CT Scan Bid Set R1 - Stamped - Drawings - Dated 1-11-2021.pdf
PDF 35 MB Posted
- Attached to
- Z2DA--642-CSI-118 Site Preparation to Replace CT Scan Federal contract opportunity
- Solicitation number
- 36C24421B0007
About this file
This solicitation package describes a federal contract opportunity for site preparation to replace a CT scan at a VA medical center in Philadelphia. The Department of Veterans Affairs is seeking a Service-Disabled Veteran-Owned Small Business to renovate the CT scan room, control room, equipment room, and supporting rooms to prepare for newly purchased CT scan equipment. Renovations include floor replacement, new finishes, wall changes, and revisions to HVAC, electrical and plumbing systems. The contract value is estimated between $500,000 and $1,000,000. The performance period is 220 calendar days from notice to proceed. Interested firms must be registered in the System for Award Management, verified through the Center for Veterans Enterprise as an SDVOSB, and meet OSHA and EPA requirements. The solicitation will be available on February 9, 2020 on SAM.gov and the bid due date will be included. The government contemplates awarding a firm fixed price contract.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Abstract of Offers 3-24-2021.pdf | ||
| 36C24421B0007 0004.docx | DOCX document | |
| 36C24421B0007 0003.docx | DOCX document | |
| 36C24421B0007 0002.docx | DOCX document | |
| Site Visit Sign-in Sheet 02.16.2021.pdf | ||
| Bid Sheet.docx | DOCX document | |
| 36C24421B0007 0001.docx | DOCX document | |
| Calculation of Self Performed Work.pdf | ||
| 21717 CT SCAN SPECS - VOL 2.pdf | ||
| Equipment Rerence Drawings 1-14-2021.pdf | ||
| 21717 CT SCAN SPECS - VOL 1 .pdf | ||
| 36C24421B0007_2.docx | DOCX document |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VAMC PHILADELPHIA
NORTH
DRAWING LIST
APPLICABLE CODES PROJECT CONTACT DIRECTORY
Approved by Medical Center Director Approved by Director of Facility Management Service
Approved by Medical DirectorApproved by Project COR
Approved by Project CO
Approved by Infection Control
Approved by Department of CLC Nursing
Approved by Safety Officer
MASTER CONSTRUCTION SPECIFICATIONS (PG-18-1)
LIFE SAFETY CODE NFPA 101 - 2018
ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS
VA DESIGN MANUALS:
FIRE PROTECTION, SEVENTH EDITION - DECEMBER 2015
INTERIOR DESIGN MANUAL, MAY 2008
VA BARRIER FREE DESIGN STANDARD (PG-18-13), REV 11/1/18
US Department of Veterans Affairs
SITE PREP TO REPLACE CT SCAN
Corporal Michael J. Crescenz VAMC
3900 Woodland Ave., Philadelphia, PA 19104
LOCATION MAP
130 WEST KINGSBRIDGE ROAD, BRONX, NEW YORK 10468
CONTRACTING OFFICER REPRESENTATIVE (COR)
ARCHITECT
MEP/FP ENGINEER
DANIEL CLARK
PHILADELPHIA VAMC
3900 WOODLAND AVENUE, BUILDING 5
PHONE: (215) 823-5800
daniel.clark@va.gov
CB DESIGN GROUP, INC
11720 BELTSVILLE DRIVE, SUITE 350
CALVERTON, MD 20705
PHONE: (443) 388-7351
kjones@cbdg-ae.com
H.F. LENZ COMPANY
1407 SCALP AVENUE
JOHNSTOWN, PA 15904
PHONE: (814) 269-9312
brager@hflenz.com
CONTRACTING OFFICER (CO)
GENERAL INFORMATION
ARCHITECTURAL INTERIORS
FIRE PROTECTION
PLUMBING
MECHANICAL
GI101 COVER SHEET
GI102 ABBREVIATIONS, SYMBOLS & PARTITION TYPES
GI103 LIFE SAFETY PLAN
AI101 DEMOLITION – FLOOR AND REFLECTED CEILING PLANS
AI102 NEW WORK – FLOOR, REFLECTED CEILING AND FINISH PLANS
AI103 ICRA REMOVAL, EQUIPMENT AND FINISH PLANS
AI104 INTERIOR ELEVATIONS
AI105 DETAILS AND LEAD SHIELDING
M001 MECHANICAL NOTES, SYMBOLS, AND ABBREVIATIONS
MD101 3RD FLOOR MECHANICAL DEMOLITION PLAN
MD102 4TH FLOOR MECHANICAL DUCTWORK DEMOLITION PLAN
MD103 4TH FLOOR MECHANICAL PIPING DEMOLITION PLAN
MH101 4TH FLOOR MECHANICAL DUCTWORK PLAN
MHP101 3RD FLOOR MECHANICAL DUCTWORK & PIPING PLAN
MP101 4TH FLOOR MECHANICAL PIPING PLAN
M501 MECHANICAL DETAILS (1 OF 2)
M502 MECHANICAL DETAILS (2 OF 2)
M601 MECHANICAL SCHEDULES AND CONTROLS
F101 3RD FLOOR FIRE PROTECTION PLAN
EVERETT SHAVER
Contracting Officer, Construction-East (VISN 4 Eastern Market) Department of Veterans Affairs | Service Area Office East | Network Contracting Office 4 20 Montchanin Rd, Room 116, Greenville DE 19807 PHONE: (302) 994-2511 x 7526 everett.shaver@va.gov
MAUREEN JACKSON
maureen.jackson@va.gov
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P
M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMP
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ENGINEER
SCALE:
H.F. LENZ COMPANY
1407 Scalp Avenue Johnstown, PA 15904
Phone: 814-269-9300 FAX: 814-269-9301 cadd@hflenz.com www.hflenz.com Engineers - Planners - Surveyors - Energy Consultants
As indicated
3900 Woodland Ave., Philadelphia, PA 19104
01/11/2021
642-CSI-118
DRKBJ
Site Prep To Replace CT ScanBID SET R1COVER SHEET
GI101
ELECTRICAL
E001 ELECTRICAL NOTES, SYMBOLS, AND ABBREVIATIONS
ED101 THIRD FLOOR ELECTRICAL DEMOLITION
ED102 FOURTH FLOOR ELECTRICAL DEMOLITION
ELP201 THIRD FLOOR LIGHTING, POWER, AND SIGNAL PLAN
EP202 PARTIAL FLOOR PLANS - POWER
E401 ELECTRICAL SINGLE LINE DIAGRAMS
E501 ELECTRICAL DETAILS (1 OF 2)
E502 ELECTRICAL DETAILS (2 OF 2)
E601 ELECTRICAL SCHEDULES
E701 CT EQUIPMENT DRAWINGS (1 OF 2)
E702 CT EQUIPMENT DRAWINGS (2 OF 2)STRUCTURAL
S001 GENERAL NOTES AND SPECIAL INSPECTIONS
SF101 STRUCTURAL 3RD FLOOR FRAMING PLAN
SF102 STRUCTURAL 4TH FLOOR INTERSTITIAL FRAMING
SF103 SECTIONS & DETAILS
SF104 3D RENDERING
SF105 3D RENDERING
DRAWING 1 OF 40
GENERAL CONTRACT
GC101 DOOR DETAILS
P101 3RD FLOOR PLUMBING PLAN
GENERAL RESOURCE
GR101 GENERAL RESOURCE - PHOTOGRAPHS
EQUIPMENT
QH101 MANUFACTURER DRAWINGS
& AND
@ AT
C CENTERLINE
# NUMBER
AB ANCHOR BOLT
ABV ABOVE
ACT ACOUSTIC CEILING TILE
AD AREA DRAIN
ADA AMERICANS WITH
DISABILITIES ACT
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
AIA AMERICAN INSTITUTE OF
ARCHITECTS
ALUM ALUMINUM
ALT ALTERNATE
AP ACCESS PANEL
APPROX APPROXIMATE
ARCH ARCHITECTURAL
AUTO AUTOMATIC
AVG AVERAGE
BD BOARD
BLDG BUILDING
BLK BLOCK
BM BEAM
BOT BOTTOM
BRG BEARING
BEL BELOW
BR BUMPER RAIL
BRK BRICK
CAB CABINET
CB CATCH BASIN
CEM CEMENT
CCT CUBICLE CURTAIN TRACK
CG CORNER GUARD
CI CAST IRON
CIP CAST IN PLACE
CJ CONTROL JOINT
CT CERAMIC TILE
CLG CEILING
CL CLOSET
COL COLUMN
CONC CONCRETE
CONF CONFERENCE
CONT CONTINUOUS
CPT CARPET
CT CERAMIC TILE
CU CUBIC
DBL DOUBLE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DISP DISPENSER
DN DOWN
DO DOOR OPENING
DOZ DOZEN
DP DAMPPROOFING
DR DOOR
DWG DRAWING
DWGS DRAWINGS
DWR DRAWER
E EAST
EA EXHAUST AIR, EACH
EL ELEVATION
ELEV ELEVATION
ELEC ELECTRICAL
EMER EMERGENCY
ENCL ENCLOSURE
ENGR ENGINEER
EP ELECTRICAL PANELBOARD
EQ EQUAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWS EYE WASH STATION
EXP EXPANSION
EJ EXPANSION JOINT
EXIST EXISTING
EXT EXTERIOR
FA FIRE ALARM
FB FACE BRICK
FD FLOOR DRAIN
FDC FIRE DEPARTMENT
CONNECTION
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER
CABINET
FF FINISH FACE
F/F FINISH TO FINISH
FHC FIRE HOSE CABINET
FIN FINISH
FLR FLOOR
FLUOR FLUORESCENT
FO __ FACE OF __
FOC FACE OF CONCRETE
FOS FACE OF STUD
FOW FACE OF WALL
FPRF FIREPROOF(ING)
FR FIRE RATING, FRAME
FRMG FRAMING
FS FULL SIZE
FT FOOT OR FEET
FTG FOOTING
FUR FURRING
FUT FUTURE
GC GENERAL CONTRACTOR
GA GAUGE
GAL GALLON
GALV GALVANIZED
GALV STL GALVANIZED STEEL
GB GRAB BAR
GC GENERAL CONTRACTOR
GD GUARD
GL GLASS
GND GROUND
GR GRADE
GWB GYPSUM WALLBOARD
GYP BD GYPSUM WALLBOARD
HB HOSE BIBB
HC HOLLOW CORE
HD HEAD
HDWR HARDWARE
HDWD HARDWOOD
HT HEIGHT
HNDRL HANDRAIL
HM HOLLOW METAL
HMD HOLLOW METAL DOOR
HMF HOLLOW METAL FRAME
HR HANDRAIL
HO HOLD OPEN
HORIZ HORIZONTAL
HP HIGH POINT
HR HOUR
HVAC HEATING, VENTILATION, AIR
CONDITIONING
IBC INTERNATIONAL BUILDING CODE
ID IDENTIFICATION, INSIDE
DIAMETER / DIMENSION
IN INCH
INCL INDLUDE(D)
INSUL INSULATION
INT INTERIOR
INV INVERT
JAN JANITOR
JST JOIST
JT JOINT
KP KICK PLATE
KO KNOCKOUT
L LENGTH
LAB LABORATORY
LAM LAMINATE
LAV LAVATORY
LBS POUND
LED LIGHT EMITTING DIODE
LF LINEAR FEET
LH LEFT HAND
LIN LINEAR
LIQ LIQUID
LKR LOCKER
LG LONG
LL LEAD LINED
LLV LONG LEG VERTICAL
LP LOW POINT
LRG LARGE
LT LIGHT
LT WT LIGHTWEIGHT
LVR LOUVER
MATL MATERIAL
MAS MASONRY
MAX MAXIMUM
MECH MECHANICAL
MTL METAL
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MP MOP PLATE
MTD MOUNTED
N NORTH
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEG NEGATIVE
NFC NATIONAL FIRE CODE
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER / DIMENSION
OFF OFFICE
OH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OH OVERHEAD
OZ OUNCE
PAV PAVING
PC PRECAST CONCRETE
PL PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLYWD PLYWOOD
PLBG PLUMBING
PMF PREMOLDED FILLER
PR PAIR
PT POINT
PTN PARTITION
QT QUARRY TILE
R RADIUS, RISER
RA RETURN AIR
RAD RADIUS
RB RESILIENT BASE, RUBBER
BASE
RD ROOF DRAIN
RL ROOF LEADER
REF REFERENCE
REFR REFRIGERATOR
REQ'D REQUIRED
REV REVISION
RFI REQUEST FOR
INFORMATION
RFP REQUEST FOR PROPOSAL
RH RIGHT HAND
RM ROOM
RO ROUGH OPENING
S SOUTH
SA SUPPLY AIR
SC SOLID CORE
SCHED SCHEDULE
SECT SECTION
SH SPRINKLER HEAD
SHT SHEET
SIM SIMILAR
SAN SANITARY
SPEC SPECIFICATION
SPKR SPEAKER
SQ SQUARE
STA STATION
STD STANDARD
STO STORAGE
STL STEEL
SS STAINLESS STEEL
STOR STEERAGE
STRUCT STRUCTURAL
SUSP SUSPENDED
SYM SYMMETRICAL
SYS SYSTEM
T TREAD
TEL TELEPHONE
TEMP TEMPERED
T&G TONGUE AND GROOVE
THK THICK
TOC TOP OF CONCRETE
TOP TOP OF PAVEMENT
TOS TOP OF STEEL
TOW TOP OF WALL
TV TELEVISION
TYP TYPICAL
UNFIN UNFINISHED
UNO UNLESS NOTED
OTHERWISE
UON UNLESS OTHERWISE
NOTED
VB BAPOR BARRIER
VERT VERTICAL
VCT VINYL COMPOSITION TILE
VIF VERIFY IN FIELD
VTR VET THRU ROOF
W WEST
W/ WITH
WD WOOD
W/O WITHOUT
WP WATERPROOF
WT WEIGHT
WWF WELDED WIRE FRAME
ARCHITECTURAL ABBREVIATIONS
NOTE: ALL ABBREVIATIONS
SHOWN MAY NOT BE USED ON
THIS PROJECT. CERTAIN COMMON
ABBREVIATIONS MAY NOT BE
SHOWN.
WOOD
WOOD FINISH
ALUMINUM
STEEL
EARTH
GYPSUM - PLASTER
MASONRY -
CONCRETE BLOCK
RIGID INSULATION
BATT INSULATION
PLYWOOD
CONCRETE
MATERIAL LEGEND
EXISTING CONSTRUCTION TO
REMAIN
EXISTING CONSTRUCTION TO BE
REMOVED
ARCHITECTURAL SYMBOLS
CENTER LINE
DETAIL INDICATOR
DETAIL INDICATOR
DETAIL INDICATOR FOR SMALL CONDITIONS
DIMENSION LINE
NEW DOOR OPENING / BORROWED LIGHT
IDENTIFIER
- SEE DOOR SCHEDULE, DETAILS AND
ELEVATIONS SHEET
DRAWING BLOCK TITLE, TYPICAL
ELEVATION INDICATOR, EXTERIOR
ELEVATION INDICATOR, INTERIOR, MULTIPLE VIEW
ELEVATION INDICATOR, INTERIOR, SINGLE VIEW
BUILDING SECTION INDICATOR
TYPICAL DETAIL INDICATOR
FURNITURE, FIXTURE, & EQUIPMENT INDICATOR
EXISTING ROOM NAME AND NUMBER
COLUMN GRID
KEYNOTE
WALL OR PARTITION TYPE
FIRE EXTINGUISHER CABINET
CORNER GUARD
NORTH ARROW
CG
FEC
A
CORRIDOR
C2
DETAIL NUMBER
SHEET WHERE
DRAWN
XX-XX
XX-XX
XX-XX
A
C B
D
XX-XX
XX-XX
X
DRAWING TITLE
SCALE: 1 1/2" = 1'-0"
1"
D2
XX-XX
XX-XX
XX-XX
CL
XX-XX
x'-x" SPOT ELEVATION
1 REVISION
REVISION CLOUD
NORTH
BREAK LINE
X DEMOLITION KEYNOTE
NEW ROOM NAME AND NUMBERCORRIDOR
C2
X
X
EXISTING DOOR OPENING
A
SECTION
PLAN
/8
3 5/8" METAL STUDS @ 16" OC, TYP
5/8" GWB, BOTH SIDES, SEE ROOM
FINISH SCHEDULE FOR FINISHES
CONTINUOUS METAL STUD TOP TRACK
CONTINUOUS METAL STUD BOTTOM
TRACK
LINE OF FINISHED FLOOR, SEE ROOM
FINISH SCHEDULE FOR FLOOR & BASE
TYPE
LINE OF EXISTING
SOFFIT/WALL
CONTINUOUS METAL HORIZONTAL
BRIDGING CHANNEL @ MID HEIGHT, TYP
FIRE-RATED SEALANT, BOTH SIDES
3 5/8" METAL STUDS @ 16" OC, 25-GAGE,
TYPICAL
5/8" TYPE "X" GWB, BOTH SIDES, STAGGER
JOINTS ON OPPOSITE SIDES OF ROOM SEE
ROOM FINISH SCHEDULE FOR FINISHES
1-HR RATED PARTITION - BASED ON UL465
TEMPORARY CONSTRUCTION BARRIER
EXISTING FINISHED CEILING
SYSTEM SOLID SURFACE WALL CAP: 1/2"
SOLID SURFACE ON 3/4" FIRE
RATED PLYWOOD
3 5/8" METAL STUDS @ 16" OC, TYP
LINE OF FINISHED FLOOR, SEE FINISH
SCHEDULE FOR FINISHES AND BASE
SECTION
PLAN
B
HALF-WALL
3 5/8" METAL STUDS @ 16" OC, TYP
1/2" SOLID SURFACE WALL FINISH,
BOTH SIDES
5/8" GWB, BOTH SIDES
5 7/8"
METAL STUD TOP TRACK
/2
6 7/8"
5/8" GWB, BOTH SIDES
1/2" THICK SOLID SURFACE
FINISH, BOTH SIDES
/2
/2
INTEGRAL SHEET VINYL BASE
FULLY ADHERED TO WALL
SHEET VINYL OVER CONCRETE SLAB
4 7/8"
/8
TS 3"x3"x1/4" @ 48" O.C. WITH 3"x7"x1/4"
STEEL PLATE WELDED TO BOTTOM
3"x7"x1/4" STEEL PLATE SECURED TO
FLOOR SLAB WITH EXPANSION BOLTS
TS 3"x3"x1/4" @ 48" O.C. WITH 3"x7"x1/4"
STEEL PLATE WELDED TO BOTTOM
METAL STUDS SECURED TO BOTH SIDES OF STEEL TUBE
BATT INSULATION
BATT INSULATION
EXPANSION BOLTS
GENERAL CONDITION NOTES - ARCHITECTURAL
1. ADJACENT PROJECT AREAS WILL BE OCCUPIED DURING PERFORMANCE OF WORK. IMMEDIATE AREAS OF ALTERATIONS WILL BE VACATED. ALL CONTRACTOR WORK SHALL BE PERFORMED DURING HOURS SET BY THE COR. CURRENTLY, WORKING HOURS ARE 2:30 PM - 10:30 PM, BUT THOSE HOURS MAY BE ADJUSTED BY THE VA
AT NO ADDITIONAL COST.
2. BEFORE STARTING WORK WITHIN AN OCCUPIED AREA, THE CONTRACTOR SHALL BE RESPONSIBLE TO SET UP TEMPORARY/PERMANENT CONSTRUCTION/ICRA BARRIERS WITH ANTEROOM AND MAINTAIN NEGATIVE PRESSURE. ALL TEMPORARY CONSTRUCTION BARRIERS OUTSIDE THE INDICATED CONSTRUCTION PHASE AREA SHALL BE REMOVED AT THE CONCLUSION OF THE WORK SHIFT. THE CONTRACTOR SHALL BE RESPONSIBLE TO CLEAN AND PREPARE THE AREA TO BE OCCUPIED BY MEDICAL CENTER STAFF.
3. DIMENSIONS SUPERSEDE DRAWINGS. DO NOT SCALE PLANS. DIMENSIONS ARE TO THE FACE OF EXISTING MATERIALS UNLESS OTHERWISE NOTED. DIMENSIONS AND ELEVATIONS SHALL BE VERIFIED AT THE SITE BEFORE PROCEEDING WITH THE WORK. NOTIFY THE COR IMMEDIATELY OF ANY DISCREPANCIES. THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS, DIMENSIONS, AND MATERIALS REQUIRED FOR THE CONTRACTED WORK. REPORT ALL DISCREPANCIES TO THE COR PRIOR TO FABRICATIONS AND ERECTION.
4. IT IS SOLELY THE CONTRACTOR'S RESPONSIBILITY TO FOLLOW ALL APPLICABLE SAFETY CODES AND REGULATIONS DURING ALL PHASES OF CONSTRUCTION. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE CONSTRUCTION PROCEDURES/ SEQUENCING AND TO ENSURE THE SAFETY OF THE BUILDING AND ITS COMPONENT PARTS DURING CONSTRUCTION. CONTRACTOR SHALL PROVIDE ADEQUATE SHORING AND BRACING DURING DEMOLITION AND CONSTRUCTION TO SUPPORT LOADS, AND REMOVE SHORING AND
BRACING UPON COMPLETION OF THE PROJECT.
5. DO NOT CUT AND PATCH STRUCTURAL ELEMENTS IN A MANNER THAT WOULD REDUCE THEIR LOAD CARRYING
CAPACITY OR LOAD-DEFLECTION RATIO.\
6. WHERE EXISTING CONSTRUCTION, EQUIPMENT, ETC. IS REQUIRED TO BE REMOVED, RESTORE EXPOSED FINISHES OF CUT AND PATCHED AREAS AND EXTEND FINISH RESTORATION INTO ADJOINING CONSTRUCTION IN A MANNER THAT WILL ELIMINATE EVIDENCE OF PATCHING AND REFINISHING. CUT EXISTING CONSTRUCTION USING METHODS LEAST LIKELY TO DAMAGE ELEMENTS TO BE RETAINED OR ADJOINING CONSTRUCTION.
WHERE INDICATED TO REMOVE FINISHES, REMOVE SO TOTALLY, FROM PLANE TO PLANE, TREAT REMAINING
SUBSURFACE TO RECEIVE NEW FINISHES DESIGNATED.
7. WHERE EXISTING CONSTRUCTION, EQUIPMENT, ETC. SHOWN TO BE RELOCATED SHALL BE COORDINATED BY THE CONTRACTOR WITH THE VA PRIOR TO START OF WORK IN EACH AREA. THE CONTRACTOR WILL REMOVE ALL ITEMS OF SALVAGEABLE VALUE, INCLUDING BUT NOT LIMITED TO DOORS, HARDWARE, MOVEABLE EQUIPMENT NOT ALREADY DESIGNATED FOR REINSTALLATION/REUSE, PRIOR TO COMMENCING WORK AND
TURN THEM OVER TO THE VA.
8. WHERE EXISTING PARTITIONS HAVE BEEN REMOVED OR NEW SERVICES PENETRATE EXISTING SURFACES, THE OPENINGS SHALL BE PATCHED TO MATCH THE EXISTING ADJACENT SURFACES FINISH, TEXTURE AND SHEEN.
9. WHERE EXISTING PARTITIONS HAVE BEEN REMOVED OR NEW SERVICES PENETRATE EXISTING SURFACES, THE OPENING SHALL BE PATCHED TO MATCH THE EXISTING ADJACENT SURFACES FINISH, TEXTURE AND SHEEN.
10. IN GENERAL, WHEREVER SERVICES ARE REMOVED, THE OPENINGS SHALL BE PATCHED TO MATCH THE EXISTING ADJACENT SURFACES FINISH TEXTURE AND SHEEN. WHERE REMOVAL OF EXISTING CONSTRUCTION, PIPING, DUCTWORK AND OTHER ITEMS CREATES OPENINGS IN THE WALLS, FLOORS OR CEILINGS, PATCH OPENINGS IMMEDIATELY WITH THE SAME MATERIALS AS ADJACENT CONSTRUCTION. MAINTAIN THE REQUIRED FIRE RATING. SEE MEP DRAWINGS FOR ADDITIONAL INFORMATION. FILL IN ALL EXISTING OPENINGS THAT ARE NOT TO REMAIN, UNLESS OTHERWISE NOTED. FINISH TO MATCH FINISH OF ADJACENT SURFACE.
11. WHERE CODED NOTE DESIGNATIONS ARE SHOWN AS "TYP" OR "TYPICAL" IT IS INTENDED THAT THE NOTE
GENERALLY REFERS TO ALL SIMILAR ITEMS OR SURFACES.
12. A HAZARDOUS MATERIALS SURVEY WAS NOT CONDUCTED. IT IS THE CONTRACTORS RESPONSIBILITY TO TAKE PROTECTIVE MEASURES FOR ITS WORKERS PRIOR TO THE BEGINNING OF ANY RENOVATION OR DEMOLITION
WORK.
13. AFTER COMPLETION OF DEMOLITION, SCHEDULE A WALK-THROUGH WITH THE COR FOR REVIEW OF EXISTING
CONDITIONS.
14. PATCH AND FIRE STOP AT ABANDONED PENETRATIONS THROUGH THE CONCRETE FLOORS, WALLS, AND ROOF
DECK.
15. CONTRACTOR MUST COMPLY WITH ALL VETERAN HEALTH ADMINISTRATION AND MEDICAL CENTER DIRECTIVES
AND MEMORANDUMS.
16. CONTRACTOR PROJECT MANAGER AND SUPERINTENDENT ARE REQUIRED TO ATTEND REGULARLY
SCHEDULED PROJECT MEETINGS DURING CONSTRUCTION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P
M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMP
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ENGINEER
SCALE:
H.F. LENZ COMPANY
1407 Scalp Avenue Johnstown, PA 15904
Phone: 814-269-9300 FAX: 814-269-9301 cadd@hflenz.com www.hflenz.com Engineers - Planners - Surveyors - Energy Consultants
As indicated
3900 Woodland Ave., Philadelphia, PA 19104
01/11/2021
642-CSI-118
DRKBJ
Site Prep To Replace CT ScanBID SET R1ABBREVIATIONS, SYMBOLS &
PARTITION TYPES
GI102
DRAWING 2 OF 40
D-W-4
C
KJD E F G
A
SM.1 P
11.1
FEC
R a d ia to r
R a d ia to r
D F
WING
TO
RESEARCH
STAIR #3
S T
A
IR
5 555
SSSSS
PROJECT WORK AREA.
CT-SCAN
T R
A V
E L D
IS
T A
N C
E T
O E
X
IT
TRAVEL DISTANCE TO EXIT
191'
PROJECT
NORTH
TRUE
NORTH
3rd FLOOR KEY PLAN
AREA OF WORK
BUILDING 2 BUILDING 1
LIFE SAFETY ANALYSIS
NFPA 101 LIFE SAFETY CODE 2018
TOTAL PROJECT AREA
TOTAL FLOOR AREA
OCCUPANCY COUNT
EGRESS CAPACITY PROVIDED
CORRIDORS
CORRIDORS MINIMUM 72" ALLOWED BY VA STANDARDS - 96" EXISTING EXIT CORRIDORS
7.1.10 MEANS OF EGRESS RELIABILITY
7.1.10.1 MEANS OF EGRESS SHALL BE CONTINUOUSLY MAINTAINED FREE OF ALL OBSTRUCTIONS OR
IMPEDIMENTS TO FULL INSTANT USE IN THE CASE OF FIRE OR OTHER EMERGENCY.
9.2.1 AIR CONDITIONING, HEATING, VENTILATION DUCTWORK, AND RELATED EQUIPMENT. AIR CONDITIONING, HEATING, VENTILATION
DUCTWORK, AND RELATED EQUIPMENT SHALL BE IN ACCORDANCE WITH NFPA 90A.
18.1.1.1.1 ALTERATION OF EXISTING HEALTH CARE OCCUPANCIES
18.1.1.4.3 REHABILITATION
18.1.1.4.3.1 (2) MINOR RENOVATIONS: RENOVATION IS LESS THAN 50% AND NOT MORE THAN 4500 SF OF THE AREA OF A SMOKE
COMPARTMENT
18.2.2.2 DOORS
18.2.2.2.4 DOORS WITHIN A REQUIRED MEANS OF EGRESS SHALL NOT BE EQUIPPED WITH A LATCH OR LOCK THAT REQUIRES THE USE OF A TOOL OR KEY FROM THE EGRESS SIDE, UNLESS OTHERWISE PERMITTED BY ONE OF THE FOLLOWING:
EXCEPTION NO. 1: KEY-LOCKING DEVICES THAT RESTRICT ACCESS TO THE ROOM FROM THE CORRIDOR AND THAT ARE OPERABLE ONLY BY STAFF FROM THE CORRIDOR SIDE SHALL BE PERMITTED. SUCH DEVICES SHALL NOT RESTRICT EGRESS FROM THE ROOM.
18.2.3.1 THE CAPACITY OF MEANS OF EGRESS SHALL BE IN ACCORDANCE WITH SECTION 7.3
7.3 / TABLE 7.3.3.1 THE CAPACITY OF MEANS OF EGRESS PROVIDING TRAVEL BY MEANS OF STAIRS SHALL BE 0.3 IN. PER PERSON, AND THE CAPACITY OF MEANS OF EGRESS PROVIDING HORIZONTAL TRAVEL (WITHOUT STAIRS) BY MEANS SUCH
AS DOORS, RAMPS, OR HORIZONTAL EXITS SHALL BE 0.2 INCHES PER PERSON.
18.2.3.4 AISLES, CORRIDORS, AND RAMPS REQUIRED FOR EXIT ACCESS IN A HOSPITAL OR NURSING HOME SHALL BE NOT LESS THAN
8 FEE IN CLEAR AND UNOBSTRUCTED WIDTH.
741 SQFT
83,694 SQFT
HEALTH CARE USE, INPATIENT TREATMENT DEPARTMENTS: 83,694 SF / 240 = 349
NUMBER OF STAIRWELLS - 6 WIDTH OF STAIRWELL DOORS - 36" CAPACITY
FACTOR - .3
NUMBER OF HORIZONTAL EXITS - 1 WIDTH OF HORIZONTAL EXIT - 96" CAPACITY
FACTOR - .2
TOTAL CAPACITY = 1200
18.2.6 TRAVEL DISTANCED TO EXITS
18.2.6.2.1 THE TRAVEL DISTANCE BETWEEN ANY POINT IN A ROOM AND AN EXIT SHALL NOT EXCEED 200 FEET.
18.3 PROTECTION.
18.3.4.1 GENERAL. HEALTH CARE OCCUPANCIES SHALL BE PROVIDED WITH A FIRE ALARM A FIRE ALARM SYSTEM IN ACCORDANCE
WITH SECTION 9.6.
18.3.4.3.1 OCCUPANT NOTIFICATION. OCCUPANT NOTIFICATION SHALL BE ACCOMPLISHED AUTOMATICALLY IN ACCORDANCE WITH 9.6.3.
18.3.4.5 DETECTION
18.3.4.5.1 GENERAL. DETECTION SYSTEMS, WHERE REQUIRED, SHALL BE IN ACCORDANCE WITH SECTION 9.6.
18.3.5.1 BUILDINGS CONTAINING HEALTH CARE FACILITIES SHALL BE PROTECTED THROUGHOUT BY AN APPROVED, SUPERVISED
AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 9.7.
18.3.5.6 PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED IN ALL HEALTH CARE OCCUPANCIES IN ACCORDANCE WITH 9.7.4.1.
18.3.6 CORRIDORS
18.3.6.1 CORRIDORS SHALL BE SEPARATED FROM ALL OTHER AREAS BY PARTITIONS..
18.3.6.2 CONSTRUCTION OF CORRIDOR WALLS SHALL FORM A BARRIER TO LIMIT THE TRANSFER OF SMOKE. SUCH WALLS SHALL BE PERMITTED TO TERMINATE AT THE CEILING WHERE THE CEILING IS CONSTRUCTED TO LIMIT THE TRANSFER OF SMOKE. NO LIMIT THE
TRANSFER OF SMOKE. NO FIRE RESISTANCE RATING REQUIRED FOR CORRIDOR WALLS.
18.3.6.3 CORRIDOR DOORS
18.3.6.3.1 CONSTRUCTED TO RESIST THE PASSAGE OF SMOKE.
18.3.6.3.2 PROVIDED WITH POSITIVE LATCHING.
18.3.6.3.11 DOOR - CLOSING DEVICES SHALL NOT B E REQUIRED ON DOORS IN CORRIDOR WALL OPENINGS OTHER THAN THOSE SERVING REQUIRED EXITS, SMOKE BARRIERS, OR ENCLOSURES OF VERTICAL OPENINGS AND HAZARDOUS AREAS.
18.3.7.1 (4) TO LIMIT THE TRAVEL DISTANCE FROM ANY POINT TO REACH A DOOR IN THE REQUIRED SMOKE BARRIER TO A DISTANCE
NOT EXCEEDING 200 FEET.
18.2.5 ARRANGEMENT OF MEANS OF EGRESS
18.2.5.6.1 EVERY HABITABLE ROOM SHALL HAVE AN EXIT ACCESS DOOR LEADING DIRECTLY TO AN EXIT ACCESS CORRIDOR
18.2.5.2 DEAD-END CORRIDORS. DEAD-END CORRIDORS SHALL NOT EXCEED 30 FT
18.2.5.3 COMMON PATH OF TRAVEL. COMMON PATH OF TRAVEL SHALL NOT EXCEED 100 FEET
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P
M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMP
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ENGINEER
SCALE:
H.F. LENZ COMPANY
1407 Scalp Avenue Johnstown, PA 15904
Phone: 814-269-9300 FAX: 814-269-9301 cadd@hflenz.com www.hflenz.com Engineers - Planners - Surveyors - Energy Consultants
As indicated
3900 Woodland Ave., Philadelphia, PA 19104
01/11/2021
642-CSI-118
DRKBJ
Site Prep To Replace CT ScanBID SET R1LIFE SAFETY PLAN
GI103
1" = 20'-0"
LIFE SAFETY PLAN
DRAWING 3 OF 40
TYPE 1
LEAD LINED HM FRAME
IN LEAD LINED GWB WALL
H
W
T Y
P
INTERIOR DOOR FRAMES
SCALE: NTS
J1
H1
TYPE 2
(HM IN GWB)
H
W
T Y
P
J2
H2
OUTSIDE CORNER TRIM
(25N032xxx)
3/8"
/8
3/8"
INSIDE CORNER TRIM
(25N035xxx)
VERTICAL JOINT TRIM
(25N033xxx)
/3
2"
TRIM PROFILES
FULL SCALE
TYPICAL WALL PROTECTION DETAILS
SCALE: 6" = 1'-0"
PROTECTIVE WALL COVERING
FULLY ADHERED TO WALL (WP-1)
TOP OF CHAIR RAIL 3'-0" AFF /
MATCH COUNTERTOP HEIGHT
CONTINUOUS SEALANT
CONTINUOUS CLEAR ANODIZED
ALUMINUM "J" TRIM, SEE
SPECIFICATIONS
S E
E F
IN
IS
H S
C H
E D
U L
E INTEGRAL SHEET VINYL BASE
FULLY ADHERED TO WALL
SEALANT AT GYPSUM BOARD /
FLOOR JOINT
COVE FILLER STRIP. FINISHED
RADIUS 1/2" MINIMUM
SHEET VINYL OVER CONCRETE
SLAB
GYPSUM BOARD, SEE
PARTITION TYPE
CONTINUOUS SEALANT
CONTINUOUS CLEAR ANODIZED
ALUMINUM "J" TRIM, SEE
SPECIFICATIONS
INTEGRAL SHEET VINYL BASE
FULLY ADHERED TO WALL
SEALANT AT GYPSUM BOARD /
FLOOR JOINT
COVE FILLER STRIP. FINISHED
RADIUS 1/2" MINIMUM
SHEET VINYL OVER CONCRETE
SLABS
E E
F
IN
IS
H
S C
H E
D U
L E
1/2" THICK x 1 1/2" HIGH SOLID
SURFACE CHAIR RAIL, MATCH
COUNTERTOP PROFILE (SS-1)
TYPICAL WALL BASE DETAIL
SCALE: 6" = 1'-0"
TYPICAL WALL PROTECTION DETAIL
SCALE: 6" = 1'-0"
RABBIT CHAIR RAIL TO ACCEPT
WALL PROTECTION
GYPSUM BOARD, SEE
PARTITION TYPE
CONTINUOUS SEALANT
CONTINUOUS SEALANT
CORNER GUARD BEYOND
(SS-2)
1/2"
/2
3"HEAT WELD BASE TO
FLOORING AT SEAM
HEAT WELD BASE TO
FLOORING AT SEAM
3"
SOLID SURFACE, SS-2
SEE FINISH SCHEDULE FOR COLOR
TYPICAL CORNER GUARD (CG-1)
SCALE: 3" = 1'-0"
WALL PROTECTION, WP-1
5/8" GWB ON METAL STUDS,
SEE PARTITION TYPE
3"
CONTINUOUS CAULK,
TYPICAL
/2
R 4
4"
NEW LEAD DOOR
SWEEPS
SS DOOR PROTECTION
RE-INSTALL EXISTING
DOOR HOLD-OPEN
NEW BRUSHED STAINLESS
STEEL LEAD LINED ASTRAGAL
NEW LEAD WOOD DOOR,
MATCH EXISTING LEAD
THICKNESS, MATCH
EXISTING DOOR FINISH
SS DOOR
PROTECTION
CT SCAN 3A177
ELEVATION
CORRIDOR C3-14
ELEVATION
1' - 0" 4' - 0"
CT SCAN 3A177
ELEVATION
NEW LEAD DOOR
SWEEP
SS DOOR PROTECTION
INSTALL EXISTING
DOOR PULL
NEW LEAD WOOD DOOR,
MATCH EXISTING LEAD
THICKNESS, MATCH
EXISTING DOOR FINISH
SS DOOR
PROTECTION
INSTALL EXISTING
SS PUSH PLATE
CONTROL ROOM
3A187 ELEVATION
R 4' - 4"
3' - 0"
SS DOOR
PROTECTION
INSTALL EXISTING
DOOR PULL
NEW WOOD DOOR,
MATCH EXISTING
DOOR FINISH
SS DOOR
PROTECTION
INSTALL SS
PUSH PLATE
CONTROL ROOM
3A187 ELEVATION
R 4' - 4"
3' - 0"
INSTALL EXISTING
DOOR CLOSER
WORK CORRIDOR
3C-16 ELEVATION
A
DOOR TYPE "A" ELEVATION
SCALE: 1/4" = 1'-0"
B
DOOR TYPE "B" ELEVATION
SCALE: 1/4" = 1'-0"
C
DOOR "C" ELEVATIONS - DOOR 3A187
SCALE: 1/4" = 1'-0"
SS DOOR EDGE
PROTECTION,
TYPICAL
SS DOOR EDGE
PROTECTION,
TYPICAL
SS DOOR EDGE
PROTECTION,
TYPICAL
FLUSH BOLT
DOOR HARDWARE, SEE
SPECIFICATIONS
TYPICAL NOTES:
1. SS DOOR PROTECTION: FACTORY PUNCH ALL
HOLES FOR DOOR HARDWARE.
2. LEAD THICKNESS: 1/8" Pb
TYPICAL NOTES:
1. SS DOOR PROTECTION: FACTORY PUNCH ALL
HOLES FOR DOOR HARDWARE.
2. LEAD THICKNESS: 1/8" Pb
TYPICAL NOTES:
1. SS DOOR PROTECTION: FACTORY PUNCH ALL
HOLES FOR DOOR HARDWARE.
D
DOOR TYPE "D" ELEVATION
SCALE: 1/4" = 1'-0"
4' - 4"
MATCH FINISH OF EXISTING ADJACENT
EQUIPMENT ROOM DOORS.7
ROOM
3A177B
WIDTH HEIGHT
DOOR SCHEDULE
PAIR MATERIAL FINISH TYPE
DOOR SIGN
TYPE MATERIAL FINISH TYPE
FRAME FIRE
RATING
HDW
SET
REMARKS
DOOR
NO.
GANTRY ROOM - 3'-0" 7'-0" WD/LL WD/SS A HM PAINT 1 - 2
3A177A GANTRY ROOM PR 1' + 4' 7'-0" WD/LL WD/SS A HM PAINT 1 - 1
3A177C EQUIPMENT ROOM PR 26"+26" 7'-0" WD WD D A HM PAINT 2 - 3 -
LEAD-LINED HM FRAME (SEE 3/GC101)
B
A
3A187 CONTROL ROOM - 3'-0" 7'-0" WD WD/SS C A HM PAINT 2 - 4 -
LEAD-LINED HM FRAME (SEE 3/GC101)
NOTE: SEE 2/GC101 FOR FRAME TYPES
WALL THICKNESS
COORD W/
9/16" 9/16"
2" 5/
8"
1 15/16"1 15/16"
GYP BOARD WALL
METAL STUD TRACK
SEALANT TYP, BOTH SIDES
FULL PERIMETER
W A
LL
T
H
IC
K N
E S
S
C O
O R
D W
9/
9/
2" 5/8"
/1 6"
/1 6"
JAMB ANCHOR
DOOR: SEE SCHEDULE
GYP BOARD WALL
SEALANT, TYP.
BOTH SIDES,
FULL PERIMETER
1. ALL SIGNS SHALL BE ADA/ABA COMPLIANT
2. MOUNT SIGNS WITH TOP OF SIGN AT +5'-0" ABOVE FINISHED FLOOR, UNLESS OTHERWISE
NOTED. SEE DETAIL 9 ON THIS SHEET.
4. SIGN TYPE REQUIREMENTS ARE SHOWN ON DOOR SCHEDULE.
5. VERIFY ALL FINAL TEXT AND ROOM NUMBERS WITH COR PRIOR TO FABRICATION.
6. ALL SIGNAGE TO MATCH EXISTING FACILITY SIGNAGE. BASIS OF DESIGN FOR SIGNS IS CREATIVE
SIGNAGE. CONTACT PAUL MOSKIOS, 301-345-3700.
SIGNAGE NOTES
9"
5'
GENERAL NOTES:
1. SPECIAL ANCHORAGE OF CLIP ANGLES AT THE INTERSTITIAL DECK WILL BE REQUIRED.
2. PROVIDE NEW LEAD LINED DOOR FRAMES AT ALL TYPE 1 DOORS.
ELEVATION JAMB-HEAD SIMILAR-DOOR &
FRAME IN LEAD LINED METAL
STUD PARTITION
CLIP ANGLES FASTENED
TO SLAB OR BEAM. SEE
GENERAL NOTE #1
2 1/2" x 2" x 3/8"
ANGLES FASTENED
BOTH ENDS
WELD
PROVIDE JAMB
REINFORCING FOR
HINGES OR PIVOTS
FRAME MUST BE AT
LEAST TWO PIECES TO
INSTALL OVER ANGLE
2" DOOR FRAME
CLIP ANGLES
FASTENED TO SLAB
1 1/8" +/- EXISTING WALL 5/8"
NEW 5/8" GYPSUM
WALL BOARD
EXISTING LEAD LINED
GYPSUM WALL BOARD
1/2"
DOUBLE STUDS
1/2"
/8
EXTEND LEAD SHIELDING COMPLETELY
AROUND INSIDE FACE OF BUCK AND
OVERLAP EXISTING LEAD SHIELDING 2" MIN.
FRAME MADE FROM STOCK
FRAME, GROUT FRAME
WITH DOOR
COORDINATE VARIES 1 15/16"
SEALANT (BOTH SIDES)
OVERLAP LEAD LINING 2" MINIMUM
LEAD-LINED DOOR
NOTE:
ENSURE CONTINUITY OF
LEAD LINING AROUND INSIDE
OF FRAME
MULTI-LAYERED FIRE RETARDANT
THERMOPLASTIC SHEET WITH
SPECTRIM #13 MAPLE FINISH
(MAGNETICALLY REMOVABLE)
1/8" ANODIZED ALUMINUM DIVIDER BAR
MAGNETICALLY REMOVABLE F-UNIT
1" TEXT, ALL CAPS
AERIAL REGULAR
PHOTOPOLYMER / BRAILLE
3 PLY NON-GLARE ACRYLIC CONSTRUCTION
SUBSURFACE UV VARIABLE DOT DIGITALLY
PRINTED BACKGROUND COLOR WHITE
5 3/16 x 9" CLEAR ACETATE - 1/16" THICK
CLEAR ACRYLIC BACKER WITH FUTURA MED TEXT
SATIN ANODIZED ALUMINUM FRAME
3A-187
CONTROL
ROOM
DIMENSION OF INSERT
9"
INSIDE DIMENSION OF FRAME
9 1/8"
F -U
N
IT
6"
IN
S
E R
T
3"
F R
A M
E
1/
8"
F R
A M
E
1/
8"
SIGN SYSTEM MECHANICALLY ATTACHES TO WALL
AND FEATURES INTERCHANGEABLE COMPONENTS
TOP OF SIGN TO BE
MOUNTED AT +5'-0" AFFTYPE A - SLIDER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P
M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMP
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ENGINEER
SCALE:
H.F. LENZ COMPANY
1407 Scalp Avenue Johnstown, PA 15904
Phone: 814-269-9300 FAX: 814-269-9301 cadd@hflenz.com www.hflenz.com Engineers - Planners - Surveyors - Energy Consultants
As indicated
3900 Woodland Ave., Philadelphia, PA 19104
01/11/2021
642-CSI-118
DRKBJ
Site Prep To Replace CT ScanBID SET R1DOOR DETAILS
GC101
DRAWING 4 OF 40
1 1/2" = 1'-0"8
HEAD AND JAMB DETAILS (J2 & H2) - FRAME TYPE 2
1/2" = 1'-0"9
DOOR SIGN MOUNTING HEIGHT
6" = 1'-0"3
LEAD LINED DOOR AND FRAME DETAILS (J1 & H1) - FRAME TYPE 1
3" = 1'-0"
SIGN TYPE A
NOTE: ALL LOCKS SHALL BE 7-PIN INTERCHANGEABLE CORE, STANLEY 9K SERIES, CYLINDRICAL LOCKSETS.
KEY NOTES: ICRA/DEMOLITION
D01 REPLACE EXISTING DOOR WITH 45 MIN. RATED DOOR FOR TEMPORARY USE DURING
RENOVATION. CONTRACTOR TO VERIFY SIZE OF DOOR.
D02 PROVIDE TEMPORARY AIR TIGHT ANTEROOM TO BE USED DURING CONSTRUCTION
PHASE. PROVIDE STICKY MATS AND HEPA VACUUM TO CLEAN WORKERS CLOTHING
WHEN LEAVING THE PROTECTED CONSTRUCTION AREA. INSTALL BASE COVE AT
TEMPORARY WALLS IN PUBLIC AREAS AND PAINT TO MATCH ADJACENT FINISHES.
COORDINATE WITH CONSTRUCTION DOCUMENTS.
D03 45 MINUTE RATED FRAME AND DOOR FOR USE DURING CONSTRUCTION PHASE. REMOVE
FRAME AND DOOR WHEN PARTITION IS SCHEDULED TO BE REMOVED. PATCH FLOOR AND
CEILING AS REQUIRED. PROVIDE AND INSTALL ALL REQUIRED DOOR HARDWARE WITH A
PUSHBUTTON DOOR LOCK-SET. COORDINATE WIDTH OF DOOR TO ENSURE ADEQUATE
CLEARANCE FOR MOVING CT SCAN EQUIPMENT IN AND OUT OF ROOM.
D04 CLOSE OFF EXISTING OPENING DURING DEMOLITION / CONSTRUCTION WITH 1 HOUR
BARRIER. PROVIDE AIR TIGHT SEAL IN ACCORDANCE TO INFECTION CONTROL POLICY.
D05 TEMPORARILY REMOVE A SECTION OF EXISTING HANDRAIL TO NEAREST JOINT.
REINSTALL HANDRAIL AFTER ICRA BARRIER IS REMOVED.
D06 CONTRACTOR TO REMOVE ALL EXISTING EQUIPMENT. EXISTING CT SCANNER MUST BE
REMOVED THROUGH THE HOSPITAL AND DOWN AN APPROVED ELEVATOR SHAFT.
CONTRACTOR WILL COORDINATE WITH THE ELEVATOR COMPANY/CONSULTANT
APPROVED BY COR TO VERIFY SIZE / WEIGHT LIMITATIONS AND SAFETY
REQUIREMENTS FOR THE ELEVATOR. COR TO APPROVE OVERALL REMOVAL PLAN.
D07 EXISTING RACEWAY TO BE FILLED WITH CONCRETE.
D08 REMOVE EXISTING DOOR , FRAME, AND HARDWARE.
D09 REMOVE EXISTING PLUMBING FIXTURE BACK TO BRANCH. NO ABANDONED LINES ARE
TO BE LEFT. SEE PLUMBING DRAWINGS. WHEN PRESENT, REMOVE ALL RELATED
ELEMENTS INCLUDING BUT NOT LIMITED TO: SOAP DISPENSERS, PAPER TOWEL
DISPENSERS, ETC. PATCH WALLS AND LEAD AS REQUIRED.
X
D10 REMOVE EXISTING MILLWORK SHOWN DASHED. PATCH WALLS AND LEAD
SHIELDING AS REQUIRED.
D11 BASE BID:
REMOVE WALL BASE, EXISTING FLOOR FINISHES, EXISTING LEAD SHIELDING
(ENTIRE FLOOR), AND ADHESIVES DOWN TO CONCRETE SLAB. PREP SLAB FOR
NEW LEAD SHIELDING AND NEW FLOOR FINISHES.
DEDUCT ALTERNATE #1
REMOVE WALL BASE AND EXISTING FLOOR FINISHES. DO NOT DISTURB
EXISTING LEAD SHIELDING. PATCH ANY DAMAGED LEAD SHIELDING (ALLOW
FOR 10 PATCHES AT 2'x2') IN PREPARATION FOR NEW FLOOR FINISHES.
D12 REMOVE EXISTING ACT CEILING SYSTEM AND ASSOCIATED LIGHT FIXTURES,
GRILLES, ETC. SEE DEMOLITION REFLECTED CEILING PLAN AND MEP/FP
DRAWINGS.
D13 PROTECT EXISTING FOLDING PARTITION DURING CONSTRUCTION.
CONTRACTOR IS RESPONSIBLE TO REPAIR/REPLACE ANY DAMAGE TO THE
DOOR, FRAME, ETC.
D14 REMOVE PORTION OF EXISTING WALL TO CEILING HEIGHT.
D15 REMOVE EXISTING METAL CHASE.
*DEMOLITION NOTES APPLY TO PHOTOGRAPHS AND DEMOLITION PLANS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P
M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMP
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ENGINEER
SCALE:
H.F. LENZ COMPANY
1407 Scalp Avenue Johnstown, PA 15904
Phone: 814-269-9300 FAX: 814-269-9301 cadd@hflenz.com www.hflenz.com Engineers - Planners - Surveyors - Energy Consultants
1/8" = 1'-0"
3900 Woodland Ave., Philadelphia, PA 19104
01/11/2021
642-CSI-118
DRKBJ
Site Prep To Replace CT ScanBID SET R1GENERAL RESOURCE -
PHOTOGRAPHS
GR101
D08
PHOTO 3A187-A PHOTO 3A187-B
PHOTO 3A187-C
PHOTO 3A187-D PHOTO 3A177-A PHOTO 3A177-B
PHOTO 3A177-C PHOTO 3A177-D PHOTO 3A177-E PHOTO 3A177-F PHOTO 3A177-G
D08 D04
D08
D01 D08D10D13D13D13
D01
D10 D10
D10
D10 D10
D06 D06
D09 D11 D11
D11
DRAWING 5 OF 40
SEE SHEET AI101.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P
M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMP
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ENGINEER
SCALE:
H.F. LENZ COMPANY
1407 Scalp Avenue Johnstown, PA 15904
Phone: 814-269-9300 FAX: 814-269-9301 cadd@hflenz.com www.hflenz.com Engineers - Planners - Surveyors - Energy Consultants
3900 Woodland Ave., Philadelphia, PA 19104
01/11/2021
642-CSI-118
DRKBJ
Site Prep To Replace CT ScanBID SET R1MANUFACTURER DRAWINGS -
SOMATOM FORCE GANTRY
QH101
NOTE: THIS DRAWING FOR INFORMATION ONLY
DRAWING 11 OF 40
D01
D08
D02
D03
D09
D10
D10
D10
D10
D10
D11
D12
D13
D11
D12
D04
D05 D05
D07
A
CONTROL ROOM
3A187
CONTROL ROOM
3A192b
GANTRY ROOM
3A186
WAITING AREA
3A192
GANTRY ROOM
3A177
EQUIPMENT
ROOM
3A177a
CORRIDOR
C3-14
ANTE ROOM
FILM PROCESS /
WORK CORRIDOR
C3-16
D15
ANTE ROOM
DOOR: C3-14
PROVIDE 45 MIN. RATED DOOR
WITH PUSH BUTTON LOCK
D06
D04
3' - 7"
D14
M A
IN
T
A
IN
M
IN
C
L R
KEY NOTES: ICRA/DEMOLITION
D01 REPLACE EXISTING DOOR WITH 45 MIN. RATED DOOR FOR TEMPORARY USE DURING
RENOVATION. CONTRACTOR TO VERIFY SIZE OF DOOR.
D02 PROVIDE TEMPORARY AIR TIGHT ANTEROOM TO BE USED DURING CONSTRUCTION
PHASE. PROVIDE STICKY MATS AND HEPA VACUUM TO CLEAN WORKERS CLOTHING
WHEN LEAVING THE PROTECTED CONSTRUCTION AREA. INSTALL BASE COVE AT
TEMPORARY WALLS IN PUBLIC AREAS AND PAINT TO MATCH ADJACENT FINISHES.
COORDINATE WITH CONSTRUCTION DOCUMENTS.
D03 45 MINUTE RATED FRAME AND DOOR FOR USE DURING CONSTRUCTION PHASE. REMOVE
FRAME AND DOOR WHEN PARTITION IS SCHEDULED TO BE REMOVED. PATCH FLOOR AND
CEILING AS REQUIRED. PROVIDE AND INSTALL ALL REQUIRED DOOR HARDWARE WITH A
PUSHBUTTON DOOR LOCK-SET. COORDINATE WIDTH OF DOOR TO ENSURE ADEQUATE
CLEARANCE FOR MOVING CT SCAN EQUIPMENT IN AND OUT OF ROOM.
D04 CLOSE OFF EXISTING OPENING DURING DEMOLITION / CONSTRUCTION WITH 1 HOUR
BARRIER. PROVIDE AIR TIGHT SEAL IN ACCORDANCE TO INFECTION CONTROL POLICY.
D05 TEMPORARILY REMOVE A SECTION OF EXISTING HANDRAIL TO NEAREST JOINT.
REINSTALL HANDRAIL AFTER ICRA BARRIER IS REMOVED.
D06 CONTRACTOR TO REMOVE ALL EXISTING EQUIPMENT. EXISTING CT SCANNER MUST BE
REMOVED THROUGH THE HOSPITAL AND DOWN AN APPROVED ELEVATOR SHAFT.
CONTRACTOR WILL COORDINATE WITH THE ELEVATOR COMPANY/CONSULTANT
APPROVED BY COR TO VERIFY SIZE / WEIGHT LIMITATIONS AND SAFETY
REQUIREMENTS FOR THE ELEVATOR. COR TO APPROVE OVERALL REMOVAL PLAN.
D07 EXISTING RACEWAY TO BE FILLED WITH CONCRETE.
D08 REMOVE EXISTING DOOR , FRAME, AND HARDWARE.
D09 REMOVE EXISTING PLUMBING FIXTURE BACK TO BRANCH. NO ABANDONED LINES ARE
TO BE LEFT. SEE PLUMBING DRAWINGS. WHEN PRESENT, REMOVE ALL RELATED
ELEMENTS INCLUDING BUT NOT LIMITED TO: SOAP DISPENSERS, PAPER TOWEL
DISPENSERS, ETC. PATCH WALLS AND LEAD AS REQUIRED.
X
D10 REMOVE EXISTING MILLWORK SHOWN DASHED. PATCH WALLS AND LEAD
SHIELDING AS REQUIRED.
D11 BASE BID:
REMOVE WALL BASE, EXISTING FLOOR FINISHES, EXISTING LEAD SHIELDING
(ENTIRE FLOOR), AND ADHESIVES DOWN TO CONCRETE SLAB. PREP SLAB FOR
NEW LEAD SHIELDING AND NEW FLOOR FINISHES.
DEDUCT ALTERNATE #1
REMOVE WALL BASE AND EXISTING FLOOR FINISHES. DO NOT DISTURB
EXISTING LEAD SHIELDING. PATCH ANY DAMAGED LEAD SHIELDING (ALLOW
FOR 10 PATCHES AT 2'x2') IN PREPARATION FOR NEW FLOOR FINISHES.
D12 REMOVE EXISTING ACT CEILING SYSTEM AND ASSOCIATED LIGHT FIXTURES,
GRILLES, ETC. SEE DEMOLITION REFLECTED CEILING PLAN AND MEP/FP
DRAWINGS.
D13 PROTECT EXISTING FOLDING PARTITION DURING CONSTRUCTION.
CONTRACTOR IS RESPONSIBLE TO REPAIR/REPLACE ANY DAMAGE TO THE
DOOR, FRAME, ETC.
D14 REMOVE PORTION OF EXISTING WALL TO CEILING HEIGHT.
D15 REMOVE EXISTING METAL CHASE.
*DEMOLITION NOTES APPLY TO PHOTOGRAPHS AND DEMOLITION PLANS.
DEMOLITION SYMBOL LEGEND
REMOVE EXISTING PARTITION SHOWN DASHED IN ITS
ENTIRETY.
REMOVE EXISTING DOOR, FRAME, AND HARDWARE.
REMOVE EXISTING BASE CABINET, COUNTERTOP,
EQUIPMENT AND WALL CABINETS SHOWN DASHED IN
THEIR ENTIRETY. VERIFY EXISTING CONDITIONS.
GENERAL DEMOLITION NOTES
1. SCOPE OF DEMOLITION WORK IS NOT LIMITED TO WORK SHOWN ON
DEMOLITION DRAWINGS. CONTRACTOR TO COORDINATE DEMOLITION WITH
NEW WORK AND PATCH EXISTING TO RECEIVE NEW FINISHES.
2. REFER TO MECHANICAL, ELECTRICAL & PLUMBING DRAWINGS FOR
DEMOLITION WORK. WHERE SUCH WORK OCCURS, ARCHITECTURAL ITEMS
OR FINISHES SHALL BE REMOVED ONLY TO THE EXTENT REQUIRED &
PATCHED TO MATCH EXISTING ADJACENT CONSTRUCTION AND FINISHES.
3. REMOVE ALL INTERIOR DOORS, FRAMES AND HARDWARE INDICATED AS
DASHED LINES.
4. REMOVE EXISTING CEILING IN ALL AREAS TO RECEIVE A NEW CEILING.
5. REMOVE EXISTING FLOOR FINISH, BASE AND ADHESIVE IN ALL AREAS
WHICH ARE TO RECEIVE NEW FLOOR FINISHES.
6. PROTECT EXISTING FINISHED WORK & EQUIPMENT WHICH IS TO REMAIN IN
AREAS OF DEMOLITION WORK.
7. REMOVE PARTITIONS SHOWN DASHED.
8. SEE FLOOR PLANS FOR LOCATION AND FINISHED SIZE OF PARTITION
OPENINGS.
9. VERIFY EXISTING FIRE PROTECTION ON ALL STRUCTURAL ELEMENTS IN
AREA OF WORK PRIOR TO INSTALLING NEW WORK. PATCH AND REPAIR AS
NECESSARY TO MAINTAIN REQUIRED RATING.
10. AFTER THE REMOVAL OF ICRA WALLS, CLEAN AND PATCH EXISTING WALLS
AFFECTED BY CONSTRUCTION AND MATCH EXISTING FINISHES.
11. USE TOMMY CARTS FOR REMOVAL OF CONSTRUCTION WASTE. NO
DUMPSTERS WILL BE ALLOWED ON SITE. A MAXIMUM OF 10 TOMMY CARTS
WILL BE ALLOWED ON SITE.
INFECTION CONTROL POLICY
PRECAUTIONS DURING CONSTRUCTION
1. EXECUTE WORK BY METHODS TO MINIMIZE RAISING DUST FROM
CONSTRUCTION OPERATIONS.
2. IMMEDIATELY REPLACE A CEILING TILE DISPLACED FOR VISUAL INSPECTION
3. PROVIDE ACTIVE MEANS TO PREVENT AIRBORNE DUST FROM DISPERSING
INTO ATMOSPHERE.
4. WATER MIST WORK SURFACES TO CONTROL DUST WHILE CUTTING DRY WALL
FOR BARRIERS.
5. NOT USED.
6. BLOCK OFF AND SEAL AIR VENTS IN THE CONSTRUCTION AREA WITH TIN CAPS.
7. PLACE DUST MAT AT ENTRANCE AND EXIT OF WORK AREA.
8. REMOVE OR ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE
TO PREVENT CONTAMINATION OF DUCT SYSTEM.
9. REMOVE CONSTRUCTION WASTE DAILY.
10. PROVIDE TEMPORARY CONSTRUCTION PARTITIONS (DRYWALL/SHEETROCK) AND
SEAL UNUSED DOORS AT PERIMETER OF THE WORK AREA BEFORE
CONSTRUCTION BEGINS.
11. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA
FILTER EQUIPPED AIR FILTRATION UNITS. COORDINATE LOCATION OF ABOVE
FLOOR PENETRATION WITH COR. PATCH FLOOR PENETRATION AFTER
CONSTRUCTION AS REQUIRED TO MATCH EXISTING. PROVIDE NEW HEPA FILTER
AT THE BEGINNING OF THE PROJECT.
12. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED
CONTAINERS OR BY COVERING IN PLASTIC AND SEALING WITH DUCT TAPE.
REMOVE WASTE DAILY EITHER AFTER 5 PM AND BEFORE 7 AM.
13. USE ROUTE AGREED UPON BY THE ICRA TEAM AND COR FOR TRANSPORT OF
TRANSPORT CONTAINERS THROUGH THE FACILITY.
14. SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES AIRTIGHT AND/OR FIRE SEAL
AS REQUIRED..
15. CONSTRUCT AN AIRTIGHT ONE-HOUR RATED ANTEROOM AND REQUIRE ALL
PERSONNEL TO PASS THROUGH THIS ROOM SO THEY CAN BE VACUUMED
USING HEPA VACUUM CLEANER BEFORE LEAVING WORK SITE; OR WEAR
PAPER COVERALLS THAT ARE REMOVED EACH TIME THEY LEAVE THE WORK
SITE.
16. ALL PERSONNEL ENTERING WORK SITE ARE REQUIRED TO WEAR SHOE
COVERS. SHOE COVERS MUST BE CHANGED EACH TIME THE WORKER EXITS
THE WORK AREA.
17 CONTRACTOR MUST COMPLY WITH MEDICAL CENTER MEMORANDUM NO. 111-
15IC SEPT 2015 OR LATEST VERSION.
18 ONLY HEPA VACUUMS ALLOWED ON PROJECT.
D51 D51
D51D51
D51 D51
D51
D51
D51
D51
D51
D51
D51
D51
D51
D51
D51
D51
D51
D51
D51 D51 D51
D51
D51
D51
D52
D52
D54
D54
D54
D54D54
D54 D55 D54
D54
D54D54
D53
CONTROL ROOM
3A187
CONTROL ROOM
3A192b
GANTRY ROOM
3A186
WAITING AREA
3A192
GANTRY ROOM
3A177
EQUIPMENT
ROOM
3A177a
CORRIDOR
C3-14
FILM PROCESS /
WORK CORRIDOR
C3-16
D50
D50
D50
REFLECTED CEILING PLAN DEMOLITION NOTES
GENERAL NOTES:
A. COORDINATE DEMOLITION WITH NEW WORK INCLUDING BUT NOT LIMITED TO ARCHITECTURAL, MEP, FIRE PROTECTION AND COMMUNICATION WORK.
B. PATCH EXISTING CONDITIONS AS REQUIRED FOR NEW FINISHES AFTER NEW WORK IS
INSTALLED.
C. COORDINATE DEMOLITION WITH ARCHITECTURAL PHASING PLANS.
D. FIRE PROTECTION DESIGN INTENT: THE INTENT IS NO SPRINKLER HEAD IS TO BE RELOCATED /
REMOVED. VERIFY WITH FIRE PROTECTION DRAWINGS AND SPECIFICATIONS IF PROVIDED.
NOTES BY SYMBOL:
D50 REMOVE EXISTING ACOUSTICAL CEILING TILE SYSTEM IN ITS ENTIRETY INCLUDING BUT NOT
LIMITED TO: ACOUSTICAL TILE, GRID AND SUSPENSION WIRE.
D51 REMOVE EXISTING LIGHT FIXTURES. SEE ELECTRICAL DRAWINGS FOR ADDITIONAL
REQUIREMENTS. GENERAL CONTRACTOR TO PROVIDE TEMPORARY LIGHTING UNTIL NEW
LIGHTING SYSTEM IS FULLY FUNCTIONING.
D52 EXISTING GWB SOFFIT TO REMAIN.
D53 REMOVE EXISTING CEILING MOUNTED DEVICE. SEE ELECTRICAL DRAWINGS FOR ADDITIONAL
REQUIREMENTS.
D54 REMOVE EXISTING HVAC GRILLE. SEE MECHANICAL DRAWINGS FOR ADDITIONAL
REQUIREMENTS.
X
PROJECT
NORTH
TRUE
NORTH
3rd FLOOR KEY PLAN
AREA OF WORK
BUILDING 2 BUILDING 1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P
M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMP
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ENGINEER
SCALE:
H.F. LENZ COMPANY
1407 Scalp Avenue Johnstown, PA 15904
Phone: 814-269-9300 FAX: 814-269-9301 cadd@hflenz.com www.hflenz.com Engineers - Planners - Surveyors - Energy Consultants
As indicated
3900 Woodland Ave., Philadelphia, PA 19104
01/11/2021
642-CSI-118
DRKBJ
Site Prep To Replace CT ScanBID SET R1DEMOLITION - FLOOR & REFLECTED
CEILING PLANS
AI101
1/4" = 1'-0"
ICRA / DEMOLITION WORK - FLOOR PLAN
1/4" = 1'-0"
02 REFLECTED CEILING PLAN - DEMOLITION
DRAWING 6 OF 40
REMOVAL OF EXISTING CT SCAN EQUIPMENT
A. CONTRACTOR SHALL COORDINATE WITH SIEMENS FOR THE CAREFUL REMOVAL OF
EXISTING CT SCAN EQUIPMENT FROM ROOM AND MOVE TO ELEVATOR SHAFT.
B. COORDINATE WITH ELEVATOR REPRESENTATIVE TO LOCK OUT ELEVATOR AT AN
UPPER FLOOR.
C. HOIST THE EXISTING EQUIPMENT DOWN THE ELEVATOR SHAFT FROM THE THIRD
FLOOR TO THE GROUND FLOOR WHERE THE LOADING DOCK IS LOCATED.
D. TRANSFER EXISTING EQUIPMENT TO THE LOADING DOCK AND TURN OVER POSSESSION
OF EQUIPMENT TO SIEMENS.
7' - 11 1/4"
7' - 11 1/4"
CT ORIENTATION POINT,
VERIFY LOCATION WITH
EQUIPMENT DRAWINGS
COUNTERTOP, VERIFY GROMMET
LOCATIONS WITH COR, TYP
COUNTERTOP, VERIFY GROMMET
LOCATIONS WITH COR, TYP
COUNTERTOP, VERIFY GROMMET
LOCATIONS WITH COR, TYP
AI104
AI1045
1' - 8"
LL
CONTROL ROOM
3A187
CONTROL ROOM
3A192b
GANTRY ROOM
3A186
WAITING AREA
3A192
GANTRY ROOM
3A177
EQUIPMENT
ROOM
3A177a
CORRIDOR
C3-14
ANTE ROOM
FILM PROCESS /
WORK CORRIDOR
C3-16
DOOR: 3A177A
DOOR: 3A177B
DOOR: 3A187
CG-1
AI105
PATCH LEAD FLOOR IN ACCORDANCE
WITH MANUFACTURER'S
REQUIREMENTS FOR NEW EQUIPMENT.
DOOR: 3A177C
INFILL RECESSED RACEWAY WITH
CONCRETE AND LEAD SHIELDING
FLUSH WITH FLOOR
FINISH EXPOSED SURFACES OF
GYP BOARD AT NEW OPENING
8' - 9 1/4"
/4
UPS FURNISHED AND
INSTALLED BY CONTRACTOR
BATTERIES FURNISHED AND
INSTALLED BY CONTRACTOR
NEW CT EQUIPMENT FURNISHED
BY SIEMENS
SP
(E)
(E)
(E)(E)(E)
(E)
(E) (E)
(E)
(E)(E)
(E)
SOFFIT WITH RECESSED
WINDOW SHADE, SEE
DETAIL B/AI-02
5' - 8"
PATIENT LIFT SYSTEM, SEE
STRUCTURAL DRAWINGS
AND SPECIFICATIONS. SEE
DETAIL A/AI102
OVERHEAD INJECTOR ARM
BASIS OF DESIGN: MEDRAD STELLANT
CT INJECTION SYSTEM W/ CERTAGRA
WORKSTATION BY BAYER
HEALTHCARE, OR EQUAL.
(WWW.RADIOLOGYSOLUTIONS.COM)
ACT-3 @ EXISTING HEIGHT
ACT-3 @ EXISTING
HEIGHT
ACT-2 @ EXISTING HEIGHT
EXISTING SOFFIT.
PATCH AS
REQUIRED. PAINT.
EXISTING SOFFIT. PATCH
AS REQUIRED. PAINT.
SHADED AREA:
SILHOUETTE OF CT
EQUIPMENT
BELOW.
(E)
WAITING AREA
3A192
CONTROL ROOM
3A187
CONTROL ROOM
3A192b
GANTRY ROOM
3A186
GANTRY ROOM
3A177
CORRIDOR
C3-14
EQUIPMENT
ROOM
3A177a
PROJECT
NORTH
TRUE
NORTH
3rd FLOOR KEY PLAN
AREA OF WORK
BUILDING 2 BUILDING 1
7'-0" AFF
5/8" LEAD GWB (1/8" LEAD), PAINT, TYP
CORNER BEAD, TYP
EXISTING LEAD PARTITION,
PATCH AND PAINT
6" METAL STUDS @ 16" OC, MAINTAIN
LEAD SHIELDING INTEGRITY.
B
SOFFIT DETAIL
SCALE: 1 1/2" = 1'-0"
FINISHED CEILING SYSTEM,
SEE REFLECTED CEILING PLAN
RECESSED WINDOW SHADE,
ADJUST POCKET DETAIL AS PER
MANUFACTURER'S WRITTEN
INSTRUCTIONS
3/4" BIRCH VENEER PLYWOOD
(FIRE RETARDANT)
EXISTING 5/8" LEAD GWB ABOVE
FIXED CEILING LIFT TRACK BY
LIFT MANUFACTURER.
MOTORIZED CEILING LIFT
TRACK. BY CEILING LIFT
MANUFACTURER.
ESCUTCHEON PLATE BY
CEILING LIFT MANUFACTURER
SUSPENDED LAY-IN CEILING:
SEE SPECIFICATIONS
CEILING TRACK CONNECTION.
WRAP WITH LEAD 4X DIAMETER.
SEE STRUCTURAL DRAWINGS.
CONTINUOUS LEAD FACE GWB.
REMOVE AND PATCH AS REQUIRED FOR
NEW WORK. OVERLAP NEW LEAD TO
EXISTING LEAD 2" MIN. MATCH EXISTING
LEAD SHIELDING ON DRAWING 1/AI-02
A
CEILING LIFT TRACK DETAIL.
SCALE: 1 1/2" = 1'-0"
STL. ANGLE: SEE STRUCTURAL
DRAWINGS.
REFLECTED CEILING PLAN LEGEND
6" RECESSED LED DOWNLIGHT
SPRINKLER HEAD, SEE FIRE
PROTECTION DRAWINGS
MECHANICAL GRILLES, SEE
MECHANICAL DRAWINGS
EXIT DEVICE
2' x 2' ACOUSTICAL PANEL CEILING
EXISTING(E)
LED LIGHT FIXTURE
1x4 LED LIGHT FIXTURE
SPEAKER
SP
SEE MEP/FP DRAWINGS FOR ADDITIONAL INFORMATION
CONTROL ROOM
3A187
CONTROL ROOM
3A192b
GANTRY ROOM
3A186
WAITING AREA
3A192
GANTRY ROOM
3A177
EQUIPMENT
ROOM
3A177a
CORRIDOR
C3-14
FILM PROCESS /
WORK CORRIDOR
C3-16
CEILING: 3/32" Pb (2.38mm)
FLOOR: 1/16" Pb (1.58mm)
C=5/32" Pb (3.97mm)
D
1/ 8"
P b
3.
m m
D=1/8" Pb (3.17mm)
D=1/8" Pb (3.17mm)
D
1/ 8"
P b
3.
m m
HATCHED AREA: NO
LEAD SHIELDING
DOOR AND FRAME:
1/8" Pb (3.17mm)
DOOR AND FRAME:
1/8" Pb (3.17mm)
WINDOW AND FRAME:
1/8" Pb (3.17mm - 140 KV)
D=1/8" Pb (3.17mm)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P
M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMP
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ENGINEER
SCALE:
H.F. LENZ COMPANY
1407 Scalp Avenue Johnstown, PA 15904
Phone: 814-269-9300 FAX: 814-269-9301 cadd@hflenz.com www.hflenz.com Engineers - Planners - Surveyors - Energy Consultants
As indicated
3900 Woodland Ave., Philadelphia, PA 19104
01/11/2021
642-CSI-118
DRKBJ
Site Prep To Replace CT ScanBID SET R1NEW WORK - FLOOR & REFLECTED
CEILING PLANS
AI102
1/4" = 1'-0"
NEW WORK - FLOOR PLAN
1/4" = 1'-0"
NEW WORK - REFLECTED CEILING PLAN
1/4" = 1'-0"
EXISTING LEAD SHIELDING
EXISTING SHIELDING CONDITIONS PROVIDED BY VA FROM PREVIOUS
RENOVATION PROJECT. CONTRACTOR TO VERIFY EXISTING SHIELDING
CONDITIONS IN THE FIELD AND MATCH EXISTING CONDITIONS FOR NEW
WORK. EXISTING CONDITIONS TAKE PREFERENCE OVER EXISTING LEAD
SHIELDING DRAWING.
DRAWING 7 OF 40
INSTALLATION OF NEW CT SCAN EQUIPMENT
A. CONTRACTOR SHALL COORDINATE WITH SIEMENS TO RECEIVE NEW CT SCAN EQUIPMENT
AT THE GROUND FLOOR LOADING DOCK.
B. COORDINATE WITH ELEVATOR REPRESENTATIVE TO LOCK OUT ELEVATOR AT AN
UPPER FLOOR.
C. CONTRACTOR SHALL CAREFULLY MOVE THE NEW CT SCAN EQUIPMENT TO THE GROUND
FLOOR ELEVATOR AND HOIST THE EXISTING EQUIPMENT UP THE ELEVATOR SHAFT TO THE
THIRD FLOOR.
D. MOVE THE NEW EQUIPMENT TO THE NEW LOCATION AND INSTALL THE NEW CT SCAN
EQUIPMENT IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.
PROJECT
NORTH
TRUE
NORTH
3rd FLOOR KEY PLAN
AREA OF WORK
BUILDING 2 BUILDING 1
D60
D61 D61
D63
D63
CONTROL ROOM
3A187
CONTROL ROOM
3A192b
GANTRY ROOM
3A186
WAITING AREA
3A192
GANTRY ROOM
3A177
EQUIPMENT
ROOM
3A177a
CORRIDOR
C3-14
ANTE ROOM
FILM PROCESS /
WORK CORRIDOR
C3-16
D62
8' - 10"
/3
CONTROL ROOM
3A187
CONTROL ROOM
3A192b
GANTRY ROOM
3A186
WAITING AREA
3A192
GANTRY ROOM
3A177
EQUIPMENT
ROOM
3A177a
CORRIDOR
C3-14
FILM PROCESS /
WORK CORRIDOR
C3-16
KEY NOTES: ICRA DEMOLITION
D60 REMOVE EXISTING ANTE-ROOM ICRA WALLS AND DOOR SYSTEMS IN THEIR ENTIRETY. PATCH AND PAINT
CORRIDOR WALL. PATCH AND REPAIR EXISTING CORRIDOR FLOOR FINISHES.
D61 RE-INSTALL CORRIDOR HANDRAIL SYSTEM.
D62 REMOVE EXISTING ICRA BARRIER SHOWN DASHED.
D63 REMOVE TEMPORARY DOOR SHOWN DASHED AND INSTALL NEW DOOR.
X
RSF-3
FLOOR: RSF-2
RSF-3
FLOOR: RSF-1
RSF-4
FLOOR: RSF-1
WALLS: P-2
WALL PROTECTION: WP-1
CHAIR RAIL: SS-2
CABINETS: PL-1
COUNTERTOP: SS-1
WALL SPLASH: SS-2
COUNTERTOP: SS-1
COUNTERTOP: SS-1
C O
U N
T E
R T
O P
: S S
-1
FLOOR: RSF-1
WALLS: P-2
FLOOR: RSF-2
WALLS: P-2
PATCH EXISTING CORRIDOR
FLOOR / WALLS / CEILING
FINISHES TO MATCH EXISTING
D O
O R
F R
A M
E : P
-1
DOOR FRAME: P-1
CORRIDOR SIDE: MATCH EXISTING
R
HM FRAME: P-1
R 14' - 0"
R
2'
R
2' -
CG-1
CG-1
WAITING AREA
3A192
CONTROL ROOM
3A187
CONTROL ROOM
3A192b
GANTRY ROOM
3A186
GANTRY ROOM
3A177
CORRIDOR
C3-14
EQUIPMENT
ROOM
3A177a
DOOR FRAME: P-1
CORRIDOR SIDE: MATCH
EXISTING
CABINETS: PL-1
COUNTERTOP: SS-1
WALL SPLASH: SS-2
8' - 6 1/2"
/4
2' - 0"
CG-1
CG-1
RESILIENT SHEET FLOORING (RSF)
RSF-1: MANNINGTON; BIOSPEC MD; BISQUE
RSF-2: MANNINGTON; BIOSPEC MD; BALSA
RSF-3: MANNINGTON; BIOSPEC MD; NEW NAVY
RSF-4: MANNINGTON; BIOSPEC MD; BLUE RIDGE
PAINT (P)
P-1: DURON: BOTANY BEIGE; 8221W; EPOXY PAINT
P-2: DURON: BOTANY BEIGE; 8221W; EGG SHELL
P-3; MATCH EXISTING PAINT COLOR, VIF.
PLASTIC LAMINATE (PL)
PL-1: FORMICA; CHERRY BIRCH; MATTE FINISH; 7484-58
SOLID SURFACE (SS)
SS-1: DUPONT; CORIAN; COBALT
SS-2: DUPONT; CORIAN; AURORA
WALL PROTECTION (WP)
WP-1: ACROVYN; WHEAT; SUEDE TEXTURE; #254
INTEGRAL BASE: WHERE RESILIENT SHEET FLOORING ABUTS WALL,
PROVIDE INTEGRAL BASE USING COLOR OF FLOORING. HEAT WELD
SEAMS BETWEEN DIFFERENT COLORS OF BASE ALONG SAME WALL
SURFACE.
FINISHES
ITEM DESCRIPTION
EQUIPMENT SCHEDULE
FURNISHED BY
GC GC
INSTALLED BYITEM #
SOAP DISPENSER AND HAND SANITIZER DISPENSER - WALL MOUNTED VA VA
2 WALL CABINET - PLASTIC LAMINATE GC GC
4 PAPER TOWEL DISPENSER - WALL MOUNTED, STAINLESS STEEL, TRI-FOLD TOWELS VA VA
1 SINK BASE CABINET - PLASTIC LAMINATE WITH SOLID SURFACE COUNTERTOP
7 30" DEEP COUNTERTOP, SOLID SURFACE WITH 3" PLASTIC GROMMET COVERS
6 WALL CABINET - PLASTIC LAMINATE
8 20" DEEP COUNTERTOP, SOLID SURFACE WITH 3" PLASTIC CROMMET COVERS
5 BASE CABINET - PLASTIC LAMINATE WITH SOLID SURFACE COUTERTOP
9 OVERHEAD PATIENT LIFT SYSTEM - SEE REFLECTED CEILING PLAN
GC GC
GC GC
GC GC
GC GC
GC GC
10 INJECTOR BOOM GC GC
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P
M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMP
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ENGINEER
SCALE:
H.F. LENZ COMPANY
1407 Scalp Avenue Johnstown, PA 15904
Phone: 814-269-9300 FAX: 814-269-9301 cadd@hflenz.com www.hflenz.com Engineers - Planners - Surveyors - Energy Consultants
As indicated
3900 Woodland Ave., Philadelphia, PA 19104
01/11/2021
642-CSI-118
DRKBJ
Site Prep To Replace CT ScanBID SET R1ICRA REMOVAL, EQUIPMENT AND
FINISH PLANS
AI103
1/4" = 1'-0"
ICRA REMOVAL - FLOOR PLAN
1/4" = 1'-0"
EQUIPMENT PLAN
1/4" = 1'-0"
FINISH PLAN
DRAWING 8 OF 40
2' - 6"
NEW LEAD DOOR, PAINT EXISTING HM FRAME,
SS DOOR PROTECTION - BOTH SIDES OF DOOR
WALL PROTECTION
6" INTEGRAL WALL BASE
SOLID SURFACE CHAIR RAIL
1/2" THICK SOLID SURFACE
WALL FINISH
EXISTING GWB SOFFIT
EXISTING GWB SOFFIT, PAINT
EXISTING WINDOW SYSTEM, PAINT HM FRAME
EXISTING GWB LEAD WALL, PATCH AND PAINT
CORNER GUARD
CEILING SYSTEM, SEE REFLECTED CEILING PLAN
FINISHED FLOOR
1" FILLER
1/2" THICK SOLID SURFACE
WALL FINISH
GWB WITH LEAD FASCIA AND SOFFIT
RECESSED 4'-4" WIDE PRIVACY SHADE
SHOWN DASHED
GC101
A
AI105
2' - 6"
WALL PROTECTION
6" INTEGRAL WALL BASE
SOLID SURFACE CHAIR RAIL
EXISTING GWB SOFFIT,
PATCH AND PAINT
EXISTING GWB LEAD WALL, PATCH AND PAINT
CEILING SYSTEM, SEE REFLECTED CEILING PLAN
FINISHED FLOOR
1" FILLER
1/2" THICK SOLID
SURFACE WALL FINISH
EXIT SIGN, SEE
ELECTRICAL DRAWINGS4" WIDE 1/2" THICK SOLID
SURFACE RETURN
GC101
B
AI105
6" INTEGRAL WALL BASE
SOLID SURFACE
WALL FINISH
EXISTING GYB SOFFIT
EXISTING GWB LEAD WALL, PATCH AND PAINT
CEILING SYSTEM, SEE REFLECTED CEILING PLAN
LEAD GWB SOFFIT AND FASCIA WITH
RECESSED ELECTRIC SHADE, SEE
ELECTRIC DRAWINGS
CORNER GUARD
WALL PROTECTION
CORNER GUARD
NEW GYB WALL
FINISH TO MATCH EXISTING
6" INTEGRAL WALL BASE
EXISTING GWB PARTITION,
PATCH & PAINT
EXISTING WINDOW SYSTEM, PAINT HM FRAME
EXISTING GWB LEAD WALL, PATCH AND PAINT
CEILING SYSTEM, SEE REFLECTED CEILING PLAN
EXISTING
OPENING
EXISTING ELECTRIC DUCT
COUNTERTOP…
This is the start of the file's text. The full file is on GovTribe.