JAIL 2 WEST - UPS UPGRADE
Solicitation number
B2500046
Issued by
Weld County, Colorado

About this file

The document is a set of electrical engineering drawings for the Weld County Jail UPS Replacement project located at 2110 O Street in Greeley, Colorado. The drawings, prepared by G2 Consulting Engineers, detail a comprehensive electrical system upgrade focusing on replacing the existing Uninterruptible Power Supply (UPS) system. The project encompasses electrical single-line diagrams, demolition work, panel schedules, and overall power plans for the first, second, and third levels of the facility. The drawings specify the installation of a new 40kW (40kVA) 480:208V UPS with integral bypass from Schneider Electric, including routing of new feeders, removal of existing transformers and equipment, and integration with the facility's existing electrical infrastructure.

The project involves precise electrical system modifications, including installing a new UPS transformer (SUP1E), routing new feeders to various existing branch circuit panels (EYL1A, EYL3A, EYL3B), and removing obsolete equipment. The work requires careful coordination with the facility's existing electrical systems, including emergency and standard power distribution panels. The drawings indicate multiple levels of electrical infrastructure, with specific attention to maintaining continuity of power in a critical infrastructure setting like a county jail. Work notes emphasize the need for minimal disruption, with instructions to coordinate shutdowns with the owner's representative and ensure proper installation and testing of new electrical equipment.

View the file

Other files

File Type Posted
BID SPECS - JAIL 2 WEST - UPS UPGRADE - 46.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SHEET

NUMBER SHEET TITLE

ELECTRICAL DRAWING INDEX

IS

SU

E

FO

R

PE

RM

IT

/12

/20

TOTAL: 9

E0.00 ELECTRICAL INDEX, LEGENDS, AND NOTES

ISSUED FOR REFERENCE ONLY

ISSUED FOR CONSTRUCTION

ELECTRICAL SYMBOLS LIST

(NOT ALL SYMBOLS MAY APPEAR IN THESE DRAWINGS)

RECESSED MOUNTED LINEAR

SURFACE MOUNTED LINEAR

FLANGED MOUNTED LINEAR

SUSPENDED MOUNTED LINEAR

LINEAR STRIP

WALL MOUNTED LINEAR

WALL BRACKET

OPEN DOWNLIGHT, SURFACE OR RECESSED

RECESSED ADJUSTABLE DOWNLIGHT

TRACK AND TRACK HEAD

DECORATIVE FIXTUREJ

LIGHTING CONTROL STATIONLCS

EXIT SIGN, SINGLE FACE, CHEVRONS AS

EXIT SIGN, DUAL FACE, CHEVRONS AS

SHADING INDICATES WIRING DEVICES ON

EMERGENCY POWER SOURCE

INDICATED

INDICATED

SWITCH, SINGLE POLES

a

SWITCH, THREE POLES

3a

DIMMER SWITCH, SINGLE POLED

a

DIMMER SWITCH, THREE POLES

3a

OCCUPANCY SWITCH, SINGLE POLE,O

a

DUAL-TECHNOLOGY, UON

CEILING MOUNTED OCCUPANCY SWITCH,JOC

SINGLE POLE, DUAL-TECHNOLOGY, UON

CONTROL STATION

JUNCTION BOXJJ

DUPLEX RECEPTACLE

DOUBLE DUPLEX RECEPTACLE

DUPLEX RECEPTACLE, GFCI

DUPLEX RECEPTACLE, HALF-SWITCHED

SPECIALTY RECEPTACLE (NEMA/IEC)

ILLUMINATED SIGNAGESIGN

S

COMBINATION DISCONNECT/MOTOR

STARTER, 30 AMP, SIZE '1' UON

DISCONNECT SWITCH, NON-FUSED,

HEAVY-DUTY, 30 AMP, UON

DISCONNECT SWITCH, FUSED,

HEAVY DUTY, 30 AMP, UON

N

F

LA-1,3,5

HOMERUN: (6) #12 AWG + (1) #12 AWG GRD,

CU, TO PANEL 'LA' CIRCUITS 1, 3, 5 - 3/4''C

MECHANICAL/PLUMBING EQUIPMENT

DESIGNATION

FCU

PANELBOARD, FLUSH MOUNT

PANELBOARD, SURFACE MOUNT

DISTRIBUTION TRANSFORMERT

SWITCH, MANUAL MOTOR STARTERS

M

TYPICALTYP

UNLESS OTHERWISE NOTEDUON

WEATHER-PROOFWP

EXISTING TO REMAIN(E)

RELOCATED(R)

EXISTING TO BE REMOVED(X)

HORSEPOWERHP

VARIABLE FREQUENCY DRIVEVFD

COUNTERCTR

GROUNDGRD

TWIN-HEAD EMERGENCY LIGHT

NIGHT LIGHT (UNSWITCHED)NL

FUSE PER EQUIPMENT NAMEPLATEFPEN

POLE MOUNTED LIGHT

EXISTING TO BE RELOCATED(E/R)

RECESSED CLOCK RECEPTACLE

CONTACTOR

PHOTOCELLPC

FURNISHED BY OTHERSFBO

FLUSH FLOOR DUPLEX RECEPTACLE

CIRCUITING IN WALL OR ABOVE CEILING

CIRCUITING IN FLOOR OR BELOW GRADE

OVERHEADO/H

DUPLEX RECEPTACLE - CEILING MOUNTED

CIRCUITING WITH ISOLATED GROUND

CONDUCTOR

EXIT SIGN, SINGLE FACE, CHEVRONS AS

INDICATED, INTEGRAL EMERGENCY LIGHT

DUPLEX RECEPTACLE, ISOLATED GROUND

CEILING MOUNTED DAYLIGHTJDS

SENSOR, 0-10V UON

UNDERCOUNTERU/C

# POWER/TELECOM RISER

EXIT SIGN, LOW-LEVEL

BOLLARD LIGHT FIXTURE

IN-GRADE DOWNLIGHT

FIRE-SMOKE DAMPERFSD

TELECOM SYMBOLS LIST

(NOT ALL SYMBOLS MAY APPEAR IN THESE DRAWINGS)

C

JS

V

WAP

TELECOM OUTLET: PROVIDE FLUSH MOUNT

4S JUNCTION BOX WITH 2-GANG OPENING AND

MUD-RING. ROUTE (1) 3/4" CONDUIT TO

ACCESSIBLE ABOVE CEILING SPACE COMPLETE

WITH PULLSTRING. FUTURE CABLING BY OTHERS.

CEILING MOUNT SPEAKER

WALL MOUNT SPEAKER

D2

V2

D1/V1

TELECOM OUTLET COMPLETE WITH CABLING/,

JACKS, CONVENTIONS AS FOLLOWS:

D = DATA

V = VOICE

# = QUANTITY OF CABLES/RJ45 JACKS, EACH

JS

WIRELESS ACCESS POINT

CCTV SYSTEM CAMERA

VOLUME CONTROL STATION

FLUSH FLOOR TELECOM OUTLET

TV A/V SYSTEM SCREEN OUTLET

P = POINT-OF-SALE

TELECOM RACK, 2-POST, 45U, UON

TELECOM RACK, 4-POST, 45U, UON

PLYWOOD MOUNTING BACKBOARD,

3/4" THICK, 8'-0" TALL, WIDTH AS

DRAWN, WHITE FIRE RETARDANT

PAINT FINISH, #6 CU GROUND WIRE

TELECOM CABINET, FLUSH MOUNT

TELECOM CABINET, SURFACE MOUNT EQUIPMENT ROOMER

TELECOM ROOMTR

MICROPHONE INPUT JACKM

AVI A/V SYSTEM INTERFACE TOUCHPAD,

+48'' AFF UON

CARD READER, +48" AFF UONCR

CLOCK OUTLET

JP WALL MOUNT PUBLIC ADDRESS

SYSTEM SPEAKER

INTERCOMM

WALL MOUNT BELL

IC

E0.02 ELECTRICAL SPECIFICATIONS

E0.20 DEMOLITION WORK ELECTRICAL SINGLE-LINE

E0.30 PANEL SCHEDULES

E1.00 FIRST LEVEL OVERALL POWER PLAN

E1.01 SECOND LEVEL OVERALL POWER PLAN

E1.02 THIRD LEVEL OVERALL POWER PLAN

E2.00 ENLARGED POWER PLANS

E0.21 NEW WORK ELECTRICAL SINGLE LINE

DRAWN

PROJECT #

DATE

FIRM NAME

2024067.00

11/12/2024

SCALE

AS NOTED

CHECKED

REVISION/ISSUENO. DATE

5000 GOODMAN STREET

UNIT 100

TIMNATH CO 80547

(970) 460-7400

G2CE.COM

SEAL

CONSULTANT FIRM NAME

W

EL

D

CO

UN

TY

JA

IL

UP

S

RE

PL

AC

EM

EN

T

O S

TR

EE

T

GR

EE

LE

Y, C

O

PROJECT DESCRIPTION

SHEET DESCRIPTION

SHEET NUMBER

G2 G2

E0.00

ELECTRICAL INDEX,

LEGENDS, AND

NOTES

11/12/2024

ELECTRICAL SPECIFICATIONS

PART 1 - GENERAL

A. GENERAL

1. GENERAL CONDITIONS, SPECIAL REQUIREMENTS, OR GENERAL REQUIREMENTS OF THE PROJECT SPECIFICATIONS MANUAL (WHERE PROVIDED) ARE MADE PART OF THIS SPECIFICATION AND HAVE THE SAME FORCE AND EFFECT AS IF COMPLETELY

REPRODUCED.

2. DEFINITIONS: THE WORD "WORK" SHALL MEAN LABOR AND ANY INCIDENTAL ITEMS OR SERVICES NECESSARY FOR THE PROPER INSTALLATION AND OPERATION OF THE COMPLETE SYSTEMS NOTED ON THESE DRAWINGS AND ASSOCIATED SPECIFICATIONS. THE WORD "PROVIDE" SHALL MEAN FURNISH, INSTALL, FEED, MAKE FINAL CONNECTIONS, COMMISSION AND LEAVE IN AN APPROVED

COMPLETE OPERATING CONDITION.

3. WORK SHALL BE PROVIDED IN ACCORDANCE WITH THE LATEST ADOPTED EDITIONS OF THE APPLICABLE NATIONAL ELECTRICAL CODE (NEC), INTERNATIONAL BUILDING CODE (IBC), INTERNATIONAL ENERGY CONSERVATION CODE (IECC), NFPA 110, AND ALL

OTHER APPLICABLE FEDERAL, STATE, AND LOCAL REGULATIONS INCLUDING AMENDMENTS.

4. OBTAIN AND PAY FOR ALL PERMITS, FEES AND INSPECTIONS REQUIRED FOR THIS WORK.

5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROPER FITTING OF MATERIAL INTO THE BUILDING AS INDICATED ON THE

DRAWINGS, WITHOUT INTERFERENCE WITH OTHER WORK, AND SHALL MAKE REASONABLE MODIFICATIONS IN THE LAYOUTS NEEDED TO PREVENT CONFLICT WITH OTHER TRADES, TO PROVIDE ACCESS AND FOR THE PROPER EXECUTION OF THE WORK.

6. THE WORK SHALL BE COORDINATED WITH THE WORK OF OTHER TRADES INCLUDING CONTRACT DOCUMENTS, SHOP DRAWINGS, AND EXISTING SYSTEMS (WHERE APPLICABLE).

7. DO NOT SCALE DRAWINGS AS THEY ARE DIAGRAMMATIC AND SCHEMATIC IN NATURE. CONTRACTOR SHALL PROVIDE NECESSARY ITEMS TO COMPLETE THE WORK ACCORDING TO INDUSTRY STANDARDS. IT IS THE INTENT OF THE DRAWINGS AND SPECIFICATIONS TO CALL OUT FOR FINISHED WORK, TESTED AND READY FOR OPERATION. ARRANGEMENT OF EQUIPMENT AND ROUTING OF RACEWAYS INDICATED ON DRAWINGS SHALL BE ROUTED PLUMB AND AT RIGHT ANGLES TO BUILDING STRUCTURE. INSTALLATION

OF SYSTEMS MAY REQUIRE MODIFICATION DUE TO UNFORESEEN CONDITIONS.

8. VERIFY ALL SIZES DIMENSIONS, AND CONDITIONS BEFORE STARTING ANY WORK. ANY DEVIATIONS OR ISSUES SHALL BE

TRANSMITTED TO THE ARCHITECT FOR REVIEW.

9. CONTRACTOR SHALL SUBMIT A BID BASED ON MANUFACTURER NAMES LISTED UNLESS "OR EQUAL" IS INDICATED. SUBSTITUTION REQUESTS WILL BE REVIEWED BY THE ENGINEER PROVIDED THEY ARE SUBMITTED A MINIMUM OF SEVEN (7) BUSINESS DAYS PRIOR TO THE BID DATE. CLOSING ACCEPTABILITY OF SUBSTITUTION WILL BE SOLELY DETERMINED BY THE OWNER.

10. IT IS THE INTENT OF THESE DRAWINGS AND SPECIFICATIONS TO ESTABLISH A STANDARD OF QUALITY.

11. EXAMINATION OF BIDDING DOCUMENTS:

11.1. EACH BIDDER SHALL EXAMINE THE BIDDING DOCUMENTS CAREFULLY AND, NOT LATER THAN SEVEN (7) DAYS PRIOR TO THE DATE OF RECEIPT AND SHALL MAKE WRITTEN REQUEST TO THE ARCHITECT FOR INTERPRETATION OR CORRECTION OF ANY DISCREPANCIES, AMBIGUITY, INCONSISTENCY OR ERROR THEREIN WHICH HE MAY DISCOVER. ANY INTERPRETATION OR CORRECTION WILL BE ISSUED AS AN ADDENDUM BY THE ARCHITECT. ONLY A WRITTEN INTERPRETATION OR CORRECTION BY ADDENDUM SHALL BE BINDING, NO BIDDER SHALL RELY UPON INTERPRETATIONS OR CORRECTIONS GIVEN BY ANOTHER METHOD. IF DISCREPANCIES, AMBIGUITY, INCONSISTENCY OR ERROR ARE NOT COVERED BY ADDENDUM OR WRITTEN DIRECTIVE, CONTRACTOR SHALL INCLUDE IN HIS BID, LABOR, MATERIALS AND METHODS OF CONSTRUCTION RESULTING IN HIGHER COST. AFTER AWARD OF CONTRACT, NO ALLOWANCE OR EXTRA COMPENSATION WILL BE MADE IN BEHALF OF THE CONTRACTOR DUE TO HIS FAILURE TO MAKE THE WRITTEN REQUESTS

AS DESCRIBED ABOVE.

11.2. THE COMPANY/CONTRACTOR SUBMITTING THE REQUEST WILL BE RESPONSIBLE FOR ITS PROMPT DELIVERY. FAILURE TO SO REQUEST CLARIFICATION OF ANY INADEQUACY, OMISSION, OR CONFLICT WILL NOT RELIEVE THE CONTRACTOR OF ANY RESPONSIBILITY. THE SIGNING OF THE CONTRACT WILL BE AS CONSIDERED AS IMPLICITLY DENOTING THAT THE CONTRACTOR HAS A THOROUGH COMPREHENSION OF THE FULL INTENT AND SCOPE OF THE WORKING DRAWINGS AND

SPECIFICATIONS.

12. WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER TO THE SATISFACTION OF THE ARCHITECT.

13. GUARANTEE THE INSTALLATION AGAINST DEFECTS IN MATERIALS AND WORKMANSHIP WHICH MAY OCCUR UNDER NORMAL USAGE

FOR A PERIOD OF ONE YEAR AFTER OWNERS ACCEPTANCE. DEFECTS SHALL BE PROMPTLY REMEDIED WITHOUT COST TO THE

OWNER.

14. SYSTEMS SHALL BE TESTED FOR PROPER OPERATION. IF TEST SHOW THAT WORK IS DEFECTIVE, CONTRACTOR SHALL MAKE

CORRECTIONS NECESSARY AT NO COST TO THE OWNER.

15. CONTRACTOR SHALL BE RESPONSIBLE FOR REPLACING EQUIPMENT WHICH IS DAMAGED DUE TO INCORRECT FIELD WIRING PROVIDED UNDER THIS SECTION OR FACTORY WIRING IN EQUIPMENT PROVIDED UNDER THIS SECTION.

16. SYSTEMS SHALL BE PROVIDED COMPLETE, OPERABLE AND READY FOR CONTINUOUS OPERATIONS. LIGHTS, SWITCHES, RECEPTACLES, MOTORS, ETC. SHALL BE CONNECTED AND OPERABLE.

17. ALL ELECTRICAL SYSTEMS COMPONENTS SHALL BE LISTED OR LABELED BY U.L. OR OTHER NATIONALLY RECOGNIZED TESTING

LABORATORIES (NRTL).

18. IN INSTANCES WHERE THE PROJECT DOES NOT INCLUDE AN ARCHITECT, THE ENGINEER SHALL RECEIVE ALL CORRESPONDENCE

AS DIRECTED HEREIN.

B. EXISTING CONDITIONS

1. THIS PROJECT INVOLVES CONSTRUCTION INSIDE AN EXISTING STRUCTURE. CONTRACTORS, BY SUBMITTING A BID ARE DEEMED TO BE COMPLETELY FAMILIAR WITH THE EXISTING CONDITIONS OF THE BUILDING AS IT INFLUENCES THE WORK DESCRIBED. NO CLAIMS FOR EXTRA COMPENSATION WILL BE CONSIDERED FOR EXISTING CONDITIONS VISIBLE OR REASONABLY INFERABLE FROM

A CAREFUL EXAMINATION OF THE EXISTING BUILDING CONDITIONS.

2. CONTRACTOR SHALL INSPECT THE EXISTING FIELD CONDITIONS AT THE SITE AND THE CONTRACT DOCUMENTS PRIOR TO THE START OF ANY WORK TO DETERMINE WHAT EFFECT THE EXISTING CONDITIONS WILL HAVE ON THE WORK. CONTRACTOR SHALL REPORT DISCREPANCIES TO THE ARCHITECT AND INCLUDE IN HIS BID ALL COSTS REQUIRED TO MAKE HIS WORK MEET EXISTING

CONDITIONS.

3. CONTRACTOR SHALL CONNECT THEIR WORK TO VARIOUS EXISTING ELECTRICAL SYSTEMS. THE NEW WORK SHALL BE COMPATIBLE

WITH THE EXISTING SYSTEM CONDITIONS.

4. CARE SHALL BE TAKEN DURING INSTALLATION OF THE NEW WORK, AS NOT TO DAMAGE OR INTERRUPT THE EXISTING BUILDING SYSTEMS AND SERVICES INSTALLED. DAMAGE TO EXISTING SYSTEMS AND EQUIPMENT CAUSED BY CONTRACTOR DURING THE INSTALLATION OF THEIR WORK SHALL BE REPAIRED AND/OR REPLACED AT THE CONTRACTORS EXPENSE TO THE SATISFACTION OF

THE BUILDING OWNER.

5. SHUTDOWN OF EXISTING SYSTEMS FOR CONNECTION TO EXISTING SERVICES SHALL BE COORDINATED WITH THE OWNER.

CONTRACTOR SHALL SUBMIT REQUESTS WHERE THEY AFFECT THE OPERATION OF THE BUILDING SYSTEMS AT LEAST ONE (1) WEEK IN ADVANCE OF ANY REQUIRED SHUTDOWN. THE ACTUAL SHUTDOWN PERIOD SHALL BE AS SHORT AS POSSIBLE AND AT A

TIME AGREED TO BY THE OWNER.

6. DEMOLITION SHALL BE COORDINATED WITH OWNER, ARCHITECT, AND GENERAL CONTRACTOR.

7. CONTRACTOR SHALL REPORT ANY EQUIPMENT DISCREPANCIES FOUND TO THE ARCHITECT WITHIN FIVE (5) DAYS OF DISCOVERY.

8. CONTRACTOR SHALL REPORT DISCREPANCIES TO THE ARCHITECT AND INCLUDE IN HIS BID ALL COSTS REQUIRED TO MAKE HIS

WORK MEET THE EXISTING CONDITIONS.

9. PROVIDE ELECTRICAL DEMOLITION REQUIRED. REFER TO ARCHITECTURAL DEMOLITION DRAWINGS FOR LOCATION AND EXTENT OF

DEMOLITION REQUIRED. CONTRACTOR SHALL VISIT SITE PRIOR TO BID TO DETERMINE THE EXTENT OF WORK INVOLVED. PROVIDE LABOR AND MATERIALS AS REQUIRED TO MAINTAIN AND/OR RESTORE CONTINUITY OF SERVICE TO EXISTING CIRCUITS.

10. CONTRACTOR SHALL BE RESPONSIBLE TO FIELD VERIFY EXISTING EQUIPMENT OR CIRCUITS THAT ARE REMAINING TO BE RECONNECTED TO NEW OR EXISTING SWITCHGEAR. PROVIDE SWITCHES RECEPTACLES, CONDUIT, WIRE, ETC., AS REQUIRED TO

RESTORE CONTINUITY OF CIRCUIT(S).

11. CONTRACTOR SHALL PROVIDE NECESSARY DEMOLITION TO REMOVE EXISTING UNUSED CONDUIT, WIRE, CABLE, JUNCTION BOXES, RECEPTACLES, SWITCHES, LIGHTS, FIRE ALARM DEVICES, ETC. COMPLETE WITH ASSOCIATED CIRCUIT TO SOURCE.

12. EXISTING LIGHT FIXTURES, SWITCHGEAR, ELECTRICAL EQUIPMENT, ETC. BEING REMOVED SHALL BE RETURNED TO THE OWNER, EXCEPT FOR THOSE BEING RELOCATED.

C. SUBMITTALS

1. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND TECHNICAL DATA SHEETS FOR EQUIPMENT AND MATERIALS SPECIFIED. THE ENGINEER SHALL REVIEW SHOP DRAWINGS AND TECHNICAL DATA SHEETS FOR CONFORMANCE WITH THE CONTRACT DOCUMENTS

AND ISSUE A WRITTEN ASSESSMENT TO THE OWNER PRIOR TO COMMENCEMENT OF WORK.

2. CONTRACTOR SHALL IDENTIFY ANY DEVIATIONS IN THE SHOP DRAWINGS FROM THE DESIGN DOCUMENTS.

3. SUBSTITUTIONS SHALL BE SUBMITTED TO THE ARCHITECT FOR CONSIDERATION PRIOR TO BIDDING. SUBSTITUTIONS SHALL BE

PRE-APPROVED IN WRITING. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING REQUIREMENTS ASSOCIATED WITH SUBSTITUTED EQUIPMENT OR MATERIALS WITH OTHER BUILDING TRADES. CONTRACTOR SHALL IDENTIFY AND ANNOTATE REVISED REQUIREMENTS PER BUILDING TRADE ON THE SHOP DRAWINGS. CONTRACTOR SHALL ALSO IDENTIFY COST DEBITS OR CREDITS IN

WRITING FOR THE PROPOSED CHANGES PER BUILDING TRADE.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR ENGINEERING FEES NECESSARY TO CHANGE PERMIT DOCUMENTS BASED ON

ALTERNATE SUBMITTAL PACKAGES/EQUIPMENT SUBSTITUTIONS.

5. PRESENT SHOP DRAWING SUBMITTAL DATA AT ONE TIME, IN ELECTRONIC PORTABLE DOCUMENT FORMAT (.PDF) IN A NEAT AND ORDERLY MANNER. PARTIAL SUBMITTALS WILL NOT BE ACCEPTED. SUBMITTALS SHALL INCLUDE BUT NOT BE LIMITED TO LIGHTING FIXTURES, SWITCHGEAR, PANELBOARDS, WIRING DEVICES, SAFETY SWITCHES, FUSES, MOTOR CONTROLLERS, LAMPS, CONDUIT, FITTINGS, TRANSFORMERS AND LIGHTING CONTROLS.

6. CONTRACTORS FAILURE TO ORDER OR RELEASE ORDER FOR MATERIALS AND/OR EQUIPMENT WILL NOT BE ACCEPTED AS A

REASON TO SUBSTITUTE ALTERNATE MATERIALS OR EQUIPMENT.

D. DRAWINGS

1. CONTRACTOR SHALL MAINTAIN, TWO (2) SETS OF WHITE PRINTS OF DRAWINGS PERTAINING TO THE WORK. ONE (1) SET OF PRINTS SHALL BE KEPT ON SITE AND CHANGES OR DEVIATIONS FROM THE CONTRACT DRAWINGS SHALL BE CAREFULLY NOTED AS

CHANGES OR DEVIATIONS ARE MADE.

E. OPERATING AND MAINTENANCE INSTRUCTIONS

1. CONTRACTOR SHALL PROVIDE THREE (3) COPIES OF MANUFACTURER'S OPERATING AND MAINTENANCE INSTRUCTIONS FOR EACH PIECE OF EQUIPMENT AND SYSTEM. COPIES SHALL BE COMPILED IN SETS AND PLACED IN A HARD COVER THREE RING BINDER WITH INDEX PAGE AND INDEX TABS. ALL NAME TAG INFORMATION SUCH AS THE MANUFACTURER'S, TYPE, SIZE, CAPACITY, SERIAL

NUMBER, ETC. SHALL BE INCLUDED AS PART OF THE MANUAL.

2. PROVIDE WRITTEN OPERATING INSTRUCTIONS WITH DIAGRAMS FOR ELECTRICAL EQUIPMENT.

3. OPERATING AND MAINTENANCE MANUALS SHALL BE SUBMITTED TO THE ARCHITECT FOR REVIEW.

PART 2 - PRODUCTS

A. GENERAL

1. PROVIDE EQUIPMENT AS SPECIFIED AND/OR SCHEDULED AND IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED INSTALLATION INSTRUCTIONS. EQUIPMENT SHALL OPERATE ACCORDING TO THE MANUFACTURER'S "OWNERS OPERATING AND MAINTENANCE

MANUAL" TROUBLE-FREE.

B. WIRE AND CABLE

1. WIRE SHALL BE COPPER, 75°C RATED FOR GENERAL USE. FOR HID FIXTURES AND WIRING WITHIN 3 INCHES OF FLUORESCENT BALLASTS WIRE SHALL BE COPPER MINIMUM 90°C RATED. SIZES INDICATED ARE FOR INSTALLATION IN A MAXIMUM 30°C AMBIENT.

CONDUCTOR AMPACITY SHALL DERATED FOR HIGHER AMBIENT INSTALLATIONS.

C. RACEWAYS AND FITTINGS

1. ALL WIRING SHALL BE INSTALLED IN LISTED METALLIC RACEWAYS. RACEWAYS IN SLAB-ON-GRADE OR BELOW GRADE SHALL BE SCHEDULE 40 PVC, WITH PVC WRAPPED (OR EQUIVALENT PROTECTION) RIGID STEEL ELBOWS AT BENDS AND TRANSITIONS FROM BELOW TO ABOVE GRADE. EMT FITTINGS SHALL BE STEEL. CONNECTORS SHALL BE INSULATED THROAT TYPE.

2. RGS OR IMC SHALL BE USED IN ALL AREAS SUBJECT TO WEATHER OR MECHANICAL DAMAGE.

3. ALL CIRCUITING SHALL BE CONCEALED. WHERE CONCEALMENT IS IMPRACTICAL, AND WITH THE SPECIFIC APPROVAL FROM THE

ARCHITECT, SURFACE RACEWAY AND OUTLETS MAY BE INSTALLED, FINISHED TO MATCH ADJACENT SURFACES.

4. METAL-CLAD (TYPE MC) CABLE MAY BE USED IN THE FOLLOWING LIMITED LOCATIONS:

4.1. 6'-0" MAXIMUM LIGHT FIXTURE WHIPS.

4.2. DEAD-END RUNS TO THE LAST WIRING DEVICE ON A CIRCUIT.

4.3. IN AREAS CONSIDERED "TIGHT" WITHIN MILLWORK AND CASEWORK INSTALLATIONS.

5. TYPE ENT RACEWAY IS NOT ALLOWED.

6. NON-METALLIC AND FLEXIBLE METAL CONDUITS SHALL HAVE A CODE SIZED COPPER GROUNDING CONDUCTOR. INCREASE

CONDUIT SIZE AS REQUIRED.

D. DISTRIBUTION EQUIPMENT

1. SWITCHBOARDS, DISTRIBUTION BOARDS, PANELBOARDS, DISCONNECT SWITCHES, MOTOR CONTROL CENTERS, ETC. SHALL BE FURNISHED BY SQUARE D (SCHNEIDER ELECTRIC), GENERAL ELECTRIC, EATON CUTLER HAMMER, OR SIEMENS. FLOOR MOUNTED

EQUIPMENT SHALL INSTALLED ATOP 4" HIGH CONCRETE HOUSEKEEPING PADS.

2. PROVIDE ENGRAVED NAMEPLATES MECHANICALLY FASTENED WITH A MINIMUM OF TWO (2) SCREWS ON ALL SWITCHBOARDS, PANELBOARDS DISCONNECT SWITCHES, MOTOR CONTROL CENTERS, TRANSFORMERS, ETC. INDICATING EQUIPMENT DESIGNATION (OR DESIGNATION OF EQUIPMENT SERVED), VOLTAGE, AND SOURCE. EXAMPLE: "PANEL HPA, SERVED FROM SWITCHBOARD 'MSB', 480/277V, 3PH, 4W".

3. DISCONNECT SWITCHES SHALL BE HEAVY-DUTY TYPE. FUSIBLE SWITCHES SHALL ACCEPT CLASS 'R' FUSES ONLY AND REJECT OTHERS. INSTALL DISCONNECT SWITCH ON TWO (2) 24" LONG UNITSTRUT CHANNELS DRILLED AND BOLTED TO HVAC UNIT FRAME WHERE POSSIBLE (COORDINATE LOCATION WITH HVAC MANUFACTURER TO AVOID WARRANTY INFRACTIONS). SILICONE SEAL ALL

HOLES IN UNIT.

4. CIRCUIT BREAKERS SHALL BE BOLT-ON TYPE AND FUSES SHALL BE BUSSMAN OR APPROVED EQUIVALENT. CIRCUIT BREAKERS SHALL BE FULLY RATED IN EXCESS OF AVAILABLE FAULT CURRENT LEVELS. SERIES RATING OF EQUIPMENT IS PROHIBITED.

5. WIRE TERMINATION PROVISIONS FOR PANELBOARDS, CIRCUIT BREAKERS, SAFETY SWITCHES, AND ALL OTHER ELECTRICAL

APPARATUS SHALL BE LISTED AS SUITABLE FOR 75°C.

6. ALL EQUIPMENT SUCH AS SWITCHBOARDS, DISTRIBUTION BOARDS, DISCONNECT SWITCHES, TRANSFORMERS AND PANELBOARDS SHALL BE BY THE SAME MANUFACTURER. ALL FUSES PROVIDED SHALL BE OF THE SAME MANUFACTURER.

7. PROVIDE HANDLE TIES OR MULTI-POLE CIRCUIT BREAKERS FOR SIMULTANEOUS OPERATION OF ALL MULTI-WIRE BRANCH CIRCUITS.

8. PROVIDE ARC-FLASH LABELING ON ALL DISTRIBUTION EQUIPMENT.

9. ALL DISCONNECT SWITCHES SHALL HAVE COPPER BLADES AND TERMINALS.

E. WIRING DEVICES

1. WIRING DEVICES SHALL BE SPECIFICATION GRADE AND RATED AT 20 AMPERES. THE DEVICE PLATES SHALL BE LEXAN OR NYLON UNLESS OTHERWISE NOTED. THE COLOR OF THE DEVICES AND COVERPLATES SHALL BE AS DIRECTED BY THE ARCHITECT.

2. SMOKE-DETECTORS SHALL BE SELF-CONTAINED WITH AUDIBLE ALARM, UL LISTED AND COMPLY WITH NFPA STANDARD 72.

INTERCONNECT DETECTORS WITHIN A DWELLING UNIT OR GUESTROOM TO SOUND A COMMON ALARM.

3. ALL 120 VOLT 15- AND 20-AMPERE RECEPTACLES LOCATED IN DWELLING UNITS, GUEST ROOMS AND SUITES, AND CHILD CARE

FACILITIES SHALL BE TAMPER-RESISTANT TYPE.

4. LIGHT SWITCHES IN PUBLIC AREAS SHALL BE SPECIFICATION GRADE ROCKER TYPE, UON. LIGHT SWITCHES IN BACK OF HOUSE

AREAS SHALL BE SPECIFICATION GRADE TOGGLE TYPE, UON.

F. BOXES

1. FLUSH FLOOR OUTLETS SHALL BE CAST IRON, QUANTITY OF GANGS AND CONDUIT ENTRIES AS REQUIRED. PROVIDE BRASS COVERPLATE FOR THE OUTLET TYPES INDICATED. PROVIDE CARPET OR TILE FLANGE TO MATCH FLOOR FINISH.

2. BOXES SHALL BE A MINIMUM OF 4" SQUARE WITH REQUIRED EXTENSIONS AND PLASTER OR TILE RINGS.

G. LIGHT FIXTURES

1. RECESSED FIXTURES INSTALLED INDOORS SHALL BE THERMALLY PROTECTED.

2. FIXTURES INDICATED AS BEING EMERGENCY SHALL BE PROVIDED WITH BATTERY POWERED INVERTER UNIT MOUNTED IN, OR

ADJACENT TO, FIXTURE. PROVIDE UNIT WITH FULLY AUTOMATIC TWO-RATE CHARGER, NICKEL CADMIUM BATTERY, AC "ON" PILOT LIGHT, AND TEST SWITCH. DESIGN AND WIRE UNIT TO AUTOMATICALLY TRANSFER TO BATTERY SUPPLY UPON LOSS OF NORMAL AC POWER AND TO OPERATE ONE LAMP AT 1300 LUMENS MINIMUM FOR LINEAR LAMPS, 700 LUMENS FOR COMPACT LAMPS FOR A MINIMUM OF 90-MINUTES. LED LUMEN LEVELS VARY, AND SHALL BE AS SPECIFIED. ALL EMERGENCY LIGHTING UNITS SHALL BE CONNECTED TO AN UNSWITCHED SOURCE. IN LOCATIONS ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION, EMERGENCY LIGHTING MAY BE CONNECTED TO THE EMERGENCY LEG OF A GENERATOR POWER SYSTEM IN LIEU OF BATTERY POWER.

PART 3 - EXECUTION

A. GENERAL

1. FINAL CONNECTIONS AND ROUGH-IN REQUIREMENTS TO EQUIPMENT SHALL BE PER MANUFACTURER'S APPROVED WIRING DIAGRAMS, DETAILS, AND INSTRUCTIONS. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE MATERIALS AND EQUIPMENT COMPATIBLE WITH EQUIPMENT ACTUALLY SUPPLIED INCLUDING ALL RACEWAYS, BOXES, WIRING, WIRING DEVICES, ETC.

2. CONTRACTOR SHALL PROVIDE CONTROLS, INTERLOCKS, ACCESSORIES, ETC. AS REQUIRED FOR MOTOR CONTROL. EACH STARTER SHALL CONTAIN 120V CONTROL TRANSFORMER, LED PILOT LIGHT, AND PUSHBUTTONS OR SELECTOR SWITCH AS REQUIRED, IN ADDITION TO OTHER ITEMS (AUXILIARY CONTACTS, DOOR SWITCHES, RELAYS, ETC.) REQUIRED. REFER TO CONTROL DRAWINGS AND CONTROL DIAGRAMS FOR ADDITIONAL CONDUIT, WIRE, RELAYS, TRANSFORMERS, CONNECTIONS, ETC. REQUIRED FOR A

COMPLETE AND OPERABLE SYSTEM.

3. EMPTY RACEWAY SYSTEMS SHALL HAVE A #12 PULLWIRE OR EQUAL AND SHALL BE IDENTIFIED AT JUNCTION, PULL AND TERMINATION POINTS, USING PERMANENT METALLIC TAGS. TAG SHALL INDICATE INTENDED USE OF CONDUIT, ORIGINATION AND TERMINATION POINTS OF EACH INDIVIDUAL CONDUIT. STUB CONDUIT OUT 6" INTO AN ACCESSIBLE AREA. CAP OPEN ENDS NOT

TERMINATED IN A JUNCTION BOX.

4. VERIFY EXACT LOCATION OF EQUIPMENT TO BE FURNISHED BY OTHERS PRIOR TO ROUGH-IN.

5. RECEPTACLES WHICH ARE SHOWN WALL MOUNTED ON THE ELECTRICAL DRAWINGS ON WALLS WHICH, ON THE ARCHITECTURAL

DRAWINGS AND ELEVATIONS ARE SHOWN AS GLASS OR PARTITIONS, SHALL BE FLUSH FLOOR DUPLEX RECEPTACLES MOUNTED ADJACENT TO BASE OR WALLS. COORDINATE MOUNTING HEIGHTS AND LOCATIONS OF OUTLETS AND DEVICES WITH

ARCHITECTURAL MILLWORK DRAWINGS AND INTERIOR ELEVATIONS.

6. PROVIDE SEPARATE NEUTRAL CONDUCTOR FOR EACH ARC-FAULT, GROUND FAULT, OR DIMMED CIRCUIT.

7. PROVIDE MAINTENANCE RECEPTACLE WITHIN 25'-0" OF ALL MECHANICAL, MOTORIZED, OR REFRIGERATION EQUIPMENT.

8. WHERE MECHANICAL EQUIPMENT IS INSTALLED ABOVE A GYPSUM BOARD CEILING REQUIRING ACCESS THROUGH AN ACCESS

PANEL, PROVIDE A RECEPTACLE, SWITCH, AND LIGHT IN THE CEILING SPACE AT THE ACCESS LOCATION.

9. RECESSED LIGHT FIXTURES INSTALLED IN GYPSUM BOARD OR PLASTER CEILINGS SHALL HAVE PLASTER FRAMES INSTALLED PRIOR

TO THE CEILING MATERIAL.

10. MULTI-BALLASTED OR DRIVER FLUORESCENT OR LED FIXTURES SHALL BE DUAL-SWITCHED UNLESS NOTED OTHERWISE.

11. LIGHT FIXTURES RECESSED IN T-BAR CEILING SHALL BE SUPPORTED INDEPENDENTLY OF THE CEILING SYSTEM WITH A MINIMUM OF

TWO (2) #12 HANGAR WIRES UP TO STRUCTURE. SECURE HANGAR WIRES TO CORNERS OF FIXTURE. CLIP FIXTURE TO GRID ON TWO (2) SIDES WITH FACTORY-FURNISHED CLIPS. FINAL CONNECTION TO FIXTURE SHALL BE MADE WITH A FLEXIBLE U.L.

APPROVED ASSEMBLY.

12. CONTRACTOR SHALL REFER TO FOOD SERVICE DRAWINGS FOR EXACT LOCATIONS AND ADDITIONAL ELECTRICAL REQUIREMENTS.

PROVIDE JUNCTION BOXES, RECEPTACLES, CONNECTIONS, CONDUITS (TO INCLUDE SODA AND LIQUOR DISPENSING SYSTEMS), WIRE, INTERLOCKS, CONTROLS, ETC. AS REQUIRED BY THE FOOD SERVICE EQUIPMENT SUPPLIER.

13. SEE DIVISION 23 DRAWINGS FOR LOCATION OF MECHANICAL EQUIPMENT. PROVIDE SERVICE TO AND CONNECT EQUIPMENT AS REQUIRED. PROVIDE FUSES OR HACR-TYPE CIRCUIT BREAKERS FOR AIR CONDITIONING EQUIPMENT SIZED IN ACCORDANCE WITH MANUFACTURER'S NAMEPLATE. WHERE FACTORY-PROVIDED DISCONNECT SWITCHES ARE UTILIZED, THEY SHALL BE RATED TO

EXCEED THE AVAILABLE FAULT CURRENT AT THE EQUIPMENT.

14. HVAC CONTROLS: PROVIDE LINE VOLTAGE WIRING, RACEWAYS, AND POWER CONNECTIONS AS REQUIRED TO ACCOMMODATE HVAC CONTROL SYSTEMS. COORDINATE REQUIREMENTS WITH TEMPERATURE CONTROL, MECHANICAL, PLUMBING, AND GENERAL CONTRACTORS PRIOR TO BID. NO EXTRAS WILL BE ALLOWED FOR FAILURE TO COMPLY WITH THIS REQUIREMENT. LOW VOLTAGE HVAC CONTROL RACEWAY SYSTEMS SHALL BE PER THE TEMPERATURE CONTROLS CONTRACTOR. THESE DOCUMENTS DO NOT

INDICATE ALL CONNECTION POINTS NECESSARY FOR A COMPLETE AND OPERABLE SYSTEM.

15. PANEL DIRECTORIES SHALL BE REMOVABLE. ROOM NAMES AND NUMBERS SHALL BE AS DIRECTED BY OWNER. DIRECTORIES

SHALL BE TYPED AND INSTALLED UNDER CLEAR PLASTIC COVERS.

16. PROVIDE DYMO-TAPE TAG PRINTED LABEL INSIDE COVER OF EACH FUSIBLE SWITCH, INDICATING SIZE AND TYPE OF FUSES

PROVIDED.

17. PROVIDE TWO (2) SETS OF THREE (3) SPARE FUSES FOR EACH SIZE AND TYPE PROVIDED ON THIS PROJECT. INSTALL FUSES IN A HINGED DOOR, SHEET METAL STORAGE CABINET EQUIPPED WITH CLIPS OR CUBICLES, EACH MARKED WITH THE SIZE AND TYPE OF FUSE STORED THEREIN. PROVIDE NAMEPLATE "SPARE FUSES". INSTALL IN LOCATIONS AS DIRECTED BY OWNER.

18. PROVIDE 4" HIGH CONCRETE EQUIPMENT PADS FOR FLOOR MOUNTED EQUIPMENT SUCH AS SWITCHBOARDS, MOTOR CONTROL CENTERS, TRANSFORMERS, ETC. COORDINATE WITH DISTRIBUTION EQUIPMENT TO ENSURE ALL SWITCH AND CIRCUIT BREAKER

HANDLES ARE BELOW 6'-6" TO THE HIGHEST POINT.

19. CONTRACTOR SHALL PROVIDE NEW UPDATED TYPE WRITTEN PANEL DIRECTORIES FOR EXISTING AND NEW CIRCUITS BEING

UTILIZED FOR COMPLETION OF THIS PROJECT.

20. FINAL CONNECTIONS TO MOTORS, TRANSFORMERS, AND OTHER VIBRATING AND/OR ROTATING EQUIPMENT SHALL BE MADE WITH SEAL-TITE FLEXIBLE FLEXIBLE CONDUIT WITH APPROVED FITTINGS (3''0" MAXIMUM LENGTH). DO NOT SECURE CONDUITS OR

DEVICES TO DUCTWORK OR OTHER MECHANICAL EQUIPMENT.

21. DEVICES INSTALLED IN FIRE-RATED WALLS SHALL HAVE NELSON FSP PUTTY PADS INSTALLED TO MAINTAIN FIRE INTEGRITY - ONE PAD PER HOUR OF RATING. CONDUIT PENETRATING FIRE-RATED WALLS SHALL COMPLY WITH THE REQUIREMENTS OF U.L. SYSTEM 147A FOR SINGLE CONDUITS OR U.L. SYSTEM 322 FOR MULTIPLE CONDUITS. DEVICES INSTALLED IN SOUND-RATED WALLS SHALL HAVE NELSON FSP (STC 54) SOUND RATED PUTTY PADS INSTALLED TO MAINTAIN THE SOUND INTEGRITY OF THE WALL.

22. RECEPTACLES INSTALLED OUTSIDE, ON THE BUILDING EXTERIOR OR ROOF, IN KITCHENS OR WITHIN 6'-0" MEASURED HORIZONTALLY FROM A SINK OR DRINKING FOUNTAIN UNLESS LOCATED BELOW A COUNTER OR OTHERWISE PROTECTED SHALL BE

GFCI TYPE OR PROTECTED BY A GFCI CIRCUIT BREAKER.

23. COORDINATE THE LOCATION OF LIGHTING FIXTURES WITH THE ARCHITECTURAL REFLECTED CEILING PLAN. UNLESS VERIFIED IN

WRITING THE REFLECTED CEILING PLAN LOCATIONS SHALL GOVERN.

24. COORDINATE THE LOCATION OF WALL MOUNTED EQUIPMENT WITH THE ARCHITECTURAL INTERIOR AND EXTERIOR ELEVATIONS.

UNLESS OTHERWISE VERIFIED IN WRITING THE ARCHITECTURAL DRAWINGS SHALL GOVERN.

PART 4 - DESIGN-BUILD FIRE ALARM AND DETECTION SYSTEM

PERFORMANCE CRITERIA

A. GENERAL

1. CONTRACTOR SHALL PROVIDE, INSTALL, TEST, AND COMMISSION A FULLY OPERATIONAL, APPROVED, FIRE ALARM AND DETECTION

SYSTEM.

2. FIRE ALARM AND DETECTION SYSTEM SHALL BE PROVIDED BY THIS CONTRACTOR, PERFORMED UNDER A DESIGN-BUILD DELIVERY

METHOD.

3. FIRE ALARM AND DETECTION SYSTEM SHALL BE IN FULL COMPLIANCE WITH ALL LOCAL, STATE, FEDERAL, AND ADA REQUIREMENTS.

4. CONTRACTOR SHALL PROVIDE SUBMITTALS. SUBMITTAL REQUIREMENTS:

4.1. SUBMITTALS SHALL BE APPROVED BY AUTHORITIES HAVING JURISDICTION PRIOR TO SUBMITTING THEM TO THE

ARCHITECT.

4.2. SHOP DRAWINGS SHALL BE PREPARED BY PERSONS WITH THE FOLLOWING QUALIFICATIONS:

4.2.1. TRAINED AND CERTIFIED BY MANUFACTURER IN FIRE-ALARM SYSTEM DESIGN.

4.2.2. NICET-CERTIFIED, FIRE ALARM TECHNICIAN; LEVEL III MINIMUM.

4.2.3. LICENSED OR CERTIFIED BY AUTHORITIES HAVING JURISDICTION.

4.3. DELEGATED-DESIGN: FOR NOTIFICATION APPLIANCES AND SMOKE AND HEAT DETECTORS, IN ADDITION TO THE SUBMITTALS LISTED ABOVE, INDICATE COMPLIANCE WITH PERFORMANCE REQUIREMENTS AND DESIGN CRITERIA, INCLUDING ANALYSIS DATA SIGNED AND SEALED BY THE QUALIFIED PROFESSIONAL ENGINEER RESPONSIBLE FOR THEIR

PREPARATION.

4.3.1. DRAWINGS SHOWING THE LOCATION OF EACH NOTIFICATION APPLIANCE AND SMOKE AND HEAT DETECTOR, RATINGS OF EACH, AND INSTALLATION DETAILS AS NEEDED TO COMPLY WITH LISTING CONDITIONS OF THE

DEVICE.

4.3.2. DESIGN CALCULATIONS: CALCULATE REQUIREMENTS FOR SELECTING THE SPACING AND SENSITIVITY OF DETECTION, COMPLYING WITH NFPA 72. CALCULATE SPACING AND INTENSITIES FOR STROBE SIGNALS AND

SOUND-PRESSURE LEVELS FOR AUDIBLE APPLIANCES.

4.3.3. INDICATED AUDIBLE APPLIANCES REQUIRED TO PRODUCE SQUARE WAVE SIGNAL PER NFPA 72.

5. EXISTING FIRE ALARM EQUIPMENT (WHERE APPLICABLE) SHALL BE MAINTAINED AND FULLY OPERATIONAL UNTIL NEW EQUIPMENT

PROVIDED UNDER THIS PROJECT HAS BEEN TESTED AND ACCEPTED. NEW COMPONENTS SHALL BE COMPATIBLE WITH, AND OPERATE AS AN EXTENSION OF, EXISTING SYSTEM. PROVIDE SYSTEM MANUFACTURERS CERTIFICATION THAT ALL COMPONENTS

PROVIDED HAVE BEEN TESTED AS, AND WILL OPERATE AS, A SYSTEM.

6. WARRANTY: CONTRACTOR SHALL AGREE TO REPAIR OR REPLACE FIRE ALARM SYSTEM EQUIPMENT AND COMPONENTS THAT FAIL IN MATERIALS OR WORKMANSHIP FOR A PERIOD OF NOT LESS THAN ONE YEAR FROM THE DATE OF SUBSTANTIAL COMPLETION.

7. COMPLY WITH NFPA 72, NFPA 101, AND REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION FOR INSTALLATION AND TESTING OF FIRE-ALARM EQUIPMENT. INSTALL ALL ELECTRICAL WIRING TO COMPLY WITH REQUIREMENTS IN NFPA 70 INCLUDING, BUT NOT

LIMITED TO, ARTICLE 760, "FIRE ALARM SYSTEMS."

B. SYSTEM DESCRIPTION

1. NONCODED, UL-CERTIFIED ADDRESSABLE SYSTEM, WITH MULTIPLEXED SIGNAL TRANSMISSION AND VOICE/STROBE EVACUATION

MEETING AUDIBILITY AND INTELLIGIBLE REQUIREMENTS.

2. AUTOMATIC SENSITIVITY CONTROL OF CERTAIN SMOKE DETECTORS.

3. ALL COMPONENTS PROVIDED SHALL BE LISTED FOR USE WITH THE SELECTED SYSTEM.

4. ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES SHALL BE LISTED AND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED

TESTING AGENCY, AND MARKED FOR INTENDED LOCATION AND APPLICATION.

C. OPERATIONAL DESCRIPTION

1. NOTE: THE FOLLOWING DESCRIPTIONS REPRESENT A MASTER LIST. NOT ALL DEVICES, SYSTEMS, AND FUNCTIONS LISTED HEREIN MAY BE REPRESENTED ON THIS PROJECT. APPLICABILITY SHALL BE DETERMINED BY QUALIFIED SYSTEM DESIGN PROFESSIONAL.

2. FIRE-ALARM SIGNAL INITIATION SHALL BE BY ONE OR MORE OF THE FOLLOWING DEVICES AND SYSTEMS:

2.1. MANUAL STATIONS.

2.2. HEAT DETECTORS.

2.3. FLAME DETECTORS.

2.4. SMOKE DETECTORS.

2.5. DUCT SMOKE DETECTORS.

2.6. AIR-SAMPLING SMOKE-DETECTION SYSTEM (VESDA).

2.7. CARBON MONOXIDE DETECTORS.

2.8. COMBUSTIBLE GAS DETECTORS.

2.9. AUTOMATIC SPRINKLER SYSTEM WATER FLOW.

2.10. PREACTION SYSTEM.

2.11. FIRE-EXTINGUISHING SYSTEM OPERATION.

2.12. FIRE STANDPIPE SYSTEM.

2.13. DRY SYSTEM PRESSURE FLOW SWITCH.

2.14. FIRE PUMP RUNNING.

3. FIRE-ALARM SIGNAL SHALL INITIATE THE FOLLOWING ACTIONS:

3.1. CONTINUOUSLY OPERATE ALARM NOTIFICATION APPLIANCES.

3.2. IDENTIFY ALARM AND SPECIFIC INITIATING DEVICE AT FIRE-ALARM CONTROL UNIT.

3.3. TRANSMIT AN ALARM SIGNAL TO THE REMOTE ALARM RECEIVING STATION.

3.4. UNLOCK ELECTRIC DOOR LOCKS IN DESIGNATED EGRESS PATHS.

3.5. RELEASE FIRE AND SMOKE DOORS HELD OPEN BY MAGNETIC DOOR HOLDERS.

3.6. ACTIVATE VOICE/ALARM COMMUNICATION SYSTEM.

3.7. SWITCH HEATING, VENTILATING, AND AIR-CONDITIONING EQUIPMENT CONTROLS TO FIRE-ALARM MODE.

3.8. ACTIVATE SMOKE-CONTROL SYSTEM (SMOKE MANAGEMENT) AT FIREFIGHTERS' SMOKE-CONTROL SYSTEM PANEL.

3.9. ACTIVATE STAIRWELL AND ELEVATOR-SHAFT PRESSURIZATION SYSTEMS.

3.10. CLOSE SMOKE DAMPERS IN AIR DUCTS OF DESIGNATED AIR-CONDITIONING DUCT SYSTEMS.

3.11. ACTIVATE PREACTION SYSTEM.

3.12. RECALL ELEVATORS TO PRIMARY OR ALTERNATE RECALL FLOORS.

3.13. ACTIVATE ELEVATOR POWER SHUNT TRIP.

3.14. ACTIVATE EMERGENCY LIGHTING CONTROL.

3.15. ACTIVATE EMERGENCY SHUTOFFS FOR GAS AND FUEL SUPPLIES.

3.16. RECORD EVENTS IN THE SYSTEM MEMORY.

3.17. RECORD EVENTS BY THE SYSTEM PRINTER.

3.18. INDICATE DEVICE IN ALARM ON THE GRAPHIC ANNUNCIATOR.

4. SUPERVISORY SIGNAL INITIATION SHALL BE BY ONE OR MORE OF THE FOLLOWING DEVICES AND ACTIONS:

4.1. VALVE SUPERVISORY SWITCH.

4.2. HIGH- OR LOW-AIR-PRESSURE SWITCH OF A DRY-PIPE OR PREACTION SPRINKLER SYSTEM.

4.3. ALERT AND ACTION SIGNALS OF AIR-SAMPLING DETECTOR SYSTEM.

4.4. ELEVATOR SHUNT-TRIP SUPERVISION.

4.5. FIRE PUMP RUNNING.

4.6. FIRE-PUMP LOSS OF POWER.

4.7. FIRE-PUMP POWER PHASE REVERSAL.

4.8. INDEPENDENT FIRE-DETECTION AND -SUPPRESSION SYSTEMS.

4.9. USER DISABLING OF ZONES OR INDIVIDUAL DEVICES.

4.10. LOSS OF COMMUNICATION WITH ANY PANEL ON THE NETWORK.

5. SYSTEM TROUBLE SIGNAL INITIATION SHALL BE BY ONE OR MORE OF THE FOLLOWING DEVICES AND ACTIONS:

5.1. OPEN CIRCUITS, SHORTS, AND GROUNDS IN DESIGNATED CIRCUITS.

5.2. OPENING, TAMPERING WITH, OR REMOVING ALARM-INITIATING AND SUPERVISORY SIGNAL-INITIATING DEVICES.

5.3. LOSS OF COMMUNICATION WITH ANY ADDRESSABLE SENSOR, INPUT MODULE, RELAY, CONTROL MODULE, REMOTE

ANNUNCIATOR, PRINTER INTERFACE, OR ETHERNET MODULE.

5.4. LOSS OF PRIMARY POWER AT FIRE-ALARM CONTROL UNIT.

5.5. GROUND OR A SINGLE BREAK IN INTERNAL CIRCUITS OF FIRE-ALARM CONTROL UNIT.

5.6. ABNORMAL AC VOLTAGE AT FIRE-ALARM CONTROL UNIT.

5.7. BREAK IN STANDBY BATTERY CIRCUITRY.

5.8. FAILURE OF BATTERY CHARGING.

5.9. ABNORMAL POSITION OF ANY SWITCH AT FIRE-ALARM CONTROL UNIT OR ANNUNCIATOR.

5.10. VOICE SIGNAL AMPLIFIER FAILURE.

5.11. HOSE CABINET DOOR OPEN.

6. SYSTEM SUPERVISORY SIGNAL ACTIONS:

6.1. INITIATE NOTIFICATION APPLIANCES.

6.2. IDENTIFY SPECIFIC DEVICE INITIATING THE EVENT AT FIRE-ALARM CONTROL UNIT.

6.3. RECORD THE EVENT ON SYSTEM PRINTER.

6.4. AFTER A TIME DELAY OF 200 SECONDS (OR PER AHJ REQUIREMENTS), TRANSMIT A TROUBLE OR SUPERVISORY SIGNAL

TO THE REMOTE ALARM RECEIVING STATION.

6.5. TRANSMIT SYSTEM STATUS TO BUILDING MANAGEMENT SYSTEM.

6.6. DISPLAY SYSTEM STATUS ON GRAPHIC ANNUNCIATOR.

DRAWN

PROJECT #

DATE

FIRM NAME

2024067.00

11/12/2024

SCALE

AS NOTED

CHECKED

REVISION/ISSUENO. DATE

5000 GOODMAN STREET

UNIT 100

TIMNATH CO 80547

(970) 460-7400

G2CE.COM

SEAL

CONSULTANT FIRM NAME

W

EL

D

CO

UN

TY

JA

IL

UP

S

RE

PL

AC

EM

EN

T

O S

TR

EE

T

GR

EE

LE

Y, C

O

PROJECT DESCRIPTION

SHEET DESCRIPTION

SHEET NUMBER

G2 G2

E0.02 - E0.02

1600/3

(MAIN)

(E) MAIN SERVICE SWITCHBOARD 'MSB-1'

1600A 277/480 VOLT, 3 PHASE, 4 WIRE, 65,000 AIC

NEUTRALGROUND

TVSS

100/3ST

KW

600/3

(E) EMERGENCY GENERATOR 'EG-1'

350 KW (437.5KVA), 600 AMPS

277/480 VOLT, 3 PHASE, 4 WIRE, 65,000 AIC

NEUTRALGROUND

(E) SERVICE LATERAL: (6) SETS OF - (4 - 500KCMIL ALUMINUM) 4"C

PROVIDE AND INSTALL PER XCEL ENERGY

STANDARDS AND SPECIFICATIONS.

T

(E) UTILITY SERVICE

TRANSFORMER 'T1'

(ESTIMATED 1000 KVA)

(E) PRIMARY FEEDER TO

UTILITY CO POINT OF SERVICE

(BY XCEL ENERGY) (E)

M

(E) UTILITY CO. METERING

4" CONCRETE

HOUSEKEEPING PAD

(TYPICAL)

REMOTE SHUNT-TRIP

STATION (LOCATION PER

FIRE MARSHAL)

1"C

ST

ANNUNCIATOR

ANNUNCIATOR

EMERGENCY ELEC. ROOM

MAIN LEVEL

SECOND LEVEL

THIRD LEVEL

ROOF

(E) SWITCHBOARD 'ESB'

200A - 480/277V, 3-PHASE, 4-WIRE, 65K AIC

BUS SPACE:

(2) 100/3

100/3100/3

(EMERGENCY)

(E) ATS 'ATS-E1'

(200A/4P)

'EH1A'

PANEL

200/3

(E) ATS 'ATS-Y1'

(600A/4P)

ELEV

ST

ELEV

ST

ELEV

ST

200/3 100/3

70/3

'EYL3A'

PANEL

(E) MAIN EMERGENCY SWITCHBOARD 'MESB'

600A - 480/277V, 3-PHASE, 4-WIRE, 65K AIC

BUS SPACE:

(2) 200/3

600/3200/3

200/3 600/3

BUS SPACE:

(2) 100/3

(E) SWITCHBOARD 'EYSB'

600A - 480/277V, 3-PHASE, 4-WIRE, 65K AIC

(EMERGENCY STANDBY)

225/3 225/3 225/3 225/3 400/3

T

75 KVA

(E) XFMR 'T-L1A'

(480-208/120V)

PANEL

'L1A'

SECTION 2

PANEL

'L1A'

SECTION 1

PANEL

'H1A'

T

75 KVA

(E) XFMR 'T-L1B'

(480-208/120V)

PANEL

'L1B'

SECTION 2

PANEL

'L1B'

SECTION 1

PANEL

'H1B'

T

45 KVA

(E) XFMR 'T-L2A'

(480-208/120V)

PANEL

'L2A'

SECTION 1

PANEL

'L2A'

SECTION 2

PANEL

'H2A'

T

75 KVA

PANEL

'L2B1'

PANEL

'L2B2'

PANEL

'H2B'

T

PANEL

'L3A'

SECTION 1

PANEL

'L3A'

SECTION 2

PANEL

'H3A'

T

PANEL

'L3B'

SECTION 1

PANEL

'L3B'

SECTION 2

PANEL

'H3B'

T 45 KVA

(X) XFMR 'T-EYL'

(480-208/120V)

'EYL1A'

PANEL

PANEL

'EYL2''EH2'

PANEL

'EH3A'

PANEL

C

T

(E)

(E) XFMR 'T-L2B'

(480-208/120V)

45 KVA

(E) XFMR 'T-L3A'

(480-208/120V)

75 KVA

(E) XFMR 'T-L3B'

(480-208/120V)

PANEL

'HL'

'ESHB'

PANEL

'ESHA'

PANEL

600/3

225/3

SECTION 1

SECTION 2

'ESHA'

PANEL

100/3100/3

'EH1B'

PANEL

'EYL1B'

PANEL

40 HP40 HP 20 HP

200/3 200/3 100/3

(2) BUSSED SPACE

200/3

SECTION 2

SECTION 1

'ESHB'

PANEL

ISC = 22,600AX

ISC = 21,506A

X

ISC = 9,642A X

ISC = 8,284 X

ISC = 8,284A X

ISC = 5,875A X

ISC = 19,499A X ISC = 12,138A X

ISC = 16,433A X ISC = 9,099A X

ISC = 13,206A X

ISC = 17,106A X ISC = 12,138A X

'EH2B'

PANEL

'EH3B'

PANEL

(E) CT CABINET / SPLICE

CABINET, LOCATED NEXT

TO THE UTILITY TRANSFORMER

ISC = 16,603A

X

ISC = 11,282AX

ISC = 4,465A X

ISC = 4,465A X

ISC = 4,465A X

ISC = 11,899A

X

ISC = 8,928A X

ISC = 8,928A X

'EYL3B'

PANEL

AREA OF WORK

(E)

(E) (E)

(E)

(E)

(E) (E)

(E)

(E)(E)(E)

(E) (E)

(E) (E) (E) (E) (E) (E) (E) (E) (E)

(E)(E)

(E) (E)

(E)(E)(E) (E)

(E)(E)(E)

(E) (E)

(E) (E) (E) (E)

(E)

(E) (E)

(E)(E)

(X)

(E)

(E)

(E) (E)

(E)

(E)

(E)

(E)

(E)

(E) (E)

(E)

(E) (E)

(E)(E) (E)

(E)(E)

(E)(E)

(E)

(E)(E)

(E) (E)

(E) (E)

(E)

(E) (E)

(E)(E) (E) (E)

(X)

(E)

(E)

(E

(E)

(E) (X)

(E)

(E)

(X) 9KVA 120/240V UPS-3-309

40/2

40/2

40/2

(X) EXTERNAL BYPASS UBS-1

(E) (E)(E)(E)

(E)(E)

(E) (E)

(E)(E)(E)(E)(E)(E)(E)(E)(E) (E) (E) (E) (E) (E) (E)

(E)

DRAWN

PROJECT #

DATE

FIRM NAME

2024067.00

11/12/2024

SCALE

AS NOTED

CHECKED

REVISION/ISSUENO. DATE

5000 GOODMAN STREET

UNIT 100

TIMNATH CO 80547

(970) 460-7400

G2CE.COM

SEAL

CONSULTANT FIRM NAME

W

EL

D

CO

UN

TY

JA

IL

UP

S

RE

PL

AC

EM

EN

T

O S

TR

EE

T

GR

EE

LE

Y, C

O

PROJECT DESCRIPTION

SHEET DESCRIPTION

SHEET NUMBER

G2 G2

E0.20

DEMOLITION WORK

ELECTRICAL

SINGLE-LINE

DEMOLITION NOTES:

1. EXISTING TRANSFORMER AND ASSOCIATED LINE AND LOAD SIDE CABLING SHALL BE DEMOLISHED UPON

COMPLETION OF NEW UPS INSTALLATION.

2. EXISTING UPS AND BYPASS SHALL BE DEMOLISHED UPON COMPLETION OF INSTALLATION OF NEW

SYSTEM.

3. MAKE EXISTING CIRCUIT BREAKER 'SPARE' UPON COMPLETION OF NEW WORK.

4. REMOVE FEEDER WIRING AND CONDUIT TO SOURCE.

SCALE:

E0.20

DEMOLITION WORK SINGLE LINE DIAGRAM

NTS

1600/3

(MAIN)

(E) MAIN SERVICE SWITCHBOARD 'MSB-1'

1600A 277/480 VOLT, 3 PHASE, 4 WIRE, 65,000 AIC

NEUTRALGROUND

TVSS

100/3ST

KW

600/3

(E) EMERGENCY GENERATOR 'EG-1'

350 KW (437.5KVA), 600 AMPS

277/480 VOLT, 3 PHASE, 4 WIRE, 65,000 AIC

NEUTRALGROUND

SERVICE LATERAL: (6) SETS OF - (4 - 500KCMIL ALUMINUM) 4"C

PROVIDE AND INSTALL PER XCEL ENERGY

STANDARDS AND SPECIFICATIONS.

T

(E) UTILITY SERVICE

TRANSFORMER 'T1'

(ESTIMATED 1000 KVA)

PRIMARY FEEDER TO

UTILITY CO POINT OF SERVICE

(BY XCEL ENERGY) (E)

M

(E) UTILITY CO. METERING

4" CONCRETE

HOUSEKEEPING PAD

(TYPICAL)

REMOTE SHUNT-TRIP

STATION (LOCATION PER

FIRE MARSHAL)

1"C

ST

ANNUNCIATOR

ANNUNCIATOR

EMERGENCY ELEC. ROOM

MAIN LEVEL

SECOND LEVEL

THIRD LEVEL

ROOF

(E) SWITCHBOARD 'ESB'

200A - 480/277V, 3-PHASE, 4-WIRE, 65K AIC

BUS SPACE:

(2) 100/3

100/3100/3

(EMERGENCY)

(E) ATS 'ATS-E1'

(200A/4P)

'EH1A'

PANEL

200/3

(E) ATS 'ATS-Y1'

(600A/4P)

ELEV

ST

ELEV

ST

ELEV

ST

200/3 100/3

70/3

(E) MAIN EMERGENCY SWITCHBOARD 'MESB'

600A - 480/277V, 3-PHASE, 4-WIRE, 65K AIC

BUS SPACE:

(2) 200/3

600/3200/3

200/3 600/3

BUS SPACE:

(2) 100/3

(E) SWITCHBOARD 'EYSB'

600A - 480/277V, 3-PHASE, 4-WIRE, 65K AIC

(EMERGENCY STANDBY)

225/3 225/3 225/3 225/3 400/3

T

75 KVA

(E) XFMR 'T-L1A'

(480-208/120V)

PANEL

'L1A'

SECTION 2

PANEL

'L1A'

SECTION 1

PANEL

'H1A'

T

75 KVA

(E) XFMR 'T-L1B'

(480-208/120V)

PANEL

'L1B'

SECTION 2

PANEL

'L1B'

SECTION 1

PANEL

'H1B'

T

45 KVA

(E) XFMR 'T-L2A'

(480-208/120V)

PANEL

'L2A'

SECTION 1

PANEL

'L2A'

SECTION 2

PANEL

'H2A'

T

75 KVA

PANEL

'L2B1'

PANEL

'L2B2'

PANEL

'H2B'

T

PANEL

'L3A'

SECTION 1

PANEL

'L3A'

SECTION 2

PANEL

'H3A'

T

PANEL

'L3B'

SECTION 1

PANEL

'L3B'

SECTION 2

PANEL

'H3B'

'EH2'

PANEL

'EH3A'

PANEL

C

T

(E)

(E) XFMR 'T-L2B'

(480-208/120V)

45 KVA

(E) XFMR 'T-L3A'

(480-208/120V)

75 KVA

(E) XFMR 'T-L3B'

(480-208/120V)

PANEL

'HL'

'ESHB'

PANEL

'ESHA'

PANEL

600/3

225/3

SECTION 1

SECTION 2

'ESHA'

PANEL

100/3100/3

'EH1B'

PANEL

40 HP40 HP 20 HP

200/3 200/3 100/3

(2) BUSSED SPACE

200/3

SECTION 2

SECTION 1

'ESHB'

PANEL

ISC = 22,600AX

ISC = 21,506A

X

ISC = 9,642A X

ISC = 8,284 X

ISC = 8,284A X

ISC = 5,875A X

ISC = 19,499A X ISC = 12,138A X

ISC = 16,433A X ISC = 9,099A X

ISC = 13,206A X

ISC = 17,106A X ISC = 12,138A X

'EH2B'

PANEL

'EH3B'

PANEL

(E) CT CABINET / SPLICE

CABINET, LOCATED NEXT

TO THE UTILITY TRANSFORMER

ISC = 16,603A

X

ISC = 11,282AX

ISC = 4,465A X

ISC = 4,465A X

ISC = 11,899A

X

ISC = 8,928A X

ISC = 8,928A X

AREA OF WORK

(E)

(E) (E)

(E)

(E)

(E) (E)

(E)

(E)(E)(E)

(E) (E)

(E) (E) (E) (E) (E) (E) (E) (E) (E)

(E)(E)

(E) (E)

(E)(E)(E) (E)

(E)(E)(E)

(E) (E)

(E) (E) (E) (E)

(E)

(E) (E)

(E)(E)

(E)

(E) (E)

(E)

(E)

(E)

(E)

(E)

(E) (E)

(E)

(E) (E)

(E)(E) (E)

(E)(E)

(E) (E)

(E) (E)

(E)

(E) (E)

(E)(E) (E) (E)

(E)(E)

(E)

'EYL1A'

PANEL

(E)

'EYL1B'

PANEL

(E)

PANEL

'EYL2'

(E)

'EYL3B'

PANEL

(E)

'EYL3A'

PANEL

(E)

(E)

(E)

(E)

(3) #1THWN CU, (1) #8 GRD CU, 1-1/2"C.

UPS TRANSFROMER 'SUP1E'

40 KW 480-208/120V 3 PH

EXTERNAL BYPASS CABINET

(MAKE-BEFORE-BREAK)

80/3

NEW

(E) (E)

#2 CU

(3) #3 THWN CU, & (1) #8 THWN CU GRD, 1.5"C

200/3

150/3

150/3

60KVA

(E)

(4) #1/0 THWN CU, (1) #6 THWN CU GRD, 1.5"C

(E) (E)(E)(E)

(E)(E)

(E)(E)(E)(E)(E)(E)(E)(E)(E) (E) (E) (E) (E) (E) (E)

WORK NOTES:

1. INSTALL NEW UPS SYSTEM. REFER TO POWER PLAN FOR

SPECIFICATIONS.

2. PROVIDE NEW CIRCUIT BREAKER AT EXISTING

DISTRIBUTION PANEL. VERIFY MANUFACTURER

INFORMATION AND BREAKER TYPE PRIOR TO ANY

PURCHASE. COORDINATE ANY SHUT DOWN WITH

OWNER'S REPRESENTATIVE.

3. PROVIDE NEW CIRCUIT BREAKER IN EXISTING PANEL.

REFER TO PANEL SCHEDULE. VERIFY MANUFACTURER

INFORMATION PRIOR TO ANY PURCHASE.

4. ROUTE NEW FEEDER TO BACKFEED EXISTING PANE EYL3B.

5. PROVIDE 3/4" RACEWAY TO ACCESSIBLE LOCATION FOR

DATA ACCESS TO NEAREST IT ROOM. REFER TO OVERALL

PLAN.

SCALE:

E0.21

NEW WORK SINGLE LINE DIAGRAM

NTS

DRAWN

PROJECT #

DATE

FIRM NAME

2024067.00

11/12/2024

SCALE

AS NOTED

CHECKED

REVISION/ISSUENO. DATE

5000 GOODMAN STREET

UNIT 100

TIMNATH CO 80547

(970) 460-7400

G2CE.COM

SEAL

CONSULTANT FIRM NAME

W

EL

D

CO

UN

TY

JA

IL

UP

S

RE

PL

AC

EM

EN

T

O S

TR

EE

T

GR

EE

LE

Y, C

O

PROJECT DESCRIPTION

SHEET DESCRIPTION

SHEET NUMBER

G2 G2

E0.21

NEW WORK

ELECTRICAL SINGLE

LINE

DRAWN

PROJECT #

DATE

FIRM NAME

2024067.00

11/12/2024

SCALE

AS NOTED

CHECKED

REVISION/ISSUENO. DATE

5000 GOODMAN STREET

UNIT 100

TIMNATH CO 80547

(970) 460-7400

G2CE.COM

SEAL

CONSULTANT FIRM NAME

W

EL

D

CO

UN

TY

JA

IL

UP

S

RE

PL

AC

EM

EN

T

O S

TR

EE

T

GR

EE

LE

Y, C

O

PROJECT DESCRIPTION

SHEET DESCRIPTION

SHEET NUMBER

G2 G2

E0.30

PANEL SCHEDULES

EYL3A

EYL2EYL1B

EYL1A

WORK NOTES:

1. PROVIDE NEW CIRCUIT BREAKER AT EXISTING BRANCH CIRCUIT PANEL. VERIFY MANUFACTURER

INFORMATION AND BREAKER TYPE PRIOR TO ANY PURCHASE. COORDINATE ANY SHUT DOWN WITH

OWNER'S REPRESENTATIVE.

2 MAKE EXISTING BREAKER SPARE UPON REMOVAL OF EXISTING UPS.

EYL3B

L3A

UP

W

V.5

V

U

T.5

T

S.5

S

R.5

R

Q

P.5

P

N

M.5

M

14.7

14.7

14.3

14.3

A.3

B

C.5

F

H

H.2

K

X

STAIR 2

1-S2

ELEV. 2

1-E2

STAIR 4

1-S4

CLASSROOM

1-198

AIR POD

1-197

AIR POD

1-176

CLASSROOM

1-175

CLASSROOM

1-156

AIR POD

1-155

AIR POD

1-134

CLASSROOM

1-133

CLASSROOM

1-114

AIR POD

1-113

POD 12

(DAYROOM)

1-185

POD 14

(DAYROOM)

1-143

POD 16

(DAYROOM)

1-101

LAUNDRY

1-102

JAN.

1-103

PROF. VISIT

1-104

PROF. VISIT

1-105

CELL

1-108

SHOWER

1-106

MECH.

CHASE

MC1

MECH.

CHASE

MC2

JAN.

1-304

CLASSIFICATION

SCREENING

1-305

POD 17

(DAYROOM)

1-301

PROF. VISIT

1-302

MEDICAL

SCREENING

1-303

ELEV. 1

1-E1

STAIR 1

1-S1

ELEV.

EQUIPMENT

RM

1-E1A

POD 18

(DAYROOM)

1-337

LAUNDRY

1-404

CLASSIFICATION

SCREENING

1-323

JAN

1-322MEDICAL

SCREENING

1-321

PROF. VISIT

1-319

BOILER

ROOM

1-300

VIDEO CONF.

1-312

VIDEO CONF.

1-402

ELEC. RM

1-406

SPRINKLER

RM

1-405

MENS RR

1-504

WOMENS RR

1-503

ELEV. LOBBY

1-L2

ELEV.

EQUIPMENT

RM

1-E2A

VEST.

1-C04

CORRIDOR

1-518

ELECTRICAL

1-329

STAIR 3

1-S3

IDF

1-501

WORK

1-519

OFFICE

1-521

OFFICE

1-522

CONF.

1-523

OFFICE

1-524

PHARM.

STORAGE

1-517

R.R.

1-516

EXAM

1-515

ELEV. EQPT.

RM.

1-E3A

OFFICE

1-509

EXAM

(DENTAL)

1-513

EXAM

1-512

INMATE

SUPPLY

STORAGE

1-403

OFFICE

1-508

NURSE

STATION

1-506

WAITING

1-505

ELEV. 3

1-E3

STOR.

1-511

OFFICE

1-507

POD 15

(DAYROOM)

1-122

LAUNDRY

1-126

JAN.

1-125

PROF. VISIT

1-124

PROF. VISIT

1-123

CELL

1-138 SHOWER

1-141

LAUNDRY

1-144

JAN.

1-145

PROF. VISIT

1-146

PROF. VISIT

1-147

CELL

1-151

SHOWER

1-148

POD 13

(DAYROOM)

1-164

LAUNDRY

1-168 JAN.

1-167

PROF. VISIT

1-166

PROF. VISIT

1-165CELL

1-181

SHOWER

1-183

LAUNDRY

1-186

JAN.

1-187

PROF. VISIT

1-188

PROF. VISIT

1-189

CELL

1-193

SHOWER

1-191

CELL

1-109

CELL

1-107

CELL

1-111

CELL

1-112

CELL

1-118

CELL

1-117

CELL

1-116

CELL

1-115 CELL (AC.)

1-119

CELL

1-152

CELL

1-149

CELL

1-153

CELL

1-154

CELL

1-161

CELL

1-159

CELL

1-158

CELL

1-157

CELL (AC.)

1-162

CELL

1-194

CELL

1-192

CELL

1-195

CELL

1-196

CELL

1-203

CELL

1-202

CELL

1-201

CELL

1-199

CELL (AC.)

1-204

MECH.

CHASE

MC3

MECH.

CHASE

MC4

MECH.

CHASE

MC5

MECH.

CHASE

MC6

CORRIDOR

1-C07

MECH.

ACCESS

MC9

MECH.

ACCESS

MC7

MECH.

ACCESS

MC8

PROF. VISIT

1-408

SALLY PORT

1-100

BLDG

BREEZEWAY

1-C08

N.5 N.5

Q.5

L

A

EXTERIOR

CORRIDOR

1-C02

EXTERIOR

CORRIDOR

1-C01

EXTERIOR

CORRIDOR

1-C03

CORRIDOR

1-C05

CORRIDOR

1-C06

OFFICE

1-401

CORRIDOR

1-C09

JAN.

1-502

HALLWAY

1-514

STOR.

1-500

CORRIDOR

1-C10

CLASSROOM

1-409

LINT

COLLECT

1-407

CELL (AC.)

1-127

CELL

1-128

CELL

1-129

CELL

1-131

CELL

1-132

CELL

1-135

CELL

1-136

CELL

1-137

CELL

1-139

CELL

1-174

CELL

1-173

CELL

1-172

CELL

1-171

CELL (AC.)

1-169

CELL

1-177

CELL

1-178

CELL

1-179

CELL

1-182

CELL

1-335

CELL

1-334

CELL

1-333

CELL

1-332

CELL

1-331

CELL

1-328

CELL

1-327

CELL

1-326

CELL

1-325

CELL (AC.)

1-324

SHOWER

1-336

SHOWER

1-318

CELL

1-317

CELL

1-316

CELL

1-315

CELL

1-314

CELL

1-313

CELL

1-311

CELL

1-309

CELL

1-308

CELL

1-307

CELL (AC.)

1-306

ACCESS CONTROL PANEL

E2.00

E2.00

(E) PANEL EYL1B

(E)PANEL EYL1A

DRAWN

PROJECT #

DATE

FIRM NAME

2024067.00

11/12/2024

SCALE

AS NOTED

CHECKED

REVISION/ISSUENO. DATE

5000 GOODMAN STREET

UNIT 100

TIMNATH CO 80547

(970) 460-7400

G2CE.COM

SEAL

CONSULTANT FIRM NAME

W

EL

D

CO

UN

TY

JA

IL

UP

S

RE

PL

AC

EM

EN

T

O S

TR

EE

T

GR

EE

LE

Y, C

O

PROJECT DESCRIPTION

SHEET DESCRIPTION

SHEET NUMBER

G2 G2

E1.00

FIRST LEVEL

OVERALL POWER

PLAN

SCALE: N

E1.00

FIRST LEVEL OVERALL POWER PLAN

1/16" = 1'-0"

DN

20 19 18 16

W

V.5

V

U

T.5

T

S.5

S

R.5

R

Q

P.5

P

N

M.5

M

14.7 14.3

A.3

A.3

B

C.5

F

H

H

H.2

H.2

K

X

ELEV. 2

2-E2

STAIR 2

2-S2

STAIR 4

2-S4

STAIR 1

2-S1

ELEV. 1

2-E1

VIDEO CONF.

2-302

MEDICAL

WARD POD 24

(DAYROOM)

2-305

CLASSROOM

2-313

AIR POD

2-314

STAIR 3

2-S3

WOMENS RR

2-403

MENS RR

2-404

WOMENS

BATH

2-406

ELEV. LOBBY

2-L2

PROF. VISIT

2-303

STORAGE

2-408

MENS BATH

2-405

TRAINING

ROOM

2-409

IDF

2-401

LAUNDRY

2-309

JAN.

2-311

SIMULATION

RM.

2-507

CORRIDOR

2-C02

ELEV. 3

2-E3

POD 23

(DAYROOM)

2-101

POD 22

(DAYROOM)

2-122

POD 21

(DAYROOM)

2-143

POD 20

(DAYROOM)

2-164

POD 19

(DAYROOM)

2-185

SHOWER

2-106

LAUNDRY

2-102

PROF. VISIT

2-104

JAN.

2-103

CELL

2-199

CELL

2-201

CELL

2-202

CELL

2-203

CELL (AC.)

2-204

CELL

2-115

CELL

2-112

CELL

2-111

CELL

2-109

CELL

2-108

CELL

2-107

CELL

2-116

CELL

2-117

CELL

2-118

CELL

2-132

CELL

2-131

CELL

2-129

CELL

2-128

CELL

2-135

CELL

2-136

CELL

2-137

CELL

2-138

CELL

2-139

CELL

2-149

CELL

2-151

CELL

2-152

CELL

2-153

CELL

2-154

CELL

2-157

CELL

2-158

CELL

2-159

CELL

2-161

CELL

2-174

CELL

2-173

CELL

2-172

CELL

2-171

CELL

2-177

CELL

2-178

CELL

2-179

CELL

2-181

CELL

2-182

CELL

2-192

CELL

2-193

CELL

2-194

CELL

2-195

CELL

2-196

SHOWER

2-141

SHOWER

2-148

SHOWER

2-183

SHOWER

2-191

CELL (AC.)

2-119

CELL (AC.)

2-127

CELL (AC.)

2-162

CELL (AC.)

2-169

LAUNDRY

2-126

JAN.

2-125

PROF. VISIT

2-124

PROF. VISIT

2-123

LAUNDRY

2-144

JAN.

2-145

PROF. VISIT

2-146

PROF. VISIT

2-147

LAUNDRY

2-168

JAN.

2-167

PROF. VISIT

2-166

PROF. VISIT

2-165

LAUNDRY

2-186

JAN.

2-187

PROF. VISIT

2-188

PROF. VISIT

2-189

PROF. VISIT

2-105

MECH.

ACCESS

MC11

MECH.

ACCESS

MC10

CLASSROOM

2-114

CLASSROOM

2-133

AIR POD

2-113

AIR POD

2-134

AIR POD

2-155

CLASSROOM

2-156

CLASSROOM

2-175

AIR POD

2-176

AIR POD

2-197

CLASSROOM

2-198

CUSTODIAL

STORAGE

2-508

ELEV. LOBBY

2-L1

CORRIDOR

2-C08

JAN.

2-402 CONFERENCE

2-501

CORRIDOR

2-C06

TRAINING

2-506

M. RR

2-504

F. RR

2-505

PART.

CLOSET

2-512

COFFEE BAR

2-502

CONFERENCE

2-509

CLASSROOM

2-320

CLOSET

2-513

CLOSET

2-511

STOR.

2-503

L

A

A

VEST.

2-C01

OFFICE

2-301

CORRIDOR

2-C04

CORRIDOR

2-C05

RR VEST.

2-407

CORRIDOR

2-C07

CORRIDOR

2-C09

EXTERIOR

CORRIROR

2-C11

ELEV. LOBBY

2-L3

VEST.

2-C10

STORAGE

2-310

CELL

2-306

CELL

2-307

MEDICAL

OFFICE

2-304

CELL

2-308

CELL

2-319

CELL

2-318

CELL

2-317

CELL

2-316

CELL (AC.)

2-315

SHOWER

2-312

STORAGE

2-510

E2.00

(E) PANEL EYL2

DRAWN

PROJECT #

DATE

FIRM NAME

2024067.00

11/12/2024

SCALE

AS NOTED

CHECKED

REVISION/ISSUENO. DATE

5000 GOODMAN STREET

UNIT 100

TIMNATH CO 80547

(970) 460-7400

G2CE.COM

SEAL

CONSULTANT FIRM NAME

W

EL

D

CO

UN

TY

JA

IL

UP

S

RE

PL

AC

EM

EN

T

O S

TR

EE

T

GR

EE

LE

Y, C

O

PROJECT DESCRIPTION

SHEET DESCRIPTION

SHEET NUMBER

G2 G2

E1.01

SECOND LEVEL

OVERALL POWER

PLAN

SCALE: N

E1.01

SECOND LEVEL OVERALL POWER PLAN

W

V.5

V

U

T.5

T

S.5

S

R.5

R

Q

P.5

P

N

M.5

M

14.7

14.7

14.3

14.3

A.3

B

B

C.5

C.5

F

F

H

H

H.2

H.2

K

K

X

STAIR 4

3-S4

STAIR 1

3-S1

ELEV 1

3-E1

STAIR 2

3-S2

ELEV. 2

3-E2

STAFF (M)

LOCKERS

3-405

CORRIDOR

3-C02

STAIR 3

3-S3

WOMENS RR

3-303

MENS RR

3-304

ELEV. LOBBY

3-L2

22 BED

22 BED

IDF

3-301

22 BED

CONF.

3-417

STAFF

LOUNGE

3-416

OPEN

OFFICES

3-421

OFFICE

3-414

OFFICE

3-412

OFFICE

3-415

OFFICE

3-413

CORRIDOR

3-C05

STAFF (F)

LOCKERS

3-409

ELEV. 3

3-E3

SOG CONF.

3-403

SOG

EQUIPMENT

3-401

SOG

STORAGE

3-402

CELL

3-157

CELL

3-156

CELL

3-155

CELL

3-154

CELL

3-153

CELL

3-158

CELL

3-163

CELL

3-162

CELL

3-161

CELL

3-159

CELL

3-164 SHOWER

3-165

CELL

3-174

CELL

3-173

CELL

3-172

CELL

3-171

CELL

3-175

SHOWER

3-169

CELL

3-181

CELL

3-179

CELL

3-178

CELL

3-177

CELL

3-176

CELL

3-182

CELL

3-147

CELL

3-146

CELL

3-145

CELL

3-144

CELL

3-143

CELL

3-148

CELL

3-141

CELL

3-139

CELL

3-138

CELL

3-137

CELL

3-142

SHOWER

3-136

CELL

3-129

CELL

3-128

CELL

3-127

CELL

3-126

CELL

3-131

SHOWER

3-132

CELL

3-124

CELL

3-123

CELL

3-122

CELL

3-121

CELL

3-119

CELL

3-125

CELL

3-114

CELL

3-113

CELL

3-112

CELL

3-111

CELL

3-109

CELL

3-115

CELL

3-108

CELL

3-107

CELL

3-106

CELL

3-105

CELL

3-104

SHOWER

3-103

22 BED

22 BED

CUSTODIAL

STORAGE

3-424

ELEV. LOBBY

3-L1

POD 19

(DAYROOM)

3-167

POD 20

(DAYROOM)

3-151

POD 21

(DAYROOM)

3-134

POD 22

(DAYROOM)

3-117

POD 23

(DAYROOM)

3-101

MASTER

CONTROL

3-307

MASTER

CONTROL

R.R.

3-306

CORRIDOR

3-C04

MASTER

CONTROL

EQPT.

3-309

STORAGE

3-308

VIDEO

VIEWING

3-305

COFFEE

WORK AREA

FACP

OFFICE

3-418

CELL

3-216

CELL

3-217

CELL

3-218

CELL

3-215

CELL (AC.)

3-214

CELL

3-224

CELL

3-219

CELL

3-221

CELL

3-222

CELL

3-223

CELL

3-203

CELL

3-205

CELL

3-206

CELL

3-207

CELL

3-204

SHOWER

3-211

SHOWER

3-225

CELL

MAINTENANCE

ACCESS

3-208

HALLWAY

3-202

CELL

MAINTENANCE

ACCESS

3-220

ELEV. LOBBY

3-L3

CELL

MAINTENANCE

ACCESS

3-212

STORAGE

3-201

N.5

L

A

OFFICE

3-419SHOWER

3-406

RR

3-407

OFFICE

3-404

SHOWER

3-411

JAN.

3-302

RR

3-408

CORRIDOR

3-C03

CORRIDOR

3-C06

POD 25

CLOSE

WATCH

3-209

LACTATION

3-420

SHAFT

M. LOCKER

VEST.

3-405A

F. LOCKER

VEST.

3-409A

SHAFT

CELL

MAINTENANCE

ACCESS

3-208

LAUNDRY

3-166

LAUNDRY

3-168

JAN.

3-183

JAN.

3-152

JAN.

3-149

LAUNDRY

3-135

LAUNDRY

3-133

JAN.

3-118

JAN.

3-116

LAUNDRY

3-102

SH

AF

T

SHAFT

SHAFT

NOTE: CLOSE WATCH CELLS ARE

ASSEMBLED ON-SITE

(FLOOR WILL BE POURED IN PLACE

CONCRETE OVER METAL DECK)

SHIPS LADDER

TO ROOF

STAIR ACCESS

OFFICE

3-404A

CLOSE

3-213

WATCH

POD 26

SHAFT

E2.00

E2.00

(E) PANEL EYL3A

(E) PANEL EYL3B

(E) PANEL EYL3A

(E) PANEL L3A

DRAWN

PROJECT #

DATE

FIRM NAME

2024067.00

11/12/2024

SCALE

AS NOTED

CHECKED

REVISION/ISSUENO. DATE

5000 GOODMAN STREET

UNIT 100

TIMNATH CO 80547

(970) 460-7400

G2CE.COM

SEAL

CONSULTANT FIRM NAME

W

EL

D

CO

UN

TY

JA

IL

UP

S

RE

PL

AC

EM

EN

T

O S

TR

EE

T

GR

EE

LE

Y, C

O

PROJECT DESCRIPTION

SHEET DESCRIPTION

SHEET NUMBER

G2 G2

E1.02

THIRD LEVEL

OVERALL POWER

PLAN

SCALE: N

E1.02

THIRD LEVEL OVERALL POWER PLAN

PROF. VISIT

1-319

WOMENS RR

1-503

IDF

1-501

PROF. VISIT

JAN.

1-502

(E) FIRE ALARM PANEL

(E) FIRE ALARM PANEL

(E) PANEL EYL1B

(E) DAS

(E) SPLIT

(E) AC

(E ) U

PS

(E)8

(E)

(E)

(E)

(E)

WOMENS RR

2-403

IDF

2-401

PROF. VISIT

JAN.

2-402

CORRIDOR

2-C05(E) FIRE ALARM PANEL

(E) FIRE ALARM PANEL

(E) PANEL EYL2

(E) SPLIT

(E) AC

(E ) U

PS

(E)8 (E)

(E)

(E) (E)

(E)

WOMENS RR

3-303

IDF

3-301

JAN.

3-302

SHAFT

(E) FIRE ALARM PANEL

(E) FIRE ALARM PANEL

(E) PANEL EYL3A(E) DAS

(E) SPLIT

(E ) U

PS

(E) AC

(E)8

(E)

(E)

(E) (E)

14.7 14.3

3 2

ELEV. LOBBY

3-L2

MASTER

CONTROL

EQPT.

3-309

JAN.

3-183

F

T

(E) PANEL 'H3B'

(E) XFMR 'T-L3B'

(E) PANEL 'L3B (SECT. 2)'

(E) PANEL 'L3B (SECT. 1)'

(E) PANEL 'ESHB'

(E) PANEL 'EH3B'

(E) LCP3B (E) BAS

CONTROL

PANEL

(E) (3) 4 POST RACKS

SERVER

(E) CRAC UNIT

(E) ELECTRICAL GUTTER (X) UPS-1 (E) PANEL 'EYL3B'

UPS

ATS

(E) CRAC

(E) MARSHALLING CABINETS

(X)

(X)

ELECTRICAL

1-329

BLDG

BREEZEWAY

CORRIDOR

1-C09

CELL

1-331 T

FACP

Y-1

(E) A

TS

E1

(E)PANEL EYL1A

(E) PANEL ESB

(E) DISTRIBUTION PANEL EYSB

UPS / B

ATTERY CABINET(S)

T

(X) EXISTING

TRANSFORMER 'X-EYL'

(E) A

TS

(E) AC

(E) SPLIT

(N) UPS XFMR 'SUP1E'

(E) CONDUIT RACK

(E) DISTRIBUTION

PANEL MESB

(X)

(X)

AC

S

2 POLE

10 11

3'-0 " M

IN.

CU

101 F

L3A-(26,28) REFER TO 3RD LEVEL OVERALL PLAN

(2 #10 THWN CU, (1) #10 CU GRD, 1"C

EXTEND CIRCUIT TO INTERIOR UNIT

30/2 NEMA 3R

36", WP

14.7 14.3

3 2

DRAWN

PROJECT #

DATE

FIRM NAME

2024067.00

11/12/2024

SCALE

AS NOTED

CHECKED

REVISION/ISSUENO. DATE

5000 GOODMAN STREET

UNIT 100

TIMNATH CO 80547

(970) 460-7400

G2CE.COM

SEAL

CONSULTANT FIRM NAME

W

EL

D

CO

UN

TY

JA

IL

UP

S

RE

PL

AC

EM

EN

T

O S

TR

EE

T

GR

EE

LE

Y, C

O

PROJECT DESCRIPTION

SHEET DESCRIPTION

SHEET NUMBER

G2 G2

E2.00

ENLARGED POWER

PLANS

WORK NOTES:

1. ROUTE NEW FEEDER FROM EXISTING DISTRIBUTION PANEL EYSB TO NEW UPS TRANSFORMER. REFER

TO SINGLE LINE FOR FEEDER INFORMATION.

2. PROVIDE AND INSTALL 40KW (40KVA) 480:208V, INTEGRAL BYPASS UPS, “SCHNEIDER ELECTRIC”

#SYMMETRA PX40 N+1, 2 HOUR RUN TIME.

3. REMOVE EXISTING TRANSFORMER, CONCRETE PAD AND LINE AND LOAD SIDE FEEDERS AT COMPLETION

OF WORK. REFER TO SINGLE LINE FOR DEMOLITION…