Current Transformer Analyzer Test System (CT Analyzer) Specification

SPECIFICATIONS:

Current Transformer Analyzer Test System, multi-functional primary test system, all-in-one for testing and insulation diagnosis of transformers and bushings in the field, includes hardware and built-in software for testing of the CT's (Current Transformer) VT's (Voltage Transformer), power transformers, resistance, etc.

Salient Characteristics Power supply and Output:

o Input voltage; 100 - 240 VAC o Permissible input voltage 85 - 264 VAC o Frequency 50 / 60 Hz o Permissible frequency 45 Hz ... 65 Hz o Input power 500 VA o Connection Standard AC Socket IEC 60320 o Output voltage 0 ... 120 V o Output current 0 ... 5 A eff (15 A peak) o Output power 0 ... 400 VA eff (1500 VA peak) o Machine weight NTE 18 LBS with accessories.

o CT SB2 - input current .02A, weight not to exceed 7 lbs.

Environmental Characteristics:

o Operating temperature range (min/max) = 10 to +50° C (-14 to 122° F).

o Storage temperature range (min/max) = -25 to +70° C (-13 to 158° F).

o Humidity Relative humidity 5 % ... 95 % not condensing

Standard Test System includes:

o 1 each CT Analyzer Standard Package Transformer Test System (w/ listed

Options), or Equal. Professional Test Equipment for Protection and Metering Current Transformers with special measurement and assessment capability for CTs according to the NEW IEC 61869-2 Standard; CTs according to IEC- 60044-1 and IEEE C57.13; CTs up to class 0,3; knee point voltage from 1 V to 4 kV; PC Tool Set; Quick Test license; Consisting of CT Analyzer incl. bag and user manual full range of cable clamps, connectors and adapters. Or Equal with salient characters.

o 1 each Transport case Trolley Elevator Case CMC 430 and CT Analyzer. Or

Equal with salient characters.

o 1 each CT Analyzer Upgrade for 3 users or Equal. License for additional CT Analyzer Suite functionality (multi-test view, Advanced reporting, Report template designer, Simulation without connected device. Or Equal with salient characters.

Shipping included.

Maximum weight of unit to be less than 85 lbs.

Current Transformer Analyzer Test System (CT Analyzer) Specification

Certificate of calibration included.

Instruction manuals included.

Standard manufacturer's warranty on material and workmanship required.