B2501Plans.pdf

PDF 5 MB Posted

Attached to
T-HANGAR ELECTRICAL SERVICE UPGRADE State and local contract opportunity
Solicitation number
B-25-01
Issued by
Volusia County, Florida

About this file

These bid documents are for the T-Hangar Electrical Upgrades project at the DeLand Municipal Airport in DeLand, Florida, prepared by AVCON, Inc., an engineering and planning firm. The project involves electrical service upgrades for three T-hangars, including demolition of existing electrical systems and installation of new electrical panels, circuits, lighting, and associated infrastructure. The project is scheduled for June 2024, with bid documents prepared in March 2024, and is supported by a Florida Department of Transportation (FDOT) funding number and a FAA Airport Improvement Program (AIP) number.

The electrical upgrade scope includes replacing electrical services, installing new panels (A1 and A2) with 70A main breakers, providing new branch circuits for unit receptacles and lighting, and implementing exterior lighting upgrades. The electrical design includes specific requirements for wire sizes, conduit, grounding, and compliance with the 2020 National Electrical Code. The project involves surface-mounted panels with NEMA 3R enclosures, surge protection devices, and detailed specifications for conductor types, mounting heights, and electrical system configurations. The total demand load is estimated at 12.55 KVA with a total demand of 52.27 amps per panel, with provisions for future expansion and spare circuits.

View the file

Other files for this state and local contract opportunity

Other files attached to T-HANGAR ELECTRICAL SERVICE UPGRADE, newest first.
File Type Posted
RCA.pdf PDF
B2501Tabulation.pdf PDF
B2501ADD3.pdf PDF
B2501ADD2.pdf PDF
B2501ADD1.pdf PDF
B2501ADD1Attachment.xlsx XLSX spreadsheet
Bid_Bond.docx DOCX document
B2501Specs.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S

N

W

E

DELAND MUNICIPAL AIRPORT

BID DOCUMENTS

T-HANGAR ELECTRICAL UPGRADES

AVCON, INC.

ENGINEERS & PLANNERS

436 W. NEW YORK AVENUE - DELAND, FLORIDA 32720

OFFICE: (386) 626-1468

www.avconinc.com

PROJECT MAP

LOCATION MAP

VICINITY MAP

NTS

CITY AND AIRPORT REPRESENTATIVES

CITY AND AIRPORT STAFF

CITY COMMISSION

XX-XX

JUNE 2024

XXXXXX-X-XX-XXFDOT FM NO.

CITY OF DELAND BID NO.

DATE

R E V I S I O N S

DESCRIPTIONDATENO.

CHRIS CLOUDMAN MAYOR

CHARLES PAIVA VICE - MAYOR

DANIEL REED COMMISSIONER

JESSICA DAVIS COMMISSIONER

KEVIN REID COMMISSIONER

RAY BAHRAMI, P.E. DEPUTY PUBLIC SERVICES

DIRECTOR / CITY ENGINEER

JOHN EIFF AIRPORT MANAGER

MINDY CONSIDINE ADMINISTRATIVE COORDINATOR

2024.187.02AVCON PROJECT NO.

X-XX-XXXX-XXX-XXXXFAA AIP NO.

AIRPORT LOCATION

DELAND

DELAND, FLORIDA

NORTH

FL-600

DELAND MUNICIPAL AIRPORT

TO INTERSTATE 4

NORTH

E. INT'L

SPEEDWAY BLVD

N. KEPPLER RD.

MARSH

RD.

92 PROJECT AREA

NORTH

ATTENTION:

THIS DOCUMENT CONTAINS PRIVILEGED AND PROPRIETARY

INFORMATION, ALL OF WHICH IS EXPRESSLY PROVIDED BY AVCON, INC.,

FOR USE BY THE INTENDED RECIPIENT, AND FOR A SPECIFIC PURPOSE.

WITHOUT THE EXPRESS WRITTEN CONSENT OF AVCON, INC. ANY

DISTRIBUTION, REPRODUCTION, OR OTHER USE OF THIS DOCUMENT, IN

WHOLE OR IN PART, IS STRICTLY PROHIBITED

DELAND MUNICIPAL

AIRPORT

DELAND, FLORIDA

T-HANGAR

ELECTRIC SERVICE

UPGRADE

2418702002G002

B

ID

D O

C U

M

EN

TS

CADD:

AVCON PROJECT NO.

FAA AIP NO.

FDOT FM NO. XXXXXX-X

X-XX-XXXX-XXX-XXXX

2024.187.02

DRAWING

DATE:

APPROVED BY:

CHECKED BY:

DRAWN BY:

DESIGNED BY:

JUNE 2024

DJN

SCALE (FT): GRAPHIC

NO. DATE BY DESCRIPTION

REVISIONS:

AVCON, INC.

ENGINEERS & PLANNERS

5555 E. MICHIGAN ST., SUITE 200 - ORLANDO, FL 32822-2779

OFFICE: (407) 599-1122 - FAX: (407) 599-1133

CORPORATE CERTIFICATE OF AUTHORIZATION NUMBER: 5057

www.avconinc.com

PROFESSIONAL SEAL

Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

This item has been digitally signed and sealed by:

GENERAL NOTES

AND SHEET INDEX

G002

DJN

PV

AMC

Sheet List Table

SHEET

NUMBER

SHEET

NAME SHEET TITLE

T-HANGAR

ELECTRICAL

UPGRADES

N

W

E

S

N

W

E

GRAPHIC SCALE (FT)

500250125

NORTH

ATTENTION:

THIS DOCUMENT CONTAINS PRIVILEGED AND PROPRIETARY

INFORMATION, ALL OF WHICH IS EXPRESSLY PROVIDED BY AVCON, INC.,

FOR USE BY THE INTENDED RECIPIENT, AND FOR A SPECIFIC PURPOSE.

WITHOUT THE EXPRESS WRITTEN CONSENT OF AVCON, INC. ANY

DISTRIBUTION, REPRODUCTION, OR OTHER USE OF THIS DOCUMENT, IN

WHOLE OR IN PART, IS STRICTLY PROHIBITED

DELAND MUNICIPAL

AIRPORT

DELAND, FLORIDA

T-HANGAR

ELECTRIC SERVICE

UPGRADE

2418702003G003

B

ID

D O

C U

M

EN

TS

CADD:

AVCON PROJECT NO.

FAA AIP NO.

FDOT FM NO. XXXXXX-X

X-XX-XXXX-XXX-XXXX

2024.187.02

DRAWING

DATE:

APPROVED BY:

CHECKED BY:

DRAWN BY:

DESIGNED BY:

JUNE 2024

DJN

SCALE (FT): GRAPHIC

NO. DATE BY DESCRIPTION

REVISIONS:

AVCON, INC.

ENGINEERS & PLANNERS

5555 E. MICHIGAN ST., SUITE 200 - ORLANDO, FL 32822-2779

OFFICE: (407) 599-1122 - FAX: (407) 599-1133

CORPORATE CERTIFICATE OF AUTHORIZATION NUMBER: 5057

www.avconinc.com

PROFESSIONAL SEAL

Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

This item has been digitally signed and sealed by:

SITE ACCESS PLAN

G003

DJN

PV

AMC

GENERAL ACCESS NOTES

LEGEND

T-HANGAR

INFORMATION, ALL OF WHICH IS EXPRESSLY PROVIDED BY AVCON, INC.,

FOR USE BY THE INTENDED RECIPIENT, AND FOR A SPECIFIC PURPOSE.

WITHOUT THE EXPRESS WRITTEN CONSENT OF AVCON, INC. ANY

DISTRIBUTION, REPRODUCTION, OR OTHER USE OF THIS DOCUMENT, IN

WHOLE OR IN PART, IS STRICTLY PROHIBITED

DELAND MUNICIPAL

AIRPORT

DELAND, FLORIDA

T-HANGAR

ELECTRIC SERVICE

UPGRADE

2418702004G101

B

ID

D O

C U

M

EN

TS

CADD:

AVCON PROJECT NO.

FAA AIP NO.

FDOT FM NO. XXXXXX-X

X-XX-XXXX-XXX-XXXX

2024.187.02

DRAWING

DATE:

APPROVED BY:

CHECKED BY:

DRAWN BY:

DESIGNED BY:

JUNE 2024

DJN

SCALE (FT): GRAPHIC

NO. DATE BY DESCRIPTION

REVISIONS:

AVCON, INC.

ENGINEERS & PLANNERS

5555 E. MICHIGAN ST., SUITE 200 - ORLANDO, FL 32822-2779

OFFICE: (407) 599-1122 - FAX: (407) 599-1133

CORPORATE CERTIFICATE OF AUTHORIZATION NUMBER: 5057

www.avconinc.com

PROFESSIONAL SEAL

Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

This item has been digitally signed and sealed by:

CONSTRUCTION

SAFETY AND

PHASING PLAN

NOTES

G101

DJN

PV

AMC

T-HANGAR

INFORMATION, ALL OF WHICH IS EXPRESSLY PROVIDED BY AVCON, INC. &

JLC-SC ENGINEERS, FOR USE BY THE INTENDED RECIPIENT, AND FOR A

SPECIFIC PURPOSE. WITHOUT THE EXPRESS WRITTEN CONSENT OF

AVCON, INC. ANY DISTRIBUTION, REPRODUCTION, OR OTHER USE OF THIS

DOCUMENT, IN WHOLE OR IN PART, IS STRICTLY PROHIBITED

M :\P ro je ct S er ve r\P ro je ct s\

\J

LS

C

.0

.0

- A vc on

In c, D el an d

T H an ga r E le c Se rv ic e U pg ra de

D el an d, F L\

D ra w in gs \E le ct ric al

\E -0

EL

EC

TR

IC

AL

L

EG

EN

D .d w g

4/

/2

2:

P

M

DELAND MUNICIPAL

AIRPORT

DELAND, FLORIDA

T-HANGAR

ELECTRIC SERVICE

UPGRADE

PROFESSIONAL SEAL

CADD:

PROJECT # JLSC24.018.00

DRAWING

DATE:

APPROVED BY:

CHECKED BY:

DRAWN BY:

DESIGNED BY:

MARCH 22, 2024

SCALE (US SVY FT): GRAPHIC

NO. DATE BY DESCRIPTION

REVISIONS:

AVCON, INC.

ENGINEERS & PLANNERS

5555 E. MICHIGAN ST., SUITE 200 - ORLANDO, FL 32822-2779

OFFICE: (407) 599-1122 - FAX: (407) 599-1133

CORPORATE CERTIFICATE OF AUTHORIZATION NUMBER: 5057

www.avconinc.com

Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

This item has been digitally signed and sealed by:

JL

C&O

Joseph, Lawrence & Co

Consulting Engineers 317 riveredge blvd. suite 110 cocoa, Florida 32922 Tel: 321.972.4466 www.jlceng.com

CA No. 32770

Space Coast

E-001

ABBREVIATIONS

DESCRIPTIONABRV.

CH COUNTER HEIGHT

ELECTRIC WATER COOLEREWC

H.I.D.

COMPACT FLUORESCENT LAMPCFL

A

A/C

AC

AFF

AFG

AHU

AWG

C

CONC

COND

CU

DISC

ELEC

EM

EMS

EMT

EF

EX

FA

AMPERES

AIR CONDITIONING

ALTERNATING CURRENT

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AIR HANDLING UNIT

AMERICAN WIRE GAUGE

CONDUIT

CONCRETE

CONDUIT

COPPER

DISCONNECT

ELECTRICAL

EMERGENCY

ENERGY MANAGEMENT SYSTEM

ELECTRICAL METALLIC TUBING

EXHAUST FAN

EXISTING

FIRE ALARM

G

GFI

GND

J

KAIC

KVA

KW

NL

NEMA

NFPA

GROUND

GROUND FAULT INTERRUPTER

GROUND

O.C.

P

PNL

PVC

RM

RGS

SPEC

SS

TYP

UON

V

W

WP

FIRE ALARM ANNUNCIATOR PANELFAAP

ENCLOSED CIRCUIT BREAKERECB

I.G.

SPD

ETR

HIGH INTENSITY DISCHARGE

GRC

HVAC

LTG

MCM

MCU

MH

N

NA

NF

NEC

NIC

GALVANIZED RIGID CONDUIT

JUNCTION

KILOVOLT-AMPERES

KILOWATT

LIGHTING

THOUSANDS OF CIRCULAR MILS

MASTER CONTROL UNIT

METAL HALIDE

NEUTRAL

NOT APPLICABLE

NON-FUSED

NATIONAL ELECTRICAL CODE

NOT IN CONTRACT

NIGHT LIGHT

NATIONAL FIRE PROTECTION ASSOCIATION

ON CENTER

POLE

PANELBOARD

POLYVINYL CHLORIDE

ROOM

RIGID GALVANIZED STEEL

SPECIFICATION

STAINLESS STEEL

TYPICAL

UNLESS OTHERWISE NOTED

VOLTS

WIRE

WEATHERPROOF

MOTOR CIRCUIT PROTECTIONMCP

ISOLATED GROUND

SURGE PROTECTION DEVICE

O.F.C.I. OWNER FURNISHED CONTRACTOR INSTALLED

FIRE ALARM CONTROL PANELFACP

NATIONAL ELECTRIC MANUFACTURERS ASSOCIATION

HEATING, VENTILATING, AND AIR CONDITIONING

(THOUSAND) AMPERE INTERRUPTING CAPACITY

EXISTING TO REMAIN

-SACP SURGE ALARM CONTROL PANEL

MC MASTER CLOCK CONTROL PANEL-

PA PUBLIC ADDRESS CONTROL PANEL-

DESCRIPTIONSYMBOL

TELECOMMUNICATIONS

COMBINATION TELECOMMUNICATIONS/DATA WALL OUTLET BOX AND BLANK PLATE WITH MIN. 3/4"C. TO ACCESSIBLE

CEILING SPACE. COORDINATE OUTLET REQUIREMENTS WITH OWNER.

TELECOMMUNICATIONS WALL OUTLET BOX AND BLANK PLATE FOR WALL MOUNTED TELEPHONE WITH MIN. 3/4"C. TO

ACCESSIBLE CEILING SPACE. COORDINATE OUTLET REQUIREMENTS WITH OWNER.

DATA WALL OUTLET BOX AND BLANK PLATE WITH MIN. 3/4"C. TO ACCESSIBLE CEILING SPACE. COORDINATE OUTLET

REQUIREMENTS WITH OWNER.

FLUSH FLOOR OUTLET BOX WITH POWER DEVICE AND TELECOMMUNICATIONS OUTLET WITH MIN. 3/4"C. TO

ACCESSIBLE CEILING SPACE.

CEILING OUTLET BOX AND BLANK PLATE WITH MIN. 3/4"C. TO TTB FOR WIRELESS ACCESS POINT. COORDINATE

OUTLET REQUIREMENTS WITH OWNER.

COMBINATION TELECOMMUNICATIONS/TELEVISION WALL OUTLET BOX AND BLANK PLATE. COORDINATE OUTLET AND

CABLING REQUIREMENTS WITH OWNER.

3/4" PLYWOOD TELEPHONE TERMINAL BOARD, SIZE AS SHOWN ON PLANS.

TELEPHONE TERMINAL CABINET, SIZE AS NOTED ON PLAN.

TV

TTC

WAP

W

GENERAL DEMOLITION NOTES

DG

DF

DE

DD

DC

DB

DA

DH

ALL ELECTRICAL DEVICES INDICATED IN DARK LINETYPE ON DRAWING SHALL BE REMOVED OR RELOCATED UNLESS NOTED OTHERWISE. REROUTING/RELOCATION OF EXISTING ELECTRICAL SYSTEMS MAY BE REQUIRED AT NEW OPENINGS IN EXISTING CONSTRUCTION OR DUE TO INTERFERENCE WITH OTHER NEW WORK AS DESCRIBED IN THE

FOLLOWING NOTES.

DRAWINGS INDICATE SPECIFIC ITEMS TO BE REMOVED, REROUTED, AND/OR RELOCATED IN ORDER TO INDICATE GENERAL SCOPE. ADDITIONAL ITEMS NOT INDICATED BUT NECESSARY FOR PROJECT RENOVATIONS SHALL BE REMOVED, REROUTED, OR RELOCATED AS REQUIRED. ASSUME WITHIN THE BASE BID A NOMINAL AMOUNT OF BRANCH CIRCUITS, FIXTURES, DEVICES, AND SYSTEMS WIRING WITHIN WALLS OR OPENINGS BEING REMOVED OR RELOCATED AS

REQUIRED TO ACCOMMODATE THE NEW CONSTRUCTION.

FOR ITEMS INDICATED TO BE DEMOLISHED, REMOVE WIRING AND CONDUIT BACK TO THE SOURCE PANELBOARD UNLESS NOTED OTHERWISE. MAINTAIN CIRCUIT CONTINUITY TO REMAINING ITEMS ON CIRCUITS REQUIRED TO REMAIN.

RELOCATE ANY CIRCUITS TO REMAIN TO AVOID CONFLICT WITH NEW CONSTRUCTION AS REQUIRED. PROPERLY

TERMINATE ALL WIRING.

MAINTAIN CIRCUIT CONTINUITY TO ALL REMAINING ELECTRICAL SYSTEMS UNAFFECTED BY BUT PASSING THROUGH RENOVATED SPACES OR WHERE ONLY A PORTION OF A CIRCUIT IS REMOVED. ANY EXISTING ELECTRICAL DEVICES LEFT WITHOUT POWER DUE TO THIS RENOVATION SHALL BE RECONNECTED TO SAME SIZE CIRCUIT(S) AS PRESENTLY SERVED.

NO ELECTRICAL DEVICES SHALL BE LEFT WITHOUT POWER.

REFER TO ARCHITECTURAL DEMOLITION DRAWINGS AND NOTES FOR COORDINATION. PATCH AND REPAIR ALL SURFACES CONTAINING DEMOLITION. COORDINATE WITH ARCHITECTURAL DRAWINGS. MATERIALS AND FINISHES SHALL

MATCH EXISTING.

VISIT THE SITE TO DETERMINE THE EXACT EXTENT OF ELECTRICAL WORK REQUIRED TO COMPLETE THE PROJECT.

EXISTING CONDITIONS INDICATED ON THESE DRAWINGS ARE TAKEN FROM EXISTING BUILDING DOCUMENTS AND FIELD OBSERVATION. OTHER ELECTRICAL ITEMS MAY EXIST FOR WHICH THE ELECTRICAL CONTRACTOR IS RESPONSIBLE

WHICH MAY NOT BE SPECIFICALLY ADDRESSED IN THESE DRAWINGS.

PROPERLY DISPOSE OF ALL ITEMS BEING REMOVED AS PART OF THIS PROJECT. THE OWNER SHALL HAVE THE RIGHT TO

RETAIN ANY ITEMS BEING REMOVED. COORDINATE ITEMS TO BE RETAINED WITH OWNER.

CONDUCTORS IN RENOVATED AREA SHALL BE NEW. DO NOT REUSE EXISTING WIRING UNLESS NOTED OTHERWISE.

EXISTING CONDUIT IN THE RENOVATED AREA MAY BE REUSED IF IT COMPLIES WITH ALL REQUIREMENTS OF THE NEC AND SPECIFICATIONS, IF NEW DEVICE OR EQUIPMENT LOCATION COINCIDES WITH EXISTING LOCATION, AND IF PRACTICAL. CONDUIT NOT INTENDED TO BE REUSED SHALL BE REMOVED IF POSSIBLE (I.E., NOT EMBEDDED IN

CONCRETE FLOOR, ETC.).

DESCRIPTION

WIRING AND POWER

WALL OUTLET BOX AND SINGLE RECEPTACLE

WALL OUTLET BOX AND DUPLEX RECEPTACLE

TWO GANG WALL OUTLET BOX AND (2) DUPLEX RECEPTACLES

WALL OUTLET BOX AND DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER

WALL OUTLET BOX AND DUPLEX RECEPTACLE WITH TOP HALF SWITCHED

TWO GANG WALL OUTLET BOX AND (2) DUPLEX RECEPTACLE WITH TOP HALF SWITCHED

WALL OUTLET BOX AND DUPLEX RECEPTACLE CONNECTED TO EMERGENCY SYSTEM

CEILING OUTLET BOX AND SINGLE RECEPTACLE

CEILING OUTLET BOX AND DUPLEX RECEPTACLE

WALL OUTLET BOX AND GFCI DUPLEX RECEPTACLE

WALL OUTLET BOX AND GFCI DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER

WALL OUTLET BOX AND DUPLEX SAFETY RECEPTACLE

WALL OUTLET BOX AND DUPLEX TWIST-LOCK RECEPTACLE

WALL OUTLET BOX AND GFCI DUPLEX RECEPTACLE WITH WEATHERPROOF COVER

WALL OULTET BOX AND SPECIAL PURPOSE OUTLET AS NOTED ON PLANS

FLUSH FLOOR OUTLET BOX WITH DUPLEX RECEPTACLE

FLUSH FLOOR OUTLET BOX WITH (2) DUPLEX RECEPTACLES

FLUSH FLOOR OUTLET BOX WITH DUPLEX RECEPTACLE AND TELECOMMUNICATIONS OUTLET

FLUSH WALL JUNCTION BOX AND BLANK PLATE

JUNCTION BOX AND BLANK PLATE ABOVE CEILING

SURFACE MOUNTED JUNCTION BOX AND BLANK PLATE

SURFACE MOUNTED WEATHERPROOF JUNCTION BOX AND COVER

FLUSH GRADE FIBER COMPOSITE PULL BOX AS NOTED

MOTOR CONNECTION AS NOTED

FLUSH SHUNT-TRIP BUTTON, MOUNTED 80" TO TOP

CONTROL AND/OR POWER EQUIPMENT CONNECTION

TIME CLOCK

PHOTO CELL

DISCONNECT SWITCH, SIZE AS NOTED

120/208V BRANCH CIRCUIT PANELBOARD, SURFACE MOUNTED

120/208V BRANCH CIRCUIT PANELBOARD, FLUSH MOUNTED

277/480V BRANCH CIRCUIT PANELBOARD

TRANSFORMER

BRANCH CIRCUIT HOMERUN WITH PANEL NAME AND CIRCUIT NUMBER,

QUANTITY OF ARROWHEADS DENOTES QUANTITY OF BRANCH CIRCUITS

BRANCH CIRCUIT WIRING, PROVIDE QUANTITY OF CONDUCTORS REQUIRED

FOR CIRCUITING AND SWITCHING INDICATED ON PLANS

POWER LEG ONLY (NO SWITCH LEG BETWEEN ROOMS)

CONDUIT CAPPED OFF

CONDUIT CONTINUED

CONDUIT RUN UP

CONDUIT RUN DOWN

GROUND OR GROUND ROD AS NOTED

SYMBOL

NOTE: GENERAL NOTES, ABBREVIATIONS, AND SYMBOLS SHOWN

ON THIS ELECTRICAL LEGEND ARE FOR REFERENCE PURPOSES

ONLY. ALL OF THESE MAY NOT BE USED FOR THIS PROJECT.

LIGHTING

CEILING MOUNTED LIGHT FIXTURE, REFER TO LIGHT FIXTURE SCHEDULE

CEILING MOUNTED RECESSED DOWNLIGHT FIXTURE, REFER TO LIGHT FIXTURE SCHEDULE

CEILING MOUNTED RECESSED WALLWASH FIXTURE, REFER TO LIGHT FIXTURE SCHEDULE

CEILING MOUNTED "CLOSE TO CEILING" FIXTURE, REFER TO LIGHT FIXTURE SCHEDULE

PENDANT MOUNTED LIGHT FIXTURE, REFER TO LIGHT FIXTURE SCHEDULE

TRACK LIGHT FIXTURE WITH HEADS AS REQUIRED, REFER TO LIGHT FIXTURE SCHEDULE

WALL MOUNTED LIGHT FIXTURE, REFER TO LIGHT FIXTURE SCHEDULE

CEILING MOUNTED LIGHT FIXTURE WITH EMERGENCY BACKUP

CEILING MOUNTED RECESSED DOWNLIGHT FIXTURE WITH EMERGENCY BACKUP

WALL MOUNTED LIGHT FIXTURE WITH EMERGENCY BACKUP

WALL MOUNTED EMERGENCY BATTERY LIGHT FIXTURE, REFER TO LIGHT FIXTURE SCHEDULE

CEILING MOUNTED EMERGENCY BATTERY LIGHT FIXTURE, REFER TO LIGHT FIXTURE SCHEDULE

CEILING MOUNTED EXIT SIGN WITH EMERGENCY BACKUP, REFER TO LIGHT FIXTURE SCHEDULE

WALL MOUNTED EXIT SIGN WITH EMERGENCY BACKUP, REFER TO LIGHT FIXTURE SCHEDULE

COMBINATION EXIT SIGN AND EMERGENCY LIGHT FIXTURE WITH BATTERY BACKUP

WALL OUTLET BOX AND SINGLE POLE SWITCH ('a' INDICATES SWITCH LEG)

WALL OUTLET BOX AND THREE-WAY SWITCH

WALL OUTLET BOX AND FAN CONTROL SWITCH

WALL OUTLET BOX AND DIMMER SWITCH AS REQUIRED FOR LOAD SERVED

WALL OUTLET BOX WITH SINGLE POLE MANUAL MOTOR STARTER SWITCH

WALL OUTLET BOX AND DUAL TECHNOLOGY OCCUPANCY SENSOR

CEILING OUTLET BOX AND DUAL TECHNOLOGY OCCUPANCY SENSOROS

GENERAL NOTES

1. ALL WORK SHALL BE DONE IN ACCORDANCE THE FLORIDA BUILDING CODE (FBC-2023) 8TH EDITION, NFPA 70 (NEC-2020) AND NFPA 101 (LIFE SAFETY CODE-2021), AND THE REGULATIONS OF THE LOCAL UTILITY TELEPHONE, CABLE TELEVISION AND POWER UTILITY COMPANIES. OBTAIN AND PAY FOR ANY AND ALL REQUIRED PERMITS, INSPECTIONS, CERTIFICATES OF INSPECTIONS AND APPROVAL, AND THE LIKE, AND DELIVER SUCH CERTIFICATES TO THE ENGINEER.

2. CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND COORDINATE WITH ALL EQUIPMENT MANUFACTURER/INSTALLERS

PRIOR TO BIDDING.

3. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES, AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED

THIRD-PARTY TESTING AGENCY.

BUILDING:

4. INSTALLATION HEIGHT OF EQUIPMENT (TO CENTERLINE) ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE SHALL BE:

RECEPTACLE = 18"

CLOCK = 7'-6"

SWITCH = 48"

MODULAR JACK FOR WALL MOUNTED TELEPHONE = 48"

MODULAR TELEPHONE JACK = 18"

TELEVISION OUTLET = 84"

COMPUTER OUTLET = 18"

CALL SWITCH = 44"

REMOTE TEST STATION FOR DUCT DETECTOR = 52"

C = ABOVE COUNTER BACKSPLASH, COORDINATE WITH ARCHITECTURAL ELEVATIONS AND MILLWORK.

5. ALL CONDUIT AND WIRING SHALL BE CONCEALED IN WALLS OR ABOVE CEILINGS UNLESS NOTED OTHERWISE OR APPROVED BY THE ARCHITECT/ENGINEER. ALL DEVICE OUTLET BOXES SHALL BE RECESSED UNLESS NOTED OTHERWISE OR APPROVED BY THE ARCHITECT/ENGINEER. WHERE APPROVED OR NOTED SURFACE METAL RACEWAY AND DEVICE BOXES SHALL BE USED IN LIEU OF CONDUIT AND CONCEALED BOXES AT NO EXTRA COST TO THE OWNER.

6. ALL CONDUIT ROUTING SHOWN IS APPROXIMATE ONLY. CONTRACTOR SHALL FIELD VERIFY FINAL ROUTE WITH ALL OTHER

TRADES AND CONDITIONS IN FIELD PRIOR TO ROUGH-IN.

7. CONDUIT RUNS SHOWN ARE SCHEMATIC AND DO NOT INDICATE THE NECESSARY FITTINGS AND JUNCTION BOXES THAT

ARE INCLUDED IN THE SCOPE OF THE WORK.

8. CONTRACTOR SHALL PERMANENTLY IDENTIFY ALL WIRING WITH THE SOURCE AND CIRCUIT AT ALL ELECTRICAL EQUIPMENT, PULL AND JUNCTION BOXES AND ELECTRICAL TERMINATIONS PROVIDED OR ASSOCIATED WITH THIS

CONSTRUCTION.

9. COORDINATE EXACT LOCATION OF LIGHTING FIXTURES IN MECH. ROOMS/SPACES WITH DUCTWORK INSTALLER PRIOR TO ROUGH-IN. LOCATE BELOW DUCTWORK(8'-0" AFF MINIMUM) CENTERED IN ROOM AS MUCH AS POSSIBLE.

10. COORDINATE EXACT INSTALLATION REQUIREMENTS OF OUTLETS IN MILLWORK WITH ARCHITECTURAL DRAWINGS, APPROVED SHOP DRAWINGS AND MILLWORK INSTALLER PRIOR TO ROUGH-IN.

11. VERIFY EXACT LOCATION OF ALL MECHANICAL EQUIPMENT WITH MECHANICAL INSTALLER PRIOR TO ROUGH-IN.

12. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF ALL LIGHT FIXTURES.

13. PROVIDE NYLON PULLSTRINGS IN ALL EMPTY CONDUITS.

14. COORDINATE THE REQUIRED SIZE OF ALL CIRCUIT BREAKERS FEEDING EQUIPMENT, (I.E. MOTORS, HVAC, KITCHEN EQUIPMENT, SPECIAL PURPOSE OUTLETS, ELEVATORS, OWNER FURNISHED EQUIPMENT ETC. ) WITH APPROVED EQUIPMENT SHOP DRAWINGS AND OWNER REPRESENTATIVES PRIOR TO ORDERING PANELBOARDS. BREAKERS SHALL BE

SIZED PER THE NEC, THE EQUIPMENT NAME PLATE AND MANUFACTURERS RECOMMENDATIONS.

15. ALL DIMMED CIRCUITS SHALL BE PROVIDED WITH DEDICATED NEUTRALS FOR EACH DIMMER AND PHASE CONDUCTOR

THROUGHOUT THE ENTIRE CIRCUIT.

16. THE POWER COMPANY SHALL BE CONTACTED WITHIN 10 DAYS OF THE AWARD OF THE CONTRACT BY THE CONTRACTOR TO VERIFY THE ACTUAL AVAILABLE SHORT CIRCUIT FAULT CURRENT (AIC) AT THE TRANSFORMER SECONDARY BUSHINGS.

THE CONTRACTOR SHALL PROVIDE ELECTRICAL DISTRIBUTION AND UTILIZATION EQUIPMENT AND PANELBOARDS WHICH HAVE AIC/WITHSTAND RATINGS GREATER THAN THE AVAILABLE AIC AT EACH POINT IN THE ELECTRICAL SYSTEM.

17. VISIT THE EXISTING FACILITY AND CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDING AND SITE AFFECTED BY THIS WORK BEFORE SUBMITTING PROPOSALS, SO AS TO BECOME FAMILIAR WITH THE EXISTING CONDITIONS AND DIFFICULTIES THAT WILL AFFECT EXECUTION OF THE WORK. SUBMISSION OF A PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE AND LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE OF

DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED.

18. CONTRACTOR SHALL INCLUDE IN HIS BID THE TRANSPORT AND DISPOSAL OR RECYCLING OF ALL WASTE MATERIALS GENERATED BY THIS PROJECT IN ACCORDANCE WITH ALL RULES, REGULATIONS AND GUIDELINES APPLICABLE.

19. PANEL SCHEDULES INDICATE CIRCUIT DESIGNATIONS ONLY. CONTRACTOR TO PROVIDE MATERIALS AS REQUIRED WHEN NEUTRALS ARE SHARED TO COMPLY WITH NEC REQUIREMENTS. ALL SINGLE PHASE MULTIWIRE BRANCH CIRCUITS SHALL BE FED VIA A TWO POLE BREAKER OR TWO SINGLE POLE BREAKERS WITH AN IDENTIFIED HANDLE TIE. ALL THREE PHASE MULTIWIRE BRANCH CIRCUITS SHALL BE FED VIA A THREE POLE BREAKER OR THREE SINGLE POLE BREAKERS WITH AN

IDENTIFIED HANDLE TIE (PER NEC 210.4B).

20. PER NEC 110.22; PROVIDE PERMANENT LABELING FOR ALL SERIES RATED PANEL ENCLOSURES TO READ AS FOLLOWS:

CAUTION - SERIES COMBINATION SYSTEM RATED ______ AMPERES. IDENTIFIED REPLACEMENT COMPONENTS REQUIRED.

GROUNDING:

21. ALL METAL RACEWAYS, INCLUDING CONDUIT, WIRE TROUGHS, WIREMOLD, ETC., SHALL BE GROUNDED. ALL CONNECTIONS IN METAL RACEWAYS SHALL BE COMPLETED IN SUCH A MANNER AS TO MAINTAIN A CONTINUOUS PATH TO GROUND

THROUGHOUT THE ENTIRE LENGTH OF THE RACEWAY.

WIRING:

22. UNLESS NOTED OTHERWISE ON THE DRAWINGS OR ON THE EQUIPMENT WIRING SCHEDULE, EACH BRANCH CIRCUIT HOME RUN SHALL BE THREE (3) #12 AWG THHN/THWN (1 HOT, 1 NEUTRAL & 1 EQUIPMENT GROUND) IN 3/4" EMT CONDUIT.

PROTECT EACH CIRCUIT WITH A 20 AMPERE, 1-POLE OVERCURRENT DEVICE UNLESS NOTED OTHERWISE. COMBINED

NEUTRALS ARE NOT PERMITTED.

GENERAL:

23. WITHIN 30 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE THE ELECTRICAL CONTRACTOR SHALL PROVIDE TO THE BUILDING OWNER RECORD DRAWINGS OF THE ACTUAL INSTALLATION INCLUDING: 1. A SINGLE-LINE DIAGRAM OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM AND 2. FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR ALL

DISTRIBUTION.

24. THE ELECTRICAL CONTRACTOR SHALL PROVIDE THE BUILDING OWNER AN OPERATING MANUAL AND MAINTENANCE MANUAL AS REQUIRED BY THE FLORIDA BUILDING CODE. THE MANUALS SHALL INCLUDE, AT A MINIMUM, THE FOLLOWING:

1. SUBMITTAL DATE STATING EQUIPMENT RATING AND SELECTED OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE. 2. OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE. REQUIRED ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY IDENTIFIED. 3. NAMES AND ADDRESSES

OF AT LEAST ONE QUALIFIED SERVICE AGENCY.

25. THE ELECTRICAL CONTRACTOR SHALL PROVIDE THE REQUIRED FUNCTIONAL TESTING OF THE LIGHTING SYSTEM TO ENSURE THAT THE CONTROL HARDWARE AND SOFTWARE ARE CALIBRATED, ADJUSTED, PROGRAMMED AND IN PROPER WORKING CONDITION IN ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS AND MANUFACTURER'S INSTALLATION INSTRUCTIONS. WHERE REQUIRED BY THE CODE OFFICIAL, AN APPROVED PARTY INDEPENDENT FROM THE DESIGN OR CONSTRUCTION OF THE PROJECT SHALL BE RESPONSIBLE FOR THE FUNCTIONAL TESTING AND SHALL PROVIDE DOCUMENTATION TO THE CODE OFFICIAL CERTIFYING THAT THE INSTALLED LIGHTING CONTROLS MEET THE PROVISIONS OF FECC SECTION C405. WHERE OCCUPANT SENSORS, TIME SWITCHES, PROGRAMMABLE SCHEDULE CONTROLS, PHOTOSENSORS OR DAYLIGHTING CONTROLS ARE INSTALLED, THE FOLLOWING PROCEDURES SHALL BE PERFORMED: 1.

CONFIRM THAT THE PLACEMENT, SENSITIVITY AND TIME-OUT ADJUSTMENTS FOR THE OCCUPANT SENSORS YIELD

ACCEPTABLE PERFORMANCE.

EXISTING DEVICES TO REMAIN:

26. UNLESS OTHERWISE NOTED:

a. ON DEMOLITION AND NEW WORK PLANS - DEVICES AND EQUIPMENT SHOWN IN LIGHT LINETYPE ARE EXISTING TO

REMAIN.

b. ON DEMOLITION PLANS - DEVICES AND EQUIPMENT SHOWN IN DARK LINETYPE ARE EXISTING TO BE REMOVED

c. ON NEW WORK PLANS - DEVICES AND EQUIPMENT SHOWN IN DARK LINETYPE ARE NEW.

ELECTRICAL SYMBOLS

LEGEND AND GENERAL

NOTES

T-HANGAR

INFORMATION, ALL OF WHICH IS EXPRESSLY PROVIDED BY AVCON, INC. &

JLC-SC ENGINEERS, FOR USE BY THE INTENDED RECIPIENT, AND FOR A

SPECIFIC PURPOSE. WITHOUT THE EXPRESS WRITTEN CONSENT OF

AVCON, INC. ANY DISTRIBUTION, REPRODUCTION, OR OTHER USE OF THIS

DOCUMENT, IN WHOLE OR IN PART, IS STRICTLY PROHIBITED

M :\P ro je ct S er ve r\P ro je ct s\

\J

LS

C

.0

.0

- A vc on

In c, D el an d

T H an ga r E le c Se rv ic e U pg ra de

D el an d, F L\

D ra w in gs \E le ct ric al

\E -0

EL

EC

TR

IC

AL

S

PE

C

IF

IC

AT

IO

N S.

dw g

4/

/2

2:

P

M

DELAND MUNICIPAL

AIRPORT

DELAND, FLORIDA

T-HANGAR

ELECTRIC SERVICE

UPGRADE

PROFESSIONAL SEAL

CADD:

PROJECT # JLSC24.018.00

DRAWING

DATE:

APPROVED BY:

CHECKED BY:

DRAWN BY:

DESIGNED BY:

MARCH 22, 2024

SCALE (US SVY FT): GRAPHIC

NO. DATE BY DESCRIPTION

REVISIONS:

AVCON, INC.

ENGINEERS & PLANNERS

5555 E. MICHIGAN ST., SUITE 200 - ORLANDO, FL 32822-2779

OFFICE: (407) 599-1122 - FAX: (407) 599-1133

CORPORATE CERTIFICATE OF AUTHORIZATION NUMBER: 5057

www.avconinc.com

Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

This item has been digitally signed and sealed by:

JL

C&O

Joseph, Lawrence & Co

Consulting Engineers 317 riveredge blvd. suite 110 cocoa, Florida 32922 Tel: 321.972.4466 www.jlceng.com

CA No. 32770

Space Coast

ELECTRICAL SPECIFICATIONS

I. GENERAL REQUIREMENTS:

A. DO ALL WORK IN COMPLIANCE WITH THE LATEST ADOPTED EDITION OF THE FLORIDA BUILDING

CODE (FBC-2023), NFPA 70 (NEC-2020) AND NFPA 101 (LIFE SAFETY CODE-2021),

AND THE REGULATIONS OF THE LOCAL UTILITY TELEPHONE, CABLE TELEVISION AND POWER UTILITY

COMPANIES. OBTAIN AND PAY FOR ANY AND ALL REQUIRED PERMITS, INSPECTIONS,

CERTIFICATES OF INSPECTIONS AND APPROVAL, AND THE LIKE, AND DELIVER SUCH CERTIFICATES

TO THE ENGINEER.

B. THE CONTRACTOR SHALL FURNISH, PERFORM, OR OTHERWISE PROVIDE ALL LABOR (INCLUDING, BUT NOT

LIMITED TO, ALL PLANNING, PURCHASING, PAINTING, TRANSPORTING, RIGGING, HOISTING,

STORING, INSTALLING, TESTING, CHASING, CHANNELING, CUTTING, TRENCHING, EXCAVATING AND BACKFILLING), COORDINATION, FIELD VERIFICATION, EQUIPMENT INSTALLATION, SUPPORT, AND SAFETY, SUPPLIES, AND MATERIALS NECESSARY FOR THE CORRECT INSTALLATION OF COMPLETE AND FUNCTIONAL ELECTRICAL SYSTEMS (AS DESCRIBED OR IMPLIED BY THESE SPECIFICATIONS

AND THE APPLICABLE DRAWINGS).

C. ALL DRAWINGS AND SPECIFICATIONS ON THE PROJECT ARE COMPLEMENTARY, EACH TO ALL OTHER

SETS, AND THEY SHALL BE USED IN COMBINATION FOR THE EXECUTION OF THIS WORK.

DIVISION 16 WORK SHOWN ON ANY ONE SET OF DRAWINGS, INCLUDING ALL ARCHITECTURAL

DRAWINGS, MECHANICAL, PLUMBING AND FIRE PROTECTION DRAWINGS FOR GENERAL WORK AND

EQUIPMENT, AND DIVISION 16 WORK CALLED FOR UNDER ANY SECTION OF THE PROJECT

SPECIFICATIONS, SHALL BE CONSIDERED AS INCLUDED IN THIS WORK UNLESS SPECIFICALLY

EXCLUDED BY INCLUSION IN SOME OTHER BRANCH OF THE WORK. THIS SHALL INCLUDE

ROUGHING-IN FOR CONNECTIONS AND EQUIPMENT AS CALLED FOR OR INFERRED. THE

CONTRACTOR SHALL CHECK ALL DRAWINGS AND SPECIFICATIONS FOR THE PROJECT AND SHALL BE

RESPONSIBLE FOR THE INSTALLATION OF ALL DIVISION 16 WORK.

D. THE CONTRACTOR SHALL CAREFULLY CHECK THE DRAWINGS AND SPECIFICATIONS OF ALL OTHER

TRADES AND DIVISIONS BEFORE INSTALLING ANY OF HIS WORK. HE SHALL IN ALL CASES

CONSIDER THE WORK OF ALL OTHER TRADES, AND SHALL COORDINATE HIS WORK WITH THEM SO THAT THE BEST ARRANGEMENTS OF ALL EQUIPMENT, PIPING, CONDUIT, DUCTS, ROUGH-IN, ETC., CAN BE OBTAINED.

E. LOCATIONS DESIGNATED FOR OUTLETS, SWITCHES, DEVICES, EQUIPMENT, ETC., ARE

APPROXIMATE AND FINAL LOCATIONS SHALL BE VERIFIED IN THE FIELD. CONTRACTOR SHALL

LOCATE ALL DEVICES UP TO 5 FEET IN ANY DIRECTION AS DIRECTED BY OWNER AND PER CODE.

WHERE INSTRUCTIONS OR NOTES ARE INSUFFICIENT TO CONVEY THE INTENT OF THE DESIGN,

CONSULT THE OWNER PRIOR TO BIDDING AND INSTALLATION.

F. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING AND COORDINATING THE LOCATIONS OF DEVICES TO BE USED AND COORDINATING THE FINAL LOCATIONS OF ELECTRICAL EQUIPMENT WITH MILLWORK, SINKS, BENCHES, COUNTERS AND SHELVING PRIOR TO BIDDING AND INSTALLATION.

ALL DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER.

G. DIVISION 16 CONTRACTOR SHALL HAVE HAD EXPERIENCE OF AT LEAST THE SAME SIZE AND SCOPE AS THIS PROJECT, ON AT LEAST TWO OTHER PROJECTS WITHIN THE LAST FIVE YEARS IN

ORDER TO BE QUALIFIED TO BID THIS PROJECT.

H. CONTRACTOR SHALL AND DOES HEREBY WARRANT ALL MATERIALS AND EQUIPMENT FURNISHED UNDER THIS SECTION OF THE SPECIFICATIONS TO BE FREE FROM DEFECTS AND TO FUNCTION OR OPERATE SATISFACTORILY FOR ONE YEAR AFTER FINAL ACCEPTANCE OF THE WORK, AND THAT ANY

ITEMS NOT MEETING THIS REQUIREMENT WILL BE MADE GOOD BY HIM WITHOUT COST TO

OWNER, PROVIDED SUCH DEFECTS OR FAILURES ARE NOT DUE TO ABUSE, NEGLECT, OR LACK OF

REASONABLE AND ORDINARY MAINTENANCE.

I. ALL WORK SHALL BE EXECUTED IN A WORKMANSHIP MANNER DISPLAYING A NEAT

MECHANICAL APPEARANCE UPON COMPLETION.

J. BALANCE TOTAL PHASE LOADS IN EACH ELECTRICAL PANEL TO A VALUE WITHIN 10% OF EACH OTHER.

K. THE CONTRACTOR SHALL PROVIDE ADEQUATE PROTECTION, WHEREVER WORK IS TO BE

PERFORMED IN FINISHED/OCCUPIED SPACES, TO PREVENT DAMAGE TO ADJACENT AREAS,

EQUIPMENT, OR FURNISHINGS; TO PREVENT ACCIDENTAL INJURY TO BUILDING OCCUPANTS AND THE PUBLIC; TO PREVENT THE SPREADING OF DUST, DIRT, DEBRIS, AND MOISTURE FROM THE

AREA WHERE WORK IS BEING PERFORMED; AND TO PREVENT DUST, DIRT, DEBRIS, AND

MOISTURE FROM GETTING ON OR IN THE BUILDING OCCUPANT'S FURNISHINGS OR EQUIPMENT.

L. THE CONTRACTOR SHALL REPAIR, AT NO COST TO THE OWNER, ANY DAMAGE DONE BY HIMSELF

OR HIS EMPLOYEES. HE SHALL ALSO BE RESPONSIBLE FOR ALL CUTTING AND PATCHING

REQUIRED TO PROPERLY INSTALL HIS WORK. THIS SHALL ALSO INCLUDE THE PATCHING OF EXISTING ROADWAYS (PAVED OR IMPROVED), PARKING AREAS, SIDEWALKS, WALLS, STAIRS, MECHANICAL WORK, CURBS, GUTTERS, ETC., CUT TO INSTALL WORK PROVIDED BY THE CONTRACTOR. PATCH

WORK SHALL COMPLY WITH THE APPLICABLE SECTIONS OF THESE SPECIFICATIONS AND SHALL

MATCH THE EXISTING FINISHES.

M. UPON COMPLETION OF WORK, THE ENTIRE WIRING SYSTEM SHALL BE TESTED, AND SHALL BE SHOWN TO BE IN PROPER WORKING CONDITION IN ACCORDANCE WITH INTENT OF SPECIFICATIONS AND DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO HAVE ALL SYSTEMS

READY FOR OPERATION AND TO HAVE AN ELECTRICIAN AVAILABLE TO OPERATE SAME IN

ACCORDANCE WITH AND UNDER THE SUPERVISION OF THE INSPECTION REPRESENTATIVE OF THE ENGINEER. THE CONTRACTOR SHALL BE AVAILABLE TO ASSIST IN REMOVAL OF PANEL FRONTS, ETC., TO PERMIT INSPECTION AS REQUIRED.

N. IN ACCORDANCE WITH DIVISION 1 AND THE CONDITIONS OF THE CONTRACT, THE CONTRACTOR SHALL PROVIDE AND KEEP UP TO DATE A COMPLETE RECORD SET OF CONSTRUCTION "AS-BUILTS"

BLUELINE PRINTS WHICH SHALL BE CORRECTED DAILY, AND SHALL SHOW EVERY CHANGE FROM

THE ORIGINAL CONTRACT DRAWINGS, INCLUDING ADDENDA AND CHANGE ORDERS IN

ACCORDANCE WITH GENERAL REQUIREMENTS AND SPECIAL CONDITIONS. THIS SET OF

PRINTS SHALL BE KEPT ON THE JOB SITE, AND SHALL BE USED ONLY AS A RECORD SET. THIS SHALL NOT BE CONSTRUED AS AUTHORIZATION FOR THE CONTRACTORS TO MAKE CHANGES IN THE

LAYOUT WITHOUT DEFINITE INSTRUCTION IN EACH CASE.

II. ELECTRICAL SCOPE:

A. FURNISHING AND INSTALLATION OF POWER SYSTEMS, AND AUXILIARY SYSTEMS AS SHOWN

OR HEREIN SPECIFIED.

B. CONNECTION OF ALL EQUIPMENT REQUIRING ELECTRICAL CONNECTION, MENTIONED IN THIS

DIVISION OR SHOWN ON DRAWINGS, WHETHER FURNISHED BY DIVISION 16 OR UNDER

OTHER DIVISIONS, OR FURNISHED BY OWNER.

C. FURNISHING AND INSTALLATION OF OUTLET BOXES, CONDUIT RACEWAYS, FOR A TELEPHONE AND DATA RACEWAY DISTRIBUTION SYSTEM. (TELEPHONE AND DATA HARDWARE, AS WELL AS WIRING AND SOFTWARE

IS NOT INCLUDED.)

D. THE CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR CONTACTING THE OFFICES OF ALL LOCAL AND/OR STATE AUTHORITIES HAVING JURISDICTION OVER THIS PROJECT IN ORDER TO SCHEDULE ALL REQUIRED INSPECTIONS AND OBTAIN ALL NECESSARY PERMITS, ETC. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT/ENGINEER OF ALL SCHEDULED INSPECTIONS AT LEAST TWO WEEKS IN ADVANCE OF THE

SCHEDULED DATE.

E. THE CONTRACTOR SHALL REPLACE ANY DEFECTIVE MATERIALS, EQUIPMENT, OR WORKMANSHIP

WITHOUT COST TO THE OWNER WITHIN THE STIPULATED GUARANTEED PERIOD.

F. IT SHALL BE THE RESPONSIBILITY OF THE DIVISION 16 CONTRACTOR TO HAVE ALL SYSTEMS READY FOR OPERATION AND TO HAVE AN ELECTRICIAN AVAILABLE FOR ALL INSPECTIONS. THE CONTRACTOR SHALL PROVIDE PERSONNEL TO ASSIST IN REMOVAL OF PANEL FRONTS, ETC. TO PERMIT

INSPECTION AS REQUIRED.

G. SUBMIT TO THE ARCHITECT/ENGINEER PROMPTLY AFTER AWARD OF CONTRACT AND PRIOR TO

PURCHASING, SIX COPIES OF MANUFACTURER'S SHOP DRAWINGS IN ACCORDANCE WITH

DIVISION 1, SECTION 01300 - SUBMITTALS FOR THE FOLLOWING ITEMS. ALL SHOP DRAWINGS OF A SPECIFIC

ITEM OR SYSTEM SHALL BE MADE IN ONE SUBMITTAL AND WITHIN TEN DAYS AFTER AWARD OF CONTRACT.

1. PANELBOARDS 4. DISCONNECT SWITCHES

2. SUPPORTS 5. CONDUIT

3. WIRING DEVICES 6. WIRE

H. COMPLETED WIRING SYSTEMS SHALL BE FREE FROM SHORT CIRCUITS AND AFTER COMPLETION, PERFORM TESTS FOR INSULATION RESISTANCE IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE. ALL WIRING SYSTEMS SHALL BE COMPLETELY AND TOTALLY "SAFED"

DURING CONSTRUCTION. ONLY QUALIFIED PERSONNEL SHALL HANDLE ELECTRICAL SYSTEMS.

I. BEFORE ROUGH-IN OF CIRCUITRY OR CONNECTING TO EQUIPMENT, FURNISHED UNDER THIS DIVISION, ANY OTHER DIVISION, OR BY THE OWNER, THE CONTRACTOR SHALL VERIFY THE ELECTRICAL

CHARACTERISTICS AND REQUIREMENTS OF THE EQUIPMENT BEING FURNISHED AND FOR THAT SPECIFIED

AND SHOWN ON THE DRAWINGS AND PROVIDE FOR PROPER ROUGH-IN AND CONNECTION.

J. THE ELECTRICAL CIRCUITS, COMPONENTS, AND CONTROLS FOR ALL EQUIPMENT ARE SELECTED AND SIZED, BASED ON THE EQUIPMENT SPECIFIED. IF SUBSTITUTIONS AND/OR EQUIVALENT EQUIPMENT ARE FURNISHED, IT SHALL BE THE RESPONSIBILITY OF ALL PARTIES CONCERNED, INVOLVED IN, AND FURNISHING

THE SUBSTITUTE AND/OR EQUIVALENT EQUIPMENT TO VERIFY AND COMPARE THE ELECTRICAL

CHARACTERISTICS AND REQUIREMENTS OF THAT FURNISHED TO THAT SPECIFIED AND/OR SHOWN. IF GREATER CAPACITY OR MORE MATERIALS OR LABOR IS REQUIRED FOR THE ROUGH-IN, CIRCUITRY OR CONNECTIONS THAN FOR THE ITEM SPECIFIED AND PROVIDED FOR, THEN IT SHALL BE THE RESPONSIBILITY OF THE PARTIES INVOLVED IN PROVIDING THE SUBSTITUTE AND/OR EQUIVALENT ITEMS OF EQUIPMENT TO PROVIDE ALL COMPENSATION FOR ADDITIONAL CHARGES MADE FOR THE PROPER ROUGH-IN, CIRCUITRY AND CONNECTIONS FOR THE EQUIPMENT FURNISHED. NO ADDITIONAL CHARGES ABOVE THE BASE BID

SHALL BE ALLOWED FOR SUCH REVISIONS.

K. EXCAVATION FOR UNDERGROUND ELECTRICAL STRUCTURES: CONFORM TO ELEVATIONS AND

DIMENSIONS SHOWN WITHIN A TOLERANCE OF PLUS OR MINUS 0.10'; PLUS A SUFFICIENT

DISTANCE TO PERMIT PLACING AND REMOVAL OF CONCRETE FORMWORK, INSTALLATION OF

SERVICES, OTHER CONSTRUCTION, AND FOR INSPECTION.

L. TRENCHING: EXCAVATE TRENCHES FOR ELECTRICAL INSTALLATIONS AS FOLLOWS:

1. EXCAVATE TRENCHES TO THE UNIFORM WIDTH, SUFFICIENTLY WIDE TO PROVIDE AMPLE WORKING ROOM AND A MINIMUM OF 6" TO 9" CLEARANCE ON BOTH SIDES OF RACEWAYS AND EQUIPMENT.

2. EXCAVATE TRENCHES TO DEPTH INDICATED OR REQUIRED.

3. LIMIT THE LENGTH OF OPEN TRENCH TO THAT IN WHICH INSTALLATIONS CAN BE MADE AND THE

TRENCH BACKFILLED WITHIN THE SAME DAY.

4. WHERE ROCK IS ENCOUNTERED, CARRY EXCAVATION BELOW REQUIRED ELEVATION AND BACKFILL

WITH A LAYER OF CRUSHED STONE OR GRAVEL PRIOR TO INSTALLATION OF RACEWAYS AND

EQUIPMENT. PROVIDE A MINIMUM OF 6" OF STONE OR GRAVEL CUSHION BETWEEN ROCK BEARING

SURFACE AND ELECTRICAL INSTALLATIONS.

M. THE CONTRACTOR SHALL PROVIDE ALL INSERTS FOR THE SUPPORT OF DIVISION 16

EQUIPMENT TO BE PLACED IN CONCRETE OR THROUGH CONCRETE SLABS AS CONSTRUCTION

PROGRESSES. HE SHALL PROVIDE ALL MISCELLANEOUS HANGING AND SUPPORTING HARDWARE. ALL ELECTRICAL WORK IS TO BE CONCEALED IN OR BUILT INTO GENERAL CONSTRUCTION SHALL BE PLACED AS CONSTRUCTION PROGRESSES. FAILURE OF THE CONTRACTOR TO COORDINATE WORK WITH OTHER TRADES AND THE PROJECT CONSTRUCTION PROGRESS SHALL MAKE HIM RESPONSIBLE FOR ALL COST OF CUTTING AND PATCHING, AS REQUIRED TO INSTALL WORK. NO STRUCTURAL MEMBER, MASONRY CONSTRUCTION OR

FINISHED WORK SHALL BE CUT OR ALTERED WITHOUT PRIOR WRITTEN APPROVAL BY THE

ARCHITECT/ENGINEER. CONTRACTOR SHALL FIRE RATE ALL PENETRATIONS THROUGH ALL FIRE RATED

SLABS OR WALLS PER THE INTENDED RATING.

N. THE CONTRACTOR SHALL SUPPLY AND SET INTO PLACE ALL WALL SLEEVES FOR CONDUITS

AND CEILING INSERTS FOR HANGERS IN AREAS OF NEW CONSTRUCTION AS BUILDING CONSTRUCTION

PROGRESSES. INSTALL EQUIPMENT NOTED TO BE CONCEALED IN WALLS BEFORE WALLS ARE

CONSTRUCTED IN ORDER THAT WALLS MAY BE CONSTRUCTED AROUND CONDUITS, ENCLOSURES, ETC.

O. METALLIC MATERIALS SHALL BE PROTECTED AGAINST CORROSION. EQUIPMENT ENCLOSURES SHALL BE GIVEN RUST-INHIBITING TREATMENT AND STANDARD FINISH BY MANUFACTURER. ALUMINUM SHALL NOT BE USED ON CONTACT WITH EARTH, AND, WHERE CONNECTED TO DISSIMILAR METAL, SHALL BE PROTECTED BY SUITABLE FITTINGS AND TREATMENT. ALL FERROUS METALS SUCH AS ANCHORS, BOLTS, BRACES, BOXES, BODIES, CLAMPS, FITTINGS, GUARDS, NUTS, PINS, RODS, SHIMS, THIMBLES, WASHERS, AND MISCELLANEOUS PARTS, NOT OF STAINLESS STEEL OR NONFERROUS MATERIALS, SHALL BE HOT-DIPPED

GALVANIZED.

P. ALL CONDUITS STUBBED OUT FOR FUTURE USE SHALL HAVE A PULL WIRE INSTALLED, A PLASTIC CAP

INSTALLED AND BE IDENTIFIED AS TO THE CONDUIT ORIGIN.

Q. THE RESPONSIBILITY FOR ANY CUTTING OF CONSTRUCTION WHICH IS REQUIRED FOR THE

INSTALLATION OF DIVISION 16 WORK, SHALL BE BY THE CONTRACTOR. THE CONTRACTOR SHALL COORDINATE WITH ALL OTHER TRADES AND THE OWNER BEFORE ANY CUTTING AND OBTAIN APPROVAL FROM THE ARCHITECT/ENGINEER PRIOR TO ANY CUTTING. ALL PATCHING AND FINISHING SHALL BE BY THE

CONTRACTOR.

R. WHERE OPENINGS OR HOLES ARE CUT IN CONSTRUCTION AND THE CUTTING BREAKS ELECTRICAL CIRCUITRY OR CONTROL CIRCUITRY CONDUIT AND WIRING, THEN IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO REROUTE THE CIRCUITRY CONDUIT AND REWIRING AND TO COMPLETE THE CIRCUITRY AS REQUIRED AND AS APPROVED BY THE ARCHITECT/ENGINEER. TEMPORARY COMPLETION SHALL BE PROVIDED WHERE NECESSARY BEFORE THE PERMANENT REROUTING AND COMPLETION WORK IS FINISHED.

S. ANY PENETRATIONS OF FIRE OR SMOKE RATED ASSEMBLIES MADE BY THIS CONTRACTOR IN VERTICAL OR HORIZONTAL CONSTRUCTION SHALL BE SEALED AND PROTECTED BY THIS CONTRACTOR IN ORDER TO MAINTAIN THE ESTABLISHED FIRE RATING WITH METHODS AS APPROVED BY THE AUTHORITY HAVING

JURISDICTION.

III. IDENTIFICATION:

A. IDENTIFICATION NAMEPLATES SHALL BE LAMINATED PLASTIC, SECURED TO EQUIPMENT WITH TWO

SCREWS.

B. EACH PANELBOARD AND SWITCHBOARD SHALL BE EQUIPPED WITH A PERMANENT PLASTIC NAMEPLATE

WITH 1/2" MINIMUM LETTERS, SECURELY FASTENED TO THE DEVICE.

C. EACH INDIVIDUALLY MOUNTED CIRCUIT BREAKER, SWITCH, TRANSFER SWITCH, MOTOR STARTER, LIGHTING CONTACTOR, TRANSFORMER AND/OR ANY OTHER CONTROL OR PROTECTIVE DEVICE INCLUDING EQUIPMENT DISCONNECT SWITCHES SHALL BE EQUIPPED WITH A PERMANENT PLASTIC NAMEPLATE WITH

1/2" MINIMUM LETTERS.

D. PANELBOARDS SHALL HAVE TYPEWRITTEN DIRECTORIES. ALL CIRCUITS TO BE IDENTIFIED BY DEVICES SERVED AND ROOM NUMBERS (I.E., LIGHTING ROOM 216). HANDWRITTEN DIRECTORIES WILL NOT BE

ALLOWED.

E. EACH JUNCTION BOX CABINET OR WIREWAY LARGER THAN 6" X 6" SHALL BE EQUIPPED WITH A

PLASTIC NAMEPLATE WITH 1/2" MINIMUM LETTERS INDICATING THE SYSTEM ENCLOSED.

F. ALL SYSTEMS JUNCTION BOXES AND CONDUIT SHALL BE COLOR CODED INSIDE AND OUTSIDE OF THE

BOX PRIOR TO THE INSTALLATION OF CONDUCTORS PER THE FOLLOWING:

1. CCTV SYSTEM: GREEN

2. TELEPHONE DATA SYSTEM: BLUE

3. FIRE ALARM SYSTEM: RED

G. ENTIRE BOX INSIDE AND OUT, INCLUDING COVER, SHALL BE PAINTED PRIOR TO INSTALLING

CONDUCTORS.

IV. WIRING DEVICES:

A. SWITCHES AND RECEPTACLES IN LOBBIES, CORRIDORS OR COMMERCIAL SPACES, UNFINISHED AND MECHANICAL SPACES SHALL BE 20 AMP COMMERCIAL GRADE 125 VAC. GRAY IN COLOR WITH STAINLESS

STEEL COVERPLATES.

B. WEATHERPROOF RECEPTACLES SHALL BE GFCI TYPES WITH GASKETED STAINLESS STEEL KEY LOCKABLE FLIP COVER TYPE COVERPLATES. SURGE SUPPRESSION TYPE OUTLETS IN MDFS AND IDFS SHALL

BE HUBBELL #83625 (BLUE) OR EQUAL.

C. RECEPTACLES PROVIDED FOR ATTACHMENT OF CORD AND PLUG EQUIPMENT SHALL BE HEAVY DUTY, SPECIFICATION GRADE, NON-INTERCHANGEABLE, FLUSH MOUNTED TYPES OF THE PROPER NEMA

CONFIGURATION TO SERVE THE EQUIPMENT. NEMA CONFIGURATIONS SHALL BE VERIFIED PRIOR TO INSTALLATION OF CIRCUIT CONDUCTORS. CONTRACTOR TO PROVIDE ALL CONNECTION, WIRING, PIGTAILS

FOR DISHWASHERS, COOKING RANGES, OVENS AND GARBAGE DISPOSALS.

D. ALL DEVICES SHALL HAVE PROPER PLATES, CARPET FLANGES, TRIMS, RINGS, ESCUTCHEONS, ETC., AS MANUFACTURED BY SAME MANUFACTURER AS DEVICES. ANY TELEPHONE OR OTHER OUTLET WHICH IS NOT EQUIPPED WITH A PLATE FURNISHED BY OTHERS SHALL HAVE ONE PROVIDED BY THIS CONTRACTOR.

DEVICE PLATES SHALL BE COLOR AND TYPE AS SHOWN BELOW.

1. FINISHED SPACES DECORA LINE:

a. IVORY DEVICES

b. IVORY NYLON PLATES

2. UNFINISHED OR INDUSTRIAL OR COMMERCIAL TYPE SPACES:

a. GRAY DEVICES

b. STAINLESS STEEL OR STAMPED GALVANIZED STEEL ON SURFACE MOUNTED BOXES

c. STAINLESS STEEL PLATES ON FLUSH MOUNTED BOXES

E. MOUNTING HEIGHTS ARE APPROXIMATE. THE EXACT LOCATIONS AND MOUNTING HEIGHTS SHALL BE DETERMINED ON THE JOB AND IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE WITH ALL TRADES TO INSURE CORRECT INSTALLATION, I.E., OVER COUNTERS IN OR ABOVE BACK-SPLASHES, IN BLOCK WALLS, TILE, AND OTHER SPECIFIC CONSTRUCTION FEATURES. LOCATION OF OUTLETS MOUNTED IN BUILT-INS, MILLWORK, AND CABINETRY SHALL BE VERIFIED. OUTLETS MOUNTED IN KICK OR TOE SPACES SHALL BE MOUNTED HORIZONTALLY. OUTLET BOXES SHALL BE MOUNTED TO PREVENT DEVICE PLATE FROM OVERLAPPING BACKSPLASH, TRIM, TILE, ETC. LOCATE SO DEVICE PLATE WILL LAY FLAT AGAINST SURFACE

COMPLETELY AROUND THE PERIMETER OF PLATE.

F. OUTLETS, OTHER THAN THOSE COORDINATED WITH COUNTER TOPS, SHELVES, AND CABINETS, SHALL BE LOCATED WITH THE CENTER LINE OF OUTLET BOXES THE FOLLOWING DISTANCE ABOVE THE FINISHED

FLOOR, UNLESS OTHERWISE INDICATED:

1. RECEPTACLES, GENERAL: 1'-6" AFF

2. TELEPHONE OUTLETS: 1'-6" AFF

3. SWITCHES, GENERAL: 4'-0" AFF

V. RACEWAYS

A. SHALL BE GALVANIZED OUTSIDE AND INSIDE BY HOT DIPPING. E.M.T. SHALL BE ELECTRO-

GALVANIZED. CONDUITS SHALL BE AS MANUFACTURED BY REPUBLIC, PITTSBURGH STANDARD,

WHEATLAND, TRIANGLE, ALLIED, OR YOUNGSTOWN.

B. SHALL BE STANDARD THREADED TYPE, GALVANIZED OUTSIDE AND INSIDE BY HOT DIPPING.

THREADLESS AND CLAMP TYPE NOT ACCEPTABLE. SHALL BE AS MANUFACTURED BY RACO,

EFCOR, OR APPLETON.

C. SHALL BE STEEL THREADED COMPRESSION TYPE. ALL COUPLINGS AND CONNECTORS SHALL BE EFCOR OR RACO. PRESSURE INDENTED TYPE CONNECTORS OR CAST METAL WILL NOT BE APPROVED FOR

ANY LOCATION.

D. CONNECTORS SHALL HAVE PLASTIC INSULATED THROAT INSERTS.

E. THE USE OF METAL CLAD CABLE IS ACCEPTABLE IN LOCATIONS AS ACCEPTED BY THE NEC AND ALL

LOCAL JURISDICTIONAL CODES.

F. STEEL METAL CLAD CABLE, TYPE MC, EMPLOYING CIRCUIT CONDUCTORS #12 SOLID TO #2 AWG, SOLID OR STRANDED COPPER WITH THHN INSULATION, AN INSULATED GREEN GROUNDING CONDUCTOR AND GALVANIZED STEEL INTERLOCKED ARMOR CLADDING. THE CABLES SHALL BE SUITABLE FOR USE IN DRY LOCATIONS AT TEMPERATURES NOT EXCEEDING 90° C ON AD CIRCUITS UP TO 600 VOLTS IN ACCORDANCE WITH N.E.C., ARTICLE 334. THE CABLE SHALL BE ONE AND TWO HOUR FIRE RATED PER ANSI/UL 1479 FOR USE

IN WALL, CEILING AND FLOOR ASSEMBLIES.

G. FLEXIBLE METALLIC CONDUIT RACEWAYS MAY BE USED TO CONNECT HVAC UNITS LOCATED IN

INTERIOR MECHANICAL AREAS. MINIMUM SIZE 3/4".

H. CONDUIT SHALL BE SIZED IN ACCORDANCE WITH THE LATEST NATIONAL ELECTRICAL CODE EXCEPT THAT NO CONDUIT SHALL BE SMALLER THAN 3/4" UNLESS OTHERWISE NOTED. CONDUIT SHALL BE SIZED LARGER THAN REQUIRED ABOVE WHEN SO SHOWN ON THE DRAWINGS OR WHEN REQUIRED BY LOCAL

CODE.

I. ANY CONDUIT STUBBED OUT FOR FUTURE SHALL BE CAPPED WITH A PLASTIC CAP AND MARKED WITH A 2" MINIMUM RED METAL TAG WHICH IDENTIFIES CONDUIT ORIGIN. CONDUITS STUBBED UP ABOVE GRADE OR ROOF SHALL BE TAGGED ON THE CONDUIT. CONDUIT STUBBED OUT BELOW GRADE SHALL BE TAGGED ON NEAREST BUILDING WALL, CURB, ETC., DIRECTLY OVER THE CONDUIT RUN. ALL EMPTY

CONDUITS SHALL HAVE PULL WIRES.

VI. SCHEDULE 40 RIGID PVC:

A. CONDUIT SHALL BE COMPOSED OF POLYVINYLCHLORIDE AND SHALL BE UL RATED TYPE 40 FOR

USE WITH 90EC RATED CONDUCTORS. CONDUIT SHALL CONFORM TO NEMA STANDARDS AND

APPLICABLE SECTIONS OF NEC.

B. INSTALLATION OF RIGID NON-METALLIC CONDUIT SHALL COMPLY WITH ARTICLE 347 OF THE

NATIONAL ELECTRICAL CODE (NFPA 70) AND THESE SPECIFICATIONS.

C. PROVIDE A CONTINUOUS, INSULATED, GROUNDING CONDUCTOR IN EVERY RIGID, NON-METALLIC

RACEWAY EVEN IF NOT SHOWN ON THE DRAWINGS. THE GROUNDING CONDUCTOR SHALL BE

CONNECTED TO GROUND AT EACH END OF THE RACEWAY IN ACCORDANCE WITH ARTICLE 250 OF

THE NATIONAL ELECTRICAL CODE (NFPA 70).

D. WHERE RIGID NON-METALLIC CONDUIT TRANSITIONS TO METALLIC CONDUIT, THE LOCATION OF THE

TRANSITION SHALL BE UNDERGROUND.

E. NO PVC CONDUIT SHALL BE RUN EXPOSED, OR ABOVE GRADE.

VII. WIRE AND CABLE 600 VOLT:

A. CONDUCTORS SHALL HAVE CURRENT CARRYING CAPACITIES AS PER NEC AND WITH 600 VOLT

INSULATION, #12 AVERAGE MINIMUM FOR 20 AMP CIRCUITS AND #14 FOR 15 AMP CIRCUITS

EXCEPT FOR CONTROLS, AND FIXTURE WIRE. CONDUCTORS SHALL BE COPPER.

B. #12 AND #10 SHALL BE SOLID, TYPE THW/THWN INSULATION.

C. #8 AND LARGER, AND ANY SIZE TO MOTORS SHALL BE STRANDED TYPE THW.

D. SHALL BE MADE WITH T & B STA-KON WIRE JOINTS, PT SERIES, COMPLETE WITH INSULATING

CAPS AND INSTALLED WITH WT161 TOOL OR WT2000 TOOL, IDEAL SUPER-NUTS (NOT WIRE

NUTS), IDEAL WING NUTS, OR BUCHANAN ELEC. PRODUCTS B CAP OR SERIES 2000 PRES-

SURE CONNECTORS COMPLETE WITH NYLON SNAP-ON INSULATORS AND INSTALLED WITH C24

PRESSURE TOOL.

E. ALL JOINTS AND SPLICES IN WIRE SHALL BE MADE WITH APPROVED SOLDERLESS CONNECTORS, AND COVERED SO THAT INSULATION IS OWNER APPROVED EQUAL TO CONDUCTOR INSULATION.

SPLICES SHALL NOT BE PERMITTED IN CONTROL, SECURITY, FIRE ALARM, TELEVISION OR

COMMUNICATIONS SYSTEMS, OR WHERE OTHERWISE NOTED. SPLICING OF WIRE OR CABLES WILL

NOT BE ALLOWED BELOW GRADE, INCLUDING IN BOXES BELOW GRADE.

F. BOTH CONDUCTORS AND CONDUITS SHALL BE CONTINUOUS FROM OUTLET TO OUTLET.

G. IN INSTALLING THE MAIN ELECTRICAL SERVICE, ADDITIONAL SLACK CONDUCTORS SHALL BE

PROVIDED AND TERMINATED AS REQUIRED BY ELECTRIC UTILITY FOR CONNECTION TO THEIR

EQUIPMENT. FIELD COORDINATE WITH UTILITY PRIOR TO INSTALLING CONDUCTORS.

H. IN INSTALLING PARALLEL CONDUCTORS IT IS MANDATORY THAT ALL CONDUCTORS MAKING UP THE

FEEDER BE EXACTLY THE SAME LENGTH, THE SAME SIZE AND THE SAME TYPE OF CONDUCTOR

WITH THE SAME INSULATION. FURTHER, EACH GROUP OF CONDUCTORS MAKING UP A PHASE OR

NEUTRAL MUST BE BONDED AT BOTH ENDS IN AN APPROVED MANNER.

I. CONDUCTOR SIZES INDICATED ON CIRCUIT HOMERUNS OR IN PANELBOARD SCHEDULES SHALL BE

INSTALLED OVER THE ENTIRE LENGTH OF THE CIRCUIT UNLESS NOTED OTHERWISE ON THE

DRAWINGS.

J. CONDUCTORS SHALL BE CONTINUOUS AND UNSPLICED WHERE INSTALLED IN CONDUIT. SPLICES SHALL OCCUR ONLY WITHIN WIRING TROUGHS, WIREWAYS, JUNCTION BOXES, OUTLET BOXES, OR EQUIPMENT ENCLOSURES WHERE SUFFICIENT ADDITIONAL ROOM IS PROVIDED FOR ALL SPLICES.

K. EACH BRANCH CIRCUIT AND FEEDER CONDUCTOR SHALL BE COLOR CODED. FOR CONDUCTOR

SIZES THRU NO. 6 AWG, THE INSULATION SHALL BE OF THE COLOR AS INDICATED BELOW. COLOR CODE SHALL BE STRICTLY ADHERED TO. FOR CONDUCTOR SIZES NO. 4 AWG AND LARGER, COLOR

CODED PHASE TAPE MAY BE APPLIED COMPLETELY AROUND THE CONDUCTOR INSULATION

WITHIN 8" OF EACH END OF THE CONDUCTOR AND IN EACH PULL OR JUNCTION BOX OR WHENEVER

CONDUCTORS ARE PHYSICALLY EXPOSED TO VIEW. GROUNDING CONDUCTORS AND GROUNDED

CONDUCTORS SHALL HAVE INSULATION COLOR AS INDICATED FOR SIZES THROUGH #6 AWG.

120/208 V, 3PHASE,4W

PHASE A, COLOR: BLACK

PHASE B, COLOR: RED

PHASE C, COLOR: BLUE

NEUTRAL, COLOR: WHITE

GROUND, COLOR: GREEN

VIII. GROUNDING:

A. THIS SECTION DEALS WITH THE GROUNDING OF SERVICE EQUIPMENT, TRANSFORMERS, NON- CURRENT CARRYING CONDUCTIVE SURFACES OF EQUIPMENT, METAL BUILDING, STRUCTURES AND

OTHER EQUIPMENT.

B. ALL GROUNDING CONNECTIONS SHALL BE INSTALLED IN ACCORDANCE WITH THE NATIONAL

ELECTRICAL CODE AND ALL LOCAL CODES AND REQUIREMENTS. SUCH CODES SHALL BE CONSIDERED

MINIMUM REQUIREMENTS AND THE INSTALLATION OF THE GROUNDING SYSTEM

SHALL INSURE FREEDOM FROM DANGEROUS SHOCK EXPOSURE AND SHALL PROVIDE A LOW IMPEDANCE GROUND FAULT PATH TO PERMIT OPERATION OF OVERCURRENT AND GROUND FAULT PROTECTIVE DEVICES.

C. ALL SERVICE AND EQUIPMENT GROUNDING CONDUCTORS, AND BONDING JUMPERS SHALL BE

INSULATED COPPER, TYPE THHN, THWN, OR THW CONDUCTORS (UNLESS NOTED OTHERWISE) AND SHALL BE SIZED IN ACCORDANCE WITH THE APPLICABLE PORTIONS OF ARTICLES 250 AND 517 OF THE NATIONAL ELECTRICAL CODE. GROUNDING CONDUCTORS #6 AWG AND SMALLER SHALL HAVE A GREEN COLOR INSULATION. ALL GROUNDING CONDUCTORS #4 AWG AND LARGER SHALL BE ADEQUATELY IDENTIFIED WITH A GREEN TRACER AND/OR GREEN COLORED TAPE AT EACH END OF THE GROUNDING CONDUCTOR AND AT

EACH PULLBOX OR OTHER ACCESSIBLE LOCATION.

D. THE MAIN SERVICE GROUNDING ELECTRODE SYSTEM SHALL CONSIST OF THE FOLLOWING ITEMS BONDED TOGETHER BY THE GROUNDING ELECTRODE CONDUCTORS IN ACCORDANCE WITH NEC ARTICLE

250, PART H:

1. THE MAIN UNDERGROUND COLD WATER PIPE, IF METAL, NEC 250- 81(A)

2. METAL FRAME OF BUILDING WHERE AVAILABLE, NEC 250-81(B)

3. CONCRETE ENCASED ELECTRODE, NEC 250-81(C)

4. THE BUILDING LIGHTNING PROTECTION SYSTEM.

E. THE NEUTRAL CONDUCTOR SHALL BE GROUNDED AT THE SERVICE ENTRANCE MAIN DISCONNECT, AND

AT EACH SEPARATELY DERIVED SYSTEM ONLY PER NEC ARTICLE 250.

F. A #4 INSULATED COPPER CONDUCTOR INSTALLED IN 3/4" CONCEALED CONDUIT SHALL BE CONNECTED FROM THE BUILDING GROUNDING ELECTRODE SYSTEM TO EACH BUILDING TELEPHONE TERMINAL/DATA IDF TERMINAL BOARDS, OR CABINETS, FIRE ALARM CONTROL CABINETS, CCTV SYSTEM CABINETS, EMS CABINETS, AND SECURITY SYSTEM CABINETS. TERMINATE ON AN APPROPRIATELY SIZED (8) TERMINAL MULTI-CONDUCTOR CONNECTION GROUNDING LUG LOCATED WITHIN CABINET OR ON TERMINAL BOARDS.

IX. PANELBOARDS:

A. PANELBOARDS SHALL BE DEAD FRONT TYPE AND SHALL BE IN ACCORDANCE WITH UNDERWRITERS' LABORATORIES, INC., STANDARD FOR PANELBOARDS AND ENCLOSING CABINETS AND SO LABELED.

B. PANELBOARDS SHALL BE FACTORY ASSEMBLED WITH BRANCH BREAKERS ARRANGED AS SHOWN IN SCHEDULES. BREAKERS SHALL BE NUMBERED VERTICALLY BEGINNING TOP LEFT. BREAKER NUMBERS SHALL BE PERMANENTLY ATTACHED TO TRIM. PANEL SHALL BE MINIMUM 20" WIDE OR 16" FOR RESIDENTIAL

LOAD CENTERS, UNLESS SPECIFICALLY NOTED OTHERWISE.

C. ANY SPECIAL REQUIREMENTS ON THE DRAWINGS OR SCHEDULES, SUCH AS GROUND FAULT

PROTECTION, ARC-FAULT CIRCUIT BREAKERS, INCREASED INTERRUPTING CAPACITY, SHUNT TRIP TYPE CIRCUIT BREAKER, FEED THRU PANELBOARDS, ETC., SHALL SUPERSEDE THESE SPECIFICATIONS, BUT ONLY

INSOFAR AS THAT PARTICULAR REQUIREMENT IS CONCERNED AND AS INDICATED.

D. WIRING IN PANELBOARD GUTTERS SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER. WIRING

SHALL BE GROUPED INTO NEAT BUNDLES AND SECURED WITH NYLON TIE WRAPS.

E. PROVIDE TYPE WRITTEN DIRECTORIES FOR EACH PANELBOARD INDICATING THE LOAD SERVED.

X. LIGHTING FIXTURES:

A. LIGHTING FIXTURES SHALL BE FURNISHED AS SHOWN ON DRAWINGS AND IN THE LIGHTING FIXTURE SCHEDULE. IT SHALL SPECIFICALLY BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY EXACT TYPE CEILING AND RECESSING DEPTH OF ALL RECESSED FIXTURES AND TO FURNISH THE MOUNTING TRIMS AND ACCESSORIES OF THE SPECIFIED AND/OR APPROVED FIXTURES FOR THE CEILING TO BE INSTALLED.

LIGHTING FIXTURES SHALL BE PROVIDED WITH JOINER PLATES, END CAPS, RETAINING CLIPS, PLASTER FRAMES, HOUSINGS, AND ALL OTHER ACCESSORIES REQUIRED FOR A COMPLETE INSTALLATION.

B. ALL FIXTURES SHALL BE EQUIPPED WITH LAMPS UNLESS OTHERWISE NOTED. LAMPS SHALL BE INSTALLED NEW, IMMEDIATELY PRIOR TO FINAL INSPECTION, AND SHALL NOT BE USED FOR CONSTRUCTION.

C. FIXTURE CATALOG NUMBER REPRESENTS BASIC LUMINARY SIZE, TYPE, QUALITY AND CONFIGURATION.

ACCESSORIES SHALL BE FURNISHED WITH EACH UNIT AS REQUIRED FOR A COMPLETE FINISHED INSTALLATION. BASIC ACCESSORIES SHALL INCLUDE, BUT ARE NOT LIMITED TO, THE FOLLOWING:

1. JOINING PLATES, END CAPS, RETAINING CLIPS, ETC.

2. TRIMS FOR RECESSED FIXTURES.

3. FIXTURE STEMS AND CANOPIES FINISHED TO MATCH FIXTURES.

4. SPECIAL MOUNTING BRACKETS, TENONS, SLIP FILTERS, CONCRETE BASES, POLES, ANCHOR BOLTS, JUNCTION BOXES, AND STANCHIONS FOR ALL EXTERIOR LIGHTING FIXTURES. PROVIDE ALL

WEATHERPROOFING FOR ALL LIGHTING FIXTURES TO BE INSTALLED IN EXTERIOR LOCATIONS.

D. STRUCTURAL SUPPORT OF ALL FIXTURES SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.

E. THE SYSTEM GROUNDING CONDUCTOR SHALL BE SECURED TO EACH FIXTURE BODY BY MEANS OF A

BONDING SCREW.

F. OWNER/DEVELOPER WILL HAVE RIGHT TO RELOCATE LIGHTING FIXTURES OR LIGHTING SWITCHES WITHIN 72" OF LOCATION SHOWN ON FIRST WALK-THROUGH AT NO ADDITIONAL EXPENSE. COORDINATE THE

WALK-THROUGH PRIOR TO THE INSTALLATION OF THE WIRING.

E-002

ELECTRICAL SPECIFICATIONS

T-HANGAR

PANEL 'A2'

PANEL 'A1'

PANEL 'MDPA'

UTILITY METER

ATTENTION:

THIS DOCUMENT CONTAINS PRIVILEGED AND PROPRIETARY

INFORMATION, ALL OF WHICH IS EXPRESSLY PROVIDED BY AVCON, INC. &

JLC-SC ENGINEERS, FOR USE BY THE INTENDED RECIPIENT, AND FOR A

SPECIFIC PURPOSE.