Bid Item Park Park Area
FMSS
Location # Building Name/Description System
FMSS
Asset #
Location Deficiency Description Recommendation /Required Repair Additional Comments
BASE BID
BELA
BELA Nome 42596 0000412 Duplex 203 A, B BP 347326 (Serial 11240, Watts 2") Check #2 leaks.
Apply rebuild kit to backflow preventer and retest.
BASE BID
BELA
BELA Nome 42596 0000412 Duplex 203 A, B BP 347326
(Serial 29397, Ames 2") Check #1 & Check #2 leak.
Apply rebuild kit to backflow preventer and retest.
BASE BID
BELA
BELA Nome 42596 0000412 Duplex 203 A, B SP 347326 Exterior Wall Missing alarm bell and FDC signage.
Provide alarm bell and FDC signage on exterior wall.
BASE BID
BELA
BELA Nome 42596 0000412 Duplex 203 A, B SP 347326 Guage on system is over 5 years old. Replace system guage x1.
BASE BID
BELA
BELA Nome 42599 0000456 Duplex 203 A, B SP 347346 Guage on system is over 5 years old. Replace system guage x1.
BASE BID
BELA
BELA Nome 42599 0000456 Duplex 203 A, B BP 347346 Test Cocks #1 and #3 corroded closed and cannot open.
Replace test cocks and re-test
BASE BID
BELA
BELA Nome 42605 00BUNK01 Bunk House-- Nome FA 347309 AC Panel in Mechanical
Room
No breaker lock on circuit breaker supplying primary power to fire alarm control panel.
Install circuit breaker lock.
BASE BID
BELA
BELA Nome 42605 00BUNK01 Bunk House-- Nome FA 347309 FACP No allen key or glass rods to restore pull stations available.
Place allen keys and glass rods at the panel.
BASE BID
BELA
BELA Nome 42605 00BUNK01 Bunk House-- Nome FA 347309 FACP No operating instructions posted at FACP. Post operating instructions at the panel.
BASE BID
BELA
BELA Nome 42605 00BUNK01 Bunk House-- Nome BP 347310 (Serial A009764, Febco 2") Check #1 and #2 leaked.
Apply rebuild kit to backflow preventer and retest.
BASE BID
BELA
BELA Nome 42605 00BUNK01 Bunk House-- Nome SP 347310 Missing alarm bell and FDC signage.
Provide alarm bell and FDC signage on exterior wall.
BASE BID
BELA
BELA Nome 42605 00BUNK01 Bunk House-- Nome SP 347310 Pipe shows signs of glycerin leaking at threaded fittings.
Pull piping and apply new pipe dope and tape.
BASE BID
BELA
BELA Nome 42605 00BUNK01 Bunk House-- Nome SP 347310 Antifreeze in system has a freezing point of 10°F.
Replace antifreeze to have a lower freezing point of -17°F
BASE BID
DENA
DENA
Park Frontcountry
1521 HQ Apartments P12 A & B Historic BP 1475822 Relief port Relief port drips continuously. Clean check valve 1 and rebuild check valve 2.
BASE BID
DENA
DENA
Park
Frontcountry 1542 HQ Residence P26 SP 1475877 Basement 1 sprinkler head is too far off of wall. Add addional head in basement.
BASE BID
DENA
DENA
Park
Frontcountry 1542 HQ Residence P26 SP 1475877 Basement Newly added duct is blocking a sprinkler head. Move sprinkler head NFPA 13 - 9.5.5.2
BASE BID
DENA
DENA
Park
Frontcountry 1544 HQ Residence P28 SP 1475881 Riser No spare heads, or listed head wrenches. Supply spare heads and wrench NFPA 25 - 5.2.1.4
BASE BID
DENA
DENA
Park
Frontcountry 2189 Maintenance B&U Building B380 BP 1475891
Backflow discharge side
System not arranged for forward flow Add forward flow test valves
BASE BID
DENA
DENA
Park
Frontcountry 2189 Maintenance B&U Building B380 BP 1475891
Discharge side of backflow
System not equipped for forward flow testing.
Add test valves/FDC bypass for forward flow testing
BASE BID
DENA
DENA Talkeetna 18918 Talkeetna Walter Harper Ranger
Station, B249 FA 1475959 No Breaker Lock Add Breaker Lock.
Typical product is https://www.tclifesafety.com/space-age-elock-fa-fire-lockout-kit.html
BASE BID
DENA
DENA Talkeetna 18918 Talkeetna Walter Harper Ranger
Station, B249
FA 1475959 FACP
Building lost AC power before voltage measurements for SLA batteries could be made.
Re-test batteries.
BASE BID
DENA
DENA Talkeetna 18918 Talkeetna Walter Harper Ranger
Station, B249 BP 1475960 System Riser System is not arranged for forward flow testing. Add 2 1/2" hose valves for forward flow test.
BASE BID
DENA
DENA Talkeetna 18918 Talkeetna Walter Harper Ranger
Station, B249
BP 1475960
System discharge side
No means of forward flow testing Add 2x 2 1/2" hose valves for testing.
BASE BID
DENA
DENA
Park
Frontcountry 86493
Murie Science and Learning Center
MSLC B547
SP 1475989 Whole System Past due for 5-Year internal inspection. Perform 5-Year internal pipe inspection.
Location # Building Name/Description System
FMSS
Asset #
Location Deficiency Description Recommendation /Required Repair Additional Comments
BASE BID
DENA
DENA
Park
Frontcountry 86493
Murie Science and Learning Center
MSLC B547
SP 1475989 Whole System QR heads are 20 years old Replace all heads
NFPA 25 or NFPA 13 reference: 5.3.1.1.1.3 FPE Comment: NFPA 25 excerpts below for reference:
5.3.1.1.1.3* Sprinklers manufactured using fast-response elements that have been installed for 20 years shall be replaced or representative samples shall be tested and then retested at 10-year intervals.
A5.3.1.1.1.3 Sprinklers defined as fast response have a thermal element with an RTI of 50 (meter-seconds)^1/2 or less, A quick-response sprinkler, residential sprinkler, and early suppression fast-response (ESFR) sprinklers are examples of fast-response sprinklers.
BASE BID
DENA
DENA
Park
Frontcountry 86498 Denali Visitor Center B548 FA 1475992 Elevator
Unable to test 4 elevator smoke detectors, elevator needs to be power cycled after each device is tested.
Test with Elevator technician present to reset elevator after testing.
NPS Staff can reset elevator after testing
BASE BID
DENA
DENA
Park
Frontcountry 86498 Denali Visitor Center B548 SP 1475994 Whole System QR heads are 20 years old Replace all heads
NFPA 25 or NFPA 13 reference: 5.3.1.1.1.3 FPE Comment: NFPA 25 excerpts below for reference:
5.3.1.1.1.3* Sprinklers manufactured using fast-response elements that have been installed for 20 years shall be replaced or representative samples shall be tested and then retested at 10-year intervals.
A5.3.1.1.1.3 Sprinklers defined as fast response have a thermal element with an RTI of 50 (meter-seconds)^1/2 or less, A quick-response sprinkler, residential sprinkler, and early suppression fast-response (ESFR) sprinklers are examples of fast-response sprinklers.
BASE BID
DENA
DENA
Park
Frontcountry 226504 Shaffer Building B570 CA 1476005
Damper above releasing panel Adjust damper motor. Damper motor needs to be adjusted
BASE BID
GAAR
GAAR Bettles 42598 00000106 BTTH House 106 FA 1750888 FACP Batteries were not installed. Install 12V x 7AH (F1 Terminal) batteries.
BASE BID
GAAR
GAAR Bettles 42598 00000106 BTTH House 106 FA 1750888 FACP/House AC Panel in Mech Room
No breaker lock installed on AC panel supplying primary power to FACP.
Install red circuit breaker lock.
BASE BID
GAAR
GAAR Bettles 42598 00000106 BTTH House 106 FA 1750888 FACP No allen key or glass rods to restore pull stations available.
Place allen keys and glass rods at the panel.
BASE BID
GAAR
GAAR Bettles 42598 00000106 BTTH House 106 SP 1750888 Hydraulic calc plate is a sticker stuck to the wall located by alarm panel.
Re-print hydraulic calc plate and locate on system riser.
BASE BID
GAAR
GAAR Bettles 42602 00000107 BTTH House 107 FA 1750889 FACP Batteries were not installed. Install 12V x 7AH (F1 Terminal) batteries.
BASE BID
GAAR
GAAR Bettles 42602 00000107 BTTH House 107 FA 1750889 FACP/House AC Panel in Mech Room
No breaker lock installed on AC panel supplying primary power to FACP.
Install red circuit breaker lock.
Location # Building Name/Description System
FMSS
Asset #
Location Deficiency Description Recommendation /Required Repair Additional Comments
BASE BID
GAAR
GAAR Bettles 42602 00000107 BTTH House 107 FA 1750889 FACP No allen key or glass rods to restore pull stations available.
Place allen keys and glass rods at the panel.
BASE BID
GAAR
GAAR Bettles 42602 00000107 BTTH House 107 SP 1750889 Hydraulic calc plate is a sticker on the wall located by alarm panel.
Re-print hydraulic calc plate and locate on system riser.
BASE BID
GAAR
GAAR Bettles 43084 00000109 BTTH House 109 FA 1750891 FACP/House AC Panel in Mech Room
No breaker lock installed on AC panel supplying primary power to FACP.
Install red circuit breaker lock.
BASE BID
GAAR
GAAR Bettles 43084 00000109 BTTH House 109 FA 1750891 FACP No allen key or glass rods to restore pull stations available.
Place allen keys and glass rods at the panel.
BASE BID
GAAR
GAAR Bettles 43084 00000109 BTTH House 109 SP 1750891 Hydraulic calc plate is a sticker on the wall located by alarm panel.
Re-print hydraulic calc plate and locate on system riser.
BASE BID
GAAR
GAAR Bettles 43086 00000110 BTTH House 110 FA 1750890 FACP/House AC Panel in Mech Room
No breaker lock installed on AC panel supplying primary power to FACP.
Install red circuit breaker lock.
BASE BID
GAAR
GAAR Bettles 43086 00000110 BTTH House 110 FA 1750890 FACP No allen key or glass rods to restore pull stations available.
Place allen keys and glass rods at the panel.
BASE BID
GAAR
GAAR Bettles 43086 00000110 BTTH House 110 SP 1750890 Hydraulic calc plate is a sticker on the wall located by alarm panel.
Re-print hydraulic calc plate and locate on system riser.
BASE BID
GAAR
GAAR Bettles 88477 BTTB-113 Visitor Center SP 1057428
Low point aux drains are above ceiling and need access.
Relocate aux drain to be accessible.
BASE BID
GAAR
GAAR Bettles 88477 BTTB-113 Visitor Center SP 1057428 10 SSP 1/2" 5.6 drain heads show corrosion. Replace drain heads.
BASE BID
GAAR
GAAR Bettles 88477 BTTB-113 Visitor Center/Office FA 1477361 Mech Rm No breaker lock installed on AC panel supplying primary power to FACP.
Install red circuit breaker lock.
BASE BID
GLBA
GLBA Bartlett Cove 42545 HQ - Resource Management / Ranger Office Building GBA06
SP 1168372 Riser Guages need replacement. Replace gauges with new.
BASE BID
GLBA
GLBA Bartlett Cove 42545 HQ - Resource Management / Ranger Office Building GBA06
FA 1477376
120 VAC
Exterior Bell No interface with alarm panel. Provide relay with contacts to module or remove.
BASE BID
GLBA
GLBA Bartlett Cove 42548 UC Power Plant Bldg GBA 08 FA 1475415
120 VAC
Exterior Bell No interface with alarm panel. Provide relay with contacts to module or remove.
BASE BID
GLBA
GLBA Bartlett Cove 42551 HQ - Headquarters Building GBA12 FA 1477755 Boiler Room Heat Detector reports on Zone 2, 2nd level. Identify and correct any incorrect zone reporting.
BASE BID
GLBA
GLBA Bartlett Cove 42565 UC Emergency Cache Bldg GBA 89 BP 224646 Both check valves failed. Replace both check valves/backflow preventors
BASE BID
GLBA
GLBA Gustavus 42586 GA - Gustavus FAA Cottage GBQ21 SP 1121930 Riser Guages need replacement. Replace gauges with new. 2023 NFPA 25 - 13.2.4.2
BASE BID
GLBA
GLBA Bartlett Cove 42590 HA - Quarters GBQ75 Apartment
Building BP 224713 Both check valves failed. Replace both check valves/backflow preventors
BASE BID
GLBA
GLBA Bartlett Cove 42618 HA - Quarters Duplex GBQ82 SP 225945 Riser Control valves are not secured. Lock, seal, or monitor NFPA 13 reference: A 16.11.3.1
BASE BID
GLBA
GLBA Gustavus 61189 GA - Gustavus Water Plant Building
GBA61
SP 1121932 Entire System Due for 5 year internal inspection Perform 5-year internal pipe inspection for MIC.
BASE BID
GLBA
GLBA Bartlett Cove 70959 MA - Maintenance Support Building
GBA99
FA 1475408
Booster panel and F.A.C.P.
Batteries due for replacement. Replace batteries.
BASE BID
GLBA
GLBA Bartlett Cove 73442 WT - Water Plant Building GBA15 SP 1477852 Riser Guages need replacement. Replace gauges with new. 2023 NFPA 25 - 13.2.4.2
BASE BID
GLBA
GLBA Bartlett Cove 73442 WT - Water Plant Building GBA15 SP 1477852 Riser Faculty currently using flow switch. Replace with proper screw in switch.
BASE BID
GLBA
GLBA Bartlett Cove 92317 PD - Huna Tribal House FA FACP Secondary power supply batteries failed load test Replace batteries NFPA 72 reference 14.4.3.2.9(5)
BASE BID
KATM
KATM Brooks Camp 88200 VRAA-SHOP W-1 FA 1027356 FACP Batteries need to be replaced. Replace batteries.
2022 NFPA 72 Table 14.4.3.2 Item 9.5 - Replace batteries every 3 years or conduct a load test of the battery capacity and replace if less than 85%.
BASE BID
KATM
KATM King Salmon 93637 KS - Seasonal and Transient Dormitory Q01
SP 1477623 FDC Auto drain is in incorrect position. Correct auto drain position.
BASE BID
KATM
KATM King Salmon 93637 KS - Seasonal and Transient Dormitory Q01
SP 1477623 Entire Building Sprinkler system due for 5 year internal inspection.
Perform 5 year internal inspection. NFPA 25 14.2.1
BASE BID
KATM
KATM King Salmon 93637 KS - Seasonal and Transient Dormitory Q01
SP 1477623 Riser Guage on system is over 5 years old. Replace system guage.
Location # Building Name/Description System
FMSS
Asset #
Location Deficiency Description Recommendation /Required Repair Additional Comments
BASE BID
KATM
KATM King Salmon 101238 KS - King Salmon Duplex FAA162/163 FA 1477635 Panel Both batteries last tested at 70%. Replace both batteries. NFPA 72 reference: 14.4.5.9
BASE BID
KATM
KATM King Salmon 101239 KS - King Salmon Housing White Sox Way FAA150
FA 1009266 2nd Floor All smoke detectors go into alarm very easily. Troubleshoot detectors and repair/replace.
BASE BID
KATM
KATM King Salmon 101239 KS - King Salmon Housing White Sox Way FAA150
FA 1009266 Riser/Bell Outside horn strobe does not work. Troubleshoot detectors and repair/replace.
BASE BID
KATM
KATM King Salmon 102827 KS - King Salmon Duplex FAA143/144 FA 1477625 Entire Building All smoke detectors go into alarm very easily. Troubleshoot detectors and repair/replace. NFPA 72 reference: 11.4.4.32
BASE BID
KATM
KATM Brooks Camp 225709 VH - Valley Road Housing Bunk House VR10
SP 1601417
Basement Crawl Riser
Gauge due for replacement Replace system gauges. NFPA 25 5.3.2.1
BASE BID
KATM
KATM Brooks Camp 225709 VH - Valley Road Housing Bunk House VR10
FA 1739191 FACP Batteries need to be replaced. Replace batteries.
2022 NFPA 72 Table 14.4.3.2 Item 9.5 - Replace batteries every 3 years or conduct a load test of the battery capacity and replace if less than 85%.
BASE BID
KATM
KATM King Salmon 230268 KS - King Salmon Housing Rainbow Ridge Road FAA164
FA 1028959
Bedroom at Top of stairs
Device has hot water damage. Replace device. NFPA 72 reference: 14.5.1
BASE BID
KATM
KATM King Salmon 230268 KS - King Salmon Housing Rainbow Ridge Road FAA164
FA 1028959
Garage and Boiler Rm
All system heat detectors appear to be past 15 year replacement date.
Replace devices. NFPA 72 reference: 14.4.3.2
BASE BID
KATM
KATM King Salmon 230268 KS - King Salmon Housing Rainbow Ridge Road FAA164
FA 1028959 Entire Building All smoke detectors go into alarm very easily. Troubleshoot detectors and repair/replace. NFPA 72 reference: 11.4.4.32
BASE BID
KATM
KATM Brooks Camp 234791 VR02 Valley Road Area Utility Buildiing
FA 1477628 FACP Batteries need to be replaced. Replace batteries.
2022 NFPA 72 Table 14.4.3.2 Item 9.5 - Replace batteries every 3 years or conduct a load test of the battery capacity and replace if less than 85%.
BASE BID
KATM
KATM King Salmon 241900 KS - King Salmon Housing FAA161 FA 1449813 Outside front door Hornstrobe by front door failed to flash and sound loud.
Reprogram NAC circuit. NFPA 72 reference: 18.4.4.1
BASE BID
KATM
KATM King Salmon 254692 KS - King Salmon Duplex FAA136/137 FA 1764864 Entire Building All system heat detectors appear to be past 15 year replacement date.
Replace devices. NFPA 72 reference: 14.4.3.2
BASE BID
KATM
KATM King Salmon 254692 KS - King Salmon Duplex FAA136/137 FA 1764864 Entire Building All smoke detectors go into alarm very easily. Troubleshoot detectors and repair/replace. NFPA 72 reference: 11.4.4.32
BASE BID
KATM
KATM King Salmon 256333 KS - King Salmon FAA Comserfac SP 1776419 Sprinkler Cabinet
No spare sprinklers. Supply 4 spare sprinklers in cabinet. NFPA 25 5.4.1.4
BASE BID
KATM
KATM King Salmon 256333 KS - King Salmon FAA Comserfac FA 1776419 FACP Branch circuit breaker is not marked in red and does not have circuit breaker lock.
Install circuit breaker lock and red label. NFPA 72 reference: 10.6.5.4
BASE BID
KATM
KATM King Salmon 256333 KS - King Salmon FAA Comserfac SP 1776419 Entire Building Sprinkler system due for 5 year internal inspection.
Perform 5 year internal inspection. NFPA 25 14.2.1
BASE BID
KATM
KATM King Salmon 256333 KS - King Salmon FAA Comserfac SP 1776419 Entire Building Dry sprinklers are due for 10 year replacement (4 total).
Replace 4 dry sprinklers NFPA 25 5.3.1.1.1.6
BASE BID
KATM
KATM King Salmon 256333 KS - King Salmon FAA Comserfac FA 1776419 FACP Batteries need to be replaced. Replace batteries.
2022 NFPA 72 Table 14.4.3.2 Item 9.5 - Replace batteries every 3 years or conduct a load test of the battery capacity and replace if less than 85%.
BASE BID
KATM
KATM King Salmon 256333 KS - King Salmon FAA Comserfac FA 1776419 Entire Building All system heat detectors appear to be past 15 year replacement date.
Replace devices. NFPA 72 reference: 14.4.3.2
BASE BID
KATM
KATM King Salmon 256333 KS - King Salmon FAA Comserfac SP 1776419 Entire Building Guages need replacement. Replace gauges with new. 2023 NFPA 25 - 13.2.4.2
BASE BID
KATM
KATM King Salmon 256333 KS - King Salmon FAA Comserfac FA 1776419 Entire Building Horn strobes near FACP and outside front entry failed to operate correctly.
Replace horn strobes. NFPA 72 reference: 14.3
BASE BID
KATM
KATM King Salmon 256333 KS - King Salmon FAA Comserfac SP 1776419 System Riser Out of Service Return to service.
BASE BID
KATM
KATM King Salmon 256333 KS - King Salmon FAA Comserfac FA 1776419 Zone 3 Zone 3 in trouble and does not reset as intended. Troubleshoot circuit. NFPA 72 reference: 14.3
BASE BID
KATM
KATM King Salmon 258861 KS - King Salmon Residence 138 FA 1776422 FACP Branch circuit breaker is not marked in red and does not have circuit breaker lock.
Install circuit breaker lock and red label. NFPA 72 reference: 10.6.5.4
BASE BID
KATM
KATM King Salmon 258861 KS - King Salmon Residence 138 FA 1776422 Entire Building All system heat detectors appear to be past 15 year replacement date.
Replace devices. NFPA 72 reference: 14.4.3.2
BASE BID
KATM
KATM King Salmon 258861 KS - King Salmon Residence 138 FA 1776422 FACP All zones are in trouble and none reset as intended.
Troubleshoot zones. NFPA 72 reference: 14.3
BASE BID
KATM
KATM King Salmon 258862 KS - King Salmon Utility Building FA 1776422 Riser Wiring is pulled from riser devices to FACP. Connect wiring after riser is returned to service. NFPA 9.7.2.2.1
Location # Building Name/Description System
FMSS
Asset #
Location Deficiency Description Recommendation /Required Repair Additional Comments
BASE BID
KATM
KATM King Salmon 258862 KS - King Salmon Utility Building FA 1776422 FACP Batteries need to be replaced. Replace batteries.
2022 NFPA 72 Table 14.4.3.2 Item 9.5 - Replace batteries every 3 years or conduct a load test of the battery capacity and replace if less than 85%.
BASE BID
KATM
KATM King Salmon 258862 KS - King Salmon Utility Building FA 1776422 Entire Building All system heat detectors appear to be past 15 year replacement date.
Replace devices. NFPA 72 reference: 14.4.3.2
BASE BID
KATM
KATM King Salmon 258862 KS - King Salmon Utility Building #301 FA 1776423 Sprinkler Cabinet
Lack of spare sprinklers. Supply 5 spare sprinklers in cabinet.
BASE BID
KATM
KATM King Salmon 258862 KS - King Salmon Utility Building #301 FA 1776423 Entire Building Sprinkler system due for 5 year internal inspection.
Perform 5 year internal inspection. NFPA 25 14.2.1
BASE BID
KATM
KATM King Salmon 258862 KS - King Salmon Utility Building #301 FA 1776423 System No sprinkler coverage. Provide full sprinkler coverage.
BASE BID
KATM
KATM King Salmon 258862 KS - King Salmon Utility Building #301 FA 1776423 System Out of Service Return Service
BASE BID
KATM
KATM King Salmon 258862 KS - King Salmon Utility Building #301 FA 1776423 Backflow Tampers did not report to FACP. Troubleshoot and repair
BASE BID
KATM
KATM King Salmon 258863 KS - King Salmon Water treatment Plant BLDG #52
FA 1776424 Entire Building Sprinkler system due for 5 year internal inspection.
Perform 5 year internal inspection. NFPA 25 14.2.1
BASE BID
KATM
KATM King Salmon 258863 KS - King Salmon Water treatment Plant BLDG #52
FA 1776424 Entire Building Guages need replacement. Replace gauges with new. 2023 NFPA 25 - 13.2.4.2
BASE BID
KEFJ
KEFJ Seward 1039 DT: Visitor Center FA 342730 Fire Alarm
Control Panel No operating instructions Post operating instructions at FACP
BASE BID
KEFJ
KEFJ Seward 1039 DT: Visitor Center FA 342730 Fire Alarm
Control Panel No spare glass rods to restore pull stations available.
Provide glass rods at panel.
BASE BID
KEFJ
KEFJ Seward 1039 DT: Visitor Center FA 342730 Fire Alarm
Control Panel Batteries need to be replaced. Replace batteries 2 qty. 12 VDC x 7AH
BASE BID
KEFJ
KEFJ Seward 1039 DT: Visitor Center SP 1737108 1" valves leak on drum drip. Replace x 2 - 1" ball valves on drum drip. NFPA 25 5.2.2.1
BASE BID
KEFJ
KEFJ Seward 99895 DT: Park Head Quarters Building FA 1477348
1st Floor Electrical Room AC panel
Branch circuit breaker is not marked in red and does not have circuit breaker lock.
Install circuit breaker lock and red label. NFPA 72 reference: 10.6.5.4
BASE BID
KEFJ
KEFJ Seward 99895 DT: Park Head Quarters Building FA 1477348 Fire Alarm Control Panel
No spare glass rods to restore pull stations available.
Provide glass rods at panel.
BASE BID
KEFJ
KEFJ Seward 99895 DT: Park Head Quarters Building FA 1477348 Exterior Sprinkler Bell
Sprinkler bell failed to operate. Replace device.
BASE BID
KEFJ
KEFJ Seward 99895 DT: Park Head Quarters Building FA 1477348 System Riser Gauges are over 5 years old Replace gauges with new.
BASE BID
KEFJ
KEFJ Seward 99895 DT: Park Head Quarters Building SP 1477351 Entire
Sprinkler System
5-year internal investigation Perform 5 year internal inspection.
BASE BID
KEFJ
KEFJ Seward 99895 DT: Park Head Quarters Building SP 1477351 Exterior Wall Electric Bell does not work. Replace Electric Bell NFPA 25 or NFPA 13 reference: 13.4.2
BASE BID
KLGO
KLGO Skagway 68537 White Pass Depot Visitor Center SP 1020922 FACP SLC circuit from panel to pull station 084 - 2nd floor has ground fault.
Re-run slc circuit wire.
BASE BID
KLGO
KLGO Skagway 68653 Lynch & Kennedy Haberdashery &
Dry Goods Store
SP 1157783
1st floor near bathroom/2nd floor … Missing Trims Replace concealer trims
BASE BID
KLGO
KLGO Skagway 236885 4th Avenue Dorm SP TBD Heat sensing devices on outside building do not appear to be acceptable for outdoor use.
Replace with proper devices.
BASE BID
SITK
SITK Sitka 64367 Sitka National Historical Park Visitor
Center FA 345995 Main Hallway Horn/strobe not audible. Replace Horn/Strobe.
BASE BID
SITK
SITK Sitka 64372 Russian Bishop's House BP 164164 #2 Shutoff failed and rocks came out of #4 testport.
Repair shutoff and clean testport.
Location # Building Name/Description System
FMSS
Asset #
Location Deficiency Description Recommendation /Required Repair Additional Comments
BASE BID
SITK
SITK Sitka 64374 Priest's Quarters SP 164185 Mech Room Dry valve is problematic and should be replaced. Replace with Tyco DPV-1
BASE BID
SITK
SITK Sitka 64540 Old School Mechanical Room BP 164184 #2 shutoff valve has been leaking slowly from stem, but passed test.
Investigation and repair. Assume worst case and replace backflow preventor
BASE BID
WEAR
WEAR Kotzebue 84667 Northwest Alaska Heritage Center FP 1139570 Fire Pump
Water tank nose for level is dirty and hard to see how much water is in the tank.
Relace/clean water tank nose.
BASE BID
WEAR
WEAR Kotzebue 84667 Northwest Alaska Heritage Center FP 1139570 Fire Pump Fire pump suction and discharge guages are not liquid filled calibrated guages. Has system guages on both so suction does not work.
Replace suction and discharge guages with correct calibrated guages.
BASE BID
WEAR
WEAR Kotzebue 84667 Northwest Alaska Heritage Center FA 1475561 AC panel near fire alarm control panel.
No breaker lock on circuit breaker supplying primary power to fire alarm control panel.
Install circuit breaker lock.
BASE BID
WEAR
WEAR Kotzebue 84667 Northwest Alaska Heritage Center FA 1475561 Sprinkler Riser
Room Fire pump test control valves #1 and #2 are not monitored.
Wire valves to fire alarm system for supervisory monitoring.
BASE BID
WEAR
WEAR Kotzebue 84667 Northwest Alaska Heritage Center SP 1475564 Dry heads are from 2008 and require testing. Replace dry sprinkler heads
BASE BID
WEAR
WEAR Kotzebue 84667 Northwest Alaska Heritage Center SP 1475564 No fire sprinkler sign on door. Add sign noting systems location.
BASE BID
WEAR
WEAR Kotzebue 84667 Northwest Alaska Heritage Center SP 1475564 No FDC or bell signage. Provide FDC and bell signage.
BASE BID
WEAR
WEAR Kotzebue 84667 Northwest Alaska Heritage Center SP 1475564 Storage tank for water has clear nose for level checking and is black/rusty and hard to recall.
Replace nose.
BASE BID
WEAR
WEAR Kotzebue 84667 Northwest Alaska Heritage Center SP 1475564 Guages on fire pump are for system and cannot read accurately for testing.
Replace with actual suction and discharge gauges.
BASE BID
WEAR
WEAR Kotzebue 108797 Duplex 297 C,D BP 1478582 Pipe was frozen and offline. New B.F. on the ground to be replaced.
Replace section of broken pipe, re-install backflow preventor and verify system functions correctly
BASE BID
WEAR
WEAR Kotzebue 108797 Duplex 297 C,D SP 1478582 System was frozen and broken. Major disrepair.
No inspection done.
Replace broken pipe, install new backflow already at site, test system for leaks to make sure all the broken pipe is replaced, and then put system back in service.
BASE BID
WEAR
WEAR Kotzebue 237769 Automotive Shop FA 1475524 AC panel near fire alarm control panel.
No breaker lock on circuit breaker supplying primary power to fire alarm control panel.
Install circuit breaker lock.
BASE BID
WEAR
WEAR Kotzebue 237769 Automotive Shop FA 1475524 FACP No operating instructions posted at fire alarm control panel.
Post operating instructions at the panel
BASE BID
WEAR
WEAR Kotzebue 237769 Automotive Shop FA 1475524 FACP No pull station key or spare glass rods to restore pull stations available.
Provide Simplex "B" key and spare glass rods at fire alarm control panel.
BASE BID
WEAR
WEAR Kotzebue 237769 Automotive Shop FA 1475524 FACP No key for fire alarm control panel.
Provide Simplex "B" Key for fire alarm control panel.
BASE BID
WEAR
WEAR Kotzebue 237769 Auto Shop 297E FA 1475524 Exterior Horn/Strobe not audible. Replace Horn/Strobe
Option Item 1
KLGO Skagway 68537 White Pass Depot Visitor Center/Admin Building
SP
Dry Pipe and Fittings
Air leak in system that park has not been able to identify causing compressor to run multiple times per hour
Identify air leak and repair, work to be coordinated with contract COR to determine extent of time and cost
Lots of concealed pipe in walls and ceiling may make finding leak difficult if not in exposed area. Will likely have to isolate branches/sections of piping one at a time to narrow down area in the system where the leak is.
Option Item 2
LACL Port Alsworth 94890 PA-19 Redoubt Duplex SP 1173618 Riser room Gauges are past their due date to be replaced, 5 year intervals.
Replace gauges with new.
Option Item 2
LACL Port Alsworth 94905 PA-17 Tanalian Duplex SP 1173614 Riser room Gauges are past their due date to be replaced, 5 year intervals.
Replace gauges with new.
Option Item 2
LACL Port Alsworth 94906 PA-18 Iliamna Duplex SP 1173616 Riser room Gauges are past their due date to be replaced, 5 year intervals.
Replace gauges with new.
Option Item 3
WRST Copper Center 32893 BA HQ Utility Building SP 1475051 Test headed control valve leaks. Replace control valve. NFPA 25 (2017) 13.3.2.2(5)