C05_SolicitationAmendmentAttachment5NorthShortCircuitReport_1232SA26Q0763.pdf
PDF 477 KB Posted
- Attached to
- Campus Arc Flash Assessment, Ames, Iowa Federal contract opportunity
- Solicitation number
- 1232SA26Q0763
About this file
This file is a Short Circuit Report appendix from a comprehensive electrical system study for the USDA ARS facility located in Ames, Iowa. The document presents detailed fault current calculations across the facility's electrical distribution network, analyzing multiple fault scenarios (3-phase, single-line-to-ground, line-to-line, and line-to-line-to-ground faults) at various voltage levels and bus locations throughout the 91-building campus.
The report tabulates initial symmetrical and asymmetrical fault currents in amperes for numerous electrical buses and distribution points, including main switchgear, motor control centers, transformers, automatic transfer switches, chillers, air handling units, fire protection systems, emergency power panels, and various load centers distributed across buildings numbered 3 through 234. The data supports the Arc Flash Hazard Assessment update referenced in the related RFQ (solicitation 1232SA26Q0763), which requires recalculation of incident energy values and confirmation of protective device settings across 663 electrical panels in accordance with current applicable electrical standards. The study was prepared by Humber Garick and dated July 8, 2022 (Revision 1).
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| C05_SolicitationAmendmentAttachment4RequestsForInformation_1232SA26Q0763.pdf | ||
| C05_SolicitationAmendment1_1232SA26Q0763.pdf | ||
| C05_SolicitationAmendmentAttachment6SouthShortCircuitReport_1232SA26Q0763.pdf | ||
| C05_SolicitationAmendmentAttachment7AppFSampleLabels_1232SA26Q0763.pdf | ||
| SolicitationAttachment2QASP_1232SA26Q0763.pdf | ||
| 1232SA26Q0763.pdf | ||
| SolicitationAttachment3Wage Determination_1232SA26Q0763.pdf | ||
| SolicitationAttachment1PWS_1232SA26Q0763.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USDA ARS FACILITY ELECTRICAL
SYSTEM REPORT
APPENDIX D – SHORT CIRCUIT
REPORT
7/8/2022
REV. 1
PREPARED FOR:
142 Eglin Parkway SE Fort Walton Beach, FL 32548-5545
850.243.6723 / 888.618.3143 Toll Free www.humber-garick.com
DAPPER Fault Contribution Brief Report Comprehensive Short Circuit Study Settings
Three Phase Fault Single Line to Ground Line to Line Fault Line to Line to Ground
All BusesFaulted Bus
Yes
Yes Yes Yes Yes
Motor Contribution Transformer Tap Xformer Phase Shift
Yes
Yes
Bus Voltages Branch Currents Phase or Sequence Fault Current Calculation Asym Fault Current at Time 0.50
First Bus From Fault First Branch From Fault Report phase quantities Initial Symmetrical RMS (with 1/2 Cycle Asym)
Cycles
USDA
Project: USDA ARS Ames, IA Alliant Feed
Bus Name 3 Phase SLG LLG LL LLG LLSLG3 Phase
----------------Initial Symmetrical Amps---------------- --------------------------Asymmetrical Amps-------------------------
----------Contributions----------
(BLDG 7)-15KV SWITCH A 7,381 6,176 7,556 6,392 7,995 6,318 7,981 6,923
InCABLEFDR_T-A (BLDG 7) 109 61 99 95 118 62 105 102 InCABLEFDR_(BLDG 7)-15KV SWITCH A 7,273 6,115 7,457 6,298 7,877 6,256 7,877 6,822
(BLDG 7)-15KV-SWITCH B 7,344 6,140 7,514 6,360 7,949 6,281 7,934 6,884
InCABLEFDR_T-B (BLDG 7) 83 46 75 72 90 47 79 78 InCABLEFDR_(BLDG 7)-15KV SWITCH B 7,261 6,094 7,439 6,289 7,860 6,234 7,855 6,807
15KV-SWGR-A (BLDG 20) 7,005 5,752 7,070 6,066 7,546 5,891 7,458 6,535
InCABLEFDR_XFMR-T1A (BLDG 20) 16 9 15 14 18 9 16 15 InCABLEFDR_XFMR-T2A (BLDG 20) 224 123 203 195 241 126 214 210 InCABLEFDR_XFMR-T3A (BLDG 20) 265 145 239 229 285 148 252 247 InCABLEFDR_15KV-SWGR-A (BLDG 20) 6,505 5,478 6,614 5,633 7,008 5,610 6,978 6,069
15KV-SWGR-B (BLDG 20) 6,880 5,613 6,919 5,958 7,400 5,749 7,294 6,409
Bus Name 3 Phase SLG LLG LL LLG LLSLG3 Phase
----------------Initial Symmetrical Amps---------------- --------------------------Asymmetrical Amps-------------------------
----------Contributions---------- InCABLEFDR_XFMR-T1B (BLDG 20) 11 6 10 10 12 6 10 10 InCABLEFDR_XFMR-T2B (BLDG 20) 245 133 220 212 263 136 232 228 InCABLEFDR_XFMR-T3B (BLDG 20) 245 133 221 212 264 137 233 228 InCABLEFDR_15KV-SWGR-B (BLDG 20) 6,385 5,344 6,468 5,530 6,868 5,473 6,819 5,948
3PA-SECTION-1 9,374 7,787 9,267 8,118 10,356 8,192 10,047 8,968
InCABLEFDR_3PA-SECTION-2 0 0 0 0 0 0 0 0 InCABLEFDR_EF-A 195 108 174 169 215 114 189 186 InCABLEFDR_3PA-SECTION-1 9,180 7,680 9,094 7,950 10,142 8,080 9,860 8,783
3PA-SECTION-2 9,323 7,732 9,212 8,074 10,292 8,131 9,982 8,913
InCABLEFDR_3PA-SECTION-2 9,323 7,732 9,212 8,074 10,292 8,131 9,982 8,913
3PB-SECTION-1 9,176 7,484 9,051 7,947 10,075 7,824 9,756 8,725
InCABLEFDR_3PB-SECTION-2 0 0 0 0 0 0 0 0 InCABLEFDR_EF-B 195 106 174 169 214 111 188 185 InCABLEFDR_3PB-SECTION-1 8,983 7,378 8,878 7,779 9,863 7,714 9,569 8,541
3PB-SECTION-2 9,127 7,433 8,999 7,904 10,014 7,767 9,694 8,673
InCABLEFDR_XFMR-3LN 0 0 0 0 0 0 0 0 InCABLEFDR_3PB-SECTION-2 9,127 7,433 8,999 7,904 10,014 7,767 9,694 8,673
4160-SWGR-BUS-A-BLDG-154 13,510 15,056 14,972 11,700 16,303 18,871 18,520 14,119
InCABLEFDR_CHILLER-4 (BLDG 154) 1,099 816 996 952 1,326 1,023 1,232 1,148 InCABLEFDR_4160-SWGR-BUS-A_BLDG 154 5,229 6,441 6,263 4,528 6,310 8,073 7,747 5,465 InPI-EQUIPI-0004 7,182 7,799 7,816 6,220 8,668 9,775 9,668 7,506
4160-SWGR-BUS-B-BLDG-154 13,520 15,063 14,978 11,709 16,325 18,889 18,536 14,137
InCABLEFDR_CHILLER-8 (BLDG 154) 1,094 813 992 948 1,321 1,019 1,227 1,144 InCABLEFDR_CHILLER-5 (BLDG 154) 1,098 816 996 951 1,326 1,023 1,232 1,149 InCABLEFDR_4160-SWGR-BUS-B_BLDG 154 5,057 6,239 6,069 4,379 6,106 7,823 7,511 5,288 InPI-EQUIPI-0004 6,271 7,196 7,101 5,431 7,572 9,024 8,787 6,558
4PA-SECTION1 9,562 7,864 9,440 8,281 10,563 8,261 10,231 9,148
InCABLEFDR_4PA-SECTION2 155 85 139 135 172 89 150 149 InCABLEFDR_SUPPLY FAN 193 106 173 167 213 111 187 185 InCABLEFDR_4PA 9,215 7,674 9,131 7,980 10,180 8,061 9,896 8,816
4PA-SECTION2 9,511 7,809 9,385 8,236 10,498 8,199 10,165 9,092
InCABLEFDR_XFMR-LN (BLDG 4) 0 0 0 0 0 0 0 0 InCABLEFDR_EXHAUST FAN 155 85 139 135 172 89 150 149
----------------Initial Symmetrical Amps---------------- --------------------------Asymmetrical Amps-------------------------
----------Contributions---------- InCABLEFDR_4PA-SECTION2 9,356 7,724 9,247 8,103 10,328 8,110 10,015 8,944
4PB-SECTION1 9,523 7,729 9,395 8,247 10,479 8,080 10,141 9,075
InCABLEFDR_4PB-SECTION2 0 0 0 0 0 0 0 0 InCABLEFDR_EXHAUST-FAN 155 84 139 134 171 88 150 148 InCABLEFDR_SUPPLY-FAN 193 104 173 167 212 109 186 184 InCABLEFDR_4PB 9,177 7,542 9,086 7,947 10,098 7,884 9,807 8,745
4PB-SECTION2 9,471 7,675 9,339 8,202 10,413 8,020 10,074 9,018
InCABLEFDR_4PB-SECTION2 9,471 7,675 9,339 8,202 10,413 8,020 10,074 9,018
AHU-1G.1 (BLDG 20) 12,375 8,225 11,688 10,717 12,468 8,240 11,754 10,797
InIND-MTRMTR_AHU-1G.1 (BLDG 20) 587 260 520 509 592 261 523 513 InCABLEFDR_AHU-1G.1 (BLDG 20) 11,851 7,993 11,191 10,264 11,940 8,007 11,254 10,340
AHU-1G.2 (BLDG 20) 9,021 5,663 8,445 7,812 9,033 5,664 8,453 7,823
InIND-MTRMTR_AHU-1G.2 (BLDG 20) 588 246 520 509 589 246 520 510 InCABLEFDR_AHU-1G.2 (BLDG 20) 8,546 5,463 7,981 7,401 8,557 5,464 7,989 7,410
AHU-1H.1 (BLDG 20) 3,773 2,206 3,456 3,267 3,773 2,206 3,456 3,267
InIND-MTRMTR_AHU-1H.1 (BLDG 20) 235 92 206 204 235 92 206 204 InCABLEFDR_AHU-1H.1 (BLDG 20) 3,651 2,158 3,324 3,162 3,651 2,158 3,324 3,162
AHU-3.E1 (BLDG 20) 19,565 14,018 18,518 16,944 21,050 14,557 19,717 18,230
InIND-MTRMTR_AHU-3.E1 (BLDG 20) 1,176 562 1,040 1,019 1,265 583 1,107 1,096 InCABLEFDR_AHU-3.E1 (BLDG 20) 18,410 13,466 17,478 15,943 19,807 13,984 18,610 17,154
AHU-3E.2 (BLDG 20) 17,831 12,565 16,871 15,442 18,757 12,862 17,606 16,244
InIND-MTRMTR_AHU-3E.2 (BLDG 20) 1,176 553 1,040 1,019 1,237 566 1,085 1,072 InCABLEFDR_AHU-3E.2 (BLDG 20) 16,689 12,029 15,832 14,453 17,557 12,313 16,522 15,204
AHU-3E.3 (BLDG 20) 12,288 8,075 11,512 10,642 12,778 8,205 11,895 11,066
InIND-MTRMTR_AHU-3E.3 (BLDG 20) 1,175 515 1,037 1,018 1,222 523 1,072 1,058 InCABLEFDR_AHU-3E.3 (BLDG 20) 11,160 7,580 10,480 9,665 11,605 7,702 10,830 10,050
AHU-3E.4 (BLDG 20) 12,360 8,127 11,574 10,704 12,836 8,255 11,948 11,116
InIND-MTRMTR_AHU-3E.4 (BLDG 20) 1,176 516 1,038 1,019 1,221 524 1,072 1,058 InCABLEFDR_AHU-3E.4 (BLDG 20) 11,232 7,632 10,542 9,727 11,665 7,752 10,883 10,102
AHU-4.E2 (BLDG 20) 17,802 12,333 16,772 15,417 19,170 12,792 17,871 16,601
InIND-MTRMTR_AHU-4.E2 (BLDG 20) 1,175 543 1,038 1,018 1,265 563 1,106 1,096 InCABLEFDR_AHU-4.E2 (BLDG 20) 16,648 11,800 15,734 14,418 17,927 12,239 16,765 15,525
----------------Initial Symmetrical Amps---------------- --------------------------Asymmetrical Amps-------------------------
----------Contributions----------
AHU-4.E3 (BLDG 20) 11,265 7,224 10,547 9,755 11,599 7,298 10,804 10,045
InIND-MTRMTR_AHU-4.E3 (BLDG 20) 1,176 503 1,039 1,019 1,211 508 1,064 1,049 InCABLEFDR_AHU-4.E3 (BLDG 20) 10,150 6,746 9,521 8,790 10,451 6,816 9,753 9,051
AHU-4.E4 (BLDG 20) 11,127 7,060 10,402 9,636 11,453 7,131 10,653 9,918
InIND-MTRMTR_AHU-4.E4 (BLDG 20) 1,176 497 1,038 1,019 1,211 502 1,063 1,048 InCABLEFDR_AHU-4.E4 (BLDG 20) 10,013 6,587 9,376 8,671 10,306 6,654 9,603 8,925
AHU4-E.1 (BLDG 20) 14,312 9,463 13,398 12,395 15,048 9,676 13,982 13,032
InIND-MTRMTR_AHU4-E.1 (BLDG 20) 1,176 518 1,038 1,019 1,237 530 1,083 1,071 InCABLEFDR_AHU4-E.1 (BLDG 20) 13,172 8,960 12,363 11,407 13,849 9,162 12,901 11,993
AHU-7.1 (BLDG 24)-R 3,797 2,255 3,481 3,288 3,797 2,255 3,481 3,288
InIND-MTRMTR_AHU-7.1-RETURN 157 62 138 136 157 62 138 136 InCABLEFDR_AHU-7.1 (BLDG 24)-R 3,701 2,217 3,382 3,205 3,701 2,217 3,382 3,205
AHU-7.1 (BLDG 24)-S 4,444 2,599 4,113 3,849 4,444 2,599 4,114 3,849
InIND-MTRMTR_AHU-7.1-SUPPLY 470 183 414 407 470 183 414 407 InCABLEFDR_AHU-7.1 (BLDG 24)-S 4,126 2,473 3,790 3,573 4,126 2,473 3,790 3,573
AIR-COMP-1 (BLDG 154) 13,384 9,630 12,962 11,591 13,615 9,668 13,124 11,791
InIND-MTRMTR_AIR-COMP-1 (BLDG 154) 784 376 699 679 798 378 708 691 InCABLEFDR_AIR-COMP-1 (BLDG 154) 12,656 9,280 12,276 10,961 12,875 9,317 12,429 11,150
AIR-COMP-2 (BLDG 154) 13,826 10,049 13,419 11,974 14,090 10,095 13,604 12,203
InIND-MTRMTR_AIR-COMP-2 (BLDG 154) 784 380 700 679 799 382 709 692 InCABLEFDR_AIR-COMP-2 (BLDG 154) 13,095 9,694 12,730 11,341 13,345 9,738 12,906 11,557
ATS-1-(BLDG 9) 23,309 22,662 23,479 20,186 28,391 26,882 28,237 24,587
InATS-1 (BLDG 9) InCABLEFDR_DSP1-2 (BLDG 9) 0 0 0 0 0 0 0 0
ATS-1-LOAD (BLDG 154) 35,980 26,867 35,112 31,159 36,357 26,928 35,368 31,486
InATS-1 (BLDG 154) InCABLEFDR_T-7 (E-PP-1) 0 0 0 0 0 0 0 0
ATS-1-SOURCE 1 (BLDG 154) 35,980 26,867 35,112 31,159 36,357 26,928 35,368 31,486 InATS-1 (BLDG 154) 35,980 26,867 35,112 31,159 36,357 26,928 35,368 31,486 InCABLEFDR_ATS-1-SOURCE 1 (BLDG 154) 35,980 26,867 35,112 31,159 36,357 26,928 35,368 31,486
ATS-1-SOURCE 1 (BLDG 9) 23,309 22,662 23,479 20,186 28,391 26,882 28,237 24,587
InATS-1 (BLDG 9) 23,309 22,662 23,479 20,186 28,391 26,882 28,237 24,587
----------------Initial Symmetrical Amps---------------- --------------------------Asymmetrical Amps-------------------------
----------Contributions---------- InCABLEFDR_ATS-1-S1 23,309 22,662 23,479 20,186 28,391 26,882 28,237 24,587
ATS-1-SOURCE 2 (BLDG 154) 34,949 26,355 34,214 30,266 35,373 26,426 34,502 30,634 InATS-1 (BLDG 154) 0 0 0 0 0 0 0 0 InCABLEFDR_ATS-1-SOURCE 2 (BLDG 154) 34,949 26,355 34,214 30,266 35,373 26,426 34,502 30,634
ATS-1-SOURCE 2 (BLDG 9) 26,802 24,988 26,435 23,211 32,575 29,672 31,806 28,211
InATS-1 (BLDG 9) 0 0 0 0 0 0 0 0 InCABLEFDR_ATS-1-S2 26,802 24,988 26,435 23,211 32,575 29,672 31,806 28,211
ATS-2-(BLDG 9) 23,546 22,800 23,667 20,391 28,649 27,027 28,442 24,811
InATS-2 (BLDG 9) InCABLEFDR_DSP3-2 (BLDG 9) 313 202 278 271 381 240 334 330
ATS-2-LOAD (BLDG 154) 19,490 12,911 18,373 16,879 19,506 12,913 18,383 16,893
InATS-2 (BLDG 154) InCABLEFDR_E-LP-1 (BLDG 154) 0 0 0 0 0 0 0 0
ATS-2-SOURCE 1 (BLDG 154) 19,490 12,911 18,373 16,879 19,506 12,913 18,383 16,893 InATS-2 (BLDG 154) 19,490 12,911 18,373 16,879 19,506 12,913 18,383 16,893 InCABLEFDR_ATS-2-SOURCE 1 (BLDG 154) 19,490 12,911 18,373 16,879 19,506 12,913 18,383 16,893
ATS-2-SOURCE 1 (BLDG 9) 23,546 22,800 23,667 20,391 28,649 27,027 28,442 24,811
InATS-2 (BLDG 9) 23,233 22,598 23,401 20,120 28,268 26,788 28,122 24,481 InCABLEFDR_ATS-2-S1 23,233 22,598 23,401 20,120 28,268 26,788 28,122 24,481
ATS-2-SOURCE 2 (BLDG 154) 23,780 16,368 22,693 20,594 23,833 16,373 22,727 20,640 InATS-2 (BLDG 154) 0 0 0 0 0 0 0 0 InCABLEFDR_ATS-2-SOURCE 2 (BLDG 154) 23,780 16,368 22,693 20,594 23,833 16,373 22,727 20,640
ATS-2-SOURCE 2 (BLDG 9) 25,075 23,023 24,755 21,716 30,007 26,712 29,237 25,987
InATS-2 (BLDG 9) 313 202 278 271 381 240 334 330 InCABLEFDR_ATS-2-S2 25,075 23,023 24,755 21,716 30,007 26,712 29,237 25,987
ATS-3-LOAD (BLDG 153) 15,487 13,394 15,928 13,412 16,080 13,537 16,330 13,926
InCABLEFDR_E-LP-2 (BLDG 153) 0 0 0 0 0 0 0 0 InATS-3 (BLDG 153)
ATS-3-SOURCE 1 (BLDG 153) 15,487 13,394 15,928 13,413 16,080 13,537 16,330 13,926 InATS-3 (BLDG 153) 15,487 13,394 15,928 13,412 16,080 13,537 16,330 13,926 InCABLEFDR_ATS-3-SOURCE 1 (BLDG 153) 15,487 13,394 15,928 13,413 16,080 13,537 16,330 13,926
ATS-3-SOURCE 2 (BLDG 153) 7,629 4,989 7,208 6,607 7,630 4,989 7,208 6,608
----------------Initial Symmetrical Amps---------------- --------------------------Asymmetrical Amps-------------------------
----------Contributions---------- InATS-3 (BLDG 153) 0 0 0 0 0 0 0 0 InCABLEFDR_ATS-3-SOURCE 2 (BLDG 153) 7,629 4,989 7,208 6,607 7,630 4,989 7,208 6,608
ATS-4-LOAD (BLDG 153) 14,873 12,547 15,218 12,881 15,283 12,627 15,487 13,236
InATS-4 (BLDG 153) InCABLEFDR_T-8 (E-PP-2) 0 0 0 0 0 0 0 0
ATS-4-SOURCE 1 (BLDG 153) 14,873 12,547 15,218 12,881 15,283 12,627 15,487 13,236 InATS-4 (BLDG 153) 14,873 12,547 15,218 12,881 15,283 12,627 15,487 13,236 InCABLEFDR_ATS-4-SOURCE 1 (BLDG 153) 14,873 12,547 15,218 12,881 15,283 12,627 15,487 13,236
ATS-4-SOURCE 2 (BLDG 153) 7,425 4,838 7,006 6,430 7,426 4,838 7,006 6,431
InATS-4 (BLDG 153) 0 0 0 0 0 0 0 0 InCABLEFDR_ATS-4-SOURCE 2 (BLDG 153) 7,425 4,838 7,006 6,430 7,426 4,838 7,006 6,431
ATS-5-LOAD (BLDG 154) 22,781 20,394 22,818 19,729 25,714 22,011 25,269 22,269
InCABLEFDR_E-LP-11 (BLDG 154) 0 0 0 0 0 0 0 0 InATS-5 (BLDG 154)
ATS-5-SOURCE1 (BLDG 154) 22,781 20,394 22,818 19,729 25,714 22,012 25,269 22,269
InATS-5 (BLDG 154) 22,781 20,394 22,818 19,729 25,714 22,011 25,269 22,269 InCABLEFDR_ATS-5-SOURCE1 (BLDG 154) 22,781 20,394 22,818 19,729 25,714 22,012 25,269 22,269
ATS-5-SOURCE2 (BLDG 154) 23,233 21,047 23,274 20,120 26,475 22,967 26,031 22,928
InATS-5 (BLDG 154) 0 0 0 0 0 0 0 0 InCABLEFDR_ATS-5-SOURCE2 (BLDG 154) 23,233 21,047 23,274 20,120 26,475 22,967 26,031 22,928
ATS-6-LOAD (BLDG 156) 10,464 8,487 10,187 9,063 11,607 9,003 11,121 10,052
InATS-6 (BLDG 156) InCABLEFDR_E-LP-12 (BLDG 156) 0 0 0 0 0 0 0 0
ATS-6-SOURCE 1 (BLDG 156) 10,465 8,487 10,187 9,063 11,607 9,004 11,121 10,052
InATS-6 (BLDG 156) 10,464 8,487 10,187 9,063 11,607 9,003 11,121 10,052 InCABLEFDR_ATS-6-SOURCE 1 (BLDG 156) 10,465 8,487 10,187 9,063 11,607 9,004 11,121 10,052
BLDG 7-MDS-A 33,507 32,947 33,504 29,018 41,521 40,383 41,298 35,959
InPI-EQUIPI-0017 0 0 0 0 0 0 0 0 InCABLEFDR_HP1 (BLDG 7) 685 449 606 593 849 550 746 735 InCABLEFDR_HP5 (BLDG 7) 1,092 716 965 946 1,353 878 1,190 1,172 InCABLEFDR_HP3-SECT1 (BLDG 7) 1,502 985 1,328 1,301 1,861 1,207 1,637 1,612 InCABLEFDR_BLDG 7-MDS-A 30,234 30,801 30,830 26,184 37,466 37,753 38,002 32,446
----------------Initial Symmetrical Amps---------------- --------------------------Asymmetrical Amps-------------------------
----------Contributions----------
BLDG 7-MDS-B 31,944 31,169 32,064 27,664 39,234 37,508 38,997 33,978
InPI-EQUIPI-0017 0 0 0 0 0 0 0 0 InCABLEFDR_HP4 (BLDG 7) 339 221 301 294 417 265 366 361 InCABLEFDR_HP6 (BLDG 7) 671 436 595 581 824 525 723 714 InCABLEFDR_HP2 (BLDG 7) 1,428 929 1,266 1,237 1,754 1,118 1,539 1,519 InCABLEFDR_BLDG 7-MDS-B 29,508 29,584 30,046 25,555 36,242 35,601 36,543 31,387
BOILER-DS (BLDG 9) 9,053 6,302 8,649 7,840 9,093 6,308 8,676 7,875
InCABLEFDR_BOILER-DS 9,053 6,302 8,649 7,840 9,093 6,308 8,676 7,875
BUS_SCHP-2 (BLDG 154) 47,683 41,294 47,230 41,294 53,177 44,139 51,783 46,053
InIND-MTRMTR_SCHP-2 (BLDG 154) 1,960 1,132 1,748 1,698 2,186 1,210 1,916 1,893 InCABLEFDR_SCHP-2 (BLDG 154) 45,738 40,171 45,497 39,610 51,008 42,939 49,883 44,174
BUS_SCHP-3 (BLDG 154) 42,461 35,002 41,781 36,773 45,988 36,456 44,584 39,827
InIND-MTRMTR_SCHP-3 (BLDG 154) 1,960 1,077 1,749 1,698 2,123 1,122 1,866 1,839 InCABLEFDR_SCHP-3 (BLDG 154) 40,531 33,941 40,036 35,101 43,898 35,350 42,721 38,016
BUS-A (DIS-SWGR-A) 7,600 6,419 7,839 6,582 8,258 6,564 8,287 7,151
InCABLE1200A-BUS-TIE 0 0 0 0 0 0 0 0 InCABLEFDR_BUS-A-GEN-SWGR 0 0 0 0 0 0 0 0 InCABLEFDR_DB-SPLICE2-BLDG-153 143 80 130 124 155 82 137 134 InCABLEFDR_MH-A 512 307 476 444 557 314 503 482 InCABLEFDR_LIS-3 (BLDG 9) 567 320 516 492 616 327 546 535 InPI-EQUIPI-0002 923 520 839 800 1,003 532 887 869 InCABLEFDR_BUS-A (DIS-SWGR-A) 5,495 5,213 5,881 4,759 5,971 5,330 6,217 5,171
BUS-A(GEN-SWGR-A) 5,450 5,442 5,449 4,720 8,505 8,484 8,498 7,365
InCABLEFDR_BUS-A-GEN-SWGR 0 0 0 0 0 0 0 0 InCABLEFDR_GEN-2(DG-2) 728 728 728 630 1,136 1,134 1,135 984 InCABLEFDR_GEN-1(DG-1) 750 750 750 649 1,170 1,168 1,169 1,013 InCABLEFDR_CT-2 (TURBINE) 1,769 1,764 1,769 1,532 2,761 2,750 2,758 2,391 InCABLE1200A-GEN-BUS-TIE 2,204 2,201 2,203 1,908 3,439 3,432 3,436 2,978
BUS-B (DIS-SWGR-B) 7,523 6,343 7,751 6,515 8,163 6,483 8,188 7,070
InCABLE1200A-BUS-TIE 0 0 0 0 0 0 0 0 InCABLEFDR_BUS-B-GEN-SWGR 0 0 0 0 0 0 0 0 InCABLEFDR_DB-SPLICE1-BLDG-153 130 73 118 113 141 75 125 122 InCABLEFDR_LIS-2 (BLDG 9) 764 429 694 661 829 439 733 718
----------------Initial Symmetrical Amps---------------- --------------------------Asymmetrical Amps-------------------------
----------Contributions---------- InPI-EQUIPI-0003 874 491 794 757 949 502 839 821 InCABLEFDR_MH-B 1,061 760 1,001 919 1,151 777 1,058 997 InCABLEFDR_BUS-B (DIS-SWGR-B) 4,739 4,619 5,147 4,104 5,143 4,721 5,437 4,454
BUS-B(GEN-SWGR-B) 5,449 5,439 5,447 4,719 8,502 8,477 8,494 7,363
InCABLEFDR_BUS-B-GEN-SWGR 0 0 0 0 0 0 0 0 InCABLEFDR_GEN-6(DG-6) 728 727 728 630 1,135 1,134 1,135 983 InCABLEFDR_GEN-5(DG-5) 728 727 728 630 1,135 1,134 1,135 983 InCABLEFDR_GEN-4(DG-4) 750 749 750 649 1,170 1,168 1,169 1,013 InCABLE1200A-GEN-BUS-TIE 3,244 3,235 3,242 2,809 5,062 5,042 5,056 4,384
CEN-UPS-INV-INPUT (BLDG 20) 24,458 19,408 23,686 21,181 26,079 20,079 24,989 22,585 InCEN-UPS-INV (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_CEN-UPS-INV (BLDG 20) 24,458 19,408 23,686 21,181 26,079 20,079 24,989 22,585
CEN-UPS-INV-OUTPUT (BLDG 20) 23,439 18,610 22,693 20,299 25,043 19,281 23,985 21,687 InCABLEFDR_UPS-OUTPUT-ISO 0 0 0 0 0 0 0 0 InCEN-UPS-INV (BLDG 20) 361 325 346 312 553 498 530 530 InCABLEFDR_BYPASS-INPUT-ISO 23,089 18,311 22,370 19,998 24,668 18,972 23,644 21,366
CEN-UPS-MBP-BUS-1 (BLDG 20) 24,650 19,832 23,933 21,348 26,502 20,638 25,433 22,952 InPI-EQUIPI-0026 0 0 0 0 0 0 0 0 InCABLEFDR_BYPASS-INPUT-ISO 361 319 346 312 388 332 367 336 InCABLEFDR_CEN-UPS-MBP (BLDG 20) 24,301 19,531 23,608 21,046 26,127 20,325 25,088 22,627
CEN-UPS-MBP-BUS-2 (BLDG 20) 22,040 17,235 21,273 19,087 23,386 17,773 22,351 20,253 InPI-EQUIPI-0026 0 0 0 0 0 0 0 0 InCABLEFDR_U4LB (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_UPS-OUTPUT-ISO 22,040 17,235 21,273 19,087 23,386 17,773 22,351 20,253
CHILLER-4 (BLDG 154) 13,344 14,753 14,591 11,556 15,841 18,005 17,630 13,718
InIND-MTRMTR_CH-4 (BLDG 154) 1,100 811 992 953 1,306 990 1,199 1,131 InCABLEFDR_CHILLER-4 (BLDG 154) 12,245 13,944 13,689 10,605 14,536 17,017 16,540 12,589
CHILLER-5 (BLDG 154) 13,292 14,649 14,459 11,512 15,696 17,721 17,337 13,593
InIND-MTRMTR_CH-5 (BLDG 154) 1,100 808 991 953 1,299 978 1,188 1,125 InCABLEFDR_CHILLER-5 (BLDG 154) 12,194 13,842 13,561 10,560 14,399 16,745 16,260 12,470
CHILLER-8 (BLDG 154) 12,860 13,881 13,562 11,137 14,662 15,934 15,525 12,698
InIND-MTRMTR_CH-8 (BLDG 154) 1,099 791 980 952 1,253 908 1,122 1,085 InCABLEFDR_CHILLER-8 (BLDG 154) 11,766 13,094 12,691 10,190 13,415 15,030 14,529 11,618
----------------Initial Symmetrical Amps---------------- --------------------------Asymmetrical Amps-------------------------
----------Contributions----------
CT-1-MCC (BLDG 154) 22,296 19,913 22,215 19,309 25,347 21,685 24,804 21,951
InCABLEFDR_CT-1-MCC (BLDG 154) 22,296 19,913 22,215 19,309 25,347 21,685 24,804 21,951
CT-2 (TURBINE GEN) 5,415 5,391 5,412 4,690 8,331 8,265 8,311 7,215
InGENCT-2 (GEN) 1,780 1,780 1,780 1,541 2,738 2,729 2,733 2,371 InCABLEFDR_CT-2 (TURBINE) 3,636 3,611 3,632 3,149 5,593 5,537 5,578 4,844
CT-2-MCC (BLDG 154) 22,345 19,731 22,214 19,351 25,472 21,484 24,849 22,059
InCABLEFDR_TURBINE 963 567 858 834 1,097 617 960 950 InCABLEFDR_CT-2-MCC (BLDG 154) 21,385 19,166 21,371 18,520 24,377 20,868 23,906 21,111
D2A1B1 (BLDG 20) 6,507 7,256 6,984 5,636 7,105 7,932 7,632 6,153
InCABLEFDR_R2A1B3 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_R2A1B5 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_R2A1B2 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_R2A1B4 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_R2A1B1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2A1B1 (BLDG 20) 6,507 7,256 6,984 5,636 7,105 7,932 7,632 6,153
D2A2A1 (BLDG 20) 8,031 8,282 8,329 6,955 8,907 9,058 9,167 7,714
InCABLEFDR_R2A2A1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_R2A2A3 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_R2A2A4 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_R2A2A2 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2A2A1 (BLDG 20) 8,031 8,282 8,329 6,955 8,907 9,058 9,167 7,714
D2A2B1 (BLDG 20) 6,968 7,732 7,473 6,034 7,668 8,535 8,241 6,641
InCABLEFDR_R2A2B2 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_R2A2B1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_R2A2B3 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2A2B1 (BLDG 20) 6,968 7,732 7,473 6,034 7,668 8,535 8,241 6,641
D2A3A1 (BLDG 20) 5,573 5,488 5,694 4,826 6,003 5,815 6,082 5,198
InCABLEFDR_R2A3A3 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_R2A3A2 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_R2A3A1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2A3A1 (BLDG 20) 5,573 5,488 5,694 4,826 6,003 5,815 6,082 5,198
D2A3B1 (BLDG 20) 4,085 4,223 4,168 3,537 4,487 4,631 4,574 3,885
InCABLEFDR_R2A3B2 (BLDG 20) 0 0 0 0 0 0 0 0
----------------Initial Symmetrical Amps---------------- --------------------------Asymmetrical Amps-------------------------
----------Contributions---------- InCABLEFDR_R2A3B3 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_R2A3B1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2A3B1 (BLDG 20) 4,085 4,223 4,168 3,537 4,487 4,631 4,574 3,885
D2L1A1 (BLDG 20)-SEC1 10,515 11,216 10,912 9,107 11,974 12,774 12,427 10,370
InCABLEFDR_RM 1219-LAB-EQUIP 0 0 0 0 0 0 0 0 InCABLEFDR_RM 1329-LAB-EQUIP 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1A5 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1A7 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_RM 1203-LAB-EQUIP 0 0 0 0 0 0 0 0 InCABLEFDR_D2L1A1 (BLDG 20)-SEC2 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1A10 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1A9 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1A8 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2L1A1 (BLDG 20) 10,515 11,216 10,912 9,107 11,974 12,774 12,427 10,370
D2L1A1 (BLDG 20)-SEC2 10,371 10,966 10,739 8,981 11,775 12,416 12,173 10,197
InCABLEFDR_X2L1A4 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1A3 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1A2 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1A6 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1A1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2L1A1 (BLDG 20)-SEC2 10,371 10,966 10,739 8,981 11,775 12,416 12,173 10,197
D2L1B1 (BLDG 20)-SEC1 9,384 10,352 10,084 8,127 10,393 11,552 11,223 9,001
InCABLEFDR_X2L1B10 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1B2 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1B4 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1B5 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1B3 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2L1B1 (BLDG 20)-SEC2 0 0 0 0 0 0 0 0 InCABLEFDR_D2L1B1 (BLDG 20)-SEC1 9,384 10,352 10,084 8,127 10,393 11,552 11,223 9,001
D2L1B1 (BLDG 20)-SEC2 9,287 10,173 9,896 8,043 10,269 11,310 10,980 8,894
InCABLEFDR_X2L1B9 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1B8 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1B6 (BLDG 20) 0 0 0 0 0 0 0 0
----------------Initial Symmetrical Amps---------------- --------------------------Asymmetrical Amps-------------------------
----------Contributions---------- InCABLEFDR_X2L1B7 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1B1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2L1B1 (BLDG 20)-SEC2 9,287 10,173 9,896 8,043 10,269 11,310 10,980 8,894
D2L1C1 (BLDG 20)-SEC1 9,575 10,505 10,164 8,292 10,832 11,913 11,516 9,380
InCABLEFDR_RM 1605A-LAB EQUIP 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1C2 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1C5 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1C9 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1C12 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1C10 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1C4 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2L1C1 (BLDG 20)-SEC2 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1C11 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1C3 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2L1C1 (BLDG 20) 9,575 10,505 10,164 8,292 10,832 11,913 11,516 9,380
D2L1C1 (BLDG 20)-SEC2 9,395 10,179 9,874 8,137 10,589 11,453 11,116 9,170
InCABLEFDR_RM 1708A-LAB EQUIP 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1C1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1C8 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1C7 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1C6 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2L1C1 (BLDG 20)-SEC2 9,395 10,179 9,874 8,137 10,589 11,453 11,116 9,170
D2L1D1 (BLDG 20) 8,566 9,672 9,349 7,419 9,550 10,844 10,463 8,271
InCABLEFDR_X2L1D7 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1D9 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1D4 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1D6 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1D5 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1D10 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1D8 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1D2 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1D3 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L1D1 (BLDG 20) 0 0 0 0 0 0 0 0
----------------Initial Symmetrical Amps---------------- --------------------------Asymmetrical Amps-------------------------
----------Contributions---------- InCABLEFDR_D2L1D1 (BLDG 20) 8,566 9,672 9,349 7,419 9,550 10,844 10,463 8,271
D2L2A1 (BLDG 20)-SEC1 10,508 11,234 10,924 9,100 11,985 12,818 12,462 10,379
InCABLEFDR_X2L2A7 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_RM 2211A-LAB-EQUIP 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2A9 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2L2A1 (BLDG 20)-SEC2 0 0 0 0 0 0 0 0 InCABLEFDR_RM 2217L-LAB-EQUIP 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2A5 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2A10 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2A8 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2L2A1 (BLDG 20)-SEC1 10,508 11,234 10,924 9,100 11,985 12,818 12,462 10,379
D2L2A1 (BLDG 20)-SEC2 10,223 10,745 10,581 8,853 11,592 12,118 11,961 10,039
InCABLEFDR_X2L2A4 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2A6 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2A3 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2A2 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2A1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2L2A1 (BLDG 20)-SEC2 10,223 10,745 10,581 8,853 11,592 12,118 11,961 10,039
D2L2B1 (BLDG 20) 9,344 10,279 10,002 8,092 10,354 11,463 11,129 8,967
InCABLEFDR_RM 2227A-LAB-EQUIP 0 0 0 0 0 0 0 0 InCABLEFDR_RM 2227B-LAB-EQUIP 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2B2 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2B9 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2B4 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2B10 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2B7 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2B1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2B5 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2B8 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2B3 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2B6 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2L2B1 (BLDG 20) 9,344 10,279 10,002 8,092 10,354 11,463 11,129 8,967
D2L2C1 (BLDG 20)-SEC1 9,549 10,401 10,057 8,270 10,785 11,753 11,362 9,340
----------------Initial Symmetrical Amps---------------- --------------------------Asymmetrical Amps-------------------------
----------Contributions---------- InCABLEFDR_RM 2609-LAB-EQUIP 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2C2 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2C10 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2C5 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2C4 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2C3 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2L2C1 (BLDG 20)-SEC2 0 0 0 0 0 0 0 0 InCABLEFDR_D2L2C1 (BLDG 20)-SEC1 9,549 10,401 10,057 8,270 10,785 11,753 11,362 9,340
D2L2C1 (BLDG 20)-SEC2 9,236 9,845 9,659 7,998 10,365 10,983 10,802 8,977
InCABLEFDR_X2L2C8 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2C9 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2C7 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2C6 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2C1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2L2C1 (BLDG 20)-SEC2 9,236 9,845 9,659 7,998 10,365 10,983 10,802 8,977
D2L2D1 (BLDG 20) 8,568 9,621 9,289 7,420 9,546 10,765 10,379 8,267
InCABLEFDR_X2L2D7 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2D4 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2D9 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2D6 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2D10 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2D5 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2D3 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2D8 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2D2 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L2D1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2L2D1 (BLDG 20) 8,568 9,621 9,289 7,420 9,546 10,765 10,379 8,267
D2L3A1 (BLDG 20)-SEC1 10,197 10,995 10,697 8,831 11,525 12,463 12,111 9,981
InCABLEFDR_X2L3A7 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3A9 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3A4 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3A6 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3A5 (BLDG 20) 0 0 0 0 0 0 0 0
----------------Initial Symmetrical Amps---------------- --------------------------Asymmetrical Amps-------------------------
----------Contributions---------- InCABLEFDR_X2L3A10 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3A3 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3A8 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3A2 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3A1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2L3A1 (BLDG 20)-SEC2 0 0 0 0 0 0 0 0 InCABLEFDR_D2L3A1 (BLDG 20)-SEC1 10,197 10,995 10,697 8,831 11,525 12,463 12,111 9,981
D2L3A1 (BLDG 20)-SEC2 9,971 10,600 10,350 8,635 11,222 11,907 11,635 9,718
InCABLEFDR_E42-LAB-EQUIP 0 0 0 0 0 0 0 0 InCABLEFDR_D2L3A1 (BLDG 20)-SEC2 9,971 10,600 10,350 8,635 11,222 11,907 11,635 9,718
D2L3B1 (BLDG 20) 9,354 10,328 10,058 8,101 10,361 11,525 11,195 8,973
InCABLEFDR_RM 3222A-LAB-EQUIP 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3B2 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3B9 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3B4 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3B10 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3B7 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3B1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3B5 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3B8 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3B3 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3B6 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2L3B1 (BLDG 20) 9,354 10,328 10,058 8,101 10,361 11,525 11,195 8,973
D2L3C1 (BLDG 20) 9,626 10,545 10,203 8,336 10,899 11,967 11,570 9,439
InCABLEFDR_E31-LAB-EQUIP 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3C1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3C4 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3C7 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3C10 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_RM 3611A-LAB-EQUIP 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3C6 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3C3 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3C5 (BLDG 20) 0 0 0 0 0 0 0 0
----------------Initial Symmetrical Amps---------------- --------------------------Asymmetrical Amps-------------------------
----------Contributions---------- InCABLEFDR_X2L3C8 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3C2 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3C9 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2L3C1 (BLDG 20) 9,626 10,545 10,203 8,336 10,899 11,967 11,570 9,439
D2L3D1 (BLDG 20) 8,535 9,646 9,324 7,391 9,508 10,808 10,428 8,234
InCABLEFDR_RM 3723-LAB-EQUIP 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3D4 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3D7 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3D2 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_RM 3725-LAB-EQUIP 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3D5 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3D3 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3D6 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2L3D1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2L3D1 (BLDG 20) 8,535 9,646 9,324 7,391 9,508 10,808 10,428 8,234
D2LBA1 (BLDG 20) 11,066 11,577 11,437 9,583 12,853 13,345 13,227 11,131
InCABLEFDR_X2LBA3 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2LBA2 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2LBA5 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2LBA1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2LBA6 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2LBA7 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2LBA4 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2LBA1 (BLDG 20) 11,066 11,577 11,437 9,583 12,853 13,345 13,227 11,131
D2LBA2 (BLDG 20) 8,707 9,036 8,935 7,541 9,887 10,211 10,119 8,563
InCABLEFDR_R2LBA1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_R2LBA2 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_R2LBA3 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2LBA2 (BLDG 20) 8,707 9,036 8,935 7,541 9,887 10,211 10,119 8,563
D2LBA3 (BLDG 20) 11,403 11,953 11,750 9,875 13,247 13,835 13,622 11,472
InCABLEFDR_D2LBA3 (BLDG 20) 11,403 11,953 11,750 9,875 13,247 13,835 13,622 11,472
D2LBB1 (BLDG 20) 11,025 11,674 11,411 9,548 12,740 13,463 13,171 11,033
InCABLEFDR_RM-0707D-LAB-EQUIP 0 0 0 0 0 0 0 0
----------------Initial Symmetrical Amps---------------- --------------------------Asymmetrical Amps-------------------------
----------Contributions---------- InCABLEFDR_X2LBB2 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2LBB3 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2LBB5 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2LBB6 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_RM-0707C-LAB-EQUIP 0 0 0 0 0 0 0 0 InCABLEFDR_RM-0226-LAB-EQUIP 0 0 0 0 0 0 0 0 InCABLEFDR_X2LBB4 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2LBB7 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2LBB1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2LBB1 (BLDG 20) 11,025 11,674 11,411 9,548 12,740 13,463 13,171 11,033
D2LBC1 (BLDG 20) 10,443 11,185 10,886 9,044 11,996 12,826 12,492 10,389
InCABLEFDR_X2LBC1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2LBC2 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2LBC3 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2LBC4 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2LBC5 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2LBC6 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2LBC7 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2LBC1 (BLDG 20) 10,443 11,185 10,886 9,044 11,996 12,826 12,492 10,389
D2LBC2 (BLDG 20) 6,050 5,373 6,128 5,239 6,307 5,477 6,324 5,462
InCABLEFDR_R2LBC1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_R2LBC2 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_R2LBC3 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D2LBC2 (BLDG 20) 6,050 5,373 6,128 5,239 6,307 5,477 6,324 5,462
D2LBD1 (BLDG 20) 10,418 11,213 10,881 9,022 11,982 12,888 12,510 10,377
InCABLEFDR_E4-1 (LAB EQUIPMENT) 0 0 0 0 0 0 0 0 InCABLEFDR_X2LBD3 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2LBD1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_X2LBD2 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_E4-2 (LAB EQUIPMENT) 0 0 0 0 0 0 0 0 InCABLEFDR_D2LBD1 (BLDG 20) 10,418 11,213 10,881 9,022 11,982 12,888 12,510 10,377
D2S11 (BLDG 24) 10,398 11,416 11,017 9,005 11,528 12,649 12,210 9,984
InCABLEFDR_R2S15 (BLDG 24) 0 0 0 0 0 0 0 0
----------------Initial Symmetrical Amps---------------- --------------------------Asymmetrical Amps-------------------------
----------Contributions---------- InCABLEFDR_R2S11 (BLDG 24)-SEC1 0 0 0 0 0 0 0 0 InCABLEFDR_R2S12 (BLDG 24)-SEC1 0 0 0 0 0 0 0 0 InCABLEFDR_R2S13 (BLDG 24) 0 0 0 0 0 0 0 0 InCABLEFDR_R2S14 (BLDG 24) 0 0 0 0 0 0 0 0 InCABLEFDR_BAILER (BLDG 20) 172 126 153 149 191 140 170 165 InCABLEFDR_D2S11 (BLDG 24) 10,226 11,290 10,875 8,856 11,338 12,509 12,052 9,819
D4A1B1 (BLDG 20) 8,227 5,861 7,729 7,125 8,665 6,033 8,087 7,504
InCABLEFDR_L4A1B1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T6K (D2A1B1) 0 0 0 0 0 0 0 0 InCABLEFDR_D4A1B1 (BLDG 20) 8,227 5,861 7,729 7,125 8,665 6,033 8,087 7,504
D4A2A1 (BLDG 20) 20,489 17,022 19,975 17,744 22,746 18,163 21,854 19,698
InCABLEFDR_L4A2A1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T6K (D2A2A1) 0 0 0 0 0 0 0 0 InCABLEFDR_D4A2A1 (BLDG 20) 20,489 17,022 19,975 17,744 22,746 18,163 21,854 19,698
D4A2B1 (BLDG 20) 9,755 7,083 9,206 8,448 10,329 7,313 9,675 8,946
InCABLEFDR_XFMR-T6K (D2A2B1) 0 0 0 0 0 0 0 0 InCABLEFDR_L4A2B1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_D4A2B1 (BLDG 20) 9,755 7,083 9,206 8,448 10,329 7,313 9,675 8,946
D4A3A1 (BLDG 20) 22,294 18,824 22,068 19,307 24,205 19,660 23,596 20,962
InCABLEFDR_L4A3A1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T5G (D2A3A1) 0 0 0 0 0 0 0 0 InCABLEFDR_D4A3A1 (BLDG 20) 22,294 18,824 22,068 19,307 24,205 19,660 23,596 20,962
D4A3B1 (BLDG 20) 13,555 10,169 13,022 11,739 14,076 10,337 13,426 12,190
InCABLEFDR_L4A3B1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T5G (D2A3B1) 0 0 0 0 0 0 0 0 InCABLEFDR_D4A3B1 (BLDG 20) 13,555 10,169 13,022 11,739 14,076 10,337 13,426 12,190
D4L1A1 (BLDG 20) 21,773 18,240 21,512 18,856 23,552 18,999 22,929 20,397
InCABLEFDR_L4L1A1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T5K (R2L1A1) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T8 (D2L1A1) 0 0 0 0 0 0 0 0 InCABLEFDR_D4L1A1 (BLDG 20) 21,773 18,240 21,512 18,856 23,552 18,999 22,929 20,397
D4L1B1 (BLDG 20) 13,555 10,169 13,022 11,739 14,076 10,337 13,426 12,190
InCABLEFDR_L4L1B1 (BLDG 20) 0 0 0 0 0 0 0 0
----------------Initial Symmetrical Amps---------------- --------------------------Asymmetrical Amps-------------------------
----------Contributions---------- InCABLEFDR_XFMR-T5K (R2L1B1) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T8 (D2L1B1) 0 0 0 0 0 0 0 0 InCABLEFDR_D4L1B1 (BLDG 20) 13,555 10,169 13,022 11,739 14,076 10,337 13,426 12,190
D4L1C1 (BLDG 20) 14,772 11,367 14,134 12,793 15,930 11,870 15,083 13,796
InCABLEFDR_XFMR-T5K (R2L1C1) 0 0 0 0 0 0 0 0 InCABLEFDR_L4L1C1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T8 (D2L1C1) 0 0 0 0 0 0 0 0 InCABLEFDR_D4L1C1 (BLDG 20) 14,772 11,367 14,134 12,793 15,930 11,870 15,083 13,796
D4L1D1 (BLDG 20) 10,330 7,555 9,765 8,946 10,962 7,811 10,281 9,493
InCABLEFDR_XFMR-T5K (R2L1D1) 0 0 0 0 0 0 0 0 InCABLEFDR_L4L1D1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T8 (D2L1D1) 0 0 0 0 0 0 0 0 InCABLEFDR_D4L1D1 (BLDG 20) 10,330 7,555 9,765 8,946 10,962 7,811 10,281 9,493
D4L2A1 (BLDG 20) 24,319 21,183 24,250 21,061 26,828 22,405 26,292 23,234
InCABLEFDR_L4L2A1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T8 (D2L2A1) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T5K (R2L2A1) 0 0 0 0 0 0 0 0 InCABLEFDR_D4L2A1 (BLDG 20) 24,319 21,183 24,250 21,061 26,828 22,405 26,292 23,234
D4L2B1 (BLDG 20) 14,414 10,945 13,891 12,483 15,020 11,144 14,361 13,007
InCABLEFDR_L4L2B1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T5K (R2L2B1) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T8 (D2L2B1) 0 0 0 0 0 0 0 0 InCABLEFDR_D4L2B1 (BLDG 20) 14,414 10,945 13,891 12,483 15,020 11,144 14,361 13,007
D4L2C1 (BLDG 20) 16,125 12,629 15,494 13,964 17,497 13,243 16,622 15,153
InCABLEFDR_XFMR-T8 (D2L2C1) 0 0 0 0 0 0 0 0 InCABLEFDR_L4L2C1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T5K (R2L2C1) 0 0 0 0 0 0 0 0 InCABLEFDR_D4L2C1 (BLDG 20) 16,125 12,629 15,494 13,964 17,497 13,243 16,622 15,153
D4L2D1 (BLDG 20) 10,864 8,000 10,286 9,408 11,552 8,280 10,848 10,004
InCABLEFDR_XFMR-T5K (R2L2D1) 0 0 0 0 0 0 0 0 InCABLEFDR_L4L2D1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T8 (D2L2D1) 0 0 0 0 0 0 0 0 InCABLEFDR_D4L2D1 (BLDG 20) 10,864 8,000 10,286 9,408 11,552 8,280 10,848 10,004
----------------Initial Symmetrical Amps---------------- --------------------------Asymmetrical Amps-------------------------
----------Contributions----------
D4L3A1 (BLDG 20) 20,343 16,681 19,992 17,618 21,797 17,262 21,141 18,876
InCABLEFDR_L4LPA1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_L4L3A1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T5K (R2L3A1) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T8 (D2L3A1) 0 0 0 0 0 0 0 0 InCABLEFDR_D4L3A1 (BLDG 20) 20,343 16,681 19,992 17,618 21,797 17,262 21,141 18,876
D4L3B1 (BLDG 20) 13,972 10,543 13,443 12,100 14,533 10,725 13,878 12,586
InCABLEFDR_L4L3B1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_L4LPB1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T5K (R2L3B1) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T8 (D2L3B1) 0 0 0 0 0 0 0 0 InCABLEFDR_D4L3B1 (BLDG 20) 13,972 10,543 13,443 12,100 14,533 10,725 13,878 12,586
D4L3C1 (BLDG 20) 15,560 11,905 14,891 13,476 16,863 12,455 15,955 14,604
InCABLEFDR_L4LPC1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T5K (R2L3C1) 0 0 0 0 0 0 0 0 InCABLEFDR_L4L3C1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T8 (D2L3C1) 0 0 0 0 0 0 0 0 InCABLEFDR_ELEV-1 232 118 206 201 252 124 220 218 InCABLEFDR_ELEV-2 232 119 206 201 252 124 221 218 InCABLEFDR_D4L3C1 (BLDG 20) 15,101 11,670 14,480 13,078 16,366 12,210 15,515 14,173
D4L3D1 (BLDG 20) 10,433 7,640 9,865 9,035 11,075 7,900 10,390 9,591
InCABLEFDR_L4LPD1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T5K (R2L3D1) 0 0 0 0 0 0 0 0 InCABLEFDR_L4L3D1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T8 (D2L3D1) 0 0 0 0 0 0 0 0 InCABLEFDR_D4L3D1 (BLDG 20) 10,433 7,640 9,865 9,035 11,075 7,900 10,390 9,591
D4LBA1 (BLDG 20) 27,995 25,947 28,030 24,245 32,715 29,164 32,196 28,332
InCABLEFDR_XFMR-T6K (D2LBA2) 0 0 0 0 0 0 0 0 InCABLEFDR_RP1-JB 0 0 0 0 0 0 0 0 InCABLEFDR_L4LBA1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T8 (D2LBA1) 0 0 0 0 0 0 0 0 InCABLEFDR_D4LBA1 (BLDG 20) 27,995 25,947 28,030 24,245 32,715 29,164 32,196 28,332
D4LBA2 (BLDG 20) 30,254 25,823 29,386 26,201 34,483 28,429 33,063 29,863
----------------Initial Symmetrical Amps---------------- --------------------------Asymmetrical Amps-------------------------
----------Contributions---------- InCABLEFDR_DESS-DEHUMID 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T8 (D2LBA3) 0 0 0 0 0 0 0 0 InCABLEFDR_D4LBA2 (BLDG 20) 30,254 25,823 29,386 26,201 34,483 28,429 33,063 29,863
D4LBB1 (BLDG 20) 24,396 21,483 24,401 21,127 27,125 22,856 26,635 23,491
InCABLEFDR_L4LBB1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T8 (D2LBB1) 0 0 0 0 0 0 0 0 InCABLEFDR_ELEV-4 (BLDG 20) 307 180 275 266 342 192 300 296 InCABLEFDR_D4LBB1 (BLDG 20) 24,090 21,303 24,130 20,862 26,785 22,665 26,339 23,196
D4LBC1 (BLDG 20) 20,101 16,611 19,571 17,408 22,266 17,692 21,370 19,283
InCABLEFDR_CAPPED1 0 0 0 0 0 0 0 0 InCABLEFDR_CAPPED2 0 0 0 0 0 0 0 0 InCABLEFDR_RP2-JB 0 0 0 0 0 0 0 0 InCABLEFDR_L4LBC1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T6K (D2LBC2) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T8 (D2LBC1) 0 0 0 0 0 0 0 0 InCABLEFDR_D4LBC1 (BLDG 20) 20,101 16,611 19,571 17,408 22,266 17,692 21,370 19,283
D4LBD1 (BLDG 20) 19,135 15,759 18,613 16,571 21,170 16,769 20,303 18,333
InCABLEFDR_L4LBD1 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T4K (R2LBD2 ) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T8 (D2LBD1) 0 0 0 0 0 0 0 0 InCABLEFDR_D4LBD1 (BLDG 20) 19,135 15,759 18,613 16,571 21,170 16,769 20,303 18,333
D4S11 (BLDG 24) 15,131 10,784 14,220 13,104 16,158 11,196 15,065 13,994
InCABLEFDR_L4S11 (BLDG 24) 0 0 0 0 0 0 0 0 InCABLEFDR_M4S12 (BLDG 24) 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-T7 (D2S11) 74 35 65 64 79 36 69 68 InCABLEFDR_M4S11 (BLDG 24) 154 73 136 134 165 76 144 143 InCABLEFDR_AHU-7.1 (BLDG 24)-S 450 214 397 390 481 222 420 416 InCABLEFDR_D4S11 (BLDG 24) 14,459 10,465 13,624 12,522 15,441 10,864 14,433 13,372
DB (BLDG 125) 3,307 2,223 3,125 2,864 3,310 2,223 3,127 2,866
InCABLEFDR_PANEL B (BLDG 125) 0 0 0 0 0 0 0 0 InCABLEFDR_DB (BLDG 125) 3,307 2,223 3,125 2,864 3,310 2,223 3,127 2,866
DC2-1-1 (BLDG 9) 10,460 10,589 10,859 9,058 11,905 11,738 12,185 10,310
InCABLEFDR_DC2-1-1 (BLDG 9) 10,460 10,589 10,859 9,058 11,905 11,738 12,185 10,310
----------------Initial Symmetrical Amps---------------- --------------------------Asymmetrical Amps-------------------------
----------Contributions----------
DC2-1-2 (BLDG 9) 10,460 10,589 10,859 9,058 11,905 11,738 12,185 10,310
InCABLEFDR_DC2-1-2 (BLDG 9) 10,460 10,589 10,859 9,058 11,905 11,738 12,185 10,310
DC4-1-1 (BLDG 9) 10,318 10,446 10,759 8,936 11,736 11,533 12,042 10,164
InCABLEFDR_DC4-1-1 (BLDG 9) 10,318 10,446 10,759 8,936 11,736 11,533 12,042 10,164
DC4-1-2 (BLDG 9) 10,318 10,446 10,759 8,936 11,736 11,533 12,042 10,164
InCABLEFDR_DC4-1-2 (BLDG 9) 10,318 10,446 10,759 8,936 11,736 11,533 12,042 10,164
DC4-1-3 (BLDG 9) 10,318 10,446 10,759 8,936 11,736 11,533 12,042 10,164
InCABLEFDR_DC4-1-3 (BLDG 9) 10,318 10,446 10,759 8,936 11,736 11,533 12,042 10,164
DISCONNECT-T6K 8,281 8,742 8,580 7,172 9,311 9,791 9,625 8,063
InCABLEFDR_D2LBC2 (BLDG 20) 0 0 0 0 0 0 0 0 InCABLEFDR_DISCONNECT-T6K 8,281 8,742 8,580 7,172 9,311 9,791 9,625 8,063
DP-125 10,184 9,889 10,302 8,820 11,294 10,755 11,317 9,781
InCABLEFDR_DS-1 (BLDG 125) 0 0 0 0 0 0 0 0 InCABLEFDR_DP-125 10,184 9,889 10,302 8,820 11,294 10,755 11,317 9,781
DP-3D1 10,704 9,221 10,737 9,270 12,033 9,790 11,789 10,420
InCABLEFDR_XFMR-DP-3D4 0 0 0 0 0 0 0 0 InCABLEFDR_DP-3D1 10,704 9,221 10,737 9,270 12,033 9,790 11,789 10,420
DP-3D4 5,964 6,481 6,287 5,165 6,665 7,259 7,035 5,772
InCABLEFDR_IRRADIATOR 0 0 0 0 0 0 0 0 InCABLEFDR_LA (BLDG 3) 0 0 0 0 0 0 0 0 InCABLEFDR_LF (BLDG 3) 0 0 0 0 0 0 0 0 InCABLEFDR_LC (BLDG 3) 0 0 0 0 0 0 0 0 InCABLEFDR_IRRADIATOR-CHILLER 0 0 0 0 0 0 0 0 InCABLEFDR_LB (BLDG 3) 0 0 0 0 0 0 0 0 InCABLEFDR_LD (BLDG 3) 0 0 0 0 0 0 0 0 InCABLEFDR_DP-3D4 5,964 6,481 6,287 5,165 6,665 7,259 7,035 5,772
DP-3D6 5,996 6,525 6,328 5,193 6,731 7,343 7,115 5,829
InCABLEFDR_LH (BLDG 3) 0 0 0 0 0 0 0 0 InCABLEFDR_LK (BLDG 3) 0 0 0 0 0 0 0 0 InCABLEFDR_LG (BLDG 3) 0 0 0 0 0 0 0 0 InCABLEFDR_LL (BLDG 3) 0 0 0 0 0 0 0 0 InCABLEFDR_LP (BLDG 3) 0 0 0 0 0 0 0 0 InCABLEFDR_LM (BLDG 3) 0 0 0 0 0 0 0 0
----------------Initial Symmetrical Amps---------------- --------------------------Asymmetrical Amps-------------------------
----------Contributions---------- InCABLEFDR_DP-3D6 5,996 6,525 6,328 5,193 6,731 7,343 7,115 5,829
DP-3M3 10,638 9,275 10,665 9,213 11,999 9,909 11,761 10,391
InCABLEFDR_XFMR-DP-3D6 0 0 0 0 0 0 0 0 InCABLEFDR_DP-3M3 10,638 9,275 10,665 9,213 11,999 9,909 11,761 10,391
DP-4D1 10,999 9,430 11,034 9,526 12,378 10,003 12,119 10,719
InCABLEFDR_XFMR-DP-4D4 0 0 0 0 0 0 0 0 InCABLEFDR_DP-4D1 10,999 9,430 11,034 9,526 12,378 10,003 12,119 10,719
DP-4D4 6,076 6,572 6,369 5,262 6,852 7,416 7,185 5,934
InCABLEFDR_LB (BLDG 4) 0 0 0 0 0 0 0 0 InCABLEFDR_LD (BLDG 4) 0 0 0 0 0 0 0 0 InCABLEFDR_LA (BLDG 4) 0 0 0 0 0 0 0 0 InCABLEFDR_LC (BLDG 4) 0 0 0 0 0 0 0 0 InCABLEFDR_LF (BLDG 4) 0 0 0 0 0 0 0 0 InCABLEFDR_DP-4D4 6,076 6,572 6,369 5,262 6,852 7,416 7,185 5,934
DP-4D6 6,042 6,561 6,371 5,233 6,772 7,375 7,153 5,864
InCABLEFDR_LH (BLDG 4) 0 0 0 0 0 0 0 0 InCABLEFDR_LM (BLDG 4) 0 0 0 0 0 0 0 0 InCABLEFDR_LK (BLDG 4) 0 0 0 0 0 0 0 0 InCABLEFDR_LJ (BLDG 4) 0 0 0 0 0 0 0 0 InCABLEFDR_LG (BLDG 4) 0 0 0 0 0 0 0 0 InCABLEFDR_LL (BLDG 4) 0 0 0 0 0 0 0 0 InCABLEFDR_DP-4D6 6,042 6,561 6,371 5,233 6,772 7,375 7,153 5,864
DP-4M3 11,160 9,763 11,216 9,665 12,654 10,454 12,416 10,959
InCABLEFDR_EX-WEATHERHEAD 0 0 0 0 0 0 0 0 InCABLEFDR_XFMR-DP-4D6 0 0 0 0 0 0 0 0 InCABLEFDR_DP-4M3 11,160 9,763 11,216 9,665 12,654 10,454 12,416 10,959
DP-B1 0 0 0 0 0 0 0 0
InCABLEFDR_DP-B1 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 230) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 231) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 232) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 233) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 234) 0 0 0 0 0 0 0 0
----------------Initial Symmetrical Amps---------------- --------------------------Asymmetrical Amps-------------------------
----------Contributions----------
DP-B2 18,665 18,118 18,584 16,164 21,357 20,537 21,171 18,496
InCABLEFDR_CAPPED (BLDG 198) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 199) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 197) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 196) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 200) 0 0 0 0 0 0 0 0 InCABLEFDR_DP-B2 18,665 18,118 18,584 16,164 21,357 20,537 21,171 18,496
DP-B3 18,679 18,127 18,601 16,176 21,390 20,556 21,203 18,524
InCABLEFDR_P-1 (BLDG 191) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 195) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 192) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 194) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 193) 0 0 0 0 0 0 0 0 InCABLEFDR_DP-B3 18,679 18,127 18,601 16,176 21,390 20,556 21,203 18,524
DP-B4 19,374 16,641 18,906 16,779 21,579 17,954 20,803 18,688
InCABLEFDR_P-1 (BLDG 17) 0 0 0 0 0 0 0 0 InCABLEFDR_LA (BLDG 11) 0 0 0 0 0 0 0 0 InCABLEFDR_MDP (BLDG 10) 171 98 152 148 191 106 167 165 InCABLEFDR_DP-B4 19,203 16,543 18,758 16,631 21,389 17,849 20,639 18,523
DP-B5 9,770 9,338 9,705 8,461 11,024 10,403 10,886 9,547
InCABLEFDR_LA-1 (BLDG 14) 0 0 0 0 0 0 0 0 InCABLEFDR_LA-2 (BLDG 16) 0 0 0 0 0 0 0 0 InCABLEFDR_LA (BLDG 13) 0 0 0 0 0 0 0 0 InCABLEFDR_DP-B5 9,770 9,338 9,705 8,461 11,024 10,403 10,886 9,547
DP-C1 0 0 0 0 0 0 0 0
InCABLEFDR_DP-C1 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 221) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 222) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 223) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 224) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 225) 0 0 0 0 0 0 0 0
DP-C2 0 0 0 0 0 0 0 0
InCABLEFDR_DP-C2 0 0 0 0 0 0 0 0
----------------Initial Symmetrical Amps---------------- --------------------------Asymmetrical Amps-------------------------
----------Contributions---------- InCABLEFDR_P-1 (BLDG 217) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 218) 0 0 0 0 0 0 0 0
DP-C3 0 0 0 0 0 0 0 0
InCABLEFDR_DP-C3 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 209) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 210) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 211) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 212) 0 0 0 0 0 0 0 0
DP-C4 0 0 0 0 0 0 0 0
InCABLEFDR_DP-C4 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 201) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 202) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 203) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 204) 0 0 0 0 0 0 0 0
DP-C5 0 0 0 0 0 0 0 0
InCABLEFDR_DP-C5 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 205) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 206) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 207) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 208) 0 0 0 0 0 0 0 0
DP-C6 0 0 0 0 0 0 0 0
InCABLEFDR_DP-C6 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 213) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 214) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 215) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 216) 0 0 0 0 0 0 0 0
DP-C7 0 0 0 0 0 0 0 0
InCABLEFDR_DP-C7 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 219) 0 0 0 0 0 0 0 0 InCABLEFDR_P-1 (BLDG 220) 0 0 0 0 0 0 0 0
DS-1 (BLDG 125) 5,413 3,947 5,262 4,688 5,426 3,948 5,270 4,699
InCABLEFDR_DB (BLDG 125) 0 0 0 0 0 0 0 0 InCABLEFDR_LA (BLDG 125) 0 0 0 0 0 0 0 0
----------------Initial Symmetrical Amps---------------- --------------------------Asymmetrical Amps-------------------------
----------Contributions---------- InCABLEFDR_DS-1 (BLDG 125) 5,413 3,947 5,262 4,688 5,426 3,948 5,270 4,699
DSP1-1 (BLDG 9) 10,707 11,311 11,139 9,272 12,649 13,248 13,094 10,954
InCABLEFDR_PP1-1-1 (BLDG 9) 0 0 0 0 0 0 0 0 InCABLEFDR_PP1-1-3 (BLDG 9) 0 0 0 0 0 0 0 0 InCABLEFDR_PP1-1-4 (BLDG 9) 0 0 0 0 0 0 0 0 InCABLEFDR_PP1-1-5 (BLDG 9) 0 0 0 0 0 0 0 0 InCABLEFDR_PP1-1-2 (BLDG 9) 0 0 0 0 0 0 0 0 InCABLEFDR_DSP1-1 (BLDG 9) 10,707 11,311 11,139 9,272 12,649 13,248 13,094 10,954
DSP-1-2 (BLDG 9) 22,811 21,946 22,949 19,754 27,561 25,726 27,336 23,868
InCABLEFDR_T1-2 (BLDG 9) 0 0 0 0 0 0 0 0 InCABLEFDR_LP1-2-1 (BLDG 9) 0 0 0 0 0 0 0 0 InCABLEFDR_LP1-2-2 (BLDG 9) 0 0 0 0 0 0 0 0 InCABLEFDR_DSP1-2 (BLDG 9) 22,811 21,946 22,949 19,754 27,561 25,726 27,336 23,868
DSP1-3 (BLDG 9) 23,348 22,659 23,777 20,220 27,748 25,949 27,753 24,030
InCABLEFDR_DSP1-3 (BLDG 9) 23,348 22,659 23,777 20,220 27,748 25,949 27,753 24,030
DSP1-4 (BLDG 9) 23,654 23,115 23,804 20,485 29,057 27,755 28,920 25,164
InIND-MTRMTR_DSP1-4(LUMPED) 782 509 694 677 961 612 843 832 InCABLEFDR_DSP1-4 (BLDG 9) 22,872 22,606 23,142 19,808 28,097 27,143 28,117 24,332
DSP2-1 (BLDG 9) 11,089 11,642 11,419 9,604 13,102 13,722 13,473 11,346
InCABLEFDR_UPS-1-MBP-INPUT 0 0 0 0 0 0 0 0 InCABLEFDR_DC2-1-1 (BLDG 9) 0 0 0 0 0 0 0 0 InCABLEFDR_DC2-1-2 (BLDG 9) 0 0 0 0 0 0 0 0 InCABLEFDR_PP2-1-3 (BLDG 9) 0 0 0 0 0 0 0 0 InCABLEFDR_PP2-1-4 (BLDG 9) 0 0 0 0 0 0 0 0 InCABLEFDR_DSP2-1 (BLDG 9) 11,089 11,642 11,419 9,604 13,102 13,722 13,473 11,346
DSP2-3 (BLDG 9) 27,649 26,008 27,271 23,944 34,016 31,390 33,270 29,459
InCABLEFDR_EAU-C-1 196 123 173 170 241 148 211 209 InCABLEFDR_EAU-A-3 196 123 173 170 241 148 211 209 InCABLEFDR_EAU-E-3 196 123 173 170 241 148 211 209 InCABLEFDR_AHU-C-1 235 147 208 203 289 178 253 250 InCABLEFDR_AHU-C-2 235 147 208 203 289 178 253 250 InCABLEFDR_EAU-C-3 235 147 208 203 289 178 253 250 InCABLEFDR_AHU-E-1 391 246 346 339 482 296 422 417
----------------Initial Symmetrical Amps----------------…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .