EDENVILLE 30% DESIGN_PROGRESS 20-10-9_Part3.pdf
PDF 5 MB Posted
- Attached to
- 761/21007. SAR; Eden Dam Modifications & Stabilization Meas State and local contract opportunity
- Solicitation number
- RFI 171 210000000002 2
- Issued by
- Gogebic County, Edmore Village, Michigan
About this file
This is a 30% design progress document for the Edenville/Tittabawassee River Restoration project, prepared by AECOM, a consulting firm based in Greenwood Village, Colorado. The project encompasses comprehensive river restoration efforts along the Tittabawassee River downstream, including channel profile modifications, bank stabilization, and habitat enhancement. The design documents detail multiple restoration components: rock riprap bank protection on left and right banks, excavated scour pools for habitat creation, large wood placement with root wads for structural stability, fabric encapsulated soil (FES) lifts for bank construction, live stake plantings for vegetation establishment, and cascade/step-pool grading sequences. The project specifications include riprap placement extending to elevation 635 feet or the top of bank (whichever is greater), with heavy riprap consisting of natural stone or broken concrete sized 16 inches minimum. Channel restoration details specify pool depths of 3 to 3.5 feet average, constructed bars adjacent to pools, slope terracing with logs and native seed mixes, and floodplain large wood installation coordinated with government representatives. All site-specific construction details including scour pool excavation depths and final configuration of habitat features are to be determined by the government representative at the time of construction.
The design documentation includes detailed construction sequencing, material specifications, and quality standards aligned with MDOT (Michigan Department of Transportation) standards and ACI (American Concrete Institute) requirements for reinforced concrete elements, including specifications for reinforcement splicing, clear cover requirements, and construction joint preparation. The project incorporates sustainable design practices with emphasis on native materials, live vegetation integration, and habitat restoration principles. Fabric materials include woven and non-woven coir fabrics for slope stabilization with stake and staple spacing requirements documented at 3-foot and 18-inch centers respectively. The design also addresses spillway construction elements with reinforced concrete slabs, stepped configurations, and waterstop details for the Tobacco Spillway component. Documentation indicates the design was last updated October 7-9, 2020, with project management oversight and multi-disciplinary consultant involvement.
View the file
Other files for this state and local contract opportunity
| File | Type | Posted |
|---|---|---|
| EDENVILLE 30% DESIGN_PROGRESS 20-10-9_Part2.pdf | ||
| RFI .pdf | ||
| EDENVILLE 30% DESIGN_PROGRESS 20-10-9_Part1.pdf | ||
| Addendum 1 21007.pdf | ||
| Request for Qualifications.pdf | ||
| Midland DC 20201007 (003).pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
E L
E V
A T
I O
N
F
T
E L
E V
A T
I O
N
F
T
STATION (FT)
31+00 32+00 33+00 34+00 35+00 36+00 37+00 38+00 39+00
SEDIMENT PLUG
0.00%
P V
I
S
T A
E L
V
P V
I
S
E L
V
00 40' 80'
KEY PLAN
REGISTRATION
CONSULTANTS
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
CONSULTANT
AECOM
6200 South Quebec Street
Greenwood Village, Colorado 80111
T 303.694.2770 F 303.694.3946 www.aecom.com
CLIENT
OWNER/CLIENT
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
PROJECT
Line #1
Line #2
Line #3
(FACILITY NAME)
Address Line 1
Address Line 2
PROJECT NUMBER
A N
S I
D x
SHEET TITLE
TITTABAWASSEE RIVER
RESTORATION PROFILE
SHEET NUMBER
R-203
L a s t s a v e d b y
M
I K
E S
T O
N E a s t
P l o t t e d
P r o j e c t
M a n a g e m e n t
I n i t i a l s
D e s i g n e r
C h e c k e d
A p p r o v e d
F i l e n a m e
C
P
W W
O R
K I N
G A
E C
O M
D
S
N A
D
M S
C
S
P T
I T
T A
B A
W A
S S
O W
N S
T R
E A
M D
W G
I/R DATE DESCRIPTION
ISSUE/REVISION
TITTABAWASSEE DOWNSTREAM CHANNEL PROFILE
1" = 40'
ROCK RIPRAP DETAIL
NOT TO SCALE
M
I N
2' MIN.
SEE STATION AND OFFSET
POINT SHOWN IN SECTION
EXISTING GROUND LINE
M
N
H
I
C
K
N
E
S
S
RIPRAP TO EXTEND TO
TOP OF BANK OR ELEV.
635 OR WHICHEVER IS
GREATER
SEE NOTE 3
NOTES:
1. RIP RAP SHALL BE 2:1 HEAVY TO PLAIN.
2. ROCK RIP RAP SHALL BE PLACED ON LEFT AND
RIGHT BANK.
3. MDOT HEAVY RIP RAP (HEAVY - NATURAL STONE
OR BROKEN CONCRETE - LENGTH OR WIDTH
MUST BE 16 INCHES (400 MM). RATIO OF 3 TO 1
FOR MAXIMUM TO MINIMUM DIMENSION. HEAVY
PRECAST MUST BE 16 INCHES (400 MM) THICK
AND 20 SQUARE FEET (1.75 M2) SURFACE AREA.
STONE SHOULD BE SOUND, DURABLE ROCK OR
SOUND PIECES OF BROKEN CONCRETE WITHOUT
EXPOSED STEEL REINFORCEMENT.)
4. MDOT PLAIN RIP RAP (PLAIN - NATURAL STONE OR
BROKEN CONCRETE - LEAST DIMENSION MUST BE
8 INCHES (1200 MM). PLAIN PRECAST MUST BE 6
INCHES (150 MM) THICK AND 15 SQUARE FEET (1.5
M2) SURFACE AREA.)
R
EXCAVATED SCOUR
POOL (NOT IN ALL
LOCATIONS)
SLASH
EXCAVATED SCOUR POOL
(NOT IN ALL LOCATIONS)
NATIVE MATERIAL
LARGE WOOD WITH
ROOT WAD, TYP.
10 FT (MIN.)
BELOW SUBGRADE
FINISH
GRADE
ALLUVIAL FILL
BF ELEV
OLW
EXISTING GRADE
LARGE
WOOD
LOG PILE, CUT
AT BF ELEV
2X LOG
DIAMETER (MIN.)
EMBED 1/2 LOG
LENGTH (MIN.)
20% CHANNEL
WIDTH (MAX.)
4.5 FT (MAX.)
6 FT (MAX.)
NOTE: SCOUR POOL EXCAVATION DEPTH
VARIES BY SITE, AND WILL BE DETERMINED
BY GOVERNMENT REPRESENTATIVE AT TIME
OF CONSTRUCTION.
EMBED 1/2 LOG (MIN.)
LARGE WOOD WITH ROOT WAD
20% CHANNEL WIDTH (MAX.)
BANK TOP
BANK TOE
20-100 FT
6 FT (MAX.)
LOG PILE, TYP.
NOTES:
1. LARGE WOOD IS A FIELD SET ITEM, TO BE INSTALLED WITH ASSISTANCE
OF ENGINEER. AT EACH LOCATION, ENGINEER MAY ADJUST
ORIENTATION, NUMBER OF LARGE WOOD PIECES, DEPTH OF
INSTALLATION, NUMBER OF CONNECTIONS, AND BALLAST
REQUIREMENTS AT THE TIME OF CONSTRUCTION.
2.
CU. YD. OF LOOSE PACKED VOLUME SLASH REQUIRED PER LARGE
WOOD OR LARGE WOOD-ROOT WAD PIECE INSTALLED (MAX.).
3. SCOUR POOL EXCAVATION SHALL NOT OCCUR IN LOCATIONS WHERE
CLAY IS PRESENT IN THE CHANNEL BED.
BF ELEV = BANKFULL ELEVATION
OLW = ORDINARY LOW WATER ELEVATION
2-YR FLOOD WATER SURFACE
ORDINARY LOW WATER SURFACE
EXISTING GRADE
5.5 FT
1 FT (MIN.)
CONNECTIONS AT ALL LOGS,
SEE DETAIL 8
10 FT (MIN.)
PACK SLASH
BETWEEN LOG
LAYERS
EMBED 2/3 LOG
LENGTH (MIN.)
SALVAGED
FILL
SET LOGS PARALLEL TO CHANNEL
AT OR BEHIND BANK TOP
LOG, TYP.
LOG PILE, TYP.
LOG WITH ROOT WAD, TYP.
CHANNEL BANK
NATIVE MATERIAL OR BACKFILL
R
SLASH
25-YR FLOOD WATER SURFACE
FRONT 10 FEET OF BACKFILL SHALL BE
SALVAGED GRAVEL AND COBBLE
NATIVE SUBSTRATE
LOG PILE - EMBED 10 FT
(MIN.) BENEATH SUBGRADE
6 FT (MAX.)
20% CHANNEL
WIDTH (MAX.)
EXCAVATED
SCOUR
POOL
FINISH GRADE
FLOW
20-40 FT
3.5 FT AVG.
30-40 FT
6.5 FT AVG.
TYPICAL SECTION
LARGE WOOD CRIB
NOT TO SCALE
R-301
TYPICAL SECTION
HABITAT JAM
NOT TO SCALE
R-301
TYPICAL PLAN
HABITAT JAM
NOT TO SCALE
R-301
TYPICAL PLAN
LARGE WOOD CRIB
NOT TO SCALE
R-301
LARGE WOOD, TYP.
TYPICAL DETAIL
CABLING
NOT TO SCALE
R-301
TYPICAL DETAIL
BOLTED CONNECTION
R-301
TYPICAL DETAIL
CABLING
NOT TO SCALE
R-301
TYPICAL DETAIL
CABLE CONNECTION
NOT TO SCALE
R-301
R
EXCAVATED SCOUR
POOL (NOT IN ALL
LOCATIONS)
SLASH
LARGE WOOD WITH
ROOT WAD, TYP.
EMBED 1/2 LOG
LENGTH (MIN.)
20% CHANNEL
WIDTH (MAX.)
6 FT (MAX.)
20% CHANNEL WIDTH (MAX.)
B
A
K
P
B
A
K
E
20-100 FT
6 FT (MAX.)
FLOW
TYPICAL PLAN
UPLAND FILL LOG AND SLASH COVER
NOT TO SCALE
R-301
LARGE WOOD, TYP.
EXCAVATED SCOUR POOL
(NOT IN ALL LOCATIONS)
NATIVE MATERIAL
10 FT (MIN.)
BELOW SUBGRADE
FINISH
GRADE
ALLUVIAL FILL
BF ELEV
OLW
EXISTING GRADE
LARGE
WOOD
LOG PILE, CUT
AT BF ELEV
2X LOG
DIAMETER (MIN.)
4.5 FT (MAX.)
NOTE: SCOUR POOL EXCAVATION DEPTH
VARIES BY SITE, AND WILL BE DETERMINED
BY GOVERNMENT REPRESENTATIVE AT TIME
OF CONSTRUCTION.
EMBED 1/2 LOG (MIN.)
LARGE WOOD WITH ROOT WAD
20-40 FT
3.5 FT AVG.
TYPICAL SECTION
UPLAND FILL LOG AND SLASH COVER
NOT TO SCALE
R-301
UPDATE PER JASON'S EMAIL
KEY PLAN
REGISTRATION
CONSULTANTS
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
CONSULTANT
AECOM
6200 South Quebec Street
Greenwood Village, Colorado 80111
T 303.694.2770 F 303.694.3946 www.aecom.com
CLIENT
OWNER/CLIENT
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
PROJECT
Line #1
Line #2
Line #3
(FACILITY NAME)
Address Line 1
Address Line 2
PROJECT NUMBER
Project Number
A N
S x
SHEET NUMBER
R-301
L a s t s a v e d b y
M
I C
H A
E L
R
A U s t
P l o t t e d
P r o j e c t
M a n a g e m e n t
I n i t i a l s
D e s i g n e r
C h e c k e d
A p p r o v e d
F i l e n a m e
C
P
W W
O R
K I N
G A
E C
O M
D
S
N A
D
M S
R
I V
S
T O
R A
T I O
N
D
E T
A I L
S D
W G
I/R DATE DESCRIPTION
ISSUE/REVISION
SHEET TITLE
RIVER RESTORATION DETAILS
DRIVEN POSTS
STOP LOGS
RIVER
4 - 12 SLOPE DISTANCE
4 - 12 SLOPE DISTANCE
TOP OF RIPRAP
PROTECTION
DRIVEN POSTS
STOP LOGS
3'
TOP OF BANK
SLOPE DISTANCE
(X)
X TO
X
8' LOGS
4'
COMPOST/TOPSOIL/MULCH
MIX COVERED WITH SLASH
LIVE STAKE VEGETATION
1 L
3/4 L
1/2 L
1/4 L
1/8 L
TAILOUT
1/2 L
POOL
1/4 L
3/4 L
1 L
RIFFLE
1/8 L
1/4 L
1/2 L
3/4 L
1 L
58 FT
3.0 FT TO 5 FT VAIRES
LOW FLOW WATER SURFACE
CHANNEL BED
CHANNEL GRADING DETAIL
NOTES:
CONTOUR INTERVAL = 1.0 FT
L = LENGTH OF CHANNEL BEND FROM START TO
END OF RADIUS ALONG CHANNEL CENTERLINE, AS
DEFINED BY THE GOVERNMENT REPRESENTATIVE
AT THE TIME OF CONSTRUCTION
MATERIAL EXCAVATED FROM POOL WILL BE USED
TO BUILD A LATERAL BAR ADJACENT TO THE POOL
CHANNEL BANK TOP, TYP.
PROFILE
SECTION SEQUENCE
PLAN
TYPICAL DETAIL
CHANNEL FINE GRADING
NOT TO SCALE
R-302
F
L
O
W
2:1 SIDE SLOPES
MAX. POOL DEPTH 3 FT
TOP OF BANK (UNDISTURBED)
NOT TO SCALE
R-302
SLOPE ESTABLISHMENT TERRACING NOTES
1. USING NATURAL, ROUND, HARDWOOD POSTS, STAKE LOGS AND BRUSH ON LOOSE
SOIL SLOPES TO AID IN STABILIZING MOVING SOIL. LOGS COMPRISED OF
UNTREATED PINE BACKING LOGS (PER SPECIFICATIONS) 6" - 8" IN DIAMETER, 8'
LENGTHS, STACKED 2-3 LOGS HIGH, ACCORDING TO SLOPE.
2. STAKE LOG SECTIONS APPROXIMATELY 4' APART ALONG TERRACE.
3. PLACE COMPOST/TOPSOIL/MULCH MIX AND SLASH BEHIND LOGS TO TERRACE
SLOPE, UP TO SECOND LOG. PLACE SLASH ON TOP OF SOIL MIX TO PREVENT
EROSION AND LEVEL SLOPE BEHIND LOGS.
4. SEED EXPOSED SLOPE AREAS WITH ANNUAL RYE.
5. BLOW IN STRAW MULCH FOR FINAL COVER AND SOIL EROSION PREVENTION.
6. SLOPE TERRACING WILL BE PAID FOR BY SQUARE YARD DUE TO VARIATION IN SITE
SLOPES, LOGS LENGTHS, AND AVAILABLE MATERIALS.
TYPICAL PROFILE
FLOODPLAIN LARGE WOOD
NOT TO SCALE
R-302
NOTE:
FLOODPLAIN LARGE WOOD TO BE INSTALLED WITH
ASSISTANCE OF GOVERNMENT REPRESENTATIVE
TO CONFIRM FINAL EXTENTS CONFIGURATION.
TYPICAL SECTION
CASCADE / STEP-POOL GRADING
R-302
KEY PLAN
REGISTRATION
CONSULTANTS
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
CONSULTANT
AECOM
6200 South Quebec Street
Greenwood Village, Colorado 80111
T 303.694.2770 F 303.694.3946 www.aecom.com
CLIENT
OWNER/CLIENT
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
PROJECT
Line #1
Line #2
Line #3
(FACILITY NAME)
Address Line 1
Address Line 2
PROJECT NUMBER
Project Number
A N
S x
SHEET NUMBER
R-302
I/R DATE DESCRIPTION
ISSUE/REVISION
LEG WIDTH 0.6"
TAPERED TO POINT
STAPLE
THICKNESS 0.4"
WOODEN STAKE AND STAPLES
FABRICATING DETAIL
NOT TO SCALE
2 X 4 STUD CUT
TO 18" LONG
FINISHED STAKES
1 FT MIN.
2 FT MIN.
KEY TRENCH DETAIL
TERMINATION TRENCH
NOT TO SCALE
1 FT MIN.
2 FT MIN.
KEY TRENCH DETAIL
TRANSITION TRENCH
NOT TO SCALE
TOE DETAIL
BIODEGRADABLE FABRICS AND STAKES
NOT TO SCALE
GENERAL NOTES ON SECURING COIR FABRIC
1. SECURE THE OUTER FABRIC (WOVEN, WHERE APPLICABLE), WITH A WOODEN STAKE THROUGH THE
FABRIC ON 3 FT CENTERS (SEE DETAIL VIEW 2)
NOTE: THE HOLES FOR STAKES SHALL NOT BE PRECUT. ALLOW THE STAKE TO BREAK THE MINIMUM
NUMBER OF STRANDS AS IT IS BEING DRIVEN IN. DRIVE STAKES SO THAT 2" TO 3" OF THE TOP OF THE
STAKE IS LEFT EXPOSED.
2. OUTER FABRIC ENDS SHALL BE JOINED BY LAPPING THE UPSTREAM PIECE OF FABRIC OVER THE
DOWNSTREAM PIECE AS SHOWN IN SECTION B-B. OVERLAPS SHALL BE A MINIMUM OF 3 FT, INNER FABRIC
ENDS SHALL BE BUTTED TOGETHER, NOT OVERLAPPED. OVERLAPS SHALL BE STAGGERED FROM LIFT TO
LIFT BY A MINIMUM OF 15 FT.
3. STAKE AND STAPLE SPACING IS DEFINED IN SPECIFICATIONS FOR FES LIFT AND SURFACE FABRIC.
3/4" PLYWOOD
8 FT
F
M
A X
90°
2 FT
TYPICAL DETAIL
STREAM BANK CONSTRUCTION FORM - FES LIFT
NOT TO SCALE
90°
TYPICAL DETAIL
STREAM BANK CONSTRUCTION FORM - FES LIFT
NOT TO SCALE
F
T
3 FT
1.
2.
3. 4. 5.
6.
1 - 1.5 FT
SUGGESTED CONSTRUCTION SEQUENCE
FES LIFT - BOX ENDS
NOT TO SCALE
3 FT
GENERAL INSTRUCTIONS FOR FABRIC ENCAPSULATED LIFTS (FES)
1. BANKS MAY BE CONSTRUCTED IN EITHER AN UPSTREAM OR DOWNSTREAM DIRECTION, AS
LONG AS THE FABRIC IS OVERLAPPED IN THE PROPER DIRECTION.
2. PLACE A SERIES OF THREE OR MORE FORMS ON THE GROUND SO THAT THE FORMS FOLLOW
THE PROPOSED STREAM BANK ALIGNMENT. BUTT THE ENDS OF THE FORMS TIGHTLY
TOGETHER. SEE TYPICAL DETAIL:
3. UNROLL THE OUTER FABRIC PARALLEL TO THE LONG AXIS OF THE CHANNEL AND POSITION IT
SO THAT 3 FEET EXTENDS FOR EMBEDMENT ON THE BANK SIDE OF THE FORMS (FIG B), AND A
MINIMUM 3 FEET EXTENDS LENGTHWISE BEYOND THE LAST FORM FOR OVERLAP. DRAPE THE
REMAINDER OF THE FABRIC OVER THE TOP OF THE FORMS ON THE STREAM SIDE (FIG B).
4. UNROLL THE INNER FABRIC OVER THE TOP OF THE WOVEN COIR FABRIC (FIG B) AND POSITION
IT SO THAT AT LEAST 1 FOOT OF THE INNER FABRIC EXTENDS AS AN EMBEDMENT LENGTH ON
THE BANK SIDE OF THE FORMS (FIG C). DRAPE THE REMAINDER OF THE FABRIC OVER THE TOP
OF THE FORMS ON THE STREAM SIDE AND ALIGN THE LONG EDGES OF THE FABRICS. STRETCH
AND PULL THE FABRIC LAYERS TO REMOVE WRINKLES.
5. APPLY NATIVE SEED MIX TO INNER FABRIC ALONG VERTICAL EDGE OF LIFT (FIG C). PLACE
SPECIFIED FILL OVER THE FABRIC ON THE BANK SIDE OF THE FORMS. LEVEL THE FILL AND
COMPACT TO 85-90 PERCENT RELATIVE COMPACTION (FIG C).
6. APPLY NATIVE SEED MIX TO TOP OF FILL FROM THE FRONT OF THE LIFT TO 3 FT BACK FROM
FRONT OF THE LIFT (FIG C).
7. FOLD THE LOOSE ENDS OF THE TWO COIR FABRIC LAYERS BACK OVER THE COMPACTED FILL
MATERIAL AND STRETCH TIGHTLY TO REMOVE WRINKLES. SECURE WITH WOODEN STAKES 1
PER 3 L.F. ALONG THE BACK EDGE AND INTO UNDISTURBED SOIL. PLACE LIVE CUTTINGS ON
TOP OF COMPLETED LIFT SO THAT BASAL END IS DIRECTED INTO THE BANK AND THE TOP
EXTENDS 0.5 TO 1 FOOT PAST THE FACE OF THE LIFT. SPREAD A THIN LAYER OF SOIL TO COVER
THE LIVE CUTTINGS PRIOR TO PLACING NEXT LAYER OF FABRIC. (FIG D)
8. REMOVE THE FORMS FROM THE FRONT OF THE COMPLETED LIFTS (FIG. H). LEAVE THE LAST
FORM IN PLACE AT THE END OF THE NEWLY CONSTRUCTED LIFT, SEE TYPICAL DETAIL:
9. REPEAT STEPS TWO THROUGH EIGHT UNTIL FINISH GRADES ARE ATTAINED.
10. WHERE THE TOP OF THE LIFT MEETS THE FINISH GROUND SURFACE, EXCAVATE A KEY TRENCH
1.5 FEET WIDE AND 1 FOOT DEEP ALONG THE BACK EDGE OF THE OUTER FABRIC LAYER,
PARALLEL TO THE FORMS. SEED ENTIRE AREA OF TOP LIFT. SECURE FABRIC IN THE KEY
TRENCH WITH WOODEN STAKES, 3 FT O.C.
11. BACKFILL THE KEY TRENCH WITH TOPSOIL AND CONTINUE TO APPLY TOPSOIL TO SMOOTHLY
MERGE WITH FINISH CONTOURS. APPLY NATIVE SEED MIX TO KEY TRENCH AREA.
12. SUPPLEMENT LIFT STAKING WITH ADDITIONAL WOODEN STAPLES ON 18" CENTERS EXCEPT
WHERE WOODEN STAKES HAVE ALREADY BEEN PLACED.
PROFILE VIEW LOOKING INTO BANK
FIG 1. PLACE A ROW OF CONSTRUCTION FORMS ALONG DESIRED
CHANNEL ALIGNMENT FOR FIRST FES LIFT.
FIG 2. CONSTRUCT FES LIFTS ALONG LENGTH OF FIRST SET OF FORMS
AND THEN BEGIN PLACEMENT OF FORMS AND CONSTRUCTION OF
SECOND LIFT.
FIG 3. STAGGER FABRIC OVERLAPS A MINIMUM OF 15 FT
BETWEEN LIFTS.
COMPLETED LENGTH OF FES LIFT
COMPLETED LENGTH OF FES LIFT
COMPLETED LENGTH OF FES LIFT
15 FT STAGGERS BETWEEN
CONSTRUCTION FORMS
3 FT EMBEDMENT FOR WOVEN (OUTER) FABRIC
1 FT EMBEDMENT FOR NON-WOVEN (INNER) FABRIC
APPLY SEED TO
FIRST 3 FT OF SOIL
APPLY SEED TO EXPOSED VERTICAL
AND HORIZONTAL AREAS OF LIFT
FIG B.
FIG D.
FIG H.
FIG A.
FIG F.
FIG G.
FIG C.
FIG E.
BANK SIDE STREAM SIDE
FILL KEY TRENCH WITH
TOPSOIL AND COMPACT
OVER COIR FABRIC
STAKE FABRIC TO
BOTTOM OF KEY TRENCH
EVERY 3 L.FT
FILL KEY TRENCH WITH
TOPSOIL AND COMPACT
OVER COIR FABRIC
WOVEN COIR FABRIC WRAP
WOVEN (OUTER)
COIR FABRIC
NON-WOVEN (INNER)
COIR FABRIC
NATIVE SEED MIX
FILL OR NATIVE SOIL
WOODEN STAKES
ON 3 FT CENTERS
1/4" LAG BOLT WITH
NUT AND WASHER
(TYPICAL)
1 " SQUARE
STEEL TUBING
UPRIGHT
1/4" X 2" STRAP
STEEL LEGS
RECTANGULAR
FRAME
1 " SQUARE
STEEL TUBING
1/4" LAG BOLT WITH
NUT AND WASHER
(TYPICAL)
WELDED JOINTS
(TYPICAL)
3/4" PLYWOOD BOLTED
TO STEEL FRAME
1/4" X 2" STRAP
STEEL LEG
EDGE OF
EXCAVATION CUT
EXISTING
STREAMBANK OR
ADJACENT
TREATMENT
WHERE PRESENT, EMBED FABRICS
INSTALLED ON ADJACENT SLOPE
BEHIND FES LIFTS
FES LIFT
EXCAVATION LIMIT
BOX END
SEQUENCE DETAIL
REMOVE SHADED
PORTION
NOTE: FES LIFT INNER FABRIC
SHOULD BE INSTALLED WITHIN BOTH
VERTICAL FACES OF THE BOX END
CONSTRUCTION
FORM
SEE DETAIL:
WOVEN COIR (OUTER FABRIC)
NON-WOVEN (INNER)
AND WOVEN (OUTER)
FABRIC
STAKE THROUGH BOTH LAYERS 6" BACK
FROM FRONT EDGE, SEE TOE DETAIL:
EXISTING GROUND
APPLY SEED TO
FABRIC FACE
FILL WITH TOPSOIL
FOLD BOTH INNER AND OUTER
FABRIC OVER SOIL
PLACE SECOND
CONSTRUCTION FORM SO
AS TO ACCOMMODATE
2H:1V
FILL WITH
TOPSOIL
FOLD BOTH INNER AND
OUTER FABRIC OVER SOIL
STAKE FABRICS IN PLACE ON 3
FT CENTERS. SEE FABRIC
STAKING DETAILS:
STAKE OUTER FABRIC IN
TERMINATION TRENCH. SEE
TRENCHING DETAILS:
AFTER INSTALLATION,
REMOVE CONSTRUCTION
FORM PRIOR TO
FLATTENING STREAM SIDE
OF LIFT TO 45°
PREPARE LEVEL SUB-GRADE PER
TYPICAL SECTION
PLACE FIRST STAKE
IMMEDIATELY IN FRONT OF
NEXT LIFT, OR 2' (IF 2:1) FROM
LIFT FACE IF THIS IS TOP LIFT
PLACE STAPLES ON 18" CENTERS. SEE FABRIC
STAKING DETAILS:
STAKES THROUGH
BOTTOM FABRIC
LAYER
DOWNSTREAM FABRIC LAYER LAPS UNDER
TYPICAL DETAIL
FABRIC JOINING
F
T M
IN
O V
E R
L A
P
F L O
W
NOT TO SCALE
B B'
F
L O
W
SECTION A - A'
FABRIC FOLD
NOT TO SCALE
STAKES 3 FT OC IN
STAGGERED ROWS
FLOW
CONSTRUCTION
FORM
STAKES THROUGH BOTH
FABRIC LAYERS
1 FT MIN
2 FT
KEY TRENCH
U P
S T
R E
A M
F A
B R
IC
L
A P
S O
V E
R
D O
W
N S
T R
E A
M
F A
B R
IC
L
A P
S U
N D
E R
ISOMETRIC DETAIL
FABRIC JOINING
NOT TO SCALE
UPSTREAM FABRIC
LAYER LAPS OVER BY 3 FT MIN.
45°
SECTION B - B'
FABRIC JOINING
NOT TO SCALE
FLOW
3 FT MIN. OVERLAP
STAKE THROUGH BOTTOM
FABRIC LAYER
STAKES THOUGH BOTH
FABRIC LAYERS
DOWNSTREAM FABRIC
LAYER LAPS UNDER
UPSTREAM FABRIC
LAYER LAPS OVER
INNER FABRIC TO BE
BUTTED TOGETHER
CONSTRUCTION
FORM
TYPICAL DETAIL
FOLDING OF OUTER FABRIC
NOT TO SCALE
FLOW
STAKES 3 FT OC IN
STAGGERED ROWS
A
A
ALL FABRIC FORMS WILL BE
LAPPED IN AN UPSTREAM TO
DOWNSTREAM DIRECTION
MAX. ANGLE 15°
FABRIC FOLD STAKES
1 FT
STAPLES 18 IN OC IN
STAGGERED ROWS
STAPLES 18 IN OC IN
STAGGERED ROWS
R-303
R-303
R-303
R-303
R-303
R-303
R-303
R-303
R-303
R-303
PLACE LIVE CUTTINGS UNDER
CONSTRUCTION FORM BENEATH
EACH LIFT ON OUTSIDE MEANDER
BANKS,
2 FT., ON AVERAGE
SUGGESTED SEQUENCE FOR PLACEMENT OF FORMS
NOT TO SCALE
R-303
INSTALLATION SEQUENCE AND INSTRUCTIONS
FOR FABRIC ENCAPSULATED SOIL LIFTS (FES)
NOT TO SCALE
R-303
R-303
R-303
R-303
+/- 1.5 FT
R-303
R-303
R-303
R-303
R-303
EDGE OF FABRIC 4 IN. (MIN.)
FROM STAKE
EDGE OF FABRIC 4 IN.
(MIN.) FROM STAKE)
STAKE FABRIC TO
BOTTOM OF KEY TRENCH
EVERY 3 L. FT
3 FT POOL DEPTH
5 FT
58 FT
FES LIFT, TYP.
SEE DETAIL:
TERMINATION TRENCH, TYP.
FINISH GRADE
NATIVE
MATERIAL
3.0 FT
3.5 FT
CHANNEL BED MATERIAL,
SEE SPECS.
TYPICAL SECTION
CONSTRUCTED CHANNEL AND BANK TREATMENTS - RIFFLE
NOT TO SCALE
A
R-303
5 FT
58 FT
TERMINATION TRENCH, TYP.
CHANNEL BED MATERIAL, SEE SPECS.
TYPICAL SECTION
CONSTRUCTED CHANNEL AND BANK TREATMENTS - POOL AND BAR
NOT TO SCALE
B
R-303
RIFFLE GEOMETRY SHOWN
FOR REFERENCE
CONSTRUCTED
BAR
NOTE:
LOCATE POOL AT
OUTER SIDE OF BEND
LIVE CUTTINGS PLACED BETWEEN
FES LIFTS, 2 FT O.C. TYP.
R-3.3
C L
FLOODPLAIN FILL, TYP., SEE SPECS.
2.0 FT (MIN.)
EXISTING GRADE
FLOODPLAIN FILL, TYP., SEE SPECS.
2.0 FT (MIN.)
NATIVE MATERIAL
EXISTING GRADE
FES LIFT, TYP.
SEE DETAIL:
R-303
FINISH GRADE
3.5 FT
FES LIFT, TYP.
WITH REVIEW AND CONCURRENCE OF GOVERNMENT
REPRESENTATIVE, UTILIZE UNDISTURBED NATIVE
CHANNEL MATERIAL IN POOL BOTTOM IF EXISTING
AND DESIGN GRADES INTERSECT
LIVE STAKE PLANTING NOTES:
1. THE LENGTH OF THE LIVE STAKES DEPEND UPON THE
APPLICATION. WHEN PLACED THROUGH RIPRAP, THE LENGTH
SHALL EXTEND THROUGH THE SURFACE OF THE STONE FILL. AT
LEAST HALF THE LENGTH SHALL BE INSERTED INTO THE SOIL,
BELOW THE STONE FILL.
2. A MINIMUM OF 2' TO 4' AND TWO LIVE BUDS OF THE LIVE STAKE
SHALL BE EXPOSED ABOVE STONE FILLING.
3. LIVE STAKES SHALL BE CUT TO A POINT ON THE BASAL END FOR
INSERTION INTO THE GROUND.
4. USE A DEAD BLOW HAMMER TO DRIVE STAKES INTO THE
GROUND. THE HAMMER HEAD SHOULD BE FILLED WITH SHOT OR
SAND. A DIBBLE, IRON BAR, OR SIMILAR TOOL SHALL BE USED
TO MAKE A PILOT HOLE TO PREVENT DAMAGING THE MATERIAL
DURING INSTALLATION.
5. LIVE CUTTINGS SHALL BE INSERTED BY HAND INTO PILOT
HOLES. LIVE STAKES SHALL REACH THE WATER TABLE.
6. WHEN POSSIBLE, TAMP SOIL AROUND LIVE STAKES.
7. CARE SHALL BE TAKEN NOT TO DAMAGE THE LIVE STAKES
DURING INSTALLATION. THOSE DAMAGED AT THE TOP DURING
INSTALLATION SHALL BE TRIMMED BACK TO UNDAMAGED
CONDITION.
STAKE SHOULD EXTEND ABOVE RIPRAP LAYER
AND HAVE AT LEAST TWO BUDS EXPOSED
ANGLE CUT 30° TO 45°
RIPRAP PROTECTION
NOT TO SCALE
R-303
LIVE STAKE PLANTINGS
NOT TO SCALE
R-303
KEY PLAN
REGISTRATION
CONSULTANTS
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
CONSULTANT
AECOM
6200 South Quebec Street
Greenwood Village, Colorado 80111
T 303.694.2770 F 303.694.3946 www.aecom.com
CLIENT
OWNER/CLIENT
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
PROJECT
Line #1
Line #2
Line #3
(FACILITY NAME)
Address Line 1
Address Line 2
PROJECT NUMBER
Project Number
A N
S x
SHEET NUMBER
R-303
I/R DATE DESCRIPTION
ISSUE/REVISION
GENERAL NOTE
REINFORCEMENT REQUIRING BENDING SHALL BE BENT AROUND A PIN HAVING
UNLESS OTHER RADIUS BENDS ARE INDICATED ON THE DRAWINGS, ALL
PARALLELING CONSTRUCTION JOINTS SHALL HAVE A MINIMUM OF 2" CLEAR COVER.
OR ROCK. CLEAR DISTANCE IS THE DESIGN DIMENSION LINE. REINFORCEMENT
CONCRETE FOR ALL BARS WHEN THE CONCRETE IS PLACED AGAINST EARTH
2" FOR #6 BARS AND LARGER. PROVIDE 3" CLEAR DISTANCE FROM FACE OF
CONCRETE AND NEAREST REINFORCEMENT IS 1 1/2" FOR #5 BARS AND SMALLER,
PLACE THE REINFORCEMENT SO THAT THE CLEAR DISTANCE BETWEEN FACE OF
DIMENSIONS ARE TO THE CENTERLINE OF THE BARS UNLESS OTHERWISE SHOWN.
SPLICES SHOWN THUS INDICATE A LAPPED SPLICE, NOT A BEND
A CLOSED CIRCLE AT THE END OF A BAR INDICATES A BEND WITH THE
AN OPEN CIRCLE AT THE END OF A BAR INDICATES A BEND WITH THE
TYPICAL BLOCKOUT RECESS OR OFFSET DETAILS
ADDITIONAL REINFORCEMENT AROUND OPENINGS
COVER
RECESS GREATER THAN 8"
ONE HALF COVER
RECESS 3" TO 8" DEEP
1"
BLOCKOUT CONCRETE
SECOND STAGE OR
e
L
90° HOOK
STIRRUP AND TIE BENDS
STANDARD BENDS
BAR NO.
10 3/4
9 1/2
5 1/4
5 1/4
4 1/2
4 1/2
3 3/4
2 1/2
1 1/2
2 1/4
PIN DIAMETER IN INCHES
THE FOLLOWING DIAMETER:
BENT BARS:
CLEAR COVER DIMENSIONS ARE MARKED "CL".
DIMENSIONS
BAR TURNED TOWARDS THE OBSERVER.
BAR TURNED AWAY FROM THE OBSERVER.
LAPPED SPLICE +B
SECOND STAGE OR
BLOCKOUT CONCRETE
SYMMETRICAL ABOUT CENTERLINE
e
L
COVER
IN THE BAR.
SYMBOLS
TABLE 2
SAME SIZE AS CORRESPONDING WALL OR SLAB BARS
EDGE BARS ACROSS THICKNESS OF MEMBER TO BE
1-CTR.
2-(1-EF)
SPC.@1'-0"
3-EQ. SPC.
EDGE BARS
TABLE FOR REINFORCEMENT AROUND OPENINGS
TIE
BARS
CORNER
e
L e
L
#6 @1'-0"
NONE
#4 @1'-0"
NONE
OVER 3'-0"
1'-7" THRU 3'-0"
10" THRU 1'-6"
LESS THAN 10"
TIE BAR
THICKNESS
MEMBER
CORNER
e
L
T
B
R
S
6" MAX.
1-#4 CTR.
2-#4 (1EF)
2-#8 (1EF)
2-#6 (1EF)
CORNER BARS
BAR
BARS
EDGE
e
L
L e e
L
BARS SPLICED BY NONCONTACT LAP SPLICES SHALL NOT BE SPACED TRANSVERSELY
THE BAR. RADIUS OF BEND TO BE AS SPECIFIED IN THE TABLE OF PIN DIAMETERS.
OF AT LEAST 6-BAR DIAMETERS BUT NOT LESS THAN 2 1/2" AT THE FREE END OF
ANCHORAGE ONLY SHALL HAVE EITHER A 90° OR 135° BEND PLUS AN EXTENSION
AND EXTENSIONS OF AT LEAST 12-BAR DIAMETERS. HOOKS FOR STIRRUP AND TIE
NOT LESS THAN 2 1/2" PARALLEL TO THE MAIN LEG OF THE BAR, OR 90° BENDS
HOOKS SHALL HAVE 180° BENDS AND EXTENSIONS OF 4-BAR DIAMETERS BUT
DEVELOPMENT LENGTHS GIVEN IN TABLE 3 ARE TO BE USED.
REQUIRED FOR #9, #10, AND #11 BARS IF SPLICE LENGTHS OR REDUCED
ANCHOR BOLTS OR OTHER EMBEDDED MATERIAL SHALL BE PLACED TO MAINTAIN
A CLEAR DISTANCE OF AT LEAST 1.33 TIMES THE MAXIMUM SIZE AGGREGATES.
CONCRETE WILL BE MAINTAINED.
TO BE MADE SO THAT THE REQUIRED CLEAR DISTANCES TO FACE OF CONCRETE
OF LAP SHALL BE GOVERNED BY THE SMALLER DIAMETER BAR. SPLICES ARE
WHEN REINFORCING BARS OF DIFFERENT SIZE ARE TO BE SPLICED, THE LENGTHS
FARTHER APART THAN ONE-FIFTH THE REQUIRED LAP SPLICE LENGTH, NOR 6 IN.
TO GIVE 12 INCHES CLEAR BETWEEN ENDS OF ADJACENT SPLICES.
IN THE APPLICABLE TABLE (TABLE 3). SPLICES SHALL BE STAGGERED
THE MINIMUM LENGTH OF LAP FOR SPLICING PARALLEL BARS SHALL BE GIVEN
ADJACENT BAR SPACING. A MINIMUM OF 2.5d CLEAR FROM THE EDGE IS
IN COLUMNS ARE TO START AND END AT A MAXIMUM OF ONE HALF OF THE
THE FIRST AND LAST BARS IN WALLS AND SLABS, STIRRUPS IN BEAMS, AND TIES
INCLINED PORTION MUST NOT EXCEED 6 TO 1. REINFORCEMENT PARALLEL TO
BARS ARE BENT DUE TO OFFSETS LESS THAN 3" DEEP, THE SLOPE OF THE
AREAS, RELOCATION OF THE EMBEDDED MATERIAL MUST BE CONSIDERED. WHEN
TIES, CONDUITS AND OTHER EMBEDDED MATERIALS. IN HEAVILY REINFORCED
BETWEEN THE REINFORCEMENT AND KEYS, WATERSTOPS, ANCHOR BOLTS, FORM
MAY BE ADJUSTED LATERALLY TO MAINTAIN A CLEAR DISTANCE OF AT LEAST 1"
SPREAD APART NOT MORE THAN 1.5 TIMES THE BAR SPACING. REINFORCEMENT
REINFORCEMENT AT SMALL OPENINGS (MAX. 1'-5") IN WALLS AND SLABS MAY BE
SPLICES:
STANDARD HOOKS:
SPACING:
PLACING:
FOR DETAILING REINFORCED CONCRETE STRUCTURES, ACI 315".
BE DETAILED ON THE REINFORCEMENT DESIGN DRAWINGS.
DEVELOPMENT LENGTHS OTHER THAN THOSE SHOWN IN THE TABLES MUST
CLASS B SPLICES IN ACCORDANCE WITH ACI 350-06. SPLICES OR
SPLICE LENGTHS SHOWN IN THE TABLES ON THIS DRAWING ARE FOR
NOTES TO DETAILERS:
BY THE AMERICAN CONCRETE INSTITUTE'S "MANUAL OF STANDARD PRACTICE
UNLESS OTHERWISE SHOWN FOLLOW THE RECOMMENDATIONS ESTABLISHED
MANUAL OR OTHER APPROVED SUPPORTING SYSTEM MAY BE USED.
THE DRAWINGS. THE RECOMMENDATIONS OF THE CURRENT ACI DETAILING
BAR SUPPORTS, SPACERS, AND OTHER ACCESSORIES ARE NOT SHOWN ON
VISCOSITY OF THE OIL SHALL HAVE A SAE RATING OF NOT LESS THAN 250.
UNIFORMLY COATED WITH A FILM OF OIL BEFORE CONCRETE PLACEMENT.
PLAIN DOWELS ACROSS CONTRACTION JOINTS SHALL BE SMOOTH BARS
EQUAL TO THAT REQUIRED FOR TOP SPLICING TO A BAR OF THE SAME
EMBEDDED A LENGTH EQUAL TO Le AND SHALL HAVE A PROJECTION
DOWELS INDICATED ON THE DRAWING, SUCH AS #8 (Db ), SHALL BE
REINFORCEMENT DOWELS:
90° HOOK
REFERENCE CODE:
ACCESSORIES:
PLAIN DOWELS:
DIAMETER.
B
TIE BARS
1. UNLESS OTHERWISE SHOWN ON THE REINFORCEMENT DESIGN DRAWINGS, THE
DETAILS AND NOTES SHOWN ON THIS DRAWING ARE TYPICAL FOR ALL
REINFORCEMENT DRAWINGS.
LAPPED SPLICE + B
b
1. OMIT EDGE BARS AND TIE BARS ALONG SIDES OF OPENINGS
WHERE DIMENSION IS LESS THAN 18".
2. OMIT CORNER BARS AT SIDES OF OPENINGS ADJACENT TO
FLOORS,WALLS, OR BEAMS.
3. CORNER BARS REQUIRED IF EITHER DIMENSION OF OPENING IS
GREATER THAN 18".
4. USE CORNER BARS IN FACE OF RECESSES DEEPER THAN 4" IF
EITHER DIMENSION OF RECESS IS GREATER THAN 8".
BAR
TABLE 1
EMBEDMENT
LENGTH, L
TABLE 3
(INCHES)
TOP BAR*
(INCHES)
OTHER BARS
SIZE
BAR
38 50
SPLICE LENGTH
CLASS B
1. THESE LENGTHS ARE BASED ON THE PROVISIONS OF ACI 350-06 CHAPTER 12 ASSUMING
UNCOATED REINFORCEMENT WITH YIELD STRESS OF 60,000 PSI, NORMAL WEIGHT
CONCRETE WITH 28-DAY COMPRESSIVE STRENGTH OF 4,000 PSI, CONCRETE COVER
CONSISTENT WITH THE REQUIREMENTS OF THIS DRAWING, AND MINIMUM CENTER TO
CENTER SPACING OF 6 d . CONDITIONS THAT ARE DIFFERENT FROM THOSE ASSUMED
REQUIRE LONGER LAP LENGTHS CONSISTENT WITH ACI 350-06.
e
(INCHES)
OTHER BARS
(INCHES)
TOP BAR*
* TOP BARS ARE HORIZONTAL BARS IN BEAMS AND SLABS SO PLACED THAT MORE
THAN 12" OF CONCRETE IS CAST IN THE MEMBER BELOW THE BAR.
**WHEN THE MINIMUM CLEAR BAR SPACING IS MET, STAGGERING OF SPLICES IS NOT
REQUIRED.
NOTES:
(SEE NOTE 1)
CLEAR
MINIMUM**
BAR SPACING
(INCHES)
2.5
4.5
5.5
8.5 b
A SECTION
NO SCALE
A
KEY PLAN
REGISTRATION
CONSULTANTS
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
CONSULTANT
AECOM
6200 South Quebec Street
Greenwood Village, Colorado 80111
T 303.694.2770 F 303.694.3946 www.aecom.com
CLIENT
OWNER/CLIENT
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
PROJECT
Line #1
Line #2
Line #3
(FACILITY NAME)
Address Line 1
Address Line 2
PROJECT NUMBER
Project Number
A N
S x
SHEET NUMBER
S-101
L a s t s a v e d b y
M
I C
H A
E L
R
A U s t
P l o t t e d
P r o j e c t
M a n a g e m e n t
I n i t i a l s
D e s i g n e r
C h e c k e d
A p p r o v e d
J B
M R
J S
F i l e n a m e
C
P
W W
O R
K I N
G A
E C
O M
D
S
N A
D
M S
S
S
R
U C
T U
R A
L
N
O T
E S
D
W G
I/R DATE DESCRIPTION
ISSUE/REVISION
STRUCTURAL NOTES
S
A N
D A
R D
H
O O
K
L E
G
T
Y P
SPLICE LENGTH
S T
A N
D A
H
O
K
L E
G
STD 90° HOOK
SPLICE LENGTH
S P
L I C
E
L E
N G
T H
SPLICE LENGTH
AT LEAST 48 HOURS SHALL
ELAPSE BETWEEN CASTING
OF ADJOINING MEMBERS
PVC WATERSTOP AS REQUIRED,
CONSTRUCTION JOINT (SEE NOTE 1 )
FILL SIDE OF WALL
STANDARD 90° HOOK
L WATERSTOP
C
NOTE: TIPS OF FINS MAY BE ROUNDED
6"
" ID &
" OD
M I N
M I N
SPLICE LENGTH
PVC WATERSTOP
(SEE NOTE 2)
OR CONTINUOUS
REINFORCEMENT
COAT W/APPROVED BOND
BREAKER
REINFORCEMENT IS CONTINUOUS
THROUGH JOINT AND MAY BE
SPLICED ON EITHER SIDE OF JOINT
AT LEAST 48 HOURS SHALL ELAPSE
BETWEEN CASTING OF ADJOINING
MEMBERS
PVC WATERSTOP
(SEE NOTE 2)
REINFORCEMENT IS CONTINUOUS THROUGH
JOINT AND MAY BE SPLICED ON EITHER SIDE
OF JOINT
SPLICE LENGTH
OR CONTINUOUS
REINFORCEMENT
SEE NOTE 1
AT LEAST 48 HOURS SHALL ELAPSE
BETWEEN CASTING OF ADJOINING
MEMBERS
PVC WATERSTOP
(SEE NOTE 2)
AT LEAST 48 HOURS SHALL ELAPSE
BETWEEN CASTING OF ADJOINING
MEMBERS
REINFORCEMENT IS NOT
CONTINUOUS THROUGH
JOINT
COAT W/APPROVED BOND
BREAKER
KEY PLAN
REGISTRATION
CONSULTANTS
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
CONSULTANT
AECOM
6200 South Quebec Street
Greenwood Village, Colorado 80111
T 303.694.2770 F 303.694.3946 www.aecom.com
CLIENT
OWNER/CLIENT
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
PROJECT
Line #1
Line #2
Line #3
(FACILITY NAME)
Address Line 1
Address Line 2
PROJECT NUMBER
Project Number
A N
S x
SHEET NUMBER
S-102
L a s t s a v e d b y
H
A M
B U
C H
G s t
P l o t t e d
P r o j e c t
M a n a g e m e n t
I n i t i a l s
D e s i g n e r
C h e c k e d
A p p r o v e d
J B
M R
J S
F i l e n a m e
C
P
W W
O R
K I N
G A
E C
O M
D
S
N A
D
M S
S
I N
F O
R C
E M
E N
T
D
E T
A I L
S D
W G
I/R DATE DESCRIPTION
ISSUE/REVISION
SHEET TITLE
REINFORCEMENT DETAILS
G-6
TYPICAL DETAIL AT WALL JUNCTION
NOT TO SCALE
DOUBLE MAT STEEL
G-6
TYPICAL DETAIL AT WALL CORNER
NOT TO SCALE
DOUBLE MAT STEEL
G-6
TYPICAL DETAIL AT WALL CORNER
NOT TO SCALE
SINGLE MAT STEEL
G-6
TYPICAL HORIZONTAL CONSTRUCTION JOINT
NOT TO SCALE
G-6
TYPICAL PVC WATERSTOP
NOT TO SCALE
TYPICAL WALL OR SLAB CONTROL JOINT
NOT TO SCALE
TYPICAL WALL OR SLAB CONSTRUCTION JOINT
NOT TO SCALE
G-6
TYPICAL CONTRACTION JOINT
NOT TO SCALE
G-6
NOTES:
1. ALL CONSTRUCTION JOINTS SHALL BE PREPARED IN ACCORDANCE WITH
ACI 350-06, PARAGRAPHS 6.4.1, 6.4.2, 6.4.3 TO ENSURE ADEQUATE
ROUGHNESS FOR TRANSFER OF SHEAR ACROSS CONSTRUCTION JOINT.
SEE TECHNICAL SPECIFICATIONS FOR ADDITIONAL CONSTRUCTION JOINT
REQUIREMENTS.
2. ALL PVC WATERSTOPS SHALL BE INSTALLED SO AS TO FORM A
CONTINUOUS WATERTIGHT DIAPHRAGM IN THE JOINT, INCLUDING AT ALL
SPLICES AND CHANGES IN ORIENTATION. WATERSTOP SHALL END 6
INCHES BELOW TOP OF WALLS, UNLESS OTHERWISE NOTED.
G-6
A TITLEMARK
G-####
Scale X
KEY PLAN
REGISTRATION
CONSULTANTS
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
CONSULTANT
AECOM
6200 South Quebec Street
Greenwood Village, Colorado 80111
T 303.694.2770 F 303.694.3946 www.aecom.com
CLIENT
OWNER/CLIENT
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
PROJECT
Line #1
Line #2
Line #3
(FACILITY NAME)
Address Line 1
Address Line 2
PROJECT NUMBER
Project Number
A N
S x
SHEET NUMBER
S-105
I/R DATE DESCRIPTION
ISSUE/REVISION
SHEET TITLE
TOBACCO SPILLWAY CONCRETE
OUTLINE AND REINFORCEMENT
PLAN
SCALE 1/4" = 1'
0 2 4 8 12
N
BAFFLE BLOCK IF REQ'D
(ABOVE SLAB)
CONC STEPS
END SILL
(ABOVE SLAB)
U/S FACE OF NEW DAM
15'-8
20'-0" 10'-0"
41'-3
87'-0
T Y
P
T Y
P
T Y
P
5'-0"
20'-0
"16'-3
CONCRETE OUTLINE AND REINFORCEMENT PLAN
1/8" = 1'-0"
A
S-106
B
S-107
CONSULTANTS
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
CONSULTANT
AECOM
6200 South Quebec Street
Greenwood Village, Colorado 80111
T 303.694.2770 F 303.694.3946 www.aecom.com
CLIENT
OWNER/CLIENT
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
PROJECT
Line #1
Line #2
Line #3
(FACILITY NAME)
Address Line 1
Address Line 2
PROJECT NUMBER
Project Number
A N
S x
SHEET NUMBER
S-106
I/R DATE DESCRIPTION
ISSUE/REVISION
SHEET TITLE
TOBACCO SPILLWAY
REINFORCEMENT SECTIONS
SCALE 1/4" = 1'
0 2 4 8 12
BAFFLE BLOCKS, IF REQ'D
SEE DETAIL 1 FOR UPPER STEP DESIGN
SEE DETAIL 2 FOR STEP REINFORCEMENT
END SILL
EXIST END SILL
TO BE REMAIN
T/CONC
EL 647.00
T/SLAB
EL 631.30
0.7
TOP SLAB MIN THICKNESS 15" #6@12" EW
STEPPED SPILLWAY CREST
#6 STEP REINFORCEMENT
SPILLWAY CREST
20'-0"
UPPER SPILLWAY STEPS VARY, TO BE DESIGNED BY FRANK LAN
LOW SPILLWAY STEP 2'-0" HIGH
UNBONDED CONST JT
W/ 6" WATER STOP
2'-0" THICK SLAB
ASSUME #8@12" EW EF
T/SLAB
EL 633.3
T/SILL
EL=636.8
3 8
ASSUME #9 SOIL ANCHORS IN STILLING BASIN
EXIST CONC
NOTE:
1. ROUGHEN SURFACE OF EXISTING CONCRETE SLAB TO EXPOSE AGGREGATE AND TREAT
AS CONSTRUCTION JOINT WHERE PLACING 2'-0" TOPPING SLAB ON EXISTING SLAB.
SELF LEVELING CONC
CONVENTIONAL CONC
CONTROL JT W/ 6"
WATER STOP
2'-0" REINFORCED
CONC SLAB
LEGEND
CONCRETE TO REMAIN
SECTION
1/4" = 1'-0"
S-105
CONSULTANTS
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
CONSULTANT
AECOM
6200 South Quebec Street
Greenwood Village, Colorado 80111
T 303.694.2770 F 303.694.3946 www.aecom.com
CLIENT
OWNER/CLIENT
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
PROJECT
Line #1
Line #2
Line #3
(FACILITY NAME)
Address Line 1
Address Line 2
PROJECT NUMBER
Project Number
A N
S x
SHEET NUMBER
S-107
I/R DATE DESCRIPTION
ISSUE/REVISION
SHEET TITLE
TOBACCO SPILLWAY
REINFORCEMENT SECTIONS AND
DETAILS
SCALE 1/4" = 1'
0 2 4 8 12
CONSULTANTS
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
DISCIPLINE
Consultant's Name
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
CONSULTANT
AECOM
6200 South Quebec Street
Greenwood Village, Colorado 80111
T 303.694.2770 F 303.694.3946 www.aecom.com
CLIENT
OWNER/CLIENT
Address Line 1
Address Line 2
000.000.0000 tel 000.000.0000 fax www.<website address>.com
PROJECT
Line #1
Line #2
Line #3
(FACILITY NAME)
Address Line 1
Address Line 2
PROJECT NUMBER
Project Number
A N
S x
SHEET NUMBER
S-108
I/R DATE DESCRIPTION
ISSUE/REVISION
SHEET TITLE
TOBACCO SPILLWAY CREST
STRUCTURE SECTIONS AND
DETAILS
SCALE 3/4" = 1'
0 1 2 3 4.5
File details come from the government source that posted it. Updated .