Equipment Specifications Generator 350kw, Natural Gas Industrial gaseous engine-driven generator, turbocharged/aftercooled 12-cylinder 21.9L engine, consisting of the following features and accessories. Bid must include (3) 200 Amp Automatic Transfer Switches. Must be delivered on site NLT 17 December 2018
· Stationary Emergency-Standby rated
· 350 Kw Rating, wired for 277/480 VAC three phase, 60 Hz
· Weather Protective Enclosure, Steel
· Standard Industrial Grey Baked-on Powder Coat Finish
· UL2200
· EPA Certified
· Power Zone Digital Control Panel for Single or MPS Generators
· Meets NFPA 99 and 110 requirements
· Temp Range -40 to 70 degrees C
· Humidity 2 – 95% (Non Condensing)
· UL6200
· C-ET-US
· CE
· FCC
· IEC801 (Radiated Emissions, Susceptibility, and Serge Immunity)
· Standard 7” Resistive Color Touchscreen
· Built-in Wi-Fi, Bluetooth, and Webserver
· IP65 (front)
· Auto/Manual/Off key switch, Alarm Indication, Not in Auto Indication, audible alarm, emergency stop switch
· Duel Core Digital Microprocessor
· RS485, Ethernet and CANbus ports
· All engine sensors must equal standard 4-20ma for minimal interference
· Sensors: Oil Pressure, optional Oil Temp, Coolant Temp and Level, Fuel Level/Pressure (where applicable), Engine Speed, DC Battery Voltage, Run-time Hours, Generator voltages, Amps, Frequency, Power, Power Factor
· Alarm Status: Low or High AC Voltage, Low or High Battery Voltage, Low or High Frequency, Pre-low or Low Oil Pressure, Pre-High or High Oil Temp, Low Water Level and Temp, Pre-high or High Engine Temp, High, Low, and Critical-low Fuel Level/Pressure (where applicable), Overcrank, Over and Under Speed, Unit Not in Automatic
· Programmable I/O
· Built-in PLC for special applications (needed to plug into monitor)
· Engine Function monitoring and control
· Full range standby operation: programmable auto crank, Emergency Stop, Auto-Off-Manual switch
· Isochronous Governor
· 0.25% digital frequency regulation with: soft-start ramping – adjustable, gain-adjustable, overshoot limit – adjustable
· 3 Phase RMS Voltage Sensing
· +/-0.05% digital frequency regulation with: soft-start voltage ramping – adjustable, loss of sensing protection – adjustable, negative power limit – adjustable, Hi/Lo voltage limit – adjustable, V/F slope and gain – adjustable, fault protection.
· Service reminders, trending, fault history (alarm log)
· I2T function for full generator protection (required to be able to test system)
· Selectable low-speed exercise (required to be able to test system)
· 2-wire start controls for any 2-wire transfer switch
· Standard MLCB, 80% rated thermal-magnetic
· 600 Amp
· Battery Charger, 10 Amp, NFPA 110 compliant, installed
· 225 AH, 155 CCA Group 8D Batteries, with rack, installed
· Coolant Heater, 2500W, 240VAC
· Standard set of three manuals
· 120V GFCI and 240V Outlet
· Flex Fuel Line
· Oil Temp Sender
· Standard 2-year Limited Warranty to include parts, labor, and travel