About this file

This document is a technical specification from the Louisiana Department of Transportation and Development (DOTD) for High Density Polyethylene (HDPE) Duct and Fittings for Electrical Wiring, specifically detailing requirements for smooth wall, gray-colored polyethylene ducts used in electrical infrastructure. The specification covers three specific duct sizes - 1 inch IPS Schedule 40, 2 inch IPS Schedule 80, and 3 inch IPS Schedule 80 - with precise dimensional requirements, including minimum wall thickness and outer diameter specifications. The document outlines comprehensive manufacturing, workmanship, installation, packaging, and shipping standards for these electrical conduits.

The specification provides detailed SAP Material Master Numbers for each duct size and corresponding couplings, with specific product references like Petroduct No. P100, P200, and P300. The ducts are required to be manufactured from virgin high-density polyethylene, capable of being coiled, transported, and stored outdoors, and must include UV light stabilization to protect against sunlight exposure for a minimum of twelve months. Additional technical requirements include pre-installed pull tape with a minimum 1800 lbs tensile strength, cable pulling lubricant effective between 20-250 degrees Fahrenheit, and the ability to be directly buried by plowing or trenching or encased in concrete without performance degradation.

View the file

Other files

File Type Posted
3000025386.pdf PDF
DOTD Specification 196-035, Rev. 9-10-2009.pdf PDF
U.S. Preference(2019).pdf PDF
Louisiana Preference(2019).pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SAP Material Master Numbers DOTD Spec. 196-034 See Below Rev. 01/04/2016

2 Pages

LOUISIANA

DEPARTMENT OF TRANSPORTATION AND DEVELOPMENT

SPECIFICATIONS

DUCT AND FITTINGS, HIGH DENSITY POLYETHYLENE,

FOR ELECTRICAL WIRING

DESCRIPTION:

The duct shall be manufactured of virgin high density polyethylene. The addition of clean rework material is permissible in duct manufacture. Duct shall be smooth wall construction and gray in color. The duct shall be capable of being coiled in continuous lengths, transported, stored outdoors and uncoiled for installation without affecting its properties or performance.

Duct shall be marked with a durable identification showing the name or trademark of the manufacturer, date of manufacture (in following format: MM-YY), and duct size (i.e., 2" IPS (Iron Pipe Size) SCH-80).

WORKMANSHIP:

The duct shall be free of visible cracks, holes or other physical defects that would degrade its performance. Duct shall be as uniform in color, dimensions, density and wall thickness as possible. Duct color shall include a UV light stabilizer to protect duct for a minimum of twelve

(12) months in direct sunlight.

DIMENSIONS:

The dimensions of the duct shall be as follows:

SIZE O. D. MIN. WALL THICKNESS

1 Inch IPS, Schedule 40 1.315 .133 2 Inch IPS, Schedule 80 2.375 .218 3 Inch IPS, Schedule 80 3.500 .300

PULL TAPE & LUBRICANT:

Pull tape shall be composed of polyester material and have a minimum tensile strength of 1800 lbs (PNA (Petroflex North America) No. WP1800-03). Lubricant shall be certified by manufacturer for installation of wire in a high density polyethylene duct. Lubricant shall be completely effective from 20 - 250 degrees Fahrenheit, will not harm duct, cable or cable insulation. Duct shall have cable pulling lubricant and pull tape pre-installed by the manufacturer.

INSTALLATION:

Duct shall be capable of being direct buried by plowing or trenching with no special consideration to using selective backfill. The duct shall also be capable of being encased in concrete with no negative effects on performance or to contents therein.

PACKAGING AND SHIPPING:

Duct shall be provided on metal non-returnable reels large enough to allow maximum lengths possible with no joints or splices. Maximum reel sizes to be:

1 inch duct - 4 foot diameter

2 inch duct - 8 foot diameter

3 inch duct - 9 1/2 foot diameter

Duct ends shall be capped to prevent the entrance of moisture, dirt and/or other foreign matter.

SAP MATERIAL MASTER NUMBERS:

10695 (12-50-0100) 1 inch IPS, Sch 40, gray, 2,400 feet continuous length per reel, Petroduct No. P100 or equal

10696 (12-50-0200) 2 inch IPS, Sch 80, gray, 3,000 feet continuous length per reel, Petroduct No. P200 or equal

10697 (12-50-0300) 3 inch ISP, Sch 80, gray, 1,600 feet continuous length per reel, Petroduct No. P300 or equal

10698 (12-50-0410) 1 inch coupling, for duct, pvc outer shell with polyurethane elastomer inner sleeve, PNA No. EL-131 or equal

10699 (12-50-0420) 2 inch coupling, for duct, pvc outer shell with polyurethane elastomer inner sleeve, PNA No EL-237 or equal

10700 (12-50-0430) 3 inch coupling for duct, pvc outer shell with polyurethane elastomer inner sleeve, PNA No. EL-350 or equal

File details come from the government source that posted it. Updated .