EQUIPMENT LIST.xls

XLS spreadsheet 69 KB Posted

Attached to
HVAC MAINTENANCE State and local contract opportunity
Solicitation number
5400019569
Issued by
Richland County, South Carolina

About this file

This is an equipment inventory list for the South Carolina Department of Employment and Workforce (SCDEW) detailing HVAC systems across eight regional locations. The document provides a comprehensive catalog of heating, cooling, and heat pump units installed at SCDEW facilities throughout the state, including locations in Greenville, Catwaba/Chester, Catwaba/Lancaster, Florence, Bennettsville, Marion, Conway, Kingstree, Beaufort, Aiken, Barnwell, Orangeburg, Abbeville, Laurens County, Anderson, and Sumter. The inventory includes manufacturer specifications, model numbers, serial numbers, filter types, belt configurations, tonnage ratings, installation dates, and expected service life of 15 to 20 years for various equipment.

The equipment list identifies multiple deficiencies and repair needs across the regional inventory, with numerous units requiring attention including compressor contactor replacements, service disconnect repairs, refrigerant leak searches, thermostat recalibration, and auxiliary heat strip replacements. Many units are noted as mismatched between condensing and air handling components, while several systems are beyond their expected service life expectancy and require replacement. The document serves as the baseline inventory assessment for the HVAC Maintenance contract opportunity, establishing the scope of equipment requiring ongoing maintenance, repairs, and potential replacement throughout the SCDEW system across multiple regions and facilities.

View the file

Other files for this state and local contract opportunity

Other files attached to HVAC MAINTENANCE, newest first.
File Type Posted
Amendment 1.docx DOCX document
SOLICITATION.docx DOCX document
Amendment 2.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Regions 1 & 3

SCDEW EQUIPMENT LISTING BY REGION
Designation/TypeManufacturerModel NumberSerial NumberFiltersV-beltsTonsAgeLifeRepairs found in need
REGION # 1 - GREENVILLE
C/U # 1 - Heat Pump Outdoor UnitTraneTWA120A300EB30912BEAD10200315Replace compressor contactor 60amp/240 v
A/H # 1 - Heat Pump Indoor UnitTraneTWE120A300EB3242YF35H4) 16X25X1A-5110200315Rebuilt blower assembly and leaking primary pans2015
C/U # 2 - Heat Pump Outdoor UnitTraneTWA120A300EB3214LNAd10200315T-stat needs moved into the Tax Office for proper control of unit
A/H # 2 - Heat Pump Indoor UnitTraneTWE120A300EB3242YE45H4) 16X25X1A-5110200315Replaced leaking primary drain pan
C/U # 3 - Heat Pump Outdoor UnitTraneBWA090C300MCC171961887.5198815Unit is beyond life expectancy
A/H # 3 - Heat Pump Indoor UnitTraneBWE090C400GAC171762292) 24X24X1A-517.5198815Air handling unit in poor condition crushed panels
C/U # 4 - Heat Pump Outdoor UnitTraneTWR024C100A2N2448P8CF2199815Replaced compressor June 2015
A/H # 4 - Heat Pump Indoor UnitTraneTWH736A140A0C093513651) 16X20X12198815Replaced leaking primary drain pan
C/U # 5 - Heat Pump Outdoor UnitTrane2TWB3024A1000AA81126N44F2200815
A/H # 5 - Heat Pump Indoor UnitTrane2TEC3F24B1000AA83526UT1V1) 20X20X12200815
C/U # 6 - Heat Pump Outdoor UnitGoodmanGSH101203AB80611112710200615Replaced outdoor unit May 2015 with new TXV's
A/H # 6 - Heat Pump Indoor UnitGoodmanAR1204AA1206336302)20X20X2 & 2)16X20X2AX-4110200615Air handling unit damaged on top from techs crawling over unit for access
C/U # 7 - Heat Pump Outdoor UnitGoodmanGSH130361BB9027502883200315Mis-matched condenser and air handling unit
A/H # 7 - Heat Pump Indoor UnitTraneTWE036C140B022717442V1) 20X20X13200215
C/U # 8 - Heat Pump Outdoor UnitGoodmanGSH101203AC110311379210200315
A/H # 8 - Heat Pump Indoor UnitGoodmanAR1204AA12060336372)20X20X2 & 2)16X20X2A-4110200615Air handling unit damaged on top from techs crawling over unit for access
REGION # 2 - NO LONGER APPLICABLE - PROPERTIES SOLD - THIS INFORMATION IS INCLUDED FOR CLARIFICATION ONLY
REGION #3- CATWABA/CHESTER - 764 WILSON STREET
C/U # 1 - Heat Pump Outdoor UnitCarrier38YCC048--5601502E031624200215Low refrigerant charge - need to perform leak search
A/H # 1 - Heat Pump Indoor UnitTraneTWH048A140a0C354414212) 20X20X14198815Mis-matched condenser and air handling unit
C/U # 2 - Heat Pump Outdoor UnitCarrier38ARZ008--5011805G100587.5200515
A/H # 2 - Heat Pump Indoor UnitTraneTWE090A300EL8194W7LBD4) 20X20X1A-487.5200815Mis-matched condenser and air handling unit
C/U # 3 - Heat Pump Outdoor UnitTraneTWA048A300A1C432974154198815Replaced leaking king valve Sept 2015
A/H # 3 - Heat Pump Indoor UnitTraneTWH048140AC254414222) 20X20X14198815
REGION #3- CATWABA/LANCASTER, 705 N. WHITE STREET
RTU # 1 - Package Heat PumpTraneWCD180B300DBK34102363D4) 20X25X2, 2) 20X20X2BX6215199315Replace (2) compressor contactors, disconnect too large
Disconnect too large and blades will not close. Need to replace

&R&"Arial,Bold"&8APPENDIX 1

Region 4 & 5

Designation/TypeManufacturerModel NumberSerial NumberFiltersV-beltsTonsAgeLifeRepairs found in need
REGION # 4 - PEE DEE/FLORENCE - 1558 W. EVANS STREET
C/U # 1 - Heat Pump Outdoor UnitCarrier38ARQ012---5013304G5006010200415Replaced compressor June 2013
A/H # 1 - Heat Pump Indoor UnitCarrier40RMQ012---B611HC3304F513274) 16X24X2A-3910200415Leak search evaporator has slow leak
C/U # 2 - Heat Pump Outdoor UnitCarrier38ARQ012---5013004G2006210200415Replaced compressor June 2013
C/U # 2A - Heat Pump Outdoor UnitCarrier38AQS016---5413504F54760142004152nd of (2) condensers. Replace compressor contactor
A/H # 2 - Heat Pump Indoor UnitCarrier40RMQ028-B511GC4304X019254)20X24X2, 4) 20X25X22) BX4215200415
REGION # 4 - PEE DEE/BENNETTSVILLE - 460 HWY, 9 WEST CHERAW HWY
C/U # 1 - Heat Pump Outdoor UnitCarrier38ARQ008--5010908G400937.5200815Compressor contactor needs to be replaced
A/H # 1 - Heat Pump Indoor Unit4) 20X20X17.5???Very old air handling unit on this system but cooling properly
C/U # 2 - Heat Pump Outdoor UnitTrane4TWB3036C100AB14382T3KBF3201415Compressor contactor needs to be replaced
A/H # 2 - Heat Pump Indoor Unit2) 20X20X13
C/U # 3 - Heat Pump Outdoor UnitBryant661CP036-C3300E241983200115Replaced defrost board & sensor March 2015
A/H # 3 - Heat Pump Indoor Unit2) 20X20X1
C/U # 4 - Heat Pump Outdoor UnitBryant661CP048-E2100E176694200115Compressor contactor needs to be replaced
A/H # 4 - Heat Pump Indoor Unit2) 20X20X1
C/U # 5 - Heat Pump Outdoor UnitTrane4TWA3036B0000AA15054UB34F3201515NEW INSTALLATION March 2015
A/H # 5 - Heat Pump Indoor UnitTraneGAM2A0A36531SEA15071758BV2) 20X20X13201515NEW INSTALLATION
REGION # 4 - PEE DEE/MARION - 2413 EAST HWY 76
C/U # 1 - Heat Pump Outdoor UnitTraneTWA090A300FB6114PHFAD7.5200615Replace compressor contactor and service disconnect
A/H # 1 - Heat Pump Indoor UnitYorkFCHP5090AANEC50133814) 16X25X1A-367.5199415
C/U # 2 - Heat Pump Outdoor UnitTraneTWA090A300FB11015WW3YA7.5201115Compressor contactor needs to be replaced
A/H # 2 - Heat Pump Indoor UnitTraneTWE090D300AA01486TPABA3) 16X25X1A-497.5201015
REGION # 5- WACCAMAW/CONWAY -
RTU # 1 - Packaged AC UnitTraneTCH600AE0E0E2BLESC00G2024217) 16X20X22) BX-9550200020Replace compressor and blower motor contactors
C/U # 2 - Split AC condensing unitTraneTTA036D300A0R253P6E3F3200115Compressor contactor needs to be replaced
A/H # 2 - Split AC air handling unitTraneTWE042C140C0R343AG21V1) 20X20X13200115Mismatched unit, 3 ton condeenser with 3.5 ton air handling unit
REGION # 5- WACCAMAW/KINGSTREE - 530 MARTIN LUTHER KING JR. AVE
C/U # 1 - Heat Pump Outdoor UnitGoodmanGSH1000903AB90727394510200915Replace compressor contactor and thermostat (out of calibration)
A/H # 1 - Heat Pump Indoor UnitTraneTWE090A300BBL212X6C5H3)16X25X1A-377.5199515Mismatched unit, 7.5 ton air handler and 10 condensing unit
C/U # 2 - Heat Pump Outdoor UnitTraneTWA048C300A3L313KYLHF4199515Replace compressor contactor and thermostat (out of calibration)
A/H # 2 - Heat Pump Indoor UnitTraneTWE063P130A0K228317671) 20X25X15199415Mismatched unit, 4 ton condenser and 5 ton air handling unit
C/U # 3 - Heat Pump Outdoor UnitTraneTWA090A300BBL164LLKAH7.5199515Replace compressor contactor and thermostat (out of calibration)
A/H # 3 - Heat Pump Indoor UnitTraneTWE090A300BBL212KJK5H3)16X25X2A-477.5199515

Region 7 & 8

Designation/TypeManufacturerModel NumberSerial NumberFiltersV-beltsTonsAgeLifeRepairs found in need
REGION # 7 - LOW COUNTRY/BEAUFORT - 164 CASTLE ROCK ROAD
PKG # 1 - Package AC unitLuxaireDU-20C00PTTACIDNOE78240925199615Circuit # 1 - low on refrigerant need to search
PKG # 2 - Package AC unitLuxaireDL05C0PTTAC2ANOE78383872) 14X14X1, 1) 20X30X15199615
REGION # 8 - LOWER SAVANNAH/AIKEN - 1571 RICHLAND AVE. E.
C/U # 1 - Heat Pump Outdoor UnitTraneTWA048A140A0C153784724198815Replace defective service disconnect at unit
A/H # 1 - Heat Pump Indoor UnitTraneTWE048A300A1C192797883) 20X20X14198815Has no auxiliary heat strip package
C/U # 2 - Heat Pump Outdoor UnitTraneTWA036A300A0C212981493198815Replace defective service disconnect at unit & crankcase heater
A/H # 2 - Heat Pump Indoor UnitTraneTWH736A140A0C224017752) 21X21X13198815Has no auxiliary heat strip package
C/U # 3 - Heat Pump Outdoor UnitGoodmanGSH0903BA13071371357.5201315
A/H # 3 - Heat Pump Indoor UnitTraneBWB090C400GAC201765762) 21X21X1A-487.5198815Electric auxiliary heat strips will not come on from thermostat
C/U # 4 - Heat Pump Outdoor UnitTraneTWA036A300A0C212981573198815
A/H # 4 - Heat Pump Indoor UnitTraneTWH736A140A0C224017782) 21X21X13198815T-stat located in conference room but away from return in lobby
C/U # 5 - Heat Pump Outdoor UnitTrane4TWA3036A3000CA1350PCD4P3201315
A/H # 5 - Heat Pump Indoor UnitTraneTAM4A0A36531SCA133342NKAV2) 21X21X13201315
REGION # 8 - LOWER SAVANNAH/BARNWELL - 248 WALL STREET
PKG # 1 - Package Heat PumpCarrier50JS-060-3013504G506281) 24X30X15200415
C/U # 2 - Heat Pump Outdoor UnitCarrier38YCC030403304E315932.5200415
A/H # 2 - Heat Pump Indoor UnitCarrierNO DATA TAG1) 20X25X12.5
REGION # 8 - LOWER SAVANNAH/ORANGEBURG - 1804 JOE. S. JEFFORDS HWY
PKG # 1 - Gas Package UnitCarrier48AYM030-DQ731441504F2667310) 20X24X22) 5VX53030200415No repairs needed
PKG # 2 - Package AC unitCarrier48TCDA09A2A5A0A0A01012G102934) 20X20X2A-487.5201215No repairs needed

Region 9, 10 & 11

Designation/TypeManufacturerModel NumberSerial NumberFiltersV-beltsTonsAgeLifeRepairs found in need
REGION # 9 - UPPER SAVANNAH/ABBEVILLE - 353 HWY 28 BYPASS
C/U # 1 - Heat Pump Outdoor UnitICPCHC048HCBE0402159794200415
A/H # 1 - Heat Pump Indoor UnitCarrierFB4ANA0481192H077161) 20X20X14199215
C/U # 2 - Heat Pump Outdoor UnitTraneTWA090A300BCR151TD5AH7.5200115
A/H # 2 - Heat Pump Indoor UnitTraneTWE090A300CAR1812NK5H3) 16X25X1A-487.5200115
C/U # 3 - Heat Pump Outdoor UnitGoodmanGSH130481AD7112052454200715
A/H # 3 - Heat Pump Indoor UnitCarrierFB4ANA0481192h077181) 20x20x14199215Drain pan and air handling unit in poor condtion, should be replaced
REGION # 9 - UPPER SAVANNAH/LAURENS COUNTY - 18 HAZEL DRIVE CLINTON
C/U # 1 - Heat Pump Outdoor UnitRheemRPKA-060JAZ5779 M1698 154685199815ROY LOWE INDICATED THAT CONDENSER COIL IS LEAKING, ENTIRE SYSTEM SHOULD BE REPLACED (TWINNED DUCT SYSTEM)
A/H # 1 - Heat Pump Indoor UnitRheemRBHA-24J215HBAT-M1098 046541) 20X25X15199815
C/U # 2 - Heat Pump Outdoor UnitNordyneGT3BA-060CAGTA0601000895200115
A/H # 2 - Heat Pump Indoor UnitLennoxCB29M-065-1P5800H056931) 20X20X15200015SHARES DUCT SYSTEM WITH A/H FOR UNIT # 1
C/U # 4 - Mini-split Outdoor UnitHitachiDATA TAG NOT LEGIBLE10Unit is not running at this time. remote control not working
A/H # 4 - Mini-split Indoor UnitHitachiRAS-3189JH218784NKF210
REGION # 10 - WORKLINK/ANDERSON - 309 W WHITNER STREET (CURRENTLY VACANT)
RTU # 1 - Gas Package UnitCarrier48TMD016--511DA4409U235512) 20X20X2, 6) 16X20X2BX-4814200920No power on building to test units
RTU # 2 - Gas Package UnitTraneYCD120B360BAG4614257106) 16X20X2A-6110199215No power on building to test units
C/U # 3 - Split AC condensing unitTraneTTA060C300H0H022961225199315No power on building to test units
A/H # 3 - Split AC Gas FurnaceTraneTUD120C960A1G335062002) 20X20X15199215No power on building to test units
REGION # 11 - SANTEE-LYNCHES/SUMTER - 29 E. CALHOUN STREET
C/U # 1 - Heat Pump Outdoor UnitGoodmanGSH1300361CD13070711583200715Mismatched C/U 3 ton, AH 4 ton
A/H # 1 - Heat Pump Indoor UnitLennoxCBS18-51-3P5189F942212) 21X21X14198915
C/U # 2 - Heat Pump Outdoor UnitTraneTWA090A300BBL21414JAH7.5199715
A/H # 2 - Heat Pump Indoor UnitLennoxCPH17-95V-1NOT AVAILABLE4) 21X21X1AX-327.5198915Replace worn bearings in air handling unit
C/U # 3 - Heat Pump Outdoor UnitGoodmanGSH1301361CD13070111563200715
A/H # 3 - Heat Pump Indoor UnitLennoxCBS18-41-3PNOT AVAILABLE2) 21X21X13.5198915
C/U # 4 - Heat Pump Outdoor UnitLennoxHP29-048-7Y5806M015774200615
A/H # 4 - Heat Pump Indoor UnitLennoxCPS18-41-3P5189G737662) 21X21X14198915Replace worn bearings in air handling unit
C/U # 5 - Heat Pump Outdoor UnitCarrier25HBC336A--5001012E003843201215
A/H # 5 - Heat Pump Indoor UnitCarrierFB4CNF0422912A896713) 21X21X13.5201215