F46C602F Kokee State Park Electrical Improvements_Plans.pdf

PDF 7 MB Posted

Attached to
F46C602F Kokee State Park – Electrical Improvements
Solicitation number
B26002691
Issued by
Kauai County, Hawaii

About this file

This is a set of electrical construction plans and specifications for the Kokee State Park Electrical Improvements project (Job No. F46C602F) prepared by the State of Hawaii Department of Land and Natural Resources Engineering Division for the Division of State Parks in Waimea, Kauai. The project scope encompasses installing new electrical services and feeders to existing buildings, demolition of outdated electrical systems, electrical reconnection of existing loads, and related work across multiple facilities including garages, storage areas, workshop, ranger's cottage, and park headquarters. The plans consist of 21 sheets detailing construction notes, electrical symbols and abbreviations, site plans, demolition plans, new electrical plans, metering elevations, equipment elevations, exterior electrical details, and one-line diagrams. The project involves three meter installations (Meters A, B, and C) serving different building groups, with new loadcenters and service equipment to replace existing systems. Work includes underground and aerial conduit installation, junction boxes, weatherhead installations, grounding systems, and restoration of disturbed areas including landscaping and concrete patching.

The construction plans specify that all exterior equipment must be stainless steel NEMA 4X enclosures suitable for wet locations, with exposed exterior conduits being PVC-coated galvanized rigid steel or stainless steel. Contractors are required to verify all existing conditions through a pre-bid site visit, become familiar with existing electrical configurations, and resolve any discrepancies with the contracting officer before commencing work. The utility provider, Kauai Island Utility Cooperative (KIUC), is responsible for removing existing aerial service lines, installing new transformers (25 kVA units and one 15 kVA unit), and installing service conductors to new meter sockets. The contractor must restore all damaged facilities to original condition or better, maintain seeded grass areas for 90 days following installation, and comply with National Electrical Code standards, seismic requirements, and environmental protection measures including erosion control and water pollution prevention. All penetrations through exterior walls and roofs must be sealed weather-tight, and conduit entries must be vapor-sealed to prevent moisture migration into electrical panels and sealed to prevent pest intrusion.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DESCRIPTION DRAWING NO. SHEET NO.

TITLE SHEET T-001 1

CONSTRUCTION NOTES - 1 G-001 2

CONSTRUCTION NOTES - 2 G-002 3

ELECTRICAL SYMBOLS, ABBREV, AND NOTES E-001 4

STUDY OVERALL SITE PLAN E-101 5

ELECTRICAL DEMO PLAN A (GARAGES AND STORAGE) E-102 6

ELECTRICAL DEMO PLAN B (WORKSHOP AND RANGER'S COTTAGE) E-103 7

ELECTRICAL DEMO PLAN C (PARK HEADQUARTERS) E-104 8

ELECTRICAL PLAN A (GARAGES AND STORAGE) E-105 9

ELECTRICAL PLAN B (WORKSHOP AND RANGER'S COTTAGE) E-106 10

ELECTRICAL PLAN C (PARK HEADQUARTERS) E-107 11

METERING ELEVATIONS - 1 E-201 12

METERING ELEVATIONS - 2 E-202 13

RANGER'S COTTAGE ELEVATIONS E-203 14

PARK HEADQUARTERS ELEVATIONS E-204 15

EXTERIOR ELECTRICAL DETAILS E-501 16

ONE-LINE DIAGRAM - (METERS A, B AND C) - DEMO E-601 17

ONE-LINE DIAGRAM - PARK HEADQUARTERS E-602 18

ONE-LINE DIAGRAM - MAINT SHED-SHED-KOKEE LODGE STORAGE - DEMO E-603 19

ONE-LINE DIAGRAM - MAINT SHED-SHED-KOKEE LODGE STORAGE E-604 20

PANEL SCHEDULES E-701 21

KOKE`E ROAD

HAWAII ROUTE 550

KAUMUALII HIGHWAY

HAWAII ROUTE 50

PROJECT SITE

STATE OF HAWAII

ENGINEERING DIVISION

DEPARTMENT OF LAND AND NATURAL RESOURCES

FOR

DIVISION OF STATE PARKS

JOB NO. F46C602F

WAIMEA, KAUAI, HAWAII

TMK: (4th Division) 1-4-001:013

APPROVED: DATE:

ALAN B. CARPENTER

ACTING ADMINISTRATOR

DIVISION OF STATE PARKS

DEPARTMENT OF LAND AND NATURAL RESOURCES

DINA U. LAU, P.E.

ACTING CHIEF ENGINEER

ENGINEERING DIVISION

DEPARTMENT OF LAND AND NATURAL RESOURCES

APPROVED: DATE:

KOKE`E STATE PARK

ELECTRICAL IMPROVEMENTS

DRAWING NO.

T-001

SHEET NO. OF SHEETS21JOB NO. F46C602F

PROJECT SITE

ELECTRICAL

IMPROVEMENTS

VARIOUS LOCATIONS

KOKE`E STATE PARK

INDEX

05/07/2026

05/07/2026 https://stateofhawaii.na1.adobesign.com/verifier?tx=CBJCHBCAABAAp1ejQktrSu8p5YSKAKt_I4DGPDU6l-N9

SHT./OFDESCRIPTIONSYM.

REVISION

NO.

DATE APPROVED

DESIGNED:

DRAWN:

CHECKED:

APPROVED:

SUBMITTED:

DATE:

SCALE:

DRAWING NO.

DATECHIEF ENGINEER

SHEET NO. OF SHEETS

KOKE'E STATE PARK

ELECTRICAL IMPROVEMENTS

21JOB NO. F46C602F

AA

JT

JTM

APRIL 2026

AS SHOWN

WAIMEA, KAUAI, HAWAII

STATE OF HAWAII

DEPARTMENT OF LAND AND NATURAL RESOURCES

ENGINEERING DIVISION

FUKUNAGA AND ASSOCIATES, INC

GENERAL CONSTRUCTION NOTES

EROSION CONTROL / BMP NOTES

GENERAL CONSTRUCTION NOTES (Cont.)

REQUIREMENTS OF STATE HISTORIC

PESERVATION DIVISION

G-001

CONSTRUCTION NOTES - 1

'LQD�/DX

(�VLJQHG�����������������$0�+67

GLQD�X�ODX#KDZDLL�JRY

6WDWH�RI�+DZDLL

&LYLO�(QJLQHHU

PERMANENT EROSION CONTROL MEASURES

TEMPORARY EROSION CONTROL MEASURES

ENVIRONMENTAL PROTECTION NOTES

TEMPORARY DUST CONTROL

TOPOGRAPHIC SURVEY NOTES

SHT./OFDESCRIPTIONSYM.

REVISION

NO.

DATE APPROVED

DESIGNED:

DRAWN:

CHECKED:

APPROVED:

SUBMITTED:

DATE:

SCALE:

DRAWING NO.

DATECHIEF ENGINEER

SHEET NO. OF SHEETS

KOKE'E STATE PARK

ELECTRICAL IMPROVEMENTS

21JOB NO. F46C602F

AA

JT

JTM

APRIL 2026

AS SHOWN

WAIMEA, KAUAI, HAWAII

STATE OF HAWAII

DEPARTMENT OF LAND AND NATURAL RESOURCES

ENGINEERING DIVISION

FUKUNAGA AND ASSOCIATES, INC

WATER POLLUTION AND EROSION CONTROL NOTES

CONSTRUCTION NOTES - 2

G-002

WATER POLLUTION AND EROSION

CONTROL NOTES (Cont.)

WATER POLLUTION AND EROSION

CONTROL NOTES (Cont.)

'LQD�/DX

(�VLJQHG�����������������$0�+67

GLQD�X�ODX#KDZDLL�JRY

6WDWH�RI�+DZDLL

&LYLO�(QJLQHHU

SMALL JUNCTION (OUTLET) BOX

ENCLOSED CIRCUIT BREAKER, +5'-6" TO TOP UON

ELECTRICAL SYMBOLS

LARGE JUNCTION BOX, SIZE AS INDICATED

LARGE JUNCTION BOX, WALL MOUNTED, SIZE AS INDICATED

SMALL JUNCTION (OUTLET) BOX, WALL MOUNTED

ANY CIRCUIT WITH NO FURTHER DESIGNATION INDICATES A

TWO (2) WIRE CIRCUIT. CIRCUITS WITH ADDITIONAL WIRES ARE

INDICATED AS FOLLOWS: 3 WIRES, 4 WIRES,

ETC. MINIMUM CONDUCTOR SIZE MUST BE #12. ALTHOUGH NOT

INDICATED A SEPARATE GREEN GROUND CONDUCTOR SIZED

PER THE N.E.C. SHALL BE INSTALLED IN ALL BRANCH CIRCUIT

CONDUITS.

1. THE DRAWINGS DO NOT REFLECT ALL THE EXISTING CONDITIONS THAT

MAY BE ENCOUNTERED DURING CONSTRUCTION. VISIT THE PROJECT

SITE AND BECOME FAMILIAR WITH THE EXISTING CONDITIONS, THE

EXTENT OF ANY DEMOLITION WORK, AND THE NEW WORK PRIOR TO THE

START OF ON-SITE CONSTRUCTION ACTIVITIES. REPORT ANY

DISCREPANCIES AND/OR DIFFERENCES BETWEEN THE EXISTING

CONDITIONS AND THE CONSTRUCTION DOCUMENTS TO THE

CONTRACTING OFFICER PRIOR TO COMMENCING CONSTRUCTION.

RESOLVE ALL DISCREPANCIES AND QUESTIONS PRIOR TO THE START OF

WORK.

2. EXISTING DEVICE LOCATIONS, CIRCUIT ASSIGNMENTS, WIRING

CONNECTIONS, AND CONDUIT RUNS INDICATED WERE DERIVED FROM

LIMITED FIELD INVESTIGATION. FIELD VERIFY ALL EXISTING CONDITIONS

AND MAKE ANY NECESSARY ADJUSTMENTS TO SATISFY THE INTENT OF

THE DRAWINGS AND SPECIFICATIONS.

3. OBTAIN ALL STANDARDS AND DRAWINGS RELATED TO THIS PROJECT

FROM THE UTILITY COMPANIES. VERIFY THAT THE UTILITY COMPANY'S

PROJECT DRAWINGS ARE THE SAME AS THE CONTRACT DRAWINGS.

NOTIFY THE ENGINEER OF ANY DIFFERENCES BETWEEN THEM. IF

DIFFERENCES EXIST, OBTAIN A RESOLUTION PRIOR TO PROCEEDING

WITH THE WORK WHICH IS AFFECTED.

4. VERIFY AND CHECK ALL DIMENSIONS AND DETAILS ON THE

CONSTRUCTION DRAWINGS AND SPECIFICATIONS FOR ANY

DISCREPANCY. ANY DISCREPANCY MUST BE BROUGHT TO THE

ATTENTION OF THE CONTRACTING OFFICER FOR CLARIFICATION.

5. WORK INCIDENTAL TO THE CONTRACT AND NECESSARY TO COMPLETE

THE PROJECT, ALTHOUGH NOT SPECIFICALLY REFERRED TO ON THE

CONTRACT DOCUMENTS, MUST BE FURNISHED AND PERFORMED BY THE

CONTRACTOR.

6. THE UNDERGROUND PIPES, CABLES OR DUCTLINES KNOWN TO EXIST BY

THE ENGINEER FROM HIS SEARCH OF RECORDS ARE INDICATED ON THE

PLANS. LOCATION OF EXISTING UTILITY LINES SHOWN ON THE PLANS

ARE APPROXIMATE. THEREFORE, NO ASSURANCE CAN BE PROVIDED

THAT THE ACTUAL LOCATIONS WILL BE PRECISELY AS SHOWN ON THE

CONTRACT DOCUMENTS. THE CONTRACTOR MUST VERIFY THE

LOCATION AND DEPTH OF THE UTILITIES AND EXERCISE PROPER CARE IN

EXCAVATING IN THE AREA. WHEREVER CONNECTIONS OF NEW UTILITIES

TO EXISTING UTILITIES ARE SHOWN ON THE PLANS, THE CONTRACTOR

MUST EXPOSE THE EXISTING LINES AT THE PROPOSED CONNECTIONS

TO VERIFY THEIR LOCATIONS.

7. THE DEMOLITION DRAWINGS ARE INTENDED TO SHOW THE GENERAL

LIMITS OF THE WORK AND DO NOT SHOW ALL THE EXISTING APPARATUS,

DEVICES, LIGHT FIXTURES, EQUIPMENT CONNECTIONS, CONDUIT RUNS,

ETC. DISCONNECT AND REMOVE THE ELECTRICAL APPARATUS, DEVICES,

LIGHT FIXTURES, ETC. AND CONDUIT AND WIRING BACK TO ITS SOURCE.

EXISTING CONCEALED WIRING TO BE REMOVED MUST BE

DISCONNECTED FROM ITS SOURCE. CONDUITS EMERGING OUT OF THE

FLOOR MUST BE CUT FLUSH WITH FLOOR AND HAVE THEIR OPENINGS

SEALED.

8. REMOVAL OF EXISTING ELECTRICAL DISTRIBUTION SYSTEM: REMOVAL

OF EXISTING ELECTRICAL DISTRIBUTION SYSTEM EQUIPMENT MUST

INCLUDE EQUIPMENT'S ASSOCIATED WIRING INCLUDING CONDUCTORS,

CABLES, EXPOSED CONDUIT, SURFACE METAL RACEWAYS, BOXES,

FITTINGS, ETC. BACK TO EQUIPMENT'S SOURCE. UNDERGROUND

CONDUITS/DUCTS NO LONGER NEEDED MAY BE ABANDONED IN PLACE.

9. RE-ROUTE ALL EXISTING CONDUIT, WIRING AND CABLING TO REMAIN

WITHIN THE PROJECT AREA AS NECESSARY TO FACILITATE THE

REMOVAL OF EXISTING EQUIPMENT AS WELL AS THE INSTALLATION OF

ALL NEW EQUIPMENT.

10. THE LOCATION OF ALL ELECTRICAL APPARATUS AND DEVICES ARE

APPROXIMATE AND BEFORE INSTALLING, STUDY THE ARCHITECTURAL,

STRUCTURAL, AND MECHANICAL DETAILS AND MAKE INSTALLATION IN

THE MOST LOGICAL MANNER. ANY PIECE OF EQUIPMENT/DEVICE MAY BE

RELOCATED WITHIN 10' BEFORE INSTALLATION AT THE DIRECTION OF

THE ENGINEER WITHOUT ADDITIONAL CHARGE TO THE OWNER.

GENERAL NOTES:

WHM

LARGE JUNCTION BOX, WALL MOUNTED, SIZE AS INDICATED

ONE-LINE SYMBOLS

SITE ELECTRICAL SYMBOLS

DUCT DESIGNATION

2 S 4 A

2 S 4 A

E-501 A

E-501 E

DUCT SECTION "A" SEE DUCT SECTION DETAILS,

SEE AND

DUPLEX RECEPTACLE WITH GFCI PROTECTION, NEMA 5-20R,

125V, +18" AFF UON

J

J

J

J

SINGLE POLE SWITCH, 20A, 120/277V - 3=3 WAY, 4=4 WAY,

D=DIMMER

11. ALL OPENINGS RESULTING FROM REMOVAL WORK AND NOT REUSED MUST

BE SEALED.

12. ALL DISCONNECT SWITCHES MUST HAVE THE PANELBOARD AND CIRCUIT

NUMBER IDENTIFIED ON THE ENCLOSURE. PROVIDE POLYESTER TYPE

LABLES THAT ARE RESISTANT TO MOISTURE, EXTREME TEMPERATURES,

CHEMICALS, FADING, AND UV LIGHT. LETTERS MUST NOT BE LESS THAN

0.75” HIGH.

13. DO NOT INSTALL DISSIMILAR METALS IN DIRECT CONTACT WITH EACH

OTHER TO PREVENT GALVANIC CORROSION. PROVIDE APPROPRIATE

BARRIERS.

14. PAINTING OF ELECTRICAL EQUIPMENT:

a. INTERIOR LOCATIONS - PRIME AND PAINT ALL EXPOSED CONDUITS, BOXES, FITTINGS, SUPPORT CHANNELS, MOUNTING HARDWARE AND

ACCESSORIES WITH TWO FINISH COATS TO MATCH THE SURFACE ON

WHICH THEY ARE MOUNTED OR TO MATCH THE FINISH OF THE

ADJACENT SURFACES. EQUIPMENT SURFACES/COMPONENTS WITH A

FACTORY-APPLIED PAINT FINISH NEED NOT BE PAINTED.

b. EXTERIOR LOCATIONS - PRIME ALL EXPOSED CONDUITS, BOXES, FITTINGS, SUPPORT CHANNELS, MOUNTING HARDWARE AND

ACCESSORIES WITH A 2-PART EPOXY PRIMER AND FINISH WITH 2

COATS OF AN ALIPHATIC ACRYLIC URETHANE PAINT. PAINT FINISH TO

MATCH THE SURFACE ON WHICH THEY ARE MOUNTED OR TO MATCH

THE FINISH OF THE ADJACENT SURFACES. STAINLESS STEEL

MATERIALS NEED NOT BE PAINTED.

15. THE CONTRACTOR MUST PROVIDE ADEQUATE, NON-SKID BRIDGING

MATERIAL OVER TRENCHES, INCLUDING SHORING WHEN TRENCHING IN

PAVEMENT AREAS TO HANDLE ALL TYPES OF VEHICULAR AND PEDESTRIAN

TRAFFIC. NO TRENCH MUST BE LEFT OPEN DURING NON-WORKING HOURS

OR JOB SHUTDOWN.

16. ALL EXTERIOR EQUIPMENT: JUNCTION BOXES AND DISCONNECT SWITCHES,

MUST BE STAINLESS STEEL, NEMA 4X.

17. THE CONDUIT LOCATIONS INDICATED ARE SCHEMATIC. RELOCATE JUNCTION

BOXES AS NECESSARY TO FACILITATE THE CONDUIT INSTALLATION AT NO

ADDITIONAL COST TO THE GOVERNMENT. JUNCTION BOXES MUST REMAIN

ACCESSIBLE PER NFPA 70.

18. ELECTRICAL APPARATUS AND INSTALLATION MUST BE SUITABLE FOR THE

SEISMIC CATEGORY FOR THE ISLAND PER THE BUILDING CODE.

19. ALL PENETRATIONS THROUGH EXTERIOR WALLS AND ROOFS MUST BE

SEALED WEATHER-TIGHT WITH UL APPROVED MATERIALS AND METHODS

AND IN ACCORDANCE WITH THE IBC.

20. ALL CONDUITS ENTERING PANELS FROM THE EXTERIOR MUST BE VAPOR

SEALED/DUCT SEALED TO PREVENT WATER VAPOR AND MOISTURE FROM

MIGRATING INTO PANELS.

21. SEAL ALL CONDUITS ENTERING JUNCTION BOXES, ENCLOSURES,

PANELBOARDS, SWITCHBOARDS, ETC. TO PREVENT INSECTS/PESTS FROM

MIGRATING THROUGH THE ELECTRICAL DISTRIBUTION SYSTEM.

22. ALL RECEPTACLES, SWITCHES, AND DISCONNECT SWITCHES MUST HAVE

THE PANELBOARD AND CIRCUIT NUMBER IDENTIFIED ON THE DEVICE PLATE.

PROVIDE INDUSTRIAL ADHESIVE VINYL OR POLYESTER TYPE LABELS THAT

ARE RESISTANT TO MOISTURE, EXTREME TEMPERATURES, CHEMICALS, AND

UV LIGHT ON THE DEVICE PLATE. LETTERS MUST BE NOT LESS THAN 1/4"

HIGH. PRESSURE SENSITIVE OR THERMAL TAPES NOT ALLOWED.

23. EXPOSED EXTERIOR CONDUITS SHALL BE PVC COATED GALVANIZED RIGID

STEEL, STAINLESS STEEL, OR FIBERGLASS WITH A PROTECTIVE UV

COATING.

24. THE CONTRACTOR, AT THEIR EXPENSE, MUST RESTORE TO THE ORIGINAL

CONDITION OR BETTER ALL EXISTING FACILITIES TO REMAIN THAT ARE

DAMAGED AS A RESULT OF CONSTRUCTION.

25. REPAIR AND PAINT ALL SURFACES DAMAGED BY NEW CONSTRUCTION OR

EXPOSED/DAMAGED DUE TO REMOVAL OF EXISTING EQUIPMENT. COLOR TO

MATCH ADJACENT SURFACES.

26. CONTRACTOR MUST TONE AREA PRIOR TO DIGGING. ANY DAMAGE TO

EXISTING UNDERGROUND UTILITIES TO REMAIN RESULTING FROM FAILURE

TO DO SO MUST BE REPAIRED BY THE CONTRACTOR AT NO ADDITIONAL

COST TO THE PROJECT.

27. THE CONTRACTOR SHALL VISIT THE PROJECT SITE AND FAMILIARIZE

HIMSELF/HERSELF WITH ALL EXISTING CONDITIONS AND THE EXTENT OF

THE REMOVAL, RECONNECTION, AND NEW WORK PRIOR TO BIDDING. BID

SUBMISSION SHALL BE CONSIDERED AS EVIDENCE THAT THE CONTRACTOR

HAS VISITED THE SITE AND RESOLVED ALL DISCREPANCIES AND QUESTIONS

AND NO EXTRA PAYMENT WILL BE AUTHORIZED FOR WORK REQUIRED BY

THE CONTRACTOR'S FAILURE TO DO SO.

28. THE CONTRACTOR MUST REGRASS AND LANDSCAPE ALL UNPAVED AREAS

DISTURBED BY CONSTRUCTION ACTIVITIES. AREAS MUST BE RESTORED

WITH GRASS SEEDING, SPRIGS OR TURF. THE GRASS MUST BE PLANTED,

FERTILIZED, WATERED AND MAINTAINED BY THE CONTRACTOR FOR 90 DAYS

OR UNTIL THE GRASS IS FULLY ESTABLISHED.

NM

WEATHERPROOF

UNLESS OTHERWISE NOTED

CONDUIT UP

CONDUIT DOWN

CONDUIT & WIRING IN WALL OR CEILING

CONDUIT & WIRING BELOW REFERENCED PLANE

CONDUIT & WIRING EXPOSED

HOMERUN TO APPLICABLE PANEL

CONDUIT STUB

FLEXIBLE CONDUIT

WP

UON

MINIMUM CONDUIT SIZE SHALL BE 3/4".

EXISTING WOOD POLE

GUY ANCHOR

DUCT SECTION INDICATOR

UNDERGROUND DUCTLINE

TYPE NM WIRING

GROUND CONNECTION

WATT-HOUR METER

TRANSFORMER

SAFETY SWITCH - NON FUSED

MOLDED CASE CIRCUIT BREAKER

PANELBOARD

LIGHT FIXTURE, CEILING MOUNTED

LED STRIP FIXTURE, SURFACE CEILING MOUNTED

PANELBOARD

SYSTEM

CONDUIT SIZE

NUMBER OF DUCTS

"S" SECONDARY ELECTRIC (NORMAL)

SPD SURGE PROTECTIVE DEVICE

PLUS+

AND

ABOVEABV

ALTERNATING CURRENTAC

A,AMPS

AMPERES

AT

NUMBER

ABBREVIATIONS

ADDITIONALADDT'L

L LENGTH

W WIDTH

W WATT

KCMIL KILO CIRCULAR MILS

IN INCH

I.E. THAT IS

EXISTINGEXIST

EQPT EQUIPMENT

DWGS DRAWINGS

CIRCUITSCKTS

AFG ABOVE FINISHED GRADE

TEMPORARYTEMP

DRY-TYPE

MOUNTINGMTG

EQUIPMENTEQUIP

ELEV ELEVATION

DISCONNECTDISC

FEEDERFDR

CLG CEILING

ADJACENTADJ

UNLESS OTHERWISE NOTEDUON

PFB

PH

MISCELLANEOUSMISC

LIGHTINGLTG

JUNCTION BOXJB

HEIGHTH

GFCI

G,GND GROUND

GALVANIZEDGALV

FOOT/FEETFT

EXHAUSTEXH

ELECTRICAL METALLIC TUBINGEMT

EA EACH

DT

CIRCUIT BREAKERCB

ABOVE FINISHED FLOORAFF

VOLT-AMPEREVA

PANELPNL

NATIONAL ELECTRICAL CODENEC

AMPERES INTERRUPTING CAPACITYAIC

KILOWATT

KILO-VOLT-AMPERE

KILO-VOLTS

KW

KVA

KV

IC

PHASE

DRAWINGDWG

TRANSFORMER

WEATHER-PROOF

VOLT

TYPICAL

NEMA TYPE 4X ENCLOSURE

NEMA TYPE 3R ENCLOSURE

NEMA TYPE 1 ENCLOSURE

XFMR

WP

V

TYP

N4X N3R N1

MOUNTED

MOUNT

MINIMUM

MTD

MT

MIN

EXST

ENCL

ELEC

CKT

C

BLDG

BKR

EXISTING

ENCLOSURE

ELECTRICAL

CIRCUIT

CONDUIT

BUILDING

BREAKER

GROUND FAULT CIRCUIT

INTERRUPTER

PROVISION FOR FUTURE

CIRCUIT BREAKER

BRANCH CIRCUIT WIRING GENERAL NOTE:

1. DO NOT USE A COMMON NEUTRAL FOR MULTI-WIRE BRANCH CIRCUITS. PROVIDE

A DEDICATED NEUTRAL FOR EACH CIRCUIT.

DEEPDP

DOWNDN

GALVANIZED RIGID CONDUITGRC

NUMBERNO.

SWITCHSW

POLYVINYL CHLORIDEPVC

SQUARESQ

INFO INFORMATION

KIUC KAUAI ISLAND UTILITY

COOPERATIVE

SECONDARYSEC

INTERRUPTING

CAPACITY

SHT./OFDESCRIPTIONSYM.

REVISION

NO.

DATE APPROVED

DESIGNED:

DRAWN:

CHECKED:

APPROVED:

SUBMITTED:

DATE:

SCALE:

DRAWING NO.

DATECHIEF ENGINEER

SHEET NO. OF SHEETS

KOKE'E STATE PARK

ELECTRICAL IMPROVEMENTS

21JOB NO. F46C602F

ACH

MKE

ACH

APRIL 2026

AS SHOWN

WAIMEA, KAUAI, HAWAII

STATE OF HAWAII

DEPARTMENT OF LAND AND NATURAL RESOURCES

ENGINEERING DIVISION

FUKUNAGA AND ASSOCIATES, INC

E-001

ELECTRICAL SYMBOLS, ABBREV, AND NOTES

C :\U se rs

\d ey n\ O ne D riv e

- M K

En gi ne er s Lt d\ f_ C

AD

_2

4-

D oc um en ts

\2

4\

2_

Ko ke eS ta te Pk

_E le cS vc

M od s\

_d w g\

2_

E0

_s ym

.d w g, L ay ou t1 , 5

/1 /2

:5

0:

A M

, d ey n, :1

'LQD�/DX

(�VLJQHG�����������������$0�+67

GLQD�X�ODX#KDZDLL�JRY

6WDWH�RI�+DZDLL

&LYLO�(QJLQHHU

MULTICORELINK:24002_E501_ExtElecDet-Layout1 MULTICOREVIEWLINK:Layout1,TYPICAL DUCT SECTION (CONCRETE ENCASED)(2) MULTICORELINK:24002_E501_ExtElecDet-Layout1 MULTICOREVIEWLINK:Layout1,UNDERGROUND TO EXPOSED TRANSITION DETAIL(2)

"METER" BUILDING

GARAGE 1

GARAGE 2

WORKSHOP

RANGER'S COTTAGE

STORAGE

KOKEE LODGE

RESTAURANT

PARK

HEADQUARTERS

J

J

SHT./OFDESCRIPTIONSYM.

REVISION

NO.

DATE APPROVED

DESIGNED:

DRAWN:

CHECKED:

APPROVED:

SUBMITTED:

DATE:

SCALE:

DRAWING NO.

DATECHIEF ENGINEER

SHEET NO. OF SHEETS

KOKE'E STATE PARK

ELECTRICAL IMPROVEMENTS

21JOB NO. F46C602F

ACH

MKE

ACH

APRIL 2026

AS SHOWN

WAIMEA, KAUAI, HAWAII

STATE OF HAWAII

DEPARTMENT OF LAND AND NATURAL RESOURCES

ENGINEERING DIVISION

FUKUNAGA AND ASSOCIATES, INC

PAVILION/RESTROOMS

FOR ENLARGED PLAN,

SEE SHEET E-107

FOR ENLARGED PLANS,

SEE SHEETS ANDE-103 E-106

FOR ENLARGED PLANS,

SEE SHEETS ANDE-102 E-105

FOR ENLARGED PLAN,

SEE SHEET E-104

1 SCALE: 1" = 10'-0"

OVERALL SITE PLAN

0 80' 160'

1" = 80'

PLAN

NORTH

E-101

STUDY OVERALL SITE PLAN

C :\U se rs

\d ey n\ O ne D riv e

- M K

En gi ne er s Lt d\ f_ C

AD

_2

4-

D oc um en ts

\2

4\

2_

Ko ke eS ta te Pk

_E le cS vc

M od s\

_d w g\

2_

E1

_s ite

.d w g, la yo ut

1, /1 /2

:5

0:

A M

, d ey n, :1

'LQD�/DX

(�VLJQHG�����������������$0�+67

GLQD�X�ODX#KDZDLL�JRY

6WDWH�RI�+DZDLL

&LYLO�(QJLQHHU

POLE

KED 105-440-9701

AERIAL SECONDARY

TRIPLEX TO POLE #1

SPLICE

TO THE METAL STRUCTURE

3 WIRE

(KIUC SEC)

AERIAL

(TO BE REMOVED BY KIUC)

PANEL "A"

PANEL "A"

CKTS 1,3

UNDERGROUND 2"C TO METER MAIN

OVERHEAD AERIAL TRIPLEX

PANEL "A"

CIRCUIT 8,10 SPLICE IN

PANEL "MS" TO FEED

RANGER'S CABIN FEED

THROUGH

PANEL "MS"

SERVICE

ENTRANCE CABLE

ROMEX CABLE

(MS-8)

JUNCTION BOX

(NEAR CEILING)

2"C UNDERGROUND, THEN EXPOSED,

PANEL "A"

CKTS 2,4,6

CKTS 8,10

SINGLE CONDUCTOR

2 EACH (MS-2)

PANEL "A"

CKTS 5,7

2 WIRES

PANEL "A"

CKTS 5,7

3 WIRES

4 WIRE KIUC SEC

(TO BE REMOVED BY KIUC)

4 WIRE

(KIUC SEC) AERIAL

(TO BE REMOVED BY KIUC)

4 WIRES

TELECOM

GAS HOUSESHED 2

SHED 1

STORAGE

GARAGE 2

GARAGE 1

P.13

P.1

P.2

P.14

P.15

METAL STRUCTURE

METER "C"

KIUC #B0220199

(CCC CAMP)

"METER" BUILDING

METER "B"

KIUC #G0710947

(GARAGE 1/GARAGE 2,

STORAGE, WORKSHOP,

RANGER'S COTTAGE,

CCC CAMP)

2"C

BASEYARD BUILDING

J

J

METER "A"

KIUC #G0710945

(LODGE/ RESTAURANT)

4 WIRE (KIUC SEC)

AERIAL (TO BE REMOVED

BY KIUC)

STATE OWNED POLE

SEE FOR TOOL STORAGE

ROOM ENLARGED PLAN

E-102

TOOL STORAGE ROOM

J J

N M aNM

NM NM

UP TO FLOOD LIGHT

MS-17

(FOR FLOODLIGHT)

MS-4

4a 4a

MC CABLES

IN CABINET

SHT./OFDESCRIPTIONSYM.

REVISION

NO.

DATE APPROVED

DESIGNED:

DRAWN:

CHECKED:

APPROVED:

SUBMITTED:

DATE:

SCALE:

DRAWING NO.

DATECHIEF ENGINEER

SHEET NO. OF SHEETS

KOKE'E STATE PARK

ELECTRICAL IMPROVEMENTS

21JOB NO. F46C602F

ACH

MKE

ACH

APRIL 2026

AS SHOWN

WAIMEA, KAUAI, HAWAII

STATE OF HAWAII

DEPARTMENT OF LAND AND NATURAL RESOURCES

ENGINEERING DIVISION

FUKUNAGA AND ASSOCIATES, INC

1 SCALE: 1" = 10'-0"

ELECTRICAL DEMO PLAN A (GARAGES AND STORAGE)

0 10' 20'

1" = 10'

PLAN

NORTH

LIGHT LINES DENOTE EXISTING CONDITION

"/" DENOTES REMOVAL WORK

1.

NOTES:

INTERCEPT EXISTING CONDUIT AND CONDUCTORS WITH NEW WIREWAY.

R "R" DENOTES REMOVAL OF EXISTING CONDUCTORS FROM EXISTING CONDUIT. CONDUIT TO BE REUSED.

MATCHLINE, SEE SHEET E-103

M

AT

C H

LI

N

E, S

EE

S

H

EE

T E-

E-102

ELECTRICAL DEMO PLAN A (GARAGES AND

STORAGE)

3. CONTRACTOR IS RESPONSIBLE FOR DISPOSAL OF ITEMS TO BE REMOVED. FOR

UNDERGROUND/BURIED CONDUIT/DUCT, REMOVE CONDUCTORS AND ABANDON

CONDUIT/DUCT IN PLACE.

PLAN

NORTH

0 4' 8'2'

1/4" = 1'

TOOL STORAGE ROOM ENLARGED

DEMOLITION PLAN

SCALE: 1/4" = 1'-0"

LIGHT LINES DENOTE EXISTING CONDITION

"/" DENOTES REMOVAL WORK

1.

NOTES:

C :\U se rs

\d ey n\ O ne D riv e

- M K

En gi ne er s Lt d\ f_ C

AD

_2

4-

D oc um en ts

\2

4\

2_

Ko ke eS ta te Pk

_E le cS vc

M od s\

_d w g\

2_

E1

_s ite

El ec

D em oA .d w g, L ay ou t1

, 5 /1

/2

:5 0:

A

M , d ey n, :1

'LQD�/DX

(�VLJQHG�����������������$0�+67

GLQD�X�ODX#KDZDLL�JRY

6WDWH�RI�+DZDLL

&LYLO�(QJLQHHU

POLE

KED 105-440-9701

OVERHEAD AERIAL TRIPLEX

LOADCENTER. CONVERT TO JB

PANEL "A"

CIRCUIT 8,10 SPLICE IN

PANEL "MS" TO FEED

RANGER'S CABIN FEED

THROUGH

PANEL "MS"

SERVICE

ENTRANCE CABLE

OVERHEAD AERIAL TRIPLEX

PANEL "A"

CKTS 8,10

ROMEX CABLE

(MS-8)

JUNCTION BOX

(NEAR CEILING)

2 EACH (MS-2)

CONDUCTORS CUT ON POLE

3-25KVA KIUC XFMRS

4 WIRE KIUC SEC

(TO BE REMOVED BY KIUC)

TELECOM

SHED 1

STORAGE

GARAGE 2

WORKSHOP

RANGER'S COTTAGE

P.13

P.14

P.15

POLE

KED 105-440 0703

P.16

LOADCENTER "A"

J

J STATE OWNED POLE

E-203

SHT./OFDESCRIPTIONSYM.

REVISION

NO.

DATE APPROVED

DESIGNED:

DRAWN:

CHECKED:

APPROVED:

SUBMITTED:

DATE:

SCALE:

DRAWING NO.

DATECHIEF ENGINEER

SHEET NO. OF SHEETS

KOKE'E STATE PARK

ELECTRICAL IMPROVEMENTS

21JOB NO. F46C602F

ACH

MKE

ACH

APRIL 2026

AS SHOWN

WAIMEA, KAUAI, HAWAII

STATE OF HAWAII

DEPARTMENT OF LAND AND NATURAL RESOURCES

ENGINEERING DIVISION

FUKUNAGA AND ASSOCIATES, INC

1 SCALE: 1" = 10'-0"

ELECTRICAL DEMO PLAN B (WORKSHOP AND RANGER'S COTTAGE)

0 10' 20'

1" = 10'

PLAN

NORTH

LIGHT LINES DENOTE EXISTING CONDITION

"/" DENOTES REMOVAL WORK

1.

NOTES:

R "R" DENOTES REMOVAL OF EXISTING CONDUCTORS FROM EXISTING CONDUIT. CONDUIT TO BE REUSED.

MATCHLINE, SEE SHEET E-102

E-103

ELECTRICAL DEMO PLAN B (WORKSHOP AND

RANGER'S COTTAGE)

2. INTERCEPT EXISTING CONDUIT AND CONDUCTORS WITH NEW WIREWAY.

3. CONTRACTOR IS RESPONSIBLE FOR DISPOSAL OF ITEMS TO BE REMOVED.

C :\U se rs

\d ey n\ O ne D riv e

- M K

En gi ne er s Lt d\ f_ C

AD

_2

4-

D oc um en ts

\2

4\

2_

Ko ke eS ta te Pk

_E le cS vc

M od s\

_d w g\

2_

E1

_s ite

El ec

D em oB .d w g, L ay ou t1

, 5 /1

/2

:5 0:

A

M , d ey n, :1

'LQD�/DX

(�VLJQHG�����������������$0�+67

GLQD�X�ODX#KDZDLL�JRY

6WDWH�RI�+DZDLL

&LYLO�(QJLQHHU

MULTICORELINK:24002_E203_ElvRANGERS-CABIN-Layout1 MULTICOREVIEWLINK:Layout1,24002-E-601

PARK

HEADQUARTERS

3 WIRE

(KIUC SEC)

AERIAL

WEATHERHEAD

4 WIRES

TELECOM

TELECOM

TELECOM

P.3

P.4

4 WIRE

(KIUC SEC)

AERIAL

P.17

P.5

P.6

PANEL "A"

CKTS 5,7

2 WIRES

PANEL "A"

CKTS 5,7

2 WIRES

E-204

SHT./OFDESCRIPTIONSYM.

REVISION

NO.

DATE APPROVED

DESIGNED:

DRAWN:

CHECKED:

APPROVED:

SUBMITTED:

DATE:

SCALE:

DRAWING NO.

DATECHIEF ENGINEER

SHEET NO. OF SHEETS

KOKE'E STATE PARK

ELECTRICAL IMPROVEMENTS

21JOB NO. F46C602F

ACH

MKE

ACH

APRIL 2026

AS SHOWN

WAIMEA, KAUAI, HAWAII

STATE OF HAWAII

DEPARTMENT OF LAND AND NATURAL RESOURCES

ENGINEERING DIVISION

FUKUNAGA AND ASSOCIATES, INC

1 SCALE: 1" = 20'-0"

ELECTRICAL DEMO PLAN C (PARK HEADQUARTERS)

0 20' 40'10'

1" = 20'

PLAN

NORTH

NOTES:

LIGHT LINES DENOTE EXISTING CONDITION

"/" DENOTES REMOVAL WORK

1.

M

AT

C H

LI

N

E, S

EE

SH

EE

T

2. CONTRACTOR IS RESPONSIBLE FOR DISPOSAL OF ITEMS TO BE REMOVED.

E-104

ELECTRICAL DEMO PLAN C (PARK

HEADQUARTERS)

E-

C :\U se rs

\d ey n\ O ne D riv e

- M K

En gi ne er s Lt d\ f_ C

AD

_2

4-

D oc um en ts

\2

4\

2_

Ko ke eS ta te Pk

_E le cS vc

M od s\

_d w g\

2_

E1

_s ite

El ec

D em oC .d w g, L ay ou t1

, 5 /1

/2

:5 0:

A

M , d ey n, :1

'LQD�/DX

(�VLJQHG�����������������$0�+67

GLQD�X�ODX#KDZDLL�JRY

6WDWH�RI�+DZDLL

&LYLO�(QJLQHHU

MULTICORELINK:24002_E204_ElvPARK-HQ-Layout1 MULTICOREVIEWLINK:Layout1,PARK HQ EQUIPMENT ELEVATION - DEMO MULTICORELINK:24002_E102_siteElecDemoA-Layout1 MULTICORELINK:24002_E102_siteElecDemoA-Layout1

POLE KED

PANEL "A"

JUNCTION BOX

3-25KVA KIUC XFMRS

P.13

P.1

P.2

P.14

P.15

J

1 S 1.25 A

2"C

2"C

1-1/4"C

NEW METER SOCKET

PANEL BOARD "G1"

NEW LOADCENTER "STOR"

JUNCTION BOX

3P100A ENCLOSED CKT BKR

(LOCKABLE)

STOR-3

STOR-1

NEW KIUC AERIAL SERVICE DROP TO NEW

METER VIA WEATHERHEAD

12" x 12" x 4" DP

NEMA 4X JB

SAWCUT AND PATCH

CONCRETE TO INSTALL

CONDUIT

LB FITTING

G1-1

STOR-5

MTD

UNDER

LOADCENTER

4/0 QUAD CONDUCTOR TO

BE INSTALLED BY KIUC

WP

AERIAL SECONDARY

TRIPLEX TO POLE #1

SEE FOR TOOL STORAGE

ROOM ENLARGED PLAN

E-105

1 S 1.5 A

SPLICE

TO THE METAL STRUCTURE

3 WIRE

(KIUC SEC)

AERIAL

(TO BE REMOVED BY KIUC)

UNDERGROUND 2"C TO METER MAIN

PANEL "MS"

4 WIRE KIUC SEC

(TO BE REMOVED BY KIUC)

4 WIRE

(KIUC SEC) AERIAL

(TO BE REMOVED BY KIUC)

4 WIRES

TELECOM

GAS HOUSESHED 2

SHED 1

STORAGE

GARAGE 2

GARAGE 1

METER "C"

KIUC #B0220199

(CCC CAMP)

"METER" BUILDING

METER "B"

KIUC #G0710947

(GARAGE 1/GARAGE 2,

STORAGE, WORKSHOP,

RANGER'S COTTAGE,

CCC CAMP)

BASEYARD BUILDING

J

J

METER "A"

KIUC #G0710945

(LODGE/ RESTAURANT)

STATE OWNED POLE

TOOL STORAGE ROOM

J

UP TO FLOOD LIGHT

MC CABLES

J

G1-2,4

6" x 6" x 4"DP JB, WP

2a2a aJ

RECONNECT

TO EXISTING

MC CABLES

TO FLOOD LIGHT.

REPLACE LAMPS (2 EA)

TO MATCH EXISTING

IN CABINET

SHT./OFDESCRIPTIONSYM.

REVISION

NO.

DATE APPROVED

DESIGNED:

DRAWN:

CHECKED:

APPROVED:

SUBMITTED:

DATE:

SCALE:

DRAWING NO.

DATECHIEF ENGINEER

SHEET NO. OF SHEETS

KOKE'E STATE PARK

ELECTRICAL IMPROVEMENTS

21JOB NO. F46C602F

ACH

MKE

ACH

APRIL 2026

AS SHOWN

WAIMEA, KAUAI, HAWAII

STATE OF HAWAII

DEPARTMENT OF LAND AND NATURAL RESOURCES

ENGINEERING DIVISION

FUKUNAGA AND ASSOCIATES, INC

BOLD LINES DENOTE NEW WORK

1 SCALE: 1" = 10'-0"

ELECTRICAL PLAN A (GARAGES AND STORAGE)

0 10' 20'

1" = 10'

PLAN

NORTH

LIGHT LINES DENOTE EXISTING CONDITION1.

NOTES:

MATCHLINE, SEE SHEET

E-105

ELECTRICAL PLAN A (GARAGES AND

STORAGE)

PLAN

NORTH

0 4' 8'2'

1/4" = 1'

2 TOOL STORAGE ROOM ENLARGED PLAN

SCALE: 1/4" = 1'-0"

REPLACE EXISTING PARTICLE BOARD ON WALL WHERE LOADCENTER TO BE MOUNTED WITH PAINTED

TREATED PLYWOOD. PROVIDE ADDITIONAL BRACING AS REQUIRED.

PROVIDE NECESSARY SUPPORT TO MOUNT METER SOCKET. LEFT EDGE OF METER SOCKET

MUST NOT ENCROACH ON GARAGE OPENING.

BOLD LINES DENOTE NEW WORK

LIGHT LINES DENOTE EXISTING CONDITION1.

NOTES:

E-106

C :\U se rs

\d ey n\ O ne D riv e

- M K

En gi ne er s Lt d\ f_ C

AD

_2

4-

D oc um en ts

\2

4\

2_

Ko ke eS ta te Pk

_E le cS vc

M od s\

_d w g\

2_

E1

_s ite

El ec

A.

dw g, L ay ou t1 , 5

/1 /2

:5

0:

A M

, d ey n, :1

'LQD�/DX

(�VLJQHG�����������������$0�+67

GLQD�X�ODX#KDZDLL�JRY

6WDWH�RI�+DZDLL

&LYLO�(QJLQHHU

MULTICORELINK:24002_E106_siteElecB-Layout1 MULTICORELINK:24002_E106_siteElecB-Layout1

POLE KED

EXISTING LOADCENTER

CONVERTED TO

JUNCTION BOX "RC"

PANEL "MS"

JUNCTION BOX

NEW KIUC AERIAL SERVICE DROP TO

NEW METER VIA WEATHERHEAD

3-25KVA KIUC XFMRS

TELECOM

P.13

P.14

P.15

POLE

KED 105-440 0703

P.16

J

J

J

1 S 1.25 A

2"C

1-1/4"C

NEW LOADCENTER "STOR"

JUNCTION BOX "RC"

12" x 12" x 6"DP, NEMA 4X

NEW METER SOCKET.

SEE

NEW PANEL "RC"

NEW METER SOCKET MTD ON STAND.

SEE

E-501 E

STOR-3

STOR-1

STUB DUCT UP EXISTING

UTILITY POLE. SEE

E-202

E-106

4 WIRE KIUC SEC

(TO BE REMOVED BY KIUC)12" x 12" x 4" DP

NEMA 4X JB

SAWCUT AND PATCH

CONCRETE TO INSTALL

CONDUIT

PROVIDE STANCHIONS AROUND

METER STAND. SEE

E-106

STOR-5

MTD

UNDER

LOADCENTER

4/0 QUAD CONDUCTOR TO

BE INSTALLED BY KIUC

RC-8

WP

1 S 1.5 A

E-203

PANEL "A"

CIRCUIT 8,10 SPLICE IN

PANEL "MS" TO FEED

RANGER'S CABIN FEED

THROUGH

SHED 1

STORAGE

GARAGE 2

WORKSHOP

RANGER'S COTTAGE

P.13

P.14

P.15

P.16

LOADCENTER "A"

J

J

E-501 D

E-501 D

BUILDING

6"

1'-6"

6"

3'-6"

METER STAND.

SEE

METER/MAIN

PERMANENT

STANCHION

(TYP OF 2).

SEE

REMOVABLE STANCHION

(TYP OF 2). SEE

E-202

WIDTH OF

METER/MAIN

ENCLOSURE

J

EXISTING

LOADCENTER

1 S 1.5 A

12" x 12" x 6"DP

NEMA 4X JB

1-1/2"C OUT BACK OF JB TO LB FITTING

LB FITTING ABOVE LOADCENTER

FOR TOP ENTRY INTO LOADCENTER

SHT./OFDESCRIPTIONSYM.

REVISION

NO.

DATE APPROVED

DESIGNED:

DRAWN:

CHECKED:

APPROVED:

SUBMITTED:

DATE:

SCALE:

DRAWING NO.

DATECHIEF ENGINEER

SHEET NO. OF SHEETS

KOKE'E STATE PARK

ELECTRICAL IMPROVEMENTS

21JOB NO. F46C602F

ACH

MKE

ACH

APRIL 2026

AS SHOWN

WAIMEA, KAUAI, HAWAII

STATE OF HAWAII

DEPARTMENT OF LAND AND NATURAL RESOURCES

ENGINEERING DIVISION

FUKUNAGA AND ASSOCIATES, INC

BOLD LINES DENOTE NEW WORK

1 SCALE: 1" = 10'-0"

ELECTRICAL PLAN B (WORKSHOP AND RANGER'S COTTAGE)

0 10' 20'

1" = 10'

PLAN

NORTH

LIGHT LINES DENOTE EXISTING CONDITION1.

NOTES:

MATCHLINE, SEE SHEET

2 SEE ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.

2 WORKSHOP METER ENLARGED PLAN

SCALE: 3/4" = 1'-0"

PLAN

NORTH

0 2' 3'1'

3/4" = 1'

E-106

ELECTRICAL PLAN B (WORKSHOP AND

RANGER'S COTTAGE)

BOLD LINES DENOTE NEW WORK

LIGHT LINES DENOTE EXISTING CONDITION1.

NOTES:

E-105

C :\U se rs

\d ey n\ O ne D riv e

- M K

En gi ne er s Lt d\ f_ C

AD

_2

4-

D oc um en ts

\2

4\

2_

Ko ke eS ta te Pk

_E le cS vc

M od s\

_d w g\

2_

E1

_s ite

El ec

B.

dw g, L ay ou t1 , 5

/1 /2

:5

0:

A M

, d ey n, :1

'LQD�/DX

(�VLJQHG�����������������$0�+67

GLQD�X�ODX#KDZDLL�JRY

6WDWH�RI�+DZDLL

&LYLO�(QJLQHHU

MULTICORELINK:24002_E501_ExtElecDet-Layout1 MULTICOREVIEWLINK:Layout1,UNDERGROUND TO EXPOSED TRANSITION DETAIL(2) MULTICORELINK:24002_E202_ElvMAINTENANCE2-Layout1 MULTICOREVIEWLINK:Layout1,METER-SERVICE ENTRANCE ELEVATION - RANGER'S COTTAGE(2) MULTICORELINK:24002_E203_ElvRANGERS-CABIN-Layout1 MULTICOREVIEWLINK:Layout1,RANGER'S COTTAGE EQUIPMENT ELEVATION MULTICORELINK:24002_E501_ExtElecDet-Layout1 MULTICOREVIEWLINK:Layout1,STANCHION DETAIL(2) MULTICORELINK:24002_E501_ExtElecDet-Layout1 MULTICOREVIEWLINK:Layout1,STANCHION DETAIL(2) MULTICORELINK:24002_E202_ElvMAINTENANCE2-Layout1 MULTICORELINK:24002_E105_siteElecA-Layout1 MULTICORELINK:24002_E105_siteElecA-Layout1

TO NEW LOADCENTER

NEW KIUC AERIAL

SERVICE DROP TO METER

VIA WEATHERHEAD

NEW METER SOCKET, PIPE MAST

WITH PUSH BRACE SUPPORTS, AND

WEATHERHEAD. SEE

E-202

KIUC TO INSTALL

NEW 15KVA XFMR

NEW LOADCENTER

PH-10

WP

PARK HEADQUARTERS

SHT./OFDESCRIPTIONSYM.

REVISION

NO.

DATE APPROVED

DESIGNED:

DRAWN:

CHECKED:

APPROVED:

SUBMITTED:

DATE:

SCALE:

DRAWING NO.

DATECHIEF ENGINEER

SHEET NO. OF SHEETS

KOKE'E STATE PARK

ELECTRICAL IMPROVEMENTS

21JOB NO. F46C602F

ACH

MKE

ACH

APRIL 2026

AS SHOWN

WAIMEA, KAUAI, HAWAII

STATE OF HAWAII

DEPARTMENT OF LAND AND NATURAL RESOURCES

ENGINEERING DIVISION

FUKUNAGA AND ASSOCIATES, INC

1 SCALE: 1" = 10'-0"

ELECTRICAL PLAN C (PARK HEADQUARTERS)

0 10' 20'

1" = 10'

PLAN

NORTH

LIGHT LINES DENOTE EXISTING CONDITION1.

NOTES:

BOLD LINES DENOTE NEW WORK

E-107

ELECTRICAL PLAN C (PARK

HEADQUARTERS)

2 COORDINATE PIPE MAST AND WEATHERHEAD SUPPORT WITH KIUC.

C :\U se rs

\d ey n\ O ne D riv e

- M K

En gi ne er s Lt d\ f_ C

AD

_2

4-

D oc um en ts

\2

4\

2_

Ko ke eS ta te Pk

_E le cS vc

M od s\

_d w g\

2_

E1

_s ite

El ec

D .d w g, L ay ou t1

, 5 /1

/2

:5 0:

A

M , d ey n, :1

'LQD�/DX

(�VLJQHG�����������������$0�+67

GLQD�X�ODX#KDZDLL�JRY

6WDWH�RI�+DZDLL

&LYLO�(QJLQHHU

MULTICORELINK:24002_E202_ElvMAINTENANCE2-Layout1 MULTICOREVIEWLINK:Layout1,METER-SERVICE ENTRANCE ELEVATION - RANGER'S COTTAGE(2) MULTICORELINK:24002_E204_ElvPARK-HQ-Layout1 MULTICOREVIEWLINK:Layout1,PARK HQ EQUIPMENT ELEVATION

5'-6" MAX

4'-6" MIN

200A METER MAIN COMBINATION SAFETY

SOCKET BOX WITH TEST BYPASS

FACILITIES, NEMA 3R CONSTRUCTED OF

STAINLESS STEEL. OVERHEAD

CONSTRUCTION. METER BY KIUC

FINISHED GRADE

TO GND

PVC, SCHED 80

WEATHERHEAD ABOVE ROOF PER

KIUC REQUIREMENTS

KIUC SECONDARY

CONDUCTORS TO POLE

PIPE MAST, 6' ABOVE ROOF, PER KIUC

REQUIREMENTS

TO PANEL "G1"

4 2"C RIGID GALVANIZED

CONDUIT (NO PIPE JOINTS)

1/2" SLOPE TYPICAL

FINISHED GRADE

3/4" x 10'-0" COPPER

GROUND ROD

DUCT SEAL

1" SCH 80 PVC,

#6 GND

MAIN BREAKER

CONCRETE BASE, 3000

PSI AT 28 DAYS, TYPICAL

3"

5'-6" MAX

TO METER

2.5" x 2.25" x 0.25"L

WELDED TO PIPE (TYP)

100A METER MAIN

COMBINATION SAFETY

SOCKET BOX WITH TEST

BYPASS FACILITIES. NEMA

3R CONSTRUCTION OF

STAINLESS STEEL,

OVERHEAD

CONSTRUCTION

TO KIUC POLE TO EXISTING LOADCENTER IN

"WORKSHOP"

12" MIN 12" MIN

3" GALVANIZED PIPE

(TYP)

CAP (TYP)

FINISHED GRADE

TO GND

5'-6" MAX

4'-6" MIN

PVC, SCHED 80

NEW

PANEL

"RC"

WEATHERHEAD

ABOVE ROOF PER

KIUC REQUIREMENTSKIUC SECONDARY CONDUCTORS

AND GUY TO POLE

CORNER

CORNER

PIPE MAST, 6' ABOVE

ROOF, PER KIUC

REQUIREMENTS

WP, GFCI

RECEPTACLE

100A METER MAIN COMBINATION SAFETY

SOCKET BOX w/ TEST BYPASS FACILITIES, NEMA 3R CONSTRUCTED OF STAINLESS

STEEL. OVERHEAD CONSTRUCTION.

METER BY KIUC

2"C RIGID GALVANIZED CONDUIT (NO PIPE JOINTS)

SHT./OFDESCRIPTIONSYM.

REVISION

NO.

DATE APPROVED

DESIGNED:

DRAWN:

CHECKED:

APPROVED:

SUBMITTED:

DATE:

SCALE:

DRAWING NO.

DATECHIEF ENGINEER

SHEET NO. OF SHEETS

KOKE'E STATE PARK

ELECTRICAL IMPROVEMENTS

21JOB NO. F46C602F

ACH

MKE

ACH

APRIL 2026

AS SHOWN

WAIMEA, KAUAI, HAWAII

STATE OF HAWAII

DEPARTMENT OF LAND AND NATURAL RESOURCES

ENGINEERING DIVISION

FUKUNAGA AND ASSOCIATES, INC

1 SCALE: 1" = 1'-0"

METER/SERVICE ENTRANCE ELEVATION - GARAGE 1

0 1' 2'1/2'

1" = 1'

3 SCALE: 1" = 1'-0"

METER/SERVICE ENTRANCE ELEVATION - RANGER'S COTTAGE

0 1' 2'1/2'

1" = 1'

LIGHT LINES DENOTE EXISTING CONDITION

"/" DENOTES REMOVAL WORK

BOLD LINES DENOTE NEW WORK

NOTES:

1.

2. CIRCUIT BREAKER AND DISCONNECT SHALL BE NEMA 4X.

3. METER SOCKET/METER MUST BE ACCESSIBLE AT ALL TIMES.

GUY TO ROOF. SEE KIUC DETAIL FOR ADDITIONAL INFORMATION.

NOTES:

2 SCALE: NTS

METER/SERVICE ENTRANCE ELEVATION - WORKSHOP

1. PEDESTAL SHALL BE HOT DIPPED GALVANIZED AFTER FABRICATION.

2. ALL FASTENING BOLTS, NUTS, AND WASHERS SHALL BE STAINLESS STEEL.

3. SERVICE EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH KIUC REQUIREMENTS.

4. PROVIDE A MINIMUM OF 4 FEET OF CLEAR AND LEVEL WORKSPACE CLEARANCE IN FRONT OF

METERING AND SERVICE EQUIPMENT.

5. PROVIDE PLASTIC METER SOCKET COVER AND BAND FOR ALL BLANK METER SOCKETS. LABEL PLASTIC

COVER WITH CONTRACTOR'S NAME AND NUMBER SO COVER CAN BE RETURNED AFTER METER

INSTALLATION.

6. PROVIDE A PERMANENT PHENOLIC NAMEPLATE (BLACK WITH WHITE LETTERS) FOR ALL METER SOCKETS TO IDENTIFY THE ADDRESS, UNIT, SPACE, AREA OR LOAD SERVED (E.G. "WORKSHOP").

7. THE GROUNDING ELECTRODE CONDUCTOR SHALL NOT PASS THROUGH KIUC'S SEALABLE SECTIONS

OR COMPARTMENTS.

NOTES:

E-201

METERING ELEVATION - 1

E-202

GUY TO ROOF. SEE KIUC DETAIL FOR ADDITIONAL INFORMATION.

E-202

LIGHT LINES DENOTE EXISTING CONDITION

"/" DENOTES REMOVAL WORK

BOLD LINES DENOTE NEW WORK

1. 2

C :\U se rs

\d ey n\ O ne D riv e

- M K

En gi ne er s Lt d\ f_ C

AD

_2

4-

D oc um en ts

\2

4\

2_

Ko ke eS ta te Pk

_E le cS vc

M od s\

_d w g\

2_

E2

_E lv

M

AI

N

TE

N

AN

C E1

.d w g, L ay ou t1 , 5

/1 /2

:5

0:

A M

, d ey n, :1

'LQD�/DX

(�VLJQHG�����������������$0�+67

GLQD�X�ODX#KDZDLL�JRY

6WDWH�RI�+DZDLL

&LYLO�(QJLQHHU

MULTICORELINK:24002_E202_ElvMAINTENANCE2-Layout1 MULTICOREVIEWLINK:Layout1,KIUC WEATHERHEAD DETAIL(2) MULTICORELINK:24002_E202_ElvMAINTENANCE2-Layout1 MULTICOREVIEWLINK:Layout1,KIUC WEATHERHEAD DETAIL(2)

FINISHED GRADE

100A METER MAIN COMBINATION

SAFETY SOCKET BOX w/ TEST

BYPASS FACILITIES,

NEMA 3R CONSTRUCTED OF

STAINLESS STEEL. OVERHEAD

CONSTRUCTION. METER BY KIUC

TO GND

5'-6" MAX

4'-6" MIN

PVC, SCHED 80

WEATHERHEAD ABOVE ROOF

PER KIUC REQUIREMENTS

KIUC SECONDARY

CONDUCTORS AND GUY

TO POLE

PIPE MAST, 6' ABOVE ROOF,

PER KIUC REQUIREMENTS

TO NEW LOADCENTER

2"C RIGID GALVANIZED

CONDUIT (NO PIPE JOINTS)

PIPE CLAMP WITH THIMBLE EYE

FOR EACH GUYY

" M

IN

"H

'-0

6"

WALL

METER SOCKET

METER

(4'-6" MIN. 5'-6" MAX)

WATER TIGHT FITTING

CONDUIT STRAP AS REQUIRED

ROOFING

FLASHING AND COLLAR

MIN 2"C RIGID GALVANIZED

CONDUIT NO PIPE JOINTS

18" MIN. LEAD

SERVICE DROP SUPPORT BY

COMPANY

SERVICE DROP-DRIP LOOP

WEATHER HEAD

GUY TO BE #4 GALVANIZED IRON

WIRE ( MAX. SLOPE : 1 TO 1)

WATERPROOFING

1 - 3/8" EYE BOLT THROUGH

RAFTER FOR EACH GUY WITH

THIMBLE EYE, NUT & WASHER

4'-0" MAX

TO KIUC TRANSFORMER

CONNECTION POINT

SERVICE DROP TAP

SHT./OFDESCRIPTIONSYM.

REVISION

NO.

DATE APPROVED

DESIGNED:

DRAWN:

CHECKED:

APPROVED:

SUBMITTED:

DATE:

SCALE:

DRAWING NO.

DATECHIEF ENGINEER

SHEET NO. OF SHEETS

KOKE'E STATE PARK

ELECTRICAL IMPROVEMENTS

21JOB NO. F46C602F

ACH

MKE

ACH

APRIL 2026

AS SHOWN

WAIMEA, KAUAI, HAWAII

STATE OF HAWAII

DEPARTMENT OF LAND AND NATURAL RESOURCES

ENGINEERING DIVISION

FUKUNAGA AND ASSOCIATES, INC

1 SCALE: 1" = 1'-0"

METER/SERVICE ENTRANCE ELEVATION - PARK HEADQUARTERS

0 1' 2'1/2'

1" = 1'

LIGHT LINES DENOTE EXISTING CONDITION

"/" DENOTES REMOVAL WORK

BOLD LINES DENOTE NEW WORK

NOTES:

1.

E-202

METERING ELEVATION - 2

2 KIUC WEATHERHEAD DETAIL

SCALE: NTS

NOTES:

1. VERIFY REQUIREMENTS WITH KIUC.

2. THIS DIAGRAM IS INTENDED TO SHOW KIUC REQUIREMENTS FOR GUY MASTS, IN ACCORDANCE WITH N.E.C. SEC. 230.28.

3. FOR ALL TYPES OF SINGLE STORY ROOFING: "H" = 5 FEET.

E-202

GUY TO ROOF. SEE KIUC DETAIL FOR ADDITIONAL INFORMATION.2

C :\U se rs

\d ey n\ O ne D riv e

- M K

En gi ne er s Lt d\ f_ C

AD

_2

4-

D oc um en ts

\2

4\

2_

Ko ke eS ta te Pk

_E le cS vc

M od s\

_d w g\

2_

E2

_E lv

M

AI

N

TE

N

AN

C E2

.d w g, L ay ou t1 , 5

/1 /2

:5

0:

A M

, d ey n, :1

'LQD�/DX

(�VLJQHG�����������������$0�+67

GLQD�X�ODX#KDZDLL�JRY

6WDWH�RI�+DZDLL

&LYLO�(QJLQHHU

STEP (TYP)

WINDOW SILL

FINISHED GRADE

TELEPHONE

NETWORK

INTERFACE

CHIMNEY EDGE

TO UTILITY POLE ADJACENT TO

"KOKEE LODGE STORAGE"

FEEDER CONDUCTORS

LOADCENTER

~ WINDOW ~ ~ WINDOW ~ ~ WINDOW ~

~ DOOR ~

TO EXISTING LOADS

STEP (TYP)

WINDOW SILL

FINISHED GRADE

TELEPHONE

NETWORK

INTERFACE

CHIMNEY EDGE

NEW JUNCTION BOX

(CONVERTED

LOADCENTER)

~ WINDOW ~ ~ WINDOW ~ ~ WINDOW ~

~ DOOR ~

CONDUITS TO NEW PANEL "RC"

TO EXISTING LOADS

1 SCALE: 3/4" = 1'-0"

RANGER'S COTTAGE EQUPMENT ELEVATION - DEMO

0 2' 3'1'

3/4" = 1'

SHT./OFDESCRIPTIONSYM.

REVISION

NO.

DATE APPROVED

DESIGNED:

DRAWN:

CHECKED:

APPROVED:

SUBMITTED:

DATE:

SCALE:

DRAWING NO.

DATECHIEF ENGINEER

SHEET NO. OF SHEETS

KOKE'E STATE PARK

ELECTRICAL IMPROVEMENTS

21JOB NO. F46C602F

ACH

MKE

ACH

APRIL 2026

AS SHOWN

WAIMEA, KAUAI, HAWAII

STATE OF HAWAII

DEPARTMENT OF LAND AND NATURAL RESOURCES

ENGINEERING DIVISION

FUKUNAGA AND ASSOCIATES, INC

LIGHT LINES DENOTE EXISTING CONDITION

"/" DENOTES REMOVAL WORK

1.

NOTES:

2 SCALE: 3/4" = 1'-0"

RANGER'S COTTAGE EQUIPMENT ELEVATION

0 2' 3'1'

3/4" = 1'

LIGHT LINES DENOTE EXISTING CONDITION

BOLD LINES DENOTE NEW WORK

1.

NOTES:

CONVERT TO A JUNCTION BOX. REMOVE SURFACE RUST AND PAINT ENCLOSURE. PROVIDE NEW COVER.2 CONVERT EXISTING LOADCENTER INTO JUNCTION BOX AND PRESERVE BRANCH CIRCUIT CONDUCTORS FOR RECONNECTION. PROVIDE NEW

COVER. REMOVE SURFACE RUST AND REPAINT ENCLOSURE.

PROVIDE JUNCTION BOXES AS NEEDED TO LIMIT CONDUIT RUN TO NO MORE THAN (3) 90 DEGREE BENDS.

3.

E-203

RANGER'S COTTAGE ELEVATIONS

C :\U se rs

\d ey n\ O ne D riv e

- M K

En gi ne er s Lt d\ f_ C

AD

_2

4-

D oc um en ts

\2

4\

2_

Ko ke eS ta te Pk

_E le cS vc

M od s\

_d w g\

2_

E2

_E lv

R

AN

G

ER

S- C

AB

IN

.d w g, L ay ou t1 , 5

/1 /2

:5

0:

A M

, d ey n, :1

'LQD�/DX

(�VLJQHG�����������������$0�+67

GLQD�X�ODX#KDZDLL�JRY

6WDWH�RI�+DZDLL

&LYLO�(QJLQHHU

~ DOOR ~

~ WINDOW ~

1P15A BKR IN

LOADCENTER

3/4" FLEX

8" SQ JB x 4" DP

LAMP SOCKET

GND

FINISHED GRADE

~ STEP ~

~ DOOR ~

~ STEP ~

ROOF OVERHANG

WEATHERHEAD

1-1/2" C

NEW JUNCTION BOX 2

~ DOOR ~

~ WINDOW ~

NEW LOADCENTER "PH"

(GALVANIZED STEEL)

8" SQ JB x 4" DP

LAMP SOCKET

GND (RECONNECT

TO EXISTING)

FINISHED GRADE~ STEP ~

~ DOOR ~

~ STEP ~

ROOF OVERHANG

3/4" FLEX

1/2"C, 2#12, #12 GND

NEW NEMA 4X JB TO

INTERCEPT EXISTING FLEX

CONDUIT AND EXISTING

CONDUCTORS. RECONNECT

EXISTING CONDUCTORS TO

NEW

TO NEW METER/MAIN

ROUTE ON UNDERSIDE

OF OVERHANG

WP, GFCI RECEPTACLE

1 SCALE: 3/4" = 1'-0"

PARK HQ EQUIPMENT ELEVATION - DEMO

SHT./OFDESCRIPTIONSYM.

REVISION

NO.

DATE APPROVED

DESIGNED:

DRAWN:

CHECKED:

APPROVED:

SUBMITTED:

DATE:

SCALE:

DRAWING NO.

DATECHIEF ENGINEER

SHEET NO. OF SHEETS

KOKE'E STATE PARK

ELECTRICAL IMPROVEMENTS

21JOB NO. F46C602F

ACH

MKE

ACH

APRIL 2026

AS SHOWN

WAIMEA, KAUAI, HAWAII

STATE OF HAWAII

DEPARTMENT OF LAND AND NATURAL RESOURCES

ENGINEERING DIVISION

FUKUNAGA AND ASSOCIATES, INC

0 2' 3'1'

3/4" = 1'

LIGHT LINES DENOTE EXISTING CONDITION

"/" DENOTES REMOVAL WORK

1.

NOTES:

2 SCALE: 3/4" = 1'-0"

PARK HQ EQUIPMENT ELEVATION

0 2' 3'1'

3/4" = 1'

LIGHT LINES DENOTE EXISTING CONDITION

BOLD LINES DENOTE NEW WORK

1.

NOTES:

PROVIDE NEW JUNCTION BOX TO INTERCEPT EXISTING BRANCH CIRCUIT CONDUIT AND CONDUCTORS. PRESERVE CONDUCTORS FOR

RECONNECTION.

BOLD LINES DENOTE NEW WORK

E-204

PARK HEADQUARTERS ELEVATIONS

C :\U se rs

\d ey n\ O ne D riv e

- M K

En gi ne er s Lt d\ f_ C

AD

_2

4-

D oc um en ts

\2

4\

2_

Ko ke eS ta te Pk

_E le cS vc

M od s\

_d w g\

2_

E2

_E lv

PA

R

K- H

Q .d w g, L ay ou t1

, 5 /1

/2

:5 0:

A

M , d ey n, :1

'LQD�/DX

(�VLJQHG�����������������$0�+67

GLQD�X�ODX#KDZDLL�JRY

6WDWH�RI�+DZDLL

&LYLO�(QJLQHHU

TYPE "A"

BACKFILL:

PVC 40

FINISHED GRADE

CONCRETE JACKET,

3000 PSI COMPRESSIVE

STRENGTH IN 28 DAYS.

" M

IN

IM

U M

3" 3"

TRACEABLE WARNING TAPE WITH

"CAUTION-ELECTRIC CABLE BELOW" IMPRINTED

ON TAPE. WARNING TAPE SHALL BE PLACED

OVER ENTIRE LENGTH OF DUCTLINE

NON-CONTAMINATED NATIVE SOIL

MATERIAL WHICH DOES NOT

CONTAIN MORE THAN 50% GRAVEL,

AND ALSO, DOES NOT CONTAIN

HARD LUMPS OF EARTH 3 INCHES

IN GREATEST DIMENSION, ROCKS

LARGER THAN 3 INCHES IN

LARGEST DIMENSION, HIGHLY

PLASTIC CLAY, POORLY-GRADED

SAND AND GRAVEL (CLASSIFIED AS

SP AND GP USING THE UNITED SOIL

CLASSIFICATION SYSTEM),

ORGANICS, DEBRIS, OR OTHER

UNSUITABLE OR DELETERIOUS

MATERIALS.

NOTES:

SEE NOTE 3

3" 3"

1. WHERE TRENCH ENCOUNTERS EXISTING CONCRETE OR ASPHALT CONCRETE, SURFACE

SHALL BE SAWCUT. BACKFILL, COMPACT AND PATCH SURFACE TO MATCH ADJACENT

AREA. SEE TRENCH RESTORATION DETAIL AND CONCRETE SIDEWALK RESTORATION

DETAIL.

2. SEE DUCT SECTION DETAILS FOR CONDUIT ARRANGEMENT.

3. PROVIDE 3" SEPARATION BETWEEN DUCTS.

A TYPICAL DUCT SECTION (CONCRETE ENCASED)

SCALE: NTS

SECTION A

F DUCT SECTION DETAILS

SCALE: NTS

NOTES:

1. SEE FOR ADDITIONAL INFORMATION.

E-501

A

APPROVED

BACKFILL

SLOPE

PRIME COAT

L TRENCHc

EXISTING GROUND

TRENCH WIDTH

EXISTING BASE

COURSE

4" TOPSOIL IN

LAWN AREAS

SUITABLE NATIVE OR

IMPORT MATERIAL

COMPACTED TO 95%

RELATIVE COMPACTION

6" MIN. BASE COURSE

EXISTING

PAVEMENT SLOPE IN PLANE OF

EXISTING PAVEMENT

1/2 SECTION

PAVED AREA

12"

2" MIN. A.C.

WEARING COURSE

SAWCUT BEFORE

TRENCHING

SAWCUT BEFORE

REPAVING

1/2 SECTION

LAWN AREA

BITUMINOUS

TACK COAT

B TRENCH RESTORATION DETAIL

SCALE: NTS

BROOM FINISH

EMBED #3 x 9" LG. SMOOTH

DOWELS 4.5" MIN. IN 3/4" EPOXY

FILLED HOLE AT 12" O.C.

SAWCUT AT NEAREST

SCORELINE/JOINT IF

SAWCUT IS LESS THAN

OR EQUAL TO 4'-0"

FROM NEAREST

SCORELINE/JOINT.

(TYP FOR OTHER SIDE)

EXISTING CONCRETE

SIDEWALK

4" MINIMUM

THICKNESS OR

MATCH EXISTING,

WHICHEVER IS

GREATER

6 x 6, W2.9 x W2.9 WIRE

MESH CENTERED IN SLAB

LIMITS OF SIDEWALK REPLACEMENT

6" 6" TRENCH WIDTH 6" 6"

3"

9" GREASED END 6" SELECT BORROW

C CONCRETE SIDEWALK RESTORATION DETAIL

SCALE: NTS

COUPLING

PVC SCHED 40

FINISHED GRADE

PVC SCHED 80, INSTALL TO 10' ABOVE

FINISHED GRADE PER KIUC REQUIREMENTS

AND CAP

CONCRETE

ENCASEMENT

TO METER SOCKET

E UNDERGROUND TO EXPOSED TRANSITION DETAIL

SCALE: NTS

TOP OF CONC SW PAD

PIPE CAP

FINISH GRADE

PIPE CAP

NOTES:

4" 4"

1. ALL STANCHIONS SHALL BE INSTALLED AT THE SAME HEIGHT ABOVE GRADE.

2. STATIONARY STANCHIONS TO BE FILLED WITH CONCRETE TO WEIGH APPROXIMATELY 160 LBS.

3. WELDED NUTS ARE FOR SCREWING IN BOLTS TO ACT AS HANDLES FOR LIFTING REMOVABLE

STANCHIONS. BOLT TO BE REMOVED AFTER INSTALLATION.

4. STANCHIONS SHALL BE PAINTED YELLOW PER ANSI SPEC. Z53.1 TO COMPLY WITH OSHA

STANDARDS PER COLOR CODING.

5. STANCHION SHALL CONFORM TO ASTM A53.

6. STANCHION TYPE AND LOCATION SHALL REQUIRE APPROVAL FROM DEPARTMENT OF WATER.

4" STANDARD GALV STEEL

PIPE SEE NOTE 2

3/4" GALVANIZED BOLT

CONC ENCASEMENT

5000 PSI @ 28 DAYS

WELD (2) GALV NUTS,

(5/8"), 180 APART,

SEE NOTE 5

5" STANDARD GALV

STEEL PIPE, TYP

1" DIA DRAIN

PIPE

2' -0

3' -6

" M

IN

3' -0

" M

IN

SE

E

N O

TE

3"

3' -0

3"3"

STATIONARY

STANCHION

REMOVABLE

STANCHION

D STANCHION DETAIL

SCALE: NTS

SHT./OFDESCRIPTIONSYM.

REVISION

NO.

DATE APPROVED

DESIGNED:

DRAWN:

CHECKED:

APPROVED:

SUBMITTED:

DATE:

SCALE:

DRAWING NO.

DATECHIEF ENGINEER

SHEET NO. OF SHEETS

KOKE'E STATE PARK

ELECTRICAL IMPROVEMENTS

21JOB NO. F46C602F

ACH

MKE

ACH

APRIL 2026

AS SHOWN

WAIMEA, KAUAI, HAWAII

STATE OF HAWAII

DEPARTMENT OF LAND AND NATURAL RESOURCES

ENGINEERING DIVISION

FUKUNAGA AND ASSOCIATES, INC

E-501

EXTERIOR ELECTRICAL DETAILS

C :\U se rs

\d ey n\ O ne D riv e

- M K

En gi ne er s Lt d\ f_ C

AD

_2

4-

D oc um en ts

\2

4\

2_

Ko ke eS ta te Pk

_E le cS vc

M od s\

_d w g\

2_

E5

_E xt

El ec

D et

.d w g, L ay ou t1 , 5

/1 /2

:5

0:

A M

, d ey n, :1

'LQD�/DX

(�VLJQHG�����������������$0�+67

GLQD�X�ODX#KDZDLL�JRY

6WDWH�RI�+DZDLL

&LYLO�(QJLQHHU

M

KIUC METER

#G0710945

(METER "A")

P.1 P.3

KIUC SERVICE TO POLE #1 VIA

WEATHERHEAD

"LODGE/RESTAURANT BLDG"

3P240A

200A

M

KIUC

METER

#G0710947

(METER "B")

3P200A

200A

JUNCTION BOX MTD

ON EXTERIOR OF

"METER" BLDG

WIREWAY

200A

DOUBLE

THROW

SAFETY

SWITCH

3P200A 1P20A

2P30A

2P80A

CKT 1,3

CKT 5,7

3#2

3#4(?)

3P100A

CKT 2,4,6 4#2

2P100A

CKT 8,10 2#1/0

PANEL "A"

225A, 208Y/120V, 3PH, 4W

CUTLER HAMMER PRL-1A

2P100A

2P60A

2P60A

PANEL "C"

(ON EXTERIOR OF

CAMP OFFICE BLDG)

PANEL

(ON EXTERIOR OF

MANAGER'S

RESIDENCE)

PANEL BUILDING "A"

PANEL BUILDING "B"

PANEL MANAGER'S

RESIDENCE

PANEL CAMP OFFICE

PANEL KITCHEN/

REC BLDG

M

KIUC METER

#B0220199

(METER "C")

2P175A 2"C, 3#2

3"C, 4#3/0, #6 GND

2-1/2"C, 4#3/0, #6 GND

3#3/0

1.

NOTES:

FEEDER FOR GARAGE 1 AND 2.

FEEDER FOR WORKSHOP.

3#3/0

3#2/0

"METER" BUILDING

RECEPTACLE MTD

ON SUPPORT

PANEL "A"

MOUNTED ON

LIGHT MTD ON SUPPORT

PANEL "A" MOUNTED ON

P.5 P.7

"PARK HEADQUARTERS"

SEE FOR

CONTINUATION

SEE AND

FOR CONTINUATION

LIGHT LINES DENOTE EXISTING CONDITION

"/" DENOTES REMOVAL WORK

BOLD LINES DENOTE NEW WORK

TO EXISTING

LOADS

1P15A

R

2"C

1 SCALE: NTS

ONE-LINE DIAGRAM - (METERS A, B, C) - DEMO

E-603 E-604

E-604

"R" DENOTES REMOVAL OF CONDUCTORS FROM EXISTING CONDUIT. CONDUIT TO BE REUSED. SHT./OFDESCRIPTIONSYM.

REVISION

NO.

DATE APPROVED

DESIGNED:

DRAWN:

CHECKED:

APPROVED:

SUBMITTED:

DATE:

SCALE:

DRAWING NO.

DATECHIEF ENGINEER

SHEET NO. OF SHEETS

KOKE'E STATE PARK

ELECTRICAL IMPROVEMENTS

21JOB NO. F46C602F

ACH

MKE

ACH

APRIL 2026

AS SHOWN

WAIMEA, KAUAI, HAWAII

STATE OF HAWAII

DEPARTMENT OF LAND AND NATURAL RESOURCES

ENGINEERING DIVISION

FUKUNAGA AND ASSOCIATES, INC

E-601

ONE-LINE DIAGRAM - (METERS A, B, C) -

DEMO

C :\U se rs

\d ey n\ O ne D riv e

- M K

En gi ne er s Lt d\ f_ C

AD

_2

4-

D oc um en ts

\2

4\

2_

Ko ke eS ta te Pk

_E le cS vc

M od s\

_d w g\

2_

E6

.d w g, L ay ou t1 , 5

/1 /2

:5

0:

A M

, d ey n, :1

'LQD�/DX

(�VLJQHG�����������������$0�+67

GLQD�X�ODX#KDZDLL�JRY

6WDWH�RI�+DZDLL

&LYLO�(QJLQHHU

MULTICORELINK:24002_E603-Layout1 MULTICORELINK:24002_E604-Layout1 MULTICORELINK:24002_E604-Layout1

1.

NOTES:

LIGHT LINES DENOTE EXISTING CONDITION

BOLD LINES DENOTE NEW WORK

1 SCALE: NTS

ONE-LINE DIAGRAM - PARK HEADQUARTERS

AERIAL SECONDARY SERVICE DROP

FROM KUIC

WEATHERHEAD

M

2"C (GRC), 3#4

#6 GND PER NEC

4 JAW METER/MAIN, 100A

120/240V, 1PH, 3 WIRE

1-1/2"C, 3#4, #6 GND

"PARK HEADQUARTERS"

TO EXISTING LOADS

1P15A

2P60A

NEW LOADCENTER "PH"

NEW WP JUNCTION BOX TO

INTERCEPT EXISTING FLEX CONDUIT

1/2"C, 2#12, #12 GND

SURGE PROTECTION DEVICE. SUITABLE FOR WET LOCATIONS.2

2P60A

2P30A

1"C, 4#10 OR AS RECOMMENDED BY

MANUFACTURER

2SPD

SHT./OFDESCRIPTIONSYM.

REVISION

NO.

DATE APPROVED

DESIGNED:

DRAWN:

CHECKED:

APPROVED:

SUBMITTED:

DATE:

SCALE:

DRAWING NO.

DATECHIEF ENGINEER

SHEET NO. OF SHEETS

KOKE'E STATE PARK

ELECTRICAL IMPROVEMENTS

21JOB NO. F46C602F

ACH

MKE

ACH

APRIL 2026

AS SHOWN

WAIMEA, KAUAI, HAWAII

STATE OF HAWAII

DEPARTMENT OF LAND AND NATURAL RESOURCES

ENGINEERING DIVISION

FUKUNAGA AND ASSOCIATES, INC

E-602

ONE-LINE DIAGRAM - PARK HEADQUARTERS

C :\U se rs

\d ey n\ O ne D riv e

- M K

En gi ne er s Lt d\ f_ C

AD

_2

4-

D oc um en ts

\2

4\

2_

Ko ke eS ta te Pk

_E le cS vc

M od s\

_d w g\

2_

E6

.d w g, L ay ou t1 , 5

/1 /2

:5

0:

A M

, d ey n, :1

'LQD�/DX

(�VLJQHG�����������������$0�+67

GLQD�X�ODX#KDZDLL�JRY

6WDWH�RI�+DZDLL

&LYLO�(QJLQHHU

1P20A

"GARAGE 1"

"STORAGE"

JB

JB

TO "SHED"

LOADCENTER

"A"

LOADCENTER

"B"

LOADCENTER

SEE AND

FOR CONTINUATION

"WORKSHOP"

"RANGER'S COTTAGE"

2"C, 4#2 (GARAGES),

2#1/0 (WORKSHOP)

PARTIAL PANEL "MS"

1.

NOTES:

CONVERT TO JUNCTION BOX. PRESERVE EXISTING BRANCH CIRCUIT CONDUCTORS FOR RECONNECTION. REMOVE SURFACE RUST FROM ENCLOSURE AND PAINT.

PROVIDE NEW BLANK COVER.

LIGHT LINES DENOTE EXISTING CONDITION

"/" DENOTES REMOVAL WORK

BOLD LINES DENOTE NEW WORK

R

1 SCALE: NTS

ONE-LINE DIAGRAM - GARAGES/STORAGE/WORKSHOP/RANGER'S COTTAGE - DEMO

"GARAGE 2"

E-601 E-602

"R" DENOTES REMOVAL OF CONDUCTORS FROM EXISTING CONDUIT. CONDUIT TO BE REUSED.

SHT./OFDESCRIPTIONSYM.

REVISION

NO.

DATE APPROVED

DESIGNED:

DRAWN:

CHECKED:

APPROVED:

SUBMITTED:

DATE:

SCALE:

DRAWING NO.

DATECHIEF ENGINEER

SHEET NO. OF SHEETS

KOKE'E STATE PARK

ELECTRICAL IMPROVEMENTS

21JOB NO. F46C602F

ACH

MKE

ACH

APRIL 2026

AS SHOWN

WAIMEA, KAUAI, HAWAII

STATE OF HAWAII

DEPARTMENT OF LAND AND NATURAL RESOURCES

ENGINEERING DIVISION

FUKUNAGA AND ASSOCIATES, INC

E-603

ONE-LINE DIAGRAM - MAINT

SHED-SHED-KOKEE LODGE STORAGE - DEMO

C :\U se rs

\d ey n\ O ne D riv e

- M K

En gi ne er s Lt d\ f_ C

AD

_2

4-

D oc um en ts

\2

4\

2_

Ko ke eS ta te Pk

_E le cS vc

M od s\

_d w g\

2_

E6

.d w g, L ay ou t1 , 5

/1 /2

:5

0:

A M

, d ey n, :1

'LQD�/DX

(�VLJQHG�����������������$0�+67

GLQD�X�ODX#KDZDLL�JRY

6WDWH�RI�+DZDLL

&LYLO�(QJLQHHU

MULTICORELINK:24002_E601-Layout1 MULTICORELINK:24002_E602-Layout1

JB

JB

NEW LOADCENTER "STOR"

"GARAGE 2"

LOADCENTER

"A"

LOADCENTER

"B"

PANEL "RC"

"WORK SHOP"

"RANGER'S COTTAGE"

AERIAL SECONDARY SERVICE DROP FROM KUIC

PARTIAL PANEL "MS"

1.

NOTES:

EXISTING LOADCENTER CONVERTED TO JUNCTION BOX. RECONNECT EXISTING BRANCH CIRCUITS VIA NEW LOADCENTER.

1/2"C, 2#12, #12 GND (FOR 2P20A BKR),

1/2"C, 2#12, #12 GND (FOR 2P20A BKR),

1/2"C, 2#12, #12 GND (FOR 2P20A BKR),

3/4"C, 2#10, #10 GND (FOR 2P30A BKR),

3/4"C, 6#12, #12 GND (FOR 1P BKRS, 3 EACH).

PROVIDE NEW CIRCUIT BREAKER IN EXISTING PANELBOARD (WESTINGHOUSE TYPE NQP).

SPLICE TO EXISTING CONDUCTORS.

SURGE PROTECTION DEVICE. SUITABLE FOR WET LOCATIONS.

SURGE PROTECTION DEVICE CONNECTED DIRECTLY TO LOADCENTER BUS. 4#10 OR AS RECOMMENDED BY MANUFACTURER.

LIGHT LINES DENOTE EXISTING CONDITION

BOLD LINES DENOTE NEW WORK

2JUNTION BOX

"LC"

1-1/2"C, 3#2, #6 GND

1-1/2"C, 3#2, #6 GND (VIA LB FITTING

ABOVE LOADCENTER)

2P60A

1P20A

1P20A

2P60A

#6 GND PER NEC

1/2"C, 2#12, #12 GND

1-1/4"C, 3#4, #6 GND

43P100A

#6 GND

PER NEC

PANEL "G1"

2"C, 4#1, #6 GND (GARAGE 2 FEEDER),

2"C, 4#1, #6 GND

"GARAGE 1"

WEATHERHEAD

1 SCALE: NTS

ONE-LINE DIAGRAM - GARAGES/STORAGE/WORKSHOP/RANGER'S COTTAGE

M

2"C (GRC), 4#2/0

#4 GND PER NEC

2-1/2"C, 4#2/0, #4 GND

3P100A

M

#4 GND PER NEC

AERIAL SECONDARY SERVICE DROP

FROM KUIC

WEATHERHEAD

M

2"C, 3#2

#6 GND PER NEC

1-1/2"C, 3#2, #6 GND

3P175A

2P100A

2P80A

JUNCTION BOX "RC"

2"C

1-1/2"C, 3#2, #6 GND

7 JAW METER/MAIN, 200A

120/208Y, 3PH, 4 WIRE

TO EXISTING

LOAD

TO EXISTING

LOAD

5 JAW METER/MAIN, 100A

120/208V, 1PH, 3 WIRE

5 JAW METER/MAIN, 100A

120/208V, 1PH, 3 WIRE

STUB UP EXISTING UTILITY POLE.

SERVICE CONDUCTORS TO METER

SOCKET BY KIUC

J

NEMA 4X JB ON EXTERIOR OF BUILDING

SPD

1"C, 5#10 OR AS RECOMMENDED BY MANUFACTURER

3P30A

SPD

2P30A

6SPD

1"C, 4#10 OR AS RECOMMENDED

BY MANUFACTURER

"STORAGE"

2P30A

6SPD

1"C, 4#10 OR AS RECOMMENDED

BY MANUFACTURER

SHT./OFDESCRIPTIONSYM.

REVISION

NO.

DATE APPROVED

DESIGNED:

DRAWN:

CHECKED:

APPROVED:

SUBMITTED:

DATE:

SCALE:

DRAWING NO.

DATECHIEF ENGINEER

SHEET NO. OF SHEETS

KOKE'E STATE PARK

ELECTRICAL IMPROVEMENTS

21JOB NO. F46C602F

ACH

MKE

ACH

APRIL 2026

AS SHOWN

WAIMEA, KAUAI, HAWAII

STATE OF HAWAII

DEPARTMENT OF LAND AND NATURAL RESOURCES

ENGINEERING DIVISION

FUKUNAGA AND ASSOCIATES, INC

E-604

ONE-LINE DIAGRAM - MAINT

SHED-SHED-KOKEE LODGE STORAGE

C :\U se rs

\d ey n\ O ne D riv e

- M K

En gi ne er s Lt d\ f_ C

AD

_2

4-

D oc um en ts

\2

4\

2_

Ko ke eS ta te Pk

_E le cS vc

M od s\

_d w g\

2_

E6

.d w g, L ay ou t1 , 5

/1 /2

:5

1:

A M

, d ey n, :1

'LQD�/DX

(�VLJQHG�����������������$0�+67

GLQD�X�ODX#KDZDLL�JRY

6WDWH�RI�+DZDLL

&LYLO�(QJLQHHU

SHT./OFDESCRIPTIONSYM.

REVISION

NO.

DATE APPROVED

DESIGNED:

DRAWN:

CHECKED:

APPROVED:

SUBMITTED:

DATE:

SCALE:

DRAWING NO.

DATECHIEF ENGINEER

SHEET NO. OF SHEETS

KOKE'E STATE PARK

ELECTRICAL IMPROVEMENTS

21JOB NO. F46C602F

ACH

MKE

ACH

APRIL 2026

AS SHOWN

WAIMEA, KAUAI, HAWAII

STATE OF HAWAII

DEPARTMENT OF LAND AND NATURAL RESOURCES

ENGINEERING DIVISION

FUKUNAGA AND ASSOCIATES, INC

E-701

PANEL SCHEDULES

C :\U se rs

\d ey n\ O ne D riv e

- M K

En gi ne er s Lt d\ f_ C

AD

_2

4-

D oc um en ts

\2

4\

2_

Ko ke eS ta te Pk

_E le cS vc

M od s\

_d w g\

2_

E7

_P an el s.

dw g, L ay ou t1

, 5 /1

/2

:5 1:

A

M , d ey n, :1

'LQD�/DX

(�VLJQHG�����������������$0�+67

GLQD�X�ODX#KDZDLL�JRY

6WDWH�RI�+DZDLL

&LYLO�(QJLQHHU

https://stateofhawaii.na1.adobesign.com/verifier?tx=CBJCHBCAABAAp1ejQktrSu8p5YSKAKt_I4DGPDU6l-N9 https://stateofhawaii.na1.adobesign.com/verifier?tx=CBJCHBCAABAAp1ejQktrSu8p5YSKAKt_I4DGPDU6l-N9

T-001 TITLE SHEET
G-001 CONSTRUCTION NOTES - 1
G-002 CONSTRUCTION NOTES - 2
E-001 ELECTRICAL SYMBOLS, ABBREV, AND NOTES
E-101 STUDY OVERALL SITE PLAN
E-102 ELECTRICAL DEMO PLAN A (GARAGES AND STORAGE)
E-103 ELECTRICAL DEMO PLAN B (WORKSHOP AND RANGER'S COTTAGE)
E-104 ELETRICAL DEMO PLAN C (PARK HEADQUARTERS)
E-105 ELETRICAL PLAN A (GARAGES AND STORAGE)
E-106 ELETRICAL PLAN B (WORKSHOP AND RANGER'S COTTAGE)
E-107 ELECTRICAL PLAN C (PARK HEADQUARTERS)
E-201 METERING ELEVATION - 1
E-202 METERING ELEVATION - 2
E-203 RANGER'S COTTAGE ELEVATIONS
E-204 PARK HEADQUARTERS ELEVATIONS
E-501 EXTERIOR ELECTRICAL DETAILS
E-601 ONE-LINE DIAGRAM - (METERS A, B, C) - DEMO
E-602 ONE-LINE DIAGRAM - PARK HEADQUARTERS
E-603 ONE-LINE DIAGRAM - MAINT SHED-SHED-KOKEE LODGE STORAGE - DEMO
E-604 ONE-LINE DIAGRAM - MAINT SHED-SHED-KOKEE LODGE STORAGE
E-701 PANEL SCHEDULES
2026-05-07T17:15:46+0000
Certified by Adobe Acrobat Sign

File details come from the government source that posted it. Updated .