Your specs on the generator don't mention whether you need exhaust system (muffler and/or flex pipe attaching to muffler) Required? Any muffler sound level specs (commercial, residential, or critical muffler)? Side entrance or end entrance?
Also -- circuit breaker not specified. Required? Or just need an electrical entrance bos.
Answers
The exhaust should be included with the generators enclosure.
Enclosure-Steel, Weather Prot, Base Mtd, w/ExhSys
There are no sound requirements, so commercial exhaust should be fine.
Also, the exhaust typically exits the top of the generators enclosure.
We need a 600 Amp circuit breaker on the right side of the unit.
Circuit Breaker-600A, Right CB on Right side, 3-pole, UL 600, IEC 590, 100%