Hanscom_AFB_35269_rpt_Binder_(1).pdf
PDF 301 KB Posted
- Attached to
- Tank Cleaning Federal contract opportunity
- Solicitation number
- F2B3AQ7306A101
About this file
Hanscom Report
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Various_Inspection_Reports.pdf | ||
| Aerial_View_of_Tanks.pptx | PPTX presentation | |
| Tank_Cleaning_Question.pdf | ||
| PWS.pdf | ||
| Wage_Determinations.pdf | ||
| Combined_Synopsis_Solicitation.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
December 7, 2017
Department of the Air Force
66 ABG/CEIE
120 Grenier Street Hanscom AFB, MA 01731
Attn: Mr. Roy Wimbish
Re: AST In-Service Inspections Hanscom AFB, MA PCA Job No. 35269__________
Dear Mr. Wimbish:
Please find the enclosed cover report and Annual In- Service Inspection forms for two (2) above ground storage tanks, at the Department of the Air Force storage terminal at Hanscom AFB in Bedford, Massachusetts.
We trust this report is complete and satisfactory;
however, if you have questions or require additional information, please contact me.
Very truly yours, Bertram Jay Phillips
STORAGE TANK
ANNUAL IN-SERVICE
INSPECTION REPORT
HANSCOM AFB, MA
PCA JOB NO. 35269
Prepared For:
Mr. Roy Wimbish
Hanscom AFB
66 ABG/CEIE
Hanscom AFB, MA 01731
Date of Inspection – December 7, 2017
Prepared by:
PCA ENGINEERING
NEW ENGLAND LLC
7 West End Way Norwell, Ma 02061 Tel (781) 261-9688 Fax (781) 261-9679
PCA ENGINEERING NE LLC
TABLE OF CONTENTS
A. SUMMARY
B. CORRESPONDENCE
C. FIRE MARSHAL ANNUAL INSPECTION FORMS
1. Tank No. 1
2. Tank No. 2
PCA ENGINEERING NE LLC
EXECUTIVE SUMMARY
The inspection of the two (2) tanks at this facility found no unusual corrosion activity or structural conditions that would prevent these tanks from remaining in active service.
We recommend continuing the present level of scheduled maintenance and general housekeeping.
Drew Lawrence PCA Engineering NE LLC
API-653 Tank Inspector Certification No. 24662
INSPECTION FORMS
Title:
Fax number:
The Tank is: In-Service Out-of Service Abandonded, since (date):
Date Constructed/Manufactured: Tank Serial Number:
Office of the Massachusetts State Fire Marshal Number, if any:
Tank Constructed/Manufactured according to: A.P.I.: A.S.M.E.: U.L.: Other:
Tank Construction Standard: Tank Gross Capacity: bbl bbl gals gals
Horizontal Tank Width/Dia. (Feet): Length (Feet): Height (Feet):
Verticle Tank Diameter (Feet): Height (Feet):
Fluid to be Stored in Tank:
Is this Tank located in a Vault? Yes No If Yes, describe vault and associated equipment:
Compartmented Tank? Yes No If so, number of compartments and capacities:
Secondary Containment Tank (Double Wall Tank)? Yes No Retaining Basin (Dike) provided? Yes No
Description of retaining basin (dike): Metal Clay Reinforced Concrete Other, describe
Was the local fire dept. present for the inspection? Yes No
Is there a valid registration (M.G.L. c. 148 §13) for this product?: Yes No Not required
If yes, fill out the following: Licensing Authority: Expiration date:
Are there valid fire department permits (M.G.L. c. 148 § 10A & 23) for this product?
Yes, expiration date: No Not required
Has this tank been inspected in the nature and frequency as prescribed in 502 CMR 5.05(1)? Yes No
Does this tank have a written record as prescribed in 502 CMR 5.05(2)? Yes No
Has the person principally in charge of the tank signed each inspection record, per 502 CMR 5.05(2)? No
Have any permits for maintenance (502 CMR 5.04(1)) been issued since the last Annual Inspection Form was submitted?
Yes No If yes, the date the permit was issued by the Office of the State Fire Marshal:
Have any permits for emergency repair (502 CMR 5.04(e)) been issued since the last Annual Inspection Form was submitted?
Yes No If yes, the date the permit was issued by the Office of the State Fire Marshal:
PCA ENGINEERING NE LLC Page 1 of 2
Tank Nominal Capacity:
X
251,118
None
5,979
NA
01857
251,253
Net Capacity of Dike:
API 650 5,979
125Flash Point ( o F):No. 6 Oil
Local fire dept. rep:
Annual Inspection Form
Boiler Plant Supervisor
Department of the Air Force
66 ABG/CE Hanscom AFB, MA 01731
120 Grenier Street Business (mailing) address:
Address or location of tank:
Contact name:
Business name:
Street address:
145 Randolf Street Bldg 1201 Hanscom AFB, MA 01731
Telephone number:
Leo Shortsleeve
781.225.6552 NA
Atmospheric type with Cone Roof designDescription of tank: Tank no.: 1
1/1/1986 bbl6,835
Yes
Date of inspection:
Satisfactory Unsatisfactory
PCA ENGINEERING NE LLC Page 2 of 2
NOAC Shell/Roof Insulated
NOAC Shell/Roof Insulated
Check for vegetation inside the dike. X
Other:
Check for combustables inside the dike. X
X
X
Inspect for paint failures. NOAC Shell/Roof Insulated
Check for proper signage.
Other:
Related Equipment (Appurtenances) Tank Piping is Insulated
Check for the good general condition of the tank. X
Check that the tank has proper static protection. X
Check for signs of leakage. X
Inspect for shell deformations. NOAC Shell/Roof Insulated
Inspect for gouges.
Inspect for dents.
NOAC Shell/Roof Insulated
Inspect for pitting. NOAC Shell/Roof Insulated
Inspect for corrosion.
X
Inspect for paint failures. NOAC Shell/Roof Insulated
Check for proper signage.
Tank Tank Shell & Roof Insulated
Other:
Check for the good general condition of the foundation. X
Check the bottom to foundation seal, if any. X
X
X
Minor near ladderX
X
Inspect for cracks. X
X
X
X
NOAC Shell/Roof Insulated
Inspect for pitting. NOAC Shell/Roof Insulated
Inspect for corrosion.
Inspect for dents. NOAC Shell/Roof Insulated
Inspect for gouges. NOAC Shell/Roof Insulated
Check that the appurtenances are in good working condition. X Check for signs of leakage. X
Check that fire protection equipment is inspected and maintained. X
Check the tank insulation, if applicable. X Good Condition
Check for the good and general condition of the appurtenances. X
Other:
Other:
X
Dikes (Secondary Containment)
Check that it is properly sized. X
X
Check for any penetrations. X
Check for any breaches.
Water within the dikeInspect that the dike drains to an approprate location. X
Concrete
Inspect that any penetrations are sealed liquid tight.
Foundation
Check that the tank is properly grounded
NOAC Shell/Roof Insulated
X
Inspect for corrosion.
Inspect for vegetation around the bottom of the tank.
Comments
Check for signs of leakage.
Inspect for settlement around the perimeter of the tank.
Check water drains away from the tank.
Inspect for broken concrete.
Inspect for spalling.
Inspect for cavities under foundation.
Check that a building is not located inside of the dike.
12/7/2017
Check for foundation levelness. X
Inspect for shell distortions.
Check for storage inside of the dike. X
X
Check for the good general condition of the dikes. X
Check that access/egress ladders, stairs or ramps are in good condition.
Title:
Fax number:
The Tank is: In-Service Out-of Service Abandonded, since (date):
Date Constructed/Manufactured: Tank Serial Number:
Office of the Massachusetts State Fire Marshal Number, if any:
Tank Constructed/Manufactured according to: A.P.I.: A.S.M.E.: U.L.: Other:
Tank Construction Standard: Tank Gross Capacity: bbl bbl gals gals
Horizontal Tank Width/Dia. (Feet): Length (Feet): Height (Feet):
Verticle Tank Diameter (Feet): Height (Feet):
Fluid to be Stored in Tank:
Is this Tank located in a Vault? Yes No If Yes, describe vault and associated equipment:
Compartmented Tank? Yes No If so, number of compartments and capacities:
Secondary Containment Tank (Double Wall Tank)? Yes No Retaining Basin (Dike) provided? Yes No
Description of retaining basin (dike): Metal Clay Reinforced Concrete Other, describe
Was the local fire dept. present for the inspection? Yes No
Is there a valid registration (M.G.L. c. 148 §13) for this product?: Yes No Not required
If yes, fill out the following: Licensing Authority: Expiration date:
Are there valid fire department permits (M.G.L. c. 148 § 10A & 23) for this product?
Yes, expiration date: No Not required
Has this tank been inspected in the nature and frequency as prescribed in 502 CMR 5.05(1)? Yes No
Does this tank have a written record as prescribed in 502 CMR 5.05(2)? Yes No
Has the person principally in charge of the tank signed each inspection record, per 502 CMR 5.05(2)? No
Have any permits for maintenance (502 CMR 5.04(1)) been issued since the last Annual Inspection Form was submitted?
Yes No If yes, the date the permit was issued by the Office of the State Fire Marshal:
Have any permits for emergency repair (502 CMR 5.04(e)) been issued since the last Annual Inspection Form was submitted?
Yes No If yes, the date the permit was issued by the Office of the State Fire Marshal:
PCA ENGINEERING NE LLC Page 1 of 2
Tank Nominal Capacity:
X
251,118
None
5,979
NA
01858
251,253
Net Capacity of Dike:
API 650 5,979
125Flash Point ( o F):No. 6 Oil
Local fire dept. rep:
Annual Inspection Form
Boiler Plant Supervisor
Department of the Air Force
66 ABG/CEIE Hanscom AFB, MA 01731
120 Grenier Street Business (mailing) address:
Address or location of tank:
Contact name:
Business name:
Street address:
145 Randolf Street Bldg 1201 Hanscom AFB, MA 01731
Telephone number:
Leo Shortsleeve
781.225.6552 NA
Atmospheric type with Cone Roof designDescription of tank: Tank no.: 2
1/1/1986 bbl6,835
Yes
Date of inspection:
Satisfactory Unsatisfactory
PCA ENGINEERING NE LLC Page 2 of 2
NOAC Shell/Roof Insulated
NOAC Shell/Roof Insulated
Check for vegetation inside the dike. X
Other:
Check for combustables inside the dike. X
X
X
Inspect for paint failures. NOAC Shell/Roof Insulated
Check for proper signage.
Other:
Related Equipment (Appurtenances) Tank Piping is Insulated
Check for the good general condition of the tank. X
Check that the tank has proper static protection. X
Check for signs of leakage. X
Inspect for shell deformations. NOAC Shell/Roof Insulated
Inspect for gouges.
Inspect for dents.
NOAC Shell/Roof Insulated
Inspect for pitting. NOAC Shell/Roof Insulated
Inspect for corrosion.
X
Inspect for paint failures. NOAC Shell/Roof Insulated
Check for proper signage.
Tank Tank Shell & Roof Insulated
Other:
No seal at base of insulation
Check for the good general condition of the foundation. X
Check the bottom to foundation seal, if any. X
X
X
Minor cracking
X
X
Inspect for cracks. X
X
X
X
NOAC Shell/Roof Insulated
Inspect for pitting. NOAC Shell/Roof Insulated
Inspect for corrosion.
Inspect for dents. NOAC Shell/Roof Insulated
Inspect for gouges. NOAC Shell/Roof Insulated
Check that the appurtenances are in good working condition. X Check for signs of leakage. X
Check that fire protection equipment is inspected and maintained. X
Check the tank insulation, if applicable. X Good Condition
Check for the good and general condition of the appurtenances. X
Other:
Other:
X
Dikes (Secondary Containment)
Check that it is properly sized. X
X
Check for any penetrations. X
Check for any breaches.
Inspect that the dike drains to an approprate location. X
Concrete
Inspect that any penetrations are sealed liquid tight.
Foundation
Check that the tank is properly grounded
NOAC Shell/Roof Insulated
X
Inspect for corrosion.
Inspect for vegetation around the bottom of the tank.
Comments
Check for signs of leakage.
Inspect for settlement around the perimeter of the tank.
Check water drains away from the tank.
Inspect for broken concrete.
Inspect for spalling.
Inspect for cavities under foundation.
Check that a building is not located inside of the dike.
12/7/2017
Check for foundation levelness. X
Inspect for shell distortions.
Check for storage inside of the dike. X
X
Check for the good general condition of the dikes. X
Check that access/egress ladders, stairs or ramps are in good condition.
File details come from the government source that posted it.