BUILDING 1036 - FIRE ALARM PLAN
SCALE: 1/8" = 1'-0"
SYMBOL DESCRIPTION
COMING IN - OUT PIPES
5t h
FI
G H
TE
R
W
IN
G
FL
O R
ID
A
A
IR
N A
TI
O
N A
L G
U A
R D
JA
C
K
SO
N V
IL
LE
IN
TE
R N
A
TI
O N
A L
A
IR
PO
R
T, F
L
SYMBOL DESCRIPTION BACK BOX MOUNTING
ATP
LAD
ADC
AO
A
ALARM TRANSCEIVER PANEL
LIGHTING ARRESTOR & DISCHARGE
ADDRESSABLE DRIVER CARD
ADDRESSABLE OUTPUT
ALARM TRANSCEIVER PANEL ANTENNA
AI ADDRESSABLE INPUT
EW EMERGENCY EYE WASH STATION
WIRING LEGEND
A
B
C
D
F
P
R
S
T
U
MARK NUMBER OF WIRES
BACK BOX LEGEND
SIZE & WIRE TYPE CIRCUIT DESCRIPTION RECOMMENDED COLOR CODE
2C THHN
FPLR OR FPLP INITIATION CIRCUIT
NOTIFICATION CIRCUIT
SPEAKER CIRCUIT
DOOR HOLDER CIRCUIT
FIREMANS PHONE JACK
24v AUXILARY POWER
FAAP DATA
ADDRESSABLE DATA LOOP
NAC TRIP CIRCUIT
BACK FLOW TAMPERS
YELLOW (+) / BLUE (-) THHN
OR WHITE JACKET FPLR OR FPLP
2C THHN
FPLR OR FPLP
2#18 FPLR
SHIELDED
2C THHN
FPLR OR FPLP
2C THHN
FPLR OR FPLP
2#14 THWN
2#18 FPLR
SHIELDED
2#18 FPLR OR FPLP
SHIELDED
4#18 FPLR OR FPLP
SHIELDED
2C FPLR OR FPLP
SHIELDED
ORANGE (+) / BROWN (-) THHN
OR RED JACKET FPLR OR FPLP
WHITE (+) / GREY (-) THHN
OR GREY JACKET FPLR OR FPLP
RED (+) / BLACK (-) THHN
OR BLACK JACKET FPLR OR FPLP
YELLOW (+) / VIOLET (-) THHN
OR VIOLET JACKET FPLR OR FPLP
PINK (+) / BLUE (-) THWN
WHITE JACKET
RED JACKET
GREEN JACKET
BLUE JACKET
A
B
C
D
E
F
G
H
I
J
MARK DIMENSIONS
4"x4"x2-1/8"
4"x4" W/ 1-1/2" EXTENTION RING
BLANK PLATE
SINGLE GANG
4-11/16" x 4-11/16" x 2-1/8"
4-11/16" x 4-11/16" W/ 1-1/2" EXT. RING
4" OCTAGON
SINGLE GANG PLASTIC RING
DOUBLE GANG PLASTIC RING
SQUARE TO ROUND PLASTIC RING
SYMBOL
FACP
NAC
FAAP
PWR
DACT
EVAC
EBB
RMIC
FATC
XPNDR
DESCRIPTION
FIRE ALARM CONTROL PANEL
NAC POWER SUPPLY
FIRE ALARM ANNUNCIATOR PANEL
AUXILLARY POWER SUPPLY
DIGITAL ALARM COMM./TRANS.
VOICE EVACUATION PANEL
EXTERNAL BATTERY BOX
VOICE REMOTE MICROPHONE
FIRE ALARM TERMINAL CAN
FIRE ALARM TRANSPONDER
BACK BOX
PROVIDED
PROVIDED
PROVIDED
PROVIDED
PROVIDED
PROVIDED
PROVIDED
PROVIDED
BY ELECT.
PROVIDED
MOUNTING
72" TO TOP
72" TO TOP
60" TO CENTER
72" TO TOP
72" TO TOP
72" TO TOP
ADJ TO FACP
60" TO CENTER
PER DWG
72" TO TOP
SYMBOL
S
S
S
M
CR
CM
RTS
A
F
DESCRIPTION
DUCT MTD. SMOKE DET.
SMOKE DETECTOR
HEAT DETECTOR
SMOKE DET. W/ SOUNDER
MONITOR MODULE
CONTROL RELAY
CONTROL MODULE
REMOTE TEST SWITCH
ANSUL HOOD SUPP. SYS.
MANUAL PULL STATION
BACK BOX
PROVIDED
A,H
A,H
A
A
A
A
A,H
A
A,H
MOUNTED BY
MECH CONTRACTOR
CEILING
(AS REQUIRED)
WITHIN 3" OF ITEM
BEING CONTROLLED
48" AFF TO CENTER
9" DOWN FROM CEILING
TO CENTER OF BOX
ADJACENT TO EQUIP
BEING MONITORED
ADJACENT TO AIR
HANDELER UNIT
MOUNTING
ADJACENT TO EQUIP
BEING CONTROLLED
ADJACENT TO EQUIP
BEING MONITORED
CEILING
(AS REQUIRED)
SYMBOL
SS
LS
PSM
FS
TS
PS
SM
LB
DH
B
BACK BOX LEGEND
DESCRIPTION
120v. SURGE SUPPRESSION MOD.
30v. SURGE SUPPRESSION MOD.
POWER SUPERVISION MOD.
WATER FLOW SWITCH
TAMPER FLOW SWITCH
PRESSURE SWITCH
SYNCHRONIZATION MOD.
LOCK BOX
DOOR HOLDER
OUTDOOR FIRE BELL
BACK BOX
NONE
A,C
A,C
A
A
A
E
PROVIDED
A,H
BY OTHERS
MOUNTING BACK BOX
A,H
A,H
N/A
N/A
N/A
N/A
A,H
A,H
A
A
MOUNTING
PER DWG
48" AFF TO CENTER
N/A
N/A
N/A
N/A
PER DWG
PER DWG
80" AFF TO BOTTOM OF BOX
CEILING (AS REQUIRED)
ON EQUIPMENT
BEING MONITORED
AT POINT OF CONDUIT
ENTRY FROM OUTDOORS
BY OTHERS
ADJACENT TO
FLOW SWITCH
PER AHJ
ADJACENT TO
NAC PANEL
PER DWG
AT END LOCATION
OF CIRCUIT
ADJACENT TO
TAMPER SWITCH
ADJACENT TO
TAMPER SWITCH
SYMBOL
T
WP
EX
RR
VP
T
CO
R
C
DESCRIPTION
CARBON MONOXIDE DET.
FIREMANS PHONE JACK
WEATHERPROOF RATED
EXISTING DEVICE
REMOVED & RELOCATED
VANDAL PROOF COVER
BEAM DETECTOR TRANS.
BEAM DETECTOR RECIEVER
WALL MOUNT STROBE
CEILING MOUNT STROBE
F
SYMBOL
F C
S
H
M
C
C C
S
S C
S C
DESCRIPTION
WALL MOUNT HORN/STROBE
CEILING MOUNT HORN/STROBE
WALL MOUNT SPEAKER/STROBE
CEILING MOUNT SPEAKER/STROBE
WALL MOUNT HORN
WALL MOUNT MINI HORN
WALL MOUNT CHIME STROBE
CEILING MOUNT CHIME/STROBE
WALL MOUNT SPEAKER ONLY
CEILING MOUNT SPEAKER ONLY
A
A
MOUNTING
80" AFF TO BOTTOM OF BOX
CEILING (AS REQUIRED)
BACK BOX
A
A
A,H
A
A
A
A
A
CEILING (AS REQUIRED)
80" AFF TO BOTTOM OF BOX
80" AFF TO BOTTOM OF BOX
80" AFF TO BOTTOM OF BOX
80" AFF TO BOTTOM OF BOX
80" AFF TO BOTTOM OF BOX
CEILING (AS REQUIRED)
CEILING (AS REQUIRED)
FIRE & COMMUNICATIONS, INC.
SUITE # 240
TAMPA, FL 33634
(813) 653-1605
(813) 653-1710
Lic# EF20000876
TEL
FAX
4517 GEORGE ROAD
PROVIDED 72" TO TOP M DUAL MONITOR MODULE A ADJACENT TO EQUIP
BEING MONITOREDD
ABBREVIATIONS
EXPLOSION PROOFEP
1. Sequence of Alarm Operation
A. The actuation of any approved alarm initiating device shall automatically initiate the following operations where furnished as part of the system:
1. All audible alarm indicating appliances within corresponding building shall sound a fire alarm signal until the System Acknowledge key or the Signal Silence button is depressed.
2. All visible alarm indicating appliances shall flash continuously until the System Acknowledge key or the Signal Silence button is depressed.
3. The off-site central monitoring station shall be notified automatically until the System Acknowledge key or the Signal Silence key is depressed.
4. Activation of all programmed outputs assigned to the initiating device shall occur until the System Acknowledge key or the Signal Silence key is depressed.
5. Any subsequent zone alarm shall reactivate the alarm indicating appliances.
2. Sequence of Alarm Verification
A. The activation of any system smoke detector or sensor shall initiate an alarm verification operation whereby the panel will reset the activated detector and wait for a second alarm activation.
B. If, within one (1) minute after resetting, a second alarm is reported from the same or any other smoke detector, the system shall process the alarm as described previously. If no second alarm occurs within one minute the system shall resume normal operation.
C. The alarm verification shall operate only on smoke detector alarms. Other activated initiating devices shall be processed immediately.
D. The alarm verification operation shall be selectable by zone.
3. Sequence of Alarm Indication
A. A pulsing alarm tone shall occur within the local building control panel, and where applicable, the remote annunciator until the event has been acknowledged.
B. A manual evacuation (drill) switch shall be provided to operate the alarm indicating appliances without causing other control circuits to be activated. However, should a true alarm occur, all alarm functions would occur as described previously.
C. The system shall have a single key that will allow the operator to display all alarms, troubles, and supervisory service conditions including the time of each occurrence.
D. Any momentary opening of an initiating or indicating appliance circuit wiring shall cause an audible signal to sound at the Building Fire Alarm Panel, and where applicable, the remote annunciator for four seconds indicating a trouble condition.
4. Sequence of Alarm Walk Test
A. The actuation of the "enable walk test" program at the control panel shall activate the "Walk Test" mode of the system, which shall initiate the following events:
1. The off-site central monitoring station connection shall be bypassed.
2. Control relay functions shall be bypassed.
3. Walk test shall be selectable by circuit.
4. Alarms received on normal circuits shall cause the control panel to go into alarm and override the walk test mode.
5. The control panel shall show a trouble condition.
6. The alarm activation of any initiation device shall cause the audible signals to activate for two seconds.
7. The panel shall automatically reset itself after signaling is complete.
8. The control panel shall automatically return to normal condition if there is no activity on a walk test circuit for a period of 30 minutes.
SEQUENCE OF OPERATION:
COLOR CHART FOR NAC CIRCUITS
RED & BLACK
BROWN & ORANGE
PURPLE & YELLOW
BLUE & WHITE
CIRCUIT # COLORNAC PANEL #
CIRCUIT 1
CIRCUIT 2
CIRCUIT 3
CIRCUIT 4
NAC PANEL #
WIRING TYPE
16 AWG 2C / FPLR
14 GA/THHN
IDC-SLC
NAC
SIZE CIRCUIT DESCRIP.
BLDNG 1036 AREA 13,102 Sq.Ft.
SCALE: N.T.S
MAAP IO MATRIX
SCALE: NOT TO SCALE
Patrick Frailey As-Built Review
Patriot Construction Management, Inc. has reviewed these as-built drawings for general conformance with the design concept of the project and general compliance with the information given in the Contract Documents. Every effort has been made to insure that corrections or comments made by the Owner or their assignee on shop drawing or submittal reviews have been incorporated and that all changes in the work, whether by contract amendment, field order or requests for change order have been incorporated into this drawing.
By:____________________
Date:08/30/2013
WIRING LEGEND
A
B
C
D
F
P
R
S
T
U
MARK NUMBER OF WIRES
BACK BOX LEGEND
SIZE & WIRE TYPE CIRCUIT DESCRIPTION RECOMMENDED COLOR CODE
2C THHN
FPLR OR FPLP INITIATION CIRCUIT
NOTIFICATION CIRCUIT
SPEAKER CIRCUIT
DOOR HOLDER CIRCUIT
FIREMANS PHONE JACK
24v AUXILARY POWER
FAAP DATA
ADDRESSABLE DATA LOOP
NAC TRIP CIRCUIT
BACK FLOW TAMPERS
YELLOW (+) / BLUE (-) THHN
OR WHITE JACKET FPLR OR FPLP
2C THHN
FPLR OR FPLP
2#18 FPLR
SHIELDED
2C THHN
FPLR OR FPLP
2C THHN
FPLR OR FPLP
2#14 THWN
2#18 FPLR
SHIELDED
2#18 FPLR OR FPLP
SHIELDED
4#18 FPLR OR FPLP
SHIELDED
2C FPLR OR FPLP
SHIELDED
ORANGE (+) / BROWN (-) THHN
OR RED JACKET FPLR OR FPLP
WHITE (+) / GREY (-) THHN
OR GREY JACKET FPLR OR FPLP
RED (+) / BLACK (-) THHN
OR BLACK JACKET FPLR OR FPLP
YELLOW (+) / VIOLET (-) THHN
OR VIOLET JACKET FPLR OR FPLP
PINK (+) / BLUE (-) THWN
WHITE JACKET
RED JACKET
GREEN JACKET
BLUE JACKET
A
B
C
D
E
F
G
H
I
J
MARK DIMENSIONS
4"x4"x2-1/8"
4"x4" W/ 1-1/2" EXTENTION RING
BLANK PLATE
SINGLE GANG
4-11/16" x 4-11/16" x 2-1/8"
4-11/16" x 4-11/16" W/ 1-1/2" EXT. RING
4" OCTAGON
SINGLE GANG PLASTIC RING
DOUBLE GANG PLASTIC RING
SQUARE TO ROUND PLASTIC RING
SYMBOL
FACP
NAC
FAAP
PWR
DACT
EVAC
EBB
RMIC
FATC
XPNDR
DESCRIPTION
FIRE ALARM CONTROL PANEL
NAC POWER SUPPLY
FIRE ALARM ANNUNCIATOR PANEL
AUXILLARY POWER SUPPLY
DIGITAL ALARM COMM./TRANS.
VOICE EVACUATION PANEL
EXTERNAL BATTERY BOX
VOICE REMOTE MICROPHONE
FIRE ALARM TERMINAL CAN
FIRE ALARM TRANSPONDER
BACK BOX
PROVIDED
PROVIDED
PROVIDED
PROVIDED
PROVIDED
PROVIDED
PROVIDED
PROVIDED
BY ELECT.
PROVIDED
MOUNTING
72" TO TOP
72" TO TOP
60" TO CENTER
72" TO TOP
72" TO TOP
72" TO TOP
ADJ TO FACP
60" TO CENTER
PER DWG
72" TO TOP
SYMBOL
S
S
S
M
CR
CM
RTS
A
F
DESCRIPTION
DUCT MTD. SMOKE DET.
SMOKE DETECTOR
HEAT DETECTOR
SMOKE DET. W/ SOUNDER
MONITOR MODULE
CONTROL RELAY
CONTROL MODULE
REMOTE TEST SWITCH
ANSUL HOOD SUPP. SYS.
MANUAL PULL STATION
BACK BOX
PROVIDED
A,H
A,H
A
A
A
A
A,H
A
A,H
MOUNTED BY
MECH CONTRACTOR
CEILING
(AS REQUIRED)
WITHIN 3" OF ITEM
BEING CONTROLLED
48" AFF TO CENTER
9" DOWN FROM CEILING
TO CENTER OF BOX
ADJACENT TO EQUIP
BEING MONITORED
ADJACENT TO AIR
HANDELER UNIT
MOUNTING
ADJACENT TO EQUIP
BEING CONTROLLED
ADJACENT TO EQUIP
BEING MONITORED
CEILING
(AS REQUIRED)
SYMBOL
SS
LS
PSM
FS
TS
PS
SM
LB
DH
B
BACK BOX LEGEND
DESCRIPTION
120v. SURGE SUPPRESSION MOD.
30v. SURGE SUPPRESSION MOD.
POWER SUPERVISION MOD.
WATER FLOW SWITCH
TAMPER FLOW SWITCH
PRESSURE SWITCH
SYNCHRONIZATION MOD.
LOCK BOX
DOOR HOLDER
OUTDOOR FIRE BELL
BACK BOX
NONE
A,C
A,C
A
A
A
E
PROVIDED
A,H
BY OTHERS
MOUNTING BACK BOX
A,H
A,H
N/A
N/A
N/A
N/A
A,H
A,H
A
A
MOUNTING
PER DWG
48" AFF TO CENTER
N/A
N/A
N/A
N/A
PER DWG
PER DWG
80" AFF TO BOTTOM OF BOX
CEILING (AS REQUIRED)
ON EQUIPMENT
BEING MONITORED
AT POINT OF CONDUIT
ENTRY FROM OUTDOORS
BY OTHERS
ADJACENT TO
FLOW SWITCH
PER AHJ
ADJACENT TO
NAC PANEL
PER DWG
AT END LOCATION
OF CIRCUIT
ADJACENT TO
TAMPER SWITCH
ADJACENT TO
TAMPER SWITCH
SYMBOL
T
WP
EX
RR
VP
T
CO
R
C
DESCRIPTION
CARBON MONOXIDE DET.
FIREMANS PHONE JACK
WEATHERPROOF RATED
EXISTING DEVICE
REMOVED & RELOCATED
VANDAL PROOF COVER
BEAM DETECTOR TRANS.
BEAM DETECTOR RECIEVER
WALL MOUNT STROBE
CEILING MOUNT STROBE
F
SYMBOL
F C
S
H
M
C
C C
S
S C
S C
DESCRIPTION
WALL MOUNT HORN/STROBE
CEILING MOUNT HORN/STROBE
WALL MOUNT SPEAKER/STROBE
CEILING MOUNT SPEAKER/STROBE
WALL MOUNT HORN
WALL MOUNT MINI HORN
WALL MOUNT CHIME STROBE
CEILING MOUNT CHIME/STROBE
WALL MOUNT SPEAKER ONLY
CEILING MOUNT SPEAKER ONLY
A
A
MOUNTING
80" AFF TO BOTTOM OF BOX
CEILING (AS REQUIRED)
BACK BOX
A
A
A,H
A
A
A
A
A
CEILING (AS REQUIRED)
80" AFF TO BOTTOM OF BOX
80" AFF TO BOTTOM OF BOX
80" AFF TO BOTTOM OF BOX
80" AFF TO BOTTOM OF BOX
80" AFF TO BOTTOM OF BOX
CEILING (AS REQUIRED)
CEILING (AS REQUIRED)
FIRE & COMMUNICATIONS, INC.
SUITE # 240
TAMPA, FL 33634
(813) 653-1605
(813) 653-1710
Lic# EF20000876
TEL
FAX
4517 GEORGE ROAD
PROVIDED 72" TO TOP M DUAL MONITOR MODULE A ADJACENT TO EQUIP
BEING MONITOREDD
5t h
FI
G H
TE
R
W
IN
G
FL
O R
ID
A
A
IR
N A
TI
O
N A
L G
U A
R D
JA
C
K
SO
N V
IL
LE
IN
TE
R N
A
TI
O N
A L
A
IR
PO
R
T, F
L
FIRE ALARM RISER DIAGRAM
SCALE: NOT TO SCALE
NAC1 - BATT. CALCULATION
SCALE: NOT TO SCALE
BATTERY CAPACITY 60 HOURS STANDBY
AND 5 MINUTES UNDER FULL ALARM MODE.
FACP - BATTERY. CALCULATION
SCALE: NOT TO SCALE
FIRE ALARM DEVICE MOUNTING DETAIL
SCALE: NOT TO SCALE
PENETRATION DETAIL
SCALE: NOT TO SCALE
FIRE RATED WALL FIRE ALARM DEVICE CEILING
SCALE: NOT TO SCALE
MOUNTING DETAIL
SCALE: NOT TO SCALE
TYPICAL ANTENNA INST. DETAIL
SINGLE LINES REPRESENT
A CLASS-A LOOP CIRCUIT
Patrick Frailey As-Built Review
Patriot Construction Management, Inc. has reviewed these as-built drawings for general conformance with the design concept of the project and general compliance with the information given in the Contract Documents. Every effort has been made to insure that corrections or comments made by the Owner or their assignee on shop drawing or submittal reviews have been incorporated and that all changes in the work, whether by contract amendment, field order or requests for change order have been incorporated into this drawing.
By:____________________
Date:08/30/2013