Equipment Specifications Generator 350kw, Natural Gas Automatic Transfer Switches Industrial gaseous engine-driven generator, turbocharged/aftercooled 12-cylinder 21.9L engine, consisting of the following features and accessories. Bid must include (3) 200 Amp Automatic Transfer Switches. Must be delivered to 7027 Old Madison Pike, Suite 100 Huntsville, AL 35806 NLT 17 December 2018 Quantity 1: Generator 350kw, Natural Gas

· Stationary Emergency-Standby rated

· 350 Kw Rating, wired for 277/480 VAC three phase, 60 Hz

· Weather Protective Enclosure, Steel

· Standard Industrial Grey Baked-on Powder Coat Finish

· UL2200

· EPA Certified

· Power Zone Digital Control Panel for Single or MPS Generators

· Meets NFPA 99 and 110 requirements

· Temp Range -40 to 70 degrees C

· Humidity 2 – 95% (Non Condensing)

· UL6200

· C-ET-US

· CE

· FCC

· IEC801 (Radiated Emissions, Susceptibility, and Serge Immunity)

· Standard 7” Resistive Color Touchscreen

· Built-in Wi-Fi, Bluetooth, and Webserver

· IP65 (front)

· Auto/Manual/Off key switch, Alarm Indication, Not in Auto Indication, audible alarm, emergency stop switch

· Duel Core Digital Microprocessor

· RS485, Ethernet and CANbus ports

· All engine sensors must equal standard 4-20ma for minimal interference

· Sensors: Oil Pressure, optional Oil Temp, Coolant Temp and Level, Fuel Level/Pressure (where applicable), Engine Speed, DC Battery Voltage, Run-time Hours, Generator voltages, Amps, Frequency, Power, Power Factor

· Alarm Status: Low or High AC Voltage, Low or High Battery Voltage, Low or High Frequency, Pre-low or Low Oil Pressure, Pre-High or High Oil Temp, Low Water Level and Temp, Pre-high or High Engine Temp, High, Low, and Critical-low Fuel Level/Pressure (where applicable), Overcrank, Over and Under Speed, Unit Not in Automatic

· Programmable I/O

· Built-in PLC for special applications (needed to plug into monitor)

· Engine Function monitoring and control

· Full range standby operation: programmable auto crank, Emergency Stop, Auto-Off-Manual switch

· Isochronous Governor

· 0.25% digital frequency regulation with: soft-start ramping – adjustable, gain-adjustable, overshoot limit – adjustable

· 3 Phase RMS Voltage Sensing

· +/-0.05% digital frequency regulation with: soft-start voltage ramping – adjustable, loss of sensing protection – adjustable, negative power limit – adjustable, Hi/Lo voltage limit – adjustable, V/F slope and gain – adjustable, fault protection.

· Service reminders, trending, fault history (alarm log)

· I2T function for full generator protection (required to be able to test system)

· Selectable low-speed exercise (required to be able to test system)

· 2-wire start controls for any 2-wire transfer switch

· Standard MLCB, 80% rated thermal-magnetic

· 600 Amp

· Battery Charger, 10 Amp, NFPA 110 compliant, installed

· 225 AH, 155 CCA Group 8D Batteries, with rack, installed

· Coolant Heater, 2500W, 240VAC

· Standard set of three manuals

· 120V GFCI and 240V Outlet

· Flex Fuel Line

· Oil Temp Sender

· Standard 2-year Limited Warranty to include parts, labor, and travel

Bid must include (3) 200 Amp Automatic Transfer Switches must be delivered to7027 Old Madison Pike, Suite 100 Huntsville, AL 35806 Not Later Than 17 December 2018.

Quantity 3 - GTS Series Automatic Transfer Switch consisting of the following features and accessories:

1. 200 Amp, 3 Pole, 277/480 VAC three phase, 60 Hz, with 2-Wire Start Circuit

0. Utility Voltage Sensing Controls:

0. Adjustable Drop-out and Pick-up

0. Adjustable Utility Interrupt Delay

0. Adjustable Logic Controls:

1. Minimum Standby Voltage

1. Minimum Standby Frequency

1. Engine Warmup

1. Inphase Monitor

1. Time Delay Neutral

1. Return to Utility

1. Engine Cooldown

1. Transfer on Exercise

1. Double set of Auxiliary Contacts

1. UL 1008 Listed, CSA Certified

1. NEMA 1 Enclosure

1. Standard set of 3 Manuals

1. 2-Year Basic Warranty- Parts, Labor and Travel

1. GTS020W-3K2LDNAY