Equipment Specifications Generator 350kw, Natural Gas Industrial gaseous engine-driven generator, turbocharged/aftercooled 12-cylinder 21.9L engine, consisting of the following features and accessories. Bid must include (3) 200 Amp Automatic Transfer Switches. Must be delivered on site NLT 17 December 2018

· Stationary Emergency-Standby rated

· 350 Kw Rating, wired for 277/480 VAC three phase, 60 Hz

· Weather Protective Enclosure, Steel

· Standard Industrial Grey Baked-on Powder Coat Finish

· UL2200

· EPA Certified

· Power Zone Digital Control Panel for Single or MPS Generators

· Meets NFPA 99 and 110 requirements

· Temp Range -40 to 70 degrees C

· Humidity 2 – 95% (Non Condensing)

· UL6200

· C-ET-US

· CE

· FCC

· IEC801 (Radiated Emissions, Susceptibility, and Serge Immunity)

· Standard 7” Resistive Color Touchscreen

· Built-in Wi-Fi, Bluetooth, and Webserver

· IP65 (front)

· Auto/Manual/Off key switch, Alarm Indication, Not in Auto Indication, audible alarm, emergency stop switch

· Duel Core Digital Microprocessor

· RS485, Ethernet and CANbus ports

· All engine sensors must equal standard 4-20ma for minimal interference

· Sensors: Oil Pressure, optional Oil Temp, Coolant Temp and Level, Fuel Level/Pressure (where applicable), Engine Speed, DC Battery Voltage, Run-time Hours, Generator voltages, Amps, Frequency, Power, Power Factor

· Alarm Status: Low or High AC Voltage, Low or High Battery Voltage, Low or High Frequency, Pre-low or Low Oil Pressure, Pre-High or High Oil Temp, Low Water Level and Temp, Pre-high or High Engine Temp, High, Low, and Critical-low Fuel Level/Pressure (where applicable), Overcrank, Over and Under Speed, Unit Not in Automatic

· Programmable I/O

· Built-in PLC for special applications (needed to plug into monitor)

· Engine Function monitoring and control

· Full range standby operation: programmable auto crank, Emergency Stop, Auto-Off-Manual switch

· Isochronous Governor

· 0.25% digital frequency regulation with: soft-start ramping – adjustable, gain-adjustable, overshoot limit – adjustable

· 3 Phase RMS Voltage Sensing

· +/-0.05% digital frequency regulation with: soft-start voltage ramping – adjustable, loss of sensing protection – adjustable, negative power limit – adjustable, Hi/Lo voltage limit – adjustable, V/F slope and gain – adjustable, fault protection.

· Service reminders, trending, fault history (alarm log)

· I2T function for full generator protection (required to be able to test system)

· Selectable low-speed exercise (required to be able to test system)

· 2-wire start controls for any 2-wire transfer switch

· Standard MLCB, 80% rated thermal-magnetic

· 600 Amp

· Battery Charger, 10 Amp, NFPA 110 compliant, installed

· 225 AH, 155 CCA Group 8D Batteries, with rack, installed

· Coolant Heater, 2500W, 240VAC

· Standard set of three manuals

· 120V GFCI and 240V Outlet

· Flex Fuel Line

· Oil Temp Sender

· Standard 2-year Limited Warranty to include parts, labor, and travel