This document contains a description of requirement and related federal contract opportunity notice. The description of requirement outlines the need for a data center solution consisting of two enclosed rows of server racks with integrated thermal management, fire suppression, uninterruptible power supply, and cable management. Each row would include four 42U racks with cooling, fire detection and suppression systems, power distribution, and a 10,000VA UPS. The related federal contract opportunity notice is a sources sought synopsis issued by the U.S. Army National Guard to identify potential qualified sources for providing the enclosed server row solution as described. Responses to the notice should include business size and socioeconomic classification information. No solicitation is currently available, but one may be issued at a later date.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESCRIPTION OF REQUIREMENT
Base Network Control Center Enclosed Server Row Solution
Procure and install a Data Center consisting of two lines of server racks with all-inclusive Thermal Management, Fire Suppression, and Uninterrupted Power Supply (UPS) system with a factory integrated cable management solution to be all self-contained within a closed equipment system.
SERVER RACKS REQUIREMENT
Each Row to include four cabinets for IT equipment with a 42U, 2000mm height, 800mm width and 1200mm. depth. Each rack to have factory integrated cable management solution. Each Row to have dedicated cooling systems and fire suppression and detection. Each row to have Load Distribution with local Emergency Power Off (EPO) tie-ins. Each rack to include Air-flow management plenums. Each IT rack to have two factory installed rear mounted Power Distribution Unit (PDU)/Cable management brackets. Each IT rack to have completely sealed front viewing door and split solid rear doors. Each rack to have vertical brush strips between the front EIA rails and side panels. Adjacent racks feature cable pass through side panels, while racks on the ends of the row feature solid and sealed side panels to effectively manage both air-flow and cable routing.
INCLUSIVE THERMAL MANAGEMENT
Each Row to have 460V/3ph/60Hz, nominal 5 ton down flow air cooled unit with top electrical and piping connection. 460V condenser for 100 degrees Fahrenheit. All air flow management plenums to be included with rack system. Emergency ventilation fans and factory installed inlet louvers for thermal unit outage.
ROW INCLUSIVE FIRE SUPPRESSION
Fire suppression and detection to include: One horn and strobe, system abort switch, 35lb agent storage container, 21 lbs. of clean agent similar to DuPont ECARO-25. CONTROL AND MONITORING Row system to include large graphic display to manage cooling system, including outdoor heat rejection. Leak sensor to provide reliable warnings of any potentially hazardous moisture leaks at critical points within plenums. Auto-changeover panel for rotating (2) room, ceiling mounted AC units.
ROW INCLUSIVE POWER DISTRIBUTION
Each row to have 120/208V/3PH/60Hz 30 pole 225A primary load distribution center with a 225A local main shunt trip.
ROW INCLUSIVE UPS SYSTEM
Each rack to have UPS system with 10000VA/9000 watt capacity. With Power output distribution of 4 5- 15/20R T-slot, 4 L6-30R receptacles with circuit breaker protection. Rack PDU to have 16 20A, 120V, NEMA 5-20, 10 5-20 outlets, 16 30A, 208V, NEMA L6-30P 20 IEC C-13, 4 IEC C-19 Outlets.
Assembly of Row system to be included.