B2501ADD2.pdf
PDF 5 MB Posted
- Attached to
- T-HANGAR ELECTRICAL SERVICE UPGRADE State and local contract opportunity
- Solicitation number
- B-25-01
- Issued by
- Volusia County, Florida
About this file
This document is Addendum No. 2 for the T-Hangar Electrical Service Upgrade project for the City of DeLand Municipal Airport, issued on November 12, 2024. The addendum provides clarifications and corrections to the original contract documents for electrical service upgrades to t-hangars, with bid number ITB-B-25-01-0-2025/CM. The addendum includes reissued plan revisions and a schedule of values for total fixture/outlet counts. Contractors are required to thoroughly familiarize themselves with the addendum contents and inform subcontractors, suppliers, and manufacturers of the applicable requirements. Failure to acknowledge receipt of the addendum may result in bid proposal rejection.
The addendum emphasizes that all parts of the original contract documents not specifically modified remain in full force and effect. The reissued plan set reflects changes noted in Addendum #1, and the document was posted on Vendor Link (www.demandstar.com). The bidder is responsible for confirming receipt of all addenda prior to submitting a bid. No specific pricing details or funding sources are disclosed in this addendum, which primarily serves to update and clarify the original bid documents for the electrical service upgrade project at the DeLand Municipal Airport.
View the file
Other files for this state and local contract opportunity
| File | Type | Posted |
|---|---|---|
| RCA.pdf | ||
| B2501Tabulation.pdf | ||
| B2501ADD3.pdf | ||
| B2501ADD1Attachment.xlsx | XLSX spreadsheet | |
| B2501ADD1.pdf | ||
| Bid_Bond.docx | DOCX document | |
| B2501Plans.pdf | ||
| B2501Specs.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ADDENDUM NO. 2
T-HANGAR ELECTRICAL SERVICE UPGRADE
CITY OF DELAND
BID NO. ITB-B-25-01-0-2025/CM
NOVEMBER 12, 2024
The following items are clarifications, corrections or deletions to the contract documents. THIS
ADDENDUM TAKES PRECEDENCE OVER THE ORIGINAL PARTS OF THE
CONTRACT DOCUMENTS.
All the parts of the contract documents, not specifically modified by this or other addenda, remain in full force and effect.
Contractors shall thoroughly familiarize themselves with the contents of this addendum before submitting bid proposals. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO
INFORM THE SUBCONTRACTORS, SUPPLIERS, MANUFACTURERS AND OTHER
PARTIES PARTICIPATING IN THE WORK OF APPLICABLE REQUIREMENTS IN
THIS ADDENDUM.
Contractors shall acknowledge receipt of this addendum, identified by number and date, on their bid proposal. Failure to acknowledge receipt of addendum may be grounds for rejection of the bid proposal.
I. GENERAL
A. Plan revisions and a schedule of values for total fixture/outlet counts are issued with this
Addendum.
II. ATTACHMENTS
A. Reissued Plan Set that reflects the changes noted in Addendum #1.
END OF ADDENDUM
Disclaimer: This Addendum was posted on Vendor Link (www.demandstar.com). It is the sole responsibility of the bidder to confirm that all Addenda have been received prior to submitting bid and acknowledge such in the Bid Documents.
http://www.demandstar.com/
S
N
W
E
DELAND MUNICIPAL AIRPORT
BID DOCUMENTS
T-HANGAR ELECTRIC SERVICE UPGRADE
AVCON, INC.
ENGINEERS & PLANNERS
436 W. NEW YORK AVENUE - DELAND, FLORIDA 32720
OFFICE: (386) 626-1468
www.avconinc.com
PROJECT MAP
LOCATION MAP
VICINITY MAP
NTS
CITY AND AIRPORT REPRESENTATIVES
CITY AND AIRPORT STAFF
CITY COMMISSION
ITB-B-25-01-0-
2025/CM
JUNE 2024
XXXXXX-X-XX-XXFDOT FM NO.
CITY OF DELAND BID NO.
DATE
R E V I S I O N S
DESCRIPTIONDATENO.
ROBERT F. APGAR MAYOR
CHARLES PAIVA VICE - MAYOR
CHRIS CLOUDMAN COMMISSIONER
JESSICA DAVIS COMMISSIONER
KEVIN REID COMMISSIONER
RAY BAHRAMI, P.E. DEPUTY PUBLIC SERVICES
DIRECTOR / CITY ENGINEER
JOHN EIFF AIRPORT MANAGER
MINDY CONSIDINE ADMINISTRATIVE COORDINATOR
2024.187.02AVCON PROJECT NO.
X-XX-XXXX-XXX-XXXXFAA AIP NO.
AIRPORT LOCATION
DELAND
DELAND, FLORIDA
NORTH
FL-600
DELAND MUNICIPAL AIRPORT
TO INTERSTATE 4
NORTH
E. INT'L
SPEEDWAY BLVD
N. KEPPLER RD.
MARSH
RD.
92 PROJECT AREA
NORTH
10/30/241 BID ADDENDUM NO. 1
AutoCAD SHX Text 0+00
AutoCAD SHX Text 1+00
AutoCAD SHX Text 2+00
AutoCAD SHX Text 3+00
AutoCAD SHX Text 4+00
AutoCAD SHX Text 5+00
AutoCAD SHX Text 6+00
AutoCAD SHX Text 7+00
AutoCAD SHX Text 8+00
AutoCAD SHX Text 9+00
AutoCAD SHX Text 10+00
AutoCAD SHX Text 11+00
AutoCAD SHX Text 12+00
AutoCAD SHX Text 13+00
AutoCAD SHX Text 14+00
AutoCAD SHX Text 15+00
AutoCAD SHX Text 16+00
AutoCAD SHX Text 17+00
AutoCAD SHX Text 18+00
AutoCAD SHX Text 19+00
AutoCAD SHX Text 20+00
AutoCAD SHX Text 21+00
AutoCAD SHX Text 22+00
AutoCAD SHX Text 23+00
AutoCAD SHX Text 24+00
AutoCAD SHX Text 25+00
AutoCAD SHX Text 26+00
AutoCAD SHX Text 27+00
AutoCAD SHX Text 28+00
AutoCAD SHX Text 29+00
AutoCAD SHX Text 30+00
AutoCAD SHX Text 31+00
AutoCAD SHX Text 32+00
AutoCAD SHX Text 33+00
AutoCAD SHX Text 34+00
AutoCAD SHX Text 35+00
AutoCAD SHX Text 36+00
AutoCAD SHX Text 37+00
AutoCAD SHX Text 38+00
AutoCAD SHX Text 39+00
AutoCAD SHX Text 40+00
AutoCAD SHX Text 41+00
AutoCAD SHX Text 42+00
AutoCAD SHX Text 43+00
AutoCAD SHX Text 44+00
AutoCAD SHX Text 45+00
AutoCAD SHX Text 46+00
AutoCAD SHX Text 47+00
AutoCAD SHX Text 48+00
AutoCAD SHX Text 49+00
AutoCAD SHX Text 50+00
AutoCAD SHX Text 51+00
AutoCAD SHX Text 52+00
AutoCAD SHX Text 53+00
AutoCAD SHX Text 54+00
AutoCAD SHX Text 55+00
AutoCAD SHX Text 56+00
AutoCAD SHX Text 57+00
AutoCAD SHX Text 58+00
AutoCAD SHX Text 59+00
AutoCAD SHX Text 60+00
AutoCAD SHX Text
NCGS
AutoCAD SHX Text
KEY WEST
AutoCAD SHX Text
FT.PIERCE
AutoCAD SHX Text
DAYTONA BEACH
AutoCAD SHX Text
TITUSVILLE
AutoCAD SHX Text
PANAMA CITY
AutoCAD SHX Text
PENSACOLA
AutoCAD SHX Text
TALLAHASSEE
AutoCAD SHX Text
JACKSONVILLE
AutoCAD SHX Text
ORLANDO
AutoCAD SHX Text
TAMPA
AutoCAD SHX Text
ST.PETERSBURG
AutoCAD SHX Text
MIAMI
AutoCAD SHX Text
OKEECHOBEE
AutoCAD SHX Text
VENICE
ATTENTION:
THIS DOCUMENT CONTAINS PRIVILEGED AND PROPRIETARY
INFORMATION, ALL OF WHICH IS EXPRESSLY PROVIDED BY AVCON, INC.,
FOR USE BY THE INTENDED RECIPIENT, AND FOR A SPECIFIC PURPOSE.
WITHOUT THE EXPRESS WRITTEN CONSENT OF AVCON, INC. ANY
DISTRIBUTION, REPRODUCTION, OR OTHER USE OF THIS DOCUMENT, IN
WHOLE OR IN PART, IS STRICTLY PROHIBITED
DELAND MUNICIPAL
AIRPORT
DELAND, FLORIDA
T-HANGAR
ELECTRIC SERVICE
UPGRADE
2418702002G002
B
ID
D O
C U
M
EN
TS
CADD:
AVCON PROJECT NO.
FAA AIP NO.
FDOT FM NO. XXXXXX-X
X-XX-XXXX-XXX-XXXX
2024.187.02
DRAWING
DATE:
APPROVED BY:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
JUNE 2024
DJN
SCALE (FT): GRAPHIC
NO. DATE BY DESCRIPTION
REVISIONS:
AVCON, INC.
ENGINEERS & PLANNERS
5555 E. MICHIGAN ST., SUITE 200 - ORLANDO, FL 32822-2779
OFFICE: (407) 599-1122 - FAX: (407) 599-1133
CORPORATE CERTIFICATE OF AUTHORIZATION NUMBER: 5057
www.avconinc.com
PROFESSIONAL SEAL
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
This item has been digitally signed and sealed by:
GENERAL NOTES
AND SHEET INDEX
G002
DJN
PV
AMC
Sheet List Table
SHEET
NUMBER
SHEET
NAME SHEET TITLE
T-HANGAR
ELECTRICAL
UPGRADES
N
W
E
S
N
W
E
GRAPHIC SCALE (FT)
500250125
NORTH
ATTENTION:
THIS DOCUMENT CONTAINS PRIVILEGED AND PROPRIETARY
INFORMATION, ALL OF WHICH IS EXPRESSLY PROVIDED BY AVCON, INC.,
FOR USE BY THE INTENDED RECIPIENT, AND FOR A SPECIFIC PURPOSE.
WITHOUT THE EXPRESS WRITTEN CONSENT OF AVCON, INC. ANY
DISTRIBUTION, REPRODUCTION, OR OTHER USE OF THIS DOCUMENT, IN
WHOLE OR IN PART, IS STRICTLY PROHIBITED
DELAND MUNICIPAL
AIRPORT
DELAND, FLORIDA
T-HANGAR
ELECTRIC SERVICE
UPGRADE
2418702003G003
B
ID
D O
C U
M
EN
TS
CADD:
AVCON PROJECT NO.
FAA AIP NO.
FDOT FM NO. XXXXXX-X
X-XX-XXXX-XXX-XXXX
2024.187.02
DRAWING
DATE:
APPROVED BY:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
JUNE 2024
DJN
SCALE (FT): GRAPHIC
NO. DATE BY DESCRIPTION
REVISIONS:
AVCON, INC.
ENGINEERS & PLANNERS
5555 E. MICHIGAN ST., SUITE 200 - ORLANDO, FL 32822-2779
OFFICE: (407) 599-1122 - FAX: (407) 599-1133
CORPORATE CERTIFICATE OF AUTHORIZATION NUMBER: 5057
www.avconinc.com
PROFESSIONAL SEAL
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
This item has been digitally signed and sealed by:
SITE ACCESS PLAN
G003
DJN
PV
AMC
GENERAL ACCESS NOTES
LEGEND
10/30/2024 PV BID ADDENDUM NO. 11
AutoCAD SHX Text V:\2024\2024.187.02 DED T-Hangar Elec Upgrades\2024.187.02 - CADD\2418702003G003.dwg 11/6/2024 4:56 PM 11/6/2024 4:56 PM
AutoCAD SHX Text A. MAINTENANCE OF TRAFFIC AND SAFETY MAINTENANCE OF TRAFFIC AND SAFETY 1. CONTRACTOR SHALL FOLLOW THE APPROVED ROUTES AND UTILIZE THE ACCESS POINTS NOTED ABOVE. CONTRACTOR SHALL FOLLOW THE APPROVED ROUTES AND UTILIZE THE ACCESS POINTS NOTED ABOVE. 2. THE CONTRACTOR SHALL USE THE EXISTING ACCESS ROADWAYS SHOWN ON THIS SHEET AS THEIR HAUL ROUTES. CONTRACTOR TO COORDINATE MAINTENANCE THE CONTRACTOR SHALL USE THE EXISTING ACCESS ROADWAYS SHOWN ON THIS SHEET AS THEIR HAUL ROUTES. CONTRACTOR TO COORDINATE MAINTENANCE EXISTING ACCESS ROADWAYS SHOWN ON THIS SHEET AS THEIR HAUL ROUTES. CONTRACTOR TO COORDINATE MAINTENANCE EXISTING ACCESS ROADWAYS SHOWN ON THIS SHEET AS THEIR HAUL ROUTES. CONTRACTOR TO COORDINATE MAINTENANCE METHODS WITH THE RPR. THE CONTRACTOR SHALL PROVIDE THEIR OWN TRAFFIC CONTROL ON THE HAUL ROUTE. ALL OPERATIONS ON ROADS INSIDE THE SECURITY FENCE SHALL OBSERVE THE 20MPH SPEED LIMIT. 3. THE CONTRACTOR'S USE OF THE HAUL ROUTES AND ACCESS ROADS SHALL IN NO WAY HINDER THE SAFE AND UNOBSTRUCTED FLOW OF AIRCRAFT OR VEHICLE THE CONTRACTOR'S USE OF THE HAUL ROUTES AND ACCESS ROADS SHALL IN NO WAY HINDER THE SAFE AND UNOBSTRUCTED FLOW OF AIRCRAFT OR VEHICLE TRAFFIC. 4. LIMITS OF WORK SHALL BE VERIFIED BY THE CONTRACTOR AND RPR PRIOR TO BEGINNING WORK. THE CONTRACTOR'S VEHICLES AND EQUIPMENT SHALL BE LIMITS OF WORK SHALL BE VERIFIED BY THE CONTRACTOR AND RPR PRIOR TO BEGINNING WORK. THE CONTRACTOR'S VEHICLES AND EQUIPMENT SHALL BE RESTRICTED TO THE CONSTRUCTION AREA LIMITS, HAUL ROUTE, AND CONTRACTOR'S STAGING AREA ONLY. NO VEHICLES ARE PERMITTED ON THE ACTIVE AIRCRAFT OPERATIONS AREA (AOA) UNLESS ESCORTED OR UNDER RADIO CONTROL. B. STAGING AND STOCKPILING AREAS - GENERAL REQUIREMENTS STAGING AND STOCKPILING AREAS - GENERAL REQUIREMENTS MATERIAL AND PERSONNEL STAGING AREAS SHALL BE AS SHOWN ON THE PLANS OR AS APPROVED BY THE OWNER. MATERIALS STORED ON THE AIRPORT SHALL NOT CREATE ANY OBSTRUCTION TO AIR NAVIGATION NOR SHALL THEY INTERFERE WITH AIRCRAFT MOVEMENT OR OTHER AIRPORT OPERATIONS. STOCKPILED MATERIALS SHALL BE STORED IN A MANNER SO THEY ARE NOT A HAZARD TO PERSONNEL AND SHALL BE PROTECTED FROM BEING DISLODGED BY WINDS OR JET BLAST, AND SHALL HAVE A MAXIMUM HEIGHT OF 15 FEET. THE LOCATION OF THE CONTRACTOR'S STAGING AREAS ARE SHOWN IN THE DRAWINGS FOR REFERENCE ONLY. THE ACTUAL SIZE AND EXACT LOCATION WILL BE ESTABLISHED PRIOR TO CONSTRUCTION. THE CONTRACTOR IS INFORMED THAT THE LOCATION SHOWN IN THESE PLANS MAY BE COMPLETELY DIFFERENT WHEN ACTUAL CONSTRUCTION STARTS DEPENDING ON THE OPERATIONAL NEEDS AND CONSTRAINTS AT THE AIRPORT AT THE TIME. THE CONTRACTOR WILL HE CONTRACTOR WILL ALSO BE ALLOWED TO PROPOSE ALTERNATIVE OR ADDITIONAL STAGING AREAS AND ACCESS ROUTES, FOR APPROVAL BY THE OWNER AND THE RPR. ANY CHANGES IN . ANY CHANGES IN THE STAGING AREA LOCATIONS SHALL BE AT NO COST TO THE OWNER. THE FOLLOWING REQUIREMENTS WILL APPLY: 1. NO HAZARDOUS OR FLAMMABLE MATERIAL MAY BE STORED AT THE STAGING AREAS. NO HAZARDOUS OR FLAMMABLE MATERIAL MAY BE STORED AT THE STAGING AREAS. 2. THE OWNER MAY, AT ITS DISCRETION, DESIGNATE THAT STAGING AREAS FOR OTHER CONTRACTORS BE LOCATED IN THE VICINITY OF THIS PROJECT SITE. IF THIS THE OWNER MAY, AT ITS DISCRETION, DESIGNATE THAT STAGING AREAS FOR OTHER CONTRACTORS BE LOCATED IN THE VICINITY OF THIS PROJECT SITE. IF THIS OCCURS, THE CONTRACTOR SHALL COOPERATE TO ACCOMMODATE OTHER CONTRACTORS' WORK ACTIVITIES. 3. CONTRACTOR SHALL PROTECT HIS/HER EQUIPMENT AND MATERIALS WITHIN THE CONTRACTOR'S STAGING AREA FROM DISLODGING AND/OR BECOMING HAZARDS. CONTRACTOR SHALL PROTECT HIS/HER EQUIPMENT AND MATERIALS WITHIN THE CONTRACTOR'S STAGING AREA FROM DISLODGING AND/OR BECOMING HAZARDS.
AutoCAD SHX Text
CONTRACTOR'S ACCESS/HAUL ROUTE
AutoCAD SHX Text
APPROXIMATE PROJECT LIMITS
AutoCAD SHX Text
RUNWAY 12-30 (6,001' X 100')
AutoCAD SHX Text
RUNWAY 5-23 (4,301' X 75')
AutoCAD SHX Text
TAXIWAY B
AutoCAD SHX Text
TAXIWAY C
AutoCAD SHX Text
TAXIWAY D
AutoCAD SHX Text
TAXIWAY G
AutoCAD SHX Text
LEXINGTON AVE
AutoCAD SHX Text
ESSEX AVE
AutoCAD SHX Text
LANGLEY AVE
AutoCAD SHX Text
FLIGHT LINE BLVD
AutoCAD SHX Text
SKYDIVE DR
AutoCAD SHX Text
OLD NDB RD
AutoCAD SHX Text
MARSH RD
AutoCAD SHX Text
E INTERNATIONAL SPEEDWAY BLVD
AutoCAD SHX Text
TAXIWAY D
AutoCAD SHX Text
TAXIWAY A
AutoCAD SHX Text
FLIGHT LINE BLVD
AutoCAD SHX Text
TAXIWAY B
AutoCAD SHX Text
TAXIWAY A
AutoCAD SHX Text
TAXIWAY A
AutoCAD SHX Text
RANGER AVE
AutoCAD SHX Text
SARATOGA ST
AutoCAD SHX Text
EXISTING FENCELINE, (TYP.)
AutoCAD SHX Text
T-HANGAR
AutoCAD SHX Text
T-HANGAR
AutoCAD SHX Text
T-HANGAR
AutoCAD SHX Text
T-HANGAR
T-HANGAR
INFORMATION, ALL OF WHICH IS EXPRESSLY PROVIDED BY AVCON, INC.,
FOR USE BY THE INTENDED RECIPIENT, AND FOR A SPECIFIC PURPOSE.
WITHOUT THE EXPRESS WRITTEN CONSENT OF AVCON, INC. ANY
DISTRIBUTION, REPRODUCTION, OR OTHER USE OF THIS DOCUMENT, IN
WHOLE OR IN PART, IS STRICTLY PROHIBITED
DELAND MUNICIPAL
AIRPORT
DELAND, FLORIDA
T-HANGAR
ELECTRIC SERVICE
UPGRADE
2418702004G101
B
ID
D O
C U
M
EN
TS
CADD:
AVCON PROJECT NO.
FAA AIP NO.
FDOT FM NO. XXXXXX-X
X-XX-XXXX-XXX-XXXX
2024.187.02
DRAWING
DATE:
APPROVED BY:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
JUNE 2024
DJN
SCALE (FT): GRAPHIC
NO. DATE BY DESCRIPTION
REVISIONS:
AVCON, INC.
ENGINEERS & PLANNERS
5555 E. MICHIGAN ST., SUITE 200 - ORLANDO, FL 32822-2779
OFFICE: (407) 599-1122 - FAX: (407) 599-1133
CORPORATE CERTIFICATE OF AUTHORIZATION NUMBER: 5057
www.avconinc.com
PROFESSIONAL SEAL
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
This item has been digitally signed and sealed by:
CONSTRUCTION
SAFETY AND
PHASING PLAN
NOTES
G101
DJN
PV
AMC
T-HANGAR
ELECTRICAL
UPGRADES
INFORMATION, ALL OF WHICH IS EXPRESSLY PROVIDED BY AVCON, INC. &
JLC-SC ENGINEERS, FOR USE BY THE INTENDED RECIPIENT, AND FOR A
SPECIFIC PURPOSE. WITHOUT THE EXPRESS WRITTEN CONSENT OF
AVCON, INC. ANY DISTRIBUTION, REPRODUCTION, OR OTHER USE OF THIS
DOCUMENT, IN WHOLE OR IN PART, IS STRICTLY PROHIBITED
M :\P ro je ct S er ve r\P ro je ct s\
\J
LS
C
.0
.0
- A vc on
In c, D el an d
T H an ga r E le c Se rv ic e U pg ra de
D el an d, F L\
D ra w in gs \E le ct ric al
\E -0
EL
EC
TR
IC
AL
L
EG
EN
D .d w g
4/
/2
2:
P
M
DELAND MUNICIPAL
AIRPORT
DELAND, FLORIDA
T-HANGAR
ELECTRIC SERVICE
UPGRADE
PROFESSIONAL SEAL
CADD:
PROJECT # JLSC24.018.00
DRAWING
DATE:
APPROVED BY:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
MARCH 22, 2024
SCALE (US SVY FT): GRAPHIC
NO. DATE BY DESCRIPTION
REVISIONS:
AVCON, INC.
ENGINEERS & PLANNERS
5555 E. MICHIGAN ST., SUITE 200 - ORLANDO, FL 32822-2779
OFFICE: (407) 599-1122 - FAX: (407) 599-1133
CORPORATE CERTIFICATE OF AUTHORIZATION NUMBER: 5057
www.avconinc.com
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
This item has been digitally signed and sealed by:
JL
C&O
Joseph, Lawrence & Co
Consulting Engineers 317 riveredge blvd. suite 110 cocoa, Florida 32922 Tel: 321.972.4466 www.jlceng.com
CA No. 32770
Space Coast
E-001
ABBREVIATIONS
DESCRIPTIONABRV.
CH COUNTER HEIGHT
ELECTRIC WATER COOLEREWC
H.I.D.
COMPACT FLUORESCENT LAMPCFL
A
A/C
AC
AFF
AFG
AHU
AWG
C
CONC
COND
CU
DISC
ELEC
EM
EMS
EMT
EF
EX
FA
AMPERES
AIR CONDITIONING
ALTERNATING CURRENT
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMERICAN WIRE GAUGE
CONDUIT
CONCRETE
CONDUIT
COPPER
DISCONNECT
ELECTRICAL
EMERGENCY
ENERGY MANAGEMENT SYSTEM
ELECTRICAL METALLIC TUBING
EXHAUST FAN
EXISTING
FIRE ALARM
G
GFI
GND
J
KAIC
KVA
KW
NL
NEMA
NFPA
GROUND
GROUND FAULT INTERRUPTER
GROUND
O.C.
P
PNL
PVC
RM
RGS
SPEC
SS
TYP
UON
V
W
WP
FIRE ALARM ANNUNCIATOR PANELFAAP
ENCLOSED CIRCUIT BREAKERECB
I.G.
SPD
ETR
HIGH INTENSITY DISCHARGE
GRC
HVAC
LTG
MCM
MCU
MH
N
NA
NF
NEC
NIC
GALVANIZED RIGID CONDUIT
JUNCTION
KILOVOLT-AMPERES
KILOWATT
LIGHTING
THOUSANDS OF CIRCULAR MILS
MASTER CONTROL UNIT
METAL HALIDE
NEUTRAL
NOT APPLICABLE
NON-FUSED
NATIONAL ELECTRICAL CODE
NOT IN CONTRACT
NIGHT LIGHT
NATIONAL FIRE PROTECTION ASSOCIATION
ON CENTER
POLE
PANELBOARD
POLYVINYL CHLORIDE
ROOM
RIGID GALVANIZED STEEL
SPECIFICATION
STAINLESS STEEL
TYPICAL
UNLESS OTHERWISE NOTED
VOLTS
WIRE
WEATHERPROOF
MOTOR CIRCUIT PROTECTIONMCP
ISOLATED GROUND
SURGE PROTECTION DEVICE
O.F.C.I. OWNER FURNISHED CONTRACTOR INSTALLED
FIRE ALARM CONTROL PANELFACP
NATIONAL ELECTRIC MANUFACTURERS ASSOCIATION
HEATING, VENTILATING, AND AIR CONDITIONING
(THOUSAND) AMPERE INTERRUPTING CAPACITY
EXISTING TO REMAIN
-SACP SURGE ALARM CONTROL PANEL
MC MASTER CLOCK CONTROL PANEL-
PA PUBLIC ADDRESS CONTROL PANEL-
DESCRIPTIONSYMBOL
TELECOMMUNICATIONS
COMBINATION TELECOMMUNICATIONS/DATA WALL OUTLET BOX AND BLANK PLATE WITH MIN. 3/4"C. TO ACCESSIBLE
CEILING SPACE. COORDINATE OUTLET REQUIREMENTS WITH OWNER.
TELECOMMUNICATIONS WALL OUTLET BOX AND BLANK PLATE FOR WALL MOUNTED TELEPHONE WITH MIN. 3/4"C. TO
ACCESSIBLE CEILING SPACE. COORDINATE OUTLET REQUIREMENTS WITH OWNER.
DATA WALL OUTLET BOX AND BLANK PLATE WITH MIN. 3/4"C. TO ACCESSIBLE CEILING SPACE. COORDINATE OUTLET
REQUIREMENTS WITH OWNER.
FLUSH FLOOR OUTLET BOX WITH POWER DEVICE AND TELECOMMUNICATIONS OUTLET WITH MIN. 3/4"C. TO
ACCESSIBLE CEILING SPACE.
CEILING OUTLET BOX AND BLANK PLATE WITH MIN. 3/4"C. TO TTB FOR WIRELESS ACCESS POINT. COORDINATE
OUTLET REQUIREMENTS WITH OWNER.
COMBINATION TELECOMMUNICATIONS/TELEVISION WALL OUTLET BOX AND BLANK PLATE. COORDINATE OUTLET AND
CABLING REQUIREMENTS WITH OWNER.
3/4" PLYWOOD TELEPHONE TERMINAL BOARD, SIZE AS SHOWN ON PLANS.
TELEPHONE TERMINAL CABINET, SIZE AS NOTED ON PLAN.
TV
TTC
WAP
W
GENERAL DEMOLITION NOTES
DG
DF
DE
DD
DC
DB
DA
DH
ALL ELECTRICAL DEVICES INDICATED IN DARK LINETYPE ON DRAWING SHALL BE REMOVED OR RELOCATED UNLESS NOTED OTHERWISE. REROUTING/RELOCATION OF EXISTING ELECTRICAL SYSTEMS MAY BE REQUIRED AT NEW OPENINGS IN EXISTING CONSTRUCTION OR DUE TO INTERFERENCE WITH OTHER NEW WORK AS DESCRIBED IN THE
FOLLOWING NOTES.
DRAWINGS INDICATE SPECIFIC ITEMS TO BE REMOVED, REROUTED, AND/OR RELOCATED IN ORDER TO INDICATE GENERAL SCOPE. ADDITIONAL ITEMS NOT INDICATED BUT NECESSARY FOR PROJECT RENOVATIONS SHALL BE REMOVED, REROUTED, OR RELOCATED AS REQUIRED. ASSUME WITHIN THE BASE BID A NOMINAL AMOUNT OF BRANCH CIRCUITS, FIXTURES, DEVICES, AND SYSTEMS WIRING WITHIN WALLS OR OPENINGS BEING REMOVED OR RELOCATED AS
REQUIRED TO ACCOMMODATE THE NEW CONSTRUCTION.
FOR ITEMS INDICATED TO BE DEMOLISHED, REMOVE WIRING AND CONDUIT BACK TO THE SOURCE PANELBOARD UNLESS NOTED OTHERWISE. MAINTAIN CIRCUIT CONTINUITY TO REMAINING ITEMS ON CIRCUITS REQUIRED TO REMAIN.
RELOCATE ANY CIRCUITS TO REMAIN TO AVOID CONFLICT WITH NEW CONSTRUCTION AS REQUIRED. PROPERLY
TERMINATE ALL WIRING.
MAINTAIN CIRCUIT CONTINUITY TO ALL REMAINING ELECTRICAL SYSTEMS UNAFFECTED BY BUT PASSING THROUGH RENOVATED SPACES OR WHERE ONLY A PORTION OF A CIRCUIT IS REMOVED. ANY EXISTING ELECTRICAL DEVICES LEFT WITHOUT POWER DUE TO THIS RENOVATION SHALL BE RECONNECTED TO SAME SIZE CIRCUIT(S) AS PRESENTLY SERVED.
NO ELECTRICAL DEVICES SHALL BE LEFT WITHOUT POWER.
REFER TO ARCHITECTURAL DEMOLITION DRAWINGS AND NOTES FOR COORDINATION. PATCH AND REPAIR ALL SURFACES CONTAINING DEMOLITION. COORDINATE WITH ARCHITECTURAL DRAWINGS. MATERIALS AND FINISHES SHALL
MATCH EXISTING.
VISIT THE SITE TO DETERMINE THE EXACT EXTENT OF ELECTRICAL WORK REQUIRED TO COMPLETE THE PROJECT.
EXISTING CONDITIONS INDICATED ON THESE DRAWINGS ARE TAKEN FROM EXISTING BUILDING DOCUMENTS AND FIELD OBSERVATION. OTHER ELECTRICAL ITEMS MAY EXIST FOR WHICH THE ELECTRICAL CONTRACTOR IS RESPONSIBLE
WHICH MAY NOT BE SPECIFICALLY ADDRESSED IN THESE DRAWINGS.
PROPERLY DISPOSE OF ALL ITEMS BEING REMOVED AS PART OF THIS PROJECT. THE OWNER SHALL HAVE THE RIGHT TO
RETAIN ANY ITEMS BEING REMOVED. COORDINATE ITEMS TO BE RETAINED WITH OWNER.
CONDUCTORS IN RENOVATED AREA SHALL BE NEW. DO NOT REUSE EXISTING WIRING UNLESS NOTED OTHERWISE.
EXISTING CONDUIT IN THE RENOVATED AREA MAY BE REUSED IF IT COMPLIES WITH ALL REQUIREMENTS OF THE NEC AND SPECIFICATIONS, IF NEW DEVICE OR EQUIPMENT LOCATION COINCIDES WITH EXISTING LOCATION, AND IF PRACTICAL. CONDUIT NOT INTENDED TO BE REUSED SHALL BE REMOVED IF POSSIBLE (I.E., NOT EMBEDDED IN
CONCRETE FLOOR, ETC.).
DESCRIPTION
WIRING AND POWER
WALL OUTLET BOX AND SINGLE RECEPTACLE
WALL OUTLET BOX AND DUPLEX RECEPTACLE
TWO GANG WALL OUTLET BOX AND (2) DUPLEX RECEPTACLES
WALL OUTLET BOX AND DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER
WALL OUTLET BOX AND DUPLEX RECEPTACLE WITH TOP HALF SWITCHED
TWO GANG WALL OUTLET BOX AND (2) DUPLEX RECEPTACLE WITH TOP HALF SWITCHED
WALL OUTLET BOX AND DUPLEX RECEPTACLE CONNECTED TO EMERGENCY SYSTEM
CEILING OUTLET BOX AND SINGLE RECEPTACLE
CEILING OUTLET BOX AND DUPLEX RECEPTACLE
WALL OUTLET BOX AND GFCI DUPLEX RECEPTACLE
WALL OUTLET BOX AND GFCI DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER
WALL OUTLET BOX AND DUPLEX SAFETY RECEPTACLE
WALL OUTLET BOX AND DUPLEX TWIST-LOCK RECEPTACLE
WALL OUTLET BOX AND GFCI DUPLEX RECEPTACLE WITH WEATHERPROOF COVER
WALL OULTET BOX AND SPECIAL PURPOSE OUTLET AS NOTED ON PLANS
FLUSH FLOOR OUTLET BOX WITH DUPLEX RECEPTACLE
FLUSH FLOOR OUTLET BOX WITH (2) DUPLEX RECEPTACLES
FLUSH FLOOR OUTLET BOX WITH DUPLEX RECEPTACLE AND TELECOMMUNICATIONS OUTLET
FLUSH WALL JUNCTION BOX AND BLANK PLATE
JUNCTION BOX AND BLANK PLATE ABOVE CEILING
SURFACE MOUNTED JUNCTION BOX AND BLANK PLATE
SURFACE MOUNTED WEATHERPROOF JUNCTION BOX AND COVER
FLUSH GRADE FIBER COMPOSITE PULL BOX AS NOTED
MOTOR CONNECTION AS NOTED
FLUSH SHUNT-TRIP BUTTON, MOUNTED 80" TO TOP
CONTROL AND/OR POWER EQUIPMENT CONNECTION
TIME CLOCK
PHOTO CELL
DISCONNECT SWITCH, SIZE AS NOTED
120/208V BRANCH CIRCUIT PANELBOARD, SURFACE MOUNTED
120/208V BRANCH CIRCUIT PANELBOARD, FLUSH MOUNTED
277/480V BRANCH CIRCUIT PANELBOARD
TRANSFORMER
BRANCH CIRCUIT HOMERUN WITH PANEL NAME AND CIRCUIT NUMBER,
QUANTITY OF ARROWHEADS DENOTES QUANTITY OF BRANCH CIRCUITS
BRANCH CIRCUIT WIRING, PROVIDE QUANTITY OF CONDUCTORS REQUIRED
FOR CIRCUITING AND SWITCHING INDICATED ON PLANS
POWER LEG ONLY (NO SWITCH LEG BETWEEN ROOMS)
CONDUIT CAPPED OFF
CONDUIT CONTINUED
CONDUIT RUN UP
CONDUIT RUN DOWN
GROUND OR GROUND ROD AS NOTED
SYMBOL
NOTE: GENERAL NOTES, ABBREVIATIONS, AND SYMBOLS SHOWN
ON THIS ELECTRICAL LEGEND ARE FOR REFERENCE PURPOSES
ONLY. ALL OF THESE MAY NOT BE USED FOR THIS PROJECT.
LIGHTING
CEILING MOUNTED LIGHT FIXTURE, REFER TO LIGHT FIXTURE SCHEDULE
CEILING MOUNTED RECESSED DOWNLIGHT FIXTURE, REFER TO LIGHT FIXTURE SCHEDULE
CEILING MOUNTED RECESSED WALLWASH FIXTURE, REFER TO LIGHT FIXTURE SCHEDULE
CEILING MOUNTED "CLOSE TO CEILING" FIXTURE, REFER TO LIGHT FIXTURE SCHEDULE
PENDANT MOUNTED LIGHT FIXTURE, REFER TO LIGHT FIXTURE SCHEDULE
TRACK LIGHT FIXTURE WITH HEADS AS REQUIRED, REFER TO LIGHT FIXTURE SCHEDULE
WALL MOUNTED LIGHT FIXTURE, REFER TO LIGHT FIXTURE SCHEDULE
CEILING MOUNTED LIGHT FIXTURE WITH EMERGENCY BACKUP
CEILING MOUNTED RECESSED DOWNLIGHT FIXTURE WITH EMERGENCY BACKUP
WALL MOUNTED LIGHT FIXTURE WITH EMERGENCY BACKUP
WALL MOUNTED EMERGENCY BATTERY LIGHT FIXTURE, REFER TO LIGHT FIXTURE SCHEDULE
CEILING MOUNTED EMERGENCY BATTERY LIGHT FIXTURE, REFER TO LIGHT FIXTURE SCHEDULE
CEILING MOUNTED EXIT SIGN WITH EMERGENCY BACKUP, REFER TO LIGHT FIXTURE SCHEDULE
WALL MOUNTED EXIT SIGN WITH EMERGENCY BACKUP, REFER TO LIGHT FIXTURE SCHEDULE
COMBINATION EXIT SIGN AND EMERGENCY LIGHT FIXTURE WITH BATTERY BACKUP
WALL OUTLET BOX AND SINGLE POLE SWITCH ('a' INDICATES SWITCH LEG)
WALL OUTLET BOX AND THREE-WAY SWITCH
WALL OUTLET BOX AND FAN CONTROL SWITCH
WALL OUTLET BOX AND DIMMER SWITCH AS REQUIRED FOR LOAD SERVED
WALL OUTLET BOX WITH SINGLE POLE MANUAL MOTOR STARTER SWITCH
WALL OUTLET BOX AND DUAL TECHNOLOGY OCCUPANCY SENSOR
CEILING OUTLET BOX AND DUAL TECHNOLOGY OCCUPANCY SENSOROS
GENERAL NOTES
1. ALL WORK SHALL BE DONE IN ACCORDANCE THE FLORIDA BUILDING CODE (FBC-2023) 8TH EDITION, NFPA 70 (NEC-2020) AND NFPA 101 (LIFE SAFETY CODE-2021), AND THE REGULATIONS OF THE LOCAL UTILITY TELEPHONE, CABLE TELEVISION AND POWER UTILITY COMPANIES. OBTAIN AND PAY FOR ANY AND ALL REQUIRED PERMITS, INSPECTIONS, CERTIFICATES OF INSPECTIONS AND APPROVAL, AND THE LIKE, AND DELIVER SUCH CERTIFICATES TO THE ENGINEER.
2. CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND COORDINATE WITH ALL EQUIPMENT MANUFACTURER/INSTALLERS
PRIOR TO BIDDING.
3. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES, AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED
THIRD-PARTY TESTING AGENCY.
BUILDING:
4. INSTALLATION HEIGHT OF EQUIPMENT (TO CENTERLINE) ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE SHALL BE:
RECEPTACLE = 18"
CLOCK = 7'-6"
SWITCH = 48"
MODULAR JACK FOR WALL MOUNTED TELEPHONE = 48"
MODULAR TELEPHONE JACK = 18"
TELEVISION OUTLET = 84"
COMPUTER OUTLET = 18"
CALL SWITCH = 44"
REMOTE TEST STATION FOR DUCT DETECTOR = 52"
C = ABOVE COUNTER BACKSPLASH, COORDINATE WITH ARCHITECTURAL ELEVATIONS AND MILLWORK.
5. ALL CONDUIT AND WIRING SHALL BE CONCEALED IN WALLS OR ABOVE CEILINGS UNLESS NOTED OTHERWISE OR APPROVED BY THE ARCHITECT/ENGINEER. ALL DEVICE OUTLET BOXES SHALL BE RECESSED UNLESS NOTED OTHERWISE OR APPROVED BY THE ARCHITECT/ENGINEER. WHERE APPROVED OR NOTED SURFACE METAL RACEWAY AND DEVICE BOXES SHALL BE USED IN LIEU OF CONDUIT AND CONCEALED BOXES AT NO EXTRA COST TO THE OWNER.
6. ALL CONDUIT ROUTING SHOWN IS APPROXIMATE ONLY. CONTRACTOR SHALL FIELD VERIFY FINAL ROUTE WITH ALL OTHER
TRADES AND CONDITIONS IN FIELD PRIOR TO ROUGH-IN.
7. CONDUIT RUNS SHOWN ARE SCHEMATIC AND DO NOT INDICATE THE NECESSARY FITTINGS AND JUNCTION BOXES THAT
ARE INCLUDED IN THE SCOPE OF THE WORK.
8. CONTRACTOR SHALL PERMANENTLY IDENTIFY ALL WIRING WITH THE SOURCE AND CIRCUIT AT ALL ELECTRICAL EQUIPMENT, PULL AND JUNCTION BOXES AND ELECTRICAL TERMINATIONS PROVIDED OR ASSOCIATED WITH THIS
CONSTRUCTION.
9. COORDINATE EXACT LOCATION OF LIGHTING FIXTURES IN MECH. ROOMS/SPACES WITH DUCTWORK INSTALLER PRIOR TO ROUGH-IN. LOCATE BELOW DUCTWORK(8'-0" AFF MINIMUM) CENTERED IN ROOM AS MUCH AS POSSIBLE.
10. COORDINATE EXACT INSTALLATION REQUIREMENTS OF OUTLETS IN MILLWORK WITH ARCHITECTURAL DRAWINGS, APPROVED SHOP DRAWINGS AND MILLWORK INSTALLER PRIOR TO ROUGH-IN.
11. VERIFY EXACT LOCATION OF ALL MECHANICAL EQUIPMENT WITH MECHANICAL INSTALLER PRIOR TO ROUGH-IN.
12. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF ALL LIGHT FIXTURES.
13. PROVIDE NYLON PULLSTRINGS IN ALL EMPTY CONDUITS.
14. COORDINATE THE REQUIRED SIZE OF ALL CIRCUIT BREAKERS FEEDING EQUIPMENT, (I.E. MOTORS, HVAC, KITCHEN EQUIPMENT, SPECIAL PURPOSE OUTLETS, ELEVATORS, OWNER FURNISHED EQUIPMENT ETC. ) WITH APPROVED EQUIPMENT SHOP DRAWINGS AND OWNER REPRESENTATIVES PRIOR TO ORDERING PANELBOARDS. BREAKERS SHALL BE
SIZED PER THE NEC, THE EQUIPMENT NAME PLATE AND MANUFACTURERS RECOMMENDATIONS.
15. ALL DIMMED CIRCUITS SHALL BE PROVIDED WITH DEDICATED NEUTRALS FOR EACH DIMMER AND PHASE CONDUCTOR
THROUGHOUT THE ENTIRE CIRCUIT.
16. THE POWER COMPANY SHALL BE CONTACTED WITHIN 10 DAYS OF THE AWARD OF THE CONTRACT BY THE CONTRACTOR TO VERIFY THE ACTUAL AVAILABLE SHORT CIRCUIT FAULT CURRENT (AIC) AT THE TRANSFORMER SECONDARY BUSHINGS.
THE CONTRACTOR SHALL PROVIDE ELECTRICAL DISTRIBUTION AND UTILIZATION EQUIPMENT AND PANELBOARDS WHICH HAVE AIC/WITHSTAND RATINGS GREATER THAN THE AVAILABLE AIC AT EACH POINT IN THE ELECTRICAL SYSTEM.
17. VISIT THE EXISTING FACILITY AND CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDING AND SITE AFFECTED BY THIS WORK BEFORE SUBMITTING PROPOSALS, SO AS TO BECOME FAMILIAR WITH THE EXISTING CONDITIONS AND DIFFICULTIES THAT WILL AFFECT EXECUTION OF THE WORK. SUBMISSION OF A PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE AND LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE OF
DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED.
18. CONTRACTOR SHALL INCLUDE IN HIS BID THE TRANSPORT AND DISPOSAL OR RECYCLING OF ALL WASTE MATERIALS GENERATED BY THIS PROJECT IN ACCORDANCE WITH ALL RULES, REGULATIONS AND GUIDELINES APPLICABLE.
19. PANEL SCHEDULES INDICATE CIRCUIT DESIGNATIONS ONLY. CONTRACTOR TO PROVIDE MATERIALS AS REQUIRED WHEN NEUTRALS ARE SHARED TO COMPLY WITH NEC REQUIREMENTS. ALL SINGLE PHASE MULTIWIRE BRANCH CIRCUITS SHALL BE FED VIA A TWO POLE BREAKER OR TWO SINGLE POLE BREAKERS WITH AN IDENTIFIED HANDLE TIE. ALL THREE PHASE MULTIWIRE BRANCH CIRCUITS SHALL BE FED VIA A THREE POLE BREAKER OR THREE SINGLE POLE BREAKERS WITH AN
IDENTIFIED HANDLE TIE (PER NEC 210.4B).
20. PER NEC 110.22; PROVIDE PERMANENT LABELING FOR ALL SERIES RATED PANEL ENCLOSURES TO READ AS FOLLOWS:
CAUTION - SERIES COMBINATION SYSTEM RATED ______ AMPERES. IDENTIFIED REPLACEMENT COMPONENTS REQUIRED.
GROUNDING:
21. ALL METAL RACEWAYS, INCLUDING CONDUIT, WIRE TROUGHS, WIREMOLD, ETC., SHALL BE GROUNDED. ALL CONNECTIONS IN METAL RACEWAYS SHALL BE COMPLETED IN SUCH A MANNER AS TO MAINTAIN A CONTINUOUS PATH TO GROUND
THROUGHOUT THE ENTIRE LENGTH OF THE RACEWAY.
WIRING:
22. UNLESS NOTED OTHERWISE ON THE DRAWINGS OR ON THE EQUIPMENT WIRING SCHEDULE, EACH BRANCH CIRCUIT HOME RUN SHALL BE THREE (3) #12 AWG THHN/THWN (1 HOT, 1 NEUTRAL & 1 EQUIPMENT GROUND) IN 3/4" EMT CONDUIT.
PROTECT EACH CIRCUIT WITH A 20 AMPERE, 1-POLE OVERCURRENT DEVICE UNLESS NOTED OTHERWISE. COMBINED
NEUTRALS ARE NOT PERMITTED.
GENERAL:
23. WITHIN 30 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE THE ELECTRICAL CONTRACTOR SHALL PROVIDE TO THE BUILDING OWNER RECORD DRAWINGS OF THE ACTUAL INSTALLATION INCLUDING: 1. A SINGLE-LINE DIAGRAM OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM AND 2. FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR ALL
DISTRIBUTION.
24. THE ELECTRICAL CONTRACTOR SHALL PROVIDE THE BUILDING OWNER AN OPERATING MANUAL AND MAINTENANCE MANUAL AS REQUIRED BY THE FLORIDA BUILDING CODE. THE MANUALS SHALL INCLUDE, AT A MINIMUM, THE FOLLOWING:
1. SUBMITTAL DATE STATING EQUIPMENT RATING AND SELECTED OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE. 2. OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE. REQUIRED ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY IDENTIFIED. 3. NAMES AND ADDRESSES
OF AT LEAST ONE QUALIFIED SERVICE AGENCY.
25. THE ELECTRICAL CONTRACTOR SHALL PROVIDE THE REQUIRED FUNCTIONAL TESTING OF THE LIGHTING SYSTEM TO ENSURE THAT THE CONTROL HARDWARE AND SOFTWARE ARE CALIBRATED, ADJUSTED, PROGRAMMED AND IN PROPER WORKING CONDITION IN ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS AND MANUFACTURER'S INSTALLATION INSTRUCTIONS. WHERE REQUIRED BY THE CODE OFFICIAL, AN APPROVED PARTY INDEPENDENT FROM THE DESIGN OR CONSTRUCTION OF THE PROJECT SHALL BE RESPONSIBLE FOR THE FUNCTIONAL TESTING AND SHALL PROVIDE DOCUMENTATION TO THE CODE OFFICIAL CERTIFYING THAT THE INSTALLED LIGHTING CONTROLS MEET THE PROVISIONS OF FECC SECTION C405. WHERE OCCUPANT SENSORS, TIME SWITCHES, PROGRAMMABLE SCHEDULE CONTROLS, PHOTOSENSORS OR DAYLIGHTING CONTROLS ARE INSTALLED, THE FOLLOWING PROCEDURES SHALL BE PERFORMED: 1.
CONFIRM THAT THE PLACEMENT, SENSITIVITY AND TIME-OUT ADJUSTMENTS FOR THE OCCUPANT SENSORS YIELD
ACCEPTABLE PERFORMANCE.
EXISTING DEVICES TO REMAIN:
26. UNLESS OTHERWISE NOTED:
a. ON DEMOLITION AND NEW WORK PLANS - DEVICES AND EQUIPMENT SHOWN IN LIGHT LINETYPE ARE EXISTING TO
REMAIN.
b. ON DEMOLITION PLANS - DEVICES AND EQUIPMENT SHOWN IN DARK LINETYPE ARE EXISTING TO BE REMOVED
c. ON NEW WORK PLANS - DEVICES AND EQUIPMENT SHOWN IN DARK LINETYPE ARE NEW.
ELECTRICAL SYMBOLS
LEGEND AND GENERAL
NOTES
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text
WP
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text
WP
AutoCAD SHX Text J
AutoCAD SHX Text
PB
AutoCAD SHX Text M
AutoCAD SHX Text C
AutoCAD SHX Text
PC
AutoCAD SHX Text T
AutoCAD SHX Text A-3
AutoCAD SHX Text S
AutoCAD SHX Text a
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text F
AutoCAD SHX Text S
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text M
AutoCAD SHX Text S
OS
INFORMATION, ALL OF WHICH IS EXPRESSLY PROVIDED BY AVCON, INC. &
JLC-SC ENGINEERS, FOR USE BY THE INTENDED RECIPIENT, AND FOR A
SPECIFIC PURPOSE. WITHOUT THE EXPRESS WRITTEN CONSENT OF
AVCON, INC. ANY DISTRIBUTION, REPRODUCTION, OR OTHER USE OF THIS
DOCUMENT, IN WHOLE OR IN PART, IS STRICTLY PROHIBITED
M :\P ro je ct S er ve r\P ro je ct s\
\J
LS
C
.0
.0
- A vc on
In c, D el an d
T H an ga r E le c Se rv ic e U pg ra de
D el an d, F L\
D ra w in gs \E le ct ric al
\E -0
EL
EC
TR
IC
AL
S
PE
C
IF
IC
AT
IO
N S.
dw g
4/
/2
2:
P
M
DELAND MUNICIPAL
AIRPORT
DELAND, FLORIDA
T-HANGAR
ELECTRIC SERVICE
UPGRADE
PROFESSIONAL SEAL
CADD:
PROJECT # JLSC24.018.00
DRAWING
DATE:
APPROVED BY:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
MARCH 22, 2024
SCALE (US SVY FT): GRAPHIC
NO. DATE BY DESCRIPTION
REVISIONS:
AVCON, INC.
ENGINEERS & PLANNERS
5555 E. MICHIGAN ST., SUITE 200 - ORLANDO, FL 32822-2779
OFFICE: (407) 599-1122 - FAX: (407) 599-1133
CORPORATE CERTIFICATE OF AUTHORIZATION NUMBER: 5057
www.avconinc.com
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
This item has been digitally signed and sealed by:
JL
C&O
Joseph, Lawrence & Co
Consulting Engineers 317 riveredge blvd. suite 110 cocoa, Florida 32922 Tel: 321.972.4466 www.jlceng.com
CA No. 32770
Space Coast
ELECTRICAL SPECIFICATIONS
I. GENERAL REQUIREMENTS:
A. DO ALL WORK IN COMPLIANCE WITH THE LATEST ADOPTED EDITION OF THE FLORIDA BUILDING
CODE (FBC-2023), NFPA 70 (NEC-2020) AND NFPA 101 (LIFE SAFETY CODE-2021),
AND THE REGULATIONS OF THE LOCAL UTILITY TELEPHONE, CABLE TELEVISION AND POWER UTILITY
COMPANIES. OBTAIN AND PAY FOR ANY AND ALL REQUIRED PERMITS, INSPECTIONS,
CERTIFICATES OF INSPECTIONS AND APPROVAL, AND THE LIKE, AND DELIVER SUCH CERTIFICATES
TO THE ENGINEER.
B. THE CONTRACTOR SHALL FURNISH, PERFORM, OR OTHERWISE PROVIDE ALL LABOR (INCLUDING, BUT NOT
LIMITED TO, ALL PLANNING, PURCHASING, PAINTING, TRANSPORTING, RIGGING, HOISTING,
STORING, INSTALLING, TESTING, CHASING, CHANNELING, CUTTING, TRENCHING, EXCAVATING AND BACKFILLING), COORDINATION, FIELD VERIFICATION, EQUIPMENT INSTALLATION, SUPPORT, AND SAFETY, SUPPLIES, AND MATERIALS NECESSARY FOR THE CORRECT INSTALLATION OF COMPLETE AND FUNCTIONAL ELECTRICAL SYSTEMS (AS DESCRIBED OR IMPLIED BY THESE SPECIFICATIONS
AND THE APPLICABLE DRAWINGS).
C. ALL DRAWINGS AND SPECIFICATIONS ON THE PROJECT ARE COMPLEMENTARY, EACH TO ALL OTHER
SETS, AND THEY SHALL BE USED IN COMBINATION FOR THE EXECUTION OF THIS WORK.
DIVISION 16 WORK SHOWN ON ANY ONE SET OF DRAWINGS, INCLUDING ALL ARCHITECTURAL
DRAWINGS, MECHANICAL, PLUMBING AND FIRE PROTECTION DRAWINGS FOR GENERAL WORK AND
EQUIPMENT, AND DIVISION 16 WORK CALLED FOR UNDER ANY SECTION OF THE PROJECT
SPECIFICATIONS, SHALL BE CONSIDERED AS INCLUDED IN THIS WORK UNLESS SPECIFICALLY
EXCLUDED BY INCLUSION IN SOME OTHER BRANCH OF THE WORK. THIS SHALL INCLUDE
ROUGHING-IN FOR CONNECTIONS AND EQUIPMENT AS CALLED FOR OR INFERRED. THE
CONTRACTOR SHALL CHECK ALL DRAWINGS AND SPECIFICATIONS FOR THE PROJECT AND SHALL BE
RESPONSIBLE FOR THE INSTALLATION OF ALL DIVISION 16 WORK.
D. THE CONTRACTOR SHALL CAREFULLY CHECK THE DRAWINGS AND SPECIFICATIONS OF ALL OTHER
TRADES AND DIVISIONS BEFORE INSTALLING ANY OF HIS WORK. HE SHALL IN ALL CASES
CONSIDER THE WORK OF ALL OTHER TRADES, AND SHALL COORDINATE HIS WORK WITH THEM SO THAT THE BEST ARRANGEMENTS OF ALL EQUIPMENT, PIPING, CONDUIT, DUCTS, ROUGH-IN, ETC., CAN BE OBTAINED.
E. LOCATIONS DESIGNATED FOR OUTLETS, SWITCHES, DEVICES, EQUIPMENT, ETC., ARE
APPROXIMATE AND FINAL LOCATIONS SHALL BE VERIFIED IN THE FIELD. CONTRACTOR SHALL
LOCATE ALL DEVICES UP TO 5 FEET IN ANY DIRECTION AS DIRECTED BY OWNER AND PER CODE.
WHERE INSTRUCTIONS OR NOTES ARE INSUFFICIENT TO CONVEY THE INTENT OF THE DESIGN,
CONSULT THE OWNER PRIOR TO BIDDING AND INSTALLATION.
F. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING AND COORDINATING THE LOCATIONS OF DEVICES TO BE USED AND COORDINATING THE FINAL LOCATIONS OF ELECTRICAL EQUIPMENT WITH MILLWORK, SINKS, BENCHES, COUNTERS AND SHELVING PRIOR TO BIDDING AND INSTALLATION.
ALL DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER.
G. DIVISION 16 CONTRACTOR SHALL HAVE HAD EXPERIENCE OF AT LEAST THE SAME SIZE AND SCOPE AS THIS PROJECT, ON AT LEAST TWO OTHER PROJECTS WITHIN THE LAST FIVE YEARS IN
ORDER TO BE QUALIFIED TO BID THIS PROJECT.
H. CONTRACTOR SHALL AND DOES HEREBY WARRANT ALL MATERIALS AND EQUIPMENT FURNISHED UNDER THIS SECTION OF THE SPECIFICATIONS TO BE FREE FROM DEFECTS AND TO FUNCTION OR OPERATE SATISFACTORILY FOR ONE YEAR AFTER FINAL ACCEPTANCE OF THE WORK, AND THAT ANY
ITEMS NOT MEETING THIS REQUIREMENT WILL BE MADE GOOD BY HIM WITHOUT COST TO
OWNER, PROVIDED SUCH DEFECTS OR FAILURES ARE NOT DUE TO ABUSE, NEGLECT, OR LACK OF
REASONABLE AND ORDINARY MAINTENANCE.
I. ALL WORK SHALL BE EXECUTED IN A WORKMANSHIP MANNER DISPLAYING A NEAT
MECHANICAL APPEARANCE UPON COMPLETION.
J. BALANCE TOTAL PHASE LOADS IN EACH ELECTRICAL PANEL TO A VALUE WITHIN 10% OF EACH OTHER.
K. THE CONTRACTOR SHALL PROVIDE ADEQUATE PROTECTION, WHEREVER WORK IS TO BE
PERFORMED IN FINISHED/OCCUPIED SPACES, TO PREVENT DAMAGE TO ADJACENT AREAS,
EQUIPMENT, OR FURNISHINGS; TO PREVENT ACCIDENTAL INJURY TO BUILDING OCCUPANTS AND THE PUBLIC; TO PREVENT THE SPREADING OF DUST, DIRT, DEBRIS, AND MOISTURE FROM THE
AREA WHERE WORK IS BEING PERFORMED; AND TO PREVENT DUST, DIRT, DEBRIS, AND
MOISTURE FROM GETTING ON OR IN THE BUILDING OCCUPANT'S FURNISHINGS OR EQUIPMENT.
L. THE CONTRACTOR SHALL REPAIR, AT NO COST TO THE OWNER, ANY DAMAGE DONE BY HIMSELF
OR HIS EMPLOYEES. HE SHALL ALSO BE RESPONSIBLE FOR ALL CUTTING AND PATCHING
REQUIRED TO PROPERLY INSTALL HIS WORK. THIS SHALL ALSO INCLUDE THE PATCHING OF EXISTING ROADWAYS (PAVED OR IMPROVED), PARKING AREAS, SIDEWALKS, WALLS, STAIRS, MECHANICAL WORK, CURBS, GUTTERS, ETC., CUT TO INSTALL WORK PROVIDED BY THE CONTRACTOR. PATCH
WORK SHALL COMPLY WITH THE APPLICABLE SECTIONS OF THESE SPECIFICATIONS AND SHALL
MATCH THE EXISTING FINISHES.
M. UPON COMPLETION OF WORK, THE ENTIRE WIRING SYSTEM SHALL BE TESTED, AND SHALL BE SHOWN TO BE IN PROPER WORKING CONDITION IN ACCORDANCE WITH INTENT OF SPECIFICATIONS AND DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO HAVE ALL SYSTEMS
READY FOR OPERATION AND TO HAVE AN ELECTRICIAN AVAILABLE TO OPERATE SAME IN
ACCORDANCE WITH AND UNDER THE SUPERVISION OF THE INSPECTION REPRESENTATIVE OF THE ENGINEER. THE CONTRACTOR SHALL BE AVAILABLE TO ASSIST IN REMOVAL OF PANEL FRONTS, ETC., TO PERMIT INSPECTION AS REQUIRED.
N. IN ACCORDANCE WITH DIVISION 1 AND THE CONDITIONS OF THE CONTRACT, THE CONTRACTOR SHALL PROVIDE AND KEEP UP TO DATE A COMPLETE RECORD SET OF CONSTRUCTION "AS-BUILTS"
BLUELINE PRINTS WHICH SHALL BE CORRECTED DAILY, AND SHALL SHOW EVERY CHANGE FROM
THE ORIGINAL CONTRACT DRAWINGS, INCLUDING ADDENDA AND CHANGE ORDERS IN
ACCORDANCE WITH GENERAL REQUIREMENTS AND SPECIAL CONDITIONS. THIS SET OF
PRINTS SHALL BE KEPT ON THE JOB SITE, AND SHALL BE USED ONLY AS A RECORD SET. THIS SHALL NOT BE CONSTRUED AS AUTHORIZATION FOR THE CONTRACTORS TO MAKE CHANGES IN THE
LAYOUT WITHOUT DEFINITE INSTRUCTION IN EACH CASE.
II. ELECTRICAL SCOPE:
A. FURNISHING AND INSTALLATION OF POWER SYSTEMS, AND AUXILIARY SYSTEMS AS SHOWN
OR HEREIN SPECIFIED.
B. CONNECTION OF ALL EQUIPMENT REQUIRING ELECTRICAL CONNECTION, MENTIONED IN THIS
DIVISION OR SHOWN ON DRAWINGS, WHETHER FURNISHED BY DIVISION 16 OR UNDER
OTHER DIVISIONS, OR FURNISHED BY OWNER.
C. FURNISHING AND INSTALLATION OF OUTLET BOXES, CONDUIT RACEWAYS, FOR A TELEPHONE AND DATA RACEWAY DISTRIBUTION SYSTEM. (TELEPHONE AND DATA HARDWARE, AS WELL AS WIRING AND SOFTWARE
IS NOT INCLUDED.)
D. THE CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR CONTACTING THE OFFICES OF ALL LOCAL AND/OR STATE AUTHORITIES HAVING JURISDICTION OVER THIS PROJECT IN ORDER TO SCHEDULE ALL REQUIRED INSPECTIONS AND OBTAIN ALL NECESSARY PERMITS, ETC. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT/ENGINEER OF ALL SCHEDULED INSPECTIONS AT LEAST TWO WEEKS IN ADVANCE OF THE
SCHEDULED DATE.
E. THE CONTRACTOR SHALL REPLACE ANY DEFECTIVE MATERIALS, EQUIPMENT, OR WORKMANSHIP
WITHOUT COST TO THE OWNER WITHIN THE STIPULATED GUARANTEED PERIOD.
F. IT SHALL BE THE RESPONSIBILITY OF THE DIVISION 16 CONTRACTOR TO HAVE ALL SYSTEMS READY FOR OPERATION AND TO HAVE AN ELECTRICIAN AVAILABLE FOR ALL INSPECTIONS. THE CONTRACTOR SHALL PROVIDE PERSONNEL TO ASSIST IN REMOVAL OF PANEL FRONTS, ETC. TO PERMIT
INSPECTION AS REQUIRED.
G. SUBMIT TO THE ARCHITECT/ENGINEER PROMPTLY AFTER AWARD OF CONTRACT AND PRIOR TO
PURCHASING, SIX COPIES OF MANUFACTURER'S SHOP DRAWINGS IN ACCORDANCE WITH
DIVISION 1, SECTION 01300 - SUBMITTALS FOR THE FOLLOWING ITEMS. ALL SHOP DRAWINGS OF A SPECIFIC
ITEM OR SYSTEM SHALL BE MADE IN ONE SUBMITTAL AND WITHIN TEN DAYS AFTER AWARD OF CONTRACT.
1. PANELBOARDS 4. DISCONNECT SWITCHES
2. SUPPORTS 5. CONDUIT
3. WIRING DEVICES 6. WIRE
H. COMPLETED WIRING SYSTEMS SHALL BE FREE FROM SHORT CIRCUITS AND AFTER COMPLETION, PERFORM TESTS FOR INSULATION RESISTANCE IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE. ALL WIRING SYSTEMS SHALL BE COMPLETELY AND TOTALLY "SAFED"
DURING CONSTRUCTION. ONLY QUALIFIED PERSONNEL SHALL HANDLE ELECTRICAL SYSTEMS.
I. BEFORE ROUGH-IN OF CIRCUITRY OR CONNECTING TO EQUIPMENT, FURNISHED UNDER THIS DIVISION, ANY OTHER DIVISION, OR BY THE OWNER, THE CONTRACTOR SHALL VERIFY THE ELECTRICAL
CHARACTERISTICS AND REQUIREMENTS OF THE EQUIPMENT BEING FURNISHED AND FOR THAT SPECIFIED
AND SHOWN ON THE DRAWINGS AND PROVIDE FOR PROPER ROUGH-IN AND CONNECTION.
J. THE ELECTRICAL CIRCUITS, COMPONENTS, AND CONTROLS FOR ALL EQUIPMENT ARE SELECTED AND SIZED, BASED ON THE EQUIPMENT SPECIFIED. IF SUBSTITUTIONS AND/OR EQUIVALENT EQUIPMENT ARE FURNISHED, IT SHALL BE THE RESPONSIBILITY OF ALL PARTIES CONCERNED, INVOLVED IN, AND FURNISHING
THE SUBSTITUTE AND/OR EQUIVALENT EQUIPMENT TO VERIFY AND COMPARE THE ELECTRICAL
CHARACTERISTICS AND REQUIREMENTS OF THAT FURNISHED TO THAT SPECIFIED AND/OR SHOWN. IF GREATER CAPACITY OR MORE MATERIALS OR LABOR IS REQUIRED FOR THE ROUGH-IN, CIRCUITRY OR CONNECTIONS THAN FOR THE ITEM SPECIFIED AND PROVIDED FOR, THEN IT SHALL BE THE RESPONSIBILITY OF THE PARTIES INVOLVED IN PROVIDING THE SUBSTITUTE AND/OR EQUIVALENT ITEMS OF EQUIPMENT TO PROVIDE ALL COMPENSATION FOR ADDITIONAL CHARGES MADE FOR THE PROPER ROUGH-IN, CIRCUITRY AND CONNECTIONS FOR THE EQUIPMENT FURNISHED. NO ADDITIONAL CHARGES ABOVE THE BASE BID
SHALL BE ALLOWED FOR SUCH REVISIONS.
K. EXCAVATION FOR UNDERGROUND ELECTRICAL STRUCTURES: CONFORM TO ELEVATIONS AND
DIMENSIONS SHOWN WITHIN A TOLERANCE OF PLUS OR MINUS 0.10'; PLUS A SUFFICIENT
DISTANCE TO PERMIT PLACING AND REMOVAL OF CONCRETE FORMWORK, INSTALLATION OF
SERVICES, OTHER CONSTRUCTION, AND FOR INSPECTION.
L. TRENCHING: EXCAVATE TRENCHES FOR ELECTRICAL INSTALLATIONS AS FOLLOWS:
1. EXCAVATE TRENCHES TO THE UNIFORM WIDTH, SUFFICIENTLY WIDE TO PROVIDE AMPLE WORKING ROOM AND A MINIMUM OF 6" TO 9" CLEARANCE ON BOTH SIDES OF RACEWAYS AND EQUIPMENT.
2. EXCAVATE TRENCHES TO DEPTH INDICATED OR REQUIRED.
3. LIMIT THE LENGTH OF OPEN TRENCH TO THAT IN WHICH INSTALLATIONS CAN BE MADE AND THE
TRENCH BACKFILLED WITHIN THE SAME DAY.
4. WHERE ROCK IS ENCOUNTERED, CARRY EXCAVATION BELOW REQUIRED ELEVATION AND BACKFILL
WITH A LAYER OF CRUSHED STONE OR GRAVEL PRIOR TO INSTALLATION OF RACEWAYS AND
EQUIPMENT. PROVIDE A MINIMUM OF 6" OF STONE OR GRAVEL CUSHION BETWEEN ROCK BEARING
SURFACE AND ELECTRICAL INSTALLATIONS.
M. THE CONTRACTOR SHALL PROVIDE ALL INSERTS FOR THE SUPPORT OF DIVISION 16
EQUIPMENT TO BE PLACED IN CONCRETE OR THROUGH CONCRETE SLABS AS CONSTRUCTION
PROGRESSES. HE SHALL PROVIDE ALL MISCELLANEOUS HANGING AND SUPPORTING HARDWARE. ALL ELECTRICAL WORK IS TO BE CONCEALED IN OR BUILT INTO GENERAL CONSTRUCTION SHALL BE PLACED AS CONSTRUCTION PROGRESSES. FAILURE OF THE CONTRACTOR TO COORDINATE WORK WITH OTHER TRADES AND THE PROJECT CONSTRUCTION PROGRESS SHALL MAKE HIM RESPONSIBLE FOR ALL COST OF CUTTING AND PATCHING, AS REQUIRED TO INSTALL WORK. NO STRUCTURAL MEMBER, MASONRY CONSTRUCTION OR
FINISHED WORK SHALL BE CUT OR ALTERED WITHOUT PRIOR WRITTEN APPROVAL BY THE
ARCHITECT/ENGINEER. CONTRACTOR SHALL FIRE RATE ALL PENETRATIONS THROUGH ALL FIRE RATED
SLABS OR WALLS PER THE INTENDED RATING.
N. THE CONTRACTOR SHALL SUPPLY AND SET INTO PLACE ALL WALL SLEEVES FOR CONDUITS
AND CEILING INSERTS FOR HANGERS IN AREAS OF NEW CONSTRUCTION AS BUILDING CONSTRUCTION
PROGRESSES. INSTALL EQUIPMENT NOTED TO BE CONCEALED IN WALLS BEFORE WALLS ARE
CONSTRUCTED IN ORDER THAT WALLS MAY BE CONSTRUCTED AROUND CONDUITS, ENCLOSURES, ETC.
O. METALLIC MATERIALS SHALL BE PROTECTED AGAINST CORROSION. EQUIPMENT ENCLOSURES SHALL BE GIVEN RUST-INHIBITING TREATMENT AND STANDARD FINISH BY MANUFACTURER. ALUMINUM SHALL NOT BE USED ON CONTACT WITH EARTH, AND, WHERE CONNECTED TO DISSIMILAR METAL, SHALL BE PROTECTED BY SUITABLE FITTINGS AND TREATMENT. ALL FERROUS METALS SUCH AS ANCHORS, BOLTS, BRACES, BOXES, BODIES, CLAMPS, FITTINGS, GUARDS, NUTS, PINS, RODS, SHIMS, THIMBLES, WASHERS, AND MISCELLANEOUS PARTS, NOT OF STAINLESS STEEL OR NONFERROUS MATERIALS, SHALL BE HOT-DIPPED
GALVANIZED.
P. ALL CONDUITS STUBBED OUT FOR FUTURE USE SHALL HAVE A PULL WIRE INSTALLED, A PLASTIC CAP
INSTALLED AND BE IDENTIFIED AS TO THE CONDUIT ORIGIN.
Q. THE RESPONSIBILITY FOR ANY CUTTING OF CONSTRUCTION WHICH IS REQUIRED FOR THE
INSTALLATION OF DIVISION 16 WORK, SHALL BE BY THE CONTRACTOR. THE CONTRACTOR SHALL COORDINATE WITH ALL OTHER TRADES AND THE OWNER BEFORE ANY CUTTING AND OBTAIN APPROVAL FROM THE ARCHITECT/ENGINEER PRIOR TO ANY CUTTING. ALL PATCHING AND FINISHING SHALL BE BY THE
CONTRACTOR.
R. WHERE OPENINGS OR HOLES ARE CUT IN CONSTRUCTION AND THE CUTTING BREAKS ELECTRICAL CIRCUITRY OR CONTROL CIRCUITRY CONDUIT AND WIRING, THEN IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO REROUTE THE CIRCUITRY CONDUIT AND REWIRING AND TO COMPLETE THE CIRCUITRY AS REQUIRED AND AS APPROVED BY THE ARCHITECT/ENGINEER. TEMPORARY COMPLETION SHALL BE PROVIDED WHERE NECESSARY BEFORE THE PERMANENT REROUTING AND COMPLETION WORK IS FINISHED.
S. ANY PENETRATIONS OF FIRE OR SMOKE RATED ASSEMBLIES MADE BY THIS CONTRACTOR IN VERTICAL OR HORIZONTAL CONSTRUCTION SHALL BE SEALED AND PROTECTED BY THIS CONTRACTOR IN ORDER TO MAINTAIN THE ESTABLISHED FIRE RATING WITH METHODS AS APPROVED BY THE AUTHORITY HAVING
JURISDICTION.
III. IDENTIFICATION:
A. IDENTIFICATION NAMEPLATES SHALL BE LAMINATED PLASTIC, SECURED TO EQUIPMENT WITH TWO
SCREWS.
B. EACH PANELBOARD AND SWITCHBOARD SHALL BE EQUIPPED WITH A PERMANENT PLASTIC NAMEPLATE
WITH 1/2" MINIMUM LETTERS, SECURELY FASTENED TO THE DEVICE.
C. EACH INDIVIDUALLY MOUNTED CIRCUIT BREAKER, SWITCH, TRANSFER SWITCH, MOTOR STARTER, LIGHTING CONTACTOR, TRANSFORMER AND/OR ANY OTHER CONTROL OR PROTECTIVE DEVICE INCLUDING EQUIPMENT DISCONNECT SWITCHES SHALL BE EQUIPPED WITH A PERMANENT PLASTIC NAMEPLATE WITH
1/2" MINIMUM LETTERS.
D. PANELBOARDS SHALL HAVE TYPEWRITTEN DIRECTORIES. ALL CIRCUITS TO BE IDENTIFIED BY DEVICES SERVED AND ROOM NUMBERS (I.E., LIGHTING ROOM 216). HANDWRITTEN DIRECTORIES WILL NOT BE
ALLOWED.
E. EACH JUNCTION BOX CABINET OR WIREWAY LARGER THAN 6" X 6" SHALL BE EQUIPPED WITH A
PLASTIC NAMEPLATE WITH 1/2" MINIMUM LETTERS INDICATING THE SYSTEM ENCLOSED.
F. ALL SYSTEMS JUNCTION BOXES AND CONDUIT SHALL BE COLOR CODED INSIDE AND OUTSIDE OF THE
BOX PRIOR TO THE INSTALLATION OF CONDUCTORS PER THE FOLLOWING:
1. CCTV SYSTEM: GREEN
2. TELEPHONE DATA SYSTEM: BLUE
3. FIRE ALARM SYSTEM: RED
G. ENTIRE BOX INSIDE AND OUT, INCLUDING COVER, SHALL BE PAINTED PRIOR TO INSTALLING
CONDUCTORS.
IV. WIRING DEVICES:
A. SWITCHES AND RECEPTACLES IN LOBBIES, CORRIDORS OR COMMERCIAL SPACES, UNFINISHED AND MECHANICAL SPACES SHALL BE 20 AMP COMMERCIAL GRADE 125 VAC. GRAY IN COLOR WITH STAINLESS
STEEL COVERPLATES.
B. WEATHERPROOF RECEPTACLES SHALL BE GFCI TYPES WITH GASKETED STAINLESS STEEL KEY LOCKABLE FLIP COVER TYPE COVERPLATES. SURGE SUPPRESSION TYPE OUTLETS IN MDFS AND IDFS SHALL
BE HUBBELL #83625 (BLUE) OR EQUAL.
C. RECEPTACLES PROVIDED FOR ATTACHMENT OF CORD AND PLUG EQUIPMENT SHALL BE HEAVY DUTY, SPECIFICATION GRADE, NON-INTERCHANGEABLE, FLUSH MOUNTED TYPES OF THE PROPER NEMA
CONFIGURATION TO SERVE THE EQUIPMENT. NEMA CONFIGURATIONS SHALL BE VERIFIED PRIOR TO INSTALLATION OF CIRCUIT CONDUCTORS. CONTRACTOR TO PROVIDE ALL CONNECTION, WIRING, PIGTAILS
FOR DISHWASHERS, COOKING RANGES, OVENS AND GARBAGE DISPOSALS.
D. ALL DEVICES SHALL HAVE PROPER PLATES, CARPET FLANGES, TRIMS, RINGS, ESCUTCHEONS, ETC., AS MANUFACTURED BY SAME MANUFACTURER AS DEVICES. ANY TELEPHONE OR OTHER OUTLET WHICH IS NOT EQUIPPED WITH A PLATE FURNISHED BY OTHERS SHALL HAVE ONE PROVIDED BY THIS CONTRACTOR.
DEVICE PLATES SHALL BE COLOR AND TYPE AS SHOWN BELOW.
1. FINISHED SPACES DECORA LINE:
a. IVORY DEVICES
b. IVORY NYLON PLATES
2. UNFINISHED OR INDUSTRIAL OR COMMERCIAL TYPE SPACES:
a. GRAY DEVICES
b. STAINLESS STEEL OR STAMPED GALVANIZED STEEL ON SURFACE MOUNTED BOXES
c. STAINLESS STEEL PLATES ON FLUSH MOUNTED BOXES
E. MOUNTING HEIGHTS ARE APPROXIMATE. THE EXACT LOCATIONS AND MOUNTING HEIGHTS SHALL BE DETERMINED ON THE JOB AND IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE WITH ALL TRADES TO INSURE CORRECT INSTALLATION, I.E., OVER COUNTERS IN OR ABOVE BACK-SPLASHES, IN BLOCK WALLS, TILE, AND OTHER SPECIFIC CONSTRUCTION FEATURES. LOCATION OF OUTLETS MOUNTED IN BUILT-INS, MILLWORK, AND CABINETRY SHALL BE VERIFIED. OUTLETS MOUNTED IN KICK OR TOE SPACES SHALL BE MOUNTED HORIZONTALLY. OUTLET BOXES SHALL BE MOUNTED TO PREVENT DEVICE PLATE FROM OVERLAPPING BACKSPLASH, TRIM, TILE, ETC. LOCATE SO DEVICE PLATE WILL LAY FLAT AGAINST SURFACE
COMPLETELY AROUND THE PERIMETER OF PLATE.
F. OUTLETS, OTHER THAN THOSE COORDINATED WITH COUNTER TOPS, SHELVES, AND CABINETS, SHALL BE LOCATED WITH THE CENTER LINE OF OUTLET BOXES THE FOLLOWING DISTANCE ABOVE THE FINISHED
FLOOR, UNLESS OTHERWISE INDICATED:
1. RECEPTACLES, GENERAL: 1'-6" AFF
2. TELEPHONE OUTLETS: 1'-6" AFF
3. SWITCHES, GENERAL: 4'-0" AFF
V. RACEWAYS
A. SHALL BE GALVANIZED OUTSIDE AND INSIDE BY HOT DIPPING. E.M.T. SHALL BE ELECTRO-
GALVANIZED. CONDUITS SHALL BE AS MANUFACTURED BY REPUBLIC, PITTSBURGH STANDARD,
WHEATLAND, TRIANGLE, ALLIED, OR YOUNGSTOWN.
B. SHALL BE STANDARD THREADED TYPE, GALVANIZED OUTSIDE AND INSIDE BY HOT DIPPING.
THREADLESS AND CLAMP TYPE NOT ACCEPTABLE. SHALL BE AS MANUFACTURED BY RACO,
EFCOR, OR APPLETON.
C. SHALL BE STEEL THREADED COMPRESSION TYPE. ALL COUPLINGS AND CONNECTORS SHALL BE EFCOR OR RACO. PRESSURE INDENTED TYPE CONNECTORS OR CAST METAL WILL NOT BE APPROVED FOR
ANY LOCATION.
D. CONNECTORS SHALL HAVE PLASTIC INSULATED THROAT INSERTS.
E. THE USE OF METAL CLAD CABLE IS ACCEPTABLE IN LOCATIONS AS ACCEPTED BY THE NEC AND ALL
LOCAL JURISDICTIONAL CODES.
F. STEEL METAL CLAD CABLE, TYPE MC, EMPLOYING CIRCUIT CONDUCTORS #12 SOLID TO #2 AWG, SOLID OR STRANDED COPPER WITH THHN INSULATION, AN INSULATED GREEN GROUNDING CONDUCTOR AND GALVANIZED STEEL INTERLOCKED ARMOR CLADDING. THE CABLES SHALL BE SUITABLE FOR USE IN DRY LOCATIONS AT TEMPERATURES NOT EXCEEDING 90° C ON AD CIRCUITS UP TO 600 VOLTS IN ACCORDANCE WITH N.E.C., ARTICLE 334. THE CABLE SHALL BE ONE AND TWO HOUR FIRE RATED PER ANSI/UL 1479 FOR USE
IN WALL, CEILING AND FLOOR ASSEMBLIES.
G. FLEXIBLE METALLIC CONDUIT RACEWAYS MAY BE USED TO CONNECT HVAC UNITS LOCATED IN
INTERIOR MECHANICAL AREAS. MINIMUM SIZE 3/4".
H. CONDUIT SHALL BE SIZED IN ACCORDANCE WITH THE LATEST NATIONAL ELECTRICAL CODE EXCEPT THAT NO CONDUIT SHALL BE SMALLER THAN 3/4" UNLESS OTHERWISE NOTED. CONDUIT SHALL BE SIZED LARGER THAN REQUIRED ABOVE WHEN SO SHOWN ON THE DRAWINGS OR WHEN REQUIRED BY LOCAL
CODE.
I. ANY CONDUIT STUBBED OUT FOR FUTURE SHALL BE CAPPED WITH A PLASTIC CAP AND MARKED WITH A 2" MINIMUM RED METAL TAG WHICH IDENTIFIES CONDUIT ORIGIN. CONDUITS STUBBED UP ABOVE GRADE OR ROOF SHALL BE TAGGED ON THE CONDUIT. CONDUIT STUBBED OUT BELOW GRADE SHALL BE TAGGED ON NEAREST BUILDING WALL, CURB, ETC., DIRECTLY OVER THE CONDUIT RUN. ALL EMPTY
CONDUITS SHALL HAVE PULL WIRES.
VI. SCHEDULE 40 RIGID PVC:
A. CONDUIT SHALL BE COMPOSED OF POLYVINYLCHLORIDE AND SHALL BE UL RATED TYPE 40 FOR
USE WITH 90EC RATED CONDUCTORS. CONDUIT SHALL CONFORM TO NEMA STANDARDS AND
APPLICABLE SECTIONS OF NEC.
B. INSTALLATION OF RIGID NON-METALLIC CONDUIT SHALL COMPLY WITH ARTICLE 347 OF THE
NATIONAL ELECTRICAL CODE (NFPA 70) AND THESE SPECIFICATIONS.
C. PROVIDE A CONTINUOUS, INSULATED, GROUNDING CONDUCTOR IN EVERY RIGID, NON-METALLIC
RACEWAY EVEN IF NOT SHOWN ON THE DRAWINGS. THE GROUNDING CONDUCTOR SHALL BE
CONNECTED TO…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .