B08_A2_CEB_DDC_-_Drawings.pdf
PDF 3 MB Posted
- Attached to
- INSTALL DIRECT DIGITAL CONTROLS C-EB Federal contract opportunity
- Solicitation number
- 140A2323R0084
About this file
This solicitation requests proposals to install direct digital controls at Cheyenne Eagle Butte High School in Eagle Butte, South Dakota. The Bureau of Indian Affairs seeks to upgrade the existing pneumatic controls system with a new digital controls system to control heating and ventilation. Offerors should have experience working with Schneider Electric controls and designing controls systems for educational facilities. Proposals are due by January 26, 2023 and the period of performance is 120 days from award. The total budget for the project is $150,000. This is a small business set-aside solicited using simplified acquisition procedures.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| B08_A4_Wage_Determination_SD20230012.pdf | ||
| B08_A3_CEB_DDC_-_Specs.pdf | ||
| B08_A11_SF-25A_Payment_Bond_Form.pdf | ||
| Sol_140A2323R0084.pdf | ||
| B08_A10_SF-25_Performance_Bond_Form.pdf | ||
| B08_A8_IA_Form_C713_Progress_Report.pdf | ||
| B08_A6_IA_Form_3000_Material_Approval_Submittal.pdf | ||
| B08_A9_SF-1413_Statement_and_Acknowledgement_Form_(Subcontracting).pdf | ||
| B08_A1_Statement_of_Work.pdf | ||
| B08_A7_IA_Form_C113_Progress_Schedule_-_Copy.pdf | ||
| B08_A5_Health_and_Safety_Codes.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
R E
G
IS
T E R
E
D
PROFESS IONA
L
E N G
I N
E E
R
S
O
UTH DAKO
T
A
15404
BRADEN S.
COX
REG . NO .
architecture +engineering
SEVEN
GENERATIONS
DESCRIPTIONDATEMARK
U.S. DEPARTMENT OF THE
INTERIOR BUREAU OF INDIAN
AFFAIRS
OFMC-GREAT PLAINS
115 4TH AVENUE SE SUITE 400,
MC202 ABERDEEN, SOUTH DAKOTA
57401 PHONE: 605-226-0877
FAX: 605-226-0881
ISSUE:
BIA #:
DWG:
DRAWN BY:
CHECKED BY:
SHEET
TITLE:
SHEET:
600 E. Michigan Ave., Suite B
Kalamazoo, MI 49007
P: 269.927.0144 www.7genae.com
259 E. Michigan Ave., Suite
Kalamazoo, MI 49007
P: 269.585.2255
100% BID DOCUMENTS
99% CD9/21/22
100% BID DOCUMENTS
70% PD7/21/22
BIA CONCUR:
BUREAU OF INDIAN AFFAIRS DATE
GREAT PLAINS REGION
DIVISION OF FACILITIES
100% CD11/28/22
1/26/23
100% BID1/26/23
CHEYENNE
EAGLE
BUTTE
SCHOOL
BIA
2004 E STREET,
EAGLE BUTTE, SD
57625
7GEN PROJECT NUMBER: 221101
GI001
COVER SHEET
MC
BSC
PROJECT TEAM
ARCHITECTURE:
OWNER:
BUILDING OCCUPANCY:
CONSTRUCTION TYPE:
TYPE II (111)
AUTOMATIC SPRINKLER SYSTEM THROUGHOUT
EDUCATIONAL FACILITY
SEVEN GENERATIONS A+E
DEPARTMENT OF INTERIOR, BIA
DIVISION OF FACILITIES MANAGEMENT AND CONSTRUCTION
1011 INDIAN SCHOOL ROAD NW - SUITE 335
ALBUQUERQUE, NM 87104
PROJECT INFORMATION
CHEYENNE EAGLE BUTTE HIGH SCHOOL
DDC CONTROLS SYSTEMS UPGRADE
EAGLE BUTTE, SOUTH DAKOTA
BUREAU OF INDIAN AFFAIRS
MECHANICAL & PLUMBING ENGINEERING:
THE STEELHEAD ENGINEERING COMPANY
259 E. MICHIGAN AVENUE, SUITE 407
KALAMAZOO, MI 49007
PHONE: 269.585.2255
WEB: steelheadengineeringco.com
600 E. MICHIGAN AVENUE - SUITE B
KALAMAZOO, MI 49007
PHONE: 269.927.0144
WEB: 7GENAE.COM
1. THIS PROJECT SHALL BE CONSTRUCTED IN CONFORMANCE WITH ALL FEDERAL REGULATIONS AND
BUILDING CODES.
2. CONTRACTOR SHALL BE RESPONSIBLE TO OBTAIN ALL ASSOCIATED PERMITS FOR CONSTRUCTION AND SHALL DO ALL NECESSARY ITEMS FOR PROCUREMENT OF A CERTIFICATE OF OCCUPANCY. ANY COSTS
DERIVED FROM OBTAINING SAID PERMITS SHALL BE BORNE BY CONTRACTOR.
3. DRAWINGS AND SPECIFICATIONS ARE SUPPLEMENTARY. ANYTHING SHOWN IN ONE SHALL BE
CONSIDERED IN BOTH.
4. IT IS THE RESPONSIBILITY OF CONTRACTOR TO COORDINATE THE WORK OF ALL TRADES. ANY
CONFLICTING WORK TO BE REPORTED TO COR PRIOR TO THE INSTALLATION OF ANY WORK.
5. CONTRACTOR(S) TO VERIFY ALL DIMENSIONS IN FIELD PRIOR TO EACH NEW PHASE OF WORK. ANY
DISCREPANCIES SHALL BE REPORTED TO COR PRIOR TO THE INSTALLATION OF ANY WORK.
6. ANY SHEET OF THE CONTRACT DOCUMENTS IS VOID UNLESS USED IN CONJUNCTION WITH THE REST OF
THE CONTRACT DOCUMENTS.
7. DESIGN TEAM WILL NOT BE RESPONSIBLE FOR ANY DEVIATIONS FROM THESE DOCUMENTS OR DEVIATIONS
FOR SPECIFIED PRODUCTS UNLESS APPROVED BY ARCHITECT AND COR.
ADA NOTE:
A. THIS PROJECT IS TO MEET THE ADA STANDARDS IN EFFECT AT THE TIME OF THE PROJECT. IF A MATERIAL OR
SYSTEM HAS BEEN SPECIFIED OR DRAWN THAT DOES NOT MEET THE STANDARDS, THE ARCHITECT REQUESTS THAT THE CONTRACTOR, SUPPLIER OR MATERIAL MANUFACTURER ADVISE AND ASSIST THE ARCHITECT TO PROVIDE THE PRODUCT OR SYSTEM. ALL PRODUCTS OR SYSTEMS WILL NEED ACCEPTANCE OF THE COR
AND THE ARCHITECT.
B. ENSURE COMPLIANCE WITH ADAABAAG; JULY 23, 2004
GENERAL NOTES:
LOCATION:
LATITUDE: 45.000487
LONGITUDE: -101.236499
CLIMATE ZONE: 6A
NOTE: USE THE MOST CURRENT EDITIONS OF THE FOLLOWING CODES, STANDARDS AND GUIDELINES.
• DIVISION OF FACILITY MANAGEMENT AND CONSTRUCTION APPLICABLE FEDERAL HEALTH AND SAFETY
CODES AND STANDARDS
• DSRM SAFETY, HEALTH AND ACCESSIBILITY DESIGN GUIDELINES FOR ARCHITECTS, ENGINEERS AND DESIGN
FIRMS
• AMERICANS WITH DISABILITIES ACT AND ARCHITECTURAL BARRIERS ACT ACCESSIBILITY GUIDELINES
(ADAABAAG), JULY 23, 2004
• ASHRAE STANDARDS, HANDBOOKS, JOURNALS AND PUBLICATIONS
• EXECUTIVE ORDER 13693, FEBRUARY 26, 2016 UPDATE, GUIDING PRINCIPLES FOR SUSTAINABLE FEDERAL
BUILDINGS
• NATIONAL ELECTRIC CODE, 2020 EDITION
• NATIONAL ENVIRONMENTAL POLICY ACT
• NFPA 5000 BUILDING DESIGN-BUILD AND SAFETY CODE, 2021 EDITION
• OSHA
• NFPA 1 FIRE CODE, 2021 EDITION
• NFPA 10 PORTABLE FIRE EXTINGUISHERS, 2018 EDITION
• UNIFORM MECHANICAL CODE 2021 EDITION
CONSTRUCTION & ACCESSIBILITY REFERENCES:APPLICABLE CODE: NFPA 5000, 2021 EDITION
GI001 COVER SHEET NOVEMBER 28, 2022 30
M001 MECHANICAL GENERAL INFO & SYMBOL LEGEND NOVEMBER 28, 2022 60
M101 FIRST FLOOR MECHANICAL PLAN NOVEMBER 28, 2022 64
M103A AREA B FIRST FLOOR ENLARGED PLAN NOVEMBER 28, 2022 64
M103B AREA B SECOND FLOOR ENLARGED PLAN NOVEMBER 28, 2022 64
M105 AREA D FIRST AND SECOND FLOOR ENLARGED PLANS NOVEMBER 28, 2022 64
M106 AREA E ENLARGED PLAN NOVEMBER 28, 2022 64
M500 MECHANICAL DETAILS & SCHEDULES NOVEMBER 28, 2022 68
E001 ELECTRICAL GENERAL INFO & SYMBOL LEGEND NOVEMBER 28, 2022 70
E201 FIRST FLOOR POWER PLAN NOVEMBER 28, 2022 74
E203A AREA B FIRST FLOOR ENLARGED POWER PLAN NOVEMBER 28, 2022 74
E203B AREA B SECOND FLOOR POWER PLAN NOVEMBER 28, 2022 74
E205 AREA D ENLARGED POWER PLAN NOVEMBER 28, 2022 74
E206 AREA E ENLARGED POWER PLAN NOVEMBER 28, 2022 74
DRAWING SHEET INDEX
DESCRIPTIONSHEET ISSUE DATE
NOTES
VICINITY MAP LOCATION MAP
WM
M
S
M
CO2
CO
H
HS
NO2
S
TH
T
MS
CHWS
CD
CDR
CWR
CWS
HWR
HWS
G
STM
(E)
CHWR CHILLED WATER RETURN
CHILLED WATER SUPPLY
CONDENSATE DRAINAGE
CONDENSATE RETURN
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
HEATING WATER RETURN
HEATING WATER SUPPLY
NATURAL GAS
STEAM
REF-L
REF-S
REFRIGERANT-LIQUID
REFRIGERANT-SUCTION
2"
2"
4"
4"
REF-HG REFRIGERANT-HOT GAS
PIPING SYMBOLS
KEYNOTE
CONTINUATION SYMBOL
NUMBER OF SHEET WHERE DETAIL APPEARS
NUMBER OF DETAIL ON SHEET
REVISION NUMBER - SHOWN ON PLANS
GENERAL SYMBOLS
ROOM NAME AND NUMBER
POINT WHERE DISCONNECT/DEMOLITION OCCURS
AT EXISTING
EXISTING PIPE TAG
ITEM TO BE DEMOLISHED
AREA NOT IN CONTRACT
PIPING BEING DEMOLISHED
ABOVE GROUND PIPING
PIPE SIZE TAG (DIAMETER)
PIPE RISE
PIPE DROP
PIPE TEE REDUCING 45
DEGREE TEE
45 DEGREE TEE
BELOW GROUND PIPING
PIPE INVERT ELEVATION TAG
PIPE SLOPE TAG
PG PROPANE GAS
Room
INVERT: -105' - 1"
1/8" / 12" SLOPE
18"x12"
18"/12"
(E)
18"Ø
EXHAUST AIR
OUTSIDE AIR
RELIEF AIR
RETURN AIR
SUPPLY AIR
TRANSFER AIR
GRILLES, REGISTERS & DIFFUSERS TAG
CFM
THROW-150FPM/ 100FPM/ 50FPM
NECK SIZE / MODULE SIZE
EXISTING DUCT TAG
OVAL DUCT SIZE TAG (WIDTH / HEIGHT)
SQUARE DUCT SIZE TAG (WIDTH x HEIGHT)
HVAC SYMBOLS
RECTANGULAR SUPPLY/OUTSIDE AIR DUCT RISE
RECTANGULAR RETURN/TRANSFER AIR DUCT RISE
MECHANICAL EQUIPMENT TAGS
ROUND DUCT SIZE TAG (DIAMETER)
LINEAR DIFFUSER TAG
CFM
TYPE (SEE SCHEDULE) NUMBER OF SLOTS /
ACTIVE SLOT LENGTH (PLENUM
LENGTH) / NECK SIZE
DUCT BEING DEMOLISHED
ELEVATION (CENTER OF FACE)
ROUND SUPPLY/OUTSIDE AIR DUCT RISE
ROUND RETURN/TRANSFER AIR DUCT RISE
RECTANGULAR EXHAUST/RELIEF AIR DUCT RISE
ROUND EXHAUST/RELIEF AIR DUCT RISE
DROP
DROP
DROP
DROP
DROP
DROP
GREASE EXHAUST AIR
SMOKE EXHAUST AIR
EQUIPMENT BY OTHERS
(REFER TO OTHER DISCIPLINE
FOR ADDITIONAL
INFORMATION)
EXISTING
EQUIPMENT TO
REMAIN
EXHAUST GAS FLUE
COMBUSTION AIR
CONDITIONED OUTSIDE AIR
Ø ROUND
ABV ABOVE
AC AIR CONDITIONING
AD AREA DRAIN
ADD ADDENDUM
AFF ABOVE FINISHED FLOOR
AFUE ANNUAL FUEL UTILIZATION
EFFICIENCY
ALT ALTERNATE
AP ACCESS PANEL
ARCH ARCHITECT/ARCHITECTURAL
BFF BELOW FINISHED FLOOR
BLW BELOW
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER
HOUR
CAP CAPACITY
CB CATCH BASIN
CFM CUBIC FEET PER MINUTE
CLG CEILING
CO CLEAN OUT
CW COLD WATER
D DEGREE
DB DRY BULB
DIA DIAMETER
DN DOWN
DW DISTILLED WATER
EA EACH
EAT ENTERING AIR TEMPERATURE
ELEC ELECTRICAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATURE
E/A EXHAUST AIR
EXIST EXISTING
F DEGREES FAHRENHEIT
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FL FLOOR
FO FUEL OIL
FOV FUEL OIL VENT
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FPM FEET PER MINUTE
FS FLOOR SINK
FT FOOT/FEET
FTR FIN TUBE RADIATION
GAL GALLON
GF GAS-FIRED
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
GW GREASE WASTE
HB HOSE BIB
HP HORSE POWER
HTG HEATING
HTR HEATER
HW HOT WATER
HYD HYDRANT
ID INDIRECT
IN INCH
INV INVERT
LB POUND
LB/HR POUNDS PER HOUR
LAT LEAVING AIR TEMPERATURE
LP LOW PRESSURE
LPG LIQUEFIED PETROLEUM GAS
LVR LOUVER
LWT LEAVING WATER
TEMPERATURE
M/A MIXED AIR
MAX MAXIMUM
MBH ONE THOUSAND BTU PER
HOUR
MCF ONE THOUSAND CUBIC FEET
MD MOTORIZED DAMPER
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTR MOTOR
MU/A MAKE-UP/AIR
NC NOISE CRITERIA
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NUMBER
NO NORMALLY OPEN
NTS NOT TO SCALE
O OXYGEN
O/A OUTSIDE AIR
ORD OVERFLOW ROOF DRAIN
PD PRESSURE DROP
PIV POST INDICATOR VALVE
PLBG PLUMBING
PRESS PRESSURE
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH
GAUGE
PWR POWER
R DUCT RISER
R/A RETURN AIR
RCP RADIANT CEILING PANEL
RD ROOF DRAIN
REC RECESSED
RED REDUCER
RH RELATIVE HUMIDITY
RL/A RELIEF AIR
RM ROOM
RPM REVOLUTIONS PER MINUTE
RW RAIN WATER
SF SQUARE FOOT
S/A SUPPLY AIR
SAN SANITARY
SF SQUARE FOOT
SD SMOKE DAMPER
SM SURFACE MOUNT
SP STANDPIPE
SP STATIC PRESSURE
STM STEAM
T THERMOSTAT
TD TEMPERATURE DROP
TDR TRENCH DRAIN
TEMP TEMPERATURE
TYP TYPICAL
UG UNDERGROUND
VAC VACUUM
V VENT
VAV VARIABLE AIR VOLUME
VENT VENTILATION
VTR VENT THROUGH ROOF
W WASTE
WB WET BULB
WCO WALL CLEAN OUT
WH WALL HYDRANT
ABBREVIATIONS
48"x2 1/2"
SLB3 400
10" / 24x24
SD3 300
12" / ---
SD9 400
LINEAR BAR GRILLE
LINEAR SLOT
DIFFUSER
PERFORATED
DIFFUSER WITH
DEFLECTORS
ROUND DIFFUSER
WITH ADJUSTABLE
PATTERNS
LOUVERED DOUBLE
DEFLECTION GRILLE 12"x10"
SG5 500
TYPE (SEE SCHEDULE)
10" / 24x24 H-5/7/1422
SD1 400
3-CONE DIFFUSER
THROW PATTERN
MAX NC RATING
1 / 4' - 0" / 8"
LSD1 200
8' - 0"AFF
1 / 4' - 0" / 8"
LSD1 200
6' - 0"
1 / 4' - 0" / 8"
LSD1 200
SECTION TOTAL TRACK LENGTH
12"x10" / 24x12
RG11 500
LOUVERED GRILLE
12"x10" / 24x24
RG2 500
EGGCRATE RETURN
GRILLE
BOTTOM OF
EQUIPMENT
ELEVATION
HEATING
COIL
FLOW
OPERATING
WEIGHT NOT
INCLUDING CURB
FUEL INPUT
GAS PIPE
FLOW
NOMINAL
COOLING
CAPACITY
2" DOM. WM
PIPE ACCESSORY TAGS
DOMESTIC WATER METER
BALANCING VALVE
1/4 TURN BALL VALVE
CHECK VALVE
3-WAY MIXING VALVE
MOTORIZED CONTROL VALVE
3 WAY MOTORIZED CONTROL
VALVE
PRESSURE REDUCING VALVE
REFRIGERANT SOLENOID
VALVE
BUTTERFLY VALVE
2" BALANCING
2" SHUTOFF
2" CHECK
2" TMV
2" M-CONTROL
2" 3-WAY CONTROL
2" PRV
3/8" SOLENOID
2" BUTTERFLY
DATA DEVICE TAGS
RTU-XX
EQUIPMENT ID
SYMBOL
SENSOR
MANUAL SWITCH
THERMOSTAT
TEMPERATURE & HUMIDITY SENSOR
HUMIDITY SENSOR
NITROGEN DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
CARBON DIOXIDE SENSOR
HUMIDISTAT
CAP
PLUG
GWR
GWS
GEOTHERMAL WATER RETURN
GEOTHERMAL WATER SUPPLY
EXISTING
RELOCATED
EQUIPMENT
AC AIR CONDITIONING UNIT
ACCU AIR COOLING CONDENSING UNIT
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
B BOILER
CH CHILLER
CT COOLING TOWER
CUH CABINET UNIT HEATER
CHWP CHILLED WATER PUMP
DBP DOMESTIC WATER BOOSTER PUMP
DC DUCT MOUNTED COIL
DCP DOMESTIC WATER CIRCULATING
PUMP
EF EXHAUST FAN
EDC ELECTRIC DUCT COIL
ET EXPANSION TANK
EWH ELECTRIC WATER HEATER
FCU FAN COIL UNIT
FP FIRE PUMP
GI GREASE INTERCEPTOR
GRV GRAVITY ROOF
VENTILATOR
HWP HEATING WATER PUMP
HRU HEAT RECOVERY UNIT
PRV POWER ROOF VENTILATOR
RE RETURN/EXHAUST FAN
RTU ROOFTOP UNIT
SP SUMP PUMP
UH UNIT HEATER
WH WATER HEATER
EQUIPMENT ABBREVIATIONS
F S C B M D
DAMPER TAGS
MOTORIZED DAMPER
BACKDRAFT DAMPERFIRE DAMPER
SMOKE DAMPER
COMB. FIRE/SMOKE DAMPER
HVAC-CP-XBMS CONTROL PANEL
MANUAL BALANCING DAMPER
12"x12" S/A
PANEL NAME
CONDENSATE EXHAUST AIR
18"x18" S/A
18"x18" S-O/A
18"x18" O/A
18"x18" R/A
18"x18" T/A
18"x18" E/A
18"x18" L/A
18"x18" GE/A
18"x18" CE/A
18"x18" SE/A
6"Ø FLUE
6"Ø C/A
* NOTE *
ALL GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL OTHER DRAWINGS
IN THIS SET. THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR
MAY NOT BE USED IN THIS SET OF DRAWINGS.
NECK SIZE / MODULE SIZE
POINT WHERE NEW CONNECTS TO EXISTING
(D)
(D)
SD1
TYPE (SEE SCHEDULE)
CFM
TS TEMPERATURE SENSOR
VAV-XX
GENERAL HVAC NOTES
1 CONTRACTOR SHALL LOCATE THERMOSTATS AND TEMPERATURE
SENSORS AT 4'-0" AFF, A MINIMUM OF 8" FROM LIGHT SWITCH.
2 REFER TO HVAC DRAWINGS FOR TEMPERATURE SENSOR
LOCATIONS.
GENERAL PROJECT NOTES
1 THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR
FIELD VERIFYING, PRIOR TO FINAL BID, ALL EXISTING CONDITIONS
FOR PLUMBING AND MECHANICAL SYSTEMS WITHIN TENANT
SPACE AND WITHIN CLOSE PROXIMITY OF TENANT SPACE.
2 THIS CONTRACTOR SHALL VISIT THE SITE, PRIOR TO FINAL
BIDDING, AND VERIFY ALL EXISTING SITE CONDITIONS. PROVIDE
ALL MATERIAL AND COMPONENTS NEEDED.
3 THE CONTRACTOR SHALL BE FAMILIAR WITH ALL THE
CONDITIONS BOTH EXISTING AND THOSE ILLUSTRATED BY THESE
DOCUMENTS AS WELL AS THOSE WHICH CAN BE REASONABLY
ANTICIPATED.
4 FINAL PRODUCT SHALL BE A COMPLETE AND FUNCTIONING
SYSTEM, AND SHALL CONFORM TO ALL REQUIREMENTS OF
APPLICABLE FEDERAL, STATE, AND LOCAL CODES, INCLUDING
BUT NOT LIMITED TO THE UNIFORM MECHANICAL CODE 2021
EDITION.
5 PENETRATIONS OF RATED ASSEMBLIES SHALL BE FIRE STOPPED.
FIRE STOPPING SHALL BE AN APPROVED MATERIAL AS
PRESCRIBED IN CSFM STANDARD 43-1 AND SHALL BE U.L. LISTED.
6 MAINTAIN CLEAR ACCESS TO SERVICE EQUIPMENT AND OTHER
ACCESSORIES REQUIRING SERVICE, VISUAL INSPECTION OR
HAND OPERATION. WHERE INDICATED OR REQUIRED, PROVIDE
ACCESS PANELS OF THE TYPE SELECTED TO SUIT MATERIALS IN
WHICH INSTALLED.
7 FOR DETAILS, EQUIPMENT CONNECTIONS, AND PIPE SIZES NOT
SHOWN ON THE SEGMENTS, REFER TO DETAILS, SCHEDULES,
AND SPECIFICATIONS.
8 INSTALL ALL EQUIPMENT IN ACCORDANCE WITH THE RESPECTIVE
MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS, AT A
LEVEL OF QUALITY AND WORKMANSHIP CONSISTENT WITH THE
SPECIFICATIONS.
9 LOCATIONS OF PIPING, DUCTWORK AND EQUIPMENT AS
INDICATED ON THE DRAWING, ARE APPROXIMATE AND SUBJECT
TO MINOR ADJUSTMENTS IN THE FIELD. WORK SHALL BE
COORDINATED WITH ALL OTHER TRADES TO AVOID
INTERFERENCE IN THE FIELD.
10 THE CONTRACTOR'S WORK SCHEDULE SHALL BE SUBMITTED TO
AND APPROVED BY THE OWNER.
11 PRIOR TO STARTING WORK, SUBMIT SHOP DRAWINGS FOR ALL
MECHANICAL EQUIPMENT AND CONTROLS EQUIPMENT.
12 CONTRACTOR SHALL OBTAIN AND PAY FOR ALL NECESSARY
PERMITS AND SHALL ARRANGE FOR ALL INSPECTIONS AS
REQUIRED.
13 PROVIDE ONE YEAR WARRANTY FOR ALL WORKMANSHIP AND
MATERIALS AFTER THE DATE OF FINAL ACCEPTANCE.
14 EACH DETAIL INCLUDED IN THIS SET OF DOCUMENTS APPLIES TO
THIS PROJECT REGARDLESS IF EACH DETAIL HAS BEEN
REFERENCED ON THE PLANS OR NOT.
MECHANICAL SHEET LIST
SHEET DESCRIPTION
M001 MECHANICAL GENERAL INFO & SYMBOL LEGEND
M101 FIRST FLOOR MECHANICAL PLAN
M103A AREA B FIRST FLOOR ENLARGED PLAN
M103B AREA B SECOND FLOOR ENLARGED PLAN
M105 AREA D FIRST AND SECOND FLOOR ENLARGED PLANS
M106 AREA E ENLARGED PLAN
M500 MECHANICAL DETAILS & SCHEDULES
R E
G
IS
T E R
E
D
PROFESS IONA
L
E N G
I N
E E
R
S
O
UTH DAKO
T
A
15404
BRADEN S.
COX
REG . NO .
architecture +engineering
SEVEN
GENERATIONS
DESCRIPTIONDATEMARK
U.S. DEPARTMENT OF THE
INTERIOR BUREAU OF INDIAN
AFFAIRS
OFMC-GREAT PLAINS
115 4TH AVENUE SE SUITE 400,
MC202 ABERDEEN, SOUTH DAKOTA
57401 PHONE: 605-226-0877
FAX: 605-226-0881
ISSUE:
BIA #:
DWG:
DRAWN BY:
CHECKED BY:
SHEET
TITLE:
SHEET:
600 E. Michigan Ave., Suite B
Kalamazoo, MI 49007
P: 269.927.0144 www.7genae.com
259 E. Michigan Ave., Suite
Kalamazoo, MI 49007
P: 269.585.2255
100% BID DOCUMENTS
99% CD9/21/22
100% BID DOCUMENTS
70% PD7/21/22
BIA CONCUR:
BUREAU OF INDIAN AFFAIRS DATE
GREAT PLAINS REGION
DIVISION OF FACILITIES
100% CD11/28/22
1/26/23
100% BID1/26/23
CHEYENNE
EAGLE
BUTTE
SCHOOL
BIA
2004 E STREET,
EAGLE BUTTE, SD
57625
7GEN PROJECT NUMBER: 221101
M001
MECHANICAL
GENERAL INFO &
SYMBOL LEGEND
MC
BSC
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD FD FD
FD FD
FD
FD FD FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FDFD
FD
FD
FD
FD
FD
FD
FD
AREA A
AREA B
AREA A
AREA B
A R
EA
A
A R
EA
C
AR
EA
A
AR
EA
C
AREA B
AREA D
A R
EA
B
A R
EA
C
AREA C
AREA D
AREA D
AREA E
AREA D
AREA E
H W S
H W S
H W R
HWS
HWS
HWS
HWS
HWR
DH
DH
T
T
T
T
T T T
T
T
TTTT
TT
T T T
T
T
T
T
T
T
T T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
TT
T T T T T T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
C N
2"
2"
2 1/2"
3/4"
T
U P
DN
D N
U P
DN D
N
D N
DN
D N
DN
UP
UP
UP
UP
UP
UP
UP
DN
D N
D N
D N
D N
D N
5 1
H-1
H -71
H -63
H -5
H -3
H -3
K-9
K -5
K -1
K-20
K -1
178A
H -9
109B
H -6
H -63B a
K-26
H -8
H -8
B
D
C
B
149A
B
H-18
142C
155A
152F
152E
A
A
B
A28
A
A
A
A
H-79
H-71
H-38
H-39
H-35
H-33
H-34
H-41
H-32
H-30
H-27
H-31
H-26
H-23 H-25
H-24
H-18
H-19H-20H-16H-12
H-8
H-11
H-9
H-8
H-6
H-3
XX
H-2
H-116
H-54
H-64
H-66
H-68
H-69
H-70
H-67
H-92
H-93
H-91
H-88
H-81
H-90
H-89
H-80
H-82
H-81
H-74
H-75
H-82
H-87
H-94
H-96
H-95
H-86
H-84
H-88
H-76
H-48
H-43
H-49
H-42
H-58
H-62
H-59
H-60
H-61
H-57
H-44
H-46
H-47
H-50 H-65
H-115
H-100
H-116
H-116 H-101
H-106
H-107
H-110
H-115
H-114
H-105
H-104
H-111
H-105
H-97
H-9
H-56
H-14
118A 118B
H124
119A
119B
120B
120A
121A
121B
116115112
112B 112C 112D
111A
109A
109C
109D
109E
109B
108 107 106
105 104
122123
122A
132 136
133 134
137 138
140 141 142
142B
145146147148149
149A
149B
149C
A28
A33
A34
A37
152B152A
150G
152D
152E
152F
153A
153B
154A
155B
155A
154B
171173174175176177
170170169168
129B
K-9
K-1
K-10
K-17
K-11
K-16
K-15
K-14
K-12
K-13
K-8
K-2
K-3
K-7
K-5
K-6
K-4
K-19
K-31
K-30
K-29
K-25
K-26
K-27
K-28
K-20
K-22
K-23
K-24
H-37
A28B
A33B
K-18
K-20 K-21
H-15
H-63
H-1
H-63B
142C
A34B
A37B
A54 A52
A26
140A 142A
M103A
M105
M106
HATCHED AREAS ARE AREAS OUT OF SCOPE
HATCHED AREAS ARE AREAS OUT OF SCOPE
HATCHED AREAS ARE AREAS OUT OF SCOPE
SCALE: NTSM101
FIRST FLOOR MECHANICAL PLAN1
R E
G
IS
T E R
E
D
PROFESS IONA
L
E N G
I N
E E
R
S
O
UTH DAKO
T
A
15404
BRADEN S.
COX
REG . NO .
architecture +engineering
SEVEN
GENERATIONS
DESCRIPTIONDATEMARK
U.S. DEPARTMENT OF THE
INTERIOR BUREAU OF INDIAN
AFFAIRS
OFMC-GREAT PLAINS
115 4TH AVENUE SE SUITE 400,
MC202 ABERDEEN, SOUTH DAKOTA
57401 PHONE: 605-226-0877
FAX: 605-226-0881
ISSUE:
BIA #:
DWG:
DRAWN BY:
CHECKED BY:
SHEET
TITLE:
SHEET:
600 E. Michigan Ave., Suite B
Kalamazoo, MI 49007
P: 269.927.0144 www.7genae.com
259 E. Michigan Ave., Suite
Kalamazoo, MI 49007
P: 269.585.2255
100% BID DOCUMENTS
99% CD9/21/22
100% BID DOCUMENTS
70% PD7/21/22
BIA CONCUR:
BUREAU OF INDIAN AFFAIRS DATE
GREAT PLAINS REGION
DIVISION OF FACILITIES
100% CD11/28/22
1/26/23
100% BID1/26/23
CHEYENNE
EAGLE
BUTTE
SCHOOL
BIA
2004 E STREET,
EAGLE BUTTE, SD
57625
7GEN PROJECT NUMBER: 221101
M101
FIRST FLOOR
MECHANICAL PLAN
MC
BSC
MECHANICAL NOTES
1 CONTRACTOR SHALL PROVIDE A COMPLETE AND WORKING
SYSTEM.
2 THIS DRAWING IS DIAGRAMMATIC IN NATURE AND SHALL NOT
BE SCALED.
A CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE A
COMPLETE AND WORKING SYSTEM.
3 THIS DRAWING IS BASED ON VISUALLY OBSERVABLE EXISTING
CONDITIONS AS OF THE TIME OF DESIGN. CONTRACTOR SHALL
BE RESPONSIBLE TO FULLY VERIFY ALL EXISTING CONDITIONS,
COMPONENTS, ETC. PRIOR TO THE START OF THE WORK. ANY
DEVIATION FROM THIS DRAWING IN KIND, OR IN LOCATION
EXCEEDING 1'-0", SHALL BE BROUGHT TO THE ATTENTION OF THE
ENGINEER.
AREA B AREA B
AREA B
AR
E A B
TT
T T T
T
T
T
T
T
T
T T
T
T
T
T
T
T
T
T
T
T
T
D N
DN
D N
DN
UP
UP
UP
UP
UP
UP
UP
DN
H-1
109B
B
D
C
B
H-8
118A 118B
H124
119A
119B
120B
120A
121A
121B
116115112
112B 112C 112D
111A
109A
109C
109D
109E
109B
108 107 106
105 104
122123
122A
H-1
TS1
1 1
TS TS
TS
TS
TS
TS
TS
1 TS TS
TS
TS
TS
TS TS
TS
TS
TS
TS
TS
TS
TS
TS
2 2
2 2
2 2 2
2 2
2 2
R E
G
IS
T E R
E
D
PROFESS IONA
L
E N G
I N
E E
R
S
O
UTH DAKO
T
A
15404
BRADEN S.
COX
REG . NO .
architecture +engineering
SEVEN
GENERATIONS
DESCRIPTIONDATEMARK
U.S. DEPARTMENT OF THE
INTERIOR BUREAU OF INDIAN
AFFAIRS
OFMC-GREAT PLAINS
115 4TH AVENUE SE SUITE 400,
MC202 ABERDEEN, SOUTH DAKOTA
57401 PHONE: 605-226-0877
FAX: 605-226-0881
ISSUE:
BIA #:
DWG:
DRAWN BY:
CHECKED BY:
SHEET
TITLE:
SHEET:
600 E. Michigan Ave., Suite B
Kalamazoo, MI 49007
P: 269.927.0144 www.7genae.com
259 E. Michigan Ave., Suite
Kalamazoo, MI 49007
P: 269.585.2255
100% BID DOCUMENTS
99% CD9/21/22
100% BID DOCUMENTS
70% PD7/21/22
BIA CONCUR:
BUREAU OF INDIAN AFFAIRS DATE
GREAT PLAINS REGION
DIVISION OF FACILITIES
100% CD11/28/22
1/26/23
100% BID1/26/23
CHEYENNE
EAGLE
BUTTE
SCHOOL
BIA
2004 E STREET,
EAGLE BUTTE, SD
57625
7GEN PROJECT NUMBER: 221101
M103A
AREA B FIRST FLOOR
ENLARGED PLAN
MC
BSC
KEYNOTES
1 REMOVE EXISTING PNEUMATIC THERMOSTAT WITH
ASSOCIATED PNEUMATIC VALVE AND CONNECTIONS,
REPLACE WITH NEW TEMPERATURE SENSOR . LOCATE THE NEW
SENSORS IN THE SAME LOCATION OF THE DEMOLISHED
THERMOSTAT.
2 DEMOLISH EXISTING PNEUMATIC VALVE. REPLACE WITH NEW
THROTTLE CONTROL VALVE AND ACTUATOR SIZED TO MATCH
EXISTING PIPING SIZE AND STEAM CAPACITY OF THE EXISTING
UNIT. REFER TO SPECIFICATIONS AND CONTROL DIAGRAM
FOR INFORMATION.
3 CONTROLLER MOUNTED ON THE WALL AS HIGH AS POSSIBLE (
ABOVE THE CEILING). CONTROLLER SHALL BE MOUNTED IN A
METAL ENCLOSURE. COORDINATE ENCLOSURE WITH THE
ELECTRICAL CONTRACTOR. CONTROLLER SHALL BE
CONNECTED TO SERVER AND 2 TEMPERATURE SENSORS AND
CONTROL VALVES AS REQUIRED. REFER TO SPECIFICATIONS
AND CONTROL DIAGRAMS FOR INFORMATION.
MECHANICAL NOTES
1 CONTRACTOR SHALL PROVIDE A COMPLETE AND WORKING
SYSTEM.
2 THIS DRAWING IS DIAGRAMMATIC IN NATURE AND SHALL NOT
BE SCALED.
A CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE A
COMPLETE AND WORKING SYSTEM.
3 THIS DRAWING IS BASED ON VISUALLY OBSERVABLE EXISTING
CONDITIONS AS OF THE TIME OF DESIGN. CONTRACTOR SHALL
BE RESPONSIBLE TO FULLY VERIFY ALL EXISTING CONDITIONS,
COMPONENTS, ETC. PRIOR TO THE START OF THE WORK. ANY
DEVIATION FROM THIS DRAWING IN KIND, OR IN LOCATION
EXCEEDING 1'-0", SHALL BE BROUGHT TO THE ATTENTION OF THE
ENGINEER.
SCALE: 1" = 10'-0"M103A
HVAC PLAN - LEVEL 1 AREA B1
M801
AREA B
AREA D
AR
E A B
AR
E A C
A
UP
UP
DN
DN
D N
D N
T
T
T
T
T
L P S
L P R
TS
TS
1 2
TS
TS
R E
G
IS
T E R
E
D
PROFESS IONA
L
E N G
I N
E E
R
S
O
UTH DAKO
T
A
15404
BRADEN S.
COX
REG . NO .
architecture +engineering
SEVEN
GENERATIONS
DESCRIPTIONDATEMARK
U.S. DEPARTMENT OF THE
INTERIOR BUREAU OF INDIAN
AFFAIRS
OFMC-GREAT PLAINS
115 4TH AVENUE SE SUITE 400,
MC202 ABERDEEN, SOUTH DAKOTA
57401 PHONE: 605-226-0877
FAX: 605-226-0881
ISSUE:
BIA #:
DWG:
DRAWN BY:
CHECKED BY:
SHEET
TITLE:
SHEET:
600 E. Michigan Ave., Suite B
Kalamazoo, MI 49007
P: 269.927.0144 www.7genae.com
259 E. Michigan Ave., Suite
Kalamazoo, MI 49007
P: 269.585.2255
100% BID DOCUMENTS
99% CD9/21/22
100% BID DOCUMENTS
70% PD7/21/22
BIA CONCUR:
BUREAU OF INDIAN AFFAIRS DATE
GREAT PLAINS REGION
DIVISION OF FACILITIES
100% CD11/28/22
1/26/23
100% BID1/26/23
CHEYENNE
EAGLE
BUTTE
SCHOOL
BIA
2004 E STREET,
EAGLE BUTTE, SD
57625
7GEN PROJECT NUMBER: 221101
M103B
AREA B SECOND
FLOOR ENLARGED
PLAN
MC
BSC
SCALE: 1" = 10'-0"M103B
HVAC PLAN - LEVEL 2 AREA B1
KEYNOTES
1 REMOVE EXISTING PNEUMATIC THERMOSTAT WITH
ASSOCIATED PNEUMATIC VALVE AND CONNECTIONS,
REPLACE WITH NEW TEMPERATURE SENSOR . LOCATE THE NEW
SENSORS IN THE SAME LOCATION OF THE DEMOLISHED
THERMOSTAT.
2 DEMOLISH EXISTING PNEUMATIC VALVE. REPLACE WITH NEW
THROTTLE CONTROL VALVE AND ACTUATOR SIZED TO MATCH
EXISTING PIPING SIZE AND STEAM CAPACITY OF THE EXISTING
UNIT. REFER TO SPECIFICATIONS AND CONTROL DIAGRAM
FOR INFORMATION.
3 CONTROLLER MOUNTED ON THE WALL AS HIGH AS POSSIBLE (
ABOVE THE CEILING). CONTROLLER SHALL BE MOUNTED IN A
METAL ENCLOSURE. COORDINATE ENCLOSURE WITH THE
ELECTRICAL CONTRACTOR. CONTROLLER SHALL BE
CONNECTED TO SERVER AND 2 TEMPERATURE SENSORS AND
CONTROL VALVES AS REQUIRED. REFER TO SPECIFICATIONS
AND CONTROL DIAGRAMS FOR INFORMATION.
AREA D
T
T
T
TT
T T T T T T
T
T
U P
DN
D N
U P
DN D
N
149A
B
142C
A
A
B
A
A
132 136
133 134
137 138
140 141 142
142B
145146147148149
149A
149B
149C
152B152A
150G
129B
142C
A26
140A 142A
CUH
C-1 C-1 C-1 C-1 C-1
C-1C-1C-1C-1C-1C-1C-1
5'
FT-1
9'
FT-1
5'
FT-1
5'
FT-1
10'
FT-1
6'
FT-1
3'
FT-1
3'
FT-1
10'
FT-1
B
A
A
A
D N
D N
210209
220 219 218 217 216 215
212A
212B
212C
222221
205 206
207203
213A
A36B
A26
TT
TTTTT
T
T
T T
T
T
T
T
T
T T
TS
TS
TS
TS
TS TS
TS
TS
TS
T S
T S
TS
2 2 2
22 2 2 2 2 2 2 2
TS
1 1
222222 2
2 2 2 2 2 2
TS
TS TS
TS TS TS TS TS TS
TS TS
TS
TSTS
TS
T S
1T S
1T S
R E
G
IS
T E R
E
D
PROFESS IONA
L
E N G
I N
E E
R
S
O
UTH DAKO
T
A
15404
BRADEN S.
COX
REG . NO .
architecture +engineering
SEVEN
GENERATIONS
DESCRIPTIONDATEMARK
U.S. DEPARTMENT OF THE
INTERIOR BUREAU OF INDIAN
AFFAIRS
OFMC-GREAT PLAINS
115 4TH AVENUE SE SUITE 400,
MC202 ABERDEEN, SOUTH DAKOTA
57401 PHONE: 605-226-0877
FAX: 605-226-0881
ISSUE:
BIA #:
DWG:
DRAWN BY:
CHECKED BY:
SHEET
TITLE:
SHEET:
600 E. Michigan Ave., Suite B
Kalamazoo, MI 49007
P: 269.927.0144 www.7genae.com
259 E. Michigan Ave., Suite
Kalamazoo, MI 49007
P: 269.585.2255
100% BID DOCUMENTS
99% CD9/21/22
100% BID DOCUMENTS
70% PD7/21/22
BIA CONCUR:
BUREAU OF INDIAN AFFAIRS DATE
GREAT PLAINS REGION
DIVISION OF FACILITIES
100% CD11/28/22
1/26/23
100% BID1/26/23
CHEYENNE
EAGLE
BUTTE
SCHOOL
BIA
2004 E STREET,
EAGLE BUTTE, SD
57625
7GEN PROJECT NUMBER: 221101
M105
AREA D FIRST AND
SECOND FLOOR
ENLARGED PLANS
MC
BSC
KEYNOTES
1 REMOVE EXISTING PNEUMATIC THERMOSTAT WITH
ASSOCIATED PNEUMATIC VALVE AND CONNECTIONS,
REPLACE WITH NEW TEMPERATURE SENSOR . LOCATE THE NEW
SENSORS IN THE SAME LOCATION OF THE DEMOLISHED
THERMOSTAT.
MECHANICAL NOTES
1 CONTRACTOR SHALL PROVIDE A COMPLETE AND WORKING
SYSTEM.
2 THIS DRAWING IS DIAGRAMMATIC IN NATURE AND SHALL NOT
BE SCALED.
A CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE A
COMPLETE AND WORKING SYSTEM.
3 THIS DRAWING IS BASED ON VISUALLY OBSERVABLE EXISTING
CONDITIONS AS OF THE TIME OF DESIGN. CONTRACTOR SHALL
BE RESPONSIBLE TO FULLY VERIFY ALL EXISTING CONDITIONS,
COMPONENTS, ETC. PRIOR TO THE START OF THE WORK. ANY
DEVIATION FROM THIS DRAWING IN KIND, OR IN LOCATION
EXCEEDING 1'-0", SHALL BE BROUGHT TO THE ATTENTION OF THE
ENGINEER.
SCALE: 1" = 10'-0"M105
HVAC PLAN - LEVEL 1 AREA D1
SCALE: 1" = 10'-0"M105
HVAC PLAN - LEVEL 2 AREA D2
AREA E
AREA D
AREA E
T
T
T
T
T T T
T
T
TTTT
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
D N
D N
5 1
178A a
155A
152F
152E
A28
A
A
A28
A33
A34
A37
152D
152E
152F
153A
153B
154A
155B
155A
154B
171173174175176177
170170169168
A28B
A33B
A34B
A37B
A54 A52
TS
TS
TS
TS
TS1
TS1
TS
TS
TS
TS
TS
TS
TS
TS
TS TS
TS
TS
TS
TS
TS
TS
TS
TS TS TS
TS
2 2 2 2 2 2
2222222
1 1 1 1
R E
G
IS
T E R
E
D
PROFESS IONA
L
E N G
I N
E E
R
S
O
UTH DAKO
T
A
15404
BRADEN S.
COX
REG . NO .
architecture +engineering
SEVEN
GENERATIONS
DESCRIPTIONDATEMARK
U.S. DEPARTMENT OF THE
INTERIOR BUREAU OF INDIAN
AFFAIRS
OFMC-GREAT PLAINS
115 4TH AVENUE SE SUITE 400,
MC202 ABERDEEN, SOUTH DAKOTA
57401 PHONE: 605-226-0877
FAX: 605-226-0881
ISSUE:
BIA #:
DWG:
DRAWN BY:
CHECKED BY:
SHEET
TITLE:
SHEET:
600 E. Michigan Ave., Suite B
Kalamazoo, MI 49007
P: 269.927.0144 www.7genae.com
259 E. Michigan Ave., Suite
Kalamazoo, MI 49007
P: 269.585.2255
100% BID DOCUMENTS
99% CD9/21/22
100% BID DOCUMENTS
70% PD7/21/22
BIA CONCUR:
BUREAU OF INDIAN AFFAIRS DATE
GREAT PLAINS REGION
DIVISION OF FACILITIES
100% CD11/28/22
1/26/23
100% BID1/26/23
CHEYENNE
EAGLE
BUTTE
SCHOOL
BIA
2004 E STREET,
EAGLE BUTTE, SD
57625
7GEN PROJECT NUMBER: 221101
M106
AREA E ENLARGED
PLAN
MC
BSC
KEYNOTES
1 REMOVE EXISTING PNEUMATIC THERMOSTAT WITH
ASSOCIATED PNEUMATIC VALVE AND CONNECTIONS,
REPLACE WITH NEW TEMPERATURE SENSOR . LOCATE THE NEW
SENSORS IN THE SAME LOCATION OF THE DEMOLISHED
THERMOSTAT.
2 DEMOLISH EXISTING PNEUMATIC VALVE. REPLACE WITH NEW
THROTTLE CONTROL VALVE AND ACTUATOR SIZED TO MATCH
EXISTING PIPING SIZE AND STEAM CAPACITY OF THE EXISTING
UNIT. REFER TO SPECIFICATIONS AND CONTROL DIAGRAM
FOR INFORMATION.
3 CONTROLLER MOUNTED ON THE WALL AS HIGH AS POSSIBLE (
ABOVE THE CEILING). CONTROLLER SHALL BE MOUNTED IN A
METAL ENCLOSURE. COORDINATE ENCLOSURE WITH THE
ELECTRICAL CONTRACTOR. CONTROLLER SHALL BE
CONNECTED TO SERVER AND 2 TEMPERATURE SENSORS AND
CONTROL VALVES AS REQUIRED. REFER TO SPECIFICATIONS
AND CONTROL DIAGRAMS FOR INFORMATION.
MECHANICAL NOTES
1 CONTRACTOR SHALL PROVIDE A COMPLETE AND WORKING
SYSTEM.
2 THIS DRAWING IS DIAGRAMMATIC IN NATURE AND SHALL NOT
BE SCALED.
A CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE A
COMPLETE AND WORKING SYSTEM.
3 THIS DRAWING IS BASED ON VISUALLY OBSERVABLE EXISTING
CONDITIONS AS OF THE TIME OF DESIGN. CONTRACTOR SHALL
BE RESPONSIBLE TO FULLY VERIFY ALL EXISTING CONDITIONS,
COMPONENTS, ETC. PRIOR TO THE START OF THE WORK. ANY
DEVIATION FROM THIS DRAWING IN KIND, OR IN LOCATION
EXCEEDING 1'-0", SHALL BE BROUGHT TO THE ATTENTION OF THE
ENGINEER.
NORTH
SCALE: 1" = 10'-0"
HVAC PLAN - LEVEL 1 AREA E
X
I/O CONTROL POINTS
.SUPPLY FAN STATUS (IF APPLICABLE)
HEATING UNIT CONTROL
SPACE AIR TEMPERATURE .X
.FILTER DIFF PRESSURE
.XDISCHARGE AIR TEMP
INPUT OUTPUT
EXISTING SCHNEIDER
ELECTRIC REMOTE
SERVER
TS
NEW ROOM TEMPERATURE
SENSOR
STEAM
PIPING
STEAM COIL
LOW PRESSURE STEAM IN
LOW PRESSURE
CONDENSATE RETURN
EXISTING STEAM FIN TUBE
RADIATOR / STEAM
CABINET UNIT
VENTILATOR
NEW DDC STEAM VALVE AND
MODULATING ACTUATOR
TS
NEW SCHNEIDER ELECTRIC
CONTROLLER FOR EVERY 2
ROOMS
SEQUENCE OF OPERATIONS :
BMS WILL DETERMINE OCCUPIED/UNOCCUPIED MODES.
OCCUPIED MODE:
STEAM VALVE ACTUATOR WILL MODULATE TO SATISFY THE SPACE
TEMPERATURE SET POINT
UNOCCUPIED MODE:
IF A ZONE IS CALLING FOR NIGHT HEAT, A SIGNAL WILL BE SENT TO
THE STEAM CONTROL VALVE TO OPEN. AN OVERRIDE BUTTON AT
THE THERMOSTAT CONTROL VALVE WILL INITIATE THE OCCUPIED
MODE FOR A PERIOD OF 2 HOURS WHENEVER THE BUTTON IS
PRESSED.
EXISTING
CONDENSATE
RETURN
EXISTING STEAM COIL
REDUCER (IF
REQUIRED),
TYPICAL
DIELECTRIC UNION
EXISTING COIL PIPING
CONNECTION
EXISTING STEAM
SUPPLY PIPING
NEW CONTROL VALVE
M
CONTROL WIRING ROUTED TO THE
CONTROLLER, REFER TO THE PLAN
VALVE ASSEMBLY MODEL NUMBER
VALVE AND ACTUATOR SCHEDULE
X
5.5SCHNEIDER ELECTRIC Vx-72x1-xxx-4-P
PORT NUMBER VALVE SIZE CV Kvs
3/4 in 4.8
N.O N.C
ACTUATOR CLOSE OFF PRESSURE
NOTE: REFER TO SCHNEIDER ELECTRIC'S VALVE CATALOGUE FOR MORE INFORMATION ABOUT VALVE AND ACTUATORS.
R E
G
IS
T E R
E
D
PROFESS IONA
L
E N G
I N
E E
R
S
O
UTH DAKO
T
A
15404
BRADEN S.
COX
REG . NO .
architecture +engineering
SEVEN
GENERATIONS
DESCRIPTIONDATEMARK
U.S. DEPARTMENT OF THE
INTERIOR BUREAU OF INDIAN
AFFAIRS
OFMC-GREAT PLAINS
115 4TH AVENUE SE SUITE 400,
MC202 ABERDEEN, SOUTH DAKOTA
57401 PHONE: 605-226-0877
FAX: 605-226-0881
ISSUE:
BIA #:
DWG:
DRAWN BY:
CHECKED BY:
SHEET
TITLE:
SHEET:
600 E. Michigan Ave., Suite B
Kalamazoo, MI 49007
P: 269.927.0144 www.7genae.com
259 E. Michigan Ave., Suite
Kalamazoo, MI 49007
P: 269.585.2255
100% BID DOCUMENTS
99% CD9/21/22
100% BID DOCUMENTS
70% PD7/21/22
BIA CONCUR:
BUREAU OF INDIAN AFFAIRS DATE
GREAT PLAINS REGION
DIVISION OF FACILITIES
100% CD11/28/22
1/26/23
100% BID1/26/23
CHEYENNE
EAGLE
BUTTE
SCHOOL
BIA
2004 E STREET,
EAGLE BUTTE, SD
57625
7GEN PROJECT NUMBER: 221101
M500
MECHANICAL DETAILS
& SCHEDULES
MC
BCS
SCALE: NTSM500
STEAM FIN TUBE RADIATORS/ COILS CONTROL DIAGRAM1
SCALE: NTSM500
EXISTING DDC SERVER AT HIGH SCHOOL BUILDING2
SCALE: NTSM500
STEAM COIL PIPING DETAIL3
J
K O
S T
T D
D
EM
P
P
J R
E T
H T
F
F
F F
D
F
P
FR
L -3
CLNG
J
F S
D
V
M
ES
ML
DC
CL
CR
MD
E
B
D
S
P
N
TV
N
N
IG
G
FI
G
FI
W
P
TP U
SB
A C
EW
C
G
FI
OS
ELECTRICAL SYMBOL NOTES
EXIT LIGHTS. STEM INDICATES WALL MOUNTING. NO STEM INDICATES
CEILING MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S).
ARROW INDICATES DIRECTIONAL ARROW ON ILLUMINATED FACE(S).
THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER. EXAMPLE: THE
WALL MOUNTED EXIT LIGHT TYPE "E1" WITH SINGLE FACE AND
DIRECTIONAL ARROW IS CONNECTED TO CIRCUIT 1.
DEVICES. THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER.
THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE: SPLIT DUPLEX RECEPTACLE IS CONNECTED TO CIRCUIT 1
AND ONE RECEPTACLE OUTLET IS CONTROLLED BY SWITCH "d".
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE
LETTER. EXAMPLE: SINGLE POLE SWITCH "d" TO CONTROL LIGHTING
FIXTURES INDICATED BY "d".
WALL BOX DIMMER WITH SIZE AS INDICATED AT DEVICE. EXAMPLE: 600
WATT WALL BOX DIMMER TO CONTROL LIGHTING FIXTURES INDICATED
BY "e". SEE SPECIFICATIONS FOR WATTAGE IF NOT INDICATED.
SPECIAL CONNECTIONS. THE EQUIPMENT IS INDICATED BY A NUMBER
IN A CIRCLE. SEE THE MOTOR AND EQUIPMENT SCHEDULE FOR THE
LOAD DESCRIPTION AND TYPE OF CONNECTION. THE CIRCUIT
DESIGNATION IS INDICATED BY NUMBER(S) ADJACENT TO THE SYMBOL.
EXAMPLE: EQUIPMENT NO. ELEC-1; 1 PHASE CONNECTION TO
CIRCUITS 2, 4.
MOTOR CONNECTIONS. THE MOTOR IS INDICATED BY A NUMBER
WITHIN OR CHARACTERS ADJACENT TO THE MOTOR SYMBOL. SEE
THE MOTOR AND EQUIPMENT SCHEDULE FOR THE MOTOR
DESCRIPTION AND ELECTRICAL REQUIREMENTS.
TRANSFORMERS. THE TRANSFORMER TYPE IS INDICATED BY A NUMBER
FOLLOWING THE UPPER CASE LETTER "T". SEE THE TRANSFORMER
SCHEDULE OR THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER
DESCRIPTION AND REQUIREMENTS. EXAMPLE: TRANSFORMER TYPE "T1".
PANELBOARDS. PANELBOARD DOORS MAY BE SHOWN TO
INDICATE OPENING SIDE OF RECESSED PANELBOARDS. SEE
PANELBOARD IDENTIFICATION FOR DESIGNATION CODES.
CONDUIT SHOWN WITHOUT SLASH MARKS SHALL CONTAIN 1 # 12
CONDUCTOR PER PHASE, NEUTRAL, AND GROUND IN 1/2" CONDUIT
UNLESS SPECIFIC EQUIPMENT REQUIRES A DIFFERENT SIZE.
CONDUIT SHOWN SHALL CONTAIN 1 # 10 CONDUCTOR PER PHASE IN
ELECTRICAL CODE SIZED MINIMUM CONDUIT UNLESS A CONDUCTOR
AND CONDUIT SIZE IS SHOWN ADJACENT.
HOME RUN TO BRANCH CIRCUIT PANELBOARD. THE PANELBOARD
DESIGNATION IS SHOWN ADJACENT TO THE HOME RUN ARROW AS A
NUMERATOR AND THE CIRCUIT DESIGNATION IS SHOWN AS THE
DENOMINATOR. CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES)
ARE SHOWN IN THE PANELBOARD SCHEDULE WITH THE
CORRESPONDING PANELBOARD AND CIRCUIT DESIGNATION.
EXAMPLE: HOME RUN TO PANELBOARD P4N-102; CIRCUITS 1, 3, 5.
SYMBOLSYMBOL SYMBOLDESCRIPTION DESCRIPTION DESCRIPTION
FIRE ALARM HORN W/STROBE
FIRE ALARM BELL
FIRE ALARM BELL W/STROBE
FIRE ALARM CHIME W/STROBE
THERMOSTAT
HUMIDISTAT
ELECTRONIC TIMER
RELAY
CABLE TAP BOX
SAFETY DISC. SWITCH (FUSED)
SAFETY DISC. SWITCH (NON-FUSED)
COMB. MOTOR STARTER (FUSED)
TRANSFORMER
FLOOR JUNCTION BOX
JUNCTION BOX
UTILITY SERVICE POWER POLE
STATIC GROUND RECEPTACLE
SURGERY SERVICE COLUMN
POWER POLE (OPEN OFFICE STYLE)
MULTIOUTLET ASSEMBLY
RECEPTACLE ON CORD REEL
FLOOR DUPLEX RECEPT.
FOURPLEX RECEPTACLE ON
EMERGENCY CIRCUIT
FOURPLEX RECEPTACLE
SINGLE RECEPTACLE
PUSH BUTTON
TIME DELAY SWITCH
TIMER SWITCH
OCCUPANCY SENSOR
DIMMER SWITCH
SWITCH W/PILOT
KEYED SWITCH
4-WAY SWITCH
3-WAY SWITCH
SINGLE POLE SWITCH
BUS DUCT W/ PLUG IN DISCONNECT
PS - D2
T1
PANELBOARD IDENTIFICATION
KEYED NOTE (SEE SCHEDULE)
NUMBER OF SHEET WHERE DETAIL APPEARS
NUMBER OF DETAIL ON SHEET
REVISION NUMBER - SHOWN ON PLANS
ROOM NAME AND NUMBER
ITEM TO BE
REMOVED
AREA NOT IN
CONTRACT
IDENTITY (SEE SCHEDULE)
EXISTING TO REMAIN RELOCATED DEMOLISHED
d ee
2,4
T1
FLOOR CLEARANCE AREA
CONDUIT IN CEILING, FLOOR OR WALL AS REQUIRED BY FIELD
CONDITIONS
CONDUIT IN FLOOR
P4N12
1. EQUIPMENT DESIGNATION:
L = LIGHTING
P = POWER
D = DISTRIBUTION
S = SWITCHBOARD
M = MOTOR CONTROL CENTER
R = RELAY PANEL
2. VOLTAGE DESIGNATION:
1 = 120/240V - 1PH
2 = 240V - 3PH
3 = 208Y/120V - 3PH
4 = 480Y/277V - 3PH
5 = 120/208 - 1PH
6 = SPECIAL
3. SYSTEM DESIGNATION:
N = NORMAL
E = EMERGENCY
C = POWER CONDITIONED
U = UNINTERRUPTIBLE POWER SOURCE
4. FLOOR DESIGNATION:
B = BASEMENT
G = GROUND
1 = FIRST FLOOR
2 = SECOND FLOOR
ETC.
5. PANEL NO. DESIGNATION:
1 = PANELBOARD #1
2 = PANELBOARD #2
3 = PANELBOARD #3
ETC.
FIRE ALARM PULL STATION
FIRE ALARM DOOR HOLDER
FIRE ALARM DOOR CLOSER
FIRE ALARM SHUT DOWN RELAY
CEILING DATA OUTLET
FLOOR DATA OUTLET
# OF VOICE AND # OF DATA PORTS
EXAMPLE 1V2D = 1 VOICE, 2 DATA
P4N-102
1, 3, 5
#10
#12
EXISTING TO REMAIN
EXISTING TO BE REMOVED
NEW
GRAPHICAL REPRESENTATION OF PHASING, TYPICAL FOR ALL
SYMBOLS.
CEILING DUPLEX RECEPT.
SPECIAL RECEPTACLE
CEILING JUNCTION BOX
FLOOR TELEPHONE OUTLET
(MOUNTING HEIGHT)
CLNG
ELEC-1
Room
FIRE ALARM SPEAKER W/STROBE
EXIT LIGHT, WALL-MOUNTED,
SHADING AND ARROWS INDICATE
FACES AND DIRECTION
WALL-MOUNTED FIXTURES, TYPICAL
EXW1
LIGHTING FIXTURE TAG DESCRIPTORS:
TOP VALUE: FIXTURE TYPE ID.
BOTTOM VALUE, NUMBER: CIRCUIT NUMBER, REFER TO
DRAWINGS FOR PANEL.
BOTTOM VALUE, LOWERCASE LETTER: SWITCH DESIGNATION.
ABSENCE OF A SWITCH ID INDICATES FIXTURE IS CONTROLLED BY THE
ONLY SWITCH IN THE SPACE.
"x" IN PLACE OF THE SWITCH ID INDICATES NIGHT LIGHT, UNSWITCHED.
S3
1d
ELECTRIC STRIKE
MAGNETIC LOCK
COMBINATION LOCK
DOOR CONTACT
CARD READER
SECURITY KEYPAD
MOTION DETECTOR
NURSE CALL EMERG. STATION
NURSE CALL CODE BLUE STATION
NURSE CALL DUTY STATION
NURSE CALL STAFF STATION
NURSE CALL PATIENT STATION
NURSE CALL DOME LIGHT
(1-COLOR)
TELEPHONE OUTLET
VOICE/DATA OUTLET
DOOR BELL
DOOR BUZZER
DOOR CHIME
DOOR SIGNAL
VOLUME CONTROL
MICROPHONE OUTLET
1V 2D
CATV OUTLET
TV OUTLET
NURSE CALL DOME LIGHT
(4-COLORS)
NURSE CALL DOME LIGHT
(2-COLORS)
AUTO DOOR PUSH PAD
EMERGENCY LIGHTING UNIT, WALL-
MOUNTED, REMOTE BATTERY
EMERGENCY LIGHTING UNIT, WALL-
MOUNTED, INTEGRAL BATTERY
EMERGENCY LIGHTING UNIT, CEILING-
MOUNTED, INTEGRAL BATTERY
EMERGENCY LIGHTING UNIT, CEILING-
MOUNTED, REMOTE BATTERY
LIGHTING FIXTURES, TYPICAL,
RECTANGULAR FILLED CIRCLES
INDICATE RECESSED, OPEN CIRCLES
INDICATE SURFACE
DIAGONAL LINE INDICATES LENSED
OUTER DOTS INDICATE SUSPENDED
LIGHTING FIXTURES, TYPICAL, ROUND
CENTER DOT INDICATES PENDANT
DIAGONAL LINE INDICATES LENSED
CHEVRON INDICATES WALL WASH
STRIP FIXTURE
DIRECTIONAL LIGHT, TRACK, FLOOD
EXIT LIGHT, CEILING-MOUNTED,
SHADING AND ARROWS INDICATE
FACES AND DIRECTION
LINEAR LIGHT, TAPE LIGHT
EXIT/ELU COMBO
DIAGONAL HATCH INDICATES LIGHT
ON A CRITICAL CIRCUIT
SOLID HATCH INDICATES LIGHT ON
AN EMERGENCY OR LIFE SAFETY
CIRCUIT
POLE/AREA LIGHTS
POST-TOP AREA LIGHT
BOLLARD LIGHT
SPRINKLER FLOW SWITCH
SPRINKLER VALVE TAMPER SWITCH
DUCT SMOKE DETECTOR
CEILING SMOKE DETECTOR
THERMAL DETECTOR
ELECTRICAL SYMBOL LEGEND
# OF COLORS.
NEMA CONFIGURATION
DUPLEX RECEPT. ON EMERG.
CIRCUIT
DUPLEX ISOLATED GROUND RECEPT.
SPLIT DUPLEX RECEPT.
DUPLEX RECEPT.
GFI DUPLEX RECEPT. (FEED
THROUGH)
GFI WEATHERPROOF RECEPT.
DUPLEX RECEPT.
TAMPER-PROOF DUPLEX
RECEPTACLE
DUPLEX RECEPTACLE
WATER COOLER RECEPTACLE
COORDINATE THE LOCATION WITH
THE EQUIPMENT SUPPLIER
GA GAUGE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT
INTERRUPTER
GFP GROUND FAULT PROTECTOR
GND GROUND
GRS GALVANIZED RIGID STEEL
(CONDUIT)
GYP BD GYPSUM BOARD
HOA HANDS-OFF-AUTOMATIC SWITCH
HORIZ HORIZONTAL
HP HORSEPOWER
HPF HIGH POWER FACTOR
HT HEIGHT
HTG HEATING
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
G ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
I/W INTERLOCK WITH
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LOC LOCATE OR LOCATION
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MAX MAXIMUM
MAG.S MAGNETIC STARTER
M/C MOMENTARY CONTACT
MC MECHANICAL CONTRACTOR
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDC MAIN DISTRIBUTION CENTER
MDP MAIN DISTRIBUTION PANEL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT
SW
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MMS MANUAL MOTOR STARTER
MOA MULTIOUTLET ASSEMBLY
MSP MOTOR STARTER
PANELBOARD
MSBD MAIN SWITCHBOARD
MT MOUNT
MT.C EMPTY CONDUIT
MTS MANUAL TRANSFER SWITCH
MTR MOTOR, MOTORIZED
N.C. NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S
ASSOCIATION
NFDS NON-FUSED SAFETY
DISCONNECT SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
N.O. NORMALLY OPEN
NPF NORMAL POWER FACTOR
NTS NOT TO SCALE
OH OVERHEAD
OL OVERLOADS
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PE PNEUMATIC ELECTRIC
PED PEDESTAL
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
PP POWER POLE
PR PAIR
ELECTRICAL ABBREVIATIONS LIST
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE
(CONDUIT)
PWR POWER
QUAN QUANTITY
RCPT RECEPTACLE
REQD REQUIRED
RM ROOM
RSC RIGID STEEL CONDUIT
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SHT SHEET
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
SPKR SPEAKER
SP SPARE
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
S/S STOP/START PUSHBUTTONS
STA STATION
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TEL TELEPHONE
TEL/DAT TELEPHONE/DATA
TERM TERMINAL
TL TWIST LOCK
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTC TELEPHONE TERMINAL
CABINET
TV TELEVISION
TVTC TELEVISION TERMINAL
CABINET
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UT UNDERGROUND TELEPHONE
UTIL UTILITY
UV ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VDT VIDEO DISPLAY TERMINAL
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WG WIRE GUARD
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
∠ ANGLE
@ AT
▲ DELTA
' FEET
" INCHES
# NUMBER
Ø PHASE
C CENTER LINE
P PLATE
* NOTE *
ALL GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL OTHER
DRAWINGS IN THIS SET. THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS
SHEET MAY OR MAY NOT BE USED IN THIS SET OF DRAWINGS.
1P 1 POLE (2P, 3P, 4P, ETC.)
A AMPERE
AC ABOVE COUNTER
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
AF AMP FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT
INTERRUPTER
AHU AIR HANDLING UNIT
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
AMPL AMPLIFIER
ANNUN ANNUNCIATOR
APPROX APPROXIMATELY
AQ-STAT AQUASTAT
ARCH ARCHITECT, ARCHITECTURAL
AS AMP SWITCH
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BATT BATTERY
BD BOARD
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
C CONDUIT
CAB CABINET
CAT CATALOG
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CLG CEILING
COMB COMBINATION
CMPR COMPRESSOR
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR
CONTINUOUS
CONTR CONTRACTOR
CONV CONVECTOR
CP CIRCULATING PUMP
CRT CATHODE-RAY TUBE
CT CURRENT TRANSFORMER
CTR CENTER
CU COPPER
DCP DOMESTIC WATER CIRCULATING
PUMP
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DPR DAMPER
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
ELU EMERGENCY LIGHTING UNIT
EM EMERGENCY
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EP ELECTRIC PNEUMATIC
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXH EXHAUST
EXP EXPLOSION PROOF
FA FIRE ALARM
FABP FIRE ALARM BOOSTER POWER
SUPPLY PANEL
FACP FIRE ALARM CONTROL PANEL
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FU FUSE
FUDS FUSED SAFETY DISCONNECT
SWITCH
1d
GENERAL PROJECT NOTES
1 ELECTRICAL WORK SHALL BE PERFORMED UNDER THE SUPERVISION OF A
LICENSED MASTER ELECTRICIAN. PROCURE PERMITS AND LICENSES AND PAY FEES
ASSOCIATED WITH THIS WORK.
2 PERFORM WORK TO COMPLY WITH THE STANDARD PRACTICES FOR GOOD
WORKMANSHIP PUBLISHED BY NATIONAL ELECTRICAL CONTRACTORS
ASSOCIATION (NECA) AND NFPA 70 2020 EDITION. COMPLY WITH THE LATEST
ENFORCED EDITION OF THE NATIONAL ELECTRICAL CODE (NEC), LOCAL CODES,
AMENDMENTS, AND ORDINANCES.
3 MATERIALS FURNISHED FOR THIS PROJECT SHALL BE NEW, COMMERCIAL GRADE,
FREE OF DEFECTS, AND LISTED BY A NATIONALLY RECOGNIZED TESTING
LABORATORY UNO.
4 LEAVE THE SITE CLEAN AND READY FOR OCCUPANCY. REMOVE DIRT, DEBRIS,
EMPTY CARTONS, TOOLS, CONDUIT AND WIRE SCRAPS AND MISCELLANEOUS
SPARE EQUIPMENT AND MATERIALS USED IN THIS DIVISION OF THE WORK DURING
CONSTRUCTION. COMPONENTS SHALL BE FREE OF DUST, GRIT AND FOREIGN
MATERIALS AND LEFT AS NEW BEFORE FINAL ACCEPTANCE OF WORK.
6 EACH DETAIL INCLUDED IN THIS SET OF DOCUMENTS APPLIES TO THIS PROJECT
REGARDLESS IF EACH DETAIL HAS BEEN REFERENCED ON THE PLANS OR NOT.
7 THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT BE
USED IN THIS SET OF DRAWINGS.
8 CONDUCTORS OPERATING AT 50 VOLTS OR GREATER SHALL BE IN RACEWAY.
RACEWAY WITHIN THE STRUCTURE ABOVE THE FLOOR SLAB SHALL BE METAL.
RACEWAY BELOW THE FLOOR SLAB AND UNDERGROUND RACEWAY OUTSIDE
THE STRUCTURE SHALL BE PVC.
9 LOW VOLTAGE CABLES OR CONDUCTORS OPERATING AT LESS THAN 50 VOLTS
SHALL BE IN METAL RACEWAY WHERE INSTALLED WITHIN WALLS OR INACCESSIBLE
SPACES. LOW VOLTAGE CABLES MAY BE RUN IN CABLE SUPPORT HOOKS ABOVE
ACCESSIBLE CEILINGS WHERE NOTED. LOW VOLTAGE CABLE SHALL BE PLENUM
RATED IN PLENUM SPACES.
11 CONTRACTOR SHALL BE RESPONSIBLE FOR WIRING ELECTRICAL ITEMS SHOWN.
13 PROVIDE CABLE OR CONDUIT AND WIRE AS REQUIRED TO ACHIEVE CIRCUITING
SHOWN. SIZE CONDUCTORS PER NEC AMPACITY AND WIRE FILL CRITERIA.
PROVIDE DEDICATED NEUTRAL AND GROUND CONDUCTORS FOR CIRCUITING,
UNLESS NOTED OTHERWISE. INCREASE BRANCH CIRCUIT AND/OR FEEDER
CONDUCTORS INCLUDING EQUIPMENT GROUNDING CONDUCTORS
PROPORTIONALLY FOR NO MORE THAN 3% VOLTAGE DROP ON BRANCH
CIRCUITS AND 2% ON FEEDERS PER ENERGY CODE.
15 COORDINATE LOCATIONS OF DEVICES WITH ARCHITECTURAL ELEVATIONS AND
DETAILS. ARCHITECTURAL ELEVATIONS AND DETAILS TAKE PRECEDENCE OVER
LOCATIONS SHOWN ON ELECTRICAL DRAWINGS.
16 COORDINATE WITH OTHER TRADES FOR PROPER INSTALLATION OF ELECTRICAL
COMPONENTS. CONSULT THE DRAWINGS OF OTHER TRADES OR CRAFTS TO
AVOID CONFLICTS WITH EQUIPMENT, ETC. CONFLICTS SHALL BE RESOLVED PRIOR
TO ROUGH-IN AND AT NO ADDITIONAL COST TO THE OWNER.
17 FOR EACH HVAC TEMPERATURE SENSOR, THERMOSTAT OR HUMIDISTAT, PROVIDE
A JUNCTION BOX, WITH A SINGLE GANG MUD RING, AT 48" ABOVE THE FINISH
FLOOR WITH A 3/4" CONDUIT (WITH A PULL STRING) TO ABOVE THE CEILING FOR
THE HVAC CONTROLS. HVAC CONTROLS WIRING, DEVICES AND TERMINATIONS
PROVIDED BY THE MECHANICAL CONTROLS CONTRACTOR.
19 IT IS THE RESPONSIBILITY OF THIS CONTRACTOR TO COORDINATE INSTALLATION
OF ELECTRICAL SYSTEMS AND THOSE REQUIRING ELECTRICAL CONNECTIONS TO
MAINTAIN NEC REQUIRED CLEARANCES, INCLUDED BY NOT LIMITED TO AREAS
ABOVE ACCESSIBLE CEILINGS.
20 FIELD COORDINATE FINAL MECHANICAL AND EQUIPMENT LOCATIONS ALONG
WITH CONNECTION REQUIREMENTS AND CONTROL WIRING PRIOR TO
ROUGH-IN. ADJUST CORRESPONDING CIRCUIT BREAKER RATINGS AND BRANCH
CIRCUITING ACCORDINGLY.
R E
G
IS
T E R
E
D
PROFESS IONA
L
E N G
I N
E E
R
S
O
UTH DAKO
T
A
15404
BRADEN S.
COX
REG . NO .
architecture +engineering
SEVEN
GENERATIONS
DESCRIPTIONDATEMARK
U.S. DEPARTMENT OF THE
INTERIOR BUREAU OF INDIAN
AFFAIRS
OFMC-GREAT PLAINS
115 4TH AVENUE SE SUITE 400,
MC202 ABERDEEN, SOUTH DAKOTA
57401 PHONE: 605-226-0877
FAX: 605-226-0881
ISSUE:
BIA #:
DWG:
DRAWN BY:
CHECKED BY:
SHEET
TITLE:
SHEET:
600 E. Michigan Ave., Suite B
Kalamazoo, MI 49007
P: 269.927.0144 www.7genae.com
259 E. Michigan Ave., Suite
Kalamazoo, MI 49007
P: 269.585.2255
100% BID DOCUMENTS
99% CD9/21/22
100% BID DOCUMENTS
70% PD7/21/22
BIA CONCUR:
BUREAU OF INDIAN AFFAIRS DATE
GREAT PLAINS REGION
DIVISION OF FACILITIES
100% CD11/28/22
1/26/23
100% BID1/26/23
CHEYENNE
EAGLE
BUTTE
SCHOOL
BIA
2004 E STREET,
EAGLE BUTTE, SD
57625
7GEN PROJECT NUMBER: 221101
E001
ELECTRICAL GENERAL
INFO & SYMBOL
LEGEND
RM
BSC
GENERAL ELECTRICAL REMODEL NOTES
2 PROVIDE TYPED CIRCUIT BOARD DIRECTORIES TO REFLECT AS-CONSTRUCTED
CONDITIONS. FIELD VERIFY DURING CONSTRUCTION AND REVISE
ACCORDINGLY.
3 PROVIDE NECESSARY DEMOLITION TO FACILITATE NEW CONSTRUCTION WORK
ASSOCIATED WITH THIS PROJECT. COORDINATE OUTAGES WITH OWNER
MINIMUM 72 HOURS IN ADVANCE. THE OWNER RETAINS THE FIRST RIGHT OF
REFUSAL FOR SALVAGE OF DEMOLISHED MATERIALS. PROVIDE DISPOSAL OF
REMOVED MATERIAL. MAINTAIN CIRCUIT CONTINUITY AS REQUIRED.
4 IT IS THE INTENT OF THESE DIAGRAMMATIC DRAWINGS TO PROVIDE THE PROJECT
SCOPE INCLUDING, BUT NOT LIMITED TO PHASED DEMOLITION AND NEW
CONSTRUCTION. EXISTING INFORMATION INDICATED ON THESE PLANS DOES NOT
REPRESENT ALL EXISTING CONDITIONS. THIS CONTRACTOR SHALL BECOME
FAMILIAR WITH EXISTING CONDITIONS, SCOPE OF PHASING, AND PROJECT
INTENT PRIOR TO BID SUBMISSION. NO EXTRA WILL BE ALLOWED DUE TO THE LACK
OF KNOWLEDGE OF EXISTING CONDITIONS TO COORDINATE RELOCATION OF
ELECTRICAL SYSTEMS AS REQUIRED.
5 PROVIDE CUTTING, PATCHING, AND RESTORATION OF FINISHES NECESSARY FOR
WORK SURFACES DAMAGED BY THIS WORK AND SPACES AROUND CONDUITS
PASSING THROUGH FLOORS AND WALLS SHALL BE NEATLY PATCHED AND
FINISHED TO MATCH NEW/EXISTING. STRUCTURAL MEMBERS SHALL NOT BE CUT
OR PENETRATED IN ANY MANNER. THE SPACES AROUND THE CONDUITS SHALL BE
SEALED TO PREVENT ENTRANCE OF MOISTURE. PROVIDE FIRE STOPPING PER UL
APPROVED METHODS.
6 REMOVE ABANDONED WIRING COMPLETE. AT CONTRACTORS OPTION, UTILIZE
EXISTING ABANDONED RACEWAY TO EXTENT AVAILABLE. ABANDONED
RACEWAY SHALL BE REMOVED.
7 COORDINATE WORK IN PHASES WITH GENERAL CONTRACTOR AND OWNER TO
FACILITATE DEMOLITION AND NEW CONSTRUCTION.
ELECTRICAL SHEET LIST
SHEET DESCRIPTION
E001 ELECTRICAL GENERAL INFO & SYMBOL LEGEND
E201 FIRST FLOOR POWER PLAN
E203A AREA B FIRST FLOOR ENLARGED POWER PLAN
E203B AREA B SECOND FLOOR POWER PLAN
E205 AREA D ENLARGED POWER PLAN
E206 AREA E ENLARGED POWER PLAN
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD FD FD
FD FD
FD
FD FD FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FDFD
FD
FD
FD
FD
FD
FD
FD
AREA A
AREA B
AREA A
AREA B
A R
EA
A
A R
EA
C
AR
EA
A
AR
EA
C
AREA B
AREA D
A R
EA
B
A R
EA
C
AREA C
AREA D
AREA D
AREA E
AREA D
AREA E
H W S
H W S
H W R
HWS
HWS
HWS
HWS
HWR
DH
DH
T
T
T
T
T T T
T
T
TTTT
TT
T T T
T
T
T
T
T
T
T T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
TT
T T T T T T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
C N
2"
2"
2 1/2"
3/4"
T
U P
DN
D N
U P
DN D
N
D N
DN
D N
DN
UP
UP
UP
UP
UP
UP
UP
DN
D N
D N
D N
D N
D N
5 1
H-1
H -71
H -63
H -5
H -3
H -3
K-9
K -5
K -1
K-20
K -1
178A
H -9
109B
H -6
H -63B a
K-26
H -8
H -8
B
D
C
B
149A
B
H-18
142C
155A
152F
152E
A
A
B
A28
A
A
A
A
H-79
H-71
H-38
H-39
H-35
H-33
H-34
H-41
H-32
H-30
H-27
H-31
H-26
H-23 H-25
H-24
H-18
H-19H-20H-16H-12
H-8
H-11
H-9
H-8
H-6
H-3
XX
H-2
H-116
H-54
H-64
H-66
H-68
H-69
H-70
H-67
H-92
H-93
H-91
H-88
H-81
H-90
H-89
H-80
H-82
H-81
H-74
H-75
H-82
H-87
H-94
H-96
H-95
H-86
H-84
H-88
H-76
H-48
H-43
H-49
H-42
H-58
H-62 H-59
H-60
H-61
H-57
H-44
H-46
H-47
H-50 H-65
H-115
H-100
H-116
H-116 H-101
H-106
H-107
H-110
H-115
H-114
H-105
H-104
H-111
H-105
H-97
H-9
H-56
H-14
118A 118B
H124
119A
119B
120B
120A
121A
121B
116115112
112B 112C 112D
111A
109A
109C
109D
109E
109B
108 107 106
105 104
122123
122A
132 136
133 134
137 138
140 141 142
142B
145146147148149
149A
149B
149C
A28
A33
A34
A37
152B152A
150G
152D
152E
152F
153A
153B
154A
155B
155A
154B
171173174175176177
170170169168
129B
K-9
K-1
K-10
K-17
K-11
K-16
K-15
K-14
K-12
K-13
K-8
K-2
K-3
K-7
K-5
K-6
K-4
K-19
K-31
K-30
K-29
K-25
K-26
K-27
K-28
K-20
K-22
K-23
K-24
H-37
A28B
A33B
K-18
K-20 K-21
H-15
H-63
H-1
H-63B
142C
A34B
A37B
A54 A52
A26
140A 142A
T
T
T
T
T
T T
T
T
T
T
T
T T
T T
T
E203A
E205
E206
HATCHED AREAS ARE AREAS OUT OF SCOPE
HATCHED AREAS ARE AREAS OUT OF SCOPE
HATCHED AREAS ARE AREAS OUT OF SCOPE
GENERAL POWER NOTES
1 WHERE CONNECTED TO A 20 AMP BRANCH CIRCUIT SUPPLYING
AN INDIVIDUAL (SIMPLEX OR DUPLEX), THE RECEPTACLE SHALL
BE RATED AT 20 AMPS.
3 REFER TO SECTION 26 0519 FOR MINIMUM CONDUCTOR SIZE
ADJUSTMENTS FOR VOLTAGE DROP.
5 WIRE COUNTS FOR CIRCUIT CONDUCTORS ARE NOT SHOWN.
PROVIDE PROPER NUMBER OF CONDUCTORS TO ACHIEVE
CIRCUIT AND SWITCHING CONNECTIONS SHOWN.
8 CIRCUIT WIRING IS NOT SHOWN EXCEPT FOR SWITCHING INTENT
OF FIXTURES AND CONTROL OF DEVICES.
9 PROVIDE PROPER NUMBER OF CONDUCTORS TO ACHIEVE
CIRCUITING AND SWITCHING SHOWN.
10 CIRCUIT NUMBERS AT DEVICES CORRESPOND TO PANELBOARD
BREAKERS (SEE PANELBOARD SCHEDULE). BRANCH CIRCUITS
SHALL BE SIZED ACCORDING TO THE CIRCUIT BREAKER RATING,
UNLESS INDICATED OTHERWISE ON THE ELECTRICAL EQUIPMENT
SCHEDULE.
11 SINGLE PHASE BRANCH CIRCUITS SHALL NOT SHARE NEUTRALS.
14 PROVIDE THE REQUIRED POWER FOR ALL MECHANICAL
EQUIPMENT SPECIFIED IN THE CONTRACT DOCUMENTS, EVEN IF
NOT SHOWN ON THE POWER PLANS.
15 THE CONTRACTOR SHALL FIELD VERIFY THE POWER
REQUIREMENTS OF ALL MECHANICAL EQUIPMENT, WITH THE
EQUIPMENT SUPPLIERS, PRIOR TO PREPARING SUBMITTALS OR
ORDERING ANY SWITCHGEAR OR EQUIPMENT. SUPPLIED
MECHANICAL EQUIPMENT MAY VARY FROM EQUIPMENT
SPECIFIED IN THE PLANS.
R E
G
IS
T E R
E
D
PROFESS IONA
L
E N G
I N
E E
R
S
O
UTH DAKO
T
A
15404
BRADEN S.
COX
REG . NO .
architecture +engineering
SEVEN
GENERATIONS
DESCRIPTIONDATEMARK
U.S. DEPARTMENT OF THE
INTERIOR BUREAU OF INDIAN
AFFAIRS
OFMC-GREAT PLAINS
115 4TH AVENUE SE SUITE 400,
MC202 ABERDEEN, SOUTH DAKOTA
57401 PHONE: 605-226-0877
FAX: 605-226-0881
ISSUE:
BIA #:
DWG:
DRAWN BY:
CHECKED BY:
SHEET
TITLE:
SHEET:
600 E. Michigan Ave., Suite B
Kalamazoo, MI 49007
P: 269.927.0144 www.7genae.com
259 E. Michigan Ave., Suite
Kalamazoo, MI 49007
P: 269.585.2255
100% BID DOCUMENTS
99% CD9/21/22
100% BID DOCUMENTS
70% PD7/21/22
BIA CONCUR:
BUREAU OF INDIAN AFFAIRS DATE
GREAT PLAINS REGION
DIVISION OF FACILITIES
100% CD11/28/22
1/26/23
100% BID1/26/23
CHEYENNE
EAGLE
BUTTE
SCHOOL
BIA
2004 E STREET,
EAGLE BUTTE, SD
57625
7GEN PROJECT NUMBER: 221101
E201
FIRST FLOOR POWER
PLAN
RM
BSC
NORTH
SCALE: 1" = 30'-0"
FIRST FLOOR POWER PLAN
AREA B AREA B
AREA B
AR
E A B
TT
T T T
T
T
T
T
T
T
T T
T
T
T
T
T
T
T
T
T
T
T
D N
DN
D N
DN
UP
UP
UP
UP
UP
UP
UP
DN
H-1
109B
B
D
C
B
H-8
118A 118B
H124
119A
119B
120B
120A
121A
121B
116115112
112B 112C 112D
111A
109A
109C
109D
109E
109B
108 107 106
105 104
122123
122A
H-1
T
T
T
T
T
1 2
R E
G
IS
T E R
E
D
PROFESS IONA
L
E N G
I N
E E
R
S
O
UTH DAKO
T
A
15404
BRADEN S.
COX
REG . NO .
architecture +engineering
SEVEN
GENERATIONS
DESCRIPTIONDATEMARK
U.S. DEPARTMENT OF THE
INTERIOR BUREAU OF INDIAN
AFFAIRS
OFMC-GREAT PLAINS
115 4TH AVENUE SE SUITE 400,
MC202 ABERDEEN, SOUTH DAKOTA
57401 PHONE: 605-226-0877
FAX: 605-226-0881
ISSUE:
BIA #:
DWG:
DRAWN BY:
CHECKED BY:
SHEET
TITLE:
SHEET:
600 E. Michigan Ave., Suite B
Kalamazoo, MI 49007
P: 269.927.0144 www.7genae.com
259 E. Michigan Ave., Suite
Kalamazoo, MI 49007
P: 269.585.2255
100% BID DOCUMENTS
99% CD9/21/22
100% BID DOCUMENTS
70% PD7/21/22
BIA CONCUR:
BUREAU OF INDIAN AFFAIRS DATE
GREAT PLAINS REGION
DIVISION OF FACILITIES
100% CD11/28/22
1/26/23
100% BID1/26/23
CHEYENNE
EAGLE
BUTTE
SCHOOL
BIA
2004 E STREET,
EAGLE BUTTE, SD
57625
7GEN PROJECT NUMBER: 221101
E203A
AREA B FIRST FLOOR
ENLARGED POWER
PLAN
RM
BSC
NORTH
SCALE: 1" = 10'-0"
FIRST FLOOR POWER PLAN - AREA…