK SHALL BE IN ACCORDANCE WITH THE 2014 EDITION OF THE
NATIONAL ELECTRICAL CODE NFPA 70.
5. MATERIALS SHALL BE LISTED BY THE UNDERWRITER'S LABORATORIES,
INC. OR ANOTHER APPROVED/CERTIFIED TESTING LABORATORY.
SHOULD PLANS AND CODES CONFLICT, CONTACT THE CONTRACTING
OFFICER. MAKE NO CHANGES, EVEN IN CASE OF CONFLICT, WITHOUT
FIRST OBTAINING THE APPROVAL OF THE CONTRACTING OFFICER.
6. A GREEN, COPPER GROUND WIRE SHALL BE INSTALLED IN ALL
CONDUIT SYSTEMS AND SHALL BE BONDED TO ALL ENCLOSURES,
BOXES, AND EQUIPMENT. RECEPTACLES WITH GREEN WIRE SHALL BE
BONDED TO BOX THEN TO RECEPTACLE SUCH THAT REMOVAL OF
RECEPTACLE DEVICE SHALL NOT INTERRUPT GREEN WIRE BOND TO
METALLIC BOX OR ENCLOSURE.
7. BONDING JUMPERS SHALL BE USED TO BOND CONDUIT TO
ENCLOSURES, BOXES, AND EQUIPMENT WHERE CONCENTRIC OR
ECCENTRIC KNOCKOUTS ARE USED.
8. EQUIPMENT SIZES INDICATED ARE MINIMUM, BEFORE INSTALLING ANY
WIRE OR CONDUIT, THE CONTRACTOR SHALL OBTAIN THE EXACT
EQUIPMENT REQUIREMENTS AND SHALL INSTALL WIRE, CONDUIT,
CIRCUIT BREAKERS AND OTHER ITEMS OF THE CORRECT SIZE FOR THE
EQUIPMENT ACTUALLY INSTALLED. HOWEVER, WIRE AND CONDUIT
SIZES FOR THE EQUIPMENT SHALL BE TAKEN AS A MINIMUM AND SHALL
NOT BE REDUCED WITHOUT WRITTEN APPROVAL.
9. THE INSTALLATION OF THE ELECTRICAL WORK SHALL BE
COORDINATED WITH THE WORK OF THE OTHER TRADES.
10. THE INSTALLATION SHALL BE ACCOMPLISHED BY WORKERS SKILLED IN
THIS TYPE OF WORK. THE INSTALLATION SHALL BE MADE SO THAT
THERE IS NO DEGRADATION OF THE DESIGNED FIRE RATINGS.
11. THE CONTRACTOR SHALL INSTALL HIS WORK IN SUCH A MANNER AND
AT SUCH A TIME AS WILL REQUIRE A MINIMUM OF CUTTING AND
PATCHING OF THE BUILDING STRUCTURE.
THE CONTRACTOR SHALL INSTALL HIS WORK IN SUCH A MANNER AND
AT SUCH A TIME AS WILL REQUIRE A MINIMUM OF CUTTING AND
PATCHING OF THE BUILDING STRUCTURE.
12. PROVIDE, AS USED HERE ON THE DRAWINGS, IS AN ALL-INCLUSIVE
TERM REQUIRING CONTRACTOR TO FURNISH, INSTALL, WIRE, AND
CONNECT ALL SPECIFIED EQUIPMENT AS WELL AS COMPONENTS,
ACCESSORIES, WIRING, AND MOUNTING HARDWARE TO INSURE THAT
SPECIFIED EQUIPMENT FUNCTIONS TO MEET SYSTEM(S)
REQUIREMENTS.
13. WHERE NEW-TO-EXISTNG CONNECTIONS ARE INDICATED, THE
CONTRACTOR SHALL PROVIDE ALL MATERIALS (JUNCTION BOXES,
CONDUIT, WIRE, AND CONNECTIONS) AND LABOR REQUIRED TO MAKE
THE CONNECTIONS.
14. UNLESS OTHERWISE NOTED, ALL POWER CIRCUIT CONDUCTORS
SHALL BE COPPER AND MINIMUM #12AWG. CONDUITS SHALL BE 3/4"
MINIMUM.
15. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROTECT
EXISTING UTILITIES FROM DAMAGE. THE CONTRACTOR SHALL BEAR
ALL EXPENSE FOR REPAIR OR REPLACEMENT OF THE UTILITIES OR
OTHER PROPERTY DAMAGED BY OPERATIONS IN CONJUNCTION WITH
THE COMPLETION OF THIS WORK.
16. ALL BOLTS, NUTS, WASHERS, ETC. USED FOR GROUNDING AND
BONDING CONNECTIONS SHALL BE COPPER. CONTRACTOR SHALL
UTILIZE CONNECTORS TO PREVENT GALVANIC ACTION.
17. FINAL ACCEPTANCE WILL DEPEND UPON SATISFACTORY
PERFORMANCE OF EQUIPMENT. NO CONDUCTOR SHALL BE
ENERGIZED UNTIL THE INSTALLATION HAS BEEN APPROVED.
18. ALL EXPOSED ELECTRICAL CONDUIT VULNERABLE TO MECHANICAL
DAMAGE SHALL BE RIGID GALVANIZED STEEL, UNLESS NOTED
OTHERWISE. ALL OTHER CONDUIT INSIDE FACILITY SHALL BE
ELECTRICAL METALLIC TUBE (EMT).
19. CONDUITS SHALL BE SUPPORTED BY SUITABLE CLAMPS, HANGERS OR
STRAPS TO PROVIDE A RIGID INSTALLATION. CONDUIT SUPPORTS
SHALL NOT BE FASTENED OR ATTACHED TO OTHER PIPES.
PERFORATED STRAP HANGERS WILL NOT BE ALLOWED. EMPTY
CONDUIT SHALL BE THOROUGHLY SWABBED OUT WITH DRY SWAB TO
REMOVE MOISTURE AND DEBRIS BEFORE WIRE IS DRAWN IN. END OF
CONDUIT SHALL BE TIGHTLY PLUGGED UNTIL WIRE IS PULLED. NO
CONDUIT SHALL BE LOCATED TO IMPAIR THE STRENGTH OF
STRUCTURAL MEMBERS. MAKE CHANGES IN DIRECTION OF RUNS WITH
SYMMETRICAL BENDS. MAKE FIELD MADE BENDS AND OFFSETS WITH
HICKEY OR CONDUIT BENDING MACHINE. DO NOT INSTALL CRUSHED
OR DEFORMED CONDUITS. AVOID TRAPPED CONDUITS. PREVENT
PLASTER, DIRT, OR TRASH FROM LODGING IN CONDUIT, BOXES, AND
FITTINGS. FREE CLOGGED CONDUITS OF OBSTRUCTIONS.
20. IN ACCORDANCE WITH NFPA 70, GROUND EXPOSED, NON CURRENT
CARRYING METALLIC PARTS OF ELECTRICAL EQUIPMENT, METALLIC
RACEWAY SYSTEMS, GROUNDING CONDUCTOR IN METALLIC
RACEWAYS.
21. FASTEN CONDUITS TO SHEET METAL BOXES AND CABINETS WITH TWO
LOCKNUTS WHERE REQUIRED BY NFPA 70, WHERE INSULATED
BUSHINGS ARE USED, AND WHERE BUSHINGS CANNOT BE BROUGHT
INTO FIRM CONTACT WITH THE BOX; OTHERWISE, USE MINIMUM
SINGLE LOCKNUT AND BUSHING. LOCKNUTS SHALL HAVE SHARP
EDGES FOR DIGGING INTO WALLS OF METAL ENCLOSURE. INSTALL
BUSHINGS ON ENDS OF CONDUITS, AND PROVIDE INSULATING TYPE
WHERE REQUIRED BY NFPA 70.
22. THE CORRIDOR AND MECHANICAL ROOM WALLS AND CEILING ARE FIRE
RATED. PENETRATIONS THROUGH THE WALLS SHALL BE A MINIMUM
OF 0.5" DIAMETER LARGER THAN THE CONDUIT REQUIRED TO
PENETRATE THE WALL. PROVIDE A FIRESTOP MATERIAL PER
REQUIREMENTS BELOW. CONDUIT THROUGH THE SLEEVE SHALL BE
GALVANIZED RIGID STEEL AND SHALL EXTEND A MINIMUM OF 18"
BEYOND THE SLEEVE OF BOTH SIDES.
23. PROVIDE AND INSTALL AT WALL OR FLOOR PENETRATIONS A
PERMANENT FIRESTOP SYSTEM. THE SYSTEM SHALL CONSIST OF A
WATERBASED FIRESTOP COMPOUND AS THE FILL, VOID, OR CAVITY
MATERIAL ALONG WITH APPROPRIATE DAMMING MATERIAL (AS PER
MANUFACTURER'S INSTRUCTIONS). THE FIRESTOP COMPOUND SHALL
NOT CONTAIN ANY SOLVENTS, INORGANIC FIBERS, OR SILICONE
COMPOUNDS AND SHALL NOT REQUIRE HEAT TO ACTIVATE THE SEAL.
THE FIRESTOP COMPOUND SHALL BE ONE-PART MATERIALS,
REQUIRING NO CRITICAL MIXING. THE PENETRATION SEAL MATERIAL
MUST BE UNAFFECTED BY MOISTURE AND MUST MAINTAIN THE
INTEGRITY OF THE FLOOR OR WALL ASSEMBLY FOR ITS RATED TIME
PERIOD WHEN TESTED IN ACCORDANCE WITH ASTM E84. THE SYSTEM
SHALL BE UL CLASSIFIED AND INSTALLED TO PROVIDE A 2 HOUR FIRE
RATING. THE PENETRATION FIRE STOP MATERIAL SHALL BE
FLAME-SAFE FS1900 SERIES COMPOUND AS MANUFACTURED BY
GRACE CONSTRUCTION PRODUCTS OR EQUAL.
A - AMPERE, AMPS
AFC - ABOVE FINISHED COUNTER
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
AHU - AIR HANDLING UNIT
AIC - AMPS INTERRUPTING CAPACITY
AUX - AUXILIARY
BFF - BELOW FINISHED FLOOR
BFG - BELOW FINISHED GRADE
BIL - BASIC INSULATION IMPULSE LEVEL
C, CDT - CONDUIT
CB - CIRCUIT BREAKER
CF - COMPACT FLUORESCENT
CFM - CUBIC FEET PER MINUTE
CKT - CIRCUIT
CLG - CEILING
CONC - CONCRETE
CONT - CONTINUED, CONTINUATION, CONTROL
CU - COPPER
DIA (�) - DIAMETER
DIM - DIMENSION
DISC - DISCONNECT
DN - DOWN
DWG - DRAWING
EA - EACH
EL - ELEVATION
ELEC - ELECTRIC
EMT - ELECTRICAL METALLIC TUBING
EOP - EDGE OF PAVEMENT
EXH - EXHAUST
FA - FIRE ALARM
FACP - FIRE ALARM CONTROL PANEL
FL - FLOOR
FLA - FULL LOAD AMPS
FLEX - FLEXIBLE
FT - FEET
GFI - GROUND FAULT INTERRUPTER
GND - GROUND
HDWR - HARDWARE
HORIZ - HORIZONTAL
HP - HORSEPOWER
HTR - HEATER
HWG - HEAVY WALL GALVANIZED CONDUIT
I - CURRENT
ID - INSIDE DIAMETER
IN - INCH, INCHES
kV, KV - KILOVOLTS
KW - KILOWATT
LB - POUND
LF - LINEAR FEET
LPS - LOW PRESSURE SODIUM
LV - LOW VOLTAGE
MCM - THOUSAND CIRCULAR MILS
MECH - MECHANICAL
MCP - MOTOR CIRCUIT PROTECTION
MH - MANHOLE
M.O. - MOTOR OPERATED
MPS - MANUAL PULL STATION
MTR - MOTOR
N/A - NOT APPLICABLE
NC - NORMALLY CLOSED
NIC - NOT IN CONTRACT
NO - NORMALLY OPEN
NTS - NOT TO SCALE
O2, 0 - OXYGEN
OA - OUTSIDE AIR
OC - ON CENTER
OD - OUTSIDE DIAMETER
OPP - OPPOSITE
OVHD - OVERHEAD
PB - PULL BOX, PUSH BUTTON
PL - PLACES
PNL - PANEL, PANELBOARD
PRESS - PRESSURE
PRV - POWERED ROOF VENT
PVC - POLYVINYL CHLORIDE
QTY - QUANTITY
R - RESISTANCE
REF - REFERENCE
RGS - RIGID GALVANIZED STEEL
RM - ROOM
SAN - SANITARY
SE - SERVICE ENTRANCE
SHT - SHEET
SIG - SIGNAL (INDICATING) CIRCUIT
SQ - SQUARE FOOT, SQUARE FEET
SS - STAINLESS STEEL
SW - SWITCH
SYS - SYSTEM
TEMP - TEMPERATURE
THK - THICK
TMCB - THERMAL MAGNETIC CIRCUIT BREAKER
TRANSF - TRANSFORMER
TTB - TELEPHONE TERMINAL BOARD
TYP - TYPICAL
UF - UNDER FLOOR
UG - UNDERGROUND
UON - UNLESS OTHERWISE NOTED
VERT - VERTICAL
W - WATT
W/ - WITH
W/O - WITHOUT
WH - WATER HEATER
WP - WEATHERPROOF
WTR - WATER
XFMR - TRANSFORMER